FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS CONDENSATE 1

CD-72 FE 147552 173441 Inspect piping downstream of flow element CD-72-FE. Inspect 2 pipe diameters.

TB ELEV. 21 FT off BFP-21 suction.

Y Y

N Y

SK-83 24" CHECWORKS - Ranked high on the Service Life Report 2

CD-75N 147554 173444 Nozzle. Insoect nozzle TB ELEV. 21 FT off BFP-22 suction.

Y Y

N Y

SK-84 24" CHECWORKS - Ranked high on the Service Life Report 3

CD-37N 147556 173447 FWH 24A TB ELEV. 42 FT off FWH 24A.

Y Y

N Y

SK-81 14" CHECWORKS - Ranked high on the Service Life Report 4

CD-VALVE-CD-18 (CD-31P-1 D/S) 147559 173456 5

CD-34N 147560 173457 Nozzle. Insoect nozzle TB ELEV. 32 FT off FWH 25B.

Y Y

N Y

SK-82 14" CHECWORKS - Ranked high on the Service Life Report 6

CD-21N 147562 173461 Nozzle. Insoect nozzle TB ELEV. 41 FT off FWH 24B.

Y Y

N Y

SK-81 14" RE-INSPECTION (TRENDING) 7 CD-108N 167217 198370 Inspect Nozzle on 22B FWH.

TB ELEV. 39'-6" off FWH 22B.

Y Y

N Y

SK-80A 14" CHECWORKS - Ranked high on the Service Life Report 8

CD-37 147597 173752 Inspect elbow plus upstream & downstream extension. Elbow plus 6 inches on either side of the elbow weld.

TB ELEV. 41 FT off FWH 24A.

Y Y

N Y

SK-81 14" RE-INSPECTION (TRENDING) 9 CD-58P 147598 173751 Inspect piping. Inspect 2 pipe diameters = 28 INCHES.

TB ELEV. 32 FT off FWH 25C.

Y Y

N Y

SK-82 14" RE-INSPECTION (TRENDING) 10 CD-65P 147600 173750 Inspect piping upstream of valve FE-72. Inspect 2 pipe diameters.

TB ELEV. 21 FT off BFP-21 suction.Upstream of flow element FE-72 Y

Y N

Y SK-83 24" RE-INSPECTION (TRENDING) 11 CD-75 147602 173749 12 CD-9 147603 173747 Inspect elbow plus upstream & downstream extension. Elbow plus 10 inches on either side of the elbow welds.

TB. Elev. 24ft. 6" Y

Y N

Y SK-83 24" RE-INSPECTION (TRENDING) 13 CD-31 147604 173746 Inspect elbow plus upstream & downstream extension. Elbow plus 6 inches on either side of the elbow weld.

TB ELEV. 45 FT off FWH 25A.

Y Y

N Y

SK-82 14" RE-INSPECTION (TRENDING)

CONDENSATE DESCOPED DESCOPED 1 of 11 2R19 FAC Scope (Ipe0067423).Xls ENT000057 Submitted: March 28, 2012

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 14 3EXB-1 147606 173745 Inspect elbow plus upstream & downstream extension. Elbow plus 6 inches on either side of the elbow weld.

TB Elev. 42ft-2' off FWH 23B Y

Y N

Y SK-2 20" RE-INSPECTION (TRENDING) 15 3EXB-1A 147607 173753 Inspect piping Downstream of valve elbow 3EXB-1. Inspect 2 pipe diameters = 40 inches. TB Elev. 42ft-2' off FWH 23B Y

Y N

Y SK-2 20" RE-INSPECTION (TRENDING) 16 3EXB-9 147608 173754 Inspect elbow plus upstream & downstream extension. Elbow plus 12 inches on either side of the elbow weld.

TB Elev. 39ft-6' downstream of Valve-3EXB-VALVE - 3EX-4 Y

Y N

Y SK-2 28" RE-INSPECTION (TRENDING) 17 3EXB-14N 167219 198367 Inspect turbine extraxtion nozzle Inside Condenser 22 off #22LP turbine Y

Y Y

Y SK-2 28" CHECWORKS - Ranked high on the Service Life Report 18 3EXC-10 147609 173755 Inspect elbow plus upstream & downstream extension. Elbow plus 12 inches on either side of the elbow weld.

TB Elev. 39ft-6' downstream of Valve 3EXC-VALVE -PCV-1161 Y

Y N

Y SK-3 28" RE-INSPECTION (TRENDING) 19 3EXC-8 147613 173758 Inspect elbow plus upstream & downstream extension. Elbow plus 12 inches on either side of the elbow weld.

TB ELEV. 32 FT downstream of Valve 3EXC-VALVE -PCV-1161.

Y Y

N Y

SK-3 28" RE-INSPECTION (TRENDING) 20 3EXC-9 147617 173759 21 4EXA-8A 147621 173776 22 4EX-D1 167242 198366 Inspect 45 degrees (back to back) elbows 4EX-D1 & 4EX-D1-1. Also Inspect 2 inches on either side of the elbow welds.

TB Elev. 42ft-2 upstream of #23A FWH Y

Y N

Y SK-21A 6"

CHECWORKS - Ranked high on the Service Life Report 23 4EX-D1-1 167242 198366 Inspect 45 degrees (back to back) elbows 4EX-D1 & 4EX-D1-1. Also Inspect 2 inches on either side of the elbow welds.

TB Elev. 42ft-2 upstream of #23A FWH Y

Y N

Y SK-21A 6"

CHECWORKS - Ranked high on the Service Life Report 24 4EX-D5 167243 198363 Inspect 4x3 reducer.

TB ELEV. 38' 3" Upstream of # 23 FWH in vecinity of LCV-1115 Y

Y N

Y SK-21A 6"

CHECWORKS - Ranked high on the Service Life Report/ Re-inspection 25 4EX-D71 167244 198364 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB ELEV. 33' 4". Downstream of #24C FWH Y

Y N

Y SK-23A 6"

RE-INSPECTION (TRENDING).

26 5EX-29 147629 173488 Inspect elbow plus piping upstream and downstream ~ 4ft total.

TB ELEV. 26 ft 6". Downstream of Heater Drain Pump 22 towards HTR DRN TK.

Y Y

N Y

SK-19 2"

RE-INSPECTION (TRENDING) 27 3EXA-14N 147633 173767 28 3EXD-51 167241 198365 Inspect TEE & Branch plus upstream &

downstream extension. Inspect 4 inches oneither side of welds.

TB Elev. 25ft- 0' In vecinity of Valve-LCV-1120A.

Y Y

N Y

SK-26B 8"

RE-INSPECTION (TRENDING).

29 BFD-5 147635 173764 Inspect elbow plus upstream & downstream extension. Elbow plus 10 inches on either side of the elbow weld.

TB. Elev. 24ft. 5". Down stream of valve BFD-2-21 discharge of BFP No.

21.

Y Y

N Y

SK-71 20" CHECWORKS - Ranked high on the Service Life Report EXTRACTION FEEDWATER DESCOPED DESCOPED DESCOPED 2 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 30 BFD-7 147636 173763 Inspect elbow plus upstream

& downstream extension.

TB. Elev. 32ft. 0". Down stream of valve BFD-2-21 discharge of BFP No.

21.

Y Y

N Y

SK-71 20" CHECWORKS - Ranked high on the Service Life Report 31 BFD-14 147637 173491 Inspect elbow plus upstream & downstream extension. Elbow plus 8 inches on either side of the elbow weld.

TB. Elev. 24ft. 5". Down stream of valve BFD-2-21 discharge of BFP No.

21.

Y Y

N Y

SK-71 20" CHECWORKS - Ranked high on the Service Life Report 32 BFD-17 147638 173760 Inspect elbow plus upstream & downstream extension. Elbow plus 8 inches on either side of the elbow weld.

TB. Elev. 24ft. 5". Down stream of valve BFD-2-22 discharge of BFP No.

22.

Y Y

N Y

SK-72 20" CHECWORKS - Ranked high on the Service Life Report 33 BFD-18 147639 173761 34 BFD-22 147640 173762 Inspect elbow plus upstream & downstream extension. Elbow plus 10 inches on either side of the elbow weld.

TB. Elev. 32ft.- 5". Down stream of valve BFD-2-22 discharge of BFP No.

22.

Y Y

N Y

SK-72 20" CHECWORKS - Ranked high on the Service Life Report 35 BFD-27 147642 173784 36 BFD-27P 147644 173794 37 BFD-28 147645 173795 Inspect elbow plus upstream extension. Elbow plus 12 inches upstream of the elbow weld.

TB. Elev. 31ft.- 0". BFP discharge header.

Y Y

N Y

SK-73 30 "

CHECWORKS - Ranked high on the Service Life Report 38 BFD-28P 147647 173798 Inspect piping. Inspect 2 pipe diameters = 60 INCHES.

TB. Elev. 31ft.- 0". BFP discharge header.

Y Y

N Y

SK-73 30 "

CHECWORKS - Ranked high on the Service Life Report 39 BFD-49 147650 173802 40 BFD-41 147652 173803 41 BFD-VALVE-BFD-3-2 (BFD-34P-1) 147653 173805 Inspect piping. Inspect 2 pipe diameters = 60 INCHES.

TB. Elev. 34ft - 9". Off FWH 26A; D/S of Valve BFD-3-2 Y

Y N

Y SK-73 18" CHECWORKS - Ranked high on the Service Life Report DESCOPED DESCOPED DESCOPED DESCOPED DESCOPED 3 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 42 BFD-35 147655 173792 Inspect ELBOW, PIPE & ELBOW. Including 10 inches Upstream and downstream of elbow welds.

TB. Elev. 34ft - 9". Off FWH 26A; D/S of Valve BFD-3-2 Y

Y N

Y SK-73 18" CHECWORKS - Ranked high on the Service Life Report 43 BFD-35P 147656 173791 Inspect piping. Inspect 2 pipe diameters = 36 INCHES.

TB. Elev. 34ft - 9". Off FWH 26A; D/S of Valve BFD-3-2 Y

Y N

Y SK-73 18" CHECWORKS - Ranked high on the Service Life Report 44 BFD-36 147657 173790 Inspect ELBOW, PIPE & ELBOW. Including 8 inches Upstream and downstream of elbow welds.

TB. Elev. 34ft - 9". Off FWH 26A; D/S of Valve BFD-3-2 Y

Y N

Y SK-73 18" CHECWORKS - Ranked high on the Service Life Report 45 BFD-36N 147659 173789 Inspect nozzle TB. Elev. 42ft - 9". Off FWH 26A.

Y Y

N Y

SK-73 18" CHECWORKS - Ranked high on the Service Life Report 46 BFD-53 147661 173788 Inspect Elbow and Pipe plus 8 inches upstream of elbow TB. Elev. 39ft - 9". Off FWH 26B.

Y Y

N Y

SK-74 18" CHECWORKS - Ranked high on the Service Life Report 47 BFD-53P 147663 173793 Inspect Elbow and Pipe plus 8 inches upstream of elbow weld. For pipe 2diameters = 36inches.

TB. Elev. 39ft - 9". Off FWH 26B.

Y Y

N Y

SK-74 18" CHECWORKS - Ranked high on the Service Life Report 48 BFD-55N 147665 173796 Inspect nozzle TB. Elev. 42ft - 9". Off FWH 26A.

Y Y

N Y

SK-74 18" CHECWORKS - Ranked high on the Service Life Report 49 BFD-58 147671 173807 Inspect ELBOW, PIPE & ELBOW. Including 8 inches Upstream and downstream of elbow welds. For pipe 2diameters = 36inches.

TB. Elev. 23ft - 6". Off FWH 26A.

Y Y

N Y

SK-74 18" CHECWORKS - Ranked high on the Service Life Report 50 BFD-58P 147667 173797 Inspect ELBOW, PIPE & ELBOW. Including 8 inches Upstream and downstream of elbow welds. For pipe 2diameters = 36inches.

TB. Elev. 23ft - 6". Off FWH 26A.

Y Y

N Y

SK-74 18" CHECWORKS - Ranked high on the Service Life Report 51 BFD-59 147673 173810 Inspect ELBOW, PIPE & ELBOW. Including 8 inches Upstream and downstream of elbow welds. For pipe 2diameters = 36inches.

TB. Elev. 23ft - 6". Off FWH 26A.

Y Y

N Y

SK-74 18" CHECWORKS - Ranked high on the Service Life Report 52 BFD-VALVE-BFD-4-2 (BFD-48P-1) 147675 173811 53 BFD-50 147677 173812 54 BFD-50P-1 147678 173813 Inspect piping. Inspect 2 pipe diameters = 60 INCHES.

TB. Elev. 23ft - 6".

Y Y

N Y

SK-74 30" CHECWORKS - Ranked high on the Service Life Report 55 BFD-62 147688 173891 56 BFD-62P US 147688 173891 57 BFD-63P DS 147689 173892 Inspect piping 2 diameters = 60 inches TB. Elev. 29ft -9".

Y Y

N Y

SK-74 30" CHECWORKS - Ranked high on the Service Life Report DESCOPED DESCOPED DESCOPED DESCOPED 4 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 58 BFD-65 147690 173893 Inspect ELBOW & PIPE. Including 8 inches Upstream elbow welds &. For pipe 2diameters

= 60inches.

TB. Elev. 43ft -0".

Y Y

N Y

SK-74 30" CHECWORKS - Ranked high on the Service Life Report 59 BFD-65P-1 147690 173893 Inspect ELBOW & PIPE. Including 8 inches Upstream elbow welds &. For pipe 2diameters

= 60inches.

TB. Elev. 43ft -0".

Y Y

N Y

SK-74 30" CHECWORKS - Ranked high on the Service Life Report 60 BFD-101 61 BFD-21 147691 173894 Inspect elbow plus upstream & downstream extension. Elbow plus 8 inches on either side of the elbow weld.

TB. Elev. 24ft-6". D/S of BFD-2-22 Y

Y N

Y sk-72 20" RE-INSPECTION (TRENDING) 62 BFD-33 147693 173895 Inspect elbow plus upstream & downstream extension. Elbow plus 8 inches on either side of the elbow weld.

TB. Elev. 29ft -9".

Y Y

N Y

SK-73 18" RE-INSPECTION (TRENDING) 63 BFD-38 147694 173902 Inspect elbow plus upstream & downstream extension. Elbow plus 8 inches on either side of the elbow weld.

TB. Elev. 28ft -0".

Y Y

N Y

SK-73 18" RE-INSPECTION (TRENDING) 64 BFD-55 147695 173903 Inspect elbow plus upstream & downstream extension. Elbow plus 8 inches on either side of the elbow weld.

TB. Elev. 45ft -0". Off FWH 26A Y

Y N

Y SK-74 18" RE-INSPECTION (TRENDING) 65 BFD-71R 147696 173904 66 BFD-83R 147698 173905 Inspect reducer.

TB. Elev. 22ft-3" D/S OF FCV-447 Y

Y N

Y SK-77 18" RE-INSPECTION (TRENDING) 67 BFD-88 147699 173906 Inspect elbow plus upstream & downstream extension. Elbow plus 8 inches on either side of the elbow weld.

TB. Elev. 35ft-0" D/S OF FCV-437 Y

Y N

Y SK-78 18" RE-INSPECTION (TRENDING) 68 BFD-99 147707 173907 69 3EXD-18 147709 173908 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 4 INCHES ON ALL SIDES OF TEE welds.

TB. Elev. 17ft-10". D/S OF LCV-1118A Y

Y N

Y SK-24B 8"

RE-INSPECTION (TRENDING) 70 3EXD-29 147710 173931 Inspect elbow plus upstream & downstream extension. Elbow plus 4 inches on either side of the elbow weld.

TB. Elev. 30ft-3" OFF 23B FWH Y

Y N

Y SK-25A 8"

RE-INSPECTION (TRENDING) 71 3EXD-3 147712 173933 Inspect elbow plus upstream & downstream extension. Elbow plus 4 inches on either side of the elbow weld.

TB. Elev. 32ft-0" OFF 23A FWH Y

Y N

Y SK-24A 8"

RE-INSPECTION (TRENDING) 72 3EXD-51 147716 173935 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 4 INCHES ON ALL SIDES OF TEE welds.

TB. Elev. 24ft-6". U/S OF LCV-1120A Y

Y N

Y SK-26B 8"

RE-INSPECTION (TRENDING)

HEATER DRAINS DESCOPED DESCOPED DESCOPED 5 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 73 4EXD-1P 147718 173936 Inspect piping 2 diameters = 12 inches TB. Elev. 42t-2". Downstream of LCV-1115 Y

Y N

Y SK-21A 6"

CHECWORKS - Ranked high on the Service Life Report 74 4EXD-4 147721 173938 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 4 INCHES ON ALL SIDES OF TEE welds.

TB. Elev. 38ft-3". Adjacent to LCV-1115 Y

Y N

Y SK-21A 6"x4" RE-INSPECTION (TRENDING) 75 4EXD-40 147724 173939 Inspect ELBOW & PIPE. Including 2 inches Upstream elbow welds &. For pipe 2diameters

= 12inches.

TB. Elev. 38ft-3". Upstream OF LCV-1116 Y

Y N

Y SK-22A 6"

RE-INSPECTION (TRENDING) 76 4EXD-40P DS 147724 173939 Inspect ELBOW & PIPE. Including 2 inches Upstream elbow welds &. For pipe 2diameters

= 12inches.

TB. Elev. 38ft-3". Upstream OF LCV-1116 Y

Y N

Y SK-22A 6"

RE-INSPECTION (TRENDING) 77 4EXD-57 147726 173941 Inspect reducer.

TB. Elev. 17ft-0". Adjacent to LCV-1116A Y

Y N

Y sk-22B 6"x3" RE-INSPECTION (TRENDING) 78 4EXD-6 147727 173942 Inspect reducer.

TB. Elev. 38ft-3". Adjacent to LCV-1115 Y

Y N

Y SK-21A 4"x3" RE-INSPECTION (TRENDING) 79 4EXD-70P 147729 173944 Inspect piping 2 diameters = 12 inches TB. Elev. 33ft-4" OFF 24C FWH Y

Y N

Y SK-23A 6"

RE-INSPECTION (TRENDING) 80 5EXV-11 147732 173947 Inspect elbow plus upstream & downstream extension. Elbow plus 4 inches on either side of the elbow weld.

TB. Elev. 30ft-3" OFF 25A FWH Y

Y N

Y SK-15 10 RE-INSPECTION (TRENDING) 81 HD-10P 147734 173946 Inspect piping 2 diameters = 16 inches TB. Elev. 13ft-7". Adjacent to HTR DRN PUMP 22 Y

Y N

Y SK-20 8"

RE-INSPECTION (TRENDING) 82 HD-5 147735 173949 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 8 INCHES ON ALL SIDES OF TEE welds.

TB. Elev. 32ft-0" Downstream of LCV 1127 Y

Y N

Y SK-20 16"x12" RE-INSPECTION (TRENDING) 83 MS-1A67P US 147742 173962 Inspect piping 2 diameters = 12 inches TB. Elev 38ft- 0". OFF FWH 26C Y

Y N

Y SK-45C 6"

RE-INSPECTION (TRENDING) 84 MS-1B35 147745 173963 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld TB. Elev. 35 ft -5". Downstream OF LCV-1105 Y

Y N

Y SK-48B 6"

RE-INSPECTION (TRENDING) 85 MS-2A13 147747 173964 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. Elev 49ft-4". OFF Reheater 22A drain Y

Y N

Y SK-46A 6"

RE-INSPECTION (TRENDING)

RE-HEATER DRAINS 6 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 86 MS-2A14 167247 198361 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. Elev 49ft-4". OFF Reheater 22A drain Y

Y N

Y SK-46A 6"

RE-INSPECTION (TRENDING) 87 MS-2B11 147748 173965 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. Elev 49ft-1". OFF Reheater 22B Y

Y N

Y SK-49A 6"

RE-INSPECTION (TRENDING) 88 MS-2B13P 147750 173951 Inspect piping 2 diameters = 12 inches TB. Elev 49ft-1". OFF Reheater 22B Y

Y N

Y SK-49A 6"

RE-INSPECTION (TRENDING) 89 MS-2B17 147751 173950 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. Elev 47ft-10". OFF Reheater 22B Y

Y N

Y SK-49A 6"

RE-INSPECTION (TRENDING) 90 MS-2B22 147752 173954 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. Elev 40ft- 0". OFF Reheater 22B Y

Y N

Y SK-49A 10" RE-INSPECTION (TRENDING) 91 MS-2B30R1 147753 173966 Inspect (10x4) reducer.

TB. Elev. 38 ft -9". Upstream OF LCV-1105A Y

Y N

Y SK-49B 10"x4" RE-INSPECTION (TRENDING) 92 MS-2B42 147756 173968 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 2 INCHES ON ALL SIDES OF TEE welds.

TB. Elev 39ft-3". OFF FWH 26A Y

Y N

Y SK-49C 6"

RE-INSPECTION (TRENDING) 93 MS-2B52 147757 173969 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. Elev. 32ft-9" OFF 26C FWH Y

Y N

Y SK-49C 6"

RE-INSPECTION (TRENDING) 94 MS-3B13P 147758 173970 Inspect piping 2 diameters = 12 inches TB. Elev 49ft-8". OFF Reheater 23B drain tank Y

Y N

Y SK-50A 6"

RE-INSPECTION (TRENDING) 7 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 95 MS-2B30 R2 167249 198362 Inspect (10x4) reducer.

TB. Elev. 38 ft -9". Downstream OF LCV-1105A Y

Y N

Y SK-49B 10"x4" Snapshot Assessment 96 MS-3B26 147761 173972 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. Elev 37ft-9". OFF Reheater 23B drain tank Y

Y N

Y SK-50A 6"

RE-INSPECTION (TRENDING) 97 MST43-PIPE US 147763 173974 Inspect piping upstream and down stream of mst 43 Tb elev 36' 0" Y

Y N

Y 9321-F-20423/

9321-F-2131 1"& 3/4' RE-INSPECTION (TRENDING) 98 1A-18 (TEE) 147765 173975 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 2 INCHES ON ALL SIDES OF TEE welds.

TB. Elev 53ft-9". OFF MS-21A Y

Y N

Y SK-27 12" RE-INSPECTION (TRENDING) 99 1A-20P 147767 174052 Inspect piping 2 diameters = 24 inches.

Component d/s of valve 5ex-19L TB. Elev 53ft-9". OFF MS-21A Y

Y N

Y SK-27 12" CHECWORKS 100 1A-20P-1 147769 174053 Inspect piping 2 diameters = 24 inches.

Component d/s of valve 5ex-19M TB. Elev 53ft-1". OFF MS-21A Y

Y N

Y SK-27 12" CHECWORKS 101 1A-20N 147773 174054 Nozzle and Tank Component d/s of valve 5ex-19M reference CR-HQN-2007-00915-CA-16 TB. Elev 53ft-1". OFF MSDT-21A Y

Y N

Y SK-27 12" Operating Experience /CHECWORKS 102 2A-20P1 147777 174057 Inspect piping 2 diameters = 24 inches.

Component d/s of valve 5ex-19K TB. Elev 53ft-1". OFF MS-22A Y

Y N

Y SK-27 12" CHECWORKS 103 2A-20P 147775 174056 Inspect piping 2 diameters = 24 inches.

Component d/s of valve 5ex-19J TB. Elev 53ft-1". OFF MS-22A Y

Y N

Y SK-27 12" CHECWORKS 104 2A-20N 147774 174055 Nozzle and Tank Component d/s of valve 5ex-19K reference CR-HQN-2007-00915-CA-16 TB. Elev 53ft-1". OFF MSDT-22A Y

Y N

Y SK-27 12" Operating Experience /CHECWORKS 105 2B-1 147780 173500 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 4 INCHES ON ALL SIDES OF TEE welds.

TB. Elev 45ft-10". OFF MSDT-22B Y

Y N

Y SK-37A 8"X6" RE-INSPECTION (TRENDING) 106 2B-3 147782 173501 Reducing elbow. Inspect elbow plus upstream

& downstream extension. Elbow plus 4 inches on either side of the elbow weld.

TB. Elev 43ft-6". OFF MSDT-22B Y

Y N

Y SK-37A 8"X6" RE-INSPECTION (TRENDING) 107 208-6P 147784 174058 Inspect piping 2 diameters = 24 inches.

TB. ELEV 10ft- 0. Downstream of LCV-1126 @ COND. 21 Y

Y N

Y SK-208 12" RE-INSPECTION (TRENDING) 108 212-1P US 147786 174059 Inspect piping 2 diameters = 12 inches TB. ELEV 10ft- 0. Downstream of LCV-1139 @ COND. 23 Y

Y N

Y SK-212 6"

RE-INSPECTION (TRENDING) 109 219-13P 147787 174060 Inspect piping 2 diameters = 24 inches.

TB. ELEV 36 ft- 0. Downstream of FCV-1208 @ COND. 22 Y

Y N

Y SK-219 12" RE-INSPECTION (TRENDING)

MSR DRAINS MAIN STEAM 8 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 110 235-5P US 147788 173922 Inspect piping 2 diameters = 6 inches TB. ELEV ft- 0. Upstream of COND.

23 PEN.

Y Y

N Y

SK-235 3"

RE-INSPECTION (TRENDING) 111 248-16P US 147789 173921 Inspect piping 2 diameters = 6 inches TB. ELEV. 15ft-0". @ BFP TURBINE Y

Y N

Y SK-248 3"

RE-INSPECTION (TRENDING) 112 254-9E 147796 173917 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. ELEV 53 ft- 0. Downstream of MS-1207(Stop valve) west side.

Y Y

N Y

SK-254 4"

RE-INSPECTION (TRENDING) 113 270-3E 147797 173916 Inspect elbow plus piping upstream and downstream ~ 4ft.

TB.

Y Y

N Y

SK-270 1"

RE-INSPECTION (TRENDING) 114 283-20R 147794 173918 Inspect reducer.

TB. ELEV. 15ft-0" AUX. STEAM TO UNIT COOLERS.

Y Y

N Y

SK-283 6" X 4" RE-INSPECTION (TRENDING) 115 283-8R 147795 173487 Inspect reducer.

TB. ELEV. 15ft-0" AUX. STEAM TO UNIT COOLERS.

Y Y

N Y

SK-283 6" X 4" RE-INSPECTION (TRENDING) 9 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 116 FWH 21A 132254 155698 Inspect FWH 21A shell 2 pipe dia. From center line of inlet nozzle radially and axially.

IINSIDE CONDENSER 23 Y

Y N

Y Shell OPERATING EXPERIENCE 117 FWH 21B 132255 155699 Inspect FWH 21B shell 2 pipe dia. From center line of nozzle radially and axially.

IINSIDE CONDENSER 22 Y

Y N

Y Shell OPERATING EXPERIENCE 118 FWH 22B 132327 155705 Inspect FWH 22B shell 2 pipe dia. From center line of nozzle radially and axially.

INSIDE CONDENSER 22 Y

Y N

Y Shell OPERATING EXPERIENCE 119 FWH 22A 148045 173900 Inspect FWH 22A shell 2 pipe dia. From center line of nozzle radially and axially.

INSIDE CONDENSER 23 Y

Y N

Y Shell OPERATING EXPERIENCE 120 EST-24 147800 173914 Inspect elbow plus upstream & downstream extension. Elbow plus 2 inches on either side of the elbow weld.

TB. ELEV. 25ft-8" off DRAIN COLLECTING TANK SK-91 4"

RE-INSPECTION (TRENDING) 121 EST-31P US 147802 173896 Inspect piping 2 diameters = 8 inches TB. ELEV. 25ft-8" off DRAIN COLLECTING TANK SK-91 4"

RE-INSPECTION (TRENDING) 122 Valve LCV-1110 147803 173897 Inspect PIPE & REDUCER d/s of LCV-1110; 23A MSR DRAIN TO DCT TB ELEV 22ft-3" D/S OF LCV-11110 Near DCT Y

Y N

Y SK-35B 6" & 6X4R Plant Specific OPERATING EXPERIENCE 123 Valve FCV-1115 147806 173899 Inspect piping & fitting d/s of FCV-1115; 21 MBDP RECIRC. to DCT TB. Elev. 22ft-8" d/s of FCV-1115 Y

Y N

Y SK-35 6 "

Plant Specific OPERATING EXPERIENCE 124 Valve-LCV-1127D 147805 173898 Inspect piping & fitting d/s of LCV-1127D; HDT Large Dump to 23 Condenser.

TB ELEV 16ft-5" D/S OF LCV-1127D Y

Y N

Y SK-18 14" Plant Specific OPERATING EXPERIENCE 125 COND-22 NOZ (3EXB-18N) 167262 198084 Inspect turbine extraxtion nozzle 3EXB-18N (previously inspected as COND-22 NOZ)

Inside Condenser 22 Y

Y N

Y SK-1 28" RE-INSPECTION (TRENDING) 126 LPFW 22A-1P3 167258 198359 127 LPFW 22A-1P4 167258 198359 128 LPFW 22B-1P4 167260 198360 129 FWH shell inspection 148046 173901 open condenser 22 & 23 condenser SCOPE ADDITIONS DESCOPED SUPPORT FEEDWATER HEATER SHELLS LOW PRESSURE FEED W ATER HEATERS EXTRACTION STEAM Drain Miscellaneous DESCOPED DESCOPED DESCOPED 10 of 11 2R19 FAC Scope (Ipe0067423).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 2R19 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS ASBESTOS 11 of 11 2R19 FAC Scope (Ipe0067423).Xls