ML12088A435

From kanterella
Jump to navigation Jump to search
Entergy Pre-Filed Evidentiary Hearing Exhibit ENT000062 - Flow Accelerated Corrosion Inspection Points for 3R16
ML12088A435
Person / Time
Site: Indian Point  
Issue date: 03/28/2012
From:
Entergy Nuclear Operations
To:
Atomic Safety and Licensing Board Panel
SECY RAS
Shared Package
ML12088A422 List:
References
RAS 22102, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01
Download: ML12088A435 (18)


Text

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS CONDENSATE 1

CD-02.1A-01N 183277 00217613 Inspect nozzle 39ft elev at FWH #32A Y

Y N

Y EC-H-50061 14 CHECWORKS - Ranked high on the Service Life Report 2

CD-02.1A-06E 183280 00217616 Inspect component D/S of Valve CD-02.1A-05V. Inspect back to back elbows, plus u/p and d/s extensions. Elbows plus 3 inches on either sides of elbow welds. Inspect 6E/7E TOGETHER 42FT ELEV D/S OF 32 OF 32A FWH.

and valve CD-18 Y

Y N

Y EC-H-50061 14" Inspect CHECWORKS Components CD-02.1A-5V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR.

3 CD-02.1A-07E 183280 00217616 Inspect component D/S of Valve CD-02.1A-05V. Inspect back to back elbows, plus u/p and d/s extensions. Elbows plus 3 inches on either sides of elbow welds. Inspect 6E/7E TOGETHER 42FT ELEV D/S OF 32 OF 32A FWH.

and valve CD-18 Y

Y N

Y EC-H-50061 14" Inspect CHECWORKS Components CD-02.1A-5V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR and in vecinity.

4 CD-02.1B-01N 183282 00217617 Inspect components 01n/03e together. Inspect nozzle and elbow plus 3 inches d/s of the elbow weld.

39ft elev at FWH #32B Y

Y N

Y EC-H-50061 14" CHECWORKS - Ranked high on the Service Life Report 5

CD-02.1B-03E 183282 00217617 Inspect components 01n/03e together. Inspect nozzle and elbow plus 3 inches d/s of the elbow weld.

39ft elev at FWH #32B Y

Y N

Y EC-H-50061 14" FEW INSPECTION IN SEGMENT 6

CD-02.1B-08P 183283 00217618 component d/s of valve CD-02.1B-07V.

Inspect pipe & elbow. Inspect two pipe diameters =28 inches plus elbows & 3 inches D/S of elbow weld. Inspect 8P/9E TOGETHER 42FT ELEV D/S OF 32B FWH. and valve CD-8 Y

Y N

Y EC-H-50061 14" Components CD-02.1B-7V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR and it is in close proximity to the valve.

7 CD-02.1C-01N 183285 217592 Inspect components CD-02.1C-01N/02P/03E together. Inspect nozzle pipE & elbow. Inspect nozzle plus 2 pipe dia =28 inches of pipe elbow plus 3 inches d/s of the elbow weld.

42FT ELEV D/S OF 32C FWH. and u/s of valve CD-8 Y

Y N

Y EC-H-50061 14" CHECWORKS - Ranked high on the Service Life Report 8

CD-02.1C-02P 183285 217592 Inspect components CD-02.1C-01N/02P/03E together. Inspect nozzle pipE & elbow. Inspect nozzle plus 2 pipe dia =28 inches of pipe elbow plus 3 inches d/s of the elbow weld.

42FT ELEV D/S OF 32C FWH. and u/s of valve CD-8 Y

Y N

Y EC-H-50061 14" FEW INSPECTION IN SEGMENT 9

CD-02.1C-03E 183285 217592 Inspect components CD-02.1C-01N/02P/03E together. Inspect nozzle pipE & elbow. Inspect nozzle plus 2 pipe dia =28 inches of pipe elbow plus 3 inches d/s of the elbow weld.

42FT ELEV D/S OF 32C FWH. and u/s of valve CD-8 Y

Y N

Y EC-H-50061 14" FEW INSPECTION IN SEGMENT 10 CD-05.1A-1N 183295 00217593 Inspect nozzle 42 ft. Elev. At 35A FWH Y

Y N

Y EC-H-50064 14" CHECWORKS - Ranked high on the Service Life Report CONDENSATE 1 of 18 3R16 Fac Scope (Ipe0086871).Xls ENT000062 Submitted: March 28, 2012

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 11 CD-05.1A-06P (CD-05.1A-05V) 183297 00217594 Inspect components d/s of valve CD-05.1A-05V. Inspect pipe & elbow. Inspect two pipe diameters =28 inches plus elbows & 3 inches D/S of elbow weld. Inspect 6P/7E TOGETHER 32 FT. ELEV. OFF 35A FWH; D/S OF VALVE CD-18-1 Y

Y N

Y EC-H-50064 14" Inspect CHECWORKS Components CD-05.1A-5V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR and is in vecinity.

12 CD-05.1A-07E 183297 00217594 Inspect components d/s of valve CD-05.1A-05V. Inspect pipe & elbow. Inspect two pipe diameters =28 inches plus elbows & 3 inches D/S of elbow weld. Inspect 6P/7E TOGETHER 32 FT. ELEV. OFF 35A FWH; D/S OF VALVE CD-18-1 Y

Y N

Y EC-H-50064 14" FEW INSPECTION IN SEGMENT 13 CD-05.1B-06P 183304 00217596 Inspect components d/s of valve CD-05.1B-05V. Inspect pipe, elbow & pipe. Inspect two pipe diameters =28 inches plus elbows & 3 inches D/S of elbow welds. Inspect 6P/7E/8P TOGETHER 32 FT ELEV. OFF 35B FWH D/S OF VALVE CD-18-2 Y

Y N

Y EC-H-50064 14" Inspect CHECWORKS Components CD-05.1B-5V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR and is in vecinity.

14 CD-05.1B-07E 183304 00217596 Inspect components d/s of valve CD-05.1B-05V. Inspect pipe & elbow. Inspect two pipe diameters =28 inches plus elbows & 3 inches D/S of elbow weld. Inspect 6P/7E/8P TOGETHER 32 FT ELEV. OFF 35B FWH D/S OF VALVE CD-18-2 Y

Y N

Y EC-H-50064 14" CALCULATION RE-INSPECTION-FAC MANAGER -

15 CD-05.1B-08P 183304 00217596 Inspect components d/s of valve CD-05.1B-05V. Inspect pipe & elbow. Inspect two pipe diameters =28 inches plus elbows & 3 inches D/S of elbow weld. Inspect 6P/7E/8P TOGETHER 32 FT ELEV. OFF 35B FWH D/S OF VALVE CD-18-2 Y

Y N

Y EC-H-50064 14" CALCULATION RE-INSPECTION-FAC MANAGER -

16 CD-02.4-4E 183307 00217597 Inspect reducing elbow (24x20) and pipe.

Inspect pipe and elbow plus upstream and downstream extension. Inspect 48" of pipe and Elbow plus 6 inches on either side of elbow welds.Inspect 4E/1P TOGETHER ELEV. 24FT.6 ins. D/S OF TCV-1110 Y

Y N

Y EC-H-50061 24X20 CALCULATION RE-INSPECTION-FAC MANAGER -

17 CD-02.5-01P 183307 00217597 Inspect reducing elbow (24x20) and pipe.

Inspect pipe and elbow plus upstream and downstream extension. Inspect 48" of pipe and Elbow plus 6 inches on either side of elbow welds.Inspect 4E/1P TOGETHER ELEV. 24FT.6 ins. D/S OF TCV-1110 Y

Y N

Y EC-H-50064 24 CHECWORKS - Ranked high on the Service Life Report 18 CD-02.3-15T 183309 00217599 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds.

ELEV. 24FT.6 ins. U/S OF TCV-1110 Y

Y N

Y EC-H-50061 24x18 CHECWORKS - Ranked high on the Service Life Report 19 CD-02.8A-08N 183310 00217600 Inspect piping ELEV.39FT OFF FWH 33A Y

Y N

Y EC-H-50061 14" CHECWORKS - Ranked high on the Service Life Report 2 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 20 CD-02.8B-08N 183317 00217602 Inspect piping D/S of valve CD-16. Inspect ELBOW,PIPE,ELBOW &

NOZZLE.(Components CD-02.8B-05E /06P

/07E/ 08N)

ELEV 34 FT. 8 INS. UPSTREAM OF FWH 33B & D/S OF VALVE CD-16 Y

Y N

Y EC-H-50061 14" CHECWORKS - Ranked high on the Service Life Report 21 CD-02.8B-05E 183317 00217602 Inspect piping D/S of valve cd-16. Inspect ELBOW,PIPE,ELBOW &

NOZZLE.(Components CD-02.8B-05E /06P

/07E/ 08N)

ELEV 34 FT. 8 INS. UPSTREAM OF FWH 33B & D/S OF VALVE CD-16 Y

Y N

Y EC-H-50061 14" CHECWORKS - Ranked high on the Service Life Report 22 CD-02.8B-06P 183317 00217602 Inspect piping D/S of valve cd-16. Inspect ELBOW,PIPE,ELBOW &

NOZZLE.(Components CD-02.8B-05E /06P

/07E/ 08N)

ELEV 34 FT. 8 INS. UPSTREAM OF FWH 33B & D/S OF VALVE CD-16 Y

Y N

Y EC-H-50061 14" CHECWORKS - Ranked high on the Service Life Report 23 CD-02.8B-07E 183317 00217602 Inspect piping D/S of valve cd-16. Inspect ELBOW,PIPE,ELBOW &

NOZZLE.(Components CD-02.8B-05E /06P

/07E/ 08N)

ELEV 34 FT. 8 INS. UPSTREAM OF FWH 33B & D/S OF VALVE CD-16 Y

Y N

Y EC-H-50061 14" CHECWORKS - Ranked high on the Service Life Report 24 CD-02.8B-02E 183318 00217603 Inspect elbow plus upstream & downstream extension. Elbow plus 3 inches on either side of the elbow welds.

ELEV 34 FT. 8 INS. UPSTREAM OF FWH 33B & U/S OF VALVE CD-16 Y

Y N

N EC-H-50061 14" CALCULATION RE-INSPECTION-FAC MANAGER -Last Inspected 2007 25 CD-02.8C-02E 183319 00217333 Inspect Pipe, elbow & Pipe. Inspect 28 inches of pipe. Inspect components CD-02.8C-01P/02.8C-02E/ 02.8C-3E TOGETHER.

ELEV 34 FT. 8 INS. UPSTREAM OF FWH 33C & U/S OF VALVE CD-16 Y

Y N

N EC-H-50061 14" CALCULATION RE-INSPECTION-FAC MANAGER - Last Inspected 2007 26 CD-02.8C-03P 183319 00217333 Inspect elbow & Pipe. Inspect 28 inches of pipe plus elbow and 3 inches on the upstream extension of the elbow. Inspect components 02.8C-02E/ 02.8C-3E TOGETHER.

ELEV 34 FT. 8 INS. UPSTREAM OF FWH 33C & U/S OF VALVE CD-16 Y

Y N

N EC-H-50061 14" RE-INSPECTION (TRENDING) last inspected 2007 with 02.8C-2E 27 CD-06.1-01T 183320 00217604 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds.

ELEV. 24FT 6 INS. OFF 35A FWH TO BFP #32 Y

Y N

N EC-H-50064 30X16 CALCULATION RE-INSPECTION-FAC MANAGER - Last Inspected 1997 28 CD-06.2A-02E 183321 00217605 Inspect elbow plus upstream & downstream extension. Elbow plus 12 inches on either side of the elbow welds.

ELEV 32 FT. 0 INS. UPSTREAM OF VALVE CD-21-2 Y

Y N

N EC-H-50064 24" CALCULATION RE-INSPECTION-FAC MANAGER - last inspection 1992 29 CD-06.2A-08P 183322 00217607 Inspect piping 2 diameters = 48 inches.

ELEV 32 FT. 0 INS. DOWNSTREAM OF VALVE CD-21-2 Y

Y N

N EC-H-50064 24" CALCULATION RE-INSPECTION-FAC MANAGER -

3 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 30 CD-06.2A-011E 183324 217606 Inspect elbow plus upstream & downstream extension. Elbow plus 12 inches on either side of the elbow welds.

ELEV 24 FT. 6 INS. DOWNSTREAM OF VALVE CD-21-2 Y

Y N

N EC-H-50064 24" CALCULATION RE-INSPECTION-FAC MANAGER -

31 CD-02.12-05P 183331 00217620 Inspect piping 2 diameters = 36 inches.

D/S OF VALVE CD-15 (CD-02.12-04V)

Y Y

N N

EC-H-50088 18" CALCULATION RE-INSPECTION-FAC MANAGER -

32 CD-02.6-3T 183332 00217612 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds.

ELEV 32 FT. 0 INS. UPSTREAM OF FWH 33B & U/S OF VALVE CD-16 Y

Y N

N EC-H-50061 24x14 CALCULATION RE-INSPECTION-FAC MANAGER -

33 CD-04.1C-02E 183333 00217621 Inspect back to back elbows. Inspect elbows Plus U/S and D/S extensions ~ 3 inches on either side of elbows.(CD-04.1C-02E &3E)

TOGETHER ELEV 41 FT. 0 INS. OFF FWH 34C.

Y Y

N N

EC-H-50062 14" CALCULATION RE-INSPECTION-FAC MANAGER -

34 CD-04.1C-03E 183333 00217621 Inspect back to back elbows. Inspect elbows Plus U/S and D/S extensions ~ 3 inches on either side of elbows.(CD-04.1C-02E &3E)

TOGETHER ELEV 41 FT. 0 INS. OFF FWH 34C.

Y Y

N N

EC-H-50062 14" CALCULATION RE-INSPECTION-FAC MANAGER -

35 EX-01.2-10L 183365 00217622 INSPECT LATERAL ELEV. 39FT. 6 INS U/S OF VALVE 6EX-1 & 6 EX-4 Y

Y N

N EC-H-50000 18"X12" Inspected in 1997. Re-inspection or NSI =

3R16. CALCULATION RE-INSPECTION-FAC MANAGER -

36 EX-01.4-02T 183367 00217624 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 3 INCHES ON ALL SIDES OF TEE welds.

ELEV. 31FT. 9 INS U/S OF LINE TO FWH 36B &VALVE 6EX-5.

Y Y

N N

EC-H-50000 18X12 CALCULATION RE-INSPECTION-FAC MANAGER -

37 EX-02.2-01N 183368 00217625 Inspect nozzle TB. ELEV.44FT. 5 INS N

EC-H-50071 10" CALCULATION RE-INSPECTION-FAC MANAGER -

38 EX-02.14-25E 183370 00217627 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 12 inches U/S & D/S of elbow welds.

Turb. Bldg. Elev. 24'-6" U/S of hanger 5EX-6 Y

Y Y

N EC-H-50001 28" CALCULATION RE-INSPECTION-FAC MANAGER -

39 EX-02.17-02V D/S = EX-02.17-03E 183371 00217628 Inspect Elbow, Pipe, Inspect COMPONENTS D/S OF VALVE 5EX-5 COMPONENTS EX-02.17-03E/04P. FOR PIPE 2 DIA=36 INCHES.

Also inspect u/s extension of first elbow 8 inches(d/s of valve)

Turb. Bldg. Elev. 42'-3" off FWH 35B Y

Y Y

Y EC-H-50001 18" Inspect CHECWORKS Components EX-02.17-2V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR.

EXTRACTION 4 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 40 EX-02.17-04P 183372 00217628 Inspect Elbow, Pipe,. Inspect COMPONENTS D/S OF VALVE 5EX-5 COMPONENTS EX-02.17-03E/04P. FOR PIPE 2 DIA=36 INCHES.

Also inspect u/s extension of first elbow 8 inches(d/s of valve)

Turb. Bldg. Elev. 42'-3" off FWH 35B Y

Y Y

Y EC-H-50001 18" Component also selected because of proximity to highly ranked component.

41 EX-03.1B-33E 183377 00217631 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 10 inches U/S & D/S of elbow welds.

Turb. Bldg. Elev. 42'-2" off FWH 34B Y

Y N

N EC-H-50006 20" CALCULATION RE-INSPECTION-FAC MANAGER -

42 EX-03.1C-37E 183379 00217634 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 10 inches U/S & D/S of elbow welds.

Turb. Bldg. Elev. 42'-2" off FWH 34C Y

Y N

N EC-H-50002 20" CALCULATION RE-INSPECTION-FAC MANAGER -

43 EX-04.13-01R 183380 00217635 Inspect reducer plus U/S & D/S EXTENSION 6

" ON EITHER SIDE OF WELD.

Turb. Bldg. Elev. 24'-6" U/S of hanger 3EX-23. LINE OFF 33B FWH Y

Y N

N EC-H-50008 28X20 CALCULATION RE-INSPECTION-FAC MANAGER -

44 EX-04..6-04P 183382 00217639 Inspect PIPE &ELBOW. (EX-04..6-04P/05E)

For piping INSPECT 2 diameters = 40 inches. Turb. Bldg. Elev. 42'-2" off FWH 33A Y

Y N

N EC-H-50007 20" CALCULATION RE-INSPECTION-FAC MANAGER -

45 EX-04..6-05E 183382 00217639 Inspect PIPE & ELBOW. (EX-04..6-04P/05E)

For piping INSPECT 2 diameters = 40 inches.

Also inspect downstream extension of elbow.

Turb. Bldg. Elev. 42'-2" off FWH 33A Y

Y N

N EC-H-50007 20" CALCULATION RE-INSPECTION-FAC MANAGER -

46 EX-04.7-01P 183383 00217640 Inspect piping 2 diameters = 40 inches.

Turb. Bldg. between Elev. 24'-2" & 42'-2".

Line OFF 33A FWH Y

Y N

N EC-H-50007 20" CALCULATION RE-INSPECTION-FAC MANAGER -

47 FW-01.2A-03T 183385 00217641 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 10 INCHES ON ALL SIDES OF TEE MAIN welds PLUD 2 INCHES D/S OF BRANCH..

TB. ELEV. 24'-5" D/S OF BFP 31 DISCHARGE.

Y Y

N N

EC-H-50039 20"X 6" CALCULATION RE-INSPECTION-FAC MANAGER -

48 FW-01.2A-10E 183386 00217662 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 10 inches U/S & D/S of elbow welds.

TB. ELEV. 24'-5" D/S OF BFP 31 DISCHARGE & FURTHER D/S OF VALVE BFD2-3.

Y Y

N N

EC-H-50039 20" CALCULATION RE-INSPECTION-FAC MANAGER -

49 FW-01.2A-23P 183387 00217663 Inspect piping 2 diameters = 40 inches.

TB. ELEV. 24'-5" D/S OF BFP 31 DISCHARGE & FURTHER D/S OF HANGER BFD-11 Y

Y N

N EC-H-50039 20" CALCULATION RE-INSPECTION-FAC MANAGER -

50 FW-01.2B-27R 183388 00217664 Inspect reducer plus U/S & D/S EXTENSION 6

" ON EITHER SIDE OF WELD.

TB. ELEV. 24'-5" D/S OF BFP 32DISCHARGE & FURTHER D/S OF HANGER BFD-6.

Y Y

N N

EC-H-50039 30X20 CALCULATION RE-INSPECTION-FAC MANAGER -

FEEDWATER 5 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 51 FW-01.3-15E 183389 00217665 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 12 inches U/S & D/S of elbow welds.

Turb. Bldg. Elev. 23'-6" D/S of hanger BFD-16. LINE OFF FWH 36A Y

Y N

N EC-H-50039 30" CALCULATION RE-INSPECTION-FAC MANAGER -

52 FW-02.1C-10P 183394 00217672 Inspect piping 2 diameters = 36 inches.

Turb. Bldg. Elev. 34'-9" D/S OF VALVE BFD-4 =. LINE OFF FWH 36C Y

Y N

N EC-H-50042 18" CALCULATION RE-INSPECTION-FAC MANAGER -

53 FW-02.1C-11T 183395 00217673 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds.

Turb. Bldg. Elev. 34'-9" D/S OF VALVE BFD-4 =. LINE OFF FWH 36C Y

Y N

N EC-H-50042 30X18 CALCULATION RE-INSPECTION-FAC MANAGER -

54 FW-02.4-05E 183396 00217700 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 12 inches U/S & D/S of elbow welds.

Turb. Bldg. Elev. 29'-9" D/S OF HANGER BFD-22 =. LINE OFF FWH 36A Y

Y N

N EC-H-50039 30" CALCULATION RE-INSPECTION-FAC MANAGER -

6 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 55 FW-02.4-07E 183397 00217699 Inspect PIPE & ELBOW. (FW-02.4-07E/08P)

For piping INSPECT 2 diameters = 60 inches.

PLUS U/S EXTENSION OF ELBOW =12 INCHES AUX. Bldg. Elev. 29'-9" D/S OF HANGER BFD-22 =. LINE OFF FWH 36A Y

Y N

Y EC-H-50040 30" CHECWORKS - Ranked high on the Service Life Report 56 FW-02.4-08P 183397 00217699 Inspect PIPE & ELBOW. (FW-02.4-07E/08P)

For piping INSPECT 2 diameters = 60 inches.

PLUS U/S EXTENSION OF ELBOW =12 INCHES AUX. Bldg. Elev. 29'-9" D/S OF HANGER BFD-22 =. LINE OFF FWH 36A Y

Y N

Y EC-H-50040 30" CHECWORKS - Ranked high on the Service Life Report 57 FW-02.4-13E 183398 00217697 Inspect PIPE, ELBOW& PIPE. (FW-02.4-12P/13E/14P) For piping INSPECT 2 diameters = 60 inches. PLUS U/S EXTENSION OF ELBOW =12 INCHES AUX. Bldg. Elev. 29'-9" D/S OF HANGER BFD-25. LINE OFF FWH 36A Y

Y N

Y EC-H-50040 30" CHECWORKS - Ranked high on the Service Life Report 58 FW-02.4-19T 183399 00217696 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds.

AUX. Bldg. Elev. 43'-0" D/S OF HANGER BFD-32. LINE OFF FWH 36A Y

Y N

N EC-H-50040 30X18 CALCULATION RE-INSPECTION-FAC MANAGER -

59 FW-02.6-02T (Elbow) 183400 00217695 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds. NOTE this really an elbow attached and not a tee.

AUX. Bldg. Elev. 43'-0" U/S OF HANGER BFD-33. LINE OFF FWH 36A Y

Y N

Y EC-H-50040/9321-F-20613 30X6 CHECWORKS - Ranked high on the Service Life Report 60 FW-02.7-02T (Elbow) 183401 00217694 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds. NOTE this really an elbow attached and not a tee.

AUX. Bldg. Elev. 43'-0" U/S OF HANGER BFD-33. LINE OFF FWH 36A Y

Y N

Y EC-H-50040/9321-F-20613 30X6 CHECWORKS - Ranked high on the Service Life Report 61 FW-02.7-4T 183402 00217693 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 12 INCHES ON ALL SIDES OF TEE welds.

AUX. Bldg. Elev. 43'-0" D/S OF HANGER BFD-33. LINE OFF FWH 36A Y

Y N

N EC-H-50040 30X18 CALCULATION RE-INSPECTION-FAC MANAGER -

62 FW-02.8A-26R 183405 00217690 Reducer and UPSM and DNSM extensions.

Prep. reducer plus 8 inches of piping U/S &

D/S of reducer welds.

AUX. BLDG. Elev 22'-3" adjacent to FCV-417 D/S Y

Y N

N EC-H-50040 18" CALCULATION RE-INSPECTION-FAC MANAGER -

63 FW-02.8B-01P 183406 00217689 Inspect piping 2 diameters = 36 inches.

AUX. Bldg. BETWEEN ELEV. 43'-0"& 22 FT 3 INS U/S OF VALVE FCV-427 Y

Y N

N EC-H-50040 18" CALCULATION RE-INSPECTION-FAC MANAGER -

64 FW-02.8B-25R 183407 00217688 Reducer and UPSM and DNSM extensions.

Prep. reducer plus 8 inches of piping U/S &

D/S of reducer welds.

AUX. BLDG. Elev 22'-3" adjacent to BFD-MOV-5-2 Y

Y N

N EC-H-50040 18" CALCULATION RE-INSPECTION-FAC MANAGER -

7 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 65 FW-02.8C-20P 183409 00217685 Inspect piping 2 diameters = 36 inches.

AUX. BLDG. Elev 57'-6" adjacent to BFD-7-4 Y

Y N

Y EC-H-50041 18" CHECWORKS - Ranked high on the Service Life Report 66 FW-02.8C-25R 183410 00217684 Reducer and UPSM and DNSM extensions.

Prep. reducer plus 8 inches of piping U/S &

D/S of reducer welds.

AUX. BLDG. Elev 22'-3" adjacent to FCV-447 D/S Y

Y N

N EC-H-50040 18" CALCULATION RE-INSPECTION-FAC MANAGER -

67 FW-02.8D-07E 183413 00217682 Inspect components D/S ov valve FW-02.8d-05V. Elbow and PIPE. Prep. 2 DIA =36" for pipe and Elbow plus 8 inches D/S of elbow weld. FW-02.8D-07E/8P AUX. BLDG. Elev 22'-3" adjacent to FCV-437 D/S Y

Y N

Y EC-H-50040 18" Inspect CHECWORKS Components FW-02.1B-5V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR. Other component selected in close proximity to highly ranked component.

68 FW-02.8D-08P 183413 00217682 Elbow and PIPE. Prep. 2 DIA =36" for pipe and Elbow plus 8 inches D/S of elbow weld.

FW-02.8D-07E/8P AUX. BLDG. Elev 22'-3" adjacent to FCV-437 D/S Y

Y N

Y EC-H-50040 18" CHECWORKS - Ranked high on the Service Life Report AND IN VECINITY OF OTHER SELECTED COMPONENTS.

8 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 69 FW-02.8D-19P 183414 00217680 Inspect piping 2 diameters = 36 inches.

AUX. BLDG. Elev 57'-6" adjacent to BFD-7-3 Y

Y N

Y EC-H-50041 18" CHECWORKS - Ranked high on the Service Life Report 70 FW-02.8D-24R 183415 00217681 INSPECT REDUCER AUX. BLDG. Elev 22'-3" adjacent to FCV-437 D/S Y

Y N

Y EC-H-50040 18"X12" CALCULATION RE-INSPECTION-FAC MANAGER -

71 FW-03.1C-14E 183418 00217678 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 8 inches U/S & D/S of elbow welds.

VC ELEV. 104'-10". Line to 34 Steam generator Y

Y N

N EC-H-50046 18" CALCULATION RE-INSPECTION-FAC MANAGER -

72 FW-04.1A-01E 183421 00217677 Inspect Elbow & Pipe. Inspect 2 dia = 12" of pipe plus elbow TB ELEV. 24'-5"D/S OF 31BFP DISCHARGE @ COMPONENT FW-01.2A-3T Y

Y N

N EC-H-50084 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

73 HD-09.1A-02R 183427 00217412 Inspect reducer plus U/S & D/S EXTENSION 6

" ON EITHER SIDE OF WELD IF POSSIBLE.. TB ELEV 38'- 3" D/S OF LCV 1121 Y

Y N

N EC-H-50031 12"X10" CALCULATION RE-INSPECTION-FAC MANAGER -

74 HD-11.1A-02V (HD-11.2A-01R) 183428 00217413 Inspect reducer plus U/S & D/S EXTENSION 6

" ON EITHER SIDE OF WELD IF POSSIBLE..

TB. ELEV 15 FT D/S OF HTR DRAIN PUMP 31 AND VALVE HD-1 Y

Y N

Y EC-H-50079 12"x8" Inspect CHECWORKS Components HD-11.1A-02V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR.

75 HD-11.2B-01R 183429 00217408 Inspect reducer plus U/S & D/S EXTENSION 6

" ON EITHER SIDE OF WELD IF POSSIBLE..

TB. ELEV 15 FT D/S OF HTR DRAIN PUMP 32 AND VALVE HD-1 Y

Y N

Y EC-H-50079 12"x8" Inspect CHECWORKS Components HD-11.1B-02V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR.

76 HD-12.2A-03E 183431 00217406 Inspect component d/s of valve HD-2 component HD-12.2A-03E.

TB. ELEV 15 FT D/S OF HTR DRAIN PUMP 31 AND VALVE HD-1 EC-H-50079 12" Inspect CHECWORKS Components HD-12.1A-01V (Ranked high on the Service Life Report). Components D/S of valve selected since valves are rarely UT INSPECTED DUE TO CONTOUR.

77 HD-12.2B-06O 183433 00217403 Inspect 2 dia = 24 inches d/s of orifice TB. ELEV 15 FT D/S OF HTR DRAIN PUMP 32 AND VALVE HD-1 Y

Y N

Y EC-H-50079 12" CALCULATION RE-INSPECTION-FAC MANAGER -

78 HD-12.2B-08T 183434 00217404 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 6 INCHES ON ALL SIDES OF TEE welds.

TB. ELEV 15 FT D/S OF HTR DRAIN PUMP 32 AND VALVE HD-1 Y

Y N

Y EC-H-50079 12" CALCULATION RE-INSPECTION-FAC MANAGER -

HEATER DRAINS 9 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 79 HD-12.3-01P 183435 00217396 Inspect piping 2 diameters = 32 inches.

TB. ELEV 32' 0" D/S OF HTR DRAIN PUMP 32.

Y Y

N N

EC-H-50079 16" CALCULATION RE-INSPECTION-FAC MANAGER -

80 99-PT-29 183436 00217402 Rre-inspect per data sheet 99UT261. Inspect 3 elbows & 3 pipes.

VENT CHAMBER DRAIN Y

Y N

N 9321-F-29013 3"

CALCULATION RE-INSPECTION-Small Bore/ Augmented Program 81 5HD-LCV-1127B 183437 00217394 HEATER DRAIN TANK LARGE DUMP TO 33 CONDENSER Inspect puiping and fitting d/s of 5HD-LCV-1127B Y

Y N

Y EC-F-20223 SH-2 14" LEAKS AFFECTING THERMAL EFFICIENCY 82 5HD-LCV-1127C 183438 00217395 HEATER DRAIN TANK LARGE DUMP TO 32 CONDENSER Inspect puiping and fitting d/s of 5HD-LCV-1127C Y

Y N

Y EC-F-20223 SH-2 14" LEAKS AFFECTING THERMAL EFFICIENCY 10 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 83 RHD01.10A-18F 183739 217723 Re-Inspect piping D/S OF FE1257-3 (includes straight pipe expander and elbow RHD01.10A-18F/20R&RHD01.11A-01E). last inspected 2005 reference datasheet 05UT077.

tb-elev. 46'-0" d/s of FE-1257-3 Y

Y N

N EC-H-50014 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

84 RHD01.10A-04N 183740 00217711 Inspect nozzle, pipe & elbow (RHD01.10A-04N/5P/6E. For pipe 2dia = 12 inches. Also inspect d/s extension of elbow =2 insches TB. ELEV 56'-4" OFF REHEATER DRAIN TANK 33A Y

Y N

Y EC-H-50014 6"

CHECWORKS - Ranked high on the Service Life Report 85 RHD01.10A-05P 183740 00217711 Inspect nozzlw, pipe & elbow (RHD01.10A-04N/5P/6E. For pipe 2dia = 12 inches. Also inspect d/s extension of elbow =2 insches TB. ELEV 56'-4" OFF REHEATER DRAIN TANK 33A Y

Y N

Y EC-H-50014 6"

Component also selected because of proximity to highly ranked component.

86 RHD01.10A-06E 183740 00217711 Inspect nozzlw, pipe & elbow (RHD01.10A-04N/5P/6E. For pipe 2dia = 12 inches. Also inspect d/s extension of elbow =2 insches TB. ELEV 56'-4" OFF REHEATER DRAIN TANK 33A Y

Y N

Y EC-H-50014 6"

Component also selected because of proximity to highly ranked component.

87 RHD01.10B-26F 183741 217712 Re-Inspect piping D/S OF flow element. last inspected 2005 reference datasheet 05UT074.

TB. ELEV. 47'-7" D/S OF FLOW ELEMENT FE-1258-3. LINE OFF RHD TANK 33B Y

Y N

N EC-H-50016 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

88 RHD01.13A-01R 183745 00217713 RE-INPECT REDUCER. LAST INSPECTED 1999 REFERENCE DATA SHEET 99UT255 TB. ELEV. 38'-9" U/S OF VALVE LCV-1104B Y

Y N

N EC-H-50014 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

89 RHD01.1A-35F 183748 00217714 INPECT 24" of piping U/S and D/S of flow element TB. ELEV. 44'-8" D/S OF FLOW ELEMENT FE-1257-1. LINE OFF RHD TANK 31A Y

Y N

N EC-H-50011 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

90 RHD01.3A-04N 183749 00217715 Inspect nozzle, pipe & elbow (RHD01.3A-04N/5P/6E. For pipe 2dia = 12 inches. Also inspect d/s extension of elbow =2 insches TB. ELEV 56'-4" OFF REHEATER DRAIN TANK 32A Y

Y N

Y EC-H-50012 6"

CHECWORKS - Ranked high on the Service Life Report 91 RHD01.3A-05P 183749 00217715 Inspect nozzle, pipe & elbow (RHD01.3A-04N/5P/6E. For pipe 2dia = 12 inches. Also inspect d/s extension of elbow =2 insches TB. ELEV 56'-4" OFF REHEATER DRAIN TANK 32A Y

Y N

Y EC-H-50012 6"

Component also selected because of proximity to highly ranked component.

92 RHD01.3A-06E 183749 00217715 Inspect nozzlw, pipe & elbow (RHD01.3A-04N/5P/6E. For pipe 2dia = 12 inches. Also inspect d/s extension of elbow =2 insches TB. ELEV 56'-4" OFF REHEATER DRAIN TANK 32A Y

Y N

Y EC-H-50012 6"

Component also selected because of proximity to highly ranked component.

RE-HEATER DRAINS 11 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 93 RHD01.3B-06E 183752 00217716 REINPECT (6") ELBOW & D/S PIPING.

REFERENCE DATA SHEET 99UT251.

TB. ELEV 49'-1" OFF REHEATER DRAIN TANK 32B Y

Y N

N EC-H-50009 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

94 RHD01.5B-03F 183754 00217717 INPECT U/S & D/S OF FLOW ELEMENT FE-1257-2 ~ 2 DIA = 12" ON EITHER SIDE OF ELEMENT.

TB. ELEV. 47'-10" D/S OF FLOW ELEMENT FE-1258-2. LINE OFF RHD TANK 32B Y

Y N

N EC-H-50009 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

95 RHD01.7B-03R 183758 00217719 REINPECT EXPANDER PER DATA SHEET 99UT277.

TB. ELEV. 47'-8" U/S OF VALVE LCV-1105A Y

Y N

N EC-H-50009 10X6 CALCULATION RE-INSPECTION-TRENDING DATABASE 96 RHD02.10A-11T 183760 00217704 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 4 INCHES ON ALL SIDES OF TEE MAIN welds PLUS 2 INCHES D/S OF BRANCH.. REFERENCE DATASHEET 3R14-FAC-07-062 TB. ELEV. 31'-8" D/S OF VALVE RHD-2.

LINE OFF FWH 36B Y

Y N

N EC-H-50015 8X6 CALCULATION RE-INSPECTION-FAC MANAGER -

12 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 97 RHD02.12B-11T 183763 00217705 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 2 INCHES ON ALL SIDES OF TEE MAIN welds PLUS 2 INCHES D/S OF BRANCH.REFERENCE DATA SHEETS 3R15-FAC-09-158/159.

TB. ELEV. 39'-3" U/S OF VALVE RHD-1.

LINE OFF FWH 36B Y

Y N

N EC-H-50010 6X6 CALCULATION RE-INSPECTION-FAC MANAGER -

98 RHD02.13A-16T 183765 00217706 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 2 INCHES ON ALL SIDES OF TEE MAIN welds PLUS 2 INCHES D/S OF BRANCH.REFERENCE DATA SHEET 3R15-FAC-09-028.

TB. ELEV. 42'-9" D/S OF VALVE RHD-1.

LINE OFF FWH 36B Y

Y N

N EC-H-50015 6X6 CALCULATION RE-INSPECTION-FAC MANAGER -

99 RHD02.14A-01N 183769 00217707 Inspect PUP PIPING U/S OF Nozzle.

REFREENCE DATA SHEET 3R14-FAC 058.

TB. ELEV. 42'-9" D/S OF VALVE RHD-1.

LINE OFF FWH 36B Y

Y N

N EC-H-50015 8"

CALCULATION RE-INSPECTION-FAC MANAGER -

100 RHD02.3A-02R 183787 00217709 INSPECT EXPANDER. REFERENCE DATA SHEET 3R14-FAC-07-054 TB. ELEV. 38'-9" D/S OF VALVE LCV-1104A Y

Y N

N EC-H-50015 4X6" CALCULATION RE-INSPECTION-FAC MANAGER -

101 RHD02.5A-02R 183790 00217710 INSPECT EXPANDER. REFERENCE DATA SHEET 3R14-FAC-07-016 TB. ELEV. 38'-9" D/S OF VALVE LCV-1104B Y

Y N

N EC-H-50015 4X6" CALCULATION RE-INSPECTION-FAC MANAGER -

102 MSD-01.10A-25N 183806 00217929 Inspect nozzle TB. ELEV. 21'-6" AT HEATER DRAIN TANK Y

Y N

N EC-H-50035 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

103 MSD-01.10B-02E 183807 00217930 Inspect elbow. Reference data sheet 99UT283 TB. ELEV 43'-6" BELOW MSR DRAIN TANK 32B Y

Y N

N EC-H-50038 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

104 MSD-01.10B-07E 183808 00217931 Elbow and UPSM and DNSM extensions.

Prep. Elbow plus 2 inches U/S & D/S of elbow welds. Reference data sheet 99UT284 TB. ELEV 39'-6" BELOW MSR DRAIN TANK 32B & D/S OF VALVE 5-HD-2 Y

Y N

N EC-H-50038 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

105 MSD-01.13A-01T 183809 217932 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 6 INCHES ON ALL SIDES OF TEE MAIN welds PLUS 6 INCHES D/S OF BRANCH..

TB. ELEV 53'96" 33A MSR DRAIN U/S OF VALVE 5HD-1.

Y Y

N N

EC-H-50078 12" CALCULATION RE-INSPECTION-FAC MANAGER -

MSR DRAINS 13 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 106 MSD-01.5B-11P-2 183813 00217934 Reinspect (6") piping.Inspected 1999.

Reference datasheet 99UT280 ~24 "

TB. ELEV 34'-0" BELOW MSR DRAIN TANK 31B & D/S OF VALVE 5-HD-3 Y

Y N

N EC-H-50038 6"

CALCULATION RE-INSPECTION-FAC MANAGER -

107 FAC-07-VCD-05 183818 00217936 3R14 EXAM. RE-INSPECT SEE DATA SHEET 3R14-FAC-07-104. Piping segments from MSR 32B. Two (2) 90 degree elbows per previous exam.

Turbine Building. Located approximately 12' west and on the centerline of F/19, El. 46' Y

Y N

N 9321-F-29013 3"

CALCULATION RE-INSPECTION-FAC MANAGER -

108 FAC-07-VCD-07 183819 00217937 3R14 EXAM. RE-INSPECT SEE DATA SHEET 3R14-FAC-07-055. EXAM CONSISTS OF ELBOW DOWNSTREAM OF VCD-2.

MSR 33B Turbine Building. Located approximately 7' West and 4' North and F/17. El 53' Y

Y N

N 9321-F-20233 3"

CALCULATION RE-INSPECTION-FAC MANAGER -

109 FAC-07-VCD-09 183823 00217939 3R14 EXAM. RE-INSPECT SEE DATA SHEET 3R14-FAC-07-101 TB EL 52'; VCD Discharge from MSR 31A Y

Y N

N 9321-F-20233 3"

CALCULATION RE-INSPECTION-FAC MANAGER -

110 FAC-07-VCD-11 183828 00217940 3R14 EXAM. RE-INSPECT SEE DATA SHEET 3R14-FAC-07-039/046. VCD Discharge from MSR 32A; 2 elbows TB EL 36' West of 33' mezz stairs; VCD Discharge from MSR 32A; 2 elbows Y

Y N

N 9321-F-20233 3"

CALCULATION RE-INSPECTION-FAC MANAGER -

14 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 111 99-PT-25-2 183833 00217941 3R10 EXAM. RE-INSPECT SEE DATA SHEET 99UT258. VDC TB EL 47'-8" VCD Discharge from MSR 31A Y

Y N

N 9321-29013 3"

CALCULATION RE-INSPECTION-TRENDING DATABASE 112 99-PT-29-5 183837 00217942 3R10 EXAM. RE-INSPECT SEE DATA SHEET 99UT261. VDC TB EL 46'-3" VCD Discharge from MSR 31B Y

Y N

N 9321-29013 3"

CALCULATION RE-INSPECTION-TRENDING DATABASE 113 03-PT-06-03 183838 00217944 3R12 EXAM. RE-INSPECT SEE DATA SHEET 03UT073. HEATER DRAIN TB. approximately 12' West and on the centerline of F/19, El. 46'.

Y Y

N N

9321-29013 3"

CALCULATION RE-INSPECTION-TRENDING DATABASE 114 03-PT-04-02/03 183839 00217945 3R12 EXAM. RE-INSPECT SEE DATA SHEET 03UT019. HEATER DRAIN TB. CONDENSER 31; 3' South and 3' West of D6/15.7. From El. 36', 3' under grating Y

Y N

N 9321-F-20233 3"

CALCULATION RE-INSPECTION-TRENDING DATABASE 115 MSD-01.3B-08N 183844 00217943 INSPECT 31 B MSR NOZZLE AND SHELL (MSD-01.3B-08N).

TB. ELEV 53'-1" AT MSR DRAIN TANK 31B Y

Y N

Y EC-H-50038 12" OPERATING EXPERIENCE 116 MSD-01.8B-08N 183845 00217946 INSPECT 32 B MSR NOZZLE AND SHELL (MSD-01.8B-08N).

TB. ELEV 53'-1" AT MSR DRAIN TANK 32B Y

Y N

Y EC-H-50038 12" OPERATING EXPERIENCE 117 MSD-01.13B-10N 183847 00217947 INSPECT 33 B MSR NOZZLE AND SHELL (MSD-01.13B-10N).

TB. ELEV 53'-1" AT MSR DRAIN TANK 33B Y

Y N

Y EC-H-50038 12" OPERATING EXPERIENCE 118 PD-02.3-01T 183848 00217948 Inspect TEE, BRANCH and upstream &

downstream extensions, TEE & BRANCH PLUS 4 INCHES ON ALL SIDES OF TEE MAIN welds PLUS 6 INCHES D/S OF BRANCH..

Turb Bldg. Elevation 16'-6"; Turb-Gen end.

Y Y

N N

EC-H-50077 16 CALCULATION RE-INSPECTION-FAC MANAGER -

119 MS-FE-439-DS 183849 217950 Main Steam Venturi from 33 SG. Inspect drain slot area. Reference datasheet 3R15-FAC 117 VC El 107' Y

Y N

Y 9321-F-25423 28" CONDITION REPORT-CR-IP3-2009-01453 120 01-PT-24-12 183851 00217951 Inspect main steam trap piping segment 12(01-PT-24-12). Reference data sheet 01UT037.

UPSTREAM OF VALVE MS-119-3 Y

Y N

N 9321-F-20423 3/4 & 1" CALCULATION RE-INSPECTION-SNM program MAIN STEAM PRE-SEPARATOR DRAINS 15 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 121 03-PT-09-05/06/08 183852 00217952 Elbow and Piping DNSM of MS-FCV-1157 until it enters the condenser. 3R12EXAM. RE-INSPECT SEE DATA SHEET 03UT093.

extraction steam TB. ELEV 31'-0" MEZZANNINE UNDER HP-TURBINE Y

Y N

N 9321-F-20173 1.5"/2" CALCULATION RE-INSPECTION-SNM program 122 MS-FCV-1154 183854 00217953 32MSLine HP Turb. Drain to Cond.

TB. ELEV 31'-0" MEZZANNINE UNDER HP-TURBINE Y

Y N

Y 9321-F-20173 1"

PROBLEMS AFFECTING THERMAL EFFICIENCY 123 LCV-1109 183857 00217954 piping/fittings downstream of LCV-1109 32B moisture separator drain tank to DCT Y

Y N

Y 9321-F-20233 6"

PROBLEMS AFFECTING THERMAL EFFICIENCY 124 FWH-31A HTX 132247 00155694 Inspect FWH 31A shell. Inspect 2 pipe dia.

From center line of inlet nozzle (26") radially and axially.

Inside condenser #33 Y

Y N

Y EC-F-20203/ 9321-f-20053 Shell OPERATING EXPERIENCE 125 FWH-32B HTX 132252 00155696 Inspect FWH 32B shell. Inspect 2 pipe dia.

From center line of nozzle (22") radially and axially.

INSIDE condenser #32 Y

Y N

Y EC-F-20203/ 9321-f-20053 Shell OPERATING EXPERIENCE FEEDWATER HEATER SHELLS 16 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 126 FAC-05-EST-03 183861 00217955 3R13EXAM. RE-INSPECT SEE DATA SHEET 05UT005. extraction steam TB elev 21ft 3" between Col 13 &14 Y

Y N

N 9321-f-21513

/9321-F-20313 6"

CALCULATION RE-INSPECTION-SNM program 127 3FAC-07-AFW-01 184170 218266 PIPE& 45 DEG ELBOW. REFERENCE DATASHEET IP3-UT-07-096 Downstream of BFD-FCV-1121 Y

Y N

N 9321-F-20193.

2" CALCULATION RE-INSPECTION-FAC MANAGER -

128 3FAC-07-AFW-02 184172 218291 Pipe. REFERENCE DATA SHEET IP3-UT-07-0Downstream of BFD-FCV-1123 Y

Y N

N 9321-F-20193.

2" CALCULATION RE-INSPECTION-FAC MANAGER -

129 3FAC-07-AFW-03 184173 218267 PIPE& 45 DEG ELBOW; PIPE & 90 DEG ELBOW. REFERENCE DATA SHEET IP3-UT-07-098/099 Downstream of throttle valves BFD-53 and BFD-55 Y

Y N

N 9321-F-20193.

2"/ 3" CALCULATION RE-INSPECTION-FAC MANAGER -

130 3FAC-07-AFW-04 184174 218268 PIPE & 90 DEG ELBOW. REFERENCE DATA SHEET IP3-UT-07-100 Upstream of BFD-FCV-1121 Y

Y N

N 9321-F-20193.

2" CALCULATION RE-INSPECTION-FAC MANAGER -

131 3FAC-07-AFW-05 184176 218269 PIPE& 45 DEG ELBOW & 90 DEG ELBOW.

REFERENCE DATA SHEET IP3-UT-07-102 Upstream of BFD-FCV-1123 Y

Y N

N 9321-F-20193.

2" CALCULATION RE-INSPECTION-FAC MANAGER -

132 3FAC-07-AFW-06 184179 218292 PIPE & 90 DEG ELBOW & TEE.

REFERENCE DATA SHEET IP3-UT 103/104 Discharge from 31 ABFP Y

Y N

N 9321-F-20193.

2"/4" CALCULATION RE-INSPECTION-FAC MANAGER -

133 3FAC-07-AFW-07 184182 218294 PIPE & 90 DEG ELBOW & TEE.

REFERENCE DATA SHEET IP3-UT-07-105 Discharge from 33 ABFP Y

Y N

N 9321-F-20193.

2"/4" CALCULATION RE-INSPECTION-FAC MANAGER -

134 3FAC-07-AFW-08 184183 218295 PIPE, ELBOW, EXPANDER TEE.

REFERENCE DATA SHEET IP3-UT 107/108/109 Discharge from 32 ABFP Y

Y N

N 9321-F-20193.

2"/4"/6' CALCULATION RE-INSPECTION-FAC MANAGER -

135 97-PT-29 192068 227301 Inspect piping off EST-17at intersection where 2",3" and 6" piping meet. Reference data sheet 97UT192 EXT steam drains off 33B FWH Y

Y N

N 9321-F-20313 2",3",6" CALCULATION RE-INSPECTION-FAC MANAGER -

136 03-PT-18-04 192069 228221 re-inspect reducer immediately DNSM of 5HD-LCV-1127D. Reference data sheet 03UT051 Piping segments located approximately 2' South and 7' West of B4/15.7 El. 13'.

Y Y

N N

9321-F-20223 10x14" CALCULATION RE-INSPECTION-FAC MANAGER -

137 MSD-01.8A-8N 191663 227303 AND SHELL AREA. INSPECT 2 PIPE DIAMETERS FROM THE CENTERLINE AXIALLY AND RADIALLY OR AS DIRECTED TB. ELEV 53'-1" AT MSR DRAIN TANK 32A Y

Y N

Y EC-H-50038 & EC-H-50078 12" OPERATING EXPERIENCE EXTRACTION STEAM Drain Aux Feed water MISC 17 of 18 3R16 Fac Scope (Ipe0086871).Xls

FLOW ACCELERATED CORROSION INSPECTION POINTS FOR 3R16 NUMBER EXAM POINT WORK REQUEST WORK ORDER DESCRIPTION LOCATION SCAFFOLD INSULATION PAINT PIPE PREP DRAWING PIPE SIZE REMARKS 138 EX-02.14-25E 210799 248902 Re-inspect Elbow in accordance with Data sheet 3R15-FAC-09-002.

15 FT ELEV.

Y Y

N N

EC-H-50001 28" RE-INSPECTION (TRENDING); WET STEAM REPLACEMENT CANCELLED 139 RHD-02.13A-16T 210808 248901 Re-inspect TEE in accordance with Data sheet 3R15-FAC-09-028.

33FT ELEV N

Y N

N EC-H-50015 6"

RE-INSPECTION (TRENDING); WET STEAM REPLACEMENT CANCELLED 140 34 FWH VENT LINE 220153 INSPECT (3") PIPING AND FITTING ON 34 FWH COMMON VENT LINE FROM THE OPERATING VENTS 4(IN THE VECINITY OF LEAK REPAIR FIX ON ELBOW 4-HD-3-1).

INSPECT FITTINGS AND ~ 3FT OF PIPING.

TB elev 30 ft - 34 FWH COMMON VENT LINE Y

Y N

Y 9321-F-20223.

3" OPERATING EXPERIENCE EX-02.14-25E 218489 248902-07 Contingency replacement RHD02.13A-16T 218490 248901-07 Contingency replacement ADDITIONS 18 of 18 3R16 Fac Scope (Ipe0086871).Xls