Text
Tennessee Valley Authority, Post Office Box 2000, Spring City, Tennessee 37381-2000 January 17, 2012 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Watts Bar Nuclear Plant, Unit 2 NRC Docket No. 50-391
Subject:
Watts Bar Nuclear Plant (WBN) Unit 2 - Submittal of Pre-op Test Instruction The following approved WBN Unit 2 Pre-op Test Instruction (PTI) is enclosed:
PTI NUMBER Rev.
TITLE 2-PTI-030L-01 0
Containment Building Temperature Survey If you have any questions, please contact Pete Olson at (423) 365-3294.
Edwin E. Freeman Watts Bar Unit 2 Completions Manager Enclosure cc (Enclosure):
U. S. Nuclear Regulatory Commission Region II Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, Georgia 30303-1257 NRC Resident Inspector Unit 2 Watts Bar Nuclear Plant 1260 Nuclear Plant Road Spring City, Tennessee 37381 ti2~
WATTS BAR NUCLEAR PLANT UNIT 2 PREOPERATIONAL TEST TITLE:
Containment Building Temperature Survey Instruction No: 2-PTI-030L-01 Revision No:
0000 PREPARED BY:
Keith Jones I
"Z--
DATE: q-t-Lf PRINT NAME / SIGNATURE REVIEWED. BY:
Sam Linainfelter DATE: 2Z L.
PRINT NAME I SIGNATd(
INSTRUCTION APPROVAL JTG MEETING No:
2-12-o0 JTG CHAIRMA DATE: _________,
APPROVED BY:
DATE:
PREOPERATIONAL STARTUP MANAGER TEST RESULTS APPROVAL JTG MEETING No:
JTG CHAIRMAN:
DATE:
APPROVED BY:
DATE:
PREOPERATIONAL STARTUP MANAGER SMP-8.0 R7 Administration of Preoperational Test instructions, Appendix B
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 2 of 109 Revision Log Revision Affected or Change Effective Page Number Date Numbers Description of RevisionlChange 0000
/,..
ALL This procedure written using the Unit 1
//-
PTI-030-01 Rev 0 as a guide.
Table of Contents 1.0 INTRO DUCTIO N...................................................................................................
6 1.1 Test Objectives 6
1.2 Scope 6
2.0 REFERENCES
7 2.1 Performance References 7
2.2 Developmental References 7
3.0 PRECAUTIONS AND LIMITATIONS.....................................................................
10 4.0 PREREQUISITE ACTIONS....................................................................................
13 4.1 P re lim ina ry A ctions................................................................................................
.. 13 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies...................... 17 4.3 Field P reparations................................................................................................
.. 20 4.4 A pprovals and Notifications....................................................................................
25 5.0 ACCEPTANCE CRITERIA....................................................................................
26 6.0 PER FO R M A N C E........................................................................................................
28 6.1 Upper Compartment Air Mass Temperature...........................................................
29 6.1.1 Upper Com partment Coolers 2A, 2B, 2C.......................................................
29 6.1.2 Upper Compartment Coolers 2A, 2B, 2D..................................................
31 6.1.3 Upper Compartment Coolers 2A, 2C, 2D..................................................
33 6.1.4 Upper Compartment Coolers 2B, 2C, 2D..................................................
35 6.2 Lower Compartment Air Mass Temperature...........................................................
37 6.2.1 Lower Compartment Coolers 2A-A, 2B-B, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air Conditioning Train 2A................ 37 6.2.2 Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A................ 39 6.2.3 Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning T ra in 2 B..................................................................................................
.. 4 1
Table of Contents (continued) 6.2.4 Lower Compartment Coolers 2B-B, 2C-A, 2D-B CRDM Coolers 2B-B, 2D-B Incore Instrument Room Air Conditioning Train 2B........................................................
......... 43 POST PERFORMANCE ACTIVITY.......................................................................
45 R E C O R D S..................................................................................................................
46 7.0 8.0 Appendix A:
Appendix B:
Appendix C:
Appendix D:
Appendix E:
Appendix F:
Appendix G:
Appendix H:
Data Sheet 1:
Data Sheet 2:
Data Sheet 3:
Data Sheet 4:
Data Sheet 5:
Data Sheet 6:
TEST PROCEDURES/INSTRUCTIONS REFERENCE R EV IEW.................................................................................................
47 TEMPORARY CONDITION LOG...........................................................
49 PERMANENT PLANT INSTRUMENTATION LOG................................
50 IC S Points.............................................................................................
56 ERCW Flow and Temperature M&TE.................................................
59 Containment and Divider Barrier Boundary......................................
64 Lower Compartment Temperature Survey Cooler Alignments (Section 6.2)......................................................................
66 Weighted Average Containment Temperatures - ICS Out of S ervice..............................................................................................
68 Upper Compartment Temperature Survey - Subsection 6.1.1.......................................................................................................
.. 73
- Upper Compartment Temperature Survey - Subsection 6.1.2.....................................................................................................
7 5 Upper Compartment Temperature Survey - Subsection 6.1.3.....................................................................................................
77 Upper Compartment Temperature Survey - Subsection 6.1.4.....................................................................................................
79 Lower Compartment Temperature Survey - Subsection 6.2.1............................................................................................................
8 1 Lower Compartment Temperature Survey - Subsection 6.2.2.....................................................................................................
86
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 5 of 109 Data Sheet 7:
Data Sheet 8:
Data Sheet 9:
Data Sheet 10:
Table of Contents (continued)
Lower Compartment Temperature Survey - Subsection 6.2.3.....................................................................................................
9 1 Lower Compartment Temperature Survey - Subsection 6.2.4.....................................................................................................
96 Upper Compartment Air Temperature Thermocouple M easurem ents.........................................................................................
101 Lower Compartment Air Temperature Thermocouple M easurem ents.........................................................................................
103 Containment Air Cooling Equipment Locations..................................
107 Table 1:
2-PTI-030L-01 Rev. 0000 Page 6 of 109 Date 1.0
1.1 INTRODUCTION
Test Objectives To demonstrate the capability of the Containment Air Cooling System to provide proper cooling of the following:
Upper and Lower Containment general spaces Incore Instrument Room 1.2 Scope NOTE This test is performed during the portion of Hot Functional Testing (HFT) at which the Reactor Coolant System is at Normal Operating Temperature (NOT) and Normal Operating Pressure (NOP).
The test demonstrates that:
A.
The Upper Compartment Cooling (UCC) units will maintain design temperatures in the Upper Containment areas.
B.
The Lower Compartment Cooling (LCC) units, in conjunction with Control Rod Drive Mechanism (CRDM) Cooling units, will maintain design temperatures in the Lower Containment areas.
C.
The Incore Instrument Room Air Conditioning (IIRAC) units will maintain design temperatures in the Incore Instrument Room.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 7 of 109 Date
2.0 REFERENCES
2.1 Performance References A. SMP-9.0, Conduct of Test B.
2-PTI-068-01, HFT - Heatup and Cooldown 2.2 Developmental References A.
Final Safety Analysis Report, Amendment 107
- 1.
Section 9.4.7, Containment Air Cooling System
- 2.
Table 14.2-1, Sheets 38 & 39, Containment Ventilation System Test Summary B.
Drawings:
- 1.
Flow Diagrams
- a.
2-47W866-1, Rev 2, HEATING AND VENTILATION AIR FLOW DRA52841-02, Rev 0
- b.
2-47W865-5, Rev 0, AIR CONDITIONING CHILLED WATER
- c.
2-47W845-2, Rev 3, ESSENTIAL RAW COOLING WATER SYSTEM
- d.
2-47W845-3, Rev 5, ESSENTIAL RAW COOLING WATER SYSTEM
- 2.
Logic/Control
- a.
2-47W610-30-2, Rev 1, CONTROL DIAGRAM VENTILATION SYSTEM
- b.
2-47W610-31-5, Rev 3, CONTROL DIAGRAM AIR CONDITIONING SYSTEM
Date 2.2 Developmental References (continued)
- 3.
Electrical
- a.
45N2616-10, Rev 3, THERMOCOUPLES & RTD'S CONNECTION DIAGRAMS DRA 52322-184, Rev 0
- b.
2-47A615-0, Rev 1, INTEGRATED COMPUTER SYSTEM TERMINATIONS AND I/O LIST (Pages 18, 19, 28)
- c.
2-45W2697-14-4, Rev 0, INTEGRATED COMPUTER SYSTEM DAQ.
PANEL 2-R104 CONNECTION DIAGRAM
- d.
2-45W2697-14-8, Rev 0, INTEGRATED COMPUTER SYSTEM DAQ.
PANEL 2-R104 CONNECTION DIAGRAM
- e.
2-45W2697-54-1, Rev 0, INTEGRATED COMPUTER SYSTEM DAQ.
PANEL 2-R1 11 CONNECTION DIAGRAM C.
Documents
- 1.
WBN2-30RB-4002, Rev 1, Reactor Building Ventilation System
- 2.
2-T-30-21 0, Rev 0, Containment Mass Air Temperature Sensors
- 3.
Unit 2 Technical Specifications (Draft)
- a.
Section 3.6.5, Containment Air Temperature
- 4.
2-TSD-30L-1, Rev 0, HFT Containment Building Temperature Survey
- 5.
2-PTI-067-02-A, Rev 0, ERCW System Flow Balance - Train A
- 6.
2-PTI-067-02-B, Rev 0, ERCW System Flow Balance - Train B
- 7.
SSD-2-LPT-67-84, Rev 0, Lower Cntmt Cooler A Temp.
- 8.
SSD-2-LPT-67-92, Rev 0, Lower Cntmt Cooler C Temp
- 9.
SSD-2-LPT-67-1 00, Rev 0, Lower Cntmt Cooler B Temp
- 10. SSD-2-LPT-67-108, Rev 0, Lower Cntmt Cooler D Temp
Date 2.2 Developmental References (continued)
- 11. SSD-2-LPT-67-85, Rev 0, Control Rod Drive Vent Cooler A Temp
- 12. SSD-2-LPT-67-93, Rev 0, Control Rod Drive Vent Cooler C Temp
- 13. SSD-2-LPT-67-1 01, Rev 0, Control Rod Drive Vent Cooler B Temp
- 14. SSD-2-LPT-67-109, Rev 0, Control Rod Drive Vent Cooler D Temp
- 15. SSD-2-LPT-67-129, Rev 0, Upper Cntmt Vent Cooler A Temp
- 16. SSD-2-LPT-67-132, Rev 0, Upper Cntmt Vent Cooler C Temp
- 17. SSD-2-LPT-67-137, Rev 0, Upper Cntmt Vent Cooler B Temp
- 18. SSD-2-LPT-67-140, Rev 0, Upper Cntmt Vent Cooler D Temp
Date 3.0 PRECAUTIONS AND LIMITATIONS A.
Standard precautions shall be followed for working around energized electrical equipment in accordance with TVA Safety Procedure 1021.
B. Steps may be repeated if all components cannot be tested in a step. However, if the test has been exited, prerequisite steps must be re-verified and a Chronological Test Log (CTL) entry made.
C.
Discrepancies between component ID tags and the description in a procedure/instruction if the UNIDs match, exclusive of place keeping zeros and train designators (e.g. 2-HS-31-468 vs. 2-HS-031-0468) and the noun description is sufficient to identify the component. This condition does not require a Test Deficiency Notice (TDN) in accordance with SMP-14.0. If the component label needs to be changed, a Tag Request Form (TR Card) should be processed in accordance with TI-12.14. Make an entry in the CTL and continue testing.
D.
IF/THEN steps may be marked N/A if stated condition does not exist.
E.
All open problems are to be tracked by a corrective action document and entered on the appropriate system punch list.
F.
Problems identified during the test shall be annotated on the CTL, including a description of the problem, the procedure step when/where the problem was identified, corrective action steps taken to resolve the problem, and the number of the corrective action document, if one was required.
G.
Observe all Radiation Protection (RP) requirements with working in or near contaminated areas.
H. Ensure there are no adverse effects to the operation of Unit 1 structures, systems, or components.
- 1.
Special precautions may be required to prevent heat stress due to high temperature and humidity in some test areas. Follow heat stress precautions in accordance with TVA Safety Procedure 806 and the Site Safety Department.
J.
Access to Containment will be controlled by applicable procedures independent of this test procedure.
Date 3.0 PRECAUTIONS AND LIMITATIONS (continued)
K. The Containment and Divider Barrier Boundary as listed in Appendix F should be maintained. Temporary means of isolation to simulate closed containment conditions is permissible including the use of plastic/plywood sheeting utilizing appropriate site procedures. A CTL entry and/or Appendix F entry shall be made to clarify any significant change of condition.
L.
CRDM Cooler fans could create a local personnel hazard due to high noise levels and high air velocity. Double hearing protection (ear plugs and ear covers) is required when near the operating CRDM Cooler fans.
M. At least one CRDM Cooler per paired set shall be in operation, and remain in service, when air temperatures at the coil intake exceed 160°F as indicated by computer point Ti 104A and/or T1 105A. Test personnel shall notify the Control Room when this condition is observed and make a CTL entry of that notification and the personnel notified.
N. A minimum of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> is required to elapse (with the specified coolers in operation) between performing the first cooler alignment and collecting the first set of data in both Section 6.1 and Section 6.2. A minimum of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> is required between subsequent sets of data within each Subsection. A minimum of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> is required between subsequent Subsections. The Test Engineer may obtain and record additional data during the test.
- 0. The Unit Supervisor may, at their discretion, provide fresh air and exhaust air using the Containment Purge System; this should be accomplished prior to the 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> stabilization period preceding data collection. A CTL entry shall be made if purging occurs within the 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> prior to data collection start, during a data collection period, or during the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> period between data sets.
Containment Purge valves should be closed during data collection.
P.
This test will be performed at conditions that mimic normal operating conditions.
The ERCW Temperature Control Valve setpoints are controlled by Operations and may not exceed 1 10OF (UCCs) or 120OF (LCCs, CRDM Coolers) in accordance with their Plant Setpoint & Scaling Documents Q.
Upper Compartment Cooler, Lower Compartment Cooler, and CRDM Cooler control switches in the Main Control Room may NOT be placed in PULL A-P AUTO.
R.
The test data from each Subsection will be reviewed by the designated Test Engineer for accuracy and completeness prior to making data available to Engineering. A review and evaluation of test data by Engineering shall be performed for each Subsection to ensure adequate data has been obtained and to request any additional test data.
Date 3.0 PRECAUTIONS AND LIMITATIONS (continued)
S.
During the test, the lower permissible temperature of 601F is not expected to occur; however, temperatures inside Containment should be closely monitored by test personnel so that, if necessary, appropriate action may be initiated to raise the temperature to acceptable limits.
T.
If the required Integrated Computer System (ICS) points are unavailable at the time of the test, the Upper and Lower Compartment weighted-average air temperatures may be calculated using Appendix H.
Date 4.0 PREREQUISITE ACTIONS NOTE Prerequisite steps may be performed in any order, unless otherwise stated, and should be completed as close in time as practicable to the start of the instruction subsection to which they apply.
4.1 Preliminary Actions
[1]
VERIFY the test/performance copy of this Preoperational Test Instruction (PTI) is the current revision and as needed, each test person assisting in this test has the current revision.
[2]
OBTAIN copies of the applicable forms from the latest revision of SMP-9.0 AND ATTACH to this PTI for use during the performance of this PTI.
[3]
ENSURE changes to the references listed on Appendix A have been reviewed and determined NOT to adversely affect the test performance.
[4]
VERIFY current revisions and change paper for referenced drawings have been reviewed and determined NOT to adversely affect test performance, AND ATTACH documentation of the current drawing revision numbers and change papers that were reviewed to the data package.
Date 4.1 Preliminary Actions (continued)
[5]
EVALUATE open items in Watts Bar Integrated Task Equipment List (WITEL) for the following systems, AND ENSURE that they will NOT adversely affect the test performance.
A.
System 30G, Upper Compartment Coolers B.
System 30H, Lower Compartment Coolers C.
System 301, CRDM Coolers D.
System 30L, Pressure, Temperature, & Humidity Monitoring E.
System 31 B, Incore Instrument Room Air Conditioning
[6]
ENSURE required Component Testing has been completed prior to start of test for the following systems.
A.
System 30G, Upper Compartment Coolers B.
System 30H, Lower Compartment Coolers C.
System 301, CRDM Coolers D.
System 30L, Pressure, Temperature, & Humidity Monitoring E.
System 31 B, Incore Instrument Room Air Conditioning
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 15 of 109 Date 4.1 Preliminary Actions (continued)
[7]
ENSURE outstanding Design Change Notices (DCNs),
Engineering Document Construction Releases (EDCRs), or Temporary Alterations (TAs) do NOT adversely impact testing, AND ATTACH documentation of DCNs, EDCRs, and TAs that were reviewed to the data package.
A.
System 30G, Upper Compartment Coolers B.
System 30H, Lower Compartment Coolers C.
System 301, CRDM Coolers D.
System 30L, Pressure, Temperature, & Humidity Monitoring E.
System 31 B, Incore Instrument Room Air Conditioning
[8]
ENSURE the GTM-05 HVAC Air Balance packages for the following systems have been completed.
A.
System 30G, Upper Compartment Coolers B.
System 30H, Lower Compartment Coolers C.
System 301, CRDM Coolers D.
System 31 B, Incore Instrument Room Air Conditioning
[9]
ENSURE the ERCW Flow Balance is complete to the extent necessary to support test activities.
A.
Train A: 2-PTI-067-02-A B.
Train B: 2-PTI-067-02-B
[10]
ENSURE a review of outstanding Clearances has been coordinated with Unit 2 Operations for impact to the test performance, AND RECORD in Appendix B, Temporary Condition Log, if required.
Date 4.1 Preliminary Actions (continued)
[11]
VERIFY plant instruments required for test performance listed in Appendix C, Permanent Plant Instrumentation Log, have been placed in service and are within their calibration interval, AND RECORD on Appendix C.
[12]
ENSURE components contained within the boundaries of this test are under the jurisdictional control of Preoperational Startup Engineering (PSE) and/or Plant Operations.
[13]
REVIEW preventive maintenance records for equipment within the scope of this test, AND VERIFY no conditions exist that will impact test performance.
A.
System 30G, Upper Compartment Coolers B.
System 30H, Lower Compartment Coolers C.
System 301, CRDM Coolers D.
System 30L, Pressure, Temperature, & Humidity Monitoring E.
System 31B, Incore Instrument Room Air Conditioning
[14]
PERFORM a pretest walkdown on equipment to be tested to ensure no conditions exist that will impact test performance.
[15]
CONDUCT a pretest briefing with Test and Operations personnel in accordance with SMP-9.0.
[16]
ENSURE that communications are available for areas where testing is to be conducted.
Date 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies
[1]
OBTAIN the following M&TE, or equivalent, AND COMPLETE the following table:
DESCRIPTION MINIMUM RANGE REQUIRED M&TE ID CALIBRATION ACCURACY NUMBER DUE DATE Flowmeter 0-1000 gpm
+2% of reading (Ultrasonic)1 6" Sch 40S Stainless Steel Pipe Flowmeter 0-1000 gpm
+2% of reading (Ultrasonic)1 6" Sch 40S Stainless Steel Pipe Flowmeter 0-1000 gpm
+2% of reading (Ultrasonic)'
6" Sch 40S Stainless Steel Pipe Flowmeter 0-1000 gpm
+/-2% of reading (Ultrasonic)1 6" Sch 40S Stainless Steel Pipe Flowmeter 0-500 gpm (Ultrasonic) 2 3" Sch 40S Stainless Steel Pipe
+/-2% of reading Flowmeter 0-500 gpm (Ultrasonic) 2 3" Sch 40S Stainless Steel Pipe
+/-2% of reading Flowmeter 0-500 gpm
+/-2% of reading (Ultrasonic) 2 3" Sch 40S Stainless Steel Pipe Flowmeter 0-500 gpm (Ultrasonic) 2 3" Sch 40S Stainless Steel Pipe
+/-2% of reading Flowmeter 0-100 gpm
+2% of reading (Ultrasonic) 3 11/2" Sch 40S Stainless Steel Pipe Flowmeter 0-100 gpm
+/-2% of reading (Ultrasonic)3 11/2" Sch 40S Stainless Steel Pipe
+/-
Flowmeter 0-100 gpm
+2% of reading (Ultrasonic)4 2" Sch 40 Carbon Steel Pipe Flowmeter 0-100 gpm
+2% of reading (Ultrasonic) 4 2" Sch 40 Carbon Steel Pipe 1 A minimum of 3 ultrasonic flowmeters calibrated to these specifications are required to perform this test.
2 A minimum of 2 ultrasonic flowmeters calibrated to these specifications are required to perform this test.
3 A minimum of 1 ultrasonic flowmeter calibrated to these specifications is required to perform this test.
4 A minimum of 1 ultrasonic flowmeter calibrated to these specifications is required to perform this test.
1-4 (N/A the unused spaces if no additional flowmeters are available)
Date 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies (continued)
REQUIRED M&TE ID CALIBRATION DESCRIPTION MINIMUM RANGE ACRC UBR DEDT ACCURACY NUMBER DUE DATE.
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150OF
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Thermocouple 32-150°F
+/-20F (Type T)
Temperature Indicating Device 32-150OF
+/-20F (Type T Thermocouple)
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 19 of 109 Date 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies (continued)
[2]
VERIFY M&TE calibration due dates will support the completion of this test performance A.
Subsection 6.1.1 B.
Subsection 6.1.2 C.
Subsection 6.1.3 D.
Subsection 6.1.4 E.
Subsection 6.2.1 F.
Subsection 6.2.2 G.
Subsection 6.2.3 H.
Subsection 6.2.4
Date 4.3 Field Preparations
[1]
ENSURE the following systems are operational and have been placed in service to the extent necessary to perform this test:
A.
System 30F, Containment Vent Air Cleanup Units B.
System 30G, Upper Compartment Coolers C.
System 30H, Lower Compartment Coolers D.
System 301, Control Rod Drive Mechanism Coolers E.
System 30L, Pressure, Temperature & Humidity Monitoring F.
System 31 B, Incore Instrument Room Air Conditioning G.
System 55, Annunciator and Sequential Events Recording System H. System 67, Essential Raw Cooling Water I.
System 261, Integrated Computer System (ICS)
Date 4.3 Field Preparations (continued)
[2]
RECORD the status of the ICS points listed in Appendix D:
[3]
RECORD whether the minimum number of ICS points are in scan (not out of service) as follows:
A.
At least two (2) of the Group 1 Upper Containment Temperature points in scan.
A.
Subsection 6.1.1 DlYES Ol NO B.
Subsection 6.1.2 DlYES Ol NO C.
Subsection 6.1.3 DlYES Ol NO D.
Subsection 6.1.4 Dl YES Ol NO B.
At least one (1) of the Group 2 Upper Containment Temperature points in scan.
A.
Subsection 6.1.1 D YES El NO B.
Subsection 6.1.2 DYES Ol NO C.
Subsection 6.1.3 DYES El NO D.
Subsection 6.1.4 D YES El NO C.
At least one (1) of the Group 1 Lower Containment Temperature points in scan.
A.
Subsection 6.2.1 El YES Ol NO B.
Subsection 6.2.2 ElYES El NO C.
Subsection 6.2.3 El YES El NO D. Subsection 6.2.4 El YES El NO
Date 4.3 Field Preparations (continued)
D. At least one (1) of the Group 2 Lower Containment Temperature points in scan.
A.
Subsection 6.2.1 Dl YES O NO B.
Subsection 6.2.2 D YES O NO C.
Subsection 6.2.3 D YES 0 NO-D.
Subsection 6.2.4 0 YES O NO E.
At least one (1) of the Group 3 Lower Containment Temperature points in scan.
A.
Subsection 6.2.1 0 YES 0 NO B.
Subsection 6.2.2 0 YES 0 NO C.
Subsection 6.2.3 0 YES 0 NO D.
Subsection 6.2.4 0 YES El NO NOTE Installation of ultrasonic flowmeters may require insulation to be removed. Removal and subsequent reinstallation of insulation should be tracked in a separate work order.
[4]
ENSURE ultrasonic flowmeters and thermocouples are installed at the locations listed in Appendix E.
A.
Section 6.1 (thermocouples only)
B.
Subsection 6.2.1 C.
Subsection 6.2.2 D.
Subsection 6.2.3 E.
Subsection 6.2.4
[5]
[6]
PERFORM a walkdown of the Containment Boundary AND COMPLETE Appendix F
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 23 of 109 Date 4.3 Field Preparations (continued)
[7]
VERIFY via the HFT Test Engineer for 2-PTI-068-01 that the plant is at the _>557°F plateau.
A.
Section 6.1 B.
Section 6.2
[8]
PERFORM a walkdown of the Containment Building AND RECORD in the CTL the general status of the Containment Building describing those conditions which may attribute to a heat loss or gain (e.g. missing insulation, scaffolds, platforms, tenting, welding machines or acetylene torches in use, standing water, etc).
[9]
RECORD whether the Rod Control Mechanism Coils are energized or de-energized:
A.
Subsection 6.1.1 RCM Coils energized B.
Subsection 6.1.2 RCM Coils energized C.
Subsection 6.1.3 RCM Coils energized D.
Subsection 6.1.4 RCM Coils energized E.
Subsection 6.2.1 RCM Coils energized F.
Subsection 6.2.2 RCM Coils energized G.
Subsection 6.2.3 RCM Coils energized H.
Subsection 6.2.4 RCM Coils energized D YES O NO D YES ONO D YES ONO D YES O NO D YES O NO D YES O NO DYES ONO DYES ONO
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 24 of 109 Date 4.3 Field Preparations (continued)
[10]
ENSURE one Containment Vent Air Cleanup Unit is in service by performing the following:
[10.1]
ENSURE one of the following valves is open (check one) 2-ISV-30-23, CNTMT PRESS RELIEF FLTR INLET ISOL 2-ISV-30-24 CNTMT PRESS RELIEF FLTR INLET ISOL
[10.2]
ENSURE the following valves are open:
2-FCV-30-37, CNTMT LOWER COMPARTMENT PURGE EXH PRESS RELIEF 2-FCV-30-40, CNTMT LOWER COMPARTMENT PURGE EXH PRESS RELIEF
[11]
IF the Unit 2 Annulus is closed (Equipment Hatch X-1 CLOSED, Blast Doors CLOSED, and Door A78 CLOSED),
THEN ENSURE one train of Unit 2 Annulus Vacuum Fans are in service (check one).
0 2-FAN-65-77, EGTS CNTMT ANN VAC FAN 2A 0
2-FAN-65-74, EGTS CNTMT ANN VAC FAN 2B
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 25 of 109 Date 4.4 Approvals and Notifications
[1]
OBTAIN permission of the Preoperational Startup Manager to perform this test.
Preoperational Startup Manager Signature Date
[2]
OBTAIN the Unit 2 Supervisor's (US/SRO) or Shift Manager's (SM) authorization to perform this test.
US/SRO/SM Signature Date
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 26 of 109 Date 5.0 ACCEPTANCE CRITERIA A. The Upper Containment Coolers will maintain design temperatures in the Upper Containment areas as follows:
Operating Coolers Upper Compartment Weighted Average Air Temperature is greater than 62.1 0F and less than 107.90F1 UCC 2A UCC 2B 6.1.1[6]
UCC 2D Required value is 60°F to 1 10°F, reduced to 62.1 OF to 107.9°F to account for instrument inaccuracies described in NESSD 2-T-30-210.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 27 of 109 Date 5.0 ACCEPTANCE CRITERIA (continued)
B. The Lower Containment Coolers in conjunction with the CRDM Coolers (operating in Shroud Suction mode), will maintain design temperatures in the Lower Containment areas as follows:
Lower Compartment Incore Instrument Room Temperature Operating Coolers Weighted Average Air Temperature is between 62.50F and 117.5°F2 is between 63.62F and 96.4°F3 LCC 2A-A LCC 2B-B LCC 2C-A C C 2A-A 6.2.1[6]A 6.2.1[6]B CRDM Cooler 2A-A CRDM Cooler 2C-A IIRAC 2A LCC 2A-A LCC 2B-B LCC 2D-B CRDM Cooler 2A-A 6.2.2[6]A 6.2.216]B CRDM Cooler 2B-B IIRAC 2A LCC 2A-A LCC 2C-A LCC 2D-B CRDM Cooler 2C-A 6.2.3[6]A 6.2.316]B CRDM Cooler 2D-B IIRAC 2B LCC 28-B LCC 2C-A LCC 2D-B CRDM Cooler 28-B 6.2.4[6]A 6.2.416]B CRDM Cooler 2D-B IIRAC 28 2
Required value is 60'F to 120'F, reduced to 62.5°F to 117.5°F to account for instrument inaccuracies described in NESSD 2-T-30-210.
3 Required value is 60'F to 100°F, reduced to 63.61F to 96.4°F to account for instrument inaccuracies described in NESSD 2-T-30-210.
Date 6.0 PERFORMANCE NOTES
- 1)
Section 6.1 of this instruction may be performed in parallel with Section 6.2. The Subsections within Section 6.1 and 6.2 may be performed in any order at the discretion of the Test Director.
- 2)
A minimum of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> is required to elapse (with the specified coolers in operation) between performing the first cooler alignment and collecting the first set of data in both Section 6.1 and Section 6.2. A minimum of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> is required between subsequent sets of data within each Subsection. A minimum of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> is required between subsequent Subsections. The Test Engineer may obtain and record additional data during the test. The flowchart below shows the general progression of steps and waiting periods in this test within both Section 6.1 and Section 6.2.
Initial Cooler alignment (step [2]) of first Subsection to be performed I
Wait 24 IhoLu1S Collect 111 set of data Wait 1 h1oLr Collect 2 nd set of data Wait I ho1ur Collect 3Yd set of data]
- 3)
If the minimum required ICS points are Out of Service, temperature measurement may be performed using Appendix H.
- 4)
Verification of equipment status may be made either locally at the device or remotely by indication in the Main Control Room, Auxiliary Control Room, or at the breaker compartment, as applicable. See Table 1 for equipment locations.
Date 6.1 Upper Compartment Air Mass Temperature 6.1.1 Upper Compartment Coolers 2A, 2B, 2C
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and Subsection 6.1.1 have been completed.
[2]
ENSURE the Upper Compartment Coolers are aligned as follows:
A.
2-CCU-30-95, CNTMT UPPER COMPARTMENT COOLER 2A, is ON B.
2-CCU-30-97, CNTMT UPPER COMPARTMENT COOLER 2B, is ON C.
2-CCU-30-99, CNTMT UPPER COMPARTMENT COOLER 2C, is ON D. 2-CCU-30-100, CNTMT UPPER COMPARTMENT COOLER 2D, is OFF NOTE Temperature controllers for in-service UCCs may be adjusted by Operations to maintain Upper Compartment weighted-average air temperature within Tech Spec limit (60 - 11 0°F).
UCC temperature controller setpoints shall NOT be adjusted above 1 100F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification) 0 24 hrs 0 4 hrs
[4]
IF the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.1.1 in step 4.3[3]), THEN PERFORM Section 2.0 of Appendix H.
(Step 6.1.1[5] may be marked "N/A")
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 30 of 109 Date 6.1.1 Upper Compartment Coolers 2A, 2B, 2C (continued)
[51 COLLECT Upper Compartment Temperature Survey data as delineated on Data Sheet 1, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 1 (Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
[6]
RECORD the Average Upper Compartment Air Mass Temperature for Subsection 6.1.1, AND VERIFY it meets Acceptance Criteria.
Data Source: (check one) o ICS Point U9019 from Data Sheet 1 o Tup from Appendix H OF Acc Crit: 62.1°F to 107.90F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Upper Compartment Temperature Survey data collected in Subsection 6.1.1 to Engineering for their review and evaluation.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 31 of 109 Date 6.1.2 Upper Compartment Coolers 2A, 2B, 2D
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and Subsection 6.1.2 have been completed.
[2]
ENSURE the Upper Compartment Coolers are aligned as follows:
A.
2-CCU-30-95, CNTMT UPPER COMPARTMENT COOLER 2A, is ON B.
2-CCU-30-97, CNTMT UPPER COMPARTMENT COOLER 2B, is ON C.
2-CCU-30-99, CNTMT UPPER COMPARTMENT COOLER 2C, is OFF D.
2-CCU-30-100, CNTMT UPPER COMPARTMENT COOLER 2D, is ON NOTE Temperature controllers for in-service UCCs may be adjusted by Operations to maintain Upper Compartment weighted-average air temperature within Tech Spec limit (60 - 11 0°F).
UCC temperature controller setpoints shall NOT be adjusted above 1 100F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification)
[124 hrs 0 4 hrs
[4]
IF the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.1.2 in step 4.3[3]), THEN PERFORM Section 2.0 of Appendix H.
(Step 6.1.2[5] may be marked "N/A")
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 32 of 109 Date 6.1.2 Upper Compartment Coolers 2A, 2B, 2D (continued)
[5]
COLLECT Upper Compartment Temperature Survey data as delineated on Data Sheet 2, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 2 (Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
[6]
RECORD the Average Upper Compartment Air Mass Temperature for Subsection 6.1.2, AND VERIFY it meets Acceptance Criteria.
Data Source: (check one) o ICS Point U9019 from Data Sheet 2 o Tup from Appendix H Acc Crit: 62.1OF to 107.91F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Upper Compartment Temperature Survey data collected in Subsection 6.1.2 to Engineering for their review and evaluation.
Date 6.1.3 Upper Compartment Coolers 2A, 2C, 2D
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and Subsection 6.1.3 have been completed.
[2]
ENSURE the Upper Compartment Coolers are aligned as follows:
A.
2-CCU-30-95, CNTMT UPPER COMPARTMENT COOLER 2A, is ON B.
2-CCU-30-97, CNTMT UPPER COMPARTMENT COOLER 2B, is OFF C.
2-CCU-30-99, CNTMT UPPER COMPARTMENT COOLER 2C, is ON D.
2-CCU-30-100, CNTMT UPPER COMPARTMENT COOLER 2D, is ON NOTE Temperature controllers for in-service UCCs may be adjusted by Operations to maintain Upper Compartment weighted-average air temperature within Tech Spec limit (60 - 11 0°F).
UCC temperature controller setpoints shall NOT be adjusted above 1 100F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification) 0 24 hrs 0 4 hrs
[4]
IF the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.1.3 in step 4.3[3]), THEN PERFORM Section 2.0 of Appendix H.
(Step 6.1.3[5] may be marked "N/A")
Date 6.1.3 Upper Compartment Coolers 2A, 2C, 2D (continued)
[5]
COLLECT Upper Compartment Temperature Survey data as delineated on Data Sheet 3, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 3 (Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
[6]
RECORD the Average Upper Compartment Air Mass Temperature for Subsection 6.1.3, AND VERIFY it meets Acceptance Criteria.
Data Source: (check one) o ICS Point U9019 from Data Sheet 3 o Tup from Appendix H OF Acc Crit: 62.1IF to 107.91F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Upper Compartment Temperature Survey data collected in Subsection 6.1.3 to Engineering for their review and evaluation.
Date 6.1.4 Upper Compartment Coolers 2B, 2C, 2D
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and Subsection 6.1.4 have been completed.
[2]
ENSURE the Upper Compartment Coolers are aligned as follows:
A.
2-CCU-30-95, CNTMT UPPER COMPARTMENT COOLER 2A, is OFF B.
2-CCU-30-97, CNTMT UPPER COMPARTMENT COOLER 2B, is ON C.
2-CCU-30-99, CNTMT UPPER COMPARTMENT COOLER 2C, is ON D.
2-CCU-30-100, CNTMT UPPER COMPARTMENT COOLER 2D, is ON NOTE Temperature controllers for in-service UCCs may be adjusted by Operations to maintain Upper Compartment weighted-average air temperature within Tech Spec limit (60 - 11 0°F).
UCC temperature controller setpoints shall NOT be adjusted above 11 0°F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification) 0 24 hrs 0 4 hrs
[4]
F the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.1.4 in step 4.3[3]), THEN PERFORM Section 2.0 of Appendix H.
(Step 6.1.4[5] may be marked "N/A")
Date 6.1.4 Upper Compartment Coolers 2B, 2C, 2D (continued)
[5]
COLLECT Upper Compartment Temperature Survey data as delineated on Data Sheet 4, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 4.
(Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
[6]
RECORD the Average Upper Compartment Air Mass Temperature for Subsection 6.1.4, AND VERIFY it meets Acceptance Criteria.
Data Source: (check one) o ICS Point U9019 from Data Sheet 4 o Tup from Appendix H OF Acc Crit: 62.1°F to 107.91F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Upper Compartment Temperature Survey data collected in Subsection 6.1.4 to Engineering for their review and evaluation.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 37 of 109 Date 6.2 Lower Compartment Air Mass Temperature 6.2.1 Lower Compartment Coolers 2A-A, 2B-B, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air Conditioning Train 2A
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.2 and Subsection 6.2.1 have been completed.
[2]
ENSURE the various coolers in Lower Containment are aligned in accordance with Appendix G for Subsection 6.2.1.
NOTE Temperature controllers for in-service LCCs and CRDM Coolers may be adjusted by Operations to maintain Lower Compartment weighted-average air temperature within Tech Spec limit (60 - 1201F). LCC and CRDM Cooler temperature controller setpoints shall NOT be adjusted above 120 0F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification) 0 24 hrs 0 4 hrs
[4]
IF the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.2.1 in step 4.3[3]), THEN PERFORM Section 3.0 of Appendix H.
(Step 6.2.1[5] may be marked "N/A")
[5]
COLLECT Lower Compartment Temperature Survey data as delineated on Data Sheet 5, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 5.
(Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
Date 6.2.1 Lower Compartment Coolers 2A-A, 2B-B, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air-Conditioning Train 2A (continued)
[6]
RECORD the following Lower Compartment Temperature Data for Subsection 6.2.1, AND VERIFY they meet Acceptance Criteria.
A.
Average Lower Compartment Air Mass Temperature Data Source (check one)
[I ICS Point U9020 from Data Sheet 5 O TLOW from Appendix H OF Acc Crit: 62.5°F to 117.5°F B.
Incore Instrument Room Temperature:
Data Source (check one) o ICS Point T1 029A from Data Sheet 5 O 2-TE-30-21 OAD from Appendix H OF Acc Crit: 63.60F to 96.4 0F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Lower Compartment Temperature Survey data collected in Subsection 6.2.1 to Engineering for their review and evaluation.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 39 of 109 Date 6.2.2 Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.2 and Subsection 6.2.2 have been completed.
[2]
ENSURE the various coolers in Lower Containment are aligned in accordance with Appendix G for Subsection 6.2.2.
NOTE Temperature controllers for in-service LCCs and CRDM Coolers may be adjusted by Operations to maintain Lower Compartment weighted-average air temperature within Tech Spec limit (60 - 120 0F). LCC and CRDM Cooler temperature controller setpoints shall NOT be adjusted above 120 0F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification) 0 24 hrs 0 4 hrs
[4]
IF the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.2.2 in step 4.3[3]), THEN PERFORM Section 3.0 of Appendix H.
(Step 6.2.2[5] may be marked "N/A")
[5]
COLLECT Lower Compartment Temperature Survey data as delineated on Data Sheet 6, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 6.
(Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
Date 6.2.2 Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A (continued)
[6]
RECORD the following Lower Compartment Temperature Data for Subsection 6.2.2, AND VERIFY they meet Acceptance Criteria.
A.
Average Lower Compartment Air Mass Temperature Data Source (check one) o ICS Point U9020 from Data Sheet 6 o TLOW from Appendix H OF Acc Crit: 62.5°F to 11 7.50F B.
Incore Instrument Room Temperature:
Data Source (check one) o ICS Point T1 029A from Data Sheet 6 o 2-TE-30-21OAD from Appendix H OF Acc Crit: 63.61F to 96.4 0F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Lower Compartment Temperature Survey data collected in Subsection 6.2.2 to Engineering for their review and evaluation.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 41 of 109 Date 6.2.3 Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning Train 2B
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.2 and Subsection 6.2.3 have been completed.
[2]
ENSURE the various coolers in Lower Containment are aligned in accordance with Appendix G for Subsection 6.2.3.
NOTE Temperature controllers for in-service LCCs and CRDM Coolers may be adjusted by Operations to maintain Lower Compartment weighted-average air temperature within Tech Spec limit (60 - 1200F). LCC and CRDM Cooler temperature controller setpoints shall NOT be adjusted above 1201F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification) 0 24 hrs 0 4 hrs
[4]
IF the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.2.3 in step 4.3[3]), THEN PERFORM Section 3.0 of Appendix H.
(Step 6.2.3[5] may be marked "N/A")
[5]
COLLECT Lower Compartment Temperature Survey data as delineated on Data Sheet 7, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 7.
(Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 42 of 109 Date 6.2.3 Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning Train 2B (continued)
[6]
RECORD the following Lower Compartment Temperature Data for Subsection 6.2.3, AND VERIFY they meet Acceptance Criteria.
A.
Average Lower Compartment Air Mass Temperature Data Source (check one)
" ICS Point U9020 from Data Sheet 7 0 TLOW from Appendix H OF Acc Crit: 62.51F to 117.50F B.
Incore Instrument Room Temperature:
Data Source (check one)
O ICS Point Ti 029A from Data Sheet 7 O 2-TE-30-21OAD from Appendix H OF Acc Crit: 63.6°F to 96.40F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Lower Compartment Temperature Survey data collected in Subsection 6.2.3 to Engineering for their review and evaluation.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 43 of 109 Date 6.2.4 Lower Compartment Coolers 2B-B, 2C-A, 2D-B CRDM Coolers 2B-B, 2D-B Incore Instrument Room Air Conditioning Train 2B
[1]
ENSURE all prerequisites listed in Section 4.0 for Section 6.2 and Subsection 6.2.4 have been completed.
[2]
ENSURE the various coolers in Lower Containment are aligned in accordance with Appendix G for Subsection 6.2.4.
NOTE Temperature controllers for in-service LCCs and CRDM Coolers may be adjusted by Operations to maintain Lower Compartment weighted-average air temperature within Tech Spec limit (60 - 120"F). LCC and CRDM Cooler temperature controller setpoints shall NOT be adjusted above 1201F.
[3]
VERIFY the required minimum time has elapsed (with the specified coolers in operation) before collecting data.
(See Note 2 at the beginning of Section 6.0 for clarification) 0 24 hrs 0 4 hrs
[4]
IF the minimum required ICS points are out of service
("NO" selected for any of the items pertaining to Subsection 6.2.4 in step 4.3[3]), THEN PERFORM Section 3.0 of Appendix H.
(Step 6.2.4[5] may be marked "N/A")
[5]
COLLECT Lower Compartment Temperature Survey data as delineated on Data Sheet 8, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 8.
(Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 44 of 109 Date 6.2.4 Lower Compartment Coolers 2B-B, 2C-A, 2D-B CRDM Coolers 2B-B, 2D-B Incore Instrument Room Air Conditioning Train 2B (continued)
[6]
RECORD the following Lower Compartment Temperature Data for Subsection 6.2.4, AND VERIFY they meet Acceptance Criteria.
A.
Average Lower Compartment Air Mass Temperature Data Source (check one) o ICS Point U9020 from Data Sheet 8 o TLOW from Appendix H OF Acc Crit: 62.50F to 11 7.50F I
B.
Incore Instrument Room Temperature:
Data Source (check one) o ICS Point T1 029A from Data Sheet 8 o 2-TE-30-21OAD from Appendix H OF Acc Crit: 63.6 0F to 96.40F NOTE Include a copy of all applicable sections of the CTL, Data Sheets, and any other pertinent test documentation in the following step.
[7]
DELIVER a copy of the Lower Compartment Temperature Survey data collected in Subsection 6.2.4 to Engineering for their review and evaluation.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 45 of 109 Date 7.0 POST PERFORMANCE ACTIVITY
[1]
VERIFY Engineering has reviewed and evaluated each Subsection's test data to the extent necessary and any request for additional data has been addressed, AND ATTACH copies of Engineering concurrence for each Subsection to the data package.
A.
Subsection 6.1.1 B.
Subsection 6.1.2 C.
Subsection 6.1.3 D.
Subsection 6.1.4 E.
Subsection 6.2.1 F.
Subsection 6.2.2 G.
Subsection 6.2.3 H.
Subsection 6.2.4
[2]
ENSURE ultrasonic flowmeters and thermocouples listed in Appendix E have been removed.
[3]
ENSURE any insulation removed to support installation of the ultrasonic flowmeters has been reinstalled.
WO NOTE The plant equipment used to verify acceptance criteria are thermocouples and cannot be calibrated. Their computer points are software calibration only. Post-test calibration of these instruments is not necessary and will not be performed.
[4]
NOTIFY the Unit 2 US/SRO of the test completion and system alignment and that the Containment Air Cooling System may be aligned as needed to support HFT.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 46 of 1.09 Date 8.0 RECORDS A.
QA Records Completed Test Package B.
Non-QA Records None
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 47 of 109 Appendix A (Page 1 of 2)
TEST PROCEDURES/INSTRUCTIONS REFERENCE REVIEW Date NOTES
- 1)
Additional copies of this table may be made as necessary
- 2)
Initial and date indicates review has been completed for impact PROCEDURE/
IMPACT INITIAL AND DATE.
INSTRUCTION Yes/No (N/A for no change) 2-TSD-30L-1 FSAR Section 9.4.7 Table 14.2-1 Sh 38 & 39 Unit 2 Tech Specs Section 3.6.5 2-PTI-067-02-A 2-PTI-067-02-B WBN2-30RB-4002 2-T-30-2 10 SSD-2-LPT-67-84 SSD-2-LPT-67-92 SSD-2-LPT-67-100 SSD-2-LPT-67-108 SSD-2-LPT-67-85 SSD-2-LPT-67-93 SSD-2-LPT-67-101 SSD-2-LPT-67-109
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 48 of 109 Appendix A (Page 2 of 2)
TEST PROCEDURES/INSTRUCTIONS REFERENCE REVIEW Date PROCEDURE/
REVISION/CHANGES IMPACT INITIAL AND DATE.
INSTRUCTION Yes/No (N/A for no change)
SSD-2-LPT-67-129 SSD-2-LPT-67-132 SSD-2-LPT-67-137 SSD-2-LPT-67-140
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 49 of 109 Appendix B (Page 1 of 1)
TEMPORARY CONDITION LOG Date NOTES
- 1)
Additional copies of this table may be made as necessary
- 2)
These steps will be N/A'd if no temporary condition existed.
ITEM TEMPORARY CONDITION PERFORMED RETURNED TO NORMAL No.
DESCRIPTION Step Performed By/Date Step Returned By/Date No.
CV By/Date No.
CV By/Date
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 50 of 109 Appendix C (Page 1 of 6)
PERMANENT PLANT INSTRUMENTATION LOG Date INSTRUMENT FILLED AND PLACED IN USED FOR POST-TEST CALIBRATION QUANTITATIVE POST-TEST CAL IBATIO2 ORVNE' SERVICE' 2
ACCEPTABLE INSTRUMENT CAL DUE DATE VENTED ACC CRIT DATE INITIAL2DATE LOOP #
INIT/DATE INIT/DATE YES NO 2-TE-30-21 OA N/A YES N/A3 N/A3 2-TE-30-210B N/A YES N/A3 N/A3 2-TE-30-21 OC N/A YES N/A3 N/A3 2-TE-30-21 0D N/A YES N/A3 N/A3 2-TE-30-21 OE N/A YES N/A3 N/A3 2-TE-30-21 OF N/A YES N/A3 N/A3 2-TE-30-21 OG N/A NO N/A N/A 2-TE-30-21 OH N/A NO N/A N/A 2-TE-30-21 01 N/A NO N/A N/A 2-TE-30-21 OJ N/A NO N/A N/A 2-TE-30-21 OK N/A NO N/A N/A 2-TE-30-210L N/A NO N/A N/A 2-TE-30-210M N/A NO N/A N/A 2-TE-30-21 ON N/A NO N/A N/A 2-TE-30-21 00 N/A YES N/A3 N/A3 2-TE-30-21 OP N/A YES N/A3 N/A 3 2-TE-30-21 0Q N/A YES N/A3 N/A3 2-TE-30-21OR N/A YES N/A3 N/A3
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 51 of 109 Appendix C (Page 2 of 6)
PERMANENT PLANT INSTRUMENTATION LOG Date INSTRUMENT FILLED AND PLACED IN USED FOR POST-TEST CALIBRATION EQUANTITATIVE POST-TEST CAL IRAT2 OR CAL DUE DATE VENTED1 SERVICE1 ACC CRITATIV PO-TE2 C INSTRUMENT ADATE INITIAL/DATE LOOP #
INIT/DATE INIT/DATE YES NO 2-TE-30-21 OS N/A YES N/A3 N/A3 2-TE-30-210T N/A YES N/A3 N/A 3 2-TE-30-21OU N/A YES N/A3 N/A3 2-TE-30-210V N/A YES N/A3 N/A3 2-TE-30-210W N/A YES N/A3 N/A3 2-TE-30-21 OX N/A YES N/A3 N/A3 2-TE-30-21 OY N/A YES N/A3 N/A3 2-TE-30-21 OZ N/A YES N/A3 N/A3 2-TE-30-21 OAA N/A YES N/A3 N/A3 2-TE-30-21OAB N/A YES N/A3 N/A3 2-TE-30-21 OAC N/A YES N/A3 N/A3 2-TE-30-21 OAD N/A YES N/A3 N/A3 2-TE-30-21 OAE N/A YES N/A3 N/A3 2-TE-30-21 OAF N/A YES N/A3 N/A3 2-TE-30-21OAG N/A YES N/A3 N/A3 2-TE-30-210AH N/A YES N/A3 N/A3
Appendix C (Page 3 of 6)
PERMANENT PLANT INSTRUMENTATION LOG Date INSTRUMENT FILLED AND PLACED IN USED FOR POST-TEST CALIBRATION OR CAL DUE DATE VENTED' SERVICE' QUANTITATIVE POST-TEST CAL ACCEPTABLE 2 INSTRUMENT ACC CRIT DATE2 I NITIAL/DATE LOOP #
INIT/DATE INIT/DATE YES NO
- 2-TE-30-211A N/A NO N/A N/A 2-TE-30-21 1 B N/A NO N/A N/A 2-TE-30-21 1C N/A NO N/A N/A 2-TE-30-211D N/A NO N/A N/A 2-TE-30-21 1 E N/A NO N/A N/A 2-TE-30-21 1 F N/A NO N/A N/A 2-TE-30-21 1 G N/A NO N/A N/A 2-TE-30-21 1 H N/A NO N/A N/A 2-TE-30-21 11 N/A NO N/A N/A 2-TE-30-21 1J N/A NO N/A N/A 2-TE-30-21 1K N/A NO N/A N/A 2-TE-30-211L N/A NO N/A N/A 2-TE-30-21 1 M N/A NO N/A N/A 2-TE-30-211N Nh/
NO N/A N/A 2-TE-30-2110 N/A NO N/A N/A 2-TE-30-211P N/A NO N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 53 of 109 Appendix C (Page 4 of 6)
PERMANENT PLANT INSTRUMENTATION LOG Date INSTRUMENT FILLED AND PLACED IN USED FOR OR 1
QUANTITATIVE POST-TEST CALIBREPATION OR CAL DUE DATE VENTED' SERVICE ACC CRIT DATE2 INSTRUMENT ACRIDTE2 ACCEPTABL INITIAL/DATE LOOP #
INIT/DATE INIT/DATE YES NO 2-TE-30-21 1 Q N/A NO N/A N/A 2-TE-30-21 1 R N/A NO N/A N/A 2-TE-30-21 1S N/A NO N/A N/A 2-TE-30-21 1T N/A NO N/A N/A 2-TE-30-21 1 U N/A NO N/A N/A 2-TE-30-21 1V N/A NO N/A N/A 2-ME-30-240 N/A NO N/A N/A 2-ME-30-241 N/A NO N/A N/A 2-LPT-31-307 N/A NO N/A N/A 2-LPT-31-328 N/A NO N/A N/A 2-TI-31-300 N/A NO N/A N/A 2-TI-31-312 N/A NO N/A N/A 2-TI-31-320 N/A NO N/A N/A 2-TI-31-333 N/A NO N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 54 of 109 Appendix C (Page 5 of 6)
PERMANENT PLANT INSTRUMENTATION LOG Date INSTRUMENT FILLED AND PLACED IN USED FOR POST-TEST CALIBRATION OR 1
QUANTITATIVE POST-TEST CAL ACCEPTABLE2 INSTRUMENT CAL DUE DATE VENTED SERVICE ACC CRIT DATE 2 INITIAL/DATE LOOP #
INIT/DATE INIT/DATE YES NO 2-LPT-67-129 N/A NO N/A N/A 2-LPT-67-137 N/A NO N/A N/A 2-LPT-67-132 N/A NO N/A N/A 2-LPT-67-140 N/A NO N/A N/A 2-LPT-67-84 N/A NO N/A N/A 2-LPT-67-92 N/A NO N/A N/A 2-LPT-67-1 00 N/A NO N/A N/A 2-LPT-67-108 N/A NO N/A N/A 2-LPT-67-85 N/A NO N/A N/A 2-LPT-67-93 N/A NO N/A N/A 2-LPT-67-1 01 N/A NO N/A N/A 2-LPT-67-109 N/A NO N/A N/A 2-LPT-67-4554 N/A NO N/A N/A 2-LPT-67-4564 N/A NO N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 55 of 109 Appendix C (Page 6 of 6)
PERMANENT PLANT INSTRUMENTATION LOG Date INSTRUMENT FILLED AND PLACED IN USED FOR POST-TEST CALIBRATION OR QUANTITATIVE POST-TEST CAL ACCEPTABLE2 INSTRUMENT CAL DUE DATE VENTED 1 SERVICE ACC CRIT DATE2 INITIA DATE LOOP #
INIT/DATE INIT/DATE YES NO 2-FI-67-263 NO N/A N/A 2-FI-67-265 NO N/A N/A 2-FI-67-267 NO N/A N/A 2-FI-67-269 NO N/A N/A 2-FI-67-332 NO N/A N/A 2-FI-67-333 NO N/A N/A 2-FI-67-334 NO N/A N/A 2-FI-67-335 NO N/A N/A 1 These items may be initialed and dated by personnel performing the task. Instrumentation not required to be filled and vented may be identified as Not Applicable. (N/A) 2 May be identified as Not Applicable (N/A) if instrument was not used to verify/record quantitative acceptance criteria data.
3 These Temperature Elements cannot be calibrated and their computer points are software calibration only. Post-test calibration of these instruments is not necessary and will not be performed 4
These instrument loops are under Unit 1 control.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 56 of 109 Appendix D (Page 1 of 3)
ICS Points Date Group ICS Point Description Point Status Initials (circle one)
Upper 1 T1000A1 CNTMT AIR TEMP AZ/EL 270/868 DOME In Scan / OOS N/A T1001A2 CNTMT TEMP 104/796 PRZ CEILG In Scan / OOS N/A T1002A2 CNTMT TEMP 0/796 SG ENCL CEILG In Scan / OOS N/A T1003A2 CNTMT TEMP 180/796 SG ENCL CEILG In Scan / OOS Lower 1 T1004A2 CNTMT TEMP 184/708 RX SHLD WALL In Scan / OOS Lower 1 T1005A2 CNTMT TEMP 0/708 RX SHLD WALL In Scan / OOS N/A T1006A CNTMT TEMP 67/708 RXN RX VSL SUPP1 In Scan / OOS N/A T1007A CNTMT TEMP 158/708 UN RX VSL SUPP2 In Scan / OOS N/A T1008A CNTMT TEMP 247/708 UN RX VSL SUPP3 In Scan / OOS N/A T1009A CNTMT TEMP 338/708 UN RX VSL SUPP4 In Scan / OOS N/A T101OA CNTMT TEMP EL719 OPP RX VSL NOZL 1 In Scan / OOS N/A T1011A CNTMT TEMP EL719 OPP RX VSL NOZL 2 In Scan / OOS N/A T1012A CNTMT TEMP EL719 OPP RX VSL NOZL 3 In Scan / OOS N/A T1013A CNTMT TEMP EL719 OPP RX VSL NOZL 4 In Scan / OOS N/A T1014A2 CNTMT TEMP 45/753 OPP REFUEL GATE In Scan / OOS Lower 1 T1015A2 CNTMT TEMP 104/726 IN PZR SUPP PLTF In Scan / OOS Upper 1 T1016A 1 CNTMT TEMP 55/809 ICE COND WALL In Scan / OOS Upper 1 T1017A1 CNTMT TEMP 235/809 ICE WALL OPP SID In Scan / OOS Upper 2 T1018A1 CNTMT TEMP 92/799 PRZR ENCL WALL In Scan / OOS Upper 2 T1019A1 CNTMT TEMP 285/766 ICE OPP PZR In Scan / OOS Upper 2 T1020Al CNTMT TEMP 180/766 SG ENCL WALL In Scan / OOS Upper 2 T1021A1 CNTMT TEMP 0/766 SG ENCL OPP SIDE In Scan / OOS
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 57 of 109 Appendix D (Page 2 of 3)
ICS Points Date Group ICS Point Description Point Status Initials (circle one)
Lower 2 T1022A2 CNTMT TEMP 126/745 ICE PLTFM RCP#2 In Scan / OOS Lower2 T1023A 2 CNTMT TEMP 309/745 ICE PLTFM RCP#4 In Scan / OOS Lower 2 T1 024A2 CNTMT TEMP 201/745 ICE PLTFM SG#3 In Scan / OOS Lower2 T1025A2 CNTMT TEMP 22/745 ICE PLTFM SG#1 In Scan / OOS N/A T1026A 2 CNTMT TEMP 90/687 SUMP In Scan / OOS Lower 3 T1027A2 CNTMT TEMP 0/723 FAN COMPT WALL In Scan / OOS Lower 3 T1 028A 2 CNTMT TEMP 180/723 FAN COMPT WALL In Scan / OOS N/A T1029A2 CNTMT TEMP 90/716 INSTR RM WALL In Scan / OOS Lower 3 T1030A2 CNTMT TEMP 40/723 ACCUM RM WALL In Scan / OOS Lower 3 T1031A2 CNTMT TEMP 140/723 ACCUM RM WALL In Scan / OOS Lower3 T1032A2 CNTMT TEMP 220/723 ACCUM RM WALL In Scan / oOS Lower 3 T1033A2 CNTMT TEMP 320/723 ACCUM RM WALL In Scan / OOS N/A T1100A CRDM COOL UNIT A-A EXHAUST In Scan / OOS N/A T1101A CRDM COOL UNIT C-C EXHAUST In Scan / OOS N/A T1 102A CRDM COOL UNIT C-A EXHAUST In Scan / OOS N/A T1 103A CRDM COOL UNIT D-A EXHAUST In Scan / OOS N/A T1 104A CRDM COOL UNIT C-A B-B INTAKE In Scan / OOS N/A T1 105A CDRM COOL UNIT A-A D-E INTAKE In Scan / OOS N/A T1110A LOWR COMPT COOL UNIT A-A EXHAUST In Scan / OOS N/A T1111A LOWR COMPT COOL UNIT CAB-B EXHAUST In Scan / OOS N/A T1112A LOWRM COO COOL UNIT C-A EXHAUST In Scan / OOS N/A Ti 11 3A LOWR COMPT COOL UNIT D-A EXHAUST In Scan / OOS N/A T1114A LOWER COMPT COOL UNIT A-A INTAKE In Scan / OOS N/A T1 115A LOWER COMPT COOL UNIT B-B INTAKE In Scan / OOS N/A T1116A LOWER COMPT COOL UNIT C-A INTAKE In Scan / OOS
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 58 of 109 Appendix D-(Page 3 of 3)
ICS Points Date Group ICS Point Description Point Status Initials (circle one)
N/A T1 11 7A LOWER COMPT COOL UNIT D-B INTAKE In Scan / OOS N/A T1118A UPPER COMPT COOL UNIT A INTAKE In Scan / OOS N/A T111 9A UPPER COMPT COOL UNIT B INTAKE In Scan / OOS N/A T1 120A UPPER COMPT COOL UNIT C INTAKE In Scan / OOS N/A T1 121A UPPER COMPT COOL UNIT D INTAKE In Scan / OOS N/A T1 122A UPPER COMPT COOL UNIT A EXHAUST In Scan / OOS N/A T1 123A UPPER COMPT COOL UNIT B EHXUAST In Scan / OOS N/A T1i124A UPPER COMPT COOL UNIT C EXHAUST In Scan / OOS N/A T1i125A UPPER COMPT COOL UNIT D EXHAUST In Scan / OOS N/A T2614A3 ERCW SUP HDR 2A TEMP In Scan / OOS N/A T2615A3 ERCW SUP HDR 2B TEMP In Scan / OOS N/A U9019 1 CNTMT UPPER CMPT AVG MASS AIR In Scan / OOS TEMP N/A U9020 2 CNTMT LOWER CMPT AVG MASS AIR T In Scan / OOS N/A Y0701A CNTMT UP-COMPARTMENT DEW PT In Scan / OOS TEMP N/A Y0702A CNTMT LOW-COMPARTMENT DEW PT In Scan / OOS TEMP 1
These ICS Points are required for performance of Section 6.1. If the minimum required points are OOS, then Appendix H may be used to determine the Upper Compartment Weighted Average Air Temperature.
2 These ICS Points are required for performance of Section 6.2. If the minimum required points are COS, then Appendix H may be used to determine the Lower Compartment Weighted Average Air Temperature.
These ICS Points are under Unit 1 control
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 59 of 109 Appendix E (Page 1 of 5)
ERCW Flow and Temperature M&TE Date Upper Compartment Air Mass Temperature - Section 6.1 Additional Removed UNID Description Location Information M&TE ID Installed 1st CV UPPER CNTMT VENT CLR A minimum range:
2-TW-67-262 DIC EPEL 802 AZ 370°215 0
DISCH TEMP 32-1501F UPPER CNTMT VENT CLR B minimum range:
2-TW-67-266 EL 802 AZ 14932-150F 2-TW-67-264 UPPER CNTMT VENTUCR C EL 802 AZ 2150 minimum range:
DISCH TEMP 32-150°F UPPER CNTMT VENT CLR D minimum range:
2-TW-67-268 DISCHEL 802 AZ 325 DISCHTEMP32-150°F
Appendix E (Page 2 of 5)
ERCW Flow and Temperature M&TE Date Lower Compartment Air Mass Temperature - Section 6.2 Additional Subsection 6.2.1 Subsection 6.2.2 Subsection 6.2.3 Subsection 6.2.4 Removed Information M&TE ID INITIALS M&TE ID INITIALS M&TE ID INITIALS M&TE ID INITIALS 1st CV EL 726 A "Sceul 0
Ultrasonic Flowmeter LOW CNTMT VENT 26" Schedule 40S near 2-FE-67-471 CLR A DISCH FLOW (S Fan R2 )
Stainless Steel Pipe Ultrasonic Flowmeter LOW CNTMT VENT EL 726 A 6" Schedule 40S near 2-FE-67-474 CLR B DISCH FLOW 159(
Stainless Steel Pipe (N Fan Rm)
Ultrasonic Flowmeter LOW CNTMT VENT EL 726 A 6" Schedule 40S near 2-FE-67-472 CLR C DISCH FLOW 201(
Stainless Steel Pipe (N Fan Rm)
Ultrasonic Flowmeter LOW CNTMT VENT EL 726 A 6" Schedule 40S near 2-FE-67-476 CLR D DISCH FLOW (S Fan R3 )
Stainless Steel Pipe LWR CNTMT VENT EL 721 AZ 90 minimum range:
CLR A DISCH TEMP (S Fan Rm)32-150'F LWR CNTMT VENT EL 721 AZ minimum range:
2-TW-67-244 CLR B DISCH TEMP 171'32-150'F (N Fan Rm)
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 61 of 109 Appendix E (Page 3 of 5)
ERCW Flow and Temperature M&TE Date Lower Compartment Air Mass Temperature - Section 6.2
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 62 of 109 Appendix E (Page 4 of 5)
ERCW Flow and Temperature M&TE Date Lower Compartment Air Mass Temperature - Section 6.2 Additional Subsection 6.2.1 Subsection 6.2.2 Subsection 6.2.3 Subsection 6.2.4 Removed Information M&TE ID INITIALS M&TE ID INITIALS M&TE ID INITIALS M&TE ID INITIALS 1st CV CONTROL ROD DR 2-TW-67-232 VENT CLR A DISCH EL 725 AZ 90 minimum range:
TEMP (S Fan Rm) 32-150°F CONTROL ROD DR EL 725 AZ 2-TW-67-246 VENT CLR B DISCH 1710 miiu5rne
- TEMP (N Fan Rm)
CONTROL ROD DR EL 725 AZ 2-TW-67-238 VENT CLR C DISCH 1870 m2iu5rne TEMP (N Fan Rm)
CONTROL ROD DR EL 725 AZ 2-TW-67-252 VENT CLR D DISCH 3510 miiu5rne TEMP (S Fan Rm)
Ultrasonic Flowmeter INSTR RM VENT Al2W /692 11/2" Schedule 40S near 2-FE-67-257 CLR A DISCH FLOW (692 Pent Stainless Steel Pipe Rm)
Ultrasonic Flowmeter INSTR RM VENT A12W/692 1V" Schedule 40S near 2-FE-67-259 CLR B DISCH FLOW (692 Pent Stainless Steel Pipe Rm)
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 63 of 109 Appendix E (Page 5 of 5)
ERCW Flow and Temperature M&TE Date Lower Compartment Air Mass Temperature - Section 6.2
Appendix F (Page 1 of 2)
Containment and Divider Barrier Boundary Date NOTES
- 1)
Record significant changes to the Containment Boundary in Remarks below.
- 2)
Temporary use of plastic sheeting and plywood to establish the Containment Boundary is acceptable.
- 3)
Additional copies of this table may be made as necessary.
Location Desired Initials Remarks Description (AZEL)
Position Equipment Hatch (X-1) 2850 / 765' CLOSED Lower Personnel Airlock (X-2A) 1620 / 716' CLOSED Upper Personnel Airlock (X-2B) 2550 / 757' CLOSED Fuel Transfer Tube (X-3) 2620 / 711' CLOSED Maintenance Port (X-37) 2650 / 771' CLOSED Thimble Tube (X-54) 900 I 740' CLOSED Ice Blowing (X-79A) 2890 / 808' CLOSED Ice Blowing (X-79B) 2900 / 808' CLOSED Maintenance Port (X-108) 2180 / 711' CLOSED Maintenance Port (X-109) 222, / 711' CLOSED Maintenance Port (X-1 17) 3000 / 758' CLOSED Layup Water Treatment (X-1 18) 2090 / 708' CLOSED Crane Wall Door (Raceway to Loop 3) 2260 I 703' CLOSED Crane Wall Door Crae al Dor314,
/ 703' CLOSED (Raceway to Loop 4)
Crane Wall Door (Incore Instr Rm to RCP 2)
Crane Wall Door (Acc Rm 4 to Lower Ice Catwalk) 3050 / 744' CLOSED Hatch (Incore Instr Rm to Raceway) 1620 / 716' CLOSED
Appendix F (Page 2 of 2)
Containment and Divider Barrier Boundary Date Location Desired Initials Remarks Description (AZ/EL)
Position Incore Instr Rm Blowout Panel 1260/ 730' CLOSED Incore Instr Rm Blowout Panel 540 / 730' CLOSED Ice Condenser Lower Inlet Doors 746' CLOSED 2-M-9 Ice Condenser End Wall 2450 / 806' CLOSED Ice Condenser End Wall 3050 / 806' CLOSED Personnel Hatch #1 (top of Pressurizer Enclosure)
Personnel Hatch #2 3050 / 757' CLOSED
("Subhatch")
East Refuel Canal Drain Plug 2720 / 714' REMOVED West Refuel Canal Drain Plug 2680 / 714' REMOVED RCP Access Plug 1 460 / 757' INSTALLED RCP Access Plug 2 1340 / 757' INSTALLED RCP Access Plug 3 2260 / 757' INSTALLED RCP Access Plug 4 3140 / 757' INSTALLED Lower Containment Access Plug 2700 / 757' INSTALLED Raceway Access Plug 1050 / 757' INSTALLED Reactor Cavity Pressure Relief 750' CLOSED Panels CRDM Missile Shields 760' INSTALLED Transfer Canal Gate Blocks 2700 / 713' INSTALLED
Appendix G (Page 1 of 2)
Lower Compartment Temperature Survey Cooler Alignments (Section 6.2)
Date Subsection 6.2.1 Subsection 6.2.2 Subsection 6.2.3 Subsection 6.2.4 UNID NOMENCLATURE STATUS I INITIALS STATUS INITIALS STATUS INITIALS STATUS INITIALS Lower Compartment Coolers CRDM Coolers & Associated Dampers 2-CLR-30-83 CRDM COOLER 2A-A ON ON OFF OFF 2-TCO-30-841 CRDM COOLER 2A-A OPEN' OPEN1 CLOSED CLOSED SHROUD SUCTION 2-TCO-30-85 CRDM COOLER 2A-A CLOSED CLOSED CLOSED CLOSED LOWER COMPARTMENT SUCT 2-CLR-30-92 CRDM COOLER 2B-B OFF ON OFF ON 2-TCO-30-93' CRDM COOLER 2B-B CLOSED OPEN' CLOSED OPEN' SHROUD SUCTION 2-TCO-30-94 CRDM COOLER 2B-B CLOSED CLOSED CLOSED CLOSED LOWER COMPARTMENT SUCT 2-CLR-30-88 CRDM COOLER 2C-A ON OFF ON OFF 2-TCO.30-89' CRDM COOLER 2C-A OPEN' CLOSED OPEN1 CLOSED SHROUD SUCTION 2-TCO30-90 CRDM COOLER 2C-A LOR COMARTN UCT9 CLOSED CLOSED CLOSED CLOSED 2-TO-3-90 LOWER COMPARTMENT SUCT 2-CLR-30-80 CRDM COOLER 2D-B OFF OFF ON ON 2-TCO-30-811 CRDM COOLER 2D-B CLOSED CLOSED OPEN' OPEN' SHROUD SUCTION 2-TCO30-82 CRDM COOLER 2D-B 2-TCO-30-82 COMPRT TUCT CLOSED CLOSED CLOSED CLOSED LOWER COMPARTMENT SUC
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 67 of 109 Appendix G (Page 2 of 2)
Lower Compartment Temperature Survey Cooler Alignments (Section 6.2)
Date Subsection 6.2.1 Subsection 6.2.2 Subsection 6.2.3 Subsection 6.2.4 UNID NOMENCLATURE F--------I STATUS IINITIALS STATUS INITIALS STATUS INITIALS STATUSTINITIALS Incore Instrument Room Air Conditioning 2-AHU-31-265 INCORE INSTRUMENT ROOM ON ON OFF OFF AIR HANDLING UNIT 2A 2-FCO-31-2632 INCORE INSTR RM AHU 2A OPEN2 OPEN2 CLOSED CLOSED DISCHARGE 2-FCO-31-2642 INCORE INSTR RM AHU 2A OPEN 2 OPEN2 CLOSED CLOSED DISCHARGE 2-CHR-31-3032 INCORE INSTR ROOM ON2 ON 2 OFF OFF CHILLER 2A 2-PMP-31-303/12 INCORE INSTR ROOM ON2 ON 2 OFF OFF CW PUMP 2A INCORE INSTRUMENT ROOM 2-AHU-31-266 IR INGTUNT 28 OFF OFF ON ON AIR HANDLING UNIT 2B 2-FCO-31-2682 INCORE INSTR RM AHU 28 CLOSED CLOSED OPEN2 OPEN2 DISCHARGE 2-FCO-31-2692 INCORE INSTR RM AHU 2B CLOSED CLOSED OPEN2 OPEN2 DISCHARGE 2-CHR-31-3242 INCORE INSTR ROOM OFF OFF ON2 ON2 CHILLER 28 2-PMP_31_324/1 2 INCORE INSTR ROOM OFF OFF ON 2 ON 2 CW PUMP 28 1
CRDM Shroud Suction Dampers are designed to automatically open if their respective Handswitch is in P AUTO and their associated CRDM Cooler starts.
2 Incore Instrument Room Air Conditioning Chiller, Pump, and Dampers are designed to automatically start/open when their associated AHU starts.
Appendix H (Page 1 of 5)
Weighted Average Containment Temperatures - ICS Out of Service Date 1.0 NOTES AND GUIDELINES A.
Additional copies of sections of this Appendix, Data Sheet 9, and Data Sheet 10 may be made as necessary.
B.
This Appendix may be used to obtain Containment Temperature data and calculate the Upper or Lower Containment weighted average air temperature if the minimum required ICS Points are Out of Service (OOS) during the performance of this instruction C.
Perform Section 2.0 for Upper Compartment Mass Air Temperature.
D.
Perform Section 3.0 for Lower Compartment Mass Air Temperature and Incore Instrument Room Temperature.
Appendix H (Page 2 of 5)
Weighted Average Containment Temperatures - ICS Out of Service Date UPPER COMPARTMENT WEIGHTED AVERAGE AIR TEMPERATURE
[1]
RECORD the Subsection number that this Appendix is being performed in:
Subsection 2.0
[2]
OBTAIN the following M&TE, or equivalent, AND COMPLETE the following table:
MINIMUM REQUIRED M&TE ID CALIBRATION RANGE ACCURACY NUMBER DUE DATE Temperature Indicating Device 40 - 1750F
+ 3.6 0F (Type T Thermocouple)
[3]
ENSURE M&TE calibration due dates will support the completion of this test performance.
NOTE Step 2.0[4] and 2.0[5] shall be performed in parallel.
[4]
MEASURE Upper Containment Temperature thermocouple temperature as delineated on Data Sheet 9, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 9.
(ENTER "OOS" for any thermocouple that is NOT indicating)
A.
Set 1 B.
Set 2 C.
Set 3
Appendix H (Page 3 of 5)
Weighted Average Containment Temperatures - ICS Out of Service Date 2.0 UPPER COMPARTMENT WEIGHTED AVERAGE AIR TEMPERATURE (continued)
[5]
COLLECT additional Upper Compartment Temperature Survey data as delineated on Data Sheet 1, 2, 3 or 4, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 1, 2, 3, or 4, as appropriate.
(Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
[6]
VERIFY the following from Data Sheet 9:
A.
At least two (2) of the Group 1 Upper Containment thermocouples NOT OOS.
B.
At least one (1) of the Group 2 Upper Containment thermocouples NOT OOS.
[7]
RECORD the Upper Compartment Air Mass Temperature (Tup) from Data Sheet 9.
Tup =
Appendix H (Page 4 of 5)
Weighted Average Containment Temperatures - ICS Out of Service Date LOWER COMPARTMENT WEIGHTED AVERAGE AIR TEMPERATURE
[1]
RECORD the Subsection number that this Appendix is being performed in:
Subsection 3.0
[2]
OBTAIN the following M&TE, or equivalent, AND COMPLETE the following table:
MINIMUM REQUIRED M&TE ID CALIBRATION RANGE ACCURACY NUMBER DUE DATE Temperature Indicating Device 40 - 175 0F
+ 3.6 0F (Type T Thermocouple)
[3]
ENSURE M&TE calibration due dates will support the completion of this test performance.
NOTE Step 3.0[4] and 3.0[5] shall be performed in parallel.
[4]
MEASURE Lower Containment Temperature thermocouple temperature as delineated on Data Sheet 10, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 10.
(ENTER "OOS" for any thermocouple that is NOT indicating)
A.
Set 1 B.
Set 2 C.
Set 3
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000
.Page 72 of 109 3.0 Appendix H (Page 5 of 5)
Weighted Average Containment Temperatures - ICS Out of Service Date LOWER COMPARTMENT WEIGHTED AVERAGE AIR TEMPERATURE (continued)
[5]
COLLECT additional Lower Compartment Temperature Survey data as delineated on Data Sheet 5, 6, 7, or 8, waiting 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> between each set of data, AND RECORD data on Data Sheet 5, 6, 7, or 8, as appropriate.
(Enter "OOS" for out of service ICS points.)
A.
Set 1 B.
Set 2 C.
Set 3
[6]
VERIFY the following from Data Sheet 10:
A.
At least one (1) of the Group 1 Lower Containment thermocouples NOT OOS.
B.
At least one (1) of the Group 2 Lower Containment thermocouples NOT OOS.
C.
At least one (1) of the Group 3 Lower Containment thermocouples NOT OOS.
[7]
RECORD the following from Data Sheet 10 A.
Lower Compartment Air Mass Temperature (TLOw).
TLOW =F B.
Incore Instrument Room Temperature (2-TE-30-210AD) 2-TE-30-21OAD =
OF
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 73 of 109 Data Sheet 1 (Page 1 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.1 Date Subsection 6.1.1: Upper Compartment Coolers 2A, 2B, 2C Upper Compartment Mass Air Temperatures UNID Location Description ICS Point Set 1 Set 2 Set 3 Average (AZ/EL) 2-TE-30-210A 2700 / 868' DOME T1000A 2-TE-30-210Q 550 / 809' ICE COND WALL T1016A 2-TE-30-210R 2350 / 809' ICE WALL OPP SID T1017A 2-TE-30-210S 920 / 766' PRZR ENCL WALL T1018A 2-TE-30-210T 2850 / 766' ICE OPP PRZR T1019A 2-TE-30-210U 180/1766' SG ENCL WALL T1020A 2-TE-30-210V, 00 / 766' SG ENCL OPP SIDE T1021A UPPER CMPT AVG MASS AIR TEMP U9019 Additional Upper Compartment Temperature Data UNID Description ICS Point Set I Set 2 Set 3 Average 2-TE-30-21 10 UPPER COMPT COOL UNIT A INTAKE T1118A 2-TE-30-21 1P UPPER COMPT COOL UNIT B INTAKE T1 119A 2-TE-30-21 1Q UPPER COMPT COOL UNIT C INTAKE T1 120A 2-TE-30-21 1 R UPPER COMPT COOL UNIT D INTAKE Ti 121A 2-TE-30-211S UPPER COMPT COOL UNIT A EXHAUST T1122A 2-TE-30-21 1T UPPER COMPT COOL UNIT B EXHAUST T1i123A 2-TE-30-211U UPPER COMPT COOL UNIT C EXHAUST T1124A 2-TE-30-21 1V UPPER COMPT COOL UNIT D EXHAUST T1125A 2-ME-30-240 CNTMT UP-COMPARTMENT DEW PT TEMP Y0701A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A Start / Stop Time & Date Data Recorded:
/
I
/
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A I
Data Sheet 1 (Page 2 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.1 Date Subsection 6.1.1: Upper Compartment Coolers 2A, 2B, 2C Additional Upper Compartment Temperature Data UNID Location Description M&TE ID Set I Set 2 Set 3 Average 2-L-329 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-263
[Al 2V / 713]
2A ERCW RET FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-332
[Al 2V / 713]
2A ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-267
[A12V / 713]
2B ERCW RET FLOW N/A (713 Pent Rm) 4 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-334
[Al 2V / 713]
2B ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-265
[Al 2V / 713]
2C ERCW RET FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-333
[Al 2V / 713]
2C ERCW SUP FLOW N/A (713 Pent Rm)
UPPER CNTMT VENT CLR 2-TW-67-262 EL 802 AZ 371 A DSCH VTEMP A DISCH TEMP 2-TW-67-266 EL 802 AZ 149, UPPER CNTMT VENT CLR B DISCH TEMP 2-T-67264EL 02 Z 250UPPER CNTMT VENT CLR 2-TW-67-264~
~~
EL82A 25 ISCH TEMP Start / Stop Time & Date Data'Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
/
I
/
N/A 4
4
.4-N/A N/A I
N/A
Data Sheet 2 (Page 1 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.2 Date Subsection 6.1.2: Upper Compartment Coolers 2A, 2B, 2D Upper Compartment Mass Air Temperatures UNID Location Description ICS Point Set 1 Set 2 Set 3 Average (AZ/EL) 2-TE-30-210A 2700 / 868' DOME T1000A 2-TE-30-210Q 550 / 809' ICE COND WALL T1016A 2-TE-30-210R 2350 / 809' ICE WALL OPP SID T1017A 2-TE-30-210S 920 / 766' PRZR ENCL WALL T1018A 2-TE-30-210T 2850 / 766' ICE OPP PRZR T1019A 2-TE-30-210U 180° / 766' SG ENCL WALL T1020A 2-TE-30-210V 00 / 766' SG ENCL OPP SIDE T1021A UPPER CMPT AVG MASS AIR TEMP U9019 Additional Upper Compartment Temperature Data UNID Description ICS Point Set I Set 2 Set 3 Average 2-TE-30-21 10 UPPER COMPT COOL UNIT A INTAKE T11 18A 2-TE-30-211P UPPER COMPT COOL UNIT B INTAKE T1119A 2-TE-30-211Q UPPER COMPT COOL UNIT C INTAKE T1120A 2-TE-30-211R UPPER COMPT COOL UNIT D INTAKE T1121A 2-TE-30-21 1S UPPER COMPT COOL UNIT A EXHAUST T1 122A 2-TE-30-21 1T UPPER COMPT COOL UNIT B EXHAUST T1 123A 2-TE-30-211U UPPER COMPT COOL UNIT C EXHAUST T1124A 2-TE-30-211V UPPER COMPT COOL UNIT D EXHAUST T1125A 2-ME-30-240 CNTMT UP-COMPARTMENT DEW PT TEMP Y0701A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A Start / Stop Time & Date Data Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
/
I I
N/A N/A N/A N/A
Data Sheet 2 (Page 2 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.2 Date Subsection 6.1.2: Upper Compartment Coolers 2A, 2B, 2D Additional Upper Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average 2-L-329 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-263
[Al 2V / 713]
2A ERCW RET FLOW N/A (713 Pent Rm) 2-FI-7-332 2-L-329 UPPER CNTMT VENT CLR N/
(713 Pent Rm) 2 RWSPFO 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-267
[Al 2V / 713]
2B ERCW SUP FLOW N/A (713 Pent Rm) 4 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-334
[Al2V / 713]
2B ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-269
[A12V / 713]
2D ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-335
[Al 2V / 713]
2D ERCW NTT FLOW N/A (713 Pent Rm) 2-TW67-62 L 80 AZ371UPPER CNTMT VENT CLR 23A DISCH TEMP UPPER CNTMT VENT CLR 2-TW-67-266 ELA82V Z 71490 2B DISCH TEMP UPPER CNTMT VENT CLR D DISCH TEMP
/
/
/
Start / Stop Time & Date Data Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A N/A
Data Sheet 3 (Page 1 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.3 Date Subsection 6.1.3: Upper Compartment Coolers 2A, 2C, 2D Upper Compartment Mass Air Temperatures UNID Location Description ICS Point Set 1 Set 2 Set 3 Average (AZ/EL) 2-TE-30-210A 2700 / 868' DOME T1000A 2-TE-30-210Q 550 / 809' ICE COND WALL T1016A 2-TE-30-210R 2350/ 809' ICE WALL OPP SID T1017A 2-TE-30-210S 92/ 766' PRZR ENCL WALL T1018A 2-TE-30-210T 285' / 766' ICE OPP PRZR T1019A 2-TE-30-210U 180/ 766' SG ENCL WALL T1020A 2-TE-30-210V 00 / 766' SG ENCL OPP SIDE T1021A UPPER CMPT AVG MASS AIR TEMP U9019 Additional Upper Compartment Temperature Data UNID Description ICS Point Set 1 Set 2 Set 3 Average 2-TE-30-21 10 UPPER COMPT COOL UNIT A INTAKE Ti 1 18A 2-TE-30-211P UPPER COMPT COOL UNIT B INTAKE T1119A 2-TE-30-211Q UPPER COMPT COOL UNIT C INTAKE T1120A 2-TE-30-211R UPPER COMPT COOL UNIT D INTAKE T1121A 2-TE-30-21 1S UPPER COMPT COOL UNIT A EXHAUST T1 122A 2-TE-30-211T UPPER COMPT COOL UNIT B EXHAUST T1123A 2-TE-30-211U UPPER COMPT COOL UNIT C EXHAUST T1124A 2-TE-30-21 1V UPPER COMPT COOL UNIT D EXHAUST T1 125A 2-ME-30-240 CNTMT UP-COMPARTMENT DEW PT TEMP Y0701A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A
/
/
/
Start / Stop Time & Date Data Recorded:
N/A
- i.
i i
Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 78 of 109 Data Sheet 3 (Page 2 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.3 Date Subsection 6.1.3: Upper Compartment Coolers 2A, 2C, 2D Additional Upper Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average 2-L-329 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-263
[Al 2V / 713]
2A ERCW RET FLOW N/A (713 Pent Rm) 2-L-329 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-332
[Al 2V / 713]
2A ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-265
[Al 2V / 713]
UPPERCN VET CLR N/A (713 Pent Rm) 2 ERCW RET FLOW 3
2-L-329 UPPER CNTMT VENT CLR 2-FI-67-333
[A12V / 713]
2C ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-269
[A12V / 713]
2D ERCW RET FLOW N/A (713 Pent Rm) 2-L-329 2-FI-67-335
[Al 2V / 713]
UPPER CNTMT VENT CLR N/A (713PentRm) 2D ERCW SUP FLOW UPPER CNTMT VENT CLR 2-TW-67-262 EL 802 AZ 370 A DISC VTEMP A DISCH TEMP UPPER CNTMT VENT CLR 2-TW-67-264 EL 802 AZ 215° C DISCH TEMP UPPER CNTMT VENT CLR 2-TW-67-268_ _ __L__802_A 325 D DISCH TEMP Start / Stop Time & Date Data Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
/
/
/
N/A N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 79 of 109 Data Sheet 4 (Page 1 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.4 Date Subsection 6.1.4: Upper Compartment Coolers 2B, 2C, 2D Upper Compartment Mass Air Temperatures UNID Location Description ICS Point Set 1 Set 2 Set 3 Average (AZIEL) 2-TE-30-210A 270' / 868' DOME T1000A 2-TE-30-210Q 550 / 809' ICE COND WALL T1016A 2-TE-30-210R 235' / 809' ICE WALL OPP SID T1017A 2-TE-30-210S 920 / 766' PRZR ENCL WALL T1018A 2-TE-30-210T 2850 / 766' ICE OPP PRZR T1019A 2-TE-30-210U 1800 / 766' SG ENCL WALL T1020A 2-TE-30-210V 00 / 766' SG ENCL OPP SIDE T1021A UPPER CMPT AVG MASS AIR TEMP U9019 Additional Upper Compartment Temperature Data UNID Description ICS Point Set 1 Set 2 Set 3 Average 2-TE-30-21 10 UPPER COMPT COOL UNIT A INTAKE Ti 1 18A 2-TE-30-211P UPPER COMPT COOL UNIT B INTAKE T1119A 2-TE-30-21 1 Q UPPER COMPT COOL UNIT C INTAKE Ti 120A 2-TE-30-211R UPPER COMPT COOL UNIT D INTAKE T1121A 2-TE-30-211S UPPER COMPT COOL UNIT A EXHAUST T1122A 2-TE-30-211T UPPER COMPT COOL UNIT B EXHAUST T1123A 2-TE-30-211U UPPER COMPT COOL UNIT C EXHAUST T1124A 2-TE-30-21 1V UPPER COMPT COOL UNIT D EXHAUST T1 125A 2-ME-30-240 CNTMT UP-COMPARTMENT DEW PT TEMP Y0701A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
CCalculations Verified By:
N/A N/A N/A
Data Sheet 4 (Page 2 of 2)
Upper Compartment Temperature Survey - Subsection 6.1.4 Date Subsection 6.1.4: Upper Compartment Coolers 2B, 2C, 2D Additional Upper Compartment Temperature Data UNID Location Description M&TE ID Set I Set 2 Set 3 Average 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-267
[A12V / 713]
2B ERCW RET FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-334
[A12V / 713]
2B ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-265
[A12V / 713]
2C ERCW RET FLOW N/A (713 Pent Rm) 3 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-333
[A12V / 713]
2C ERCW SUP FLOW N/A (713 Pent Rm) 2-L-329
[2V-13]9 UPPER CNTMT VENT CLR 2-FI-67-269
[An2V / 713]
2D ERCW RET FLOW N/A (713 Pent Rm) 2-L-329 UPPER CNTMT VENT CLR 2-FI-67-335
[Al 2V / 713]
2D ERCW SUP FLOW N/A (713 Pent Rm)
UPPER CNTMT VENT CLR 2-TW-67-266 EL 802 AZ 1490 B DISC VTEMP B DlSCH TEMP UPPER CNTMT VENT CLR 2-TW-67-264 EL 802 AZ 2150 C DISC VTEMP C DISCH TEMP UPPER CNTMT VENT CLR 2-TW-67-268 EL 802 AZ 3250 D DSCH VTEMP D DISCH TEMP Start / Stop Time & Date Data Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
/
/
/
N/A N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 81 of 109 Data Sheet 5 (Page 1 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.1 Date Subsection 6.2.1:
Lower Compartment Coolers 2A-A, 213-B3, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air Conditioning Train 2A Lower Compartment Mass Air Temperatures UNID Location Description ICS Point Set I Set 2 Set 3 Average (AZ/EL) 2-TE-30-210B 104° / 796' PRZ ENCL CEILG T1001A 2-TE-30-210C 00 / 796' SG ENCL CEILG T1002A 2-TE-30-210D 1800 / 796' SG ENCL CEILG T1003A 2-TE-30-210E 1840 / 708' RX SHLD WALL T1004A 2-TE-30-210F 0/
708' RX SHLD WALL T1005A 2-TE-30-2100 450 / 753' OPP REFUEL GATE T1014A 2-TE-30-210P 1040 / 726' IN PZR SUPP PLTF T1015A 2-TE-30-210W 1260 / 745' ICE PLTFM RCP#2 T1022A 2-TE-30-210X 3090 / 745' ICE PLTFM RCP#4 T1023A 2-TE-30-210Y 2010 / 745' ICE PLTFM SG#3 T1024A 2-TE-30-210Z 220 / 745' ICE PLTFM SG#1 T1025A 2-TE-30-21OAA 90° / 687' SUMP T1026A 2-TE-30-21OAB 00 / 723' FAN COMPT WALL T1027A 2-TE-30-21OAC 1800 / 723' FAN COMPT WALL T1028A 2-TE-30-21OAD 901 / 716' INSTR RM WALL T1029A 2-TE-30-21OAE 40° / 723' ACCUM RM WALL T1030A 2-TE-30-21OAF 1400 / 723' ACCUM RM WALL T1031A 2-TE-30-210AG 2200 / 723' ACCUM RM WALL T1032A 2-TE-30-21OAH 320/
723' ACCUM RM WALL T1033A LOWER CMPT AVG MASS AIR TEMP U9020
/
I
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A [ N/A N/A
Data Sheet 5 (Page 2 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.1 Date Subsection 6.2.1:
Lower Compartment Coolers 2A-A, 2B-B, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data 2-TE-30-211A CRDM COOL UNIT A-A EXHAUST T1100A 2-TE-30-211B CRDM COOL UNIT B-B EXHAUST T1101A 2-TE-30-211C CRDM COOL UNIT C-A EXHAUST T1102A 2-TE-30-211D CRDM COOL UNIT D-B EXHAUST T1103A 2-TE-30-211E CRDM COOL UNIT C-A B-B INTAKE T1104A 2-TE-30-211 F CRDM COOL UNIT A-A D-B INTAKE Ti 105A 2-TE-30-21 1 G LOWR COMPT COOL UNIT A-A EXHAUST T111 OA 2-TE-30-21 1 H LOWR COMPT COOL UNIT B-B EXHAUST T1111A 2-TE-30-2111 LOWR COMPT COOL UNIT C-A EXHAUST T1112A 2-TE-30-211J LOWR COMPT COOL UNIT D-B EXHAUST T1113A 2-TE-30-21 1K LOWER COMPT COOL UNIT A-A INTAKE T1 114A 2-TE-30-211L LOWER COMPT COOL UNIT B-B INTAKE T1115A 2-TE-30-211M LOWER COMPT COOL UNIT C-A INTAKE T1116A 2-TE-30-211N LOWER COMPT COOL UNIT D-B INTAKE T1117A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A Start / Stop Time & Date Data Recorded:
I 1
I N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A jN/A N/A
Data Sheet 5 (Page 3 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.1 Date Subsection 6.2.1:
Lower Compartment Coolers 2A-A, 2B-B, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data UNID Description ICS Point Set 1 Set 2 Set 3 Average 2-TE-30-210G UN RX VSL SUPP1 T1006A 2-TE-30-210H UN RX VSL SUPP2 T1007A 2-TE-30-2101 UN RX VSL SUPP3 T1008A 2-TE-30-210J ULN RX VSL SUPP4 T1009A 2-TE-30-210K EL719 OPP RX VSL NOZL 1 T1010A 2-TE-30-210L EL719 OPP RX VSL NOZL 2 T1011A 2-TE-30-210M EL719 OPP RX VSL NOZL 3 T1012A 2-TE-30-210N EL719 OPP RX VSL NOZL 4 T1013A 2-ME-30-241 CNTMT LOW-COMPARTMENT DEWPT TEMP Y0702A
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A
Data Sheet 5 (Page 4 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.1 Date Subsection 6.2.1:
Lower Compartment Coolers 2A-A, 2B-B, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set I Set 2 Set 3 Average Ultrasonic EL 726 AZ 21 0 LOW CNTMT VENT CLR A 2-FE-67-471 (S Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 1590 LOW CNTMT VENT CLR B Flowmeter near 2-FE-67-474 (N Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 2010 LOW CNTMT VENT CLR C Flowmeter near 2-FE-67-472 (N Fan Rm)
DISCH FLOW 2-TW-67-230 EL 721 AZ 90 LOW CNTMT VENT CLR A (S Fan Rm)
DISCH TEMP 2-TW-67-244 EL 721 AZ 1710 LOW CNTMT VENT CLR B (N Fan Rm)
DISCH TEMP 2-TW-67-236 EL 721 AZ 1870 LOW CNTMT VENT CLR C (N Fan Rm)
DISCH TEMP Ultrasonic CONT ROD DRIVE VENT Flowmeter near EL 720 AZ 90 CLR A DISCH FLOW 2-FE-67-470 UltrasonicUltraonicCONT ROD DRIVE VENT Flowmeter near EL 720 AZ 1870 CON R
DRIVE VENT 2-FE-7-473CLR C DISCH FLOW 2-FE-67-473 2-TW-67-232 EL 725 AZ 90 CONTROL ROD DR VENT (S Fan Rm)
CLR A DISCH TEMP 2-TW-67-238 EL 725 AZ 1870 CONTROL ROD DR VENT (N Fan Rm)
CLR C DISCH TEMP
/
Start / Stop Time & Date Data Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
/
/
N/A N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 85 of 109 Data Sheet 5 (Page 5 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.1 Date Subsection 6.2.1:
Lower Compartment Coolers 2A-A, 2B-B, 2C-A CRDM Coolers 2A-A, 2C-A Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average Ultrasonic A12W /692 INSTR RM VENT CLR A Flowmeter near 2-FE-67-257 (692 Pent Rm)
DISCH FLOW A12W / 692 INSTR RM VENT CLR A (692 Pent Rm)
DISCH TEMP 2-TI-31-300 A12W /692 INCORE INSTR ROOM N/A (692 Pent Rm)
CHILLER 2A CW IN TEMP 2-TI-31-312 A12W / 692 INCORE INSTR ROOM N/A (692 Pent Rm)
CHILLER 2A CW OUT TEMP Ultrasonic A12W / 692 INCORE INST RM CHILL A Flowmeter near 2-FE-31-311 (692 Pent Rm)
CWS FLOW
/
I
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A j
N/A N/A j
Containment Building Temperature 2-PTI-030L-01 Survey Rev. 0000 Paqe 86 of 109 Data Sheet 6 (Page 1 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.2 Date Subsection 6.2.2:
Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A Lower Compartment Mass Air Temperatures Location DsrpinICS UNID LocaZ/P Description oint Set 1 Set 2 Set 3 Average UND(AZ/EL)Pon 2-TE-30-210B 1040 / 796' PRZ ENCL CEILG T1001A 2-TE-30-210C 00 / 796' SG ENCL CEILG T1002A 2-TE-30-210D 1800 / 796' SG ENCL CEILG T1003A 2-TE-30-210E 1840 / 708' RX SHLD WALL T1004A 2-TE-30-21 OF 00 / 708' RX SHLD WALL T1005A 2-TE-30-2100 450/ 753' OPP REFUEL GATE T1014A 2-TE-30-210P 1040 / 726' IN PZR SUPP PLTF T1015A 2-TE-30-210W 1260 / 745' ICE PLTFM RCP#2 T1022A 2-TE-30-210X 3090 / 745' ICE PLTFM RCP#4 T1023A 2-TE-30-210Y 2010 / 745' ICE PLTFM SG#3 T1024A 2-TE-30-210Z 220 / 745' ICE PLTFM SG#1 T1025A 2-TE-30-21OAA 90° / 687' SUMP T1026A 2-TE-30-21OAB 0° / 723' FAN COMPT WALL T1027A 2-TE-30-210AC 1800 / 723' FAN COMPT WALL T1028A 2-TE-30-21OAD 900 /716' INSTR RM WALL T1029A 2-TE-30-21OAE 400 /723' ACCUM RM WALL T1030A 2-TE-30-210AF 1400 / 723' ACCUM RM WALL T1031A 2-TE-30-21OAG 2200 / 723' ACCUM RM WALL T1032A 2-TE-30-21OAH 3200 / 723' ACCUM RM WALL T1033A LOWER CMPT AVG MASS AIR TEMP U9020
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A j N/A j
Data Sheet 6 (Page 2 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.2 Date Subsection 6.2.2:
Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data 2-TE-30-211A CRDM COOL UNIT A-A EXHAUST T1100A 2-TE-30-211B CRDM COOL UNIT B-B EXHAUST T1101A 2-TE-30-211C CRDM COOL UNIT C-A EXHAUST T1102A 2-TE-30-211D CRDM COOL UNIT D-B EXHAUST T1103A 2-TE-30-211E CRDM COOL UNIT C-A B-B INTAKE T1104A 2-TE-30-211F CRDM COOL UNIT A-A D-B INTAKE T1105A 2-TE-30-21 1G LOWR COMPT COOL UNIT A-A EXHAUST T1110A 2-TE-30-211H LOWR COMPT COOL UNIT B-B EXHAUST T1111A 2-TE-30-2111 LOWR COMPT COOL UNIT C-A EXHAUST T1112A 2-TE-30-211J LOWR COMPT COOL UNIT D-B EXHAUST T1113A 2-TE-30-21 1K LOWER COMPT COOL UNIT A-A INTAKE T1 114A 2-TE-30-211L LOWER COMPT COOL UNIT B-B INTAKE T1115A 2-TE-30-211M LOWER COMPT COOL UNIT C-A INTAKE T1116A 2-TE-30-211N LOWER COMPT COOL UNIT D-B INTAKE T1117A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A
/
I
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A j
Data Sheet 6 (Page 3 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.2 Date Subsection 6.2.2:
Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data ICS UNID Description Point Set 1 Set 2 Set 3 Average 2-TE-30-210G UN RX VSL SUPP1 T1006A 2-TE-30-210H UN RX VSL SUPP2 T1007A 2-TE-30-2101 UN RX VSL SUPP3 T1008A 2-TE-30-210J UN RX VSL SUPP4 T1009A 2-TE-30-210K EL719 OPP RX VSL NOZL 1 T1010A 2-TE-30-210L EL719 OPP RX VSL NOZL 2 T1011A 2-TE-30-210M EL719 OPP RX VSL NOZL 3 T1012A 2-TE-30-210N EL719 OPP RX VSL NOZL 4 T1013A 2-ME-30-241 CNTMT LOW-COMPARTMENT DEWPT TEMP Y0702A
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A IN/Al N/A j
Data Sheet 6 (Page 4 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.2 Date Subsection 6.2.2:
Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average Ultrasonic EL 726 AZ 210 LOW CNTMT VENT CLR A 2-FE-67-471 (S Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 1590 LOW CNTMT VENT CLR B Flowmeter near 2-FE-67-474 (N Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 3390 LOW CNTMT VENT CLR D Flowmeter near 2-FE-67-476 (S Fan Rm)
DISCH FLOW 2-TW-67-230 EL 721 AZ 90 LOW CNTMT VENT CLR A (S Fan Rm)
DISCH TEMP EL 721 AZ 171 0 LOW CNTMT VENT CLR B (N Fan Rm)
DISCH TEMP 2-TW-67-250 EL 721 AZ 3510 LOW CNTMT VENT CLR D (S Fan Rm)
DISCH TEMP UltrasonicUltraonicCONT ROD DRIVE VENT Flowmeter near EL 720 AZ 90 CLROA DRIVE FLOW 2-FE-7-470CLR A DISCH FLOW 2-FE-67-470 Ultrasonic Flowmeter near EL 720 AZ 1710 CONT ROD DRIVE VENT 2-FE-7-477CLR B DISCH FLOW 2-FE-67-477 2-TW-67-232 EL 725 AZ 90 CONTROL ROD DR VENT (S Fan Rm)
CLR A DISCH TEMP 2-TW-67-246 EL 725 AZ 171 CONTROL ROD DR VENT (N Fan Rm)
CLR B DISCH TEMP
/
/
Start / Stop Time & Date Data Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A N/A I
3ontainment Building Temperature 2-PTI-030L-01 Survey Rev. 0000 Page 90 of 109 Data Sheet 6 (Page 5 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.2 Date Subsection 6.2.2:
Lower Compartment Coolers 2A-A, 2B-B, 2D-B CRDM Coolers 2A-A, 2B-B Incore Instrument Room Air Conditioning Train 2A Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average Ultrasonic A12W /692 INSTR RM VENT CLR A Flowmeter near 2-FE-67-257 (692 Pent Rm)
DISCH FLOW A12W / 692 INSTR RM VENT CLR A (692 Pent Rm)
DISCH TEMP 2-TI-31-300 A12W / 692 INCORE INSTR ROOM N/A (692 Pent Rm)
CHILLER 2A CW IN TEMP A12W / 692 INCORE INSTR ROOM 2-TI-31-312 (692 Pent Rm)
CHILLER 2A CW OUT TEMP N/A Ultrasonic A12W / 692 INCORE INST RM CHILL A Flowmeter near (692 Pent Rm)
CWS FLOW 2-FE-31-311
(
I
/
/
Start / Stop Time & Date Data Recorded:
Data Recorded/Calculated By:
Calculations Verified By:
N/A
- 1-t 1*
N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 91 of 109 Data Sheet 7 (Page 1 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.3 Date Subsection 6.2.3:
Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning Train 2B Lower Compartment Mass Air Temperatures LocationICS UNID Location Description Point Set I Set 2 Set 3 Average (AZ/EL)Pon 2-TE-30-210B 1040 / 796' PRZ ENCL CEILG T1001A 2-TE-30-210C 00 / 796' SG ENCL CEILG T1002A 2-TE-30-210D 1800 / 796' SG ENCL CEILG T1003A 2-TE-30-210E 1840 / 708' RX SHLD WALL T1004A 2-TE-30-210F 00 / 708' RX SHLD WALL T1005A 2-TE-30-2100 450/ 753' OPP REFUEL GATE T1014A 2-TE-30-210P 1040 / 726' IN PZR SUPP PLTF T1015A 2-TE-30-210W 1260 / 745' ICE PLTFM RCP#2 T1022A 2-TE-30-210X 3090 / 745' ICE PLTFM RCP#4 T1023A 2-TE-30-210Y 2010 / 745' ICE PLTFM SG#3 T1024A 2-TE-30-210Z 220 / 745' ICE PLTFM SG#1 T1025A 2-TE-30-21OAA 900 / 687' SUMP T1026A 2-TE-30-21OAB 00 / 723' FAN COMPT WALL T1027A 2-TE-30-21OAC 180/
723' FAN COMPT WALL T1028A 2-TE-30-21OAD 90, /716' INSTR RM WALL T1029A 2-TE-30-210AE 400 / 723' ACCUM RM WALL T1030A 2-TE-30-210AF 1400 / 723' ACCUM RM WALL T1031A 2-TE-30-21OAG 2200 / 723' ACCUM RM WALL T1032A 2-TE-30-21OAH 3200 / 723' ACCUM RM WALL T1033A LOWER CMPT AVG MASS AIR TEMP U9020
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A j
N/A N/A
Data Sheet 7 (Page 2 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.3 Date Subsection 6.2.3:
Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data 2-TE-30-21 1A CRDM COOL UNIT A-A EXHAUST T1 100A 2-TE-30-211B CRDM COOL UNIT B-B EXHAUST T1101A 2-TE-30-211C CRDM COOL UNIT C-A EXHAUST T1102A 2-TE-30-211D CRDM COOL UNIT D-B EXHAUST T1103A 2-TE-30-211E CRDM COOL UNIT C-A B-B INTAKE T1104A 2-TE-30-211F CRDM COOL UNIT A-A D-B INTAKE T1105A 2-TE-30-21 1 G LOWR COMPT COOL UNIT A-A EXHAUST T1110A 2-TE-30-211H LOWR COMPT COOL UNIT B-B EXHAUST T1111A 2-TE-30-2111 LOWR COMPT COOL UNIT C-A EXHAUST T1112A 2-TE-30-211J LOWR COMPT COOL UNIT D-B EXHAUST T1113A 2-TE-30-21 1K LOWER COMPT COOL UNIT A-A INTAKE Ti 1 14A 2-TE-30-211L LOWER COMPT COOL UNIT B-B INTAKE T1115A 2-TE-30-211M LOWER COMPT COOL UNIT C-A INTAKE T1116A 2-TE-30-211N LOWER COMPT COOL UNIT D-B INTAKE T1117A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A JN/A N/A I
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 93 of 109 Data Sheet 7 (Page 3 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.3 Date Subsection 6.2.3:
Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data ICS UNID Description Point Set 1 Set 2 Set 3 Average 2-TE-30-210G UN RX VSL SUPP1 T1006A 2-TE-30-210H UN RX VSL SUPP2 T1007A 2-TE-30-2101 UN RX VSL SUPP3 T1008A 2-TE-30-210J UN RX VSL SUPP4 T1009A 2-TE-30-210K EL719 OPP RX VSL NOZL 1 T1010A 2-TE-30-210L EL719 OPP RX VSL NOZL 2 T1011A 2-TE-30-210M EL719 OPP RX VSL NOZL 3 T1012A 2-TE-30-210N EL719 OPP RX VSL NOZL 4 T1013A 2-ME-30-241 CNTMT LOW-COMPARTMENT DEWPT TEMP Y0702A
/
I
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 94 of 109 Data Sheet 7 (Page 4 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.3 Date Subsection 6.2.3:
Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average Ultrasonic EL 726 AZ 210 LOW CNTMT VENT CLR A 2-FE-67-471 (S Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 2010 LOW CNTMT VENT CLR C 2-FE-67-472 (N Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 3390 LOW CNTMT VENT CLR D 2-FE-67-476 (S Fan Rm)
DISCH FLOW 2-TW-67-230 EL 721 AZ 90 LOW CNTMT VENT CLR A (S Fan Rm)
DISCH TEMP 2-TW-67-236 EL 721 AZ 1870 LOW CNTMT VENT CLR C (N Fan Rm)
DISCH TEMP 2-TW-67-250 EL 721 AZ 3510 LOW CNTMT VENT CLR D (S Fan Rm)
DISCH TEMP Ultrasonic CONT ROD DRIVE VENT Flowmeter near EL 720 AZ 1870 CLR C DISCH FLOW 2-FE-67-473 Ultrasonic CONT ROD DRIVE VENT Flowmeter near EL 720 AZ 3510 CLR D DISCH FLOW 2-FE-67-475 2-TW-67-238 EL 725 AZ 1870 CONTROL ROD DR VENT (N Fan Rm)
CLR C DISCH TEMP 2-TW-67-252 EL 725 AZ 3510 CONTROL ROD DR VENT (S Fan Rm)
CLR D DISCH TEMP
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A j N/A N/A j
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 95 of 109 Data Sheet 7 (Page 5 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.3 Date Subsection 6.2.3:
Lower Compartment Coolers 2A-A, 2C-A, 2D-B CRDM Coolers 2C-A, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average Ultrasonic A12W /692 INSTR RM VENT CLR B Flowmeter near 2-FE-67-259 (692 Pent Rm)
DISCH FLOW 2-TW-67-258 A12W /692 INSTR RM VENT CLR B (692 Pent Rm)
DISCH TEMP 2-TI-31-320 A12W /692 INCORE INSTR ROOM N/A (692 Pent Rm)
CHILLER 2B CW IN TEMP 2-Tl-31-333 A12W / 692 INCORE INSTR ROOM N/A (692 Pent Rm)
CHILLER 2B CW OUT TEMP Ultrasonic A12W / 692 INCORE INST RM CHILL B Flowmeter near 2-FE-31-332 (692 Pent Rm)
CWS FLOW
/
I Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A
[N/A N/A j
Data Sheet 8 (Page 1 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.4 Date Subsection 6.2.4:
Lower Compartment Coolers 2B3-B3, 2C-A, 2D-13 CROM Coolers 213-13, 20-B Incore Instrument Room Air Conditioning Train 2B Lower Compartment Mass Air Temperatures Location DsrpinICS UNID LocaZ/P Description oint Set I Set 2 Set 3 Average UND(AZ/EL)Pon 2-TE-30-210B 1040 / 796' PRZ ENCL CEILG T1001A 2-TE-30-210C 00 / 796' SG ENCL CEILG T1002A 2-TE-30-210D 1800 / 796' SG ENCL CEILG T1003A 2-TE-30-210E 1840 / 708' RX SHLD WALL T1004A 2-TE-30-210F 00 / 708' RX SHLD WALL T1005A 2-TE-30-2100 450 / 753' OPP REFUEL GATE T1014A 2-TE-30-210P 1040 / 726' IN PZR SUPP PLTF T1015A 2-TE-30-210W 1260 / 745' ICE PLTFM RCP#2 T1022A 2-TE-30-210X 3090 / 745' ICE PLTFM RCP#4 T1023A 2-TE-30-210Y 2010 / 745' ICE PLTFM SG#3 T1024A 2-TE-30-210Z 220 / 745' ICE PLTFM SG#1 T1025A 2-TE-30-21OAA 900 / 687' SUMP T1026A 2-TE-30-21OAB 00 / 723' FAN COMPT WALL T1027A 2-TE-30-21OAC 1800 / 723' FAN COMPT WALL T1028A 2-TE-30-21OAD 900 / 716' INSTR RM WALL T1029A 2-TE-30-21OAE 400 / 723' ACCUM RM WALL T1030A 2-TE-30-21OAF 1400 / 723' ACCUM RM WALL T1031A 2-TE-30-210AG 2200 / 723' ACCUM RM WALL T1032A 2-TE-30-210AH 3200 / 723' ACCUM RM WALL T1033A LOWER CMPT AVG MASS AIR TEMP U9020
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 97 of 109 Data Sheet 8 (Page 2 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.4 Date Subsection 6.2.4:
Lower Compartment Coolers 2B-B, 2C-A, 2D-B CRDM Coolers 2B-B, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data 2-TE-30-211A CRDM COOL UNIT A-A EXHAUST T1100A 2-TE-30-211B CRDM COOL UNIT B-B EXHAUST T1101A 2-TE-30-211C CRDM COOL UNIT C-A EXHAUST T1102A 2-TE-30-211D CRDM COOL UNIT D-B EXHAUST T1103A 2-TE-30-21 1 E CRDM COOL UNIT C-A B-B INTAKE T1 104A 2-TE-30-211F CRDM COOL UNIT A-A D-B INTAKE T1105A 2-TE-30-21 1 G LOWR COMPT COOL UNIT A-A EXHAUST T1110A 2-TE-30-21 1 H LOWR COMPT COOL UNIT B-B EXHAUST T1111A 2-TE-30-2111 LOWR COMPT COOL UNIT C-A EXHAUST T1112A 2-TE-30-211J LOWR COMPT COOL UNIT D-B EXHAUST T1113A 2-TE-30-21 1K LOWER COMPT COOL UNIT A-A INTAKE T1 114A 2-TE-30-211L LOWER COMPT COOL UNIT B-B INTAKE T1115A 2-TE-30-211M LOWER COMPT COOL UNIT C-A INTAKE T1116A 2-TE-30-211N LOWER COMPT COOL UNIT D-B INTAKE T1117A 2-TE-67-455 ERCW SUP HDR 2A TEMP T2614A 2-TE-67-456 ERCW SUP HDR 2B TEMP T2615A
/
/
/
Start / Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 98 of 109 Data Sheet 8 (Page 3 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.4 Date Subsection 6.2.4:
Lower Compartment Coolers 2B-B, 2C-A, 2D-B CRDM Coolers 2B-B, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data ICS UNID Description Point Set 1 Set 2 Set 3 Average 2-TE-30-210G UN RX VSL SUPP1 T1006A 2-TE-30-210H UN RX VSL SUPP2 T1007A 2-TE-30-2101 UN RX VSL SUPP3 T1008A 2-TE-30-210J UN RX VSL SUPP4 T1009A 2-TE-30-210K EL719 OPP RX VSL NOZL 1 T1010A 2-TE-30-210L EL719 OPP RX VSL NOZL 2 T1011A 2-TE-30-210M EL719 OPP RX VSL NOZL 3 T1012A 2-TE-30-210N EL719 OPP RX VSL NOZL 4 T1013A 2-ME-30-241 CNTMT LOW-COMPARTMENT DEWPT TEMP Y0702A
/
I
/
Start / Stop Time & Date Data Recorded:
N/A f
4 4
Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 99 of 109 Data Sheet 8 (Page 4 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.4 Date Subsection 6.2.4:
Lower Compartment Coolers 2B-B, 2C-A, 2D-B CRDM Coolers 2B-B, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average Ultrasonic EL 726 AZ 1590 LOW CNTMT VENT CLR B Flowmeter near 2-FE-67-474 (N Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 2010 LOW CNTMT VENT CLR C 2-FE-67-472 (N Fan Rm)
DISCH FLOW Ultrasonic EL 726 AZ 3390 LOW CNTMT VENT CLR D 2-FE-67-476 (S Fan Rm)
DISCH FLOW 2-TW-67-244 EL 721 AZ 1710 LOW CNTMT VENT CLR B (N Fan Rm)
DISCH TEMP EL 721 AZ 1870 LOW CNTMT VENT CLR C (N Fan Rm)
DISCH TEMP 2-TW-67-250 EL 721 AZ 251 0 LOW CNTMT VENT CLR D (S Fan Rm)
DISCH TEMP Ultrasonic CONT ROD DRIVE VENT Flowmeter near EL 720 AZ 1710 2-FE-7-477CLR B DISCH FLOW 2-FE-67-477 Ultrasonic CONT ROD DRIVE VENT Flowmeter near EL 720 AZ 3510 CLR D DISCH FLOW 2-FE-67-475 2-TW-67-246 EL 725 AZ 1710 CONTROL ROD DR VENT (N Fan Rm)
CLR B DISCH TEMP 2-TW-67-252 EL 725 AZ 3510 CONTROL ROD DR VENT (S Fan Rm)
CLR D DISCH TEMP
/
/
/
Start / Stop Time & Date Data Recorded:
N/A t
I.
Data Recorded/Calculated By:
Calculations Verified By:
N/A [
N/A I
N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 100 of 109 Data Sheet 8 (Page 5 of 5)
Lower Compartment Temperature Survey - Subsection 6.2.4 Date Subsection 6.2.4:
Lower Compartment Coolers 2B-B, 2C-A, 2D-B CRDM Coolers 2B-B, 2D-B Incore Instrument Room Air Conditioning Train 2B Additional Lower Compartment Temperature Data UNID Location Description M&TE ID Set 1 Set 2 Set 3 Average Ultrasonic A12W /692 INSTR RM VENT CLR B Flowmeter near 2-FE-67-259 (692 Pent Rm)
DISCH FLOW A12W /692 INSTR RM VENT CLR B (692 Pent Rm)
DISCH TEMP 2-TI-31-320 A12W / 692 INCORE INSTR ROOM N/A (692 Pent Rm)
CHILLER 2B CW IN TEMP 2-TI-31-333 A12W /692 INCORE INSTR ROOM N/A (692 Pent Rm)
CHILLER 2B CW OUT TEMP Ultrasonic A12W / 692 INCORE INST RM CHILL B Flowmeter near 2-FE-31-332 (692 Pent Rm)
CWS FLOW
/
/
Start/ Stop Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
N/A N/A N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 101 of 109 Data Sheet 9 (Page 1 of 2)
Upper Compartment Air Temperature Thermocouple Measurements Date Subsection:
M&TE ID:
Cal Due Date:
Thermocouple Terminations 1 Temperatures UNID Description ICS Point Terminal Terminals Average Rack Bok Cable (hed1-)
Set 1 Set 2 Set 3 Tm T
Block (Shield / + /I-Temp (T) 2-TE-30-210A DOME T1000A 2-R-104 E/00 2CR397 Si1/+1 /-1 2-TE-30-210Q ICE COND WALL T1016A 2-R-111 03 2R802 SO/+0/-0 2-TE-30-210R ICE WALL OPP SID T1017A 2-R-111 03 2R803
$1/+1 /-
2-TE-30-210S PRZR ENCL WALL T1018A 2-R-111 03 2R804 S2/+2/-2 2-TE-30-210T ICE OPP PRZR T1019A 2-R-1 11 03 2R805 S3/+3/-3 2-TE-30-210U SG ENCL WALL T1020A 2-R-111 03 2R806 S4/+4/-4 2-TE-30-210V SG ENCL OPP SIDE T1021A 2-R-111 03 2R807 S5/+5/-5 Time & Date Data Recorded:
N/A i
t t
Data Recorded/Calculated By:
Calculations Verified By:
1 Reference Drawings 2-45W2697-14-4 for Rack 2-R-104 and 2-45W2697-14-8 for Rack 2-R-111.
N/A I
N/A
[
N/A
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 102 of 109 Data Sheet 9 (Page 2 of 2)
Upper Compartment Air Temperature Thermocouple Measurements Date Subsection:
Group UNID Description ICS Point Average Temp Volume Fraction Temperature Fraction (T)
(VF)
(TF= T x VF) 1 2-TE-30-210A DOME T1000A 0.25 1
2-TE-30-210Q ICE COND WALL T1016A 0.11 1
2-TE-30-210R ICE WALL OPP SID T1017A 0.11 2
2-TE-30-21 OS PRZR ENCL WALL T1018A 0.11 2
2-TE-30-210T ICE OPP PRZR T1019A 0.20 2
2-TE-30-210U SG ENCL WALL T1020A 0.11 2
2-TE-30-210V SG ENCL OPP SIDE T1021A 0.11 SUM of OOS Volume Fractions (XVFoos):
Sum of Temp Fractions (XTF):
Upper Compartment Weighted Average Air Temperature (Tup) -
TF 1 -XVFoos 1 -
Calculations Performed By:
Calculations Verified By
Data Sheet 10 (Page 1 of 4)
Lower Compartment Air Temperature Thermocouple Measurements Date Subsection:
M&TE ID:
Cal Due Date:
Thermocouple Terminations 2 Temperatures UNID Description ICS Point Rack Terminal Cable Terminals Set 1 Set 2 Set 3 Average Block (Shield / + / -)
Temp (T) 2-TE-30-210B PRZ ENCL CEILG T100IA 2-R-104 E/00 2CR399 S2/+2/-2 2-TE-30-210C SG ENCL CEILG T1002A 2-R-104 E/00 2CR401 S3 / +3/-3 2-TE-30-210D SG ENCL CEILG T1003A 2-R-104 E/00 2CR403 S4 / +4 /-4 2-TE-30-210E RX SHLD WALL T1004A 2-R-104 E/00 2CR405 S5 / +5/-5 2-TE-30-210F RX SHLD WALL T1005A 2-R-104 J/10 2CR407 SO/ +o /-0 2-TE-30-2100 OPP REFUEL GATE T1014A 2-R-104 J/08 2CR425 S2/+2/-2 2-TE-30-210P IN PZR SUPP PLTF T1015A 2-R-104 J/08 2CR427 S3 / +3 / -3 2-TE-30-210W ICE PLTFM RCP#2 T1022A 2-R-111 03 2R808 S6/+6/-6 2-TE-30-210X ICE PLTFM RCP#4 T1023A 2-R-1 11 03 2R809 S7 / +7/-7 2-TE-30-210Y ICE PLTFM SG#3 T1024A 2-R-111 04 2R810
$1/+1/-1 2-TE-30-210Z ICE PLTFM SG#1 T1025A 2-R-111 04 2R811 S2/+2/-2 2-TE-30-21OAA SUMP T1026A 2-R-111 04 2R812 S3/+3/-3 2-TE-30-21OAB FAN COMPT WALL T1027A 2-R-111 04 2R813 S4/ +4/-4 2-TE-30-210AC FAN COMPT WALL T1028A 2-R-1 11 04 2R814 S5/ +5/ -5
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 104 of 109 Data Sheet 10 (Page 2 of 4)
Lower Compartment Air Temperature Thermocouple Measurements Date Subsection:
Thermocouple Terminations 2 Temperatures UNID Description ICS Point Terminal Terminals Average Rack Bok Cable (hed1-)
Set 1 Set 2 Set 3 Tm T
Block (Shield / + / -)
Temp (T) 2-TE-30-210AD INSTR RM WALL T1029A 2-R-111 04 2R815 S6/+6/-6 2-TE-30-210AE ACCUM RM WALL T1030A 2-R-111 04 2R816 S7/+7/-7 2-TE-30-210AF ACCUM RM WALL T1031A 2-R-1 11 05 2R817 SO / +0/-0 2-TE-30-210AG ACCUM RM WALL T1032A 2-R-111 05 2R818 S1/+1 /-1 2-TE-30-210AH ACCUM RM WALL T1033A 2-R-111 05 2R819 S2/+2/-2 2-TE-30-210G UN RX VSL SUPP1 T1006A 2-R-104 J/10 2CR409
$1/+1 /-
2-TE-30-210H UN RX VSL SUPP2 T1007A 2-R-104 J/10 2CR411 S2 /+2/-2 2-TE-30-2101 UN RX VSL SUPP3 T1008A 2-R-104 J/10 2CR413 S3/+3 / -3 2-TE-30-210J UN RX VSL SUPP4 T1009A 2-R-104 J/10 2CR415 S4/+4 / -4 Time & Date Data Recorded:
N/A Data Recorded/Calculated By:
Calculations Verified By:
2 Reference Drawings 2-45W2697-14-4 for Rack 2-R-104 and 2-45W2697-14-8 & 2-45W2697-54-lfor Rack 2-R-111.
N/A J N/A j N/A j
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 105 of 109 Data Sheet 10 (Page 3 of 4)
Lower Compartment Air Temperature Thermocouple Measurements Date Subsection:
Group UNID Description ICS Point Average Temp Volume Fraction Temperature Fraction (T)
(VF)
(TF = T x VF)
N/A 2-TE-30-210B PRZ ENCL CEILG T1001A 0.007 N/A 2-TE-30-210(C SG ENCL CEILG T1002A 0.072 N/A 2-TE-30-210D SG ENCL CEILG T1003A 0.072 1
2-TE-30-210E RX SHLD WALL T1004A 0.122 1
2-TE-30-210F RX SHLD WALL T1005A 0.122 N/A 2-TE-30-2100 OPP REFUEL GATE T1014A 0.034 1
2-TE-30-210P IN PZR SUPP PLTF T1 01 5A 0.007 2
2-TE-30-210W ICE PLTFM RCP#2 T1022A 0.061 2
2-TE-30-210X ICE PLTFM RCP#4 T1023A 0.061 2
2-TE-30-210Y ICE PLTFM SG#3 T1024A 0.061 2
2-TE-30-210Z ICE PLTFM SG#1 T1025A 0.061 N/A 2-TE-30-210AA SUMP T1026A 0.034
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 106 of 109 Data Sheet 10 (Page 4 of 4)
Lower Compartment Air Temperature Thermocouple Measurements Date Subsection:
Group UNID Description ICS Point Average Temp Volume Fraction Temperature Fraction (T)
(VF)
(TF = T x VF) 3 2-TE-30-210AB FAN COMPT WALL T1027A 0.037 3
2-TE-30-21OAC FAN COMPT WALL T1028A 0.038 N/A 2-TE-30-21OAD INSTR RM WALL T1029A 0.043 3
2-TE-30-210AE ACCUM RM WALL T1030A 0.053 3
2-TE-30-210AF ACCUM RM WALL T1031A 0.047 3
2-TE-30-21OAG ACCUM RM WALL T1032A 0.034 3
2-TE-30-21OAH ACCUM RM WALL T1033A 0.034 Sum of OOS Volume Fractions (Y-VFoos):
Sum of Temp Fractions (XTF):
Lower Compartment Weighted Average Air Temperature (TLow) -
-TF a -
BaVF aos I Jlations Performed By:
Calculations Verified By OF Calcu
Table 1 (Page 1 of 3)
Containment Air Cooling Equipment Locations Date Upper Compartment Coolers UNID Main Control Room Breaker Location UCC 2A 2-CCU-30-95 2-HS-30-95A 2-BKR-30-95 802'/370
[2-M-9]
[RX VENT BD 2A-A]
UCC 2B 2-CCU-30-97 2-HS-30-97A 2-BKR-30-97 802' /1490
[2-M-9]
[RX VENT BD 2B-B]
UCC 2C 2-CCU-30-99 2-HS-30-99A 2-BKR-30-99 802' /2150
[2-M-9]
[RX VENT BD 2A-A]
UCC 2D 2-CCU-30-1 00 2-HS-30-100A 2-BKR-30-100 802' /3250
[2-M-9]
[RX VENT BD 2B-B]
Lower Compartment Coolers UNID Main Control Room Breaker Location 2-HS-30-74A 2-BKR-30-74 716'/ 21 0
[2-M-9]
(S Fan Rm) 2-HS-30-75A 2-BKR-30-75 716'/ 1590
[2-M-9]
(N Fan Rm) 2-HS-30-77A 2-BKR-30-77 716'/ 201 0
[2-M-9]
(N Fan Rm) 2-HS-30-78A 2-BKR-30-78 716'/ 3390
[2-M-9]
(S Fan Rm)
Table 1 (Page 2 of 3)
Containment Air Cooling Equipment Locations Date CRDM Coolers & Associated Dampers UNID Main Control Room Aux Control Room Breaker Location 4
2-CLR-30-83 2-HS-30-83A N/A 2-BKR-30-83 703' /250
[2-M-9]
-0 2-HS-30-84A 2-HS-30-84C 0
2-TCO-30-841 N/A 703'/ 150 o
[2-M-9]
[2-L-10]
2 32-HS-30-85A 2-HS-30-85C r*
2-TCO-30-85
[2M9 2L1]N/A 703' / 150 0
[2-M-9]
[2-L-10]
2-CLR-30-92 2-HS-30-92A N/A 2-BKR-30-92 703'/ 1650
[2-M-9]
-0 2-HS-30-93A 2-HS-30-93C 0
2-TCO-30-931 N/A 703' /1650 o
[2-M-9]
[2-L-10]
2-HS-30-94A 2-HS-30-94C 2-T60-30-94
[2-M-9]
[2-L-1O0]
N/A 703'/1650 2-CLR-30-88 2-HS-30-88A N/A 2-BKR-30-88 703'/ 2050 0
[2-M-9]
0 2_TCO_30_89 1 2-HS-30-89A 2-HS-30-89C N/A 703'! 1950 O
[2-M-9]
[2-L-10]
2-TCO-30-90 2-HS-30-90A 2-HS-30-90C N/A 703'! 1950 0
[2-M-9]
[2-L-10]
C?
2-CLR-30-80 2-HS-30-80A N/A 2-BKR-30-80 703' /3350 0
[2-M-9]
04
-0 2-HS-30-81A 2-HS-30-81C 0
2-TCO-30-811 N/A 703' /3450 O
[2-M-9]
[2-L-10]
2-TCO-30-82 2-HS-30-82A 2-HS-30-82C N/A 703'!3450 0
[2-M-9]
[2-L-10]
1 CRDM Shroud Suction Dampers are designed to automatically open if their respective Handswitch is in P AUTO and their associated CRDM Cooler starts.
WBN Containment Building Temperature 2-PTI-030L-01 Unit 2 Survey Rev. 0000 Page 109 of 109 Table 1 (Page 3 of 3)
Containment Air Cooling Equipment Locations Date Incore Instrument Room Air Conditioning UNID Main Control Room Breaker Location 2-HS-31-265A 2-BKR-31-265 730' /570
[2-M-9]
(IIR) 2-FCO-31-2632 2-XI-31-263 N/A 730'/570
[2-M-9]
(IIR) 2-FCO-31-264"2 2-X-31-264 N/A 730'/570 U
[2-M-9]NA (IIR) 2-CHR-31-303 2 N/A 2-BKR-31-303B A12W / 692
(692 Pent Rm) 2-PMP-31-303/1 2 N/A 2-BKR-31-303A A12W / 692
(692 Pent Rm) 2-HS-31-266A 2-BKR-31-266 730'/ 1120
[2-M-9]
(IIR) 2-FCO-31-268 2 2-XI-31-268 N/A 730'/ 1120
[2-M-9]
(1IR) 2 2-XI-31-269 730'/ 1120 "U
2-FCO-31-269
[2-M-9]
N/A (IIR) 2-CHR-31-324 2 N/A 2-BKR-31-324B A12W / 692
(692 Pent Rm) 2-PMP-31-324/1 2 N/A 2-BKR-31-324A A12W / 692
(692 Pent Rm) 2 Incore Instrument Room Air Conditioning Chiller, Pump, and Dampers are designed to automatically start/open when their associated AHU starts.