MONTHYEARML24052A0552023-08-15015 August 2023 News Release-IV-23-008: NRC Names New Resident Inspector at Cooper Nuclear Power Plant Press Release-IV-21-011, NRC Names New Resident Inspector at the Cooper Nuclear Station2021-08-17017 August 2021 Press Release-IV-21-011: NRC Names New Resident Inspector at the Cooper Nuclear Station Press Release-IV-21-005, NRC to Hold Virtual Meeting to Discuss 2020 Performance of 10 Region IV Nuclear Power Plants2021-04-30030 April 2021 Press Release-IV-21-005: NRC to Hold Virtual Meeting to Discuss 2020 Performance of 10 Region IV Nuclear Power Plants Press Release-IV-20-007, NRC to Hold Virtual Meeting to Discuss 2019 Performance of 12 Region IV Nuclear Power Plants2020-06-22022 June 2020 Press Release-IV-20-007: NRC to Hold Virtual Meeting to Discuss 2019 Performance of 12 Region IV Nuclear Power Plants Press Release-IV-20-002, NRC Names New Senior Resident Inspector at Cooper Nuclear Power Plant2020-01-0606 January 2020 Press Release-IV-20-002: NRC Names New Senior Resident Inspector at Cooper Nuclear Power Plant Press Release-IV-20-001, NRC to Conduct Special Inspection at Cooper Nuclear Power Plant2020-01-0202 January 2020 Press Release-IV-20-001: NRC to Conduct Special Inspection at Cooper Nuclear Power Plant Press Release-IV-17-019, NRC Schedules Regulatory Conference to Discuss Apparent Violation at Cooper Nuclear Station2017-10-26026 October 2017 Press Release-IV-17-019: NRC Schedules Regulatory Conference to Discuss Apparent Violation at Cooper Nuclear Station Press Release-IV-17-018, NRC Names New Resident Inspector at Cooper Nuclear Power Plant2017-09-20020 September 2017 Press Release-IV-17-018: NRC Names New Resident Inspector at Cooper Nuclear Power Plant Press Release-IV-17-003, NRC Will Conduct a Special Inspection at Cooper Nuclear Station2017-03-0606 March 2017 Press Release-IV-17-003: NRC Will Conduct a Special Inspection at Cooper Nuclear Station Press Release-IV-15-029, NRC Names New Senior Resident Inspector at Cooper Nuclear Station2015-11-24024 November 2015 Press Release-IV-15-029: NRC Names New Senior Resident Inspector at Cooper Nuclear Station Press Release-IV-13-016, NRC to Hold Meeting with Nebraska Public Power District on Cooper Nuclear Station2013-06-17017 June 2013 Press Release-IV-13-016: NRC to Hold Meeting with Nebraska Public Power District on Cooper Nuclear Station ML22346A0592012-11-22022 November 2012 News Release-IV-22-014: NRC Names New Senior Resident Inspector at the Cooper Nuclear Station Press Release-IV-12-004, NRC Names New Resident Inspector at Cooper Nuclear Station2012-01-18018 January 2012 Press Release-IV-12-004: NRC Names New Resident Inspector at Cooper Nuclear Station ML1202501352012-01-18018 January 2012 Press Release-IV-12-004: NRC Names New Resident Inspector at Cooper Nuclear Station Press Release-IV-11-045, NRC to Hold Meeting with Nebraska Public Power District on Cooper Nuclear Station2011-10-21021 October 2011 Press Release-IV-11-045: NRC to Hold Meeting with Nebraska Public Power District on Cooper Nuclear Station Press Release-11-166, NRC Issues Mid-Cycle Assessments for Nation'S Nuclear Plants2011-09-0606 September 2011 Press Release-11-166: NRC Issues Mid-Cycle Assessments for Nation'S Nuclear Plants Press Release-IV-11-030, NRC Tracking Flooding at Two Nebraska Nuclear Power Plants2011-06-22022 June 2011 Press Release-IV-11-030: NRC Tracking Flooding at Two Nebraska Nuclear Power Plants Press Release-IV-11-026, NRC to Discuss 2010 Performance Assessment for Cooper Nuclear Station2011-06-13013 June 2011 Press Release-IV-11-026: NRC to Discuss 2010 Performance Assessment for Cooper Nuclear Station Press Release-IV-11-015, NRC to Hold Regulatory Conference with Nebraska Public Power District on Cooper Nuclear Station2011-04-21021 April 2011 Press Release-IV-11-015: NRC to Hold Regulatory Conference with Nebraska Public Power District on Cooper Nuclear Station Press Release-IV-11-014, NRC to Discuss 2010 Performance Assessment for Cooper Nuclear Plant2011-04-20020 April 2011 Press Release-IV-11-014: NRC to Discuss 2010 Performance Assessment for Cooper Nuclear Plant Press Release-IV-11-012, NRC Sends Special Inspection Team to Cooper Nuclear Station2011-04-11011 April 2011 Press Release-IV-11-012: NRC Sends Special Inspection Team to Cooper Nuclear Station Press Release-IV-10-038, NRC Names New Senior Resident Inspector at Cooper Nuclear Station2010-11-17017 November 2010 Press Release-IV-10-038: NRC Names New Senior Resident Inspector at Cooper Nuclear Station Press Release-10-157, NRC Issues Final Safety Evaluation Report for Cooper Nuclear Power Plant License Renewal2010-09-0808 September 2010 Press Release-10-157: NRC Issues Final Safety Evaluation Report for Cooper Nuclear Power Plant License Renewal Press Release-10-140, NRC Issues Final Environmental Impact Statement for Cooper Nuclear Power Plant License Renewal Application2010-08-16016 August 2010 Press Release-10-140: NRC Issues Final Environmental Impact Statement for Cooper Nuclear Power Plant License Renewal Application Press Release-IV-10-017, NRC to Discuss 2009 Performance Assessment for Cooper Nuclear Plant2010-04-22022 April 2010 Press Release-IV-10-017: NRC to Discuss 2009 Performance Assessment for Cooper Nuclear Plant Press Release-IV-10-012, NRC to Hold Public Meeting with Nebraska Public Power District2010-04-0909 April 2010 Press Release-IV-10-012: NRC to Hold Public Meeting with Nebraska Public Power District Press Release-IV-10-008, NRC to Hold Public Meeting with Entergy Operations, Inc2010-03-19019 March 2010 Press Release-IV-10-008: NRC to Hold Public Meeting with Entergy Operations, Inc Press Release-10-031, NRC Seeks Public Input on Draft Environmental Impact Statement for Cooper Nuclear Plant License Renewal; Meetings Scheduled2010-02-18018 February 2010 Press Release-10-031: NRC Seeks Public Input on Draft Environmental Impact Statement for Cooper Nuclear Plant License Renewal; Meetings Scheduled Press Release-IV-09-006, NRC to Discuss 2008 Performance Assessment for Cooper Nuclear Plant2009-03-17017 March 2009 Press Release-IV-09-006: NRC to Discuss 2008 Performance Assessment for Cooper Nuclear Plant Press Release-09-042, NRC Issues Annual Assessments for Nations Nuclear Plants2009-03-0606 March 2009 Press Release-09-042: NRC Issues Annual Assessments for Nations Nuclear Plants Press Release-IV-09-002, NRC Conducting Special Inspection at Cooper Nuclear Station2009-02-23023 February 2009 Press Release-IV-09-002: NRC Conducting Special Inspection at Cooper Nuclear Station Press Release-09-024, NRC Seeks Public Input in Cooper Nuclear Plant License Renewal Application; Meeting Feb 25 in Nebraska2009-02-0909 February 2009 Press Release-09-024: NRC Seeks Public Input in Cooper Nuclear Plant License Renewal Application; Meeting Feb 25 in Nebraska Press Release-08-236, NRC Announces Opportunity to Request Hearing on License Renewal Application for Cooper Nuclear Station2008-12-30030 December 2008 Press Release-08-236: NRC Announces Opportunity to Request Hearing on License Renewal Application for Cooper Nuclear Station Press Release-08-202, License Renewal Application for Cooper Nuclear Plant Available for Public Inspection2008-11-0606 November 2008 Press Release-08-202: License Renewal Application for Cooper Nuclear Plant Available for Public Inspection Press Release-IV-08-034, NRC Finalizes White Finding for Cooper Nuclear Plant2008-08-0404 August 2008 Press Release-IV-08-034: NRC Finalizes White Finding for Cooper Nuclear Plant Press Release-08-124, - NRC Approves Power Uprate for Cooper Nuclear Power Plant2008-07-0202 July 2008 Press Release-08-124 - NRC Approves Power Uprate for Cooper Nuclear Power Plant Press Release-IV-08-028, NRC to Provide Additional Oversight to Cooper Nuclear Station2008-06-16016 June 2008 Press Release-IV-08-028: NRC to Provide Additional Oversight to Cooper Nuclear Station Press Release-IV-08-023, NRC to Discuss 2007 Performance Assessment for Cooper Nuclear Plant2008-05-20020 May 2008 Press Release-IV-08-023: NRC to Discuss 2007 Performance Assessment for Cooper Nuclear Plant Press Release-IV-08-016, NRC to Hold Regulatory Conference with Nebraska Public Power District on Cooper Nuclear Station2008-04-28028 April 2008 Press Release-IV-08-016: NRC to Hold Regulatory Conference with Nebraska Public Power District on Cooper Nuclear Station Press Release-IV-07-030, - NRC Finalizes White Finding for Cooper Nuclear Station2007-08-20020 August 2007 Press Release-IV-07-030 - NRC Finalizes White Finding for Cooper Nuclear Station Press Release-IV-07-020, - NRC to Discuss 2006 Performance Assessment for Cooper Nuclear Station2007-06-18018 June 2007 Press Release-IV-07-020 - NRC to Discuss 2006 Performance Assessment for Cooper Nuclear Station Press Release-IV-07-019, - NRC Names New Resident Inspectors at Cooper Nuclear Station2007-06-12012 June 2007 Press Release-IV-07-019 - NRC Names New Resident Inspectors at Cooper Nuclear Station Press Release-IV-05-037, NRC to Meet with Nebraska Nuclear Power District to Discuss Performance Initiatives at Cooper Nuclear Station2005-10-19019 October 2005 Press Release-IV-05-037: NRC to Meet with Nebraska Nuclear Power District to Discuss Performance Initiatives at Cooper Nuclear Station Press Release-IV-05-027, NRC to Meet with Nebraska Public Power District to Discuss March 14 Fire at Cooper Nuclear Station2005-07-0606 July 2005 Press Release-IV-05-027: NRC to Meet with Nebraska Public Power District to Discuss March 14 Fire at Cooper Nuclear Station Press Release-IV-05-011, NRC to Discuss 2004 Performance at Cooper Nuclear Power Plant2005-04-0808 April 2005 Press Release-IV-05-011: NRC to Discuss 2004 Performance at Cooper Nuclear Power Plant Press Release-IV-05-003, NRC to Meet with Nebraska Public Power District to Discuss Performance Improvement Actions at Cooper Nuclear Station2005-01-19019 January 2005 Press Release-IV-05-003: NRC to Meet with Nebraska Public Power District to Discuss Performance Improvement Actions at Cooper Nuclear Station Press Release-IV-04-038, NRC to Discuss Safety Significance of Inspection Planning at Cooper Nuclear Station2004-09-17017 September 2004 Press Release-IV-04-038: NRC to Discuss Safety Significance of Inspection Planning at Cooper Nuclear Station ML0426100932004-09-17017 September 2004 Press Release-IV-04-038: NRC to Discuss Safety Significance of Inspection Finding at Cooper Nuclear Station Press Release-IV-04-019, NRC to Meet with Nebraska Public Power District to Discuss Recent Inspection at Cooper Nuclear Station2004-04-20020 April 2004 Press Release-IV-04-019: NRC to Meet with Nebraska Public Power District to Discuss Recent Inspection at Cooper Nuclear Station Press Release-IV-04-016, NRC Cites Cooper Nuclear Plant for Inspection Finding of Low to Moderate Safety Significance2004-03-25025 March 2004 Press Release-IV-04-016: NRC Cites Cooper Nuclear Plant for Inspection Finding of Low to Moderate Safety Significance 2023-08-15
[Table view] |
Text
NRC NEWS U.S. NUCLEAR REGULATORY COMMISSION Office of Public Affairs Region IV 612 E. Lamar Blvd., Suite 400 Arlington, TX 76011-4125 Telephone: (817) 860-8128 Site: http://www.nrc.gov Blog: http://public-blog.nrc-gateway.gov No. IV-11-26 June 13, 2011
Contact:
Victor Dricks: (817) 860-8128 E-Mail: OPA4.Resource@nrc.gov Lara Uselding: (817) 276-6519 NRC CITES COOPER NUCLEAR STATION FOR INSPECTION FINDING OF LOW TO MODERATE SAFETY SIGNIFICANCE Cooper Nuclear Station will receive additional oversight from the Nuclear Regulatory Commission because of problems with procedures needed to safely shutdown the plant in the event of some fires. The plant, which is operated by the Nebraska Public Power District (NPPD), is located 23 miles south of Nebraska City, Neb.
NRC inspectors reported that the licensees procedures to manually operate valves that are part of the high pressure coolant injection system would not prove effective in the event of a fire.
The system is an independent emergency cooling system that is one of the means available to provide water to cool the reactor during certain loss of coolant accidents.
Fire protection programs are a critical component in plant safety and the NRC is paying special attention to ensure the licensee takes actions to fully correct this issue, Region IV Administrator Elmo E. Collins said.
The NRC uses a color-coded system to categorize inspection findings. They range from green, for an issue of very low safety significance, to red for a highly significant safety issue.
In this case, the violation has been determined to be white, indicating the issue is of low to moderate safety significance. The finding is based on an NRC inspection completed on March 14.
NRC held a regulatory conference at its Region IV office in Arlington, Texas, on April 27, and based its final significance determination, in part, on information presented there. The NRC will conduct a supplemental inspection at a future date to evaluate the company s corrective actions.
NRC news releases are available through a free list serve subscription at the following Web address: