PSEG Internal Use Only PSEG NUCLEAR L.L.C.
Page 1 of 1 HOPE CREEK GENERATING STATION HC.OP-AR.ZZ-0024(Q) - Rev. 7 CRIDS COMPUTER POINTS BOOK 5 D3624 THRU D4288 USE CATEGORY: II
- Packages and Affected Document Numbers incorporated into this revision:
CP No.
CP Rev.
AD No.
Rev No.
None 9
- The following OPEX were incorporated into this revision: None
- The following OTSCs were incorporated into this revision: None REVISION
SUMMARY
- Adds Operator Action 5 to D3837 to DISPATCH an operator to the Torus Room (RB 4102, 54 ft elev) to check the drywell shell, drywell pedestal, and drains at the bottom of the drywell air gap for leakage. This enhances the monitoring of the drywell shell. This additional step is for an observation and does not impact any actions. This is an editorial change. (20473157)
- Adds an operator action to LOWER fuel pool level back to normal level band IAW HC.OP-SO.EC-0001(Q), Section 5.17 to D3832 and D3833. This action refers to an approved procedure and is editorial. (70104815-0020)
IMPLEMENTATION REQUIREMENTS Effective Date 8/24/10 None
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 1 of 195 Rev. 7 DIGITAL ALARM POINT D3624 NOMENCLATURE MN TURB QUILL SHAFT SETPOINT
>100 rpm FAILURE with <1.5 rpm DESCRIPTION Problem at front standard as ORIGIN Speed elements indicated by conflicting speed indications AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE proper turning gear operation (IF turbine is coasting down, locking out automatic turning gear operation may be necessary to prevent premature engagement.
- 2.
MAINTAIN proper bearing oil header pressure.
CAUSE CORRE CTIVE ACTION
- 1. Quill Shaft failed OR MSOP Shaft/Gear failed 1A. ENSURE TGOP OR EBOP auto starts to maintain bearing header pressure.
1B. REQUEST SM/CRS initiate a NOTF.
Associated Annunciator D3 B5
REFERENCES:
J-0100-0, Sht. 2, Sht. 12, Sht. 13, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 2 of 195 Rev. 7 DIGITAL ALARM POINT D3625 NOMENCLATURE TURBINE GEAR MALF/INOP SETPOINT N/A DESCRIPTION INOP/MALF ORIGIN N/A AUTOMATIC ACTION:
None OPERATOR ACTION:
- 1.
MAINTAIN proper bearing oil header pressure.
- 2.
ENSURE proper Turning Gear operation.
CAUSE CORRE CTIVE ACTION
- 1. Low Speed Switch made up with Turning Gear failure to automatically operate.
1A. Manually START Turning Gear (HS-7110)
WHEN directed by SM/CRS.
1B. DETERMINE cause of failure of automatic operation.
- 2. Loss of control power to DC638 from MCC B323.
2A. DETERMINE cause of power failure AND RESTORE the power, IF possible.
Associated Annunciator D3 B5
REFERENCES:
J-0100-0, Sht. 2, Sht. 12, Sht. 13, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 3 of 195 Rev. 7 DIGITAL ALARM POINT D3626 NOMENCLATURE MN TURB EHC PMP A SETPOINT N/A IN AUTO DESCRIPTION AP116 not in AUTO ORIGIN HS-7064-1 WHEN BP116 is running AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF conditions permit, PLACE AP116 in AUTO (HS-7064-1).
CAUSE CORRE CTIVE ACTION
- 1. AP116 not in AUTO 1A. IF conditions permit, WHEN BP116 is running.
PLACE AP116 in AUTO.
Associated Annunciator D3 F5
REFERENCES:
J-0100-0, Sht. 4, Sht. 17
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 4 of 195 Rev. 7 DIGITAL ALARM POINT D3627 NOMENCLATURE MAIN TURB EHC PUMP A SETPOINT 100 psid FILTER DP DESCRIPTION EHC Pump A discharge filter ORIGIN PDSH-7075 high differential pressure PDSH-7077 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
DISPATCH EO to the EHC skid to investigate the problem.
- 2.
PRESS HYDR FLUID PUMP B MAN Pb.
- 3.
PRESS BP116 START Pb AND ENSURE HDYR FLUID PUMP B LOW DISCH PRESS is OFF.
- 4.
SWAP the AP116 HYDR FLUID PUMP in service Discharge Filter IAW HC.OP-SO.CH-0001(Q).
- 5.
PRESS HYDR FLUID PUMP A(B) STOP Pb.
- 6.
PRESS HYDR FLUID PUMP A(B) AUTO Pb.
CAUSE CORRE CTIVE ACTION
- 1. Clogged filter 1A. CLEAN OR REPLACE the filter.
- 2. Hi hydraulic fluid flow 2A. INVESTIGATE cause of high flow (Possibilities are pump start, system leak, bypass valve open).
Associated Annunciator D3 F5
REFERENCES:
J-0100-0, Sht. 4, Sht. 17 M3TK1-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 5 of 195 Rev. 7 DIGITAL ALARM POINT D3628 NOMENCLATURE MAIN TURB EHC PUMP B SETPOINT N/A IN AUTO DESCRIPTION BP116 not in AUTO ORIGIN HS-7065-1 WHEN AP116 is running AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF conditions permit, PLACE BP116 in AUTO (HS-7065-1).
CAUSE CORRE CTIVE ACTION
- 1. BP116 not in AUTO 1A. IF conditions permit, WHEN AP116 is running.
PLACE BP116 in AUTO.
Associated Annunciator D3 F5
REFERENCES:
J-0100-0, Sht. 5, Sht. 17
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 6 of 195 Rev. 7 DIGITAL ALARM POINT D3629 NOMENCLATURE MAIN TURB EHC PUMP B SETPOINT 100 psid FILTER DP DESCRIPTION EHC Pump B discharge filter ORIGIN PDSH-7076 high differential pressure PDSH-7078 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
DISPATCH EO to the EHC Skid to investigate the problem.
- 2.
PRESS HYDR FLUID PUMP A MAN PB.
- 3.
PRESS AP116 START PB AND ENSURE HYDR FLUID PUMP A LOW DISCH PRESS is off.
- 4.
SWAP the BP116 HYDR FLUID PUMP in service Discharge Filter IAW HC.OP-SO.CH-0001(Q).
- 5.
PRESS HYDR FLUID PUMP B(A) STOP PB.
- 6.
PRESS HYDR FLUID PUMP B(A) AUTO PB.
CAUSE CORRE CTIVE ACTION
- 1. Clogged filter 1A. CLEAN OR REPLACE the filter.
- 2. Hi hydraulic fluid flow 2A. INVESTIGATE cause of high flow (Possibilities are pump start, system leak, bypass valve open).
Associated Annunciator D3 F5
REFERENCES:
J-0100-0, Sht. 5, Sht. 17 M3TKL1-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 7 of 195 Rev. 7 DIGITAL ALARM POINT D3630 NOMENCLATURE SETPOINT
< 1.5 psig STEAM SEAL HEADER PRESSURE LOW DESCRIPTION Steam Seal Hdr Pressure low ORIGIN PSL-1997 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
CHECK PI-1998 STEAM SEAL FEED PRESS indicates approximately 4 psig.
- 2. IF Steam Seal Header Pressure is < 4 psig, PERFORM the following:
- a. IF Main Steam is available, throttle OPEN HV-2001 SEALING STM SUPPLY S/U SHUT OFF VLV BYP until Steam Seal Header Pressure is normal.
- b.
ENSURE HV-2037 SEALING STM SUPPLY AUX STM SHUT OFF is open.
- c. IF Steam Seal Header Pressure cannot be maintained, REDUCE Reactor power AND REFER to HC.OP-AB.BOP-0006(Q), Main Condenser Vacuum.
CAUSE CORRE CTIVE ACTION
- 1. Improper valve lineup 1A. ENSURE that the following valves are open:
1.1A PSL-1997 Instrument Root Vlv 1.2A 1CA-V012 1.3A HV-1999 1.4A HV-1991 1.5A 1CA-V162
- 2. Loss of heating steam 2A. RESTORE Main or Auxiliary Steam supply WHEN possible.
- 3. PIC-2038 improperly set 3A. REQUEST SM/CRS to initiate corrective action.
Associated with Annunciator C8 F4
REFERENCES:
M-29-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 8 of 195 Rev. 7 DIGITAL ALARM POINT D3631 NOMENCLATURE SETPOINT
< 5WC VAC SPE CONDENSER HIGH PRESSURE DESCRIPTION ORIGIN PSH-1988 Stm Packing Exhaust Condenser pressure high AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN Steam Packing Exhaust Condenser pressure at 10-12 inches H2O as indicated on A2499.
- 2. IF A2499 indicates pressure oscillations are occurring, THEN PERFORM the following:
- a. Throttle OPEN V026 (V025) to increase vacuum until pressure oscillations stop.
(Vacuum may be increased to a maximum of 20 inches H2O.)
CAUSE CORRE CTIVE ACTION
- 1. Stm Packing Exhaust Fan not running 1A. ENSURE that Stm Exhaust Fan A(B)K103 is running.
- 2. Exhaust fan inlet valve closed 2A. ENSURE that valves V026 (V025) are open.
- 3. Drain Trap DT144 clogged 3A. CLEAN AND REPLACE drain trap.
- 4. Condenser Water inlet/outlet valves closed 4A. ENSURE that (CONDENSATE - PRI CNDS FLOW PATH) HV-1660& HV-1661 OPEN is on. (Pnl 10C651C)
- 5. Loss of coolant water to Condenser 5A. ENSURE Condensate System is in service IAW HC.OP-SO.AP-0001(Q).
Associated with Annunciator C8 F4
REFERENCES:
J-29-0, Sht. 7 M-29-1 M-05-1, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 9 of 195 Rev. 7 DIGITAL ALARM POINT D3632 NOMENCLATURE SSE LEVEL HI HI SETPOINT 12" (80% indicated on LI-2010)
DESCRIPTION Stm Seal Evap lvl high high ORIGIN LSHH-2010 AUTOMATIC ACTION:
HV-2013 STEAM SEAL EVAP FEED WTR VLV closes.
OPERATOR ACTION:
- 1. IF required, MAINTAIN Steam Seal Evaporator level manually by throttling HV-2024 STEAM SEAL EVAP FEED WTR BYP VLV as necessary to maintain LI-2010 (MAIN STEAM INDICATION) STEAM SEAL EVAPORATOR LEVEL at 50%.
- 2. IF required, TRANSFER Sealing Steam to Auxiliary Steam System as follows:
- a.
ENSURE Auxiliary Steam is available.
- b.
ENSURE HV-2037 SEALING STM SUPPLY AUX STM SHUT OFF is open.
- c.
CLOSE HV-1999 SEALING STM SUPPLY STM SEAL EVAP SHUT OFF.
CAUSE CORRE CTIVE ACTION
- 1. Level Control Valve LV-2003 fail opened 1A. ENSURE instrument air is available for Control Valve.
1B. REQUEST SM/CRS to initiate corrective action.
- 2. Level instrument LT-2010 root valves not opened 2A. ENSURE V157 & V158 are open.
Associated with Annunciator C8 F4
REFERENCES:
J-29-0, Sht. 2, Sht. 4, Sht. 7 Drawing J-L-5000 Sheet 247 M-29-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 10 of 195 Rev. 7 DIGITAL ALARM POINT D3633 - D3643 NOMENCLATURE Room Damper Status (see below)
SETPOINT Closed DESCRIPTION ORIGIN D3633 STM TUNNEL RM 4316 ISLN DMPR 1 GUZS-9428A1 D3635 STM TUNNEL RM 4316 ISLN DMPR 2 GUZS-9428A2 D3637 HEAT EXCH ROOM 4506 DAMPER 1 GUZS-9429A1 D3639 HEAT EXCH ROOM 4506 DAMPER 2 GUZS-9429A2 D3641 RHR PUMP ROOM 4113 DAMPER 1 GUZS-9432A1 D3643 RHR PUMP ROOM 4113 DAMPER 2 GUZS-9432A2 AUTOMATIC ACTION Alarm Only OPERATOR ACTION
- 1.
NOTIFY SM/CRS of alarm condition.
- 2.
REFER to HC.OP-AB.CONT-0003, Reactor Building, HC.OP-AB.BOP-0005 Main Steam Tunnel Temperature, OR EOP-103 as appropriate.
- 3.
DIRECT Operator to monitor operation of exhaust dampers.
CAUSE CORRE CTIVE ACTION
- 1. Room High Temperature.
1A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E1 F5
REFERENCES:
M-84-1 sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 11 of 195 Rev. 7 DIGITAL ALARM POINT D3644 - D3661 NOMENCLATURE SENSOR FAILURE SETPOINT N/A DESCRIPTION CRT analog/digital point and ORIGIN Various nomenclature displayed in red AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
DETERMINE the digital point in alarm AND REQUEST SM/CRS to initiate corrective action.
CAUSE CORRE CTIVE ACTION
- 1. A single process instrument input to the 2/3 Feedwater Logic is in the TRIPPED state for one or more of the parameters listed on the first two pages of Attachment F5.
1A. REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B1 F5
REFERENCES:
E-6765-0, Sht. 2 E-6797-0, Sht. A J-31-0, Sht. 6; 7, 8; 13, 14 J-108-0, Sht. 12 N1-C32-1050-12, Sht. 7
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 12 of 195 Rev. 7 DIGITAL ALARM POINT D3668 NOMENCLATURE DRYWELL CLR FAN A TROUBLE SETPOINT 1.2 inches water gauge DESCRIPTION Drywell Cooler Fan(s) malfunction ORIGIN PDSL-9463A1 thru 9463H1 AUTOMATIC ACTION:
Standby fan auto starts.
OPERATOR ACTION:
- 1. NOTIFY SM/CRS of alarm condition.
- 2. IF necessary, ENTER HC.OP-AB.CONT-0001(Q), Drywell Pressure.
- 3. DETERMINE the Drywell Cooler that initiated the trouble alarm.
- 4. IF Drywell Cooler Fan(s) is stopped AND power is available, THEN ATTEMPT to restart.
CAUSE CORRE CTIVE ACTION
ENSURE power AND control power are available to the Drywell Cooler Fan Motor(s).
- 2.
Low flow condition 2A.
DETERMINE IF a low flow condition exists by observing Control Room indication.
- 3. Fan trip 3A.
RESET breaker IAW OP-HC-108-106-1001, Equipment Operational Control AND RESTART.
3B.
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E6 A2
REFERENCES:
H-86-0, Sht. 1, 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 13 of 195 Rev. 7 DIGITAL ALARM POINT D3671 NOMENCLATURE INTAKE STRUCTURE HVAC TROUBLE SETPOINT Various DESCRIPTION Intake Structure HVAC Panel 1EC581 Trouble ORIGIN 1EC581 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. DISPATCH Equipment Operator to Intake Structure HVAC Panel 1EC581 to determine cause of alarm.
- 2. ENSURE compliance with the Service Water operability requirements of Technical Specifications 3.7.1.2.
CAUSE CORRECTIVE ACTION
- 1. Intake Structure Supply Fan Low Flow 1A. RESPOND IAW HC.OP-SO.GQ-0001(Q);
Service Water Intake Structure Ventilation
- 2. Intake Structure Exhaust Fan Low Flow System Operation.
- 3. Traveling Screen Motor Room Fan Low Flow
- 4. Traveling Screen Motor Room High/Low Temperature Associated Annunciator A1 F1
REFERENCES:
E-6792 H-95-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 14 of 195 Rev. 7 DIGITAL ALARM POINT D3678 NOMENCLATURE Room Damper Status SETPOINT Closed DESCRIPTION RHR PUMP ROOM 4109 DAMPER 1 ORIGIN GUZS-9433A1 AUTOMATIC ACTION Alarm Only OPERATOR ACTION
- 1.
NOTIFY SM/CRS of alarm condition.
- 2.
REFER to HC.OP-AB.CONT-0003, Reactor Building, HC.OP-AB.BOP-0005 Main Steam Tunnel Temperature, OR EOP-103 as appropriate.
- 3.
DIRECT Operator to monitor operation of exhaust dampers.
CAUSE CORRE CTIVE ACTION
- 1. Room High Temperature.
1A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E1 F5
REFERENCES:
M-84-1 sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 15 of 195 Rev. 7 DIGITAL ALARM POINT D3680 NOMENCLATURE Room Damper Status SETPOINT Closed DESCRIPTION RHR PUMP ROOM 4109 DAMPER 2 ORIGIN GUZS-9433A2 AUTOMATIC ACTION Alarm Only OPERATOR ACTION
- 1.
NOTIFY SM/CRS of alarm condition.
- 2.
REFER to HC.OP-AB.CONT-0003, Reactor Building, HC.OP-AB.BOP-0005 Main Steam Tunnel Temperature, OR EOP-103 as appropriate.
- 3.
DIRECT Operator to monitor operation of exhaust dampers.
CAUSE CORRE CTIVE ACTION
- 1. Room High Temperature.
1A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E1 F5
REFERENCES:
M-84-1 sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 16 of 195 Rev. 7 DIGITAL ALARM POINT D3694 - D3698 NOMENCLATURE Room Damper Status (see below)
SETPOINT Closed DESCRIPTION ORIGIN D3694 PIPE CHASE 4327 ISLN DAMPER 1 GUZS-9437A1 D3696 PIPE CHASE 4327 ISLN DAMPER 2 GUZS-9437A2 D3698 PIPE CHASE 4329 ISLN DAMPER 1 GUZS-9439A1 AUTOMATIC ACTION Alarm Only OPERATOR ACTION
- 1.
NOTIFY SM/CRS of alarm condition.
- 2.
REFER to HC.OP-AB.CONT-0003, Reactor Building, HC.OP-AB.BOP-0005 Main Steam Tunnel Temperature, OR EOP-103 as appropriate.
- 3.
DIRECT Operator to monitor operation of exhaust dampers.
CAUSE CORRE CTIVE ACTION
- 1. Room High Temperature.
1A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E1 F5
REFERENCES:
M-84-1 sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 17 of 195 Rev. 7 DIGITAL ALARM POINT D3699 NOMENCLATURE SETPOINT N/A HPCI VAC BRKR ISLN HV-F075 DESCRIPTION ORIGIN ZS-F075 HPCI Vac Breaker Vlv HV-F075 not fully open AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE limiting conditions for operation of Emergency Core Cooling Systems in accordance with Technical Specifications 3/4.5.1.
CAUSE CORRE CTIVE ACTION
- 1. Vacuum Breaker Valve HV-F075 closed 1A. OPEN HV-F075 VAC BRKR ISLN VLV, WHEN possible Associated Annunciator B1 D5
REFERENCES:
J-55-0, Sht. 11
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 18 of 195 Rev. 7 DIGITAL ALARM POINT D3700 - 3702 NOMENCLATURE Room Damper Status (see below)
SETPOINT Closed DESCRIPTION ORIGIN D3700 PIPE CHASE 4329 ISLN DAMPER 2 GUZS-9439A2 D3702 TORUS ROOM 4102 ISLN DAMPER 1 GUZS-9436A1 AUTOMATIC ACTION Alarm Only OPERATOR ACTION
- 1.
NOTIFY SM/CRS of alarm condition.
- 2.
REFER to HC.OP-AB.CONT-0003, Reactor Building, HC.OP-AB.BOP-0005 Main Steam Tunnel Temperature, OR EOP-103 as appropriate.
- 3.
DIRECT Operator to monitor operation of exhaust dampers.
CAUSE CORRE CTIVE ACTION
- 1. Room High Temperature.
1A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E1 F5
REFERENCES:
M-84-1 sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 19 of 195 Rev. 7 DIGITAL ALARM POINT D3725 NOMENCLATURE Room Damper Status (see below)
SETPOINT Closed DESCRIPTION TORUS ROOM 4102 ISLN ORIGIN GUZS-9436A2 DAMPER 2 AUTOMATIC ACTION Alarm Only OPERATOR ACTION
- 1.
NOTIFY SM/CRS of alarm condition.
- 2.
REFER to HC.OP-AB.CONT-0003, Reactor Building, HC.OP-AB.BOP-0005 Main Steam Tunnel Temperature, OR EOP-103 as appropriate.
- 3.
DIRECT Operator to monitor operation of exhaust dampers.
CAUSE CORRE CTIVE ACTION
- 1. Room High Temperature.
1A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E1 F5
REFERENCES:
M-84-1 sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 20 of 195 Rev. 7 DIGITAL ALARM POINT D3731 - D3733 NOMENCLATURE Room Damper Status (see below)
SETPOINT Closed DESCRIPTION ORIGIN D3731 HPCI PMP RM 4111 ISLN DAMPER 1 GUZS-9434A1 D3733 HPCI PMP RM 4111 ISLN DAMPER 2 GUZS-9434A2 AUTOMATIC ACTION Alarm Only OPERATOR ACTION
- 1.
NOTIFY SM/CRS of alarm condition.
- 2.
REFER to HC.OP-AB.CONT-0003, Reactor Building, HC.OP-AB.BOP-0005 Main Steam Tunnel Temperature, OR EOP-103 as appropriate.
- 3.
DIRECT Operator to monitor operation of exhaust dampers.
CAUSE CORRE CTIVE ACTION
- 1. Room High Temperature.
1A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E1 F5
REFERENCES:
M-84-1 sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 21 of 195 Rev. 7 DIGITAL ALARM POINT D3737 NOMENCLATURE CW PUMP A DISCHARGE SETPOINT N/A HV-2152A DESCRIPTION CW Pump discharge valve not in the proper position ORIGIN Logic Cabinet 1AC653 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
MONITOR CW Pump amps AND discharge valve position.
CAUSE CORRE CTIVE ACTION
- 1. Malfunction of the CW Pump Discharge Valve Hydraulic Control Unit 1A. DISPATCH an operator to inspect the discharge valve, Hydraulic Control Unit, AND associated hydraulic piping for leaks.
- 2. Bound discharge valve 2A. REQUEST the CRS to initiate corrective action.
- 3. Malfunction of the valve position logic 3A. Same as 2A above.
- 4. Malfunctioning limit switch 4A. Same as 2A above.
Associated Annunciator A2 D4
REFERENCES:
M-09-0, Sht. 1 J-09-0, Sht. 7, Sht. 16
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 22 of 195 Rev. 7 DIGITAL ALARM POINT D3738 NOMENCLATURE CS B 24VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray B 24VDC isolator power loss ORIGIN N/A or input card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored Digital Point/
Indication Nomenclature Alarm Window Engraving D3756 CS B MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3757 CS CHAN B INVERTER POWER FAIL CORE SPRAY LOOP B TROUBLE D3159 CS LOOP B INJECTION LINE PRESS CORE SPRAY LOOP B TROUBLE D5492 RHR B/CS B/RCIC ALM TEST/INOP ECCS B/RCIC TRIP UNIT TEST/INOP D3768 CORE SPRAY CHAN B AUTO START CORE SPRAY PUMP B START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 23 of 195 Rev. 7 DIGITAL ALARM POINT D3738 CAUSE CORRECTIVE ACTION
- 1.
Input isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action.
- 2. Breaker tripped 2A.
CHECK AND UNDER the direction of SM/CRS RESET IF necessary, 120VAC Instrument Bus B 1BJ481, Breaker 1BJ481-18.
- 3. Blown fuse 3A.
CHECK AND REPLACE IF necessary, 10 amps fuse F41B at Panel C618.
3B.
CHECK AND REPLACE IF necessary, 5 amps fuse F44B at Panel C618.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 24 of 195 Rev. 7 DIGITAL ALARM POINT D3739 NOMENCLATURE CS B 125VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray B 125VDC isolator power loss ORIGIN N/A or output card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored Digital Point/
Indication Nomenclature Alarm Window Engraving D3756 CS B MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3757 CS CHAN B INVERTER POWER FAIL CORE SPRAY LOOP B TROUBLE D3159 CS LOOP B INJECTION LINE PRESS CORE SPRAY LOOP B TROUBLE D5492 RHR B/CS B/RCIC ALM TEST/INOP ECCS B/RCIC TRIP UNIT TEST/INOP D3768 CORE SPRAY CHAN B AUTO START CORE SPRAY PUMP B START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 25 of 195 Rev. 7 DIGITAL ALARM POINT D3739 CAUSE CORRECTIVE ACTION
- 1.
Output isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action.
- 2. Breaker Tripped 2A.
REFER TO HC.OP-AB.MISC-0002(Q)
Crids / Overhead Annunciators.
2B.
REQUEST SM/CRS to initiate corrective action.
- 3. Blown fuse 3A.
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 26 of 195 Rev. 7 DIGITAL ALARM POINT D3756 NOMENCLATURE CS B MANUAL INIT SWITCH ARMED SETPOINT N/A DESCRIPTION CS B Manual Initiation Switch armed ORIGIN S22B MAN INIT SW AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF manual initiation is not required, THEN DISARM B MAN INIT.
CAUSE CORRE CTIVE ACTION
- 1.
CS B Manual Initiation Switch armed 1A.
IF manual initiation is not required, THEN DISARM the switch.
Associated Annunciator B3 C5
REFERENCES:
J-52-0, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 27 of 195 Rev. 7 DIGITAL ALARM POINT D3757 NOMENCLATURE CS CHAN B INVERTER PWR FAIL SETPOINT N/A DESCRIPTION Loss of power from Inverter 1BD481 ORIGIN N/A AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
OBSERVE which instrument indication and alarms have been lost (Chan B).
- 2.
ENSURE compliance with the operability requirements of T/S 3.5.1 and 3.6.3.
CAUSE CORRE CTIVE ACTION NOTE Re-energization of the ECCS Trip Units will result in an ESF actuation, NOTIFY I&C to disable the trip units prior to re-energization.
- 1. Breaker tripped.
1A.
IF tripped, DETERMINE cause AND RESET.
1B.
CHECK CB 1BJ481-18 Vert Bd, RHR & CS Rly 10C618.
- 2. Fuse Blown 2A.
CHECK fuse 9B in Panel 10C618
- 3. Inverter Failure 3A.
REFER TO Inverter 1BD481 operating procedure HC.OP-SO.PN-0001(Q)
Associated Annunciator B3 C3
REFERENCES:
N1-A41-46-(1)-2 J-52-0, Sht. 7, Sht. 8 M-52-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 28 of 195 Rev. 7 DIGITAL ALARM POINT D3758 NOMENCLATURE CS C 24VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray C 24VDC isolator power loss ORIGIN N/A or input card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored Digital Point/
Indication Nomenclature Alarm Window Engraving D3760 CS C MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3761 CS CHAN C INVERTER POWER FAIL CORE SPRAY LOOP A TROUBLE D5493 RHR C TRIP UNIT IN TEST/INOP RHR C TRIP UNIT TEST/ INOP D3769 CORE SPRAY CHAN C AUTO START CORE SPRAY PUMP C START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)-11 J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 29 of 195 Rev. 7 DIGITAL ALARM POINT D3758 CAUSE CORRE CTIVE ACTION
- 1.
Input isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action.
- 2. Breaker tripped 2A.
CHECK AND UNDER the direction of SM/CRS RESET IF necessary, 120VAC Instrument Bus C 1CJ481, Breaker 1CJ481-20.
- 3. Blown fuse 3A.
CHECK AND REPLACE IF necessary, 10 amps fuse F41A at Panel C617.
3B.
CHECK AND REPLACE IF necessary, 5 amps fuse F44A at Panel C617.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 30 of 195 Rev. 7 DIGITAL ALARM POINT D3759 NOMENCLATURE CS C 125VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray C 125VDC isolator power loss ORIGIN N/A or output card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored Digital Point/
Indication Nomenclature Alarm Window Engraving D3760 CS C MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3761 CS CHAN C INVERTER POWER FAIL CORE SPRAY LOOP A TROUBLE D5493 RHR C TRIP UNIT IN TEST/INOP RHR C TRIP UNIT TEST / INOP D3769 CORE SPRAY CHAN C AUTO START CORE SPRAY PUMP C START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 31 of 195 Rev. 7 DIGITAL ALARM POINT D3759 CAUSE CORRECTIVE ACTION
- 1.
Output isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action.
- 2. Breaker Tripped 2A.
REFER TO HC.OP-AB.MISC-0002(Q)
Crids / Overhead Annunciators 2B.
REQUEST SM/CRS to initiate corrective action.
- 3. Blown fuses 3A.
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 32 of 195 Rev. 7 DIGITAL ALARM POINT D3760 NOMENCLATURE CS C MANUAL INIT SWITCH ARMED SETPOINT N/A DESCRIPTION CS C Manual Initiation Switch armed ORIGIN S22C MAN INIT SW AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF manual initiation is not required, THEN DISARM C MAN INIT.
CAUSE CORRE CTIVE ACTION
- 1.
CS C Manual Initiation Switch armed 1A.
IF manual initiation is not required, THEN DISARM the switch.
Associated Annunciator B3 C5
REFERENCES:
J-52-0, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 33 of 195 Rev. 7 DIGITAL ALARM POINT D3761 NOMENCLATURE CS CHAN C INVERTER PWR FAIL SETPOINT N/A DESCRIPTION Loss of power from inverter1CD481 ORIGIN N/A AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
OBSERVE which instrument indication and alarms have been lost (Chan C).
- 2.
ENSURE compliance with the operability requirements of T/S 3.5.1 and 3.6.3.
CAUSE CORRE CTIVE ACTION NOTE Re-energization of the ECCS Trip Units will result in an ESF actuation, NOTIFY I&C to disable the trip units prior to re-energization.
- 1. Breaker tripped.
1A.
IF tripped, DETERMINE cause AND RESET.
1B.
CHECK CB 1CJ481-20 Vert Bd, RHR & CS Rly 10C641.
- 2. Fuse Blown 2A.
CHECK fuse 9C in Panel 10C641
- 3.
Inverter Failure 1CD481 3A.
REFER TO Inverter operating procedure HC.OP-SO.PN-0001(Q).
Associated Annunciator B3 C1
REFERENCES:
N1-A41-46-(1)-2 J-52-0, Sht. 7, Sht. 8 M-52-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 34 of 195 Rev. 7 DIGITAL ALARM POINT D3762 NOMENCLATURE CS D 24VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray D 24VDC isolator power loss ORIGIN N/A or input card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored Digital Point/
Indication Nomenclature Alarm Window Engraving D3764 CS D MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3765 CS CHAN D INVERTER POWER FAIL CORE SPRAY LOOP B TROUBLE D5490 RHR D TRIP UNIT IN TEST/INOP RHR D TRIP UNIT TEST/ INOP D3766 CORE SPRAY CHAN D AUTO START CORE SPRAY PUMP D START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 35 of 195 Rev. 7 DIGITAL ALARM POINT D3762 CAUSE CORRECTIVE ACTION
- 1.
Input isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action.
- 2. Breaker tripped 2A.
CHECK AND UNDER the direction of SM/CRS RESET if necessary, 120VAC Instrument Bus D 1DJ481, Breaker 1DJ481-20.
- 3. Blown fuse 3A.
CHECK AND REPLACE IF necessary, 10 amps fuse F41D at Panel C640.
3B.
CHECK AND REPLACE IF necessary, 5 amps fuse F44D at Panel 10C640.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 36 of 195 Rev. 7 DIGITAL ALARM POINT D3763 NOMENCLATURE CS D 125VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray D 125VDC isolator power loss ORIGIN N/A or output card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored.
Digital Point/
Indication Nomenclature Alarm Window Engraving D3764 CS D MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3765 CS CHAN D INVERTER POWER FAIL CORE SPRAY LOOP B TROUBLE D5490 RHR D TRIP UNIT IN TEST/INOP RHR D TRIP UNIT TEST/ INOP D3766 CORE SPRAY CHAN D AUTO START CORE SPRAY PUMP D START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 37 of 195 Rev. 7 DIGITAL ALARM POINT D3763 CAUSE CORRECTIVE ACTION
- 1.
Output isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action.
- 2. Breaker Tripped 2A.
REFER TO HC.OP-AB.MISC-0002(Q)
Crids / Overhead Annunciators.
2B.
REQUEST SM/CRS to initiate corrective action.
- 3. Blown fuse 3A.
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 38 of 195 Rev. 7 DIGITAL ALARM POINT D3764 NOMENCLATURE CS D MANUAL INIT SWITCH ARMED SETPOINT N/A DESCRIPTION CS D Manual Initiation Switch armed ORIGIN S22D MAN INIT SW AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF manual initiation is not required, THEN DISARM D MAN INIT.
CAUSE CORRECTIVE ACTION
- 1.
CS D Manual Initiation Switch armed 1A.
IF manual initiation is not required, THEN DISARM the switch.
Associated Annunciator B3 C5
REFERENCES:
J-52-0, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 39 of 195 Rev. 7 DIGITAL ALARM POINT D3765 NOMENCLATURE CS CHAN D INVERTER PWR FAIL SETPOINT N/A DESCRIPTION Loss of power from Inverter 1DD-481 ORIGIN N/A AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
OBSERVE which instrument indication and alarms have been lost (Chan D).
- 2.
ENSURE compliance with the operability requirements of T/S 3.5.1 and 3.6.3.
CAUSE CORRECTIVE ACTION NOTE Re-energization of the ECCS Trip Units will result in an ESF actuation, NOTIFY I&C to disable the trip units prior to re-energization.
- 1. Breaker tripped.
1A.
IF tripped, DETERMINE cause AND RESET.
1B.
CHECK CB 1DJ481-20 Vert Bd, RHR & CS Rly 10C640.
- 2. Fuse Blown 2A.
CHECK fuse 9A in Panel 10C640.
- 3. Inverter Failure 3A.
REFER TO Inverter 1DD481 operating procedure HC.OP-SO.PN-0001(Q)
Associated Annunciator B3 C3
REFERENCES:
N1-A41-46-(1)-2 J-52-0, Sht. 7, Sht. 8 M-52-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 40 of 195 Rev. 7 DIGITAL ALARM POINT D3766 NOMENCLATURE CORE SPRAY CHAN D AUTO START SETPOINT
-129" RPV(or)
Drywell Pressure 1.68 psig DESCRIPTION Core Spray Pump D running ORIGIN LIS-691D or H (or) PIS-N694D or H 1/2 Twice Logic AUTOMATIC ACTION:
Core Spray Pump D starts AND Emergency Diesel Generator "D" starts.
OPERATOR ACTION:
- 1.
ENSURE valid initiation signal is present.
- 2. IF not, THEN STOP DP206 CORE SPRAY PUMP D.
- 3.
ENSURE compliance with operability requirements of T/S 3.5.1.
- 4.
VERIFY actuations/isolations IAW HC.OP-SO.SM-0001(Q), Isolation Systems Operation.
CAUSE CORRE CTIVE ACTION
- 1.
Valid initiation signal 1A.
ENSURE that Core Spray Pump D has started.
1B.
REFER TO HC.OP-EO.ZZ-0101(Q) and/or HC.OP-EO.ZZ-0102(Q) as applicable.
- 2.
Malfunction of originating device 2A.
STOP Core Spray Pump D AND REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 A4
REFERENCES:
GEK Vol. VII, Part 1 J-52-0, Sht. 7 M-42-1 Sht. 2
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 41 of 195 Rev. 7 DIGITAL ALARM POINT D3767 NOMENCLATURE CORE SPRAY CHAN A AUTO START SETPOINT
-129" RPV (or)
Drywell Pressure 1.68 psig DESCRIPTION Core Spray Pump A running ORIGIN LIS-N691A or E (or) PIS-N694A or E 1/2 Twice Logic AUTOMATIC ACTION:
Core Spray Pump A starts AND Emergency Diesel Generator "A" starts.
OPERATOR ACTION:
- 1.
ENSURE valid initiation signal is present.
- 2. IF not, THEN STOP AP206 CORE SPRAY PUMP A.
- 3.
ENSURE compliance with operability requirements of T/S 3.5.1.
- 4.
VERIFY actuations/isolations IAW HC.OP-SO.SM-0001(Q), Isolation Systems Operation.
CAUSE CORRE CTIVE ACTION
- 1.
Valid initiation signal 1A.
ENSURE that Core Spray Pump A has started.
1B.
REFER TO HC.OP-EO.ZZ-0101(Q) and/or HC.OP-EO.ZZ-0102(Q) as applicable.
- 2.
Malfunction of originating device 2A.
STOP Core Spray Pump A AND REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 A1
REFERENCES:
GEK Vol. VII, Part 1 J-52-0, Sht. 7 M-42-1, Sht. 2
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 42 of 195 Rev. 7 DIGITAL ALARM POINT D3768 NOMENCLATURE CORE SPRAY CHAN B AUTO START SETPOINT
-129" RPV(or)
Drywell Pressure 1.68 psig DESCRIPTION Core Spray Pump B running ORIGIN LIS-N691B or F (or) PIS-N694B or F 1/2 Twice Logic AUTOMATIC ACTION:
Core Spray Pump B starts AND Emergency Diesel Generator "B" starts.
OPERATOR ACTION:
- 1.
ENSURE valid initiation signal is present.
- 2. IF not, THEN STOP BP206 CORE SPRAY PUMP B.
- 3.
ENSURE compliance with operability requirements of T/S 3.5.1.
- 4.
VERIFY actuations/isolations IAW HC.OP-SO.SM-0001(Q), Isolation Systems Operation.
CAUSE CORRE CTIVE ACTION
- 1.
Valid initiation signal 1A.
ENSURE that Core Spray Pump B has started.
1B.
REFER TO HC.OP-EO.ZZ-0101(Q) and/or HC.OP-EO.ZZ-0102(Q) as applicable.
- 2.
Malfunction of originating device 2A.
STOP Core Spray Pump B AND REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 A3
REFERENCES:
GEK Vol. VII, Part 1 J-52-0, Sht. 7 M-42-1 Sht. 2
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 43 of 195 Rev. 7 DIGITAL ALARM POINT D3769 NOMENCLATURE CORE SPRAY CHAN C AUTO START SETPOINT
-129" RPV (or)
Drywell Pressure 1.68 psig DESCRIPTION Core Spray Pump C running ORIGIN LIS-N691C or G (or) PIS-N694C or G 1/2 Twice Logic AUTOMATIC ACTION:
Core Spray Pump C starts AND Emergency Diesel Generator "C" starts.
OPERATOR ACTION:
- 1.
ENSURE valid initiation signal is present.
- 2. IF not, THEN STOP CP206 CORE SPRAY PUMP C.
- 3.
ENSURE compliance with operability requirements of T/S 3.5.1.
- 4.
VERIFY actuations/isolations IAW HC.OP-SO.SM-0001(Q), Isolation Systems Operation.
CAUSE CORRE CTIVE ACTION
- 1.
Valid initiation signal 1A.
ENSURE that Core Spray Pump C has started.
1B.
REFER TO HC.OP-EO.ZZ-0101(Q) and/or HC.OP-EO.ZZ-0102(Q) as applicable.
- 2.
Malfunction of originating device 2A.
STOP Core Spray Pump C AND REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 A2
REFERENCES:
GEK Vol. VII, Part 1 J-52-0, Sht. 7 M-42-1 Sht. 2
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 44 of 195 Rev. 7 DIGITAL ALARM POINT D3770 NOMENCLATURE CS A 24VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray A 24VDC isolator power loss or ORIGIN N/A input card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored Digital Point/
Indication Nomenclature Alarm Window Engraving D3772 CS A MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3158 CS LOOP A OR B LINE BREAK CORE SPRAY LINE BREAK D3773 CS CHAN A INVERTER POWER FAIL CORE SPRAY LOOP A TROUBLE D3157 CS LOOP A INJECTION LINE PRESS CORE SPRAY LOOP A TROUBLE D5491 RHR A/CS A/HPCI ALM TEST/INOP ECCS A/HPCI TRIP UNIT TEST/INOP D3767 CORE SPRAY CHAN A AUTO START CORE SPRAY PUMP A START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)-11 J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 45 of 195 Rev. 7 DIGITAL ALARM POINT D3770 CAUSE CORRE CTIVE ACTION
- 1.
Input isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action
- 2. Breaker tripped 2A.
CHECK AND UNDER the direction of SM/CRS, RESET IF necessary, 120VAC Instrument Bus A 1AJ481, Breaker 1AJ481-19.
- 3. Blown fuse 3A.
CHECK AND REPLACE IF necessary, 10 amps fuse F41A at Panel C617.
3B.
CHECK AND REPLACE IF necessary, 5 amps fuse F44A at Panel C617.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)-11 J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 46 of 195 Rev. 7 DIGITAL ALARM POINT D3771 NOMENCLATURE CS A 125VDC PWR LOSS/CARD OUT SETPOINT N/A DESCRIPTION Core Spray A 125VDC isolator power loss ORIGIN N/A or output card out of file AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Emergency Core Cooling Systems operability limits of T/S 3.5.1.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored Digital Point/
Indication Nomenclature Alarm Window Engraving D3772 CS A MANUAL INIT SWITCH ARMED CORE SPRAY MANUAL INIT SW ARMED D3158 CS LOOP A OR B LINE BREAK CORE SPRAY LINE BREAK D3773 CS CHAN A INVERTER POWER FAIL CORE SPRAY LOOP A TROUBLE D3157 CS LOOP A INJECTION LINE PRESS CORE SPRAY LOOP A TROUBLE D5491 RHR A/CS A/HPCI ALM TEST/INOP ECCS A/HPCI TRIP UNIT TEST/INOP D3767 CORE SPRAY CHAN A AUTO START CORE SPRAY PUMP A START Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 47 of 195 Rev. 7 DIGITAL ALARM POINT D3771 CAUSE CORRE CTIVE ACTION
- 1.
Output isolator card out of file 1A.
CHECK the file for missing card AND IF missing, REQUEST SM/CRS to initiate corrective action.
- 2. Breaker Tripped 2A.
REFER TO HC.OP-AB.MISC-0002(Q)
Crids / Overhead Annunciators.
2B.
REQUEST SM/CRS to initiate corrective action.
- 3. Blown fuses 3A.
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B3 C4
REFERENCES:
N1-E21-1040-383(6A)
J-52-0, Sht. 7, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 48 of 195 Rev. 7 DIGITAL ALARM POINT D3772 NOMENCLATURE CS A MANUAL INIT SWITCH ARMED SETPOINT N/A DESCRIPTION CS A Manual Initiation Switch armed ORIGIN S22A MAN INIT SW AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF manual initiation is not required, THEN DISARM A MAN INIT.
CAUSE CORRE CTIVE ACTION
- 1.
CS A Manual Initiation Switch armed 1A.
IF manual initiation is not required, THEN DISARM the switch.
Associated Annunciator B3 C5
REFERENCES:
J-52-0, Sht. 6
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 49 of 195 Rev. 7 DIGITAL ALARM POINT D3773 NOMENCLATURE CS CHAN A INVERTER PWR FAIL SETPOINT N/A DESCRIPTION Loss of power from inverter1AD481 ORIGIN N/A AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
OBSERVE which instrument indication and alarms have been lost (Chan A).
- 2.
ENSURE compliance with the operability requirements of T/S 3.5.1 and 3.6.3.
CAUSE CORRECTIVE ACTION NOTE Re-energization of the ECCS Trip Units will result in an ESF actuation, NOTIFY I&C to disable the trip units prior to re-energization.
- 1. Breaker tripped.
1A.
IF tripped, DETERMINE cause AND RESET.
1B.
CHECK CB 1AJ481-19 Vert Bd, RHR & CS Rly 10C617.
- 2. Fuse Blown 2A.
CHECK fuse 9A in Panel 10C617
- 3.
Inverter Failure 1AD481 3A.
REFER TO Inverter operating procedure HC.OP-SO.PN-0001(Q).
Associated Annunciator B3 C1
REFERENCES:
N1-A41-46-(1)-2 J-52-0, Sht. 7, Sht. 8 M-52-1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 50 of 195 Rev. 7 DIGITAL ALARM POINT D3827 NOMENCLATURE FUEL POOL CLG PMP DISCH TEMP SETPOINT 130°F DESCRIPTION Fuel Pool Cooling Pump ORIGIN TE-4683 discharge temp. above normal AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
MONITOR the Refuel Pool Water temperature.
CAUSE CORRE CTIVE ACTION
- 1. Improper SACS lineup to Fuel Pool Heat Exchanger AE202 and/or BE202.
1A. ENSURE SACS is properly aligned to supply cooling to Fuel Pool Heat Exchanger AE202 and/or BE202.
- 2. Fuel Pool Heat Exchanger Bypass Valve 1EC-V084 is open.
2A. CLOSE Fuel Pool Heat Exchanger Bypass Valve 1EC-V084.
- 3. Fuel Pool F/D system malfunction.
3A. DISPATCH an operator to Fuel Pool F/D Panel 10C305 to investigate F/D operation.
3B. IF the F/D System cannot be readily corrected BYPASS the F/D System as needed.
- 4. Loss of SACS cooling to the Fuel Pool Cooling Heat Exchangers.
4A. REFER TO HC.OP-AB.COOL-0002(Q),
SAFETY/TURBINE AUXILIARIES COOLING SYSTEM.
- 5. Loss of service water cooling to SACS due to a SSWS malfunction.
5A. REFER TO HC.OP-AB.COOL-0001(Q),
STATION SERVICE WATER.
Associated annunciator D1 D5 REFERENCES M-53-1, Sht. 1 M-11-1, Sht. 2 M-54-1, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 51 of 195 Rev. 7 DIGITAL ALARM POINT D3828 NOMENCLATURE SKIMMER SURGE TANK BT208 SETPOINT 22" LEVEL - LSLL-4661B DESCRIPTION Lo-lo level existing in Skimmer Surge Tank BT208 ORIGIN LSLL-4661B AUTOMATIC ACTION:
- 1.
Fuel Pool Cooling Pump BP211 trips.
- 2.
HV-4676B and HV-4678 Fuel Pool Filter Demin Isolation Valves closes.
OPERATOR ACTION:
- 1. CONFIRM AUTOMATIC ACTION.
- 2. IF unable to re-start a FPCC Pump THEN IMPLEMENT HC.OP-AB.COOL-0004(Q); Fuel Pool Cooling.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Instrument Air to Skimmer Surge Tank Level Control Valve LV-4660.
1A. RESTORE Instrument Air to Level Control Valve LV-4660 OR manually OPEN valve IF possible.
1B. ENSURE valve is in AUTO AND OPEN valve LV-4660.
- 2. Fuel Pool Cooling System process piping leakage.
2A. ENSURE proper Fuel Pool Cooling System valve lineup IAW applicable SAP/WCM lineup.
Associated annunciator D1 D5 REFERENCES M-53-1, Sht. 1 J-L 5000(A)-34 J-53-0, Shts. 2, 6, & 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 52 of 195 Rev. 7 DIGITAL ALARM POINT D3829 NOMENCLATURE FUEL POOL CLG PUMP B SETPOINT Various DESCRIPTION Malfunction/overload of Fuel Pool Cooling Pump BP211 ORIGIN MCC 10B222 AUTOMATIC ACTION:
Fuel Pool Cooling Pump BP211 trips OPERATOR ACTION:
- 1. CONFIRM AUTOMATIC ACTION
- 2. IF unable to re-start a FPCC Pump THEN IMPLEMENT HC.OP-AB.COOL-0004(Q); Fuel Pool Cooling.
CAUSE CORRE CTIVE ACTION
- 1. Fuel Pool Cooling BP211 low discharge flow. (Low flow trip enabled 30 seconds after pump start.)
1A.
1B.
START Fuel Pool Cooling Pump AP211.
INSPECT pump BP211 for faults.
- 2. Fuel Pool Cooling Pump BP211 INOP due to:
2A. DISPATCH an operator to pump's motor circuit breaker 52-222103 to determine fault.
- a. breaker tripped 2B. IF breaker
- b. thermal overloads tripped OR thermal overloads have tripped,
- c. control power fuse faulty OR control fuse is blown,
- d. control power transformer faulty INSPECT BP211pump/motor for mechanical interference, low lube oil level, high motor temperature.
2C. NOTIFY the SM/CRS PRIOR to correcting breaker fault OR IF any pump/motor problems are found.
Associated annunciator D1 D5 REFERENCES J-53-0, Sht. 2 E-0324-0
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 53 of 195 Rev. 7 DIGITAL ALARM POINT D3830 NOMENCLATURE FUEL POOL CLG PUMP A SETPOINT Various DESCRIPTION Malfunction/overload of Fuel Pool Cooling Pump AP211 ORIGIN MCC 10B212 AUTOMATIC ACTION:
Fuel Pool Cooling Pump AP211 trips OPERATOR ACTION:
- 1. CONFIRM AUTOMATIC ACTION
- 2. IF unable to re-start a FPCC Pump THEN IMPLEMENT HC.OP-AB.COOL-0004(Q); Fuel Pool Cooling.
CAUSE CORRE CTIVE ACTION
- 1. Fuel Pool Cooling AP211 low discharge flow. (Low flow trip enabled 30 seconds after pump start.)
1A.
1B.
START Fuel Pool Cooling Pump BP211.
INSPECT pump AP211 for faults.
- 2. Fuel Pool Cooling Pump AP211 INOP due to:
2A. DISPATCH an operator to pump's motor circuit breaker 52-212103 to determine fault.
- a. breaker tripped 2B. IF breaker
- b. thermal overloads tripped OR thermal overloads have tripped,
- c. control power fuse faulty OR control fuse is blown,
- d. control power transformer faulty INSPECT AP211pump/motor for mechanical interference, low lube oil level, high motor temperature.
2C. NOTIFY the SM/CRS PRIOR to correcting breaker fault OR IF any pump/motor problems are found.
Associated annunciator D1 D5 REFERENCES J-53-0, Sht. 2 E-0324-0
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 54 of 195 Rev. 7 DIGITAL ALARM POINT D3831 NOMENCLATURE SKIMMER SURGE TANK BT208 SETPOINT 22" LEVEL - LSLL-4661A DESCRIPTION Lo-lo level existing in Skimmer Surge Tank BT208 ORIGIN LSLL-4661A AUTOMATIC ACTION:
- 1.
Fuel Pool Cooling Pump AP211 trips.
- 2.
HV-4676A Fuel Pool Filter Demin Isolation Valve closes.
OPERATOR ACTION:
- 1. CONFIRM AUTOMATIC ACTION.
- 2. IF unable to re-start a FPCC Pump THEN IMPLEMENT HC.OP-AB.COOL-0004(Q); Fuel Pool Cooling.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Instrument Air to Skimmer Surge Tank Level Control Valve LV-4660.
1A. RESTORE Instrument Air to level Control Valve LV-4660 OR manually OPEN valve IF possible.
1B. ENSURE valve is in AUTO AND OPEN valve LV-4660.
- 2. Fuel Pool Cooling System process piping leakage.
2A. ENSURE proper Fuel Pool Cooling System valve lineup IAW applicable SAP/WCM lineup.
Associated annunciator D1 D5 REFERENCES M-53-1, Sht. 1 J-L 5000(A)-34 J-53-0, Shts. 2, 6, & 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 55 of 195 Rev. 7 DIGITAL ALARM POINT D3832 NOMENCLATURE SKIMMER SURGE TANK BT208 SETPOINT 187" LEVEL - LSHH-4660 DESCRIPTION Hi-Hi level existing in Skimmer Surge Tank BT208 ORIGIN LSHH-4660 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
CONFIRM level on Level Recorder LR-4661B Panel 10C650D.
Section 5.17.
CAUSE CORRE CTIVE ACTION
- 1. Failure of Skimmer Surge Tank BT208 level control valve LV-4660 to auto-close on a high Surge Tank level.
1A. CLOSE valve LV-4660 electrically OR manually IF possible.
- 2. Instrument line break down-stream of Excess Flow Check Valve XV-4660.
2A. CLOSE valve LV-4660 electrically OR manually IF possible.
- 3. Excessive makeup to the Fuel Storage Pool from the RHR System.
3A. REDUCE OR STOP RHR System makeup to the Fuel Storage Pool.
- 4. Excessive makeup to the Reactor Well from the CST.
4A. REDUCE OR STOP makeup to the Reactor Well from the CST by closing valves 1EC-V024, 1EC-V027, and/or 1EC-V049.
- 5. Excessive makeup to the Fuel Storage Pool from the SSWS Loop A and/or B.
5A. REDUCE OR STOP makeup to the Fuel Storage Pool via SSWS Loop A and/or B.
Associated annunciator D1 D5 REFERENCES M-53-1, Sht. 1 J-L 5000(A)-34
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 56 of 195 Rev. 7 DIGITAL ALARM POINT D3833 NOMENCLATURE FUEL STORAGE POOL LEVEL HI SETPOINT 40 6 DESCRIPTION High water level in the Fuel Storage Pool ORIGIN LSH 4657 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. CONFIRM that the Fuel Pool HI/LO alarm setpoint has been reached.
- 2. ACKNOWLEDGE the FUEL POOL LEVEL HI/LO alarm.
Section 5.17.
CAUSE CORRE CTIVE ACTION
- 1. Excessive makeup to the Fuel Storage Pool.
1A. ENSURE HV-4660 SKIMMER SURGE TANK MAKEUP VALVE is closed.
1B. IF aligned, STOP makeup to the Fuel Pool Cooling Pumps from the CST.
1C. IF aligned, STOP makeup to the Fuel Storage Pool from the RHR System.
1D. IF ON in the Refueling mode, STOP the ECCS Pumps.
1E. ENSURE valves HV-4647 AND HV-4648 SSWS MAKEUP TO THE FUEL STORAGE POOL are closed.
1F. ALIGN the Fuel Pool System to reject the excessive water to the Condensate Storage Tank or CRW as necessary.
- 2. The Fuel Storage Pool Over-flow Weirs are blocked.
2A. REQUEST the SM/CRS to initiate corrective action.
Associated annunciator D1 A5 REFERENCES M-10-0, Sht. 2 M-51-1, Sht. 1; 2 M-53-0, Sht. 1 J-53-0, Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 57 of 195 Rev. 7 DIGITAL ALARM POINT D3834 NOMENCLATURE FUEL STORAGE POOL LEVEL LOW SETPOINT 39 9 DESCRIPTION Low water level in the Fuel Storage Pool ORIGIN LSH 4657 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
CONFIRM that the FUEL POOL HI/LO alarm setpoint has been reached.
- 2.
ENSURE compliance with the operability requirements of T/S 3.9.9 WATER LEVEL-SPENT FUEL STORAGE POOL.
- 3.
ACKNOWLEDGE the FUEL POOL LEVEL HI/LO alarm.
- 4.
REFER TO HC.OP-AB.COOL-0004(Q) Fuel Pool Cooling.
- 5.
ACKNOWLEDGE the low level alarm at Local Panel 10C214 (Rx. Bldg. El. 201').
NOTE Annunciator on local Panel 10C214 is always valid for low Spent Fuel Pool level, however it is only enabled for the low Reactor cavity water level during refueling operations. The annunciator on local Panel 10C214 alarms on low Spent Fuel Pool level and/or low Reactor cavity water level when the annunciator is enabled.
CAUSE CORRE CTIVE ACTION
- 1. Leakage past the Fuel Storage Pool Inner Gate(s) with drain valve(s) 1EC-V034, 1EC-V097, and/or 1EC-V182 open.
1A. ENSURE HV-4660 SKIMMER SURGE TANK MAKEUP VALVE is open.
1B. MONITOR Fuel Storage Pool gate(s) leakage rate AND IF high, ENSURE drain valves 1EC-V097, 1EC-V034 and 1EC-V182 are closed.
Associated annunciator D1 A5 REFERENCES M-10-0, Sht. 2 M-51-1, Sht. 1; 2 DCP 4-HM-0660 M-53-0, Sht. 1 J-53-0, Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 58 of 195 Rev. 7 DIGITAL ALARM POINT D3834 CAUSE CORRE CTIVE ACTION
- 1. (Continued) 1C. MONITOR Reactor Building Sump leakage rates AND IF high, NOTIFY the SM/CRS to initiate corrective action.
1D. IF water level is dropping AND time permits LINE UP makeup to the Fuel Storage Pool from the Condensate Storage Tank via the Fuel Pool Cooling Pump(s).
1E. IF water level continues to drop MAINTAIN Fuel Storage Pool level using makeup from the RHR System.
1F. IF Fuel Storage Pool level cannot be maintained ALIGN makeup from the Station Service Water System.
1G. IF the appropriate entry criteria is satisfied IMPLEMENT the HCGS Emergency Plan.
- 2. Evaporation of coolant from the Fuel Storage Pool.
2A. ENSURE HV-4660 SKIMMER SURGE TANK MAKEUP VALVE is open.
- 3. 3A.
DETERMINE if leakage is from the RHR System.
Leakage from RHR IF in Shutdown Cooling to support Refueling operations.
3B. IF leakage is from RHR, DETERMINE if RHR Pump trip AND isolation is necessary.
(1BC-HV-F008, 1BC-HV-F009, 1BC-HV-F015A, 1BC-HV-F015B, require manual isolation IF HC.OP-GP.SM-0001(Q) has been implemented).
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 59 of 195 Rev. 7 DIGITAL ALARM POINT D3835 NOMENCLATURE Fuel/Cask Pool Gates Leakage SETPOINT 1 3/4 DESCRIPTION ORIGIN LSH-4668*
Leakage past the Fuel Storage Pool and/or the Fuel Cask Storage Pit gates AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN the Fuel Storage Pool and/or the Fuel Cask Storage Pit water level(s).
- 2. ENSURE compliance with the WATER LEVEL - SPENT FUEL STORAGE POOL requirements of Technical Specifications 3.9.9.
- 3. VERIFY proper valve alignment.
IF the gate area between the Fuel Pool and either the Reactor Well or Fuel Cask Pit is intentionally flooded, the affected leak detection drain (1-EC-V053 Fuel Storage Pool GT Seal Drn and/or 1-EC-V052 Fuel Cask Stor Pit GT Seal Drn must be isolated or D3835 will alarm.
- 4. Visually IDENTIFY the source of leakage at the refuel floor, if possible.
NOTE - This condition may be due to long term gate seal leakage.
To Clear The Alarm OPEN 1-EC-V097 and 1-EC-V034 to drain LSH-4668 THEN, RE-CLOSE 1-EC-V097 and 1-EC-V034.
IF the alarm is received again in a short period of time THEN IDENTIFY the Leakage Source and/or Qualitatively Estimate the Leak Rate as follows:
- a. CLOSE 1-EC-V052 and 1-EC-V053
- b. DRAIN LSH-4668 by opening 1-EC-V097 Fuel Pool/Fuel Cks GT Seal Drn Vlv UNTIL the alarm clears THEN
, RE-CLOSE 1-EC-V097.
- c. RE-OPEN 1-EC-V052 and 1-EC-V053 alternately UNTIL the alarm re-occurs.
- 5. VERIFY proper gate seal valve alignment and seal pressure.
- 6. IF the leak can be contained between the gates (visually verify),
ISOLATE the affected drain path (1-EC-V052 and/or 1-EC-V053) to minimize leakage through the switch to CRW. LSH-4668 may then be drained by opening 1-EC-V097 and reset to monitor the remaining drain path.
IF leakoff is desired, OPEN either 1-EC-V034 FP FC Gate Seal Hdr Drn to CRW OR 1-EC-V033 FP F/C GT Seal Drn TO FPC to FPCC Pump suction.
LSH-4668 is a float switch and flow will occur through the switch to CRW WHEN in alarm unless the switch is isolated.
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 60 of 195 Rev. 7 DIGITAL ALARM POINT D3835 CAUSE CORRE CTIVE ACTION
- 1. Leakage past the Fuel Storage Pool inner gate(s) (i.e. from the Fuel Pool toward the Reactor Well or Fuel Cask Storage Pit).
1A. OPEN HV-4660 SKIMMER SURGE TANK MAKEUP VALVE to maintain Fuel Storage Pool water level as needed.
1B. IF ACTION 1A is insufficient to maintain Fuel Storage Pool water level, ALIGN the RHR System to inject into the Fuel Storage Pool by opening valve 1EC-V060 and/or 1EC-V061.
1C. MONITOR the Fuel Storage water level.
1D. REQUEST the SM/CRS to initiate corrective action.
- 2. Leakage past the Fuel Cask Storage Pit removable blocks and outer gates.
2A. MAINTAIN the Fuel Cask Storage Pit water level within prescribed limits by opening valve(s) 1EC-V047, 1EC-V051 and/or 1EC-V032.
2B. ALIGN makeup to the Fuel Cask Storage Pit via the Condensate Transfer System to maintain the water level within limits using valve 1EC-V049.
2C. REQUEST the SM/CRS to initiate corrective action.
Associated annunciator D1 B5 REFERENCES M-53-1, Sht. 1 JL-5000(A)-34 J-53-0, Sht. 10, 11
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 61 of 195 Rev. 7 DIGITAL ALARM POINT D3837 NOMENCLATURE Drywell/React Well Seal Lkg Leakage SETPOINT 0' 7 1/2" DESCRIPTION Leakage past the Drywell to Reactor Well Seal ORIGIN LSH-4665*
AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. CONFIRM that the DRYWELL/REACT WELL LKG alarm setpoint has been reached.
- 2. MAINTAIN the Reactor Well water level.
- 3. ENSURE compliance with the WATER LEVEL - REACTOR VESSEL requirements of Technical Specifications 3.9.8.
- 4. To prevent overflowing the Drywell to Reactor Well Seal Area, 1-EC-V095 and/or 1-EC-V085 should be opened to increase flow to CRW as necessary.
- 5. DISPATCH an operator to the Torus Room (RB 4102, 54 ft elev) to check the drywell shell, drywell pedestal and drains at the bottom of the drywell air gap for leakage.
CAUSE CORRE CTIVE ACTION
- 1. Defective Drywell to Reactor Well Seal.
1A. DETERMINE Seal leakage by monitoring Reactor Well leakage rates and level.
1B. IF needed, ALIGN make up to the Reactor Well via the Fuel Pool Cooling Pump(s) by opening valves 1EC-V047, 1EC-V027 and/or 1EC-V024 to maintain the Reactor Well level within prescribed limits.
Associated annunciator D1 B5 REFERENCES M-53-1, Sht. 1 JL-5000(A)-34 J-53-0, Sht. 10, 11 LSH-4665 is a float switch and flow will pass through the switch to CRW when in alarm.
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 62 of 195 Rev. 7 DIGITAL ALARM POINT D3837 CAUSE CORRE CTIVE ACTION
- 1. Defective Drywell to Reactor Well Seal. (Continued) 1C. ALIGN makeup to the Reactor Well via the Condensate Transfer System to maintain Reactor Well water level, IF needed, by using valve 1EC-V049.
1D. REQUEST the SM/CRS to initiate corrective action.
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 63 of 195 Rev. 7 DIGITAL ALARM POINT D3838 NOMENCLATURE Vessel/Drywell Seal Leakage SETPOINT 2' 6 3/8" DESCRIPTION Leakage past the Vessel to Drywell Seal ORIGIN LSH-4666*
AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. CONFIRM that the VESSEL/DRYWELL SEAL LEAKAGE alarm setpoint has been reached.
- 2. MAINTAIN the Reactor Well water level within the prescribed limits.
- 3. ENSURE compliance with the WATER LEVEL - REACTOR LEVEL requirements of Technical Specifications 3.9.8.
- 4. NOTIFY HP Shift Tech of contaminated water leak into drywell from Reactor Well.
- 5. To prevent overflowing into the Drywell 1-EC-V028 and/or 1-EC-V094 should be opened to increase flow to CRW as necessary if drywell entry is possible.
CAUSE CORRE CTIVE ACTION
- 1. Defective Vessel to Drywell Seal.
1A. DETERMINE Seal leakage by monitoring Reactor Well leakage rate and level.
1B. ALIGN make up to the Reactor Well via the Fuel Pool Cooling Pump(s) by opening valves 1EC-V047, 1EC-V027 and/or 1EC-V024 to maintain the Reactor Well level within prescribed limits, IF needed.
Associated annunciator D1 B5 REFERENCES M-53-1, Sht. 1 JL-5000(A)-34 J-53-0, Sht. 10, 11 LSH-4666 is afloat switch and flow will pass through the switch to CRW when in alarm.
LSH-4666 is located in the drywell.
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 64 of 195 Rev. 7 DIGITAL ALARM POINT D3838 CAUSE CORRE CTIVE ACTION
- 1. Defective Vessel to Drywell Seal.
(Continued) 1C. ALIGN makeup to the Reactor Well via the Condensate Transfer System to maintain Reactor Well water level, IF needed, by using valve 1EC-V047.
1D. REQUEST the SM/CRS to initiate corrective action.
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 65 of 195 Rev. 7 DIGITAL ALARM POINT D3840 NOMENCLATURE TORUS WTR CLNUP PMP OP229 FLOW SETPOINT 300 gpm DESCRIPTION Torus water cleanup system low flow ORIGIN FSL-4684 AUTOMATIC ACTION:
Torus Water Cleanup Pump OP229 trips after 15 second time delay.
OPERATOR ACTION:
- 1.
CONFIRM AUTOMATIC ACTION.
- 2.
DISPATCH an operator to Remote Panel 10C305 to investigate the cause of alarm.
CAUSE CORRE CTIVE ACTION
- 1. Torus Water Cleanup Pump breaker 52-253014 OR thermal overloads have tripped, faulty control power fuse, OR faulty control power transformer.
1A. DISPATCH an operator to breaker to determine fault.
IF the breaker OR thermal overloads have tripped OR the control power fuse has blown, INSPECT Pump/Motor OP229 for mechanical interference, low lube oil level, high motor temperature.
1B. NOTIFY the SM/CRS prior to resetting OR attempting to correct any breaker fault OR IF any pump/motor problems are detected.
Associated annunciator D1 C5 REFERENCES M-53-1, Sht. 2 E-0031-1, Sht. 1 J-53-0, Sht. 3, 10; 11 J-102-0, Sht. 2, 3, 6, 8
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 66 of 195 Rev. 7 DIGITAL ALARM POINT D3840 CAUSE CORRE CTIVE ACTION
- 2. Improper valve lineup.
2A. ENSURE the proper Torus Water Cleanup System valve lineup.
- 3. Torus Water Cleanup Isolation Valves HV-4652, HV-4679, AND HV-4680, AND HV-4681 closed due to a containment isolation signal being present.
3A. CONFIRM that the containment isolation signal is valid.
- 4. Torus Water Cleanup System suction strainer plugged.
4A. BACK FLUSH the strainer.
- 5. Fuel Pool Filter Demin Hi D/P.
5A. PLACE another Filter Demin in service AND REMOVE the affected Filter Demin from service.
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 67 of 195 Rev. 7 DIGITAL ALARM POINT D3847 NOMENCLATURE TORUS WTR CLNUP V HV-4652 SETPOINT N/A DESCRIPTION Motor operated valve HV-4652 inoperative ORIGIN MCC 10B212 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with the CONTAINMENT ISOLATION VALVES requirements of Technical Specifications 3.6.3.
CAUSE CORRE CTIVE ACTION
- 1. HV-4652 TWC Inboard Return Containment Isolation Valve inoperative due to:
1A. DISPATCH an operator to breaker 52-212233.
- a. breaker 52-212233 tripped
- b. thermal overloads tripped 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS PRIOR to resetting.
- c. control power fuse faulty
- d. control power transformer faulty 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Shts. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 68 of 195 Rev. 7 DIGITAL ALARM POINT D3848 NOMENCLATURE TORUS WTR CLNUP V HV-4680 SETPOINT N/A DESCRIPTION Motor operated valve HV-4680 inoperative ORIGIN MCC 10B212 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with the CONTAINMENT ISOLATION VALVES requirements of Technical Specifications 3.6.3.
CAUSE CORRE CTIVE ACTION
- 1. HV-4680 Torus Water Cleanup Inboard Supply Containment Isolation Valve 1A. DISPATCH an operator to breaker 52-212241.
inoperative due to:
1B. IF breaker OR thermal overloads are tripped,
- a. breaker 52-212241 tripped NOTIFY SM/CRS PRIOR to resetting.
- b. thermal overloads tripped
- c. control power fuse faulty 1C. IF OVLD/PWR FAIL can not be cleared,
- d. control power transformer faulty REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Sht. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 69 of 195 Rev. 7 DIGITAL ALARM POINT D3849 NOMENCLATURE FUEL POOL F/D BYP HV-4689A OPF SETPOINT N/A DESCRIPTION Motor operated valve HV-4689A inoperative ORIGIN MCC 10B212 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRE CTIVE ACTION
- 1. HV-4689A Fuel Pool F/D Bypass Valve inoperative due to:
1A. DISPATCH an operator to breaker 52-212244
- a. breaker 52-212244 tripped
- b. thermal overloads tripped 1B. IF breaker OR thermal overloads are tripped,
- c. control power fuse faulty NOTIFY SM/CRS PRIOR to resetting.
- d. control power transformer faulty 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Sht. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 70 of 195 Rev. 7 DIGITAL ALARM POINT D3850 NOMENCLATURE EMERG MKUP TO FUEL POOL LP A V SETPOINT N/A DESCRIPTION Motor operated valve HV-4647 inoperative ORIGIN MCC 10B212 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRE CTIVE ACTION
- 1. HV-4647 Spent Fuel Storage Pool Emergency Fill Valve inoperative due to:
1A. DISPATCH an operator to breaker 52-212254 1B. IF breaker
- a. breaker 52-212254 tripped OR thermal overloads are tripped,
- b. thermal overloads tripped NOTIFY SM/CRS PRIOR to resetting.
- c. control power fuse faulty
- d. control power transformer faulty 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Sht. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 71 of 195 Rev. 7 DIGITAL ALARM POINT D3851 NOMENCLATURE TORUS WTR CLNUP V HV-4679 SETPOINT N/A DESCRIPTION Motor operated valve HV-4679 inoperative ORIGIN MCC 10B222 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with the CONTAINMENT ISOLATION VALVES requirements of Technical Specifications 3.6.3.
CAUSE CORRE CTIVE ACTION
- 1. HV-4679 TWC Outboard Return Containment Isolation Valve inoperative due to:
1A. DISPATCH an operator to breaker 52-222212 1B. IF breaker
- a. breaker 52-222212 tripped OR thermal overloads are tripped,
- b. thermal overloads tripped NOTIFY SM/CRS PRIOR to resetting.
- c. control power fuse faulty
- d. control power transformer faulty 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Sht. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 72 of 195 Rev. 7 DIGITAL ALARM POINT D3852 NOMENCLATURE TORUS WTR CLNUP V HV-4681 SETPOINT N/A DESCRIPTION Motor operated valve HV-4681 inoperative ORIGIN MCC 10B222 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with the CONTAINMENT ISOLATION VALVES requirements of Technical Specifications 3.6.3.
CAUSE CORRE CTIVE ACTION
- 1. HV-4681 TWC Outboard Supply Containment Isolation Valve inoperative due to:
1A. DISPATCH an operator to breaker 52-222221 1B. IF breaker
- a. breaker 52-222221 tripped OR thermal overloads are tripped,
- b. thermal overloads tripped NOTIFY SM/CRS PRIOR to resetting.
- c. control power fuse faulty
- d. control power transformer faulty 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Sht. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 73 of 195 Rev. 7 DIGITAL ALARM POINT D3853 NOMENCLATURE EMERG MKUP TO FUEL POOL LP B V SETPOINT N/A DESCRIPTION Motor operated valve HV-4648 inoperative ORIGIN MCC 10B222 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRE CTIVE ACTION
- 1. HV-4648 Spent Fuel Storage Pool Emergency Fill Valve inoperative due to:
1A. DISPATCH an operator to breaker 52-222154 1B. IF breaker
- a. breaker 52-222154 tripped OR thermal overloads are tripped,
- b. thermal overloads tripped NOTIFY SM/CRS PRIOR to resetting.
- c. control power fuse faulty
- d. control power transformer faulty 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Sht. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 74 of 195 Rev. 7 DIGITAL ALARM POINT D3854 NOMENCLATURE FUEL POOL F/D BYP HV-4689B OPF SETPOINT N/A DESCRIPTION Motor operated valve HV-4689B inoperative ORIGIN MCC 10B222 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRE CTIVE ACTION
- 1. HV-4689B Fuel Pool Filter Demin Bypass Valve inoperative due to:
1A. DISPATCH an operator to breaker 52-222244 1B. IF breaker
- a. breaker 52-222244 tripped OR thermal overloads are tripped,
- b. thermal overloads tripped NOTIFY SM/CRS PRIOR to resetting.
- c. control power fuse faulty
- d. control power transformer faulty 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated annunciator D1 D5 REFERENCES E-0021-1, Sht. 1, 2 & 3
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 75 of 195 Rev. 7 DIGITAL ALARM POINT D3855 NOMENCLATURE SSWS STRAINER B DIFF PRESSURE SETPOINT 138.55 inwc (5 psid)
DESCRIPTION Hi Hi differential pressure ORIGIN PDSHH-2196B AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. DISPATCH operator to Service Water Intake Structure to investigate problem.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- 1. Clogged filter 1A. CHECK operation of strainer backwash system and strainer motor.
1B. CHECK strainer drive unit sheer pin.
1C. CHECK condition/operation of traveling screen.
- 2. Hi system flow/Header break 2A. INVESTIGATE cause of excessive flow 2B. WHEN possible.
RESTORE flow to normal.
Associated Annunciator A1 B3
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 19, Sht. 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 76 of 195 Rev. 7 DIGITAL ALARM POINT D3857 NOMENCLATURE SSWS STRAINER A DIFF PRESSURE SETPOINT 138.55 in wc (5 psid)
DESCRIPTION Hi Hi differential pressure ORIGIN PDSHH-2196A AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. DISPATCH operator to Service Water Intake Structure to investigate problem.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- 1. Clogged filter 1A. CHECK operation of Strainer backwash system AND Strainer motor.
1B. CHECK Strainer drive unit sheer pin.
1C. CHECK condition/operation of traveling screen.
- 2. Hi system flow/Header break 2A. INVESTIGATE cause of excessive flow 2B. WHEN possible, RESTORE flow to normal.
Associated Annunciator A1 B1
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 18, Sht. 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 77 of 195 Rev. 7 DIGITAL ALARM POINT D3859 NOMENCLATURE SSWS STRAINER C DIFF PRESSURE SETPOINT 138.55 inwc (5 psid)
DESCRIPTION Hi Hi differential pressure ORIGIN PDSHH-2196C AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. DISPATCH operator to Service Water Intake Structure to investigate problem.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- 1. Clogged filter 1A. CHECK operation of Strainer backwash system and strainer motor.
1B. CHECK Strainer drive unit sheer pin.
1C. CHECK condition/operation of traveling screen.
- 2. Hi system flow/header break 2A. INVESTIGATE cause of excessive flow.
2B. WHEN possible, RESTORE flow to normal.
Associated Annunciator A1 C1
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 19, Sht. 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 78 of 195 Rev. 7 DIGITAL ALARM POINT D3861 NOMENCLATURE SSW LOOP A DUMP VLV LOCKED CLS SETPOINT N/A DESCRIPTION HV-2356A Locked Closed ORIGIN HS-2356A AUTOMATIC ACTION:
HV-2356A STATION SERVICE WATER LOOP A YARD DUMP VALVE closes.
OPERATOR ACTION:
None CAUSE CORRECTIVE ACTION
- 1. HS-2356A STATION SERVICE WATER LOOP A YARD DUMP VALVE 1A. WHEN proper Service Water flow is established, PRESS HS-2356A STATION SERVICE Switch in LOCKOUT.
WATER LOOP A YARD DUMP VALVE AUTO PB.
Associated Annunciator A1 D1
REFERENCES:
J-10-0, Sht. 11, Sht. 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 79 of 195 Rev. 7 DIGITAL ALARM POINT D3943 NOMENCLATURE SSW LOOP B DUMP VLV LOCKED CLS SETPOINT N/A DESCRIPTION HV-2356B Locked Closed ORIGIN HS-2356B AUTOMATIC ACTION:
HV-2356B STATION SERVICE WATER LOOP B YARD DUMP VALVE closes.
OPERATOR ACTION:
None CAUSE CORRECTIVE ACTION
- 1. HS-2356B STATION SERVICE WATER LOOP B YARD DUMP VALVE switch in LOCKOUT.
1A. WHEN conditions permit, PRESS HS-2356B STATION SERVICE WATER LOOP B YARD DUMP VALVE AUTO PB.
Associated Annunciator A1 D3
REFERENCES:
J-10-0, Sht. 11, Sht. 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 80 of 195 Rev. 7 DIGITAL ALARM POINT D3945 - D3946 NOMENCLATURE SACS HX B1(B2) FLOW SETPOINT 8.0 psig DESCRIPTION SACS Hx B1 Low Flow SACS Hx B2 Low Flow ORIGIN PDSL-2354B PDSL-2373B AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. ENSURE proper cooling flow to SACS AND RACS Heat Exchangers.
- 2. OBSERVE the Service Water System operability requirements of T/S 3.7.1.2.
- 3. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- 1. SACS Hx Inlet Hdr Leak/Break 1A. REQUEST SM/CRS to initiate investigative action.
IF room is flooding HAVE operator isolate SACS loop.
- 2. Loss of Running Service Water Pump 2A. RESTORE service water flow IAW HC.OP-SO.EA-0001(Q).
- 3. Improper valve lineup 3A. RESTORE proper valve lineup IAW HC.OP-SO.EA-0001(Q).
Associated Annunciator A1 D3
REFERENCES:
J-10-0, Sht. 7, Sht. 23 CD-273Y NRC Q410.66
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 81 of 195 Rev. 7 DIGITAL ALARM POINT D3947 - D3948 NOMENCLATURE SACS HX A1(A2 FLOW SETPOINT 8.0 psid DESCRIPTION SACS Hx A1 Low Flow and HV-2371A full open SACS Hx A2 Low Flow and HV-2355A full open ORIGIN PDSL-2354A PDSL-2373A AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. ENSURE proper cooling flow to SACS AND RACS Heat Exchangers.
- 2. IF low flow cannot be corrected, TRANSFER to standby Service Water loop.
- 3. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- 1. SACS Hx 1A. REQUEST SM/CRS to initiate OR RACS Hx Inlet Hdr Leak/Break investigative action.
IF room is flooding HAVE operator isolate SACS loop.
- 2. Loss of Running Service Water Pump 2A. RESTORE service water flow IAW HC.OP-SO.EA-0001(Q).
- 3. Improper valve lineup 3A. RESTORE proper valve lineup IAW HC.OP-SO.EA-0001(Q).
Associated Annunciator A1 D1
REFERENCES:
J-10-0, Sht. 6, Sht. 23 CD-273Y Q410.66 TASK NO.: 0001
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 82 of 195 Rev. 7 DIGITAL ALARM POINT D3949 NOMENCLATURE SSWS PUMP B LUBE WATER FLOW SSWS PUMP B GLAND TEMPERATURE SETPOINT 5 psig 100 °F DESCRIPTION Low SSWS Pump B Lube Water Pressure High SSWS Pump B Gland Temperature ORIGIN PSL-2224B TSH-2251B AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 2. DISPATCH an operator to the Service Water Intake Structure to investigate the problem.
- 3. ENSURE compliance with the Service Water operability requirements of T/S 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- 1.
1A. ENSURE proper valve alignment, and system integrity.
1B. DETERMINE whether alarm is either Low lube Water Pressure AND/OR a High Gland Temperature (and take action) as follows:
Low lube water pressure (5 psig with BP502 running)
High Gland Temperature (100 °F)
VERIFY whether lubrication water supply pressure is adequate using 1EAPI-2224B (local). (This pressure should be > 5 psig based on existing low lubrication supply pressure alarm set point.)
IF pressure is 5 psig or less, THEN, SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers Visually VERIFY adequate packing gland leak-off flow is present from packing gland follower leak off line.
(REMOVE tygon tubing from gland follower leak off line and visually witness steady stream of water)
IF there is NOT a steady stream of packing leak off water and steam is being emitted from this leak off line, THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
MEASURE gland temperature sensor mounting plate temperature using calibrated pyrometer and validate metal temperatures in the vicinity of temperature probe at or above 100 °F.
IF metal temperatures are NOT above alarm temperature set point of 100 °F, THEN INITIATE notification for maintenance to troubleshoot temperature switch (1EATSH-2251B)
MEASURE gland follower temperature just below upper adjustment flange. (This temperature should not exceed 120 °F (based on internal OE, reference notification 20189430) in an attempt to maintain SSW Pump lubrication/cooling water flow below 100 °F)
IF gland follower temperature just below upper adjustment flange exceeds 120 °F THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
1C. IF alarm condition persists periodically RE-VALIDATE whether alarm is due to Low lube Water Pressure AND/OR a High Gland Temperature (Temporary Log) IAW above criteria.
Associated Annunciator A1 B3
REFERENCES:
E-6754-0, Sht. A; J-10-0, Shts. 5, 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 83 of 195 Rev. 7 DIGITAL ALARM POINT D3951 NOMENCLATURE SSWS PUMP A LUBE WATER FLOW SSWS PUMP A GLAND TEMPERATURE SETPOINT 5 psig 100 °F DESCRIPTION Low SSWS Pump A Lube Water Pressure High SSWS Pump A Gland Temperature ORIGIN PSL-2224A TSH-2251A AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers, (MONITOR SACS & RACS temperatures).
- 2. DISPATCH an operator to the Service Water Intake Structure to investigate the problem.
- 3. ENSURE compliance with the Service Water operability requirements of T/S 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- 1.
1A.
ENSURE proper valve alignment, and system integrity.
1B.
DETERMINE whether alarm is either Low lube Water Pressure AND/OR a High Gland Temperature (and take action) as follows:
Low lube water pressure (5 psig with AP502 running)
High Gland Temperature (100 °F)
VERIFY whether lubrication water supply pressure is adequate using 1EAPI-2224A (local). (This pressure should be > 5 psig based on existing low lubrication supply pressure alarm set point.)
IF pressure is 5 psig or less, THEN, SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers Visually VERIFY adequate packing gland leak-off flow is present from packing gland follower leak off line.
(REMOVE tygon tubing from gland follower leak off line and visually witness steady stream of water)
IF there is NOT a steady stream of packing leak off water and steam is being emitted from this leak off line, THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
MEASURE gland temperature sensor mounting plate temperature using calibrated pyrometer and validate metal temperatures in the vicinity of temperature probe at or above 100 °F.
IF metal temperatures are NOT above alarm temperature set point of 100 °F, THEN INITIATE notification for maintenance to troubleshoot temperature switch (1EATSH-2251A)
MEASURE gland follower temperature just below upper adjustment flange. (This temperature should not exceed 120 °F (based on internal OE, reference notification 20189430) in an attempt to maintain SSW Pump lubrication/cooling water flow below 100 °F)
IF gland follower temperature just below upper adjustment flange exceeds 120 °F THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
1C. IF alarm condition persists periodically RE-VALIDATE whether alarm is due to Low lube Water Pressure AND/OR a High Gland Temperature (Temporary Log) IAW above criteria.
Associated Annunciator A1 B1
REFERENCES:
E-6754-0, Sht. A; J-10-0, Shts. 3, 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 84 of 195 Rev. 7 DIGITAL ALARM POINT D3953 NOMENCLATURE SSWS PUMP D LUBE WATER FLOW SSWS PUMP D GLAND TEMPERATURE SETPOINT 5 psig 100 °F DESCRIPTION Low SSWS Pump D Lube Water Pressure High SSWS Pump D Gland Temperature ORIGIN PSL-2224D TSH-2251D AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 2. DISPATCH an operator to the Service Water Intake Structure to investigate the problem.
- 3. ENSURE compliance with the Service Water operability requirements of T/S 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- 1.
1A.
ENSURE proper valve alignment, and system integrity.
1B.
DETERMINE whether alarm is either Low lube Water Pressure AND/OR a High Gland Temperature (and take action) as follows:
Low lube water pressure (5 psig with DP502 running)
High Gland Temperature (100 °F)
VERIFY whether lubrication water supply pressure is adequate using 1EAPI-2224D (local). (This pressure should be > 5 psig based on existing low lubrication supply pressure alarm set point.)
IF pressure is 5 psig or less, THEN, SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers Visually VERIFY adequate packing gland leak-off flow is present from packing gland follower leak off line.
(REMOVE tygon tubing from gland follower leak off line and visually witness steady stream of water)
IF there is NOT a steady stream of packing leak off water and steam is being emitted from this leak off line, THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
MEASURE gland temperature sensor mounting plate temperature using calibrated pyrometer and validate metal temperatures in the vicinity of temperature probe at or above 100 °F.
IF metal temperatures are NOT above alarm temperature set point of 100 °F, THEN INITIATE notification for maintenance to troubleshoot temperature switch (1EATSH-2251D)
MEASURE gland follower temperature just below upper adjustment flange. (This temperature should not exceed 120 °F (based on internal OE, reference notification 20189430) in an attempt to maintain SSW Pump lubrication/cooling water flow below 100 °F)
IF gland follower temperature just below upper adjustment flange exceeds 120 °F THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
1C.
IF alarm condition persists periodically RE-VALIDATE whether alarm is due to Low lube Water Pressure AND/OR a High Gland Temperature (Temporary Log) IAW above criteria.
Associated Annunciator A1 C3
REFERENCES:
E-6754-0, Sht. A; J-10-0, Shts. 5, 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 85 of 195 Rev. 7 DIGITAL ALARM POINT D3960 NOMENCLATURE RBVS EXH RTM PNL C382 SETPOINT Various DESCRIPTION Reactor Building HVAC Exhaust System trouble ORIGIN Multiple AUTOMATIC ACTION:
Low flow condition on operating fan results in fan trip AND auto start of standby fan(s).
OPERATOR ACTION:
- 1. NOTIFY SM/CRS of alarm condition.
- 2. OBSERVE Control Room indication to determine IF fan tripped.
- 3. REFER TO HC.OP-AB.CONT-0003(Q), Reactor Building.
- 4. DISPATCH operator to the Remote Control Panel 10C382 to determine cause of alarm.
CAUSE CORRE CTIVE ACTION
- 1.
Low flow (FSL-9420A, B, C) 1A.
ENSURE standby fan(s) auto starts to maintain a negative pressure in Secondary Containment.
1B.
IF insufficient exhaust fans available to maintain a negative pressure in Secondary Containment ISOLATE the Reactor Building AND START FRVS (Filtration Recirculation and Ventilation System).
1C.
DIRECT operator to monitor damper operation to determined if a malfunction exists. This action requires a restart of the fan which may be undesirable.
Continued next page Associated Annunciator E6 C5
REFERENCES:
E-6787-0 H-84-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 86 of 195 Rev. 7 DIGITAL ALARM POINT D3960 CAUSE CORRE CTIVE ACTION
- 2. A(B,C)VH3 01 Filter high D/P (alarm setpoint 3.5 inches water gauge) 2A.
DIRECT operator to determine filter D/P for the fan(s) in operation.
PDSH-9420A, B, C
- 3.
Exhaust air temperature high (alarm setpoint 120°F; TSH-9415 located at common inlet to Exhaust Filters) 3A.
DISPATCH operator to check for steam leaks AND other room temperature alarms.
3B.
RESPOND IAW HC.OP-AR.GR-0001(Q).
3C.
REQUEST SM/CRS to initiate corrective action.
REFERENCES:
E-6787-0 H-84-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 87 of 195 Rev. 7 DIGITAL ALARM POINT D3961 NOMENCLATURE RBVS SUPPLY RTM PNL C382 SETPOINT Various DESCRIPTION Reactor Building HVAC Supply System trouble ORIGIN Multiple AUTOMATIC ACTION:
Low flow condition on operating fan(s) results in fan trip AND auto start of standby fan(s).
OPERATOR ACTION:
- 1. NOTIFY SM/CRS of alarm condition.
- 2. DISPATCH operator to the Remote Control Panel 10C382 to determine cause of alarm.
- 3. OBSERVE Control Room indication to determine IF fan tripped.
CAUSE CORRE CTIVE ACTION
- 1.
Low flow (trip setpoint 30,000 cfm) 1A.
ENSURE standby fan(s) auto start AND fan with low flow trips.
1B.
DIRECT operator to monitor damper operation to determined IF a malfunction exists. This action requires a restart of the fan which may be undesirable.
1C.
ALIGN ventilation to maintain a negative pressure in Secondary Containment
(< -.50 inches water)
- 2. A(B,C)VH3 00 Filter high D/P (alarm setpoint 1.5 inches water gauge) PDSH-9368A, B, C 2A.
DIRECT operator to determine filter D/P (PDI-9368)
Continued next page Associated Annunciator E6 C5
REFERENCES:
E-6787-0 H-83-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 88 of 195 Rev. 7 DIGITAL ALARM POINT D3961 CAUSE CORRE CTIVE ACTION
- 3. A(B,C)VH3 00 low temperature (alarm setpoint 35°F, TSL-9368A, B, C) 3A.
ENSURE steam is available to Steam Heating Coils.
- 4. A(B,C)VH300 high temperature (alarm setpoint 65°F TSH-9368A,B,C) 4A.
DIRECT operator to inspect Heating System to determine IF a malfunction exists.
- 5.
Supply air temperature high (alarm setpoint 67°F, TSH-9369) 5A.
DIRECT operator to inspect Heating System to determine malfunction.
- 6. Refueling Dampers in abnormal position 6A.
Any one OR more dampers out of position for normal OR refueling operations.
DIRECT operator to check dampers as indicated on H-83-0, Sht. 7 to determine which damper(s) have malfunctioned.
- 7.
A(B,C)VH300 Roll Filter media runout 7A.
RESPOND IAW HC.OP-AR.GR-0001(Q).
ZAL-9368B 7B.
REQUEST SM/CRS to initiate corrective action.
REFERENCES:
E-6787-0 H-83-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 89 of 195 Rev. 7 DIGITAL ALARM POINT D3974 NOMENCLATURE SSWS STRAINER D DIFF PRESSURE SETPOINT 138.55 inwc (5 psid)
DESCRIPTION Hi Hi differential pressure ORIGIN PDSHH-2196D AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. DISPATCH operator to Service Water Intake Structure to investigate problem.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- 1. Clogged filter 1A. CHECK operation of strainer backwash system AND strainer motor.
1B. CHECK strainer drive unit sheer pin.
1C. CHECK condition/operation of traveling screen.
- 2. Hi system flow/header break 2A. INVESTIGATE cause of excessive flow 2B. WHEN possible, RESTORE flow to normal.
Associated Annunciator A1 C3
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 19, Sht. 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 90 of 195 Rev. 7 DIGITAL ALARM POINT D3976 NOMENCLATURE SSWS PUMP C LUBE WATER FLOW SSWS PUMP C GLAND TEMPERATURE SETPOINT 5 psig 100 °F DESCRIPTION Low SSWS Pump C Lube Water Pressure High SSWS Pump C Gland Temperature ORIGIN PSL-2224C TSH-2251C AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 2. DISPATCH an operator to the Service Water Intake Structure to investigate the problem.
- 3. ENSURE compliance with the Service Water operability requirements of T/S 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- 1.
1A.
ENSURE proper valve alignment, and system integrity.
1B.
DETERMINE whether alarm is either Low lube Water Pressure AND/OR a High Gland Temperature (and take action) as follows:
Low lube water pressure (5 psig with AP502 running)
High Gland Temperature (100 °F)
VERIFY whether lubrication water supply pressure is adequate using 1EAPI-2224C (local). (This pressure should be > 5 psig based on existing low lubrication supply pressure alarm set point.)
IF pressure is 5 psig or less, THEN, SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers Visually VERIFY adequate packing gland leak-off flow is present from packing gland follower leak off line.
(REMOVE tygon tubing from gland follower leak off line and visually witness steady stream of water)
IF there is NOT a steady stream of packing leak off water and steam is being emitted from this leak off line, THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
MEASURE gland temperature sensor mounting plate temperature using calibrated pyrometer and validate metal temperatures in the vicinity of temperature probe at or above 100 °F.
IF metal temperatures are NOT above alarm temperature set point of 100 °F, THEN INITIATE notification for maintenance to troubleshoot temperature switch (1EATSH-2251C)
MEASURE gland follower temperature just below upper adjustment flange. (This temperature should not exceed 120 °F (based on internal OE, reference notification 20189430) in an attempt to maintain SSW Pump lubrication/cooling water flow below 100 °F)
IF gland follower temperature just below upper adjustment flange exceeds 120 °F THEN SECURE SSW Pump after ensuring required service water flow to SACS and RACS Heat Exchangers.
1C.
IF alarm condition persists periodically RE-VALIDATE whether alarm is due to Low lube Water Pressure AND/OR a High Gland Temperature (Temporary Log) IAW above criteria.
Associated Annunciator A1 C1
REFERENCES:
E-6754-0, Sht. A; J-10-0, Shts. 5, 23
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 91 of 195 Rev. 7 DIGITAL ALARM POINT D3977 NOMENCLATURE SEISMIC TROUBLE ALARM SETPOINT Multiple DESCRIPTION ORIGIN Various Seismic Occurrence at OBE alarm level AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
DISPATCH an operator to Local Panel 10C673 to validate alarm AND RESET IAW HC.OP-SO.SG-0001(Z) Seismic Instrumental System Operation.
- 2.
OBSERVE Seismic Response Spectrum Annunciator (10C650C)
AND INDICATE on Attachment C4-1 the lamps that are illuminated.
- 3.
RESET in accordance with HC.OP-SO.SG-0001(Q).
- 4.
REQUEST I&C to retrieve the earthquake record IAW I&C procedure.
- 5.
IMPLEMENT procedure HC.OP-AB.MISC-0001(Q) Acts of Nature.
- 6.
REPORT cause AND severity of alarm to SM/CRS.
CAUSE CORRE CTIVE ACTION
- 1. Seismic event 1A. REQUEST SM/CRS to initiate corrective action.
1B. IMPLEMENT procedure HC.OP-AB.MISC-0001(Q)
Acts of Nature.
Associated Annunciator C6 C4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 92 of 195 Rev. 7 DIGITAL ALARM POINT D3996 - D3997 NOMENCLATURE SACS HX A1 OUTLET HV-2371A OPF SACS LP A/CLG TWR HV-2357A OPF SETPOINT N/A DESCRIPTION HV-2371A Overload/Power Failure HV-2357A Overload/Power Failure ORIGIN AC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload HV-2371A
- d. control power transformer failure
- e. breaker open HV-2357A Bkr 52-212132 SACS LP A CLG OUT TO TWR 1B. IF breaker OR thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D1
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 93 of 195 Rev. 7 DIGITAL ALARM POINT D3998 - D3999 NOMENCLATURE SACS HX B1 OUTLET HV-2371B OPF SACS LP B/CLG TWR HV-2357B OPF SETPOINT N/A DESCRIPTION HV-2371B Overload/Power Failure HV-2357B Overload/Power Failure ORIGIN BC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE the Service Water System operability requirements of T/S 3.7.1.2.
CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload HV-2371B
- d. control power transformer failure
- e. breaker open HV-2357B Bkr 52-222132 SACS LP B CLG OUT TO TWR.
1B. IF breaker is tripped, NOTIFY SM/CRS prior to resetting.
1C. IF the thermal overload relay is tripped, THEN, DIRECT Maintenance to inspect valve. [PR 970811169]
1D. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D3
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 94 of 195 Rev. 7 DIGITAL ALARM POINT D4000 NOMENCLATURE SACS HX A2 OUTLET HV-2355A OPF SETPOINT N/A DESCRIPTION HV-2355A Overload/Power Failure ORIGIN CC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload 1B. IF breaker
- c. control power fuse blown OR thermal overloads are tripped,
- d. control power transformer failure NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D1
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 95 of 195 Rev. 7 DIGITAL ALARM POINT D4002 NOMENCLATURE SACS HX B2 OUTLET HV-2355B OPF SETPOINT N/A DESCRIPTION HV-2355B Overload/Power Failure ORIGIN DC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE the Service Water System operability requirements of T/S 3.7.1.2.
CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload 1B. IF breaker is tripped,
- c. control power fuse blown NOTIFY SM/CRS prior to resetting.
- d. control power transformer failure
- e. breaker open 1C. IF the thermal overload relay is tripped, THEN, DIRECT Maintenance to inspect valve. [PR 970811169]
1D. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D3
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 96 of 195 Rev. 7 DIGITAL ALARM POINT D4004 - D4005 NOMENCLATURE SSW LP A DUMP HV-2356A OPF SSW LP A/RACS HX HV-2203 OPF SETPOINT N/A DESCRIPTION HV-2356A Overload/Power Failure HV-2203 Overload/Power Failure ORIGIN AC652 CC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload HV-2356A
- c. control power fuse blown Bkr 52-212131 SERVICE WTR LOOP A DUMP
- d. control power transformer failure
1B. IF breaker OR thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D1
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 97 of 195 Rev. 7 DIGITAL ALARM POINT D4006 NOMENCLATURE SSW LP B DUMP HV-2356B OPF SETPOINT N/A DESCRIPTION HV-2356B Overload/Power Failure ORIGIN BC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE the Service Water System operability requirements of T/S 3.7.1.2 CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload 1B. IF breaker
- c. control power fuse blown OR thermal overloads are tripped,
- d. control power transformer failure NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D3
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 98 of 195 Rev. 7 DIGITAL ALARM POINT D4007 NOMENCLATURE SSW LP B/RACS HX HV-2204 OPF SETPOINT N/A DESCRIPTION HV-2204 Overload/Power Failure ORIGIN BC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE the Service Water System operability requirements of T/S 3.7.1.2.
CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload 1B. IF breaker is tripped,
- c. control power fuse blown NOTIFY SM/CRS prior to resetting.
- d. control power transformer failure
- e. breaker open 1C. IF the thermal overload relay is tripped, THEN, DIRECT Maintenance to inspect valve. [PR 970811169]
1D. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D3
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 99 of 195 Rev. 7 DIGITAL ALARM POINT D4008 - D4009 NOMENCLATURE RACS HX INLET ISLN HV-2207 OPF RACS HX OUTLET ISLN HV-2346 OPF SETPOINT N/A DESCRIPTION HV-2207 Overload/Power Failure HV-2346 Overload/Power Failure ORIGIN CC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRECTIVE ACTION
- a. breaker trip HV-2207
- b. thermal overload Bkr 52-232081 RACS HX CLG SUPPLY.
- c. control power fuse blown
- d. control power transformer failure HV-2346
- e. breaker open Bkr 52-232082 RACS HX CLG OUTLET.
1B. IF breaker OR thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D1
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 100 of 195 Rev. 7 DIGITAL ALARM POINT D4010 NOMENCLATURE SSW PUMP A DISCH HV-2198A OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-553041 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- a. breaker trip DIS MOV.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker
- d. control power transformer failure OR thermal overloads are tripped,
- e. breaker open NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 B1
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 101 of 195 Rev. 7 DIGITAL ALARM POINT D4011 NOMENCLATURE SSW STR A BCKWSH HV-2197A OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-553021 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MONITOR Strainer differential pressure for signs of Strainer clogging.
- 2. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperature).
PLACE "C" SSW Pump I/S IF necessary.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- a. breaker trip BK WASH.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker
- d. control power transformer failure OR thermal overloads are tripped,
- e. breaker open NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 B1
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 102 of 195 Rev. 7 DIGITAL ALARM POINT D4012 NOMENCLATURE SSW PUMP C DISCH HV-2198C OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-573041 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- a. breaker trip DIS MOV.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker
- d. control power transformer failure OR thermal overloads are tripped,
- e. breaker open NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 C1
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 103 of 195 Rev. 7 DIGITAL ALARM POINT D4013 NOMENCLATURE SSW STR C BCKWSH HV-2197C OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-573021 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MONITOR Strainer differential pressure for signs of strainer clogging.
- 2. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperature).
START "A" SSW Pump IF necessary.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- a. breaker trip BK WASH.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker
- d. control power transformer failure OR thermal overloads are tripped,
- e. breaker open NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 C1
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 104 of 195 Rev. 7 DIGITAL ALARM POINT D4034 NOMENCLATURE SSW PMP B DISCH V HV-2198B OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-563041 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- a. breaker trip DIS MOV.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker is tripped,
- d. control power transformer failure NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C. IF the thermal overload relay is tripped, THEN, DIRECT Maintenance to inspect valve. [PR 970811169]
1D. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 B3
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 105 of 195 Rev. 7 DIGITAL ALARM POINT D4035 NOMENCLATURE SSW STR B BCKWSH HV-2197B OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-563021 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MONITOR Strainer differential pressure for signs of strainer clogging.
- 2. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
PLACE "D" SSW Pump I/S IF necessary.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- a. breaker trip BK WASH.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker is tripped,
- d. control power transformer failure NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C. IF the thermal overload relay is tripped, THEN, DIRECT Maintenance to inspect valve. [PR 970811169]
1D. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 B3
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 106 of 195 Rev. 7 DIGITAL ALARM POINT D4036 NOMENCLATURE SSW PUMP D DISCH HV-2198D OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-583041 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperatures).
- 3. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
CAUSE CORRECTIVE ACTION
- a. breaker trip DIS MOV.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker is tripped,
- d. control power transformer failure NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C. IF the thermal overload relay is tripped, THEN, DIRECT Maintenance to inspect valve. [PR 970811169]
1D. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 C3
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 107 of 195 Rev. 7 DIGITAL ALARM POINT D4046 NOMENCLATURE SSW STR D BCKWSH HV-2197D OPF SETPOINT N/A DESCRIPTION Thermal overload or loss of control power ORIGIN 52-583021 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
- 1. MONITOR Strainer differential pressure for signs of strainer clogging.
- 2. MAINTAIN required Service Water flow to RACS AND SACS Heat Exchangers (MONITOR SACS & RACS temperature).
PLACE "B" SSW Pump I/S IF necessary.
- 4. ENSURE compliance with the Service Water operability requirement of Technical Specification 3/4.7.1.2.
- 5. REFER to HC.OP-AB.COOL-0001(Q); Station Service Water.
CAUSE CORRECTIVE ACTION
- a. breaker trip BK WASH.
- b. thermal overload
- c. control power fuse blown 1B. IF breaker is tripped,
- d. control power transformer failure NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C. IF the thermal overload relay is tripped, THEN, DIRECT Maintenance to inspect valve. [PR 970811169]
1D. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 C3
REFERENCES:
E-6754-0, Sht. A J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 108 of 195 Rev. 7 DIGITAL ALARM POINT D4047 - D4048 NOMENCLATURE SSW LP A/EMER MKUP HV-2234 OPF SSW LP A/EMER MKUP HV-2236 OPF SETPOINT N/A DESCRIPTION HV-2234 Overload/Power Failure HV-2236 Overload/Power Failure ORIGIN AC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
None CAUSE CORRECTIVE ACTION
- a. breaker trip HV-2234
- b. thermal overload Bkr 52-212221 FUEL POOL CLG MKUP WTR.
- c. control power fuse blown
- d. control power transformer failure HV-2236
- e. breaker open Bkr 52-212222 FUEL POOL CLG MKUP WTR.
1B. IF breaker OR thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D1
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 109 of 195 Rev. 7 DIGITAL ALARM POINT D4049 - D4050 NOMENCLATURE SSW LP B/EMER MKUP HV-2238B OPF SSW LP B/EMER MKUP HV-F073 OPF SETPOINT N/A DESCRIPTION HV-2238 Overload/Power Failure HV-F073 Overload/Power Failure ORIGIN BC652 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE the Service Water System operability requirements of T/S 3.7.1.2 CAUSE CORRECTIVE ACTION
- a. breaker trip
- b. thermal overload HV-2238
- c. control power fuse blown Bkr 52-222224 FUEL POOL CLG & M/U WATER.
- d. control power transformer failure
- e. breaker open HV-F073 Bkr 52-222082 FUEL POOL & SACS LP B MAKEUP ISLN VLV 1B. IF breaker OR thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator A1 D3
REFERENCES:
J-10-0, Sht. 23, Sht. 28
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 110 of 195 Rev. 7 DIGITAL ALARM POINT D4053 NOMENCLATURE WTR CHILLER AK111 SETPOINT Various REMOTE PANEL DESCRIPTION AK111 Chiller Remote Control ORIGIN Multiple Panel Trouble Alarm AUTOMATIC ACTION:
AK111 Chiller trips except on HI/LO CHILLER OUTLET TEMP.
OPERATOR ACTION:
DISPATCH EO to Chilled Water Panel 10C152 to determine cause of alarm.
CAUSE CORRE CTIVE ACTION
- 1. Chiller AK111 Panel Alarm 1A. RESPOND IAW HC.OP-AR.GB-0005(Q).
- 2. Low Chiller Outlet Temp 2A. OBSERVE AK111 restarts WHEN Chilled Wtr Outlet Temp 50°F.
- 3. High Chiller Outlet Temp 3A. CHECK A2259 TURB BLDG COND CLR A OTLT TEMP < 100°F.
3B. CHECK TI-9489A CHW TEMP SPLY
< 55°F on 10C651E.
3C. CHECK TI-9489B AK111 CHILLED WTR DISCH < 65°F.
Continued next page Associated Annunciator E5 E1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 111 of 195 Rev. 7 DIGITAL ALARM POINT D4053 CAUSE CORRE CTIVE ACTION
- 3. High Chiller Outlet Temp (continued) 3D. IF differential temperature between 3B AND 3C, listed above, is > 10°F PERFORM the following:
- 1.
START standby Chiller IAW HC.OP-SO.GB-0001(Q).
- 2.
STOP effected Chiller IAW HC.OP-SO.GB-0001(Q).
3E. REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 E1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 112 of 195 Rev. 7 DIGITAL ALARM POINT D4054 NOMENCLATURE WTR CHILLER BK111 SETPOINT Various REMOTE PANEL DESCRIPTION BK111 Chiller Remote Control ORIGIN Multiple Panel Trouble Alarm AUTOMATIC ACTION:
BK111 Chiller trips except on HI/LO CHILLER OUTLET TEMP.
OPERATOR ACTION:
DISPATCH EO to Chilled Water Panel 10C152 to determine cause of alarm.
CAUSE CORRE CTIVE ACTION
- 1. Chiller BK111 Panel Alarm 1A. RESPOND IAW HC.OP-AR.GB-0005(Q).
- 2. Low Chiller Outlet Temp 2A. OBSERVE BK111 restarts WHEN Chilled Wtr Outlet Temp 50°F
- 3. High Chiller Outlet Temp 3A. CHECK A2260 TURB BLDG COND CLR B OTLT TEMP < 100°F.
3B. CHECK TI-9489A CHW TEMP SPLY < 55°F on 10C651E.
3C. CHECK TI-9489B BK111 CHILLED WTR DISCH < 65°F.
Continued next page Associated Annunciator E5 E1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 113 of 195 Rev. 7 DIGITAL ALARM POINT D4054 CAUSE CORRE CTIVE ACTION
- 3. High Chiller Outlet Temp (continued) 3D. IF differential temperature between 3B AND 3C, listed above, is > 10°F PERFORM the following:
- 1.
START standby Chiller IAW HC.OP-SO.GB-0001(Q).
- 2.
STOP effected Chiller IAW HC.OP-SO.GB-0001(Q).
3E. REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 E1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 114 of 195 Rev. 7 DIGITAL ALARM POINT D4055 NOMENCLATURE WTR CHILLER CK111 SETPOINT Various REMOTE PANEL DESCRIPTION CK111 Chiller Remote Control ORIGIN Multiple Panel Trouble Alarm AUTOMATIC ACTION:
CK111 Chiller trips except on HI/LO CHILLER OUTLET TEMP OPERATOR ACTION:
DISPATCH EO to Chilled Water Panel 10C152 to determine cause of alarm.
CAUSE CORRE CTIVE ACTION
- 1. Chiller CK111 Panel Alarm 1A. RESPOND IAW HC.OP-AR.GB-0005(Q).
- 2. Low Chiller Outlet Temp 2A. OBSERVE CK111 restarts WHEN Chilled Wtr Outlet Temp 50°F.
- 3. High Chiller Outlet Temp 3A. CHECK A2261 TURB BLDG COND CLR C OTLT TEMP < 100°F.
3B. CHECK TI-9489A CHW TEMP SPLY < 55°F on 10C651E.
3C. CHECK TI-9489B CK111 CHILLED WTR DISCH < 65°F.
Continued next page Associated Annunciator E5 E1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 115 of 195 Rev. 7 DIGITAL ALARM POINT D4055 CAUSE CORRE CTIVE ACTION
- 3. High Chiller Outlet Temp (continued) 3D. IF differential temperature between 3B AND 3C, listed above, is > 10°F PERFORM the following:
- 1.
START standby Chiller IAW HC.OP-SO.GB-0001(Q).
- 2.
STOP effected Chiller IAW HC.OP-SO.GB-0001(Q).
3E. REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 E1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 116 of 195 Rev. 7 DIGITAL ALARM POINT D4072 NOMENCLATURE CTMT ISLN OUTBD SETPOINT N/A HV-9531A1 DESCRIPTION Loop A Sup Hdr Outboard ORIGIN 1DC652 Containment Isln HV-9531A1 Overload/Power failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B242 CHW SYS OUTBD ISLN 1GB-HV-9531A1
- a.
breaker trip Brkr 52-242181 is on.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1, Rev. 11
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 117 of 195 Rev. 7 DIGITAL ALARM POINT D4073 NOMENCLATURE CTMT ISLN OUTBD SETPOINT N/A HV-9531A2 DESCRIPTION Loop A Ret Hdr Outboard ORIGIN 1DC652 Containment Isln HV-9531A2 Overload/Power failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B242 CHW SYS OUTBD ISLN 1GB-HV-9531A2
- a.
breaker trip Brkr 52-242182 is ON
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1, Rev. 11
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 118 of 195 Rev. 7 DIGITAL ALARM POINT D4074 NOMENCLATURE CTMT ISLN OUTBD SETPOINT N/A HV-9531A3 DESCRIPTION Loop B Sup Hdr Outboard ORIGIN 1DC652 Containment Isln HV-9531A3 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B242 CHW SYS OUTBD ISLN 1GB-HV-9531A3
- a.
breaker trip Brkr 52-242183 is ON.
b thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 119 of 195 Rev. 7 DIGITAL ALARM POINT D4082 NOMENCLATURE CTMT ISLN OUTBD SETPOINT N/A HV-9531A4 DESCRIPTION Loop B Ret Hdr Outboard ORIGIN 1DC652 Containment Isln HV-9531A4 AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B242 CHW SYS OUTBD ISLN 1GB-HV-9531A4
- a.
breaker trip Brkr 52-242184 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 120 of 195 Rev. 7 DIGITAL ALARM POINT D4134 NOMENCLATURE ADS CH B DW PR BYP TIMER INIT SETPOINT Various DESCRIPTION ADS Logic B High Drywell Pressure ORIGIN Multiple Bypass Timer running AUTOMATIC ACTION:
ADS Logic B High Drywell Pressure Bypass Timer (5 minute) started.
OPERATOR ACTION:
VERIFY that the ADS High Drywell Pressure Bypass Timer initiation setpoint (RPV Level 1 ( -129")) has been reached.
CAUSE CORRE CTIVE ACTION
- 1. The following ADS Logic B 1A. REFER to HC.OP-EO.ZZ-0101(Q).
condition exist:
RPV Level 1 ( -129")
Associated Annunciator C1 F3
REFERENCES:
J-41-0, Sht. 13 PN1-B21-1060-0063
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 121 of 195 Rev. 7 DIGITAL ALARM POINT D4135 NOMENCLATURE ADS CH D DW PR BYP TIMER INIT SETPOINT Various DESCRIPTION ADS Logic D High Drywell Pressure ORIGIN Multiple Bypass Timer running AUTOMATIC ACTION:
ADS Logic D High Drywell Pressure Bypass Timer (5 minute) started.
OPERATOR ACTION:
VERIFY that the ADS High Drywell Pressure Bypass Timer initiation setpoint (RPV Level 1 ( -129")) has been reached.
CAUSE CORRE CTIVE ACTION
- 1. The following ADS Logic D 1A. REFER to HC.OP-EO.ZZ-0101(Q).
condition exist:
RPV Level 1 ( -129")
Associated Annunciator C1 F3
REFERENCES:
J-41-0, Sht. 13 PN1-B21-1060-0063
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 122 of 195 Rev. 7 DIGITAL ALARM POINT D4140 NOMENCLATURE SRV LO-LO SET DIV 4 ARMED SETPOINT 1047 psig DESCRIPTION SRV LO LO SET Function Initiated ORIGIN Multiple AUTOMATIC ACTION:
SRV PSV-F013P open OPERATOR ACTION:
- 1.
VERIFY AUTOMATIC ACTION AND MONITOR Reactor pressure.
- 2.
ENSURE compliance with Technical Specification 3.6.2.1, Suppression Chamber temperature requirements.
- 3. IF it is necessary to prevent SRV Low-Low Set Function Initiation OR continued operation PLACE SRV PSV-F013P Control Switch to CLOSE.
CAUSE CORRE CTIVE ACTION
- 1. High Reactor pressure 1A. Same as above.
NOTE PSV-F013P Open at 1047 psig, Close at 935 psig.
Associated Annunciator C1 E5
REFERENCES:
J-41-0, Sht. 13 PN1-B21-1060-0063
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 123 of 195 Rev. 7 DIGITAL ALARM POINT D4146 NOMENCLATURE CTMT ISLN INBD HV-9531B1 SETPOINT N/A DESCRIPTION Loop A Sup Hdr Inboard ORIGIN 1CC652 Containment Isln HV-9531B1 Overload/Power Failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B232 CHW SYS INBD ISLN 1GB-HV-9531B1
- a.
breaker trip Brkr 52-232181 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 124 of 195 Rev. 7 DIGITAL ALARM POINT D4147 NOMENCLATURE CTMT ISLN INBD HV-9531B2 SETPOINT N/A DESCRIPTION Loop A Ret Hdr Inboard ORIGIN 1CC652 Containment Isln HV-9531B2 Overload/Power Failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B232 CHW SYS INBD ISLN 1GB-HV-9531B2
- a.
breaker trip Brkr 52-232182 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 125 of 195 Rev. 7 DIGITAL ALARM POINT D4148 NOMENCLATURE CTMT ISLN INBD HV-9531B3 SETPOINT N/A DESCRIPTION ORIGIN 1CC652 Loop B Sup Hdr Inboard Containment Isln HV-9531B3 Overload/Power Failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B232 CHW SYS INBD ISLN 1GB-HV-9531B3
- a.
breaker trip Brkr 52-232183 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 126 of 195 Rev. 7 DIGITAL ALARM POINT D4149 NOMENCLATURE CTMT ISLN INBD HV-9531B4 SETPOINT N/A DESCRIPTION ORIGIN 1CC652 Loop B Ret Hdr Inboard Containment Isln HV-9531B4 Overload/Power Failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B232 CHW SYS INBD ISLN 1GB-HV-9531B4
- a.
breaker trip Brkr 52-232193 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 127 of 195 Rev. 7 DIGITAL ALARM POINT D4150 NOMENCLATURE CHW RB ISLN RTN SETPOINT N/A HV-9532-1 OPF DESCRIPTION ORIGIN 1CC652 CHW Rx Bldg Isln Ret HV-9532-1 Overload/Power Failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GB-HV-9532-1 Brkr 52-232161 is ON.
- b.
thermal overload
- c. control power fuse blown 1B. IF breaker
- d. control power transformer failure OR thermal overloads are tripped,
- e. breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 128 of 195 Rev. 7 DIGITAL ALARM POINT D4151 NOMENCLATURE SRV LO-LO SET DIV 2 ARMED SETPOINT 1047 psig DESCRIPTION SRV LO LO SET Function Initiated ORIGIN Multiple AUTOMATIC ACTION:
SRV PSV-F013H open OPERATOR ACTION:
- 1.
VERIFY AUTOMATIC ACTION AND MONITOR Reactor pressure.
- 2.
ENSURE compliance with Technical Specification 3.6.2.1, Suppression Chamber temperature requirements.
- 3. IF it is necessary to prevent SRV Low-Low Set Function Initiation OR continued operation PLACE SRV PSV-F013H Control Switch to CLOSE.
CAUSE CORRE CTIVE ACTION
- 1. High Reactor pressure 1A. Same as above.
NOTE PSV-F013H Open at 1047 psig, Close at 905 psig.
Subsequent opening 1017 psig.
Associated Annunciator C1 E5
REFERENCES:
J-41-0, Sht. 13 PN1-B21-1060-0063
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 129 of 195 Rev. 7 DIGITAL ALARM POINT D4152 NOMENCLATURE CHW RB ISLN RTN SETPOINT N/A HV-9532-2 OPF DESCRIPTION ORIGIN 1CC652 CHW Supply Rx Bldg Isln HV-9532-2 Overload/Power Failure AUTOMATIC ACTION:
Valve fails in present position.
OPERATOR ACTION:
ENSURE compliance with operability requirements of Technical Specifications 3.6.3 Primary Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GB-HV-9532-2 Brkr 52-232162 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal overloads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 F1
REFERENCES:
H-87-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 130 of 195 Rev. 7 DIGITAL ALARM POINT D4153 NOMENCLATURE AUX BOILER RCP 00C504 SETPOINT N/A DESCRIPTION Auxiliary Boiler Control Panels ORIGIN N/A 0BC502, 0CC502 and/or 00C504 Alarm AUTOMATIC ACTION:
REFER to appropriate Local Alarm Response Procedure.
OPERATOR ACTION:
DISPATCH EO to Auxiliary Boiler Control Panels 0BC502, 0CC502 AND 00C504 to determine cause of alarm.
CAUSE CORRE CTIVE ACTION
- 1. Alarm condition at Panel 0BC502.
1A REFER dispatched Operator to procedure HC.OP-AR.FA-0002(Z).
- 2. Alarm condition at Panel 0CC502.
2A REFER dispatched Operator to procedure HC.OP-AR.FA-0003(Z).
- 3. Alarm condition at Panel 00C504.
3A REFER dispatched Operator to procedure HC.OP-AR.FA-0004(Z).
- 4. IF in Winterization (10/1 thru 4/1).
4A. REFER to HC.OP-AB.MISC-0003(Q).
Associated Annunciator A2 D1
REFERENCES:
J-20-0, Sht. 2
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 131 of 195 Rev. 7 DIGITAL ALARM POINT D4169 NOMENCLATURE BLR SUBSTA WTR PRETREAT HVAC SETPOINT Multiple DESCRIPTION Alarm on Panel 00C591 ORIGIN Various AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1. DISPATCH operator to Panel 00C591 to determine the system effected and the cause of alarm.
- 2. NOTIFY SM/CRS of alarm condition.
CAUSE CORRE CTIVE ACTION
- 1.
Multiple Alarm inputs include:
1A.
RESPOND IAW HC.OP-AR.GF-0003(Z).
a) 0A(B)VH536 low flow/high DP 1B.
REQUEST SM/CRS to initiate FSL-9792A(B) corrective action.
b) 0A(B)VH537 low flow/high DP FSL-9794A(B) c) 00VH538 low flow/high DP FSL-9796 d) Boiler area temperature hi/low TSHL-9792 e) Substation temperature hi/low TSHL-9794 f) Wtr treatment temperature hi/low TSHL-9796 Associated Annunciator E6 F3
REFERENCES:
H-95-0, Sht. 1 E-6792-0
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 132 of 195 Rev. 7 DIGITAL ALARM POINT D4170 NOMENCLATURE CIRC WATER PUMP SETPOINT N/A HOUSE HVAC DESCRIPTION HVAC Trouble Alarm at Circ ORIGIN Various Water Pump House Local Panel 00C590 AUTOMATIC ACTION Alarm only OPERATOR ACTION DISPATCH Equipment Operator to Local Panel 00C590 to determine cause of the alarm.
CAUSE CORRE CTIVE ACTION
- 1. Hi/Lo ambient temp. in Pump House 1A. REFER to HC.OP-AR.GF-0001(Z);
(TSHL-9784 at 120°F Hi, 60°F Low)
Circulating Water Pump HVAC Trouble 00C590.
- 2. Hi/Lo ambient temp. in Switchgear Room (TSHL-9785 at 104°F Hi, 60°F Low)
- 3. Low air flow at a Pump House Exhaust Fan (FSL-9784 at 27,000 cfm)
- 4. Low air flow at a Switchgear Room Supply Fan (FSL-9785 at 12,000 cfm)
- 5. High differential pressure across intake filter of a Switchgear Room Supply Unit (PDSH-9785 at 0.4" wg)
Associated Annunciator A2 C3
REFERENCES:
DITS D3.57B H-95-0, Sht. 1 P-0076-0 E-0499-0, Sht. A M-81-0, Sht. 2 M-95-0, Sht. 1
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 133 of 195 Rev. 7 DIGITAL ALARM POINT D4203 NOMENCLATURE CONT ATM ANALYZER A H2 SETPOINT 2%
DESCRIPTION ORIGIN ASH-5037A Containment Hydrogen/Oxygen Analyzer 'A' High H2 Concentration AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
CHECK Containment H2/O2 Analyzer 'A' HIGH H2 light is ON AND % H2 indication is > 2% on Containment Atmosphere Section of 10650E.
- 2.
CHECK Containment H2/O2 Analyzer 'B' % H2 is > 2% on Containment Atmosphere Section of 10C650E.
CAUSE CORRE CTIVE ACTION
- 1. Meter Calibration 1A. CHECK SPAN light is ON.
1B. IF no testing in progress, PLACE 'A' H2/O2 Analyzer in service IAW HC.OP-SO.GS-0002(Q) H2/O2 Analyzer System Operation.
- 2. Inoperable H2/O2 Analyzer 2A.
IF Cntmt H2/O2 Analyzer 'B'
% H2 indicates < 2%,
REQUEST SM/CRS to initiate corrective action.
- 3. H2 generation in Drywell 3A. IF Cntmt H2/O2 Analyzers 'A' AND 'B' indicates > 0.0% H2, PLACE both H2 Recombiners in service AND NOTIFY SM/CRS.
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10 CD-195Y SER 6.2.5/p6-26
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 134 of 195 Rev. 7 DIGITAL ALARM POINT D4204 NOMENCLATURE CONT ATM ANALYZER A O2 SETPOINT 4.25%
DESCRIPTION ORIGIN ASH-5041A Containment Hydrogen/Oxygen Analyzer 'A' High O2 Concentration AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
CHECK Containment H2/O2 Analyzer 'A' HIGH O2 light is ON AND % O2 indication is > 4.25% on Containment Atmosphere Section of 10C650E.
- 2.
ENSURE compliance with operability requirements of T/S 3.3.7.5 Accident Monitoring Instrumentation and 3.6.6.2 Drywell and Suppression Chamber Oxygen Concentration.
CAUSE CORRE CTIVE ACTION
- 1. Containment de-inerted 1A. CHECK Rx Operational Condition AND ENSURE compliance with operability requirements of T/S 3.6.6.2.
- 2. Air inleakage to Drywell 2A. IF Cntmt H2/O2 Analyzers 'A' AND 'B' indicates > 4.0% O2, REDUCE O2 conc < 4% IAW HC.OP-SO.GS-0001(Q) Containment Atmosphere Control System Operation.
2B. IF trend of Nitrogen makeup indicates excessive usage, REFER TO HC.OP-AB.CONT-0002(Q),
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 135 of 195 Rev. 7 DIGITAL ALARM POINT D4204 CAUSE CORRE CTIVE ACTION
- 3. Meter Calibration 3A. CHECK SPAN light is ON.
3B. IF no testing in progress, PLACE 'A' H2/O2 Analyzer in service IAW HC.OP-SO.GS-0002(Q) H2/O2 Analyzer System Operation.
- 4. Inoperable H2/O2 Analyzer 4A. IF Cntmt H2/O2 Analyzer
'B' %O2 indicates < 4.25%,
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 136 of 195 Rev. 7 DIGITAL ALARM POINT D4205 NOMENCLATURE SETPOINT Various CONT ATM H2/O2 ANALYZER A UNIT DESCRIPTION ORIGIN XA-5042A Containment Hydrogen/Oxygen Analyzer 'A' Common Trouble Alarm AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
DISPATCH NEO to 1A-C200 H2/O2 Analyzer A Panel to determine cause of alarm.
- 2.
ENSURE compliance with operability requirements of T/S 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. Hot Box Temperature - High
- 2. Hot Box Temperature - Low REFER TO HC.OP-AR.GS-0006(Q),
H2/O2 Analyzer Panel 1A(B)C200, local alarm reponse
- 3. Reagent and Calibrate Gas Pressure - Low
- 4. Cell Failure Hi/Lo while in ANALYZE Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 137 of 195 Rev. 7 DIGITAL ALARM POINT D4212 NOMENCLATURE CONT ATM ANALYZER B H2 SETPOINT 2%
DESCRIPTION ORIGIN ASH-5037B Containment Hydrogen/Oxygen Analyzer 'B' High H2 Concentration AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
CHECK Containment H2/O2 Analyzer 'B' HIGH H2 light is ON AND % H2 indication is > 2% on Containment Atmosphere Section of 10650E.
- 2.
CHECK Containment H2/O2 Analyzer 'A' % H2 is > 2% on Containment Atmosphere Section of 10C650E.
CAUSE CORRE CTIVE ACTION
- 1. Meter Calibration 1A. CHECK SPAN light is ON.
1B. IF not testing in progress, PLACE 'A' H2/O2 Analyzer in service IAW HC.OP-SO.GS-0002(Q) H2/O2 Analyzer System Operation.
- 2. Inoperable H2/O2 Analyzer 2A. IF Cntmt H2/O2 Analyzer 'A'
% H2 indicates < 2%,
REQUEST SM/CRS to initiate corrective action.
- 3. H2 generation in Drywell 3A.
IF Cntmt H2/O2 Analyzers 'B' AND 'A' indicates > 0.0% H2, PLACE both H2 Recombiners in service AND NOTIFY SM/CRS.
REFERENCES:
J-57-0; Sht. 10 CD-195Y SER 6.2.5/p6-26
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 138 of 195 Rev. 7 DIGITAL ALARM POINT D4213 NOMENCLATURE CONT ATM ANALYZER B O2 SETPOINT 4.25%
DESCRIPTION ORIGIN ASH-5041B Containment Hydrogen/Oxygen Analyzer 'B' High O2 Concentration AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
CHECK Containment H2/O2 Analyzer 'B' HIGH O2 light is ON AND % O2 indication is > 4.25% on Containment Atmosphere Section of 10650E.
- 2.
ENSURE compliance with operability requirements of T/S 3.3.7.5 Accident Monitoring Instrumentation and 3.6.6.2 Drywell and Suppression Chamber Oxygen Concentration.
CAUSE CORRE CTIVE ACTION
- 1. Containment de-inerted 1A.
CHECK Rx Operational Condition and ENSURE compliance with operability requirements of T/S 3.6.6.2.
- 2. Air inleakage to Drywell 2A. IF Cntmt H2/O2 Analyzers 'B' and 'A' indicates > 4.0% O2, REDUCE O2 conc. < 4% IAW HC.OP-SO.GS-0001(Q) Containment Atmosphere Control System Operation.
2B. IF trend of Nitrogen makeup indicates excessive usage, REFER TO HC.OP-AB.CONT-0002(Q),
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 139 of 195 Rev. 7 DIGITAL ALARM POINT D4213 CAUSE CORRE CTIVE ACTION
- 3. Meter Calibration 3A. CHECK SPAN light is ON.
3B. IF no testing in progress, PLACE 'A' H2/O2 Analyzer in service IAW HC.OP-SO.GS-0002(Q)
H2/O2 Analyzer System Operation.
- 4. Inoperable H2/O2 Analyzer 4A.
IF Cntmt H2/O2 Analyzer 'A' %O2 indicates < 4.25%,
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 140 of 195 Rev. 7 DIGITAL ALARM POINT D4214 NOMENCLATURE SETPOINT Various CONT ATM H2/O2 ANALYZER B UNIT DESCRIPTION ORIGIN XA-5042B Containment Hydrogen/Oxygen Analyzer 'B' Common Trouble Alarm AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
DISPATCH NEO to 1B-C200 H2/O2 Analyzer B Panel to determine cause of alarm.
- 2.
ENSURE compliance with operability requirements of T/S 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. Hot Box Temperature - High
- 2. Hot Box Temperature - Low
- 3. Reagent and Calibrate Gas Pressure -
Low REFER TO HC.OP-AR.GS-0006(Q),
H2/O2 Analyzer Panel 1A(B)C200, local alarm response.
- 4. Cell Failure Hi/Lo while in ANALYZE Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 141 of 195 Rev. 7 DIGITAL ALARM POINT D4234 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-4955A OPF DESCRIPTION ORIGIN AC652 Containment Hydrogen/Oxygen Analyzer A HV-4955A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B212 H2/O2 ANALY 'A' ISLN 1GS-HV-4955A Brkr 52-212152 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e.
Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10 J-57-0; Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 142 of 195 Rev. 7 DIGITAL ALARM POINT D4235 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-5019A OPF SETPOINT DESCRIPTION ORIGIN AC652 Containment Hydrogen/
Oxygen Analyzer A HV-5019A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION MOV inoperative
- a. Breaker trip
- 1.
- b. Thermal overload 1A. DISPATCH an NEO to check 10B212 H2/O2 ANALY 'A' ISLN 1GS-HV-5019A Brkr 52-212162 is ON.
- c.
Control power fuse blown 1B.
- d.
Control power transformer failure IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10 J-57-0; Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 143 of 195 Rev. 7 DIGITAL ALARM POINT D4236 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-4959A OPF DESCRIPTION ORIGIN AC652 Containment Hydrogen/Oxygen Analyzer A HV-4959A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to CHECK 10B212 H2/O2 ANALY 'A' ISLN 1GS-HV-4959A Brkr 52-212153 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0; Sht. 10 J-57-0; Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 144 of 195 Rev. 7 DIGITAL ALARM POINT D4237 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-4966A OPF DESCRIPTION ORIGIN AC652 Containment Hydrogen/Oxygen Analyzer A HV-4966A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to CHECK 10B212 H2/O2 ANALY 'A' ISLN 1GS-HV-4966A Brkr 52-212161 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 145 of 195 Rev. 7 DIGITAL ALARM POINT D4238 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A H2 SPLY OPF DESCRIPTION ORIGIN AC652 Containment Hydrogen/Oxygen Analyzer A HV-5741A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A.
- a. Breaker trip
- b. Thermal overload DISPATCH an NEO to check 10B212 H2/O2 ANALY 'A' H2 SPLY 1GS-HV-5741A Brkr 52-212151 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 146 of 195 Rev. 7 DIGITAL ALARM POINT D4239 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4952 OPF DESCRIPTION Drywell Purge Exhaust ORIGIN AC652 1GS-SV-4952 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1AJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1AJ481-11 is on (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF401 for blown fuse 1YF401-FU08 (102' Const Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 147 of 195 Rev. 7 DIGITAL ALARM POINT D4240 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4956 OPF DESCRIPTION Drywell Purge Exhaust ORIGIN AC652 1GS-SV-4956 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1AJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1AJ481-11 is on (137' Const Bldg) 1B. CHECK Fuse Panel 1YF401 for blown fuse 1YF401-FU09 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 148 of 195 Rev. 7 DIGITAL ALARM POINT D4241 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4958 OPF DESCRIPTION Drywell Purge Exhaust ORIGIN AC652 1GS-SV-4958 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1AJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1AJ481-11 is ON (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF401 for blown fuse 1YF401-FU09 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 149 of 195 Rev. 7 DIGITAL ALARM POINT D4242 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4964 OPF DESCRIPTION Suppression Chamber Purge ORIGIN AC652 Exhaust 1GS-SV-4964 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1AJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1AJ481-11 is ON (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF401 for blown fuse 1YF401-FU08 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 150 of 195 Rev. 7 DIGITAL ALARM POINT D4243 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-4955B OPF DESCRIPTION ORIGIN BC652 Containment Hydrogen/Oxygen Analyzer B HV-4955B Overload/ Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A.
- a. Breaker trip
- b. Thermal overload DISPATCH an NEO to check 10B222 H2/O2 ANALY 'B' ISLN 1GS-HV-4955B Brkr 52-222152 is ON.
- c.
Control power fuse blown 1B.
- d.
Control power transformer failure IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 151 of 195 Rev. 7 DIGITAL ALARM POINT D4244 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-5019B OPF DESCRIPTION ORIGIN BC652 Containment Hydrogen/Oxygen Analyzer B HV-5019B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to CHECK 10B222 H2/O2 ANALY 'B' ISLN 1GS-HV-5019B Brkr 52-222162 is ON.
- c.
Control power fuse blown 1B.
- d.
Control power transformer failure IF breaker or thermal overloads are
- tripped, NOTIFY SM/CRS prior to resetting
- e. Breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 152 of 195 Rev. 7 DIGITAL ALARM POINT D4245 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-4959B OPF DESCRIPTION ORIGIN BC652 Containment Hydrogen/Oxygen Analyzer B HV-4959B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A.
- a. Breaker trip
- b. Thermal overload DISPATCH an NEO to check 10B222 H2/O2 ANALY 'B' ISLN 1GS-HV-4959B Brkr 52-222153 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 153 of 195 Rev. 7 DIGITAL ALARM POINT D4246 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-4966B OPF DESCRIPTION Containment Hydrogen/Oxygen ORIGIN BC652 Analyzer B HV-4966B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B222 H2/O2 ANALY 'B' ISLN 1GS-HV-4966B Brkr 52-222161 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are
- tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 154 of 195 Rev. 7 DIGITAL ALARM POINT D4247 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER H2 SPLY OPF DESCRIPTION ORIGIN BC652 Containment Hydrogen/Oxygen Analyzer B HV-5741B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A.
- a. Breaker trip
- b. Thermal overload DISPATCH an NEO to check 10B222 H2/O2 ANALY 'B' H2 SPLY 1GS-HV-5741B Brkr 52-222053 is ON.
- c.
Control power fuse blown 1B.
- d.
Control power transformer failure IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 155 of 195 Rev. 7 DIGITAL ALARM POINT D4248 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-4983A OPF DESCRIPTION ORIGIN CC652 Containment Hydrogen/Oxygen Analyzer A HV-4983A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B232 H2/O2 ANALY 'A' ISLN 1GS-HV-4983A Brkr 52-232091 is ON.
- c.
Control power fuse blown 1B.
- d.
Control power transformer failure IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 156 of 195 Rev. 7 DIGITAL ALARM POINT D4249 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-4984A OPF DESCRIPTION ORIGIN CC652 Containment Hydrogen/Oxygen Analyzer A HV-4984A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B232 H2/O2 ANALY 'A' ISLN 1GS-HV-4984A Brkr 52-232092 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 157 of 195 Rev. 7 DIGITAL ALARM POINT D4250 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-4965A OPF DESCRIPTION ORIGIN CC652 Containment Hydrogen/Oxygen Analyzer A HV-4965A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B232 H2/O2 ANALY 'A' ISLN 1GS-HV-4965A Brkr 52-232073 is ON.
- c. Control power fuse blown 1B.
- d. Control power transformer failure IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 158 of 195 Rev. 7 DIGITAL ALARM POINT D4251 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER A HV-5022A OPF DESCRIPTION ORIGIN CC652 Containment Hydrogen/Oxygen Analyzer A HV-5022A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B232 H2/O2 ANALY 'A' ISLN 1GS-HV-5022A Brkr 52-232093 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 159 of 195 Rev. 7 DIGITAL ALARM POINT D4252 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-4983B OPF DESCRIPTION ORIGIN DC652 Containment Hydrogen/Oxygen Analyzer A HV-4983B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B242 H2/O2 ANALY 'B' ISLN 1GS-HV-4983B Brkr 52-242091 is ON.
- c. Control power fuse blown 1B.
- d. Control power transformer failure IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 160 of 195 Rev. 7 DIGITAL ALARM POINT D4253 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-4984B OPF DESCRIPTION Containment Hydrogen/Oxygen ORIGIN DC652 Analyzer A HV-4984B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B242 H2/O2 ANALY 'B' ISLN 1GS-HV-4984B Brkr 52-242092 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 161 of 195 Rev. 7 DIGITAL ALARM POINT D4254 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-4965B OPF DESCRIPTION ORIGIN DC652 Containment Hydrogen/Oxygen Analyzer B HV-4965B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B242 H2/O2 ANALY 'B' ISLN 1GS-HV-4965B Brkr 52-242073 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. Breaker open 1C. IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 162 of 195 Rev. 7 DIGITAL ALARM POINT D4255 NOMENCLATURE SETPOINT N/A H2/O2 ANALYZER B HV-5022B OPF DESCRIPTION ORIGIN DC652 Containment Hydrogen/Oxygen Analyzer B HV-5022B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with operability requirements of T/S 3.6.3 Primary Containment Isolation Valves AND 3.3.7.5 Accident Monitoring Instrumentation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative
- a. Breaker trip
- b. Thermal overload 1A. DISPATCH an NEO to check 10B242 H2/O2 ANALY 'B' ISLN 1GS-HV-5022B Brkr 52-242093 is ON.
- c.
Control power fuse blown
- d.
Control power transformer failure 1B. IF breaker or thermal overloads are tripped, NOTIFY SM/CRS prior to resetting.
- e. breaker open 1C.
IF OVLD/PWR FAIL can not be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E3 F5
REFERENCES:
J-57-0, Sht. 10 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 163 of 195 Rev. 7 DIGITAL ALARM POINT D4256 NOMENCLATURE SETPOINT N/A DRYWELL PURGE EXH HV-4951 OPF DESCRIPTION ORIGIN DC652 Drywell Purge Exhaust 1GS-HV-4951 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
1B. CHECK Fuse Panel 1YF404 for blown fuse (102' Cont Bldg).
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action Associated Annunciator E5 A4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 164 of 195 Rev. 7 DIGITAL ALARM POINT D4257 NOMENCLATURE SETPOINT N/A TORUS PURGE EXH HV-4963 OPF DESCRIPTION ORIGIN DC652 Suppression Chamber Purge Exhaust 1GS HV-4963 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
1B. CHECK Fuse Panel 1YF404 for blown fuse (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 A4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 165 of 195 Rev. 7 DIGITAL ALARM POINT D4258 NOMENCLATURE CONT RB N2 MKUP SETPOINT N/A HV-4974 OPF DESCRIPTION Nitrogen Makeup Isolation ORIGIN DC652 1GS-HV-4974 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH EO to check NITROGEN MAKEUP ISOLATION 1GS-HV-4974 Brkr 52-242202 is ON.
- a.
breaker trip
- b.
thermal overload 1B. IF breaker
- c.
control power transformer failure OR thermal overloads are tripped,
- d.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 166 of 195 Rev. 7 DIGITAL ALARM POINT D4259 NOMENCLATURE CONT RB N2 MKUP SETPOINT N/A HV-4978 OPF DESCRIPTION Nitrogen Makeup Isolation ORIGIN DC652 1GS-SV-4978 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1DJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1DJ481-11 is ON (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF404 for blown fuse 1YF404-FU07 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 167 of 195 Rev. 7 DIGITAL ALARM POINT D4260 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4950 OPF DESCRIPTION Suppression Chamber Purge ORIGIN DC652 Exhaust 1GS-SV-4950 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1DJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1DJ481-11 is ON (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF404 for blown fuse 1YF404-FU05 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 168 of 195 Rev. 7 DIGITAL ALARM POINT D4261 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4962 OPF DESCRIPTION Suppression Chamber Purge ORIGIN DC652 Exhaust 1GS-SV-4962 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1DJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1DJ481-11 is ON (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF404 for blown fuse 1YF404-FU05 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 169 of 195 Rev. 7 DIGITAL ALARM POINT D4262 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4979 OPF DESCRIPTION Drywell Prepurge Cleanup Inlet ORIGIN DC652 1GS-SV-4979 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1DJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1DJ481-11 is ON (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF404 for blown fuse 1YF404-FU08 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 170 of 195 Rev. 7 DIGITAL ALARM POINT D4263 NOMENCLATURE PREPURGE CLNUP SETPOINT N/A HV-4980 OPF DESCRIPTION Drywell Prepurge Cleanup Inlet ORIGIN DC652 1GS-SV-4980 Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
ENSURE compliance with Technical Specifications 3.6.3 Containment Isolation Valves.
CAUSE CORRE CTIVE ACTION
- 1. Loss of Control Power/Overload 1A. DISPATCH EO to check 1DJ481 CLASS 1E, CH A, 120V Inst Dist Pnl Brkr 1DJ481-11 is ON (137' Cont Bldg) 1B. CHECK Fuse Panel 1YF404 for blown fuse 1YF404-FU08 (102' Cont Bldg) 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C4
REFERENCES:
J-57-0, Sht. 11 J-57-0, Sht. 18
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 171 of 195 Rev. 7 DIGITAL ALARM POINT D4264 NOMENCLATURE RECOMB A GAS RTN SETPOINT N/A HV-5054A OPF DESCRIPTION H2 Recombiner A Gas Return ORIGIN AC652 HV-5054A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B212 RECOMB 'A' GAS INBD ISLN 1GS-HV-5054A Bkr 52-212172 is on.
- a.
breaker trip
- b.
thermal overload 1B. IF breaker
- c.
control power fuse blown OR thermal over loads are tripped,
- d.
control power transformer failure NOTIFY SM/CRS prior to resetting.
- e.
breaker racked out 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 172 of 195 Rev. 7 DIGITAL ALARM POINT D4265 NOMENCLATURE RECOMB A GAS SPLY SETPOINT N/A HV-5050A OPF DESCRIPTION H2 Recombiner A Gas Supply ORIGIN AC652 HV-5050A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B212 RECOMB 'A' GAS INBD ISLN 1GS-HV-5050A Bkr 52-212171 is on.
- a.
breaker trip
- b.
thermal overload 1B. IF breaker
- c.
control power fuse blown OR thermal over loads are tripped,
- d.
control power transformer failure NOTIFY SM/CRS prior to resetting.
- e.
breaker racked out 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 173 of 195 Rev. 7 DIGITAL ALARM POINT D4266 NOMENCLATURE RECOMB B GAS RTN SETPOINT N/A HV-5054B OPF DESCRIPTION H2 Recombiner B Gas Return ORIGIN BC652 HV-5054B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- 1. MOV inoperative 1A. DISPATCH an EO to check MCC 10B222 RECOMB 'B' GAS INBD ISLN 1GS-HV-5054B Bkr 52-222172 is on.
- a.
breaker trip
- b.
thermal overload 1B. IF breaker
- c.
control power fuse blown OR thermal over loads are tripped,
- d.
control power transformer failure NOTIFY SM/CRS prior to resetting.
- e.
breaker racked out 1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 174 of 195 Rev. 7 DIGITAL ALARM POINT D4267 NOMENCLATURE RECOMB B GAS SPLY SETPOINT N/A HV-5050B OPF DESCRIPTION H2 Recombiner B Gas Supply ORIGIN BC652 HV-5050B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5050B Bkr 52-222171 is on.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 175 of 195 Rev. 7 DIGITAL ALARM POINT D4268 NOMENCLATURE RECOMB A GAS RTN SETPOINT N/A HV-5053A OPF DESCRIPTION H2 Recombiner A Gas Return ORIGIN CC652 HV-5053A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5053A Bkr 52-232121 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 176 of 195 Rev. 7 DIGITAL ALARM POINT D4269 NOMENCLATURE RECOMB A GAS SPLY SETPOINT N/A HV-5052A OPF DESCRIPTION H2 Recombiner A Gas Supply ORIGIN CC652 HV-5052A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5052A Bkr 52-232112 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 177 of 195 Rev. 7 DIGITAL ALARM POINT D4270 NOMENCLATURE RECOMB B GAS RTN SETPOINT N/A HV-5053B OPF DESCRIPTION H2 Recombiner B Gas Return ORIGIN DC652 HV-5053B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5053B Bkr 52-242121 is ON.
b thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 178 of 195 Rev. 7 DIGITAL ALARM POINT D4271 NOMENCLATURE RECOMB B GAS SPLY SETPOINT N/A HV-5052B OPF DESCRIPTION H2 Recombiner B Gas Supply ORIGIN DC652 HV-5052B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5052B Bkr 52-242112 is ON.
- b.
thermal overload
- c. control power fuse blown 1B. IF breaker
- d. control power transformer failure OR thermal over loads are tripped,
- e. breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 179 of 195 Rev. 7 DIGITAL ALARM POINT D4272 NOMENCLATURE RECOMB A RHR WTR SETPOINT N/A HV-5055A OPF DESCRIPTION H2 Recombiner A RHR Water ORIGIN AC652 Supply HV-5055A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5055A Bkr 52-212273 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 180 of 195 Rev. 7 DIGITAL ALARM POINT D4273 NOMENCLATURE RECOMB B RHR WTR SETPOINT N/A HV-5055B OPF DESCRIPTION H2 Recombiner B RHR Water ORIGIN BC652 Supply HV-5055B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5055B Bkr 52-222192 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 181 of 195 Rev. 7 DIGITAL ALARM POINT D4274 NOMENCLATURE RECOMB A RHR WTR SETPOINT N/A HV-5057A OPF DESCRIPTION H2 Recombiner A RHR ORIGIN CC652 Water Supply HV-5057A Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H2 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5057A Bkr 52-232202 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 182 of 195 Rev. 7 DIGITAL ALARM POINT D4275 NOMENCLATURE RECOMB B RHR WTR SETPOINT N/A HV-5057B OPF DESCRIPTION H2 Recombiner B RHR ORIGIN DC652 Water Supply HV-5057B Overload/Power Failure AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
- 1.
ENSURE compliance with operability requirements of Technical Specifications 3.6.1.1 Primary Containment Integrity.
- 2. IF necessary, USE alternate H3 Recombiner IAW HC.OP-SO.GS-0003(Q); Containment Hydrogen Recombiner System Operation.
CAUSE CORRE CTIVE ACTION
- a.
breaker trip 1GS-HV-5057B Bkr 52-242222 is ON.
- b.
thermal overload
- c.
control power fuse blown 1B. IF breaker
- d.
control power transformer failure OR thermal over loads are tripped,
- e.
breaker racked out NOTIFY SM/CRS prior to resetting.
1C. IF OVLD/PWR FAIL cannot be cleared, REQUEST SM/CRS to initiate corrective action.
Associated Annunciator E5 C5
REFERENCES:
J-58-0, Sht. 3; Sht. 4
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 183 of 195 Rev. 7 DIGITAL ALARM POINT D4276 NOMENCLATURE RCIC ISOLATION SETPOINT POWER LOSS DESCRIPTION ORIGIN AT4 at Pnl P621 Loss of Input/Output card, power to Isolator, Channel B AT4 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Reactor Core Isolation Cooling System operability limits of Technical Specifications 3.7.4.
NOTE Due to optical isolation card trouble, the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored.
INPUTS Digital Point/
Indication Nomenclature/Condition Automatic Action D3553 RCIC TURB OUTBD BRG OIL TEMP Alarm only D3554 RCIC TURB INBOARD BRG OIL TEMP Alarm only D3555 RCIC VACUUM TANK LEVEL Alarm only D3556 RCIC TURB OIL FLTR DIFF PRESS Alarm only D3557 RCIC VACUUM TANK LEVEL Alarm only D3561 RCIC CHAN B ISLN RESET REQUIRED Alarm only D3558 RCIC MNL INITIATION SW ARMED Alarm only D5339 RCIC OUT OF SERVICE Alarm only
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 184 of 195 Rev. 7 DIGITAL ALARM POINT D4276 CAUSE CORRE CTIVE ACTION
- 1. Input/Output Isolator Card out of file 1A. REQUEST SM/CRS to initiate corrective action.
- 2. Input/Output Isolator Card failure 2A. REQUEST SM/CRS to initiate corrective action.
- 3. Input power breaker tripped 3A. CHECK 120 VAC Instrument Bus B 1BJ481 Brkr #18 (P618 Panel) for trip 3B. WHEN directed by SM/CRS RESET the breaker
- 4. Input power fuse blown 4A. CHECK AND REPLACE if necessary, 5 amp F48 fuse at Panel P618.
4B. CHECK AND REPLACE if necessary, 10 amp fuse F41B at Panel P618.
- 5. Output card power failure 5A. REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B1 F2
REFERENCES:
N1-E51-1040-59(16)-15 N1-E51-1040-59(
5)-11 N1-E51-1040-59(15)-18 N1-E21-1040-383(6B)
-10 N1-E21-1040-383(6A)
-11 E-6769-0, Sht. 1; Sht. 2
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 185 of 195 Rev. 7 DIGITAL ALARM POINT D4277 NOMENCLATURE RCIC CH D ISLN RESET SETPOINT N/A REQUIRED DESCRIPTION RCIC Channel D Isolation Reset Switch in Reset ORIGIN S25 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF the logic is reset, PLACE ISOLATION LOGIC D in NORMAL.
CAUSE CORRE CTIVE ACTION
- 1. ISOLATION LOGIC D Switch placed in RESET 1A. IF logic resetting is complete, PLACE ISOLATION LOGIC D in NORMAL.
Associated Annunciator B1 D2
REFERENCES:
J-50-0, Sht. 10 N1-E51-1040-59(17)-8 N1-E51-1040-59(
8)-17
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 186 of 195 Rev. 7 DIGITAL ALARM POINT D4278 NOMENCLATURE RCIC WARM-UP ISOLATION SETPOINT N/A VLV F076 DESCRIPTION RCIC Warmup Isln Vlv ORIGIN ZS-F076 not fully closed AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
IF RCIC steam line is NOT being warmed-up, CLOSE HV-F076 RCIC STM LINE WARMUP VLV.
CAUSE CORRE CTIVE ACTION
- 1. HV-F076 RCIC STM LINE WARM-UP VLV is opened for warming-up 1A. CLOSE the valve after warming-up the RCIC System Associated Annunciator B1 D2
REFERENCES:
J-49-0, Sht. 13 N1-E51-1040-59(12)-13
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 187 of 195 Rev. 7 DIGITAL ALARM POINT D4279 NOMENCLATURE RCIC VAC BRKR ISLN V F084 SETPOINT N/A DESCRIPTION RCIC Vac Brkr Vlv ORIGIN ZS-F084 HV-F084 not fully open AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE limiting conditions for operation of RCIC System in accordance with Technical Specifications 3.7.4.
CAUSE CORRE CTIVE ACTION
- 1. Valve is being tested 1A. OPEN valve after test
- 2. RCIC Turbine Steam supply pressure
< 64.5 psig (after a 4 second time delay)
AND Drywell pressure > 1.68 psig 2A. IF RCIC is being operated for non-emergency purpose, TRIP the turbine.
2B. OPEN HV-F084 RCIC VAC BRKR VLV WHEN directed by SM/CRS
- 3. Improper valve lineup 3A.
ENSURE proper valve lineup IAW HC.OP-SO.BD-0001(Q)
Associated Annunciator B1 D2
REFERENCES:
N1-E51-1040-59( 6)-18 N1-E51-1040-59(10)-15 N1-E51-1040-59(14)-11 J-49-0, Sht. 13
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 188 of 195 Rev. 7 DIGITAL ALARM POINT D4280 NOMENCLATURE RCIC ISOLATION SETPOINT POWER LOSS DESCRIPTION ORIGIN AT1 at Pnl P640 Loss of Input/Output card, power to Isolator, Channel D AT1 AUTOMATIC ACTION:
Alarm only OPERATOR ACTION:
OBSERVE Reactor Core Isolation Cooling System operability limits of Technical Specifications 3.7.4.
NOTE Due to optical isolation card trouble the following alarms will not be annunciated on the panel.
It is recommended that the associated parameters of digital points be monitored.
INPUTS Digital Point/
Indication Nomenclature/Condition Automatic Action D4277 RCIC CH D ISLN RESET REQUIRED Alarm only D4279 RCIC VACUUM BRK ISLN VLV F084 Alarm only D4286 RCIC STREAM LINE DIFF PRESS Alarm only D4287 RCIC TURB EXH DIAPH RUPTURED Alarm only D4288 RCIC STEAM SUPPLY PRESS Alarm only D7132 RCIC ISOLATION BYP VLV HV-F076 Alarm only D3559 RCIC OUT OF SERVICE Alarm only
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 189 of 195 Rev. 7 DIGITAL ALARM POINT D4280 CAUSE CORRE CTIVE ACTION
- 1. Input/Output Isolator Card out of file 1A. REQUEST SM/CRS to initiate corrective action.
- 2. Input/Output Isolator Card failure 2A. REQUEST SM/CRS to initiate corrective action.
- 3. Input power breaker tripped 3A. CHECK 120 VAC Instrument Bus D 1DJ481 Brkr #20 (P640 Pnl) for trip.
3B.
WHEN directed by SM/CRS RESET the breaker.
- 4. Input power fuse blown 4A. CHECK AND REPLACE if necessary, 5 amp F46 fuse at Panel P640.
4B. CHECK AND REPLACE if necessary, 10 amp fuse F41D at Panel P640.
- 5. Output Card power failure 5A.
REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B1 F2
REFERENCES:
N1-E51-1040-59(16)-15 N1-E51-1040-59(
5)-11 N1-E51-1040-59(15)-18 N1-E21-1040-383(6B)
-10 N1-E21-1040-383(6A)
-11 E-6769-0, Sht. 1; Sht. 2
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 190 of 195 Rev. 7 DIGITAL ALARM POINT D4282 NOMENCLATURE SETPOINT
> 10 psig RCIC TURB EXH DIAPH B/F RUPTD DESCRIPTION ORIGIN RCIC Turbine exhaust diaphragm ruptured PISH-N655B PISH-N655F AUTOMATIC ACTION:
IF the signal is from BOTH the sensors, Turbine trips under Auto-Isolation, otherwise alarm only OPERATOR ACTION:
- 1.
VALIDATE alarm by checking PI-R603 TURBINE EXH PRESS (Blue)
- 2.
ENSURE compliance with operability requirements of Technical Specifications 3.7.4, 3.3.2.
CAUSE CORRE CTIVE ACTION
- 1. HV-F059 TURBINE EXHAUST VLV is closed.
1A. ENSURE HV-F059 TURBINE EXHAUST VLV is open.
- 2. Check Valve V003 is stuck closed.
2A. REQUEST SM/CRS to initiate corrective action.
- 3. Mechanical failure of diaphragm 3A REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B1 B1
REFERENCES:
J-50-0, Sht. 10 N1-E51-1040-59(
9)-16 N1-E51-1040-59(
6)-18 N1-E51-1040-59(10)-15
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 191 of 195 Rev. 7 DIGITAL ALARM POINT D4283 NOMENCLATURE RCIC STEAM SUPPLY PRESS B/F SETPOINT
< 64.5 psig w/4sec TD DESCRIPTION RCIC Steam Supply Pressure low ORIGIN PISL-N658B or PISL-N658F AUTOMATIC ACTION:
RCIC Div 2 isolation AND Turbine trip OPERATOR ACTION:
- 1.
RESET System Logic B WHEN directed by SM/CRS in accordance with HC.OP-SO.BD-0001(Q).
- 2.
OBSERVE limiting conditions for operation of RCIC System in accordance with Technical Specifications 3.7.4, 3.3.2.
CAUSE CORRE CTIVE ACTION
- 1. Improper valve lineup 1A. ENSURE proper valve lineup IAW HC.OP-SO.BD-0001(Q).
- 2. Low Reactor pressure 2A. ----
- 3. Steam supply line break 3A. CHECK the following for abnormalities:
- 1.
PI-602 TURBINE INL PRESS
- 2.
PI-R603 TURBINE EXH PRESS
- 3.
SI-4280-1 TURBINE SPEED Associated Annunciator B1 C1
REFERENCES:
J-49-0, Sht. 15 N1-E51-1040-59(10)-15 N1-E51-1040-59(
8)-17
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 192 of 195 Rev. 7 DIGITAL ALARM POINT D4284 NOMENCLATURE RCIC STEAM LINE B DIFF PRESS SETPOINT 272-300% Normal Flow
( 598" H2O)
OR - 50" H2O DESCRIPTION RCIC Steam line flow high ORIGIN PDISH-N657B PDSH-N660B AUTOMATIC ACTION:
- 1.
RCIC Steam Line Outbd Isln Vlv HV-F008 closes.
- 2.
OPERATOR ACTION:
- 1.
RESPOND in accordance with HC.OP-AR.ZZ-0006(Q), Attachment A1.
- 2.
OBSERVE LIMITING conditions for operation of RCIC System in accordance with Technical Specifications 3.7.4, 3.3.2.
CAUSE CORRE CTIVE ACTION
- 1. Improper valve lineup 1A. ENSURE proper valve lineup IAW HC.OP-SO.BD-0001(Q)
- 2. RCIC steam supply/instrument line break 2A. CHECK the following for any abnormalities to validate the alarm:
- 1.
D4286 RCIC STEAM LINE D DIFF PRESS
- 2.
PI-R602 TURBINE INL PRESS
- 3.
PR-4960B2 (CONTAINMENT ATMOSPHERE) DRYWELL PRESSURE (BLUE)
- 4.
TR-4967B2 (CONTAINMENT ATMOSPHERE) DRYWELL ATMOSPHERE TEMPERATURE (BLUE)
- 5.
D5858 RCIC STM LEAK DETECT TEMP CH D
- 6.
D5860 RCIC/RHR STM LEAK DETECT TEMP CH B Associated Annunciator B1 A2
REFERENCES:
J-49-0, Sht. 15 E51-9-1, Sht. 7
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 193 of 195 Rev. 7 DIGITAL ALARM POINT D4286 NOMENCLATURE RCIC STEAM LINE D DIFF PRESS SETPOINT 272-300% Normal Flow
( 598" H2O)
OR - 50" H2O DESCRIPTION RCIC Steam line flow high ORIGIN PDISH-N657D PDSH-N660D AUTOMATIC ACTION:
- 1.
RCIC STEAM LINE INBD ISLN VLV HV-F007 closes.
- 2.
RCIC WARM-UP ISOLATION HV-F076 closes
- 3.
OPERATOR ACTION:
- 1.
RESPOND in accordance with HC.OP-AR.ZZ-0006(Q), Attachment A1.
- 2.
OBSERVE limiting conditions for operation of RCIC System in accordance with Technical Specifications 3.7.4, 3.3.2.
CAUSE CORRE CTIVE ACTION
- 1. Improper valve lineup 1A. ENSURE proper valve lineup IAW HC.OP-SO.BD-0001(Q)
- 2. RCIC steam supply/instrument line break 2A. CHECK the following for any abnormalities to validate the alarm:
- 1.
D4284 RCIC STEAM LINE B DIFF PRESS
- 2.
PI-R602 TURBINE INL PRESS
- 3.
PR-4960B2 (CONTAINMENT ATMOSPHERE) DRYWELL PRESSURE (BLUE)
- 4.
TR-4967B2 (CONTAINMENT ATMOSPHERE) DRYWELL ATMOSPHERE TEMPERATURE (BLUE)
- 5.
D5858 RCIC STM LEAK DETECT TEMP CH D
- 6.
D5860 RCIC/RHR STM LEAK DETECT TEMP CH B Associated Annunciator B1 A2
REFERENCES:
J-49-0, Sht. 15 E51-9-1, Sht. 7
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 194 of 195 Rev. 7 DIGITAL ALARM POINT D4287 NOMENCLATURE SETPOINT
> 10 psig RCIC TURB EXH DIAPH D/H RUPTD DESCRIPTION ORIGIN RCIC turbine exhaust diaphragm ruptured PISH-N655D PISH-N655H AUTOMATIC ACTION:
IF the signal is from BOTH the sensors, turbine trips under auto-isolation, otherwise alarm only OPERATOR ACTION:
- 1.
VALIDATE alarm by checking PI-R603 TURBINE EXH PRESS (Blue)
- 2.
ENSURE compliance with operability requirements of Technical Specifications 3.7.4, 3.3.2.
CAUSE CORRE CTIVE ACTION
- 1. HV-F059 TURBINE EXHAUST VLV is closed.
1A. ENSURE HV-F059 TURBINE EXHAUST VLV is open.
- 2. Check Valve V003 is stuck closed.
2A. REQUEST SM/CRS to initiate corrective action.
- 3. Mechanical failure of diaphragm 3A. REQUEST SM/CRS to initiate corrective action.
Associated Annunciator B1 B1
REFERENCES:
J-50-0, Sht. 10 N1-E51-1040-59(
9)-16 N1-E51-1040-59(
6)-18 N1-E51-1040-59(10)-15
HC.OP-AR.ZZ-0024(Q)
Hope Creek Page 195 of 195 Rev. 7 DIGITAL ALARM POINT D4288 NOMENCLATURE SETPOINT
< 64.5 psig w/4sec TD RCIC STEAM SUPPLY PRESS D/H DESCRIPTION RCIC Steam Supply Pressure low ORIGIN PISL-N658D or PISL-N658H AUTOMATIC ACTION:
RCIC Div 4 isolation AND Turbine trip OPERATOR ACTION:
- 1.
RESET System Logic D WHEN directed by SM/CRS in accordance with HC.OP-SO.BD-0001(Q).
- 2.
OBSERVE limiting conditions for operation of RCIC System in accordance with Technical Specifications 3.7.4, 3.3.2.
CAUSE CORRE CTIVE ACTION
- 1. Improper valve lineup 1A. ENSURE proper valve lineup IAW HC.OP-SO.BD-0001(Q).
- 2. Low Reactor pressure 2A. ----
- 3. Steam supply line break 3A. CHECK the following for abnormalities:
- 1.
PI-602 TURBINE INL PRESS
- 2.
PI-R603 TURBINE EXH PRESS
- 3.
SI-4280-1 TURBINE SPEED Associated Annunciator B1 C1
REFERENCES:
J-49-0, Sht. 15 N1-E51-1040-59(10)-15 N1-E51-1040-59(
8)-17