Text
Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 This letter forwards proprietary information in accordance with 10 CFR 2.390. The balance of this letter may be considered lF= L non-proprietary upon removal of the identified sections of Attachment 5.
November 22, 2010 L-2010-259 10 CFR 50.90 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Re:
St. Lucie Plant Unit I Docket No. 50-335 Renewed License No. DPR-67 License Amendment Request for Extended Power Uprate On April 16, 2010, Florida Power and Light Company (FPL) submitted a license amendment request (LAR) to the U. S. Nuclear Regulatory Commission (NRC) which proposed an amendment to Renewed Operating License No. DPR-67 for St. Lucie Plant Unit I to increase the licensed core power level from 2700 MWt to 3020 MWt. (ML101160182). By letter dated August 13, 2010, FPL withdrew the April 16, 2010 license amendment request and stated that it may re-submit a revised application at a future time (ML102290018). The NRC acknowledged FPL's request to withdraw the April 16, 2010 license amendment request by letter dated August 13, 2010 (ML102240195). Additionally, the NRC provided supplemental information specifying the areas where additional information was required to enable the NRC staff to complete its detailed review of the application.
Pursuant to 10 CFR 50.90, FPL hereby re-submits a request for an amendment to Renewed Operating License No. DPR-67 for St. Lucie Plant Unit 1. The proposed LAR addresses the information requested in the enclosure to the NRC's letter to FPL dated August 13, 2010 pertaining to Spent Fuel Pool Criticality, Control Rod Withdrawal at Power, and Station Blackout (SBO) Coping Analysis. Additionally, a summary of the substantive changes made to this LAR is provided in Enclosure I of this letter.
an FPL Group company
L-2010-259 Page 2 The proposed LAR will increase the licensed core power level of Unit I from 2700 MWt to 3020 MWt and revise the Renewed Operating License and the Technical Specifications to support operation at this increased core thermal power level. This represents a net increase in licensed thermal power of approximately 11.85% and includes a 10.0% extended power uprate and a 1.7% measurement uncertainty recapture (MUR). The net increase from the current core thermal power level is calculated as follows:
(2700 MWt x 1.10) x 1.017% z 3020 MWt (3020 - 2700 MWt) / 2700 MWt = 11.85%
Therefore, this amendment is an Extended Power Uprate (EPU). The increase in core thermal power is currently planned to be accomplished mid-cycle, after the fall 2011 refueling outage.
St. Lucie Unit I Amendment No. 48 dated November 23, 1981 (ML013530273) approved a Stretch Power Uprate from 2560 MWt to 2700 MWt. The proposed EPU core thermal power level represents an increase of approximatelyl 8 percent from the original licensed thermal power level of 2560 MWt.
The proposed LAR was developed using the guidance provided in RS-001, "Review Standard for Extended Power Uprates," Revision 0, dated December 2003 as it applies to the design bases of St. Lucie Plant Unit 1. The proposed LAR was also developed consistent with the format and content contained in the R.E. Ginna Nuclear Power Plant for an EPU (ML051950123).
Plant modifications to support EPU are being implemented over time. A list of key plant modifications (plant changes) associated with the proposed EPU is provided in, Section 1.0.
Attachment I contains the Descriptions and Technical Justifications for the changes to the Renewed Facility Operating License, Technical Specifications, and License Basis. In accordance with 10 CFR 50.91 (a)(1), FPL has completed a No Significant Hazards Consideration analysis and concludes that the changes proposed by this license amendment request present no significant hazards under the standards set forth in 10 CFR 50.92(c), and accordingly, a finding of"no significant hazards consideration" is justified.
FPL's No Significant Hazards Consideration analysis is included in Attachment 1. contains the Supplemental Environmental Report. This report presents FPL's assessment of the environmental impacts associated with St. Lucie Units I and 2 EPU from the current licensed core rated power level of 2700 MWt to an updated core power level of 3020 MWt. This report demonstrates that the EPU will not significantly affect human health or the natural environment.
L-2010-259 Page 3 contains the Renewed Facility Operating License, Technical Specifications Markups, and Clean Pages. This attachment is provided to facilitate identification of the proposed changes and retyped Operating License and Technical Specifications pages. contains the Technical Specification Bases Markups. This attachment is provided as information only to facilitate identification of the proposed bases. contains the Licensing Report (LR). The LR follows the guidance of RS-001. The LR demonstrates that the EPU can be safely achieved, and that the increase will not be inimical to the common defense and security or to the health and safety of the public. The LR provides the details supporting the requested power uprate, and is supported by the other attachments to the LAR to provide a comprehensive evaluation of the effects of the EPU. The LR is supported by nine appendices: Appendix A - Safety Evaluation Report Compliance; Appendix B - Additional Codes & Methods; Appendix C
- Realistic Large Break LOCA Summary Report with Zr-4 Fuel Cladding; Appendix D -
List of Key Acronyms; Appendix E - Supplement to LR Section 2.4.1, Reactor Protection, Engineered Safety Features Actuation, and Control Systems; Appendix F -
Caldon Ultrasonics Engineering Reports; AppendixG - WCAP-! 7197-NP, Revision 0, St. Lucie Unit I RCS Pressure and Temperature Limits and Low-Temperature Overpressure Protection Report for 54 Effective Full Power Years; Appendix H - Grid Stability Analysis and System Impact Study for St. Lucie Plant with Proposed EPU; and Appendix I - Holtec Criticality Analysis Reports. contains copies of the Proprietary Information Affidavits. The purpose of this attachment is to withhold the proprietary information contained in the specified tables and appendices of the LR (Attachment 5) from public disclosure. Attachment 5 contains information proprietary to Westinghouse Electric Company, LLC (Westinghouse), ArevaNP Inc. (Areva), Cameron International Corporation (Cameron),
Holtec International (Holtec) and Babcock & Wilcox Canada Ltd. (B&W). Affidavits signed by Westinghouse, Areva, Cameron, Holtec and B&W as the owners of the information set forth the basis for which the information may be withheld from public disclosure by the Commission and address with specificity the considerations listed in paragraph (b)(4) of § 2.390 of the Commission's regulations. Accordingly, it is respectfully requested that the information which is proprietary to Westinghouse, Areva, Cameron, Holtec and B&W be withheld from public disclosure in accordance with 10 CFR 2.390.
Correspondence with respect to the copyright or proprietary aspects of the items provided in Attachment 5 of this letter in LR Sections 2.2.2.1, 2.2.2.3, 2.2.2.4, 2.2.2.6 and 2.2.3, or the supporting Westinghouse affidavit should reference CAW-10-3007 and be addressed to J. A. Gresham, Manager Regulatory Compliance and Plant Licensing, Westinghouse Electric Company LLC, P.O. Box 355, Pittsburgh, Pennsylvania 15230-0355.
Correspondence with respect to the copyright or proprietary aspects of the items provided in Attachment 5 of this letter in LR Section 2.2.2.5 or the supporting B&W affidavit
L-2010-259 Page 4 should be addressed to Jeffrey Millman, Manager, Nuclear Engineering, Babcock &
Wilcox Canada Ltd., 581 Coronation Blvd., Cambridge, Ontario, NIR 5V3, Canada.
Correspondence with respect to the copyright or proprietary aspects of the items provided in Appendix C of Attachment 5 of this letter in Page 3-7; Table 3-2; Table 3-7; Figure 3-1; Figure 3-2; Figure 3-3; Figure 3-4; and Figure 3-5 or the supporting Areva affidavit should be addressed to Gayle F. Elliott, Manager, Product Licensing, Areva NP Inc., P.O.
Box 10935, Lynchburg, VA 24506-0935.
Correspondence with respect to the copyright or proprietary aspects of the items provided in Appendix F of Attachment 5 of this letter or the supporting Cameron affidavit should reference CAWIO-08 and should be addressed to Ernest M. Hauser, Director of Sales, Cameron International Corporation, Caldon Ultrasonics Technology Center, 1000 McClaren Woods Drive, Coraopolis, PA 15108.
Correspondence with respect to the copyright or proprietary aspects of the items provided in Appendix I of Attachment 5 of this letter or the supporting Holtec affidav.it should be addressed to Jay Leff, Project Manager, Holtec International, Holtec Center, 555 Lincoln Drive West, Marlton, NJ 08053., Summary of Regulatory Commitments, provides the regulatory commitments made based upon the analyses and plant changes that are summarized in., 10 CFR 50.63 Station Blackout DC Coping, provides an analysis of the plant's ability to cope on dc power for the first hour of a station blackout event., Core Operating Limits Report Markups, provides the proposed changes made to the Core Operating Limits Report and is provided for information only.
In accordance with 10 CFR 50.91, a copy of this license amendment request is being provided to the designated State of Florida official.
Approval of this license amendment request is requested by February 1, 2012 to allow implementation of the EPU following the 2011 Unit 1 refueling outage. Should you have any questions regarding the information provided in this submittal, please contact Mr.
Chris Wasik, St. Lucie Extended Power Uprate LAR Project Manager, at 772-429-7138.
I declare under penalty of perjury that the foregoing is true and correct to the best of my knowledge.
L-2010-259 Page 5 Executed on i CAA-4 Very truly yours, Richard L. Anderson Site Vice President St. Lucie Plant Attachments: I proprietary and I non-proprietary EPU LAR CD cc:
Administrator, Region I1, USNRC Project Manager, St. Lucie Nuclear Plant, USNRC Senior Resident Inspector, St. Lucie Nuclear Plant, USNRC Mr. William Passetti, Florida Department of Health
L-2010-259 Page 6 ENCLOSURE 1 Summary of Substantive Changes Since FPL's April 16, 2010 Submittal This enclosure is provided as an aid to the NRC; it identifies those portions of the St. Lucie Unit I extended power uprate license amendment request (LAR) that have changed significantly since the previously submitted and subsequently withdrawn LAR.
LAR Sci Title Change Summary Section Descriptions and Technical Justifications for the Renewed Facility Operating Revised to reflect the new spent fuel pool criticality analysis.
Attachment I License, Technical Specifications, and Licensing Basis Changes Renewed Facility Operating License and Technical Specifications Markups and Revised to reflect the new spent fuel pool criticality analysis.
Clean Pages Revised to reflect commitments associated with the updated Summary of Regulatory Commitments spent fuel pool criticality analysis and the environmental qualification of electrical equipment.
o Coping analysis has been separated from the EPU station blackout discussion based on discussions with the NRC.
o Coping analysis has been revised to address feedback from 10 CFR 50.63 Station Blackout DC the NRC (NRC letter to FPL dated 8/13/10; TAC No.
Coping ME3699).
o Previous loss of ventilation analyses that extrapolated results of the original 25-minute calculations to 60-minutes were replaced with new 60-minute Gothic analyses. Licensing Report (LR) Sections 2.1.9 Steam Generator Tube Inservice Added detail on tube wear (NRC RAIs from another EPU)
Inspection 2.2.2.2 Balance of Plant Piping, Components Added detail on pipe support modifications and flow-induced and Supports vibration (NRC RAIs from another EPU).
Added detail on tube wear, flow-induced vibration and loose parts monitoring (NRC RAIs from another EPU).
Added detail on environmental qualification of electrical 2.3.1 Environmental Qualification of equipment as provided in FPL's response to NRC acceptance Electrical Equipment review questions (FPL letter L-2010-162 dated 7/30/10).
L-2010-259 Page 7 Sci Title Change Summary Section Based on discussions with the NRC, this section was revised to 2.3.5 Station Blackout remove the dc coping analysis, which is now presented in.
Revised to conform to updated CEA withdrawal analyses (LR 2.8.5.0 Accident and Transient Analyses Sections 2.8.5.4.1 and 2.8.5.4.2).
Feedwater System Pipe Breaks Inside Revised to add detail related to credited mitigating systems as 2.8.5.2.4 and Outside Containment provided in FPL's response to NRC acceptance review questions (FPL letter L-2010-144 dated 7/23/10).
Uncontrolled Control Rod Assembly Revised to address feedback from the NRC (NRC letter to FPL 2.8.5.4.1 Withdrawal from a Subcritical or Low-dated 8/13/10; TAC No. ME3699).
Power Startup Condition Uncontrolled Rod Cluster Control Revised to address feedback from the NRC (NRC letter to FPL Assembly Withdrawal at Power dated 8/13/10; TAC No. ME3699),
Inadvertent Opening of Pressurizer Revised to add detail related to RCS level as provided in FPL's 2.8.5.6.1 Relief Valve response to NRC acceptance review questions (FPL letter L-2010-144 dated 7/23/10).
Emergency Core Cooling System and Revised to add detail related to RCS level as provided in FPL's 2.8.5.6.3 Loss-of-Coolant Accidents response to NRC acceptance review questions (FPL letter L-2010-144 dated 7/23/10).
Revised to reflect the new spent fuel pool criticality analysis performed to addresses feedback from the NRC (NRC letter to 2.8.6.2 Spent Fuel Storage FPL dated 8/13/10; TAC No. ME3699) and NRC draft interim staff guidance, DSS-ISG-2010-01, Spent Fuel Pool Criticality Analysis.
Revised to add code MCNP5 used in support of the new spent App. B Additional Codes and Methodsfulpocrtaiyanys.
fuel pool criticality analysis.
Grid Stability Analysis and System New appendix that provides the grid stability analysis as App. H Impact Study for St. Lucie Plant with provided in FPL's response to NRC acceptance review questions Proposed EPU (FPL letter L-2010-144 dated 7/23/10).
New appendix that provides supporting documentation related to App. I Holtec Criticality Analysis Reports the new spent fuel pool criticality analysis presented in LR Section 2.8.6.2.
Non-Public Files:
001 Att 1 OL TS & Lic Basis Chgs.pdf 002 Att 2 Supp Environmental Report.pdf 003 Att 3 Markup & Clean OL & TS pages.pdf 004 Att 4 Markup TS Bases pages.pdf 005 Att 5 EPU Licensing Report np.pdf 006 Att 5 EPU LR App A.pdf 007 Att 5 EPU LR App B.pdf 008 Att 5 EPU LR App C Realistic LBLOCA Report np.pdf 009 Att 5 EPU LR App D.pdf 010 Att 5 EPU LR App E.pdf 011 Att 5 EPU LR App F pt lnp.pdf 012 Att 5 EPU LR App F pt 2_np.pdf 013 Att 5 EPU LR App F pt 3_np.pdf 014 Att 5 EPU LR App F pt 4_np.pdf 015 Att 5 EPU LR App G PTL & LTOP Report.pdf 016 Ant5 EPU LR App H Grid Stability & System Impact.pdf 017 Att 5 EPU LR App I pt 1 Criticality Analysis np.pdf 018 Att 5 EPU LR App I pt 2 MCNP Calcs np.pdf 019 Aft 6 Appl for Withhold Prop Info.pdf 020 Att 7 Summary of Reg Commitments.pdf 021 Att 8 10 CFR 50.63 SBO DC Coping.pdf 022 Att 9 COLR Markups.pdf 339,372 Bytes 5,028,268 Bytes 16,012,784 Bytes 134,145 Bytes 10,668,701 Bytes 250,067 Bytes 104,884 Bytes 18,085,697 Bytes 112,266 Bytes 122,275 Byte 35,344,106 Bytes 27,581,234 Bytes 43,820,468Bytes 28,589,830 Bytes 22,563,441 Bytes 4,058,780 Bytes 41,137,991 Bytes 10,297,467 Bytes 8,986,560 Bytes 111,105 Bytes 8,299,146 Bytes 5,275,224 Bytes publicly available publicly available publicly available publicly available Proprietary publicly -available publicly available Proprietary publicly available publicly available Proprietary Proprietary Proprietary Proprietary publicly available publicly available Proprietary Proprietary publicly available publicly available publicly available publicly available
Public Files:
001 Att 1 OL TS & Lic Basis Chgs.pdf 002 Att 2 Supp EnvironmentalReport.pdf 003 Att 3 Markup & Clean OL & TS pages.pdf 004 Att 4 Markup TS Bases pages.pdf 005 Att 5 EPU Licensing Reportp.pdf 006 Att 5 EPU LR App A.pdf 007 Att 5 EPU LR App B.pdf 008 Att 5 EPU LR App C Realistic LBLOCA Reportp.pdf 009 Att 5 EPU LR App D.pdf 010 Att 5 EPU LR App E.pdf 011 Att 5 EPU LRApp Fp.pdf 012 Att 5 EPU LR App G PTL & LTOP Report.pdf 013 Att5EPU LR App H Grid Stability & System Impact.pdf 014 Att 5 EPU LR App I Crit Anal & MCNP Calcs p.pdf 015 Att 6 Appl for Withhold Prop Info.pdf 016 Att 7 Summary of Reg Commitments.pdf 017 Ant 8 10 CFR 50.63 SBO DC Coping.pdf 018 Att 9 COLR Markups.pdf 339,373 Bytes 5,028,268 Bytes 15,045,259 Bytes 134,145 Bytes 9,023,252 Bytes 250,067 Bytes 104,884 Bytes 17,852,371 Bytes 112,266 Bytes 122,275 Bytes 123,906 Bytes 22,563,441 Bytes 4,058,780 Bytes 1,402,263 Bytes 8,896,560 Bytes 111,105 Bytes 8,299,146 Bytes 5,275,224 Bytes publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available publicly available
(
)Westinghouse Westinghouse Electric Company Nuclear Services P.O. Box 355 Pittsburgh, Pennsylvania 15230-0355 USA U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Direct tel:
Direct fiax:
e-mail:
Prmlect Ltr:
(412) 374-4643 (412) 374-3846 greshaja@westinghouse.comn FPL-10-384 CAW-] 0-3007 November 9, 2010 APPLICATION FOR WITHHOLDING PROPRIETARY INFORMATION FROM PUBLIC DISCLOSURE
Subject:
Information Supporting St. Lucie Unit I Extended Power Uprate (EPU) (Proprietary)
The proprietary information for which withholding is being requested in the above-referenced report is further identified in Affidavit CAW-1 0-3007 signed by the owner of the proprietary information, Westinghouse Electric Company LLC. The affidavit, which accompanies this letter, sets forth the basis on which the information may be withheld from public disclosure by the Commission and addresses with specificity the considerations listed in paragraph (b)(4) of 10 CFR Section 2.390 of the Commission's regulations.
Accordingly, this letter authorizes the utilization of the accompanying affidavit by Florida Power & Light Company, in conjunction with its EPU application to the NRC Correspondence with respect to the proprietary aspects of the application for withholding or the Westinghouse affidavit should reference this letter, CAW-1 0-3007, and should be addressed to J. A. Gresham, Manager, Regulatory Compliance and Plant Licensing, Westinghouse Electric Company LLC, P.O. Box 355, Pittsburgh, Pennsylvania 15230-0355.
eY trul2s, J. A. Gresham, Manager Regulatory Compliance and Plant Licensing Enclosures
CAW-] 0-3007 AFFIDAVIT STATE OF CONNECTICUT:
COUNTY OF HARTFORD:
Before ine, the undersigned authority, personally appeared C. M. Molnar, who, being by me duly sworn according to law, deposes and says that lie is authorized to execuite this Affidavit on behalf of Westinghouse Electric Company LLC ("Westinghouse"), and that the averments of fact set forth in this Affidavit are true and correct to the best of his knowledge, information, and belief:
C. M. Molnar, Senior Engineer Regulatory Compliance and Plant Licensing Sworn to and subscribed before me this day of Nov ber, 2010
.,'2
~
"* ko*.':**n s:*
eme, a Notary ic, in and 'im" County of._Iiartord d CState of 'Connecticut, this day JOA N,_ GRAY Notary Public My Commission Expires January31, 2012
2 CAW-10-3007 (1)
I am Senior Engineer, Regulatory Compliance and Plant Licensing, in Nuclear Services, Westinghouse Electric Company LLC (Westinghouse), and as such, I have been specifically delegated the function of reviewing the proprietary information sought to be withheld from public disclosure iII connection with nuclear power plant licensing and rule making proceedings, and am authorized to apply for its withholding on behalf of Westinghouse.
(2) l am making this Affidavit in conformance with the provisions of 10 CFR Section 2.390 of the Commission's regulations and in con Junction with the Westinghouse Application for Withholding Proprietary Information from Public Disclosure accompanying this Affidavit.
(3) 1 have personal knowledge of the criteria and procedures utilized by Westinghouse in designating information as a trade secret, privileged or as confidential commercial or financial information.
(4)
Pursuant to the provisions of paragraph (b)(4) of Section 2.390 of tle Commission's regulations, the following is furnished for consideration by the Commission in determining whether the information sought to be withheld from public disclosure should be withheld.
(i)
The information sought to be withheld from public disclosure is owned and has been held in confidence by Westinghouse.
(ii)
The information is of a type customarily held in confidence by Westinghouse and not customarily disclosed to the public. Westinghouse has a rational basis for determining the types of information customarily held in confidence by it and, in that connection, utilizes a system to determine when and whether to hold certain types of information in confidence. The application of that system and the substance of that system constitutes Westinghouse policy and provides the rational basis required.
Under that system, information is held in confidence if it falls in one or more of several types, the release of which might result in the loss of an existing or potential competitive advantage, as follows:
(a)
The information reveals tile distinguishing aspects of a process (or component, structure, tool, method, etc.) where prevention of its use by any of
3 CAW-10-3007 Westinghouse's competitors without license from Westinghouse constitutes a competitive economic advantage over other companies.
(b)
It consists of supporting i data, inciuding test data, relative to a process (or conmponent, structure, tool, method, etc.), the application of which data secures a competitive economic advantage, e.g., by optimization or improved marketability.
(c)
Its use by a competitor would reduce his expenditure of resources or improve his competitive position in the design, manufacture, shipment, instal lation assurance of'quality, or licensing a similar product.
(d)
It reveals cost or price information, production capacities, budget levels, or commercial strategies of Westinghouse, its customers or suppliers.
(e)
It reveals aspects of past, present, or future Westinghouse or customer funded development plans and programs of potential commercial value to Westinghouse.
(f)
It contains patentable ideas, for which patent protection may be desirable.
There are sound policy reasons behind the Westinghouse system which inchlde the following:
(a)
The use of such information by Westinghouse gives Westinghouse a competitive advantage over its competitors. It is, therefore, withheld from disclosure to protect the Westinghouse competitive position.
(b)
It is information that is marketable in many ways. The extent to which such information is available to competitors diminishes the Westinghouse ability to sell products and services involving the use of the information.
(c)
Use by our competitor would put Westinghouse at a competitive disadvantage by reducing his expenditure of resources at our expense.
4 CAW-10-3007 (d)
Each component of proprietary information pertinent to a particular competitive advantage is potentially as valuable as the total competitive advantage. If competitors acquire components of proprietary information, any one component may be the key to the entire puzzle, thereby depriving Westinghouse of a competitive advantage.
(e)
Unrestricted disclosure would jeopardize the position of prominence of Westinghouse in the world market, and thereby give a market advantage to the competition of those countries.
(f)
The Westinghouse capacity to invest corporate assets in research and development depends upon the success in obtaining and maintaining a competitive advantage.
(iii)
The information is being transmitted to the Commission in confidence and, under the provisions of 10 CFR Section 2.390; it is to be received in confidence by the Commission.
(iv)
The information sought to be protected is not available in public sources or available information has not been previously employed in the same original manner or method to the best of our knowledge and belief.
(v)
The proprietary information sought to be withheld in this submittal is that which is appropriately marked in Florida Power and Light's St. Lucie Unit I extended power uprate (EPU) submittal transmittal letter to the NRC, Attachment 5, Sections: 2.2.2. 1; 2.2.2.3, 2.2.2.4; 2.2.2.6; and 2.2.3, transmitted with an Application for Withholding Proprietary Information from Public Disclosure, to the Document Control Desk. The proprietary information as submitted by Westinghouse is that associated with the St.
Lucie Unit I EPU license amendment request.
This information is part of that which enables Westinghouse to demnonstrate for St. Lucie Unit I structural margins that will exist after the proposed EPU has been implemented.
Further, this information has substantial commercial value, as follows:
5 CAW-10-3007 (a)
Westinghouse generated this inlormation for St. Lucie Unit I, solely For the support of that un it's planned EPU.
(b)
The information requested to be withheld reveals the stresses and margins for key plant components after thie proposed EPU has been implemented.
Public disclosure of this proprietary information is likely to cause substantial harm to the competitive position of Westinghouse because it would enhance the ability of competitors to provide similar calculations and licensing defense services for commercial power reactors without com mensurate expenses.
The development of the technology described in part by the information is the result of applying the results of many years of experience in aii intensive Westinghouse effort and the expenditure of a considerable sum of money.
In order for competitors of Westinghouse to duplicate this information, similar technical programs would have to be performed and a significant manpower effort, having the requisite talent and experience, would have to be expended.
Further the deponent sayeth not.
PROPRIETARY INFORMATION NOTICE Transmitted herewith are proprietary and/or non-proprietary versions of documents furnished to tile NRC in connection with requests for generic and/or plant-specific review and approval.
In order to conform to tile requirements of 10 CFR 2.390 of the Commission's regulations concerning the protection of proprietary information so submitted to the NRC, the information which is proprietary in the proprietary versions is contained within brackets, and whllere the proprietary information has been deleted in the non-proprietary versions, only the brackets remain (the information that was contained within the brackets in the proprietary versions having been deleted). The justification for claiming the information so designated as proprietary is indicated in both versions by means of lower case letters (a) through (f) located as a superscript immediately following the brackets enclosing each item of information being identified as proprietary or in the margin opposite such information. These lower case letters refer to the types of information Westinghouse customarily holds in confidence identified in Sections (4)(ii)(a) throutgh (4)(ii)(f) of the affidavit accompanying this transmittal pursuant to 10 CFR 2.390(b)(1).
COPYRIGHT NOTICE The documents transmitted herewith each bear a WestinghotIse copyright notice. The NRC is permitted to make the number of copies of the information contained in these documents which are necessary for its internal use in connection with generic and plant-specific reviews and approvals as well as the issuance, denial, amendment, transfer, renewal, modification, suspension, revocation, or violation of a license, permit, order, or regulation subject to the requirements of 10 CFR 2.390 regarding restrictions on public disclosure to the extent such information has been identified as proprietary by Westinghouse, copyright protection notwithstanding. With respect to the non-proprietary versions of these documents, the NRC is permitted to make the number of copies beyond those necessary for its internal use which are necessary in order to have one copy available for public viewing in the appropriate docket files in the public document room in Washington, DC and in local public document rooms as may be required by NRC regulations if the number of copies submitted is insufficient for this purpose. Copies made by the NRC must include the copyright notice in all instances and the proprietary notice if the original was identified as proprietary.
St. Lucie Unit I Letter for Transmittal to the NJRC The following paragraphs should be included in your letter to the NRC:
Enclosed, please find a proprietary and non-proprietary copy of pertinent sections of Attachment 5 to the LAR submitted by Florida Power and Light for the extended power uprate (EPU) of St. Lucie Unit 1. sections: 2.2.2.1; 2.2.2.3, 2.2.2.4; 2.2.2.6; and 2.2.3 contain Westinghouse proprietary information.
Also enclosed is the Westinghouse Application for Withholding Proprietary Information from Public Disclosure CAW-10-3007, accompanying Affidavit, Proprietary Information Notice, and Copyright Notice.
As Item I contains information proprietary to Westinghouse Electric Company LLC, it is supported by an affidavit signed by Westinghouse, the owner of the information. The affidavit sets forth the basis on which the information may be withheld from public disclosure by the Commission and addresses with specificity the considerations listed in paragraph (b)(4) of Section 2.390 of the Commission's regulations.
Accordingly, it is respectfully requested that the information which is proprietary to Westinghouse be withheld from public disclosure in accordance with 10 CFR Section 2.390 of the Commission's regulations.
Correspondence with respect to the copyright or proprietary aspects of the items listed above or the supporting Westinghouse affidavit should reference CAW-]0-3007 and should be addressed to J. A. Gresham, Manager, Regulatory Compliance and Plant Licensing, Westinghouse Electric Company LLC, P.O. Box 355, Pittsburgh, Pennsylvania 15230-0355.
AFFIDAVIT COMMONWEALTH OF VIRGINIA
)
) SS.
CITY OF LYNCHBURG
)
- 1.
My name is Gayle F. Elliott. I am Manager, Product Licensing, for AREVA NP Inc. and as such I am authorized to execute this Affidavit.
- 2.
I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to ensure the proper application of these criteria.
- 3.
I am familiar with the AREVA NP information contained in the report ANP-2903(P), Revision 000, entitled "St. Lucie Nuclear Plant Unit 1 EPU Cycle Realistic Large Break LOCA Summary Report with Zr-4 Fuel Cladding," dated February 2010 and referred to herein as "Document." Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.
- 4.
This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public. Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.
- 5.
This Document has been made available to the U.S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is
requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information."
- 6.
The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:
(a)
The information reveals details of AREVA NP's research and development plans and programs or their results.
(b)
Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.
(c)
The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.
(d)
The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.
(e)
The information is vital to a competitive advantage held by AREVA NIP, wOuld be helpful to competitors to AREVA NP, and would likely cause substantial-harm to the competitive position of AREVA NP.
The information in the Document is considered proprietary for the reasons set forth in paragraphs 6(b) and 6(c) above.
- 7.
In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document have been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.
- 8.
AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.
- 9.
The foregoing statements are true and correct to the best of my knowledge, information, and belief.
SUBSCRIBED before me this day of 7/%*
9t*f 2010.
Kathleen Ann Bennett NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA MY COMMISSION EXPIRES: 8/31/11 Reg. # 110864
Measurement Systems Caldon Ultrasonics Technology Center 1000 McClaren Woods Drive Coraopolis, PA 15108 Tel 724-273-9300 Fax 724-273-9301 www.c-a-m.com SCAMERON November 2, 2010 CAW 10-08 Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555 APPLICATION FOR WITHHOLDING PROPRIETARY INFORMATION FROM PUBLIC DISCLOSURE
Subject:
- 1. Caldon Ultrasonics Engineering Report ER-740 Rev. 0 "Bounding Uncertainty Analysis for Thermal Power Determination at St. Lucie Unit 1 & 2 Using the LEFM$+ System"
- 2. Caldon Ultrasonics Engineering Report No. ER-733 Rev. 3, "LEFM/+ Meter Factor Calculation and Accuracy Assessment for St. Lucie Unit 1" Gentlemen:
This application for withholding is submitted by Cameron International Corporation, a Delaware Corporation (herein called "Cameron") on behalf of its operating unit, Caldon Ultrasonics Technology Center, pursuant to the provisions of paragraph (b)(1) of Section 2.390 of the Commission' s regulations. It contains trade secrets and/or commercial information proprietary to Cameron and customarily held in confidence.
The proprietary information for which withholding is being requested is identified in the subject submittal. In conformance with 10 CFR Section 2.390, Affidavit CAW 10-08 accompanies this application for withholding setting forth the basis on which the identified proprietary information may be withheld from public disclosure.
November 2, 2010 Page 2 Accordingly, it is respectfully requested that the subject information, which is proprietary to Cameron, be withheld from public disclosure in accordance with 10 CFR Section 2.390 of the Commission's regulations.
Correspondence with respect to this application for withholding or the accompanying affidavit should reference CAW 10-08 and should be addressed to the undersigned.
Very truly yours, Ernest M.
uSer Director of Sales Cameron Measurement Systems Division Enclosures (Only upon separation of the enclosed confidential material should this letter and affidavit be released.)
November 2, 2010 CAW 10-08 AFFIDAVIT COMMONWEALTH OF PENNSYLVANIA:
ss COUNTY OF ALLEGHENY:
Before me, the undersigned authority, personally appeared Ernie Hauser, who, being by me duly sworn according to law, deposes and says that he is authorized to execute this Affidavit on behalf of Cameron International Corporation, a Delaware Corporation (herein called "Cameron")
on behalf of its operating unit, Caldon Ultrasonics Technology Center, and that the averments of fact set forth in this Affidavit are true and correct to the best of his knowledge, information, and belief:
st M user Director of Sales Sworn to and subscribed before me this cZL4 day of
,2010 Nqo y Public COMMONWEALTH OF PENNSYLVANIA Notarial Seal Joann B. Thomas, Notary Public Findlay Twp., Alegheny County My Commission Expires July 28,2011 Member, Pennsv!,,ý......
,: ; ýation of Notaries
November 2, 2010 CAW 10-08
- 1. I am the Director of Sales of Caldon Ultrasonics Technology Center, and as such, I have been specifically delegated the function of reviewing the proprietary information sought to be withheld from public disclosure in connection with nuclear power plant licensing and rulemaking proceedings, and am authorized to apply for its withholding on behalf of Cameron.
- 2.
I am making this Affidavit in conformance with the provisions of 10 CFR Section 2.390 of the Commission's regulations and in conjunction with the Cameron application for withholding accompanying this Affidavit.
- 3.
I have personal knowledge of the criteria and procedures utilized by Cameron in designating information as a trade secret, privileged or as confidential commercial or financial information.
The material and information provided herewith is so designated by Cameron, in accordance with those criteria and procedures, for the reasons set forth below.
- 4. Pursuant to the provisions of paragraph (b) (4) of Section 2.390 of the Commission's regulations, the following is furnished for consideration by the Commission in determining whether the information sought to be withheld from public disclosure should be withheld.
(i)
The information sought to be withheld from public disclosure is owned and has been held in confidence by Cameron.
(ii)
The information is of a type customarily held in confidence by Cameron and not customarily disclosed to the public. Cameron has a rational basis for determining the types of information customarily held in confidence by it and, in that connection utilizes a system to determine when and whether to hold certain types of information in confidence. The application of that system and the substance of that system constitutes Cameron policy and provides the rational basis required. Furthermore, the information is submitted voluntarily and need not rely on the evaluation of any rational basis.
November 2, 2010 CAW 10-08 Under that system, information is held in confidence if it falls in one or more of several types, the release of which might result in the loss of an existing or potential advantage, as follows:
(a) The information reveals the distinguishing aspects of a process (or component, structure, tool, method, etc.) where prevention of its use by any of Cameron's competitors without license from Cameron constitutes a competitive economic advantage over other companies.
(b) It consists of supporting data, including test data, relative to a process (or component, structure, tool, method, etc.), the application of which data secures a competitive economic advantage, e.g., by optimization or improved marketability.
(c) Its use by a competitor would reduce his expenditure of resources or improve his competitive position in the design, manufacture, shipment, installation, and assurance of quality, or licensing a similar product.
(d) It reveals cost or price information, production capacities, budget levels, or commercial strategies of Cameron, its customer or suppliers.
(e) It reveals aspects of past, present or future Cameron or customer funded development plans and programs of potential customer value to Cameron.
(f) It contains patentable ideas, for which patent protection may be desirable.
There are sound policy reasons behind the Cameron system, which include the following:
(a) The use of such information by Cameron gives Cameron a competitive advantage over its competitors. It is, therefore, withheld from disclosure to protect the Cameron competitive position.
November 2, 2010 CAW 10-08 (b) It is information that is marketable in many ways. The extent to which such information is available to competitors diminishes the Cameron ability to sell products or services involving the use of the information.
(c) Use by our competitor would put Cameron at a competitive disadvantage by reducing his expenditure of resources at our expense.
(d) Each component of proprietary information pertinent to a particular competitive advantage is potentially as valuable as the total competitive advantage. If competitors acquire components of proprietary information, any one component may be the key to the entire puzzle, thereby depriving Cameron of a competitive advantage.
(e) Unrestricted disclosure would jeopardize the position of prominence of Cameron in the world market, and thereby give a market advantage to the competition of those countries.
(f) The Cameron capacity to invest corporate assets in research and development depends upon the success in obtaining and maintaining a competitive advantage.
(iii) The information is being transmitted to the Commission in confidence, and, under the provisions of 10 CFR §§ 2. 390, it is to be received in confidence by the Commission.
(iv)
The information sought to be protected is not available in public sources or available information has not been previously employed in the same manner or method to the best of our knowledge and belief
November 2, 2010 CAW 10-08 (v)
The proprietary information sought to be withheld are the submittals titled:
Caldon Ultrasonics Engineering Report ER-740 Rev. 0 "Bounding Uncertainty Analysis for Thermal Power Determination at St. Lucie Unit 1 & 2 Using the LEFMV'+ System"
" Caldon Ultrasonics Engineering Report No. ER-733 Rev. 3, "LEFM/+ Meter Factor Calculation and Accuracy Assessment for St. Lucie 1."
It is designated therein in accordance with 10 CFR §§ 2.390(b)(1)(i)(A,B), with the reason(s) for confidential treatment noted in the submittal and further described in this affidavit. This information is voluntarily submitted for use by the NRC Staff in their review of the accuracy assessment of the proposed methodology for LEFM CheckPlus System used by St. Lucie Unit 1 for an MUR UPRATE.
Public disclosure of this proprietary information is likely to cause substantial harm to the competitive position of Cameron because it would enhance the ability of competitors to provide similar flow and temperature measurement systems and licensing defense services for commercial power reactors without commensurate expenses. Also, public disclosure of the information would enable others to use the information to meet NRC requirements for licensing documentation without the right to use the information.
The development of the technology described in part by the information is the result of applying the results of many years of experience in an intensive Cameron effort and the expenditure of a considerable sum of money.
In order for competitors of Cameron to duplicate this information, similar products would have to be developed, similar technical programs would have to be performed, and a significant manpower effort, having the requisite talent and experience, would have to be expended for developing analytical methods and receiving NRC approval for those methods.
Further the deponent sayeth not.
'Holtec Center, 555 Lincoln Drive West, Marlton, NJ 08053 H O LT EC Telephone (856) 797-0900 INTERNATIONAL Fax (856) 797-0909 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk AFFIDAVIT PURSUANT TO 10 CFR 2.390 I, Jay Leff, state as follows:
(1)
I am the Holtec International Project Manager for the Extended Power Uprate Analysis for St. Lucie Unit 1 Project and have reviewed the information described in paragraph (2) which is sought to be withheld, and am authorized to apply for its withholding.
(2)
The information sought to be withheld is Revision 2 of Holtec Report HI-2094486 and Revision 1 of Holtec Report HI-2104714, which contains Holtec Proprietary information and is appropriately marked as such.
(3)
In making this application for withholding of proprietary information of which it is the owner, Holtec International relies upon the exemption from disclosure set forth in the Freedom of Information Act ("FOIA"), 5 USC Sec. 552(b)(4) and the Trade Secrets Act, 18 USC Sec. 1905, and NRC regulations 10CFR Part 9.17(a)(4), 2.390(a)(4), and 2.390(b)(1) for "trade secrets and commercial or financial information obtained from a person and privileged or confidential" (Exemption 4). The material for which exemption from disclosure is here sought is all "confidential commercial information", and some portions also qualify under the narrower definition of "trade secret", within the meanings assigned to those terms for purposes of FOIA Exemption 4 in, respectively, Critical Mass Energy Project v. Nuclear Regulatory Commission, 975 F2d 871 (DC Cir.
1992), and Public Citizen Health Research Group v. FDA, 704 F2d 1280 (DC Cir. 1983).
1 of 5
m Em mE Holtec Center, 555 Lincoln Drive West, Marlton, NJ 08053 H O LT EC Telephone (856) 797-0900 INTERNATIONAL Fax (856) 797-0909 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk AFFIDAVIT PURSUANT TO 10 CFR 2.390 (4)
Some examples of categories of information which fit into the definition of proprietary information are:
- a.
Information that discloses a process, method, or apparatus, including supporting data and analyses, where prevention of its use by Holtec's competitors without license from Holtec International constitutes a competitive economic advantage over other companies;
- b.
Information which, if used by a competitor, would reduce his expenditure of resources or improve his competitive position in the design, manufacture, shipment, installation, assurance of quality, or licensing of a similar product.
- c.
Information which reveals cost or price information, production, capacities, budget levels, or commercial strategies of Holtec International, its customers, or its suppliers;
- d.
Information which reveals aspects of past, present, or future Holtec International customer-funded development plans and programs of potential commercial value to Holtec International;
- e.
Information which discloses patentable subject matter for which it may be desirable to obtain patent protection.
The information sought to be withheld is considered to be proprietary for the reasons set forth in paragraphs 4.a and 4.b, above.
(5)
The information sought to be withheld is being submitted to the NRC in confidence. The information (including that compiled from many sources) is of 2 of 5
EHoitec Center, 555 Lincoln Drive West, Marlton, NJ 08053 H O LT EC Telephone (856) 797-0900 INTERNATIONAL Fax (856) 797-0909 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk AFFIDAVIT PURSUANT TO 10 CFR 2.390 a sort customarily held in confidence by Holtec International, and is in fact so held. The information sought to be withheld has, to the best of my knowledge and belief, consistently been held in confidence by Holtec International. No public disclosure has been made, and it is not available in public sources. All disclosures to third parties, including any required transmittals to the NRC, have been made, or must be made, pursuant to regulatory provisions or proprietary agreements which provide for maintenance of the information in confidence. Its initial designation as proprietary information, and the subsequent steps taken to prevent its unauthorized disclosure, are as set forth in paragraphs (6) and (7) following.
(6)
Initial approval of proprietary treatment of a document is made by the manager of the originating component, the person most likely to be acquainted with the value and sensitivity of the information in relation to industry knowledge.
Access to such documents within Holtec International is limited on a "need to know" basis.
(7)
The procedure for approval of external release of such a. document typically requires review by the staff manager, project manager, principal scientist or other equivalent authority, by the manager of the cognizant marketing function (or his designee), and by the Legal Operation, for technical content, competitive effect, and determination of the accuracy of the proprietary designation.
Disclosures outside Holtec International are limited to regulatory bodies, customers, and potential customers, and their agents, suppliers, and licensees, and others with a legitimate need for the information, and then only in accordance with appropriate regulatory provisions or proprietary agreements.
(8)
The information classified as proprietary was developed and compiled by Holtec International at a significant cost to Holtec International. This information is classified as proprietary because it contains detailed descriptions of analytical 3 of 5
M M M mI Holtec Center, 555 Lincoln Drive West, Marlton, NJ 08053 H O LT EC Telephone (856) 797-0900 INTERNATIONAL Fax (856) 797-0909 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk AFFIDAVIT PURSUANT TO 10 CFR 2.390 approaches and methodologies not available elsewhere. This information would provide other parties, including competitors, with information from Holtec International's technical database and the results of evaluations performed by Holtec International. A substantial effort has been expended by Holtec International to develop this information. Release of this information would improve a competitor's position because it would enable Holtec's competitor to copy our technology and offer it for sale in competition with our company, causing us financial injury.
(9)
Public disclosure of the information sought to be withheld is likely to cause substantial harm to Holtec International's competitive position and foreclose or reduce the availability of profit-making opportunities. The information is part of Holtec International's comprehensive spent fuel storage technology base, and its commercial value extends beyond the original development cost. The value of the technology base goes beyond the extensive physical database and analytical methodology, and includes development of the expertise to determine and apply the appropriate evaluation process.
The research, development, engineering, and analytical costs comprise a substantial investment of time and money by Holtec International.
The precise value of the expertise to devise an evaluation process and apply the correct analytical methodology is difficult to quantify, but it clearly is substantial.
Holtec International's competitive advantage will be lost if its competitors are able to use the results of the Holtec International experience to normalize or verify their own process or if they are able to claim an equivalent understanding by demonstrating that they can arrive at the same or similar conclusions.
4 of 5
Holtec Center, 555 Lincoln Drive West, Marlton, NJ 08053 H O LT EC Telephone (856) 797-0900 INTERNATIONAL Fax (856) 797-0909 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk AFFIDAVIT PURSUANT TO 10 CFR 2.390 The value of this information to Holtec International would be lost if the information were disclosed to the public. Making such information available to competitors without their having been required to undertake a similar expenditure of resources would unfairly provide competitors with a windfall, and deprive Holtec International of the opportunity to exercise its competitive advantage to seek an adequate return on its large investment in developing these very valuable analytical tools.
Executed at Marlton, New Jersey, this 5th day of November, 2010
)~-
Jay Leff Project Manager Holtec International MAFU*AC MASS' t40XS PBUIC bNE4W jEsSEY WOTAVEYpUBUs~pd
- 2.
015 MYCOU" 5 of 5
B*w babcock & wilcox canada ltd.
R 581 coronation boulevard I cambridge, on n1r 5v3 canada P phone 519.621.2130 1 fax 519.621.2310 D www.babcock.com November 10, 2010 Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 U.S.A.
APPLICATION FOR WITHHOLDING PROPRIETARY INFORMATION FROM PUBLIC DISCLOSURE
Subject:
Section 2.2.2.5 of Florida Power and Light's St. Lucie Unit 1 EPU submittal transmittal letter to the NRC, Attachment 5 (Proprietary)
Dear Sir/Madam:
The proprietary information for which withholding is being requested in the above-referenced document section is identified in the attached affidavit signed by the owner of the proprietary information, Babcock &
Wilcox Canada Ltd. The affidavit, which accompanies this letter, sets forth the basis on which the information may be withheld from public disclosure by the Commission and address with specificity the considerations listed in paragraph (b)(4) of 10 CFR Section 2.390 of the Commission's regulations.
Accordingly, this letter authorizes the utilization of the accompanying affidavit by Florida Power and Light.
Correspondence with respect to the proprietary aspects of the application for withholding or the Babcock &
Wilcox Affidavit should reference this letter, and should be addressed to the undersigned.
Yours truly, BABCOCK & WILCOX CANADA LTD.
- j
- yMillman, Manager, Nuclear Engineering Attach./
Cc:
V.J. Manica J. MacQuarrie J. Albert
PROVINCE OF ONTARIO REGIONAL MUNICIPALITY OF WATERLOO AFFIDAVIT OF JEFFREY MILLMAN I, Jeffrey Millman, of the Village of Ayr, in the Township of North Dumfries, Regional Municipality of Waterloo, in the Province of Ontario, being sworn, make oath and say as follows:
- 1.
I am the Manager, Nuclear Engineering of Babcock & Wilcox Canada Ltd. ("B&W"),
and as such, I have been specifically delegated the function of reviewing the proprietary information sought to be withheld from public disclosure in connection with nuclear power plant licensing and rulemaking proceedings, and am authorized to apply for its withholding on behalf of B&W.
- 2.
I am making this Affidavit in conformance with the provisions of 10CFR Section 2.390 of the Commission's regulations and in conjunction with the Babcock & Wilcox Canada Ltd. Application for Withholding accompanying this Affidavit.
- 3.
I have personal knowledge of the criteria and procedures utilized by B&W in designating information as a trade secret, proprietary or as confidential commercial or financial information.
- 4.
Pursuant to the provisions of paragraph (b)(4) of Section 2.390 of the Commission's regulations, the following is furnished for consideration by the Commission in determining whether the information sought to be withheld from public disclosure should be withheld.
(i)
The information sought to be withheld from public disclosure is owned and has been held in confidence by B&W.
(ii)
The information is of a type customarily held in confidence by B&W and not customarily disclosed to the public. B&W has a rational basis for determining the types of information customarily held in confidence by it and, in that connection, utilizes a system to determine when and whether to hold certain types of information in confidence.
The application of that system and the substance of that system constitutes B&W policy and provides the rational basis required.
Under that system, information is held in confidence if it falls in one or more of several types, the release of which might result in the loss of an existing or potential competitive advantage, as follow:
(a)
The information reveals the distinguishing aspects of a process, component, structure, tool, method, etc., where prevention of its use by
2 any of B&W's competitors without license from B&W constitutes a competitive economic advantage over other companies.
(b)
It consists of supporting data, including test data, relative to a process (or component, structure, tool, method, etc.), the application of which data secures a competitive economic advantage, e.g., by optimization or improved marketability.
(c)
Its use by a competitor would reduce its expenditure of resources or improve its competitive position in the design, manufacture, shipment, installation, quality assurance, or licensing of a similar product.
(d)
It contains patentable ideas, for which patent protection may be desirable.
There are sound policy reasons behind the B&W system which include the following:
The use of such information by B&W gives B&W a competitive advantage over its competitors.
It is, therefore, withheld from disclosure to protect B&W's competitive advantage.
It is information which is marketable in many ways. The extent to which such information is available to competitors diminishes the B&W ability to sell products and services involving the use of such information.
" Use by a competitor of B&W would put B&W at a competitive disadvantage by reducing the competitor's expenditure of resources at B&W's expense.
- B&W's capacity to invest corporate assets in research and development depends upon the success in obtaining and maintaining a competitive advantage.
(iii)
The information is being transmitted to the Commission in confidence and, under the provisions of 10CFR Section 2.390, it is to be received in confidence by the Commission.
(iv)
The information sought to be protected is not available in public sources or available information has not been previously employed in the same original manner or method to the best of our knowledge and belief.
(v)
The proprietary information sought to be withheld in this submittal is that which is identified in Florida Power and Light's St. Lucie Unit 1 EPU submittal transmittal letter to the NRC, Attachment 5, Section 2.2.2.5 and Application for Withholding Proprietary Information from Public Disclosure, to the Document Control Desk.
3 The information which is proprietary in the proprietary version is contained within brackets, and where the proprietary information has been deleted in the non-proprietary versions, only the brackets remain (the information that was contained within the brackets in the proprietary versions having been deleted).
The justification for claiming the information so designated as proprietary is indicated in both versions by means of lower case letters (a) through (d) located as a superscript immediately following the brackets enclosing each item of information being identified as proprietary. These lower case letters refer to the types of information B&W customarily holds in confidence identified in Sections (4)(ii)(a) through (4 )(ii)(d) of this affidavit pursuant to 10 CFR 2.390(b)(1).
SWORN BEFORE ME in the
)
City of Cambridge in the
)
Province of Ontario, this
)
10 th day of November, 2010.