Lent. Susan From:

Yates, Bert G [GYates@ameren.com]

Sent:

Thursday, December 16,201011:00 AM To:

Polickoski, James Cc:

Maglio, Scott A; Elwood, Thomas B; Eickelman, Richard E Attachments:

LDCN 09-0039 12-15-10 complete TS markups. pdf Importance:

High Scott Maglio asked that I send the attached file to you. It has been through several review iterations here and reflects our latest perspectives.

Condition M has been revised to reflect a baseline Condition that can be re-entered each time a channel becomes inoperable. It has a 24-hour CT and a bypass testing Note.

Multiple inoperable channel Conditions would also be entered simultaneously, whether under Condition J or Condition T Condition J now covers the lowest common denominator for a loss of actuation function (a loss of function is "blind" as to whether it's due to 2 inoperable channels on one pump or on different pumps) and is limited to a 1-hour CT It has no bypass testing Note.

Condition T covers more than 2 inoperable channels and requires that one actuation train (two channels in the same separation group) be restored in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

Condition U is a universal default to MODE 3 when the Required Action and Associated Completion Time of Conditions J, M, or T are not met.

Table 3.3.2-1 has been revised to specify 4 Required Channels.

A new footnote (u) has also been added to MODE 1 with a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> limitation for placing an I\\t1FP into service. This reflects not only the feedback from the BOP Branch and OTSB during our 11/18/10 meeting, but also mirrors Watts Bar LA75 dated 3/4/09 (ADAMS ML090480566) and Sequoyah LA 319/312 dated 8/29/08 (ADAMS ML082401330, ML082401385, and ML082401446), except that those amendments both include a 4-hour loss of function delay time prior to entering a TS Condition for starting the 2nd MFP whereas we're limiting that footnote to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> per the previously expressed Staff positions.

This combination of Conditions (absent any undue Note clutter to the extent possible) and new footnote (u) provides what we feel is the best approach to satisfy the risk basis for the amendment as well as our desire to human factor this complex situation for the operators (if that's possible for a function with 3 Conditions). We would like to receive Staff feedback at your earliest convenience since Bases markUps still need to be generated, the 10/20/10 RAI responses need to be revised, and our review committees need to be engaged on the final supplement.

Bert Yates Principal Engineer Regulatory Affairs - Licensing gyates@ameren.com Ameren Missouri Callaway Plant P.O. Box 620, Mail Code CA-460 Junction Hwy CC and Hwy 0 Fulton, MO 65251 Ameren.com 1

The information contained in this message may be privileged and/or confidential and protected from disclosure.

If the reader of this message is not the intended recipient, or an employee or agent responsible for delivering this message to the intended recipient, you are hereby notified that any dissemination, distribution or copying of this communication is strictly prohibited. Note that any views or opinions presented in this message are solely those of the author and do not necessarily represent those of Ameren. All e-mails are subject to monitoring and archival. Finally, the recipient should check this message and any attachments for the presence of viruses.