Draft Request for Additional Information Re. Downcomer Boiling for the Proposed LBLOCA Amendment
ML103050566
Person / Time
Site: Cook 
Issue date: 11/01/2010
From: Tam P
Plant Licensing Branch III
To: Etheridge H, Huang T, Anthony Mendiola, Robert Pascarelli, Scarpello M, Ulses A, Ward L, Waters J
Indiana Michigan Power Co, Plant Licensing Branch III, NRC/NRR/DSS/SNPB, NRC/NRR/DSS/SRXB
Tam P
References
TAC ME1017
Download: ML103050566 (2)


Text

Accession No. ML103050566 From:

Tam, Peter Sent:

Monday, November 01, 2010 1:32 PM To:

Helen Etheridge; Joe Waters (jrwaters@aep.com); mkscarpello@aep.com Cc:

Mendiola, Anthony; Huang, Tai; Pascarelli, Robert; Ulses, Anthony; Ward, Leonard

Subject:

D.C. Cook Unit 2 - Draft RAI re.downcomer boiling for the proposed LBLOCA amendment (TAC ME1017)

Helen::

The NRC staff completed its sensitivity study on downcomer boiling and the effect of lateral k-factor on this phenomenon. The case with zero lateral k-factor in the downcomer cross flow paths joining the azimuthal cells resulted in a 400 degrees F reduction in peak clad temperature. This was due to the maximization of mixing between the downcomer azimuthal cells which severely limited downcomer boiling. The cold water entering the downcomer during the long term readily mixed into the adjacent downcomer volumes and reduced boiling and the resulting core uncover and clad temperature. ECC bypass and liquid sweep-out that dominate the very early portion of the event (the first 100-200 seconds) does not prevail during the longer term when the downcomer fills with liquid and vapor velocities are no longer high enough to entrain and sweep out the injected liquid.

Based on these results, he NRC staff needs to request that an additional analysis of downcomer boiling be performed for D. C. Cook Unit 2 with the lateral k-facors based on Idelchik included in the downcomer resistance model in the WCOBRA/TRAC model. The additional comparative study should show the impact of the lateral k-factor on PCT during downcomer boiling following a large break LOCA.

If you so desire, the NRC staff will be ready to discuss with you in a conference call this information request.

Peter S. Tam, Senior Project Manager (for D.C. Cook and Monticello)

Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Tel. 301-415-1451 E-mail Properties Mail Envelope Properties (0A64B42AAA8FD4418CE1EB5240A6FED1219553AC81)

Subject:

D.C. Cook Unit 2 - Draft RAI re.downcomer boiling for the proposed LBLOCA amendment (TAC ME1017)

Sent Date: 11/1/2010 1:32:12 PM Received Date: 11/1/2010 1:32:00 PM From: Tam, Peter Created By: Peter.Tam@nrc.gov Recipients:

hletheridge@aep.com (Helen Etheridge)

Tracking Status: None jrwaters@aep.com (Joe Waters (jrwaters@aep.com))

Tracking Status: None mkscarpello@aep.com (mkscarpello@aep.com)

Tracking Status: None Anthony.Mendiola@nrc.gov (Mendiola, Anthony)

Tracking Status: None Tai.Huang@nrc.gov (Huang, Tai)

Tracking Status: None Robert.Pascarelli@nrc.gov (Pascarelli, Robert)

Tracking Status: None Anthony.Ulses@nrc.gov (Ulses, Anthony)

Tracking Status: None Leonard.Ward@nrc.gov (Ward, Leonard)

Tracking Status: None Post Office:

HQCLSTR02.nrc.gov Files Size Date & Time MESSAGE 12461 11/1/2010 Options Expiration Date:

Priority: olImportanceNormal ReplyRequested: False Return Notification: False Sensitivity: olNormal Recipients received: