E-mail Response to Eeeb AST RAI on June 10, 2010
ML101610394
Person / Time
Site: LaSalle  
Issue date: 06/10/2010
From: Nicely K
Exelon Corp
To: Goodwin C
Plant Licensing Branch III
References
Download: ML101610394 (2)


Text

From:

ken.nicely@exeloncorp.com Sent:

Thursday, June 10, 2010 10:29 AM To:

Goodwin, Cameron

Subject:

RE: LaSalle AST Attachments:

AST Question.pdf

Cameron, The attached information addresses the question related to the usable diesel fuel volume.
Thanks, Ken Nicely From: Goodwin, Cameron [1]

Sent: Wednesday, June 02, 2010 2:13 PM To: Nicely, Ken:(GenCo-Nuc)

Subject:

LaSalle AST Per UFSAR Section 9.5.4.1.1 (Rev. 18), the usable diesel fuel volume required to support each Division 1 and 2 diesel generator continuous operation at rated load for 7 days is 32,200 gallons. Division 1 diesels will now be loaded above the continuous rating due to the load increase needed for the AST amendment. Provide a detailed discussion addressing how the EDG 7 day fuel supply requirement is satisfied as a result of this AST amendment.

Thank you, Cameron Mrs. Cameron Goodwin Division of Operating Reactor Licensing LaSalle Project Manager Phone: (301)415-3719 Email: Cameron.Goodwin@nrc.gov

                                                                                                    • This e-mail and any of its attachments may contain Exelon Corporation proprietary information, which is privileged, confidential, or subject to copyright belonging to the Exelon Corporation family of Companies.

This e-mail is intended solely for the use of the individual or entity to which it is addressed. If you are not the intended recipient of this e-mail, you are hereby notified that any dissemination, distribution, copying, or action taken in relation to the contents of and attachments to this e-mail is strictly prohibited and may be unlawful. If you have received this e-mail in error, please notify the sender immediately and permanently delete the original and any copy of this e-mail and any printout. Thank You. **************************************************

E-mail Properties

Mail Envelope Properties (BB85B9582429394AAD8F2969B2FD7C976F6FAD)

Subject:

RE: LaSalle AST Sent Date: 6/10/2010 10:29:09 AM Received Date: 6/10/2010 10:29:09 AM From: ken.nicely@exeloncorp.com Created By: ken.nicely@exeloncorp.com Recipients:

Cameron.Goodwin@nrc.gov (Goodwin, Cameron)

Tracking Status: None Post Office:

cccmsxch18.energy.power.corp Files Size Date & Time MESSAGE 81168 6/10/2010 AST Question.pdf 61288 Options Expiration Date:

Priority: olImportanceNormal ReplyRequested: True Return Notification: False Sensitivity: olNormal Recipients received: