Developmental Revision B - Technical Specifications 3.8 - Electrical Power Systems
ML100550462
Person / Time
Site: Watts Bar 
Issue date: 02/02/2010
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
References
Download: ML100550462 (39)


Text

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-1 (developmental)

B 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 AC Sources - Operating LCO 3.8.1 The following AC electrical sources shall be OPERABLE:

a.

Two qualified circuits between the offsite transmission network and the onsite Class 1E AC Electrical Power Distribution System; and

b.

Four diesel generators (DGs) capable of supplying the onsite Class 1E AC Electrical Power Distribution System.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS


NOTE-------------------------------------------------------------

LCO 3.0.4.b is not applicable to DGs.

CONDITION REQUIRED ACTION COMPLETION TIME A. One offsite circuit inoperable.

A.1 Perform SR 3.8.1.1 for OPERABLE offsite circuit.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter AND A.2 Declare required feature(s) with no offsite power available inoperable when its redundant required feature(s) is inoperable.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from discovery of no offsite power to one train concurrent with inoperability of redundant required feature(s)

(continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-2 (developmental)

B ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

AND A.3 Restore offsite circuit to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND 6 days from discovery of failure to meet LCO B. One or more DG(s) in Train A inoperable.

OR One or more DG(s) in Train B inoperable.

B.1 Perform SR 3.8.1.1 for the offsite circuits.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter AND B.2 Declare required feature(s) supported by the inoperable DG(s) inoperable when its required redundant feature(s) is inoperable 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> from discovery of Condition B concurrent with inoperability of redundant required feature(s)

AND B.3.1 Determine OPERABLE DG(s) is not inoperable due to common cause failure.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR B.3.2 Perform SR 3.8.1.2 for OPERABLE DG(s).

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> AND (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-3 (developmental)

A ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued)

B.4 Restore required DG(s) to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND 6 days from discovery of failure to meet LCO C. Two offsite circuits inoperable.

C.1 Declare required feature(s) inoperable when its redundant required feature(s) is inoperable.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> from discovery of Condition C concurrent with inoperability of redundant required features AND C.2 Restore one offsite circuit to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> D. One offsite circuit inoperable.

AND One or more required DG(s) in Train A inoperable.

OR One or more required DG(s) in Train B inoperable.


NOTE-------------------

Enter applicable Conditions and Required Actions of LCO 3.8.9, "Distribution Systems - Operating,"

when Condition D is entered with no AC power source to any train.

D.1 Restore offsite circuit to OPERABLE status.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> OR D.2 Restore required DG(s) to OPERABLE status.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-4 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. One or more required DG(s) in Train A inoperable.

AND One or more required DG(s) in Train B inoperable.

E.1 Restore required DGs in Train A to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> OR E.2 Restore required DGs in Train B to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> F. Required Action and Associated Completion Time of Condition A. B, C, D, or E not met.

F.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND F.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> G. Two offsite circuits inoperable.

AND One or more required DG(s) in Train A inoperable.

OR One or more required DG(s) in Train B inoperable.

G.1 Enter LCO 3.0.3.

Immediately H. One offsite circuit inoperable.

AND One or more required DG(s) in Train A inoperable.

AND One or more required DG(s) in Train B inoperable.

H.1 Enter LCO 3.0.3.

Immediately

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-5 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.1.1 Verify correct breaker alignment and indicated power availability for each offsite circuit.

7 days SR 3.8.1.2


NOTES----------------------------

1. Performance of SR 3.8.1.7 satisfies this SR.
2. A modified DG start involving idling and gradual acceleration to synchronous speed may be used for this SR as recommended by the manufacturer. When modified start procedures are not used, the time, voltage, and frequency tolerances of SR 3.8.1.7 must be met.

Verify each DG starts from standby conditions and achieves steady state voltage 6800 V and 7260 V, and frequency 58.8 Hz and 61.2 Hz.

As specified in Table 3.8.1-1 SR 3.8.1.3


NOTES----------------------------

1. DG loadings may include gradual loading as recommended by the manufacturer.
2. Momentary transients outside the load range do not invalidate this test.
3. This Surveillance shall be conducted on only one DG at a time.
4. This SR shall be preceded by and immediately follow without shutdown a successful performance of SR 3.8.1.2 or SR 3.8.1.7.

Verify each DG is synchronized and loaded and operates for 60 minutes at a load 3960 kW and 4400 kW.

As specified in Table 3.8.1-1 SR 3.8.1.4 Verify each skid mounted day tank contains 218.5 gal of fuel oil.

31 days (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-6 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.5 Check for and remove accumulated water from each skid mounted day tank.

31 days SR 3.8.1.6 Verify the fuel oil transfer system operates to automatically transfer fuel oil from 7 day storage tank to the skid mounted day tank.

31 days SR 3.8.1.7 Verify each DG starts from standby condition and achieves in 10 seconds, voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.8 Hz and 61.2 Hz.

184 days SR 3.8.1.8


NOTE------------------------------

This Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.

Verify automatic and manual transfer of each 6.9 kV shutdown board power supply from the normal offsite circuit to each alternate offsite circuit.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-7 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.9


NOTES----------------------------

1. This Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
2. If performed with the DG synchronized with offsite power, it shall be performed at a power factor 0.8 and 0.9.

Verify each DG rejects a load greater than or equal to its associated single largest post-accident load, and:

a.

Following load rejection, the frequency is 66.75 Hz;

b.

Within 3 seconds following load rejection, the voltage is 6555 V and 7260 V; and

c.

Within 4 seconds following load rejection, the frequency is 58.8 Hz and 61.2 Hz.

18 months SR 3.8.1.10


NOTE------------------------------

This Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG operating at a power factor 0.8 and 0.9 does not trip and voltage is maintained 8880 V during and following a load rejection of 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-8 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.11


NOTE------------------------------

This Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated loss of offsite power signal:

a.

De-energization of emergency buses;

b.

Load shedding from emergency buses;

c.

DG auto-starts from standby condition and:

1. energizes permanently connected loads in 10 seconds,
2. energizes auto-connected shutdown loads through automatic load sequencer,
3. maintains steady state voltage 6800 V and 7260 V,
4. maintains steady state frequency 58.8 Hz and 61.2 Hz, and
5. supplies permanently connected and auto-connected shutdown loads for 5 minutes.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-9 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.12


NOTE------------------------------

This Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated Engineered Safety Feature (ESF) actuation signal each Unit 2 DG auto-starts from standby condition and:

a.

In 10 seconds after auto-start and during tests, achieves voltage 6800 V and frequency 58.8 Hz;

b.

After DG fast start from standby conditions the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.8 Hz and 61.2 Hz.

c.

Operates for 5 minutes;

d.

Permanently connected loads remain energized from the offsite power system; and

e.

Emergency loads are energized from the offsite power system.

18 months SR 3.8.1.13


NOTE------------------------------

This Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG's automatic trips are bypassed on automatic or emergency start signal except:

a.

Engine overspeed; and

b.

Generator differential current 18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-10 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.14


NOTES----------------------------

1. Momentary transients outside the load and power factor ranges do not invalidate this test.
2. For performance of this test in MODE 1, 2, 3 or 4, three DGs must be maintained operable and in a standby condition.
3. Credit may be taken for unplanned events that satisfy this SR.

Verify each DG operating at a power factor 0.8 and 0.9 operates for 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

a.

For 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 4620 kW and 4840 kW and 3465 kVAR and 3630 kVAR; and

b.

For the remaining hours of the test loaded 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.

18 months SR 3.8.1.15


NOTES----------------------------

This Surveillance shall be performed within 5 minutes of shutting down the DG after the DG has operated 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 3960 kW and 4400 kW.

Momentary transients outside of load range do not invalidate this test.

Verify each DG starts and achieves, in 10 seconds, voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.8 Hz and 61.2 Hz.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-11 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.16


NOTE------------------------------

This Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG:

a.

Synchronizes with offsite power source while loaded with emergency loads upon a simulated restoration of offsite power;

b.

Transfers loads to offsite power source; and

c.

Returns to ready-to-load operation.

18 months SR 3.8.1.17


NOTE------------------------------

This Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify, with each Unit 2 DG operating in test mode and connected to its bus, an actual or simulated ESF actuation signal overrides the test mode by:

a.

Returning DG to ready-to-load operation; and

b.

Automatically energizing the emergency load from offsite power.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-12 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.18


NOTE------------------------------

This Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify the time delay setting for each sequenced load block is within limits for each accident condition and non-accident condition load sequence.

18 months SR 3.8.1.19


NOTE------------------------------

This Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated loss of offsite power signal in conjunction with an actual or simulated ESF actuation signal:

a.

De-energization of emergency buses;

b.

Load shedding from emergency buses; and

c.

DGs of the same power train auto-start from standby condition and:

1. energizes permanently connected loads in 10 seconds,
2. energizes auto-connected emergency loads through load sequencer,
3. achieves steady state voltage:

6800 V and 7260 V,

4. achieves steady state frequency 58.8 Hz and 61.2 Hz, and
5. supplies permanently connected and auto-connected emergency loads for 5 minutes.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-13 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.20 Verify during idle operation that any automatic or emergency start signal disables the idle start circuitry and commands the engine to full speed.

18 months SR 3.8.1.21 Verify when started simultaneously from standby condition, each DG achieves, in 10 seconds, voltage 6800 V and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.8 Hz and 61.2 Hz.

10 years

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-14 (developmental)

A Table 3.8.1-1 (page 1 of 1)

Diesel Generator Test Schedule NUMBER OF FAILURES IN LAST 25 VALID TESTS(a)

FREQUENCY 3

31 days 4

7 days(b)

(but no less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />)

(a) Criteria for determining number of failures and valid tests shall be in accordance with Regulatory Position C.2.1 of Regulatory Guide 1.9, Revision 3, where the number of tests and failures is determined on a per DG basis.

(b) This test frequency shall be maintained until seven consecutive failure free starts from standby conditions and load and run tests have been performed. If, subsequent to the 7 failure free tests, 1 or more additional failures occur, such that there are again 4 or more failures in the last 25 tests, the testing interval shall again be reduced as noted above and maintained until 7 consecutive failure free tests have been performed.

AC Sources - Shutdown 3.8.2 Watts Bar - Unit 2 3.8-15 (developmental)

B 3.8 ELECTRICAL POWER SYSTEMS 3.8.2 AC Sources - Shutdown LCO 3.8.2 The following AC electrical power sources shall be OPERABLE:

a.

One qualified circuit between the offsite transmission network and the onsite Class 1E AC electrical power distribution subsystem(s) required by LCO 3.8.10, "Distribution Systems-Shutdown;" and

b.

Two diesel generators (DGs) either Train A or Train B capable of supplying one train of the onsite Class 1E AC electrical power distribution subsystem(s) required by LCO 3.8.10.

APPLICABILITY:

MODES 5 and 6, During movement of irradiated fuel assemblies.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required offsite circuit inoperable.


NOTE-------------------

Enter applicable Conditions and Required Actions of LCO 3.8.10, with one required train de-energized as a result of Condition A.

A.1 Declare affected required feature(s) with no offsite power available inoperable.

Immediately OR A.2.1 Suspend CORE ALTERATIONS Immediately AND (continued)

AC Sources - Shutdown 3.8.2 Watts Bar - Unit 2 3.8-16 (developmental)

A ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.2.2 Suspend movement of irradiated fuel assemblies.

Immediately AND A.2.3 Initiate action to suspend operations involving positive reactivity additions.

Immediately AND A.2.4 Initiate action to restore required offsite power circuit to OPERABLE status.

Immediately B. One required DG inoperable.

B.1 Suspend CORE ALTERATIONS.

Immediately AND B.2 Suspend movement of irradiated fuel assemblies.

Immediately AND B.3 Initiate action to suspend operations involving positive reactivity additions.

Immediately AND B.4 Initiate action to restore required DG to OPERABLE status.

Immediately

AC Sources - Shutdown 3.8.2 Watts Bar - Unit 2 3.8-17 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.2.1


NOTE------------------------------

The following SRs are not required to be performed:

SR 3.8.1.3, SR 3.8.1.6, SR 3.8.1.9 through SR 3.8.1.16, SR 3.8.1.18 and SR 3.8.1.19.

For AC sources required to be OPERABLE, the SRs of Specification 3.8.1, "AC Sources-Operating,"

except SR 3.8.1.8, SR 3.8.1.17, and SR 3.8.1.21, are applicable.

In accordance with applicable SRs

Diesel Fuel Oil, Lube Oil, and Starting Air 3.8.3 Watts Bar - Unit 2 3.8-18 (developmental)

A 3.8 ELECTRICAL POWER SYSTEMS 3.8.3 Diesel Fuel Oil, Lube Oil, and Starting Air LCO 3.8.3 The stored diesel fuel oil, lube oil, and starting air subsystem shall be within limits for each required diesel generator (DG).

APPLICABILITY:

When associated DG is required to be OPERABLE.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each DG.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more DGs with fuel level < 56,754 gal and

> 48,648 gal in storage tank.

A.1 Restore fuel oil level to within limits.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> B. One or more diesel engines with lube oil inventory

< 287 gal and > 267 gal.

B.1 Restore lube oil inventory to within limits.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> C. One or more DGs with stored fuel oil total particulates not within limit.

C.1 Restore fuel oil total particulates within limit.

7 days D. One or more DGs with new fuel oil properties not within limits.

D.1 Restore stored fuel oil properties to within limits.

30 days (continued)

Diesel Fuel Oil, Lube Oil, and Starting Air 3.8.3 Watts Bar - Unit 2 3.8-19 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. One or more DGs with starting air receiver pressure < 190 psig and 170 psig.

E.1 Restore starting air receiver pressure to 190 psig.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> F. Required Action and associated Completion Time not met.

OR One or more DGs diesel fuel oil, lube oil, or starting air subsystem not within limits for reasons other than Condition A, B, C, D, or E.

F.1 Declare associated DG inoperable.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.3.1 Verify each 7 day fuel oil storage tank contains 56,754 gal of fuel.

31 days SR 3.8.3.2 Verify lubricating oil inventory is 287 gal per engine.

31 days SR 3.8.3.3 Verify fuel oil properties of new and stored fuel oil are tested in accordance with, and maintained within the limits of, the Diesel Fuel Oil Testing Program.

In accordance with the Diesel Fuel Oil Testing Program SR 3.8.3.4 Verify each DG air start receiver pressure is 190 psig.

31 days (continued)

Diesel Fuel Oil, Lube Oil, and Starting Air 3.8.3 Watts Bar - Unit 2 3.8-20 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.3.5 Check for and remove accumulated water from each of the four interconnected tanks which constitute the 7 day fuel oil storage tank.

31 days SR 3.8.3.6 Perform a visual inspection for leaks in the exposed fuel oil system piping while the DG is running.

18 months SR 3.8.3.7 For each of the four interconnected tanks which constitute the 7 day fuel oil storage tank:

a.

Drain the fuel oil;

b.

Remove the sediment; and

c.

Clean the tank.

10 years

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-21 (developmental)

B 3.8 ELECTRICAL POWER SYSTEMS 3.8.4 DC Sources - Operating LCO 3.8.4 Four channels of vital DC and four Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE.


NOTE--------------------------------------------

Vital Battery V may be substituted for any of the required vital batteries.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One vital DC electrical power subsystem inoperable.

A.1 Restore vital DC electrical power subsystem to OPERABLE status 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> B. Required Action and Associated Completion Time of Condition A not met.

B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> C. One DG DC electrical power subsystem inoperable C.1 Restore DG DC electrical power subsystem to OPERABLE status 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> D. Required Action and associated Completion Time of Condition C not met D.1 Declare associated DG inoperable.

Immediately

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-22 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.4.1 Verify vital battery terminal voltage is 128 V (132 V for vital battery V) on float charge.

7 days SR 3.8.4.2 Verify DG battery terminal voltage is 124 V on float charge.

7 days SR 3.8.4.3 Verify for the vital batteries that the alternate feeder breakers to each required battery charger are open.

7 days SR 3.8.4.4 Verify correct breaker alignment and indicated power availability for each DG 125 V DC distribution panel and associated battery charger 7 days SR 3.8.4.5 Verify no visible corrosion at terminals and connectors for the vital batteries.

OR Verify connection resistance for the vital batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

92 days SR 3.8.4.6 Verify no visible corrosion at terminals and connectors for the DG batteries.

OR Verify connection resistance for the DG batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

92 days SR 3.8.4.7 Verify battery cells, cell plates, and racks show no visual indication of physical damage or abnormal deterioration.

12 months (continued)

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-23 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.4.8 Remove visible terminal corrosion and verify battery cell to cell and terminal connections are coated with anti-corrosion material.

12 months SR 3.8.4.9 Verify connection resistance for the vital batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

12 months SR 3.8.4.10 Verify connection resistance for the DG batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

12 months SR 3.8.4.11


NOTE------------------------------

This Surveillance is normally not performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify each vital battery charger is capable of recharging its associated battery from a service or capacity discharge test while supplying normal loads.

OR Verify each vital battery charger is capable of operating for 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> at current limit 220 amps -

250 amps.

18 months (continued)

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-24 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.4.12


NOTE------------------------------

Credit may be taken for unplanned events that satisfy this SR.

Verify each diesel generator battery charger is capable of recharging its associated battery from a service or capacity discharge test while supplying normal loads.

18 months SR 3.8.4.13


NOTES----------------------------

1. The modified performance discharge test in SR 3.8.4.14 may be performed in lieu of the service test in SR 3.8.4.13 once per 60 months.
2. This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.

Verify battery capacity is adequate to supply, and maintain in OPERABLE status, the required emergency loads and any connected nonsafety loads for the design duty cycle when subjected to a battery service test.

18 months (continued)

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-25 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.4.14


NOTE------------------------------

This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.

Verify battery capacity is 80% of the manufacturer's rating when subjected to a performance discharge test or a modified performance discharge test.

60 months AND 12 months when battery shows degradation or has reached 85% of expected life with capacity < 100% of manufacturer's rating AND 24 months when battery has reached 85% of the expected life with capacity 100% of manufacturer's rating

DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-26 (developmental)

B 3.8 ELECTRICAL POWER SYSTEMS 3.8.5 DC Sources - Shutdown LCO 3.8.5 Vital DC and Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE to support the DC electrical power distribution subsystem(s) required by LCO 3.8.10, "Distribution Systems - Shutdown" and to support the Diesel Generators (DGs) required by LCO 3.8.2, "AC Sources - Shutdown."


NOTES------------------------------------------

Vital Battery V may be substituted for any of the required vital batteries.

APPLICABILITY:

MODES 5 and 6, During movement of irradiated fuel assemblies.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required vital DC electrical power subsystems inoperable.

A.1.1 Declare affected required feature(s) inoperable.

Immediately OR A.2.1 Suspend CORE ALTERATIONS.

Immediately AND A.2.2 Suspend movement of irradiated fuel assemblies.

Immediately AND (continued)

DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-27 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.2.3 Initiate action to suspend operations involving positive reactivity additions.

Immediately AND A.2.4 Initiate action to restore required DC electrical power subsystems to OPERABLE status.

Immediately B. One required DG DC electrical power subsystem inoperable.

B.1 Declare associated DG inoperable.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.5.1


NOTE------------------------------

The following SRs are not required to be performed:

SR 3.8.4.11, SR 3.8.4.12, SR 3.8.4.13, and SR 3.8.4.14.

For DC sources required to be OPERABLE, the following SRs are applicable:

SR 3.8.4.1 SR 3.8.4.6 SR 3.8.4.11 SR 3.8.4.2 SR 3.8.4.7 SR 3.8.4.12 SR 3.8.4.3 SR 3.8.4.8 SR 3.8.4.13 SR 3.8.4.4 SR 3.8.4.9 SR 3.8.4.14 SR 3.8.4.5 SR 3.8.4.10 In accordance with applicable SRs

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-28 (developmental)

A 3.8 ELECTRICAL POWER SYSTEMS 3.8.6 Battery Cell Parameters LCO 3.8.6 Battery cell parameters for 125 V vital batteries and 125 V diesel generator (DG) batteries shall be within the limits of Table 3.8.6-1.

APPLICABILITY:

When associated DC electrical power subsystems and DGs are required to be OPERABLE.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each battery bank.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more batteries with one or more battery cell parameters not within Category A or B limits.

A.1 Verify pilot cells electrolyte level and float voltage meet Table 3.8.6-1 Category C limits.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND A.2 Verify battery cell parameters meet Table 3.8.6-1 Category C limits.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> AND Once per 7 days thereafter AND A.3 Restore battery cell parameters to Category A and B limits of Table 3.8.6-1.

31 days (continued)

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-29 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. Required Action and associated Completion Time of Condition A not met.

OR One or more batteries with average electrolyte temperature of the representative cells < 60°F for vital batteries and

< 50°F for DG batteries.

OR One or more batteries with one or more battery cell parameters not within Category C values.

B.1 Declare associated battery inoperable.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.6.1 Verify battery cell parameters meet Table 3.8.6-1 Category A limits.

7 days (continued)

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-30 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.6.2 Verify battery cell parameters meet Table 3.8.6-1 Category B limits.

92 days AND Once within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a battery discharge

< 110 V for vital batteries (113.5 V for vital battery V) or 106.5 V for DG batteries AND Once within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a battery overcharge

> 150 V for vital batteries (155 V for vital battery V) or 145 V for DG batteries SR 3.8.6.3 Verify average electrolyte temperature of representative cells is 60°F for vital batteries and 50°F for the DG batteries.

92 days

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-31 (developmental)

A Table 3.8.6-1 (page 1 of 1)

Battery Cell Parameters Requirements PARAMETER CATEGORY A:

LIMITS FOR EACH DESIGNATED PILOT CELL CATEGORY B:

LIMITS FOR EACH CONNECTED CELL CATEGORY C:

ALLOWABLE LIMIT FOR EACH CONNECTED CELL Electrolyte Level

> Minimum level indication mark, and 1/4 inch above maximum level indication mark (a)

> Minimum level indication mark, and 1/4 inch above maximum level indication mark (a)

Above top of plates, and not overflowing Float Voltage 2.13 V 2.13 V

> 2.07 V Specific Gravity (b)(c) 1.200 1.195 AND Average of all connected cells

> 1.205 Not more than 0.020 below average of all connected cells AND Average of all connected cells 1.195 (a) It is acceptable for the electrolyte level to temporarily increase above the specified maximum level during equalizing charges provided it is not overflowing.

(b) Corrected for electrolyte temperature and level. Level correction is not required, however, when battery charging is < 2 amps when on float charge for vital batteries and < 1.0 amp for DG batteries.

(c) A battery charging current of < 2 amps when on float charge for vital batteries and

< 1.0 amp for DG batteries is acceptable for meeting specific gravity limits following a battery recharge, for a maximum of 31 days. When charging current is used to satisfy specific gravity requirements, specific gravity of each connected cell shall be measured prior to expiration of the 31 day allowance.

Inverters - Operating 3.8.7 Watts Bar - Unit 2 3.8-32 (developmental)

B 3.8 ELECTRICAL POWER SYSTEMS 3.8.7 Inverters - Operating LCO 3.8.7 Two inverters in each of four channels shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One inverter in one channel inoperable.

A.1


NOTE------------

Enter applicable Conditions and Required Actions of LCO 3.8.9, "Distribution Systems-Operating", with any AC Vital Bus deenergized.

Restore inverter to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> B. Required Action and associated Completion Time not met.

B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />

Inverters - Operating 3.8.7 Watts Bar - Unit 2 3.8-33 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.7.1 Verify correct inverter voltage, frequency, and alignment to required AC vital bus and from associated vital battery board and 480 V shutdown board.

7 days

Inverters - Shutdown 3.8.8 Watts Bar - Unit 2 3.8-34 (developmental)

A 3.8 ELECTRICAL POWER SYSTEMS 3.8.8 Inverters - Shutdown LCO 3.8.8 Inverters shall be OPERABLE to support the onsite Class 1E AC vital bus electrical power distribution subsystem(s) required by LCO 3.8.10, "Distribution Systems - Shutdown."

APPLICABILITY:

MODES 5 and 6, During movement of irradiated fuel assemblies.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required inverter channels inoperable.

A.1 Declare affected required feature(s) inoperable.

Immediately OR A.2.1 Suspend CORE ALTERATIONS.

Immediately AND A.2.2 Suspend movement of irradiated fuel assemblies.

Immediately AND A.2.3 Initiate action to suspend operations involving positive reactivity additions Immediately AND A.2.4 Initiate action to restore required inverters to OPERABLE status Immediately

Inverters - Shutdown 3.8.8 Watts Bar - Unit 2 3.8-35 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.8.1 Verify correct inverter voltage, frequency, and alignments to required AC vital bus and from associated vital battery board and 480 V shutdown board.

7 days

Distribution Systems - Operating 3.8.9 Watts Bar - Unit 2 3.8-36 (developmental)

A 3.8 ELECTRICAL POWER SYSTEMS 3.8.9 Distribution Systems - Operating LCO 3.8.9 Train A and Train B AC, four channels of vital DC, and four channels of AC vital bus electrical power distribution subsystems shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more AC electrical power distribution subsystems inoperable.

A.1 Restore AC electrical power distribution subsystem to OPERABLE status.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> AND 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> from discovery of failure to meet LCO B. One or more AC vital buses in one channel inoperable.

B.1 Restore AC vital bus(es) to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> from discovery of failure to meet LCO C. One or more vital DC electrical power distribution buses inoperable.

C.1 Restore DC electrical power distribution bus to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> from discovery of failure to meet LCO (continued)

Distribution Systems - Operating 3.8.9 Watts Bar - Unit 2 3.8-37 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME D. Required Action and associated Completion Time not met.

D.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND D.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> E. Two trains with one or more inoperable distribution subsystems that result in a loss of safety function.

E.1 Enter LCO 3.0.3.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.9.1 Verify correct breaker alignments and voltage to required AC, vital DC, and AC vital bus electrical power distribution subsystems.

7 days

Distribution Systems - Shutdown 3.8.10 Watts Bar - Unit 2 3.8-38 (developmental)

A 3.8 ELECTRICAL POWER SYSTEMS 3.8.10 Distribution Systems - Shutdown LCO 3.8.10 The necessary portion of AC, vital DC, and AC vital bus electrical power distribution subsystems shall be OPERABLE to support equipment required to be OPERABLE.

APPLICABILITY:

MODES 5 and 6, During movement of irradiated fuel assemblies.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required AC, vital DC, or AC vital bus electrical power distribution subsystems inoperable.

A.1 Declare associated supported required feature(s) inoperable.

Immediately OR A.2.1 Suspend CORE ALTERATIONS.

Immediately AND A.2.2 Suspend movement of irradiated fuel assemblies.

Immediately AND A.2.3 Initiate action to suspend operations involving positive reactivity additions.

Immediately AND (continued)

Distribution Systems - Shutdown 3.8.10 Watts Bar - Unit 2 3.8-39 (developmental)

A ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.2.4 Initiate actions to restore required AC, vital DC, and AC vital bus electrical power distribution subsystems to OPERABLE status.

Immediately AND A.2.5 Declare associated required residual heat removal subsystem(s) inoperable and not in operation.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.10.1 Verify correct breaker alignments and voltage to required AC, vital DC, and AC vital bus electrical power distribution subsystems.

7 days