/kAs /4 -qý DOCKETED USNRC UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION OFFICE OF THE SECRETARY June 18, 2008 (4:49pm)
OFFICE OF SECRETARY RULEMAKINGS AND ADJUDICATIONS STAFF BEFORE THE COMMISSION In the Matter of
))
AMERGEN ENERGY COMPANY, LLC
))
(License Renewal for the Oyster Creek
)
Nuclear Generating Station)
)
Docket No. 50-0219-LR NýUCLEAR INFORMATION AND RESOURCE SERVICE, JERSEY SHORE NUCLEAR WATCH, GRANDMOTHERS, MOTHERS AND MORE FOR ENERGY SAFETY, NEW"JERSEY PUBLIC INTEREST RESEARCH GROUP, NEW JERSEY SIERRA CLUB AND NEW JERSEY ENVIRONMENTAL FEDERATION (COLLECTIVELY "CITIZENS")
REPLY TO NRC STAFF AND AMERGEN RESPONSES TO COMMISSION ORDER DATED MAY 28, 2008 Richard Webster Eastern Environmental Law Center 744 Broad Street - Suite 1525 Newark, New Jersey 07079 Counsel for Citizens June 18,2008 S-pý~eA~
0,3A c~5 Sh-0 7
I.
Introduction AmerGen Energy Co. LLC ("AmerGen") and the NRC Staff both make the erroneous claim that AmerGen's commitment matches or bounds the modeling that Judge Baratta would require. In fact, AmerGen has put forward an approach that is even less conservative than the approach Judge Baratta implicitly rejected by putting forward the additional requirements. Furthermore, the proposed sensitivity analyses totally fail to reflect the full amount of uncertainty present. The NRC Staff's opinion that AmerGen's additional modeling would meet Judge Baratta's requirements is based on the' misapprehension that AmerGen will use the latest external data to conservatively characterize the thicknessof the shell and then do additional sensitivity analyses, which it will not. In any event, Judge Baratta would require AmerGen to use all of the data to generate a best estimate of the drywell thickness at each point on the drywell using a mathematical interpolation and extrapolation scheme, such as contouring. Sensitivity could then be explored automatically using a Monte Carlo simulation or manual variation of the input parameters. Finally, neither the Staff nor AmerGen discuss what will be required if further analysis does not determine compliance with the Code with sufficient certainty. In contrast, Citizens offer a solution to this problem. Citizens' Ex. CR 5, Attachment at 3-5.
II.
Judge Baratta Intended To Impose Additional Requirements Citizens submitted as hearing exhibits AmerGen documents discussing how AmerGen would derive drywell thicknesses for the required three dimensional modeling. Citizens' Ex. 45, 46, 65. The most definitive of these is a technical evaluation dated April 20, 2007, which proposed to use similar values for average thickness in the sandbed region to those AmerGen is now proposing. Affidavit of John F. O'Rourke, dated June 11, 2008 ("O'Rourke Aff.") at ¶ 16. In addition, the technical evaluation stated that there are "several locally thin areas in the sandbed" and proposed to include estimates of the extent and average thickness of those areas in the model. Citizens' Ex. 45 at 3, 6, 8-12. In contrast, Citizens suggested an approach based on contour plotting of both the internal and external data. Having heard all the evidence for and against the use of the external data ahd contour plotting, Judge Baratta decided to
impose additional requirements on the proposed modeling. In particular, he endorsed using an "extrapolation scheme" that "might be similar to the one suggested by Citizens' expert Dr. Hausler, that uses contour plots generated from known thicknesses both interior and exterior." Additional Statement of Judge Baratta at 6. This amounted to a rejection of the approach outlined in the technical evaluation.
Far from heeding the words of Judge Baratta, AmerGen has now come back with a proposed modeling scheme that is even less realistic than the technical evaluation that Judge Baratta found wanting.
The latest approach omits most of the local areas of severe corrosion from the base case, and i2 overestimates the average thicknesses of the Bays.
Furthermore, AmerGen has not proposed an extrapolation scheme that is remotely akin to that set forth by Dr. Hausler. Thus, its approach is completely unresponsive to Judge Baratta's additional requirements for a conservative assessment of the drywell thicknesses distributed over the shell using all of the data, followed by a sensitivity analysis to assess the uncertainty.
II.
AmerGen's Approach Does Not Provide The Best Estimate Of The Drywell Thickness At Each Point On The Shell And Fails To Fully Assess Uncertainty The modeling conducted by General Electric ("GE") showed that that small areas (<1 square foot) of severe corrosion have a significant effect on buckling capacity. Citizens' Ex. 3 at 2 (Item 4);
AmerGen Ex. 39. Thus, in addition to an acceptance criterion for the average thickness of each Bay, the licensee also developed an acceptance criterion to control small areas of severe corrosion that were less than 0.736" thick. Citizens' Ex. 3 at 2 (Item 4). Such areas of severe corrosion have been observed in six adjacent Bays. Citizens' Ex. CR 4, Attachment at Figures 3-5, 7-11. Thus, as Judge Baratta has recognized, best estimates of these areas must be included in any modeling. In addition, because the thickness and extent of these areas are not well characterized, they must also be varied in thickness and There is an oblique reference to a locally thinned area in Bay 19 in the base case in the description of the second sensitivity analysis proposed by AmerGen. 0' Rourke Aff. at ¶ 23-24. However this is not mentioned in Table 1 which presents a "bay-by-bay explanation of... what thicknesses are being used in the base case." Id. at
¶16.
2 A further memorandum from Dr. Hausler providing a detailed response to AmerGen's proposal is provided as an attachment to Citizens' Exhibit CR 4.
2
extent in a sensitivity analysis. Inexplicably, AmerGen has failed to even include its own estimate of the existing severely corroded areas in its modeling proposal base-case, let alone the more realistic analysis of Dr. Hausler. Although, it has proposed to add one such area in Bay I as part of the sensitivity analysis, Id. at ¶ 18, this is non-conservative because the size of the area will not be expanded beyond its currently estimated extent, Citizens Ex. 45 at 8, and many other severely corroded areas would be omitted from the model. The base case and the sensitivity analyses proposed by AmerGen therefore completely fail to capture the full range of uncertainty associated with the lack of knowledge about the thickness and extent of the severely corroded areas in these six Bays.
Judge Baratta recognized that the best way to include the severely corroded areas is to use spatially distributed estimates of thickenesses distributed across the drywell using contouring or a similar interpolation technique. However, even if using average thicknesses were acceptable, AmerGen has produced over-optimistic estimates of those thicknesses in part by estimating the average thickness of the shell in Bays 1, 3, 7, and 15 below the 11 '3" level without using any of the measurements taken in those Bays. O'Rourke Aff. at ¶ 14, Table 1; Citizens' Ex. CR 4 Attachment at 4-7. This approach even conflicts with numerous other AmerGen documents, which derived more conservative estimates of average thickness using external measurements taken in each Bay. E.g. AmerGen Ex. 16 at 5.
Notably, the NRC Staff does not appear to believe AmerGen's proposed approach is adequate.
The Staff expected AmerGen to meet its commitment by using conservative thickness estimates for unmeasured areas. NRC Staff Br. At 3. However, in contrast to AmerGen, the Staff has rightly concluded that the 106 external thickness measurements "conservatively characterize the degraded drywell shell." Affidavit of Hansraj G. Ahsar, dated June 11, 2008 ("Ashar Aff.") at ¶ 13. Furthermore, the Staff believe that the 106 external measurements should form the base case from which the sensitivity studies should be conducted. Id. at ¶ 8. As shown above, AmerGen has a different view of the 3
For example, AmerGen proposed to model the lower part of Bay 15 at thickness 0.931", O'Rourke Aff.,
but has previously estimatedthe same thickness to be 0.788", which is a very significant difference. AmerGen Ex.
16 at 5. Furthermore, O'Rourke mistakenly states that the thickness selected for Bay 1 is consistent with the external data for that Bay. The proposed average thickness is 0.826 inches, whereas.the average of the external data is 0.802". Citizens Ex. 16 at 5.
3
commitment, because it is currently intending to rely primarily on the internal measurements, which only cover a tiny area of the shell (less than 1%) and therefore produce even more uncertain estimates of the spatially distributed thickness. Citizens CR 4 Attachment at 2, Figures 3-13. Finally, Citizens and Judge Baratta believe that both the internal and the external thickness data should be input into a mathematical extrapolation technique to derive the most accurate picture possible of the actual state of the vessel.
Furthermore, once the best estimate is derived, both Citizens and Judge Baratta believe a sensitivity analysis should be carried out to illustrate the full range of uncertainty. As Dr. Hausler has suggested, this could be achieved through a Monte Carlo simulation, or, as Judge Baratta suggested, this could be done manually.
IV.
At Present There Is No Reasonable Assurance That The Drywell Meets The Safety Requirements During Refueling The Staff relies upon the GE modeling acceptance criteria and the Sandia Study to argue that there is currently reasonable assurance that the drywell meets the safety requirements. Ashar Aff. at ¶¶ 10-14. However, neither are persuasive. First, as the NRC Staff acknowledged, where there is both local thinning and generalized thinning, the acceptance criteria could allow the factor of safety to drop to 1.81.
NRC Staff Ex. C I at A54. Here, the data undoubtedly show both general thinning and local areas of severe corrosion. See e.g. AmerGen Ex. 16 at 5 (average wall thickness in Bay 13 is 0.786", 0.05" above the acceptance criterion for mean thickness); see also e.g. Citizens" Ex. Cl at A7; Citizens' Ex. 61 at 17 (the local area acceptance criterion was probably violated in Bay 13). Thus, a comparison of the measurements with the acceptance criteria cannot establish reasonable assurance that the shell is meeting the factor. of safety requirements.
Second, the NRC Staff s reliance. upon the Sandia Study is misplaced. The Sandia model largely used average external data to characterize the sandbed, but the average thicknesses used by Sandia are consistently higher than the latest measurements indicate. Compare NRC Staff Ex. 6.at 49 (Table 2-7) 4
with AmerGen Ex. 16 at 5.4 In addition, Sandia placed two small 30 inch by 18 inch locally thin areas directly under the ventlines in Bays I and 13. Id. at 49. However, Dr. Hausler's contour plots show larger and thinner severely corroded areas than assumed by Sandia well away from the vent lines in these Bays. Citizens' Ex. 61 at 14-17. Because severe corrosion away from the vent lines has more effect than areas of severe corrosion below those lines, the placement assumed by Sandia does not bound the effect of the severely corroded areas. Moreover, as discussed earlier, six Bays, not two, have local areas of severe corrosion. Even with these non-conservative assumptions, the Sandia study estimated the factor of safety during refueling as 2.15, just above the required 2.0.5 Both the lack of conservatism in the analysis and the high degree of uncertainty in the modeled estimate of the factor of safety mean that the Sandia study cannot provide reasonable assurance that the ASME code will be met during the next refueling.
V.
Conclusion For the foregoing reasons, the Commission should require AmerGen to conduct additional analyses of the buckling capacity of the drywell shell to ensure there is sufficient certainty that the shell.
meets the buckling capacity requirements prior io any decision on relicensing and grant any other relief as it may see fit.
Respectfully submitted, Richard Webster, Esq.
Eastern Environmental Law Center Attorneys for Citizens Dated: June 18, 2008 4
For example, the area comprising half of Bay I and half of Bay 19 was assigned a thickness of 0.858 inches by Sandia, NRC Staff Ex. 6 at 49, but in 2006 Bay I had an average thickness of 0.802 inches and Bay 19 had an average thickness of 0.801 inches. AmerGen Ex. 16 at 5. Similarly the area comprising half of Bay 13 and half of Bay 15 was assigned a thickness of 0.842 inches by Sandia, but in 2006 Bay 13 had an average thickness of 0.786 inches and Bay 15 had an average thickness of 0.788 inches.
5 It is not possible to argue that Sandia's rejection of the enhanced capacity reduction factor builds in any conservatism. Citizens' Ex. CR 5 at 2.
5
Exhibit CR 4
EXHIBIT CR 4 UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION BEFORE THE COMMISSION In the Matter of
))
AMERGEN ENERGY COMPANY, LLC
)
Docket No. 50-219-LR (Oyster CreekNuclear Generating Station)
))
)
)
DECLARATION OF DR. RUDOLF HIAUSLER
- 1.
My name is Dr. Rudolf Hausler. Citizens have retained me as an expert witness in proceedings concerning the application of AmerGen Energy Company LLC to renew its operating license for the Oyster Creek Nuclear Generating Station ("Oyster Creek") for twenty years beyond the current expiration date of April 9, 2009.
- 2.
I am an expert on the corrosion of metals during operation.
- 3.
The attached memorandum dated June 17, 2008 represents my current opinion regarding the topics it covers.
I declare under penalty of perjury that the foregoing and the attached memorandum, dated June 17, 2008 is true and correct.
Executed this day of June, 2008 at Kaufman, Texas I/7
-, PhD 2
MEMORANDUM To:
Richard Webster, Esq.
June 17, 2008 Legal Director Eastern Environmental Law Center 744 Broad Street, Suite 1525 Newark, NJ 07102 From: Rudolf H. Hausler Corro-Consulta 8081 Diane Drive Kaufman, TX 75142
Subject:
Discussion of Sensitivity Analyses Proposed By NRC Staff and AmerGen AmerGen has proposed an approach to the sensitivity analyses requested by. Judge Barrata1). The approach would consist of modeling base case along with two sensitivity analyses. These would consist of a) defining some hypothetical remaining wall thickness in Bay I for an area of 51 inches in diameter 596 mils. This is an area of 14 ft2 or 20% of the area of one Bay and b) reducing the average remaining wall thickness of Bay 19 by 50 mils to 776 mils but only for an area of 8.5 ft either side of the centerline.
The rational for these definitions is hard to understand. The base case is entirely based on the internal grid UT measurements which in the majority of the bays do not reflect the corrosion which occurred below the 1I'00" elevation, i.e. in the sandbed. For the "sensitivity analyses" I cannot find any justification for either the areas over which the wall thicknesses are being reduced, or the value to which they are reduced. All of the data input to the three models is based on the internal UT measurements and some arguments as to why the measurements from adjacent bays should be controlling in those instances where the internal grid measurements returned only nominal wall thickness and where therefore judged not to be relevant. These sensitivity analyses are therefore totally unrealistic and do not address the problem Judge Barrata wanted analyzed, namely the uncertainties existing due to the limitations of the existing data.
For this reason I shall discuss below the entire existing data set in order to put in perspective the proposed AmerGen sensitivity analysis juxtaposed to the sensitivity analysis Judge Barrata had in mind when he specified the determination of the effects caused by the uncertainties in the size of the thinned areas.
")AmerGen Initial Brief in Response to CLI-08-10 (6/11/08) 6/18/2008 I of 7 sensitivity analyses v. 2
I. Introduction There are really several kinds of uncertainties with respect to the degree the drywell liner was thinned by corrosion. The first pertains to the size of the grid used to perform the internal UT measurements - 36 in2 (0.25 ft2) per Bay out of 73 ft2 total bay area. Even two or three grid measurements would not be representative of the total bay area. Second, in many instances the internal grids simply did not reflect the actual corrosion of the respective bays. Third, the external measurements were few and far between and left open the question as to the extent of the corroded area and the nature of the remaining surface between the measured points.
The sensitivity analysis found necessary by judge Barrata in order to assess the confidence limits attached to the modeling result of the remaining safety factor attached to the buckling resistance of the Oyster Creek drywell liner, as I understand it would have been aimed at a realistic estimation of the thinning of the large areas of the sandbed region of the drywell that have not been measured. AmerGen is doing the exact opposite. They worry about modifying measured areas. In fact, they have incorrectly used "Engineering Judgment" instead of using objective interpolation and extrapolation techniques, such as those that I have proposed.
The following discussion outlines once more what it is that one knows for certain about the deterioration of the drywell liner at this stage. The information is extracted from AmerGen documents which have been in evidence2 *.
II. The Nature of the Data There are basically two types of data available to assess the integrity of the liner. These are "Internal UT Wall Thickness Measurements" and"External UT Wall Thickness Measurements"
.referred to in the following simply as internal and external measurements.
The internal measurements were made by means of templates which measured 7 inch by 7 inch (see Figure 1) and contained 7 one-inch holes at one-inch spacing across in seven rows in the vertical direction. This template therefore held 49 regularly spaced holes for reproducible placing on a well marked location on the inside of the liner. In some instances templates with only seven holes in one horizontal row were used.
The external UT measurements were made in what has repeatedly been claimed to be the most corroded areas3). The locations for these measurements were recorded with respect to a reference point which was located more or less in the center of the bay below the torus vent pipe, approximately at the top of the sandbed. At the hearing the relationship between the internal grid reference and the external reference was revealed. Therefore, I can now compare the two data sets within the same bay. In some bays multiple grid measurements were made.
- 2) AmerGen Ex. 19 Attachment 4; and OCLROOO18581-18598.
- 3) The "most corroded areas" as has been pointed out repeated were identified visually. However, since the extent of corrosion is determined by the remaining wall thickness and the most corroded Bays have been described as having exterior surfaces like a golfball it is difficult to understand how the thinnest remaining wall thicknesses could be determined visually.
6/18/2008 2 of 7 sensitivity analyses v. 2
II.
Discussion of the Data The attached Table I summarizes all internal and external measurements by their respective averages. Thus one finds for instance that for Bay I the average remaining wall thickness from the 7-hole grid is 1087 mils (1.087 inches) while the external measurements averaged 801 mils.
The difference between internal and external measurements is 24%. It turns out that for 3 of 6 Bays where there is comparable data, the internal and external measurements agree within the margin of error. This shows that there is no strong bias in the external data. This is hardly surprising because AmerGen has only presented evidence that a few points were overground, and has not provided any point by point data to establish any bias. However, from the point of view of sensitivity analysis this is only half the story as a closer more detailed analysis of all the data will show below.
IV. Detailed Analysis of the External data.
In order to put all these results into perspective one needs remember that the sandbed is approximately 3'0" to 3'3" high (see Fig. 2) and approximately 20 feet wide per bay (10 feet either side of the torus vent pipe) for a total area of about 73 square feet (ft2). With this background we can proceed to discuss Figures 3 through 13, one for each bay and the respective external measurements.
Figure 1 shows a schematic of the two kinds of templates that had been used for the internal measurements.
Figure 2 attempts to show the location for the internal grid measurements. There is a concrete curb on the inside of the liner about two feet above the reactor floor. A cutout below the reinforcements for the torus vent pipe allows the placement of the UT template at 11 feet. The template measurements therefore extend from 11 feet to I1 feet 7 inches. According to the design this should be well within the sandbed area and should correspond to at least some external measurements. However, a number of the 7 hole templates (see below) returned original wall thicknesses even though corrosion occurred at lower elevations. This indicates that the sand in the sandbed did probably not reach as high as required by the design and was very likely unevenly distributed. This needs to be kept in mind through out the following discussions because this unevenness is another source of the uncertainty as to where corrosion might have occurred and where it would have been most severe.
The subsequent figures represent contour plots for the remaining wall thickness based on the data as reported by AmerGen. Thus Figure 1 shows a contour plot for the Bay I external measurements. The vertical axis4) is the distance from the reference point toward the bottom of the sandbed. The numbers are in inches. The horizontal axis represents the location of a particular measurement either left or right of the reference point which usually was placed in or near the center of the bay just below the torus vent pipe.
- 4) The liner wall at this point is actually not vertical (as shown in Fig. 1) but slanted at about a 45 deg angle off horizontal.
6/18/2008 3 of 7 sensitivity analyses v. 2
There has been a lot of controversy regarding this approach of presenting the UT data. The reason for the controversy is the fact that these external measurements are point measurements and no effort had been made to determine the extent (x/y expanse) of the corrosion around the point of the measurement. One may therefore reasonably ask whether it should be permitted to essentially average the remaining wall thickness between two points or whether the "pits" are singular events not really affecting the remainder of the area where the pit occurred.
But this is precisely the uncertainty judge Barrata asked the parties to deal with. It may well be that the contour plots, which are based on the average (slope) UT measurements between each point and any other around it, are the proper representation of the corroded liner. It could be that they over estimate the deterioration (as AmerGen would have it), but they could also underestimate the extent of the corrosion. Judge Barrata indicated that he agreed with me that a methodology such as contouring or something similar is the best approach to deal with the uncertainty of the remaining wall thicknesses caused by the relatively sparse density of measurements.
Bay 1: The internal measurements in Bay I were made with a lx7 inch template. For comparison the template was drawn into the graph at the 0/0 location (Figure 3) where it most likely was located. As it turned out the internal measurements were non-representative of the corrosion in Bay 1 and therefore irrelevant. AmerGen realized this and went ahead to characterize this Bay 1 by way of the results obtained for Bay 19 because a) they are adjacent Bays and b) because they were both the most corroded ones. However, AmerGen uses the internal grid measurements for Bay 19, the average of which was 826 mils (836 mils according to our calculations) rather than the average of the external measurements of Bay 19 the average of which was 801 mils. (As it turns out the averages of the external measurements for Bays I and 19 are most nearly identical.)
There is still an additional difficulty to which Judge Barrata alluded. The external measurements in Bay I extended over the Bay from - 40 inches of center to + 40 inches. The Bay however extends to roughly 120 inches on either side. Therefore less than 30 % of the Bay was covered with external measurements. The contours drawn in Figure 1 for Bay 1 suggest that the "bath tub ring" of severe corrosion might well extend the entire width of the Bay. This is another uncertainty which modeling must take into consideration by way of a sensitivity analysis.
Finally, Judge Barrata decided that from a structural point of view it is preferable to use mathematical interpolation and extrapolation techniques to make the best possible estimate of the distribution of the thickness over the Bay, rather then averaging the remaining wall thicknesses over a broad area.
Bay 3: Figure 4 shows the contours for Bay 3. The internal grid measurements (Ix7) are not representative of the corrosion in that Bay. For this reason AmerGen creates a complex argument which should justify using data from Bays 1 and 5 below 11 '0" for an average of 950 mils.
However, again the average for the external measurements in Bay 3 is 865 mils. AmerGen has failed to justify how 950 mils can be a conservative thickness estimate for the average thickness of this this Bay when average of the external measurements in this Bay is 865 mils.
6/18/2008 4 of 7 sensitivity analyses v. 2
Bay 5: Here too one finds the internal grid results to reflect no corrosion (Fig 5). It is noted that the external measurements were made very low near the bottom ofthesandbed and indicate on average a 20% deterioration over the nominal wall thickness.
In this Bay a trench was dug on the inside of the containment vessel to assess the corrosion in the sandbed area through UT measurements from the inside 5). AmerGen finds an average of these "Trench Measurements" to be 1074 mils for the remaining wall thickness. However, as a detailed analysis in Fig 5B shows this assessment may be too optimistic for certain elevations in the sandbed. Indeed the average of the external UT measurements for Bay 5 almost near the bottom of the sandbed is 960 mils and essentially confirmed by the trench data at elevation 5 to i 0 inches from the bottom corresponding to -47.5 to -42.5 inch elevation in Figure 5. Therefore, here as well, one finds that AmerGen tends to embellish the extent of the damage corrosion may have caused in Bay 5.
Bay 7: As Figure 6 shows only 7 external measurements were made in this Bay. There was additionally some confusion about certain points from 1993 which could not be repeated in 2006.
Adjusting for this, the external average remaining wall thickness is 995 mils. The internal measurements returned nominal wall thickness. AmerGen however determines an average thickness of 1034 mil for the wall below 11 '0", a number apparently based on some averages from Bays 5 and 9. Additionally, it appears that there was some significant corrosion in this Bay (see Fig. 6) which AmerGen choose to ignore and not further investigate.
Bay 9: As shown in Figure 7 10 external measurements were made in an area of 1.5 ft by 7 ft. or barely 15% of the total bay area. The average remaining wall thickness in that area was 905 mils or a reduction of 22% from nominal. The I x7 internal grid showed no corrosion while the 7x7 grid returned an average of 988 with a standard deviation of 78 indicating fairly large variation between individual measurements (not instrument error). Note: AmerGen choosesthe smaller of the two internal grid averages (993 mils6)) and disregards entirely the external measurements.
Additionally, there is within the grid a top down drift toward the lower values of the external measurements indicating that the residual wall thickness in the area where the sand was is probably of the order of 903 mils rather than the 993 preferred by AmerGen.
Again one can see that AmerGen tends toward interpreting the best estimate of the average thickness UT measurements less conservatively than the data would indicate. In addition, the sensitivity analysis fails to take account of the large uncertainties.
Bay 11: Figure 10 shows that Bay 11 was actually quite corroded. Here the most corrosion is observed at one spot measured about 20" from the top at 705 mils or 40% of wall loss. This point should have been explored in greater detail, particularly since the internal grid measurements returned values of the same order of magnitude (720, 737 mils at higher elevations). Here AmerGen relies entirely on the internal measurements which led to using optimistic (860 mils) rather than conservative values for the modeling.
- 5) The trench reached down to the elevation of the sandbed floor but was only wide enough to accommodate a series of vertically stacked 7x7 grids as shown in Figure 2.
- 6) The average of the 7x7 internal grid is actually 988 rather than 993 according to their own data 6/18/2008 5 of 7 sensitivity analyses v. 2
Bay 13: This is oneof the most corroded bays. As Figure 9 illustrates there are sizable areas with remaining wall thickness below 700 mils, nearly 40% loss of wall thickness. The average of the external measurements is 785 mils. AmerGen chooses to use the average of the two 7x7 internal Grids which is 907 mils. However, as Fig. 1 illustrates the grid measurements are well outside the elevation where the most corrosion occurred and can therefore hardly be representative of the corrosion which occurred in this Bay.
AmerGen again chooses to ignore their own data and chooses an overly optimistic approach.
Bay 15: Figure 10 indicates that this bay may be corroded throughout its entire depth. It would seem therefore that it should not be permissible to characterize this bay entirely by the internal measurements which were made well above the corroded zone. Nevertheless, AmerGen chooses values from adjacent bays to characterize this one. Hence, AmerGen uses 931 mils as the average thickness for this bay when in fact 797 mils would be more appropriate.
Bay 17: This Bay (Figure 1 )does not appear to be badly corroded on average, however, as has happened before in other bays, the one spot, where residual wall thickness of less than 700 mils-was observed, was not further investigated, leaving open the possibility that serious corrosion might indeed extend beyond that point.
A trench had been dug in this bay from the inside of the containment vessel as well. Again, the residual wall thickness had been UT measured using a series of 7x7 inch grids stacked one on top of each other. These measurements are shown in Figure 12 in comparison to the (regular) internal 7x7 grids (see also Table 1). The trench data indicate that most of the corrosion occurred at the highest elevation from the bottom of the sandbed. In fact here the remaining wall thicknesses correspond to the results of one set of grid data. And since the top of the trench and the grids were not at the same peripheral location in this bay it is reasonable to assume that the corrosion was wide spread on the top of the sand bed, which in this case must have reached up quite high.
AmerGen uses a convoluted argument to arrive at a representative residual wall thickness for this bay of 954 mils. The actual data would suggest, however, large parts of the wall in this bay are substantially thinner and more of the order of 800 to 850 mils.
Bay 19: Figure 13 shows the data for this bay. It turns out that the most severe corrosion occurred toward the top of the sandbed. Internal and external averages appear to agree, but the fact that there is very likely an area of severe corrosion between the top of the external measurements and the bottom of the internal ones suggests that perhaps the average wall thickness chosen by AmerGen (826 mils) is somewhat too high and the average of the external measurements, 801 mils may be. more appropriate.
V. Summary The overall conclusion from this discussion is that AmerGen has disregarded the external UT wall thickness measurements in the sandbed region as not representative. Conversely, AmerGen 6/18/2008 6 of 7 sensitivity analyses v. 2
has found the internal grid measurements to be representative of the present state of the drywell.
It is a fact, however, that the internal grids (0.25 ft2) cover a tiny area in comparison to the entire bay and the fact that over 0.25 ft2 49 measurements are made does not help the lack of information with regards to the rest of the surface. It is precisely here where additional information gained from the external measurermients could have helped. In addition it turns out that nearly half the internal measurements could not be used because the templates were placed too high above the actual (not nominal) top of the original sandbed. In these cases, rather than using the external data, complex averages were calculated by AmerGen, using the data from adjacent bays under the assumption that a certain uniformity of corrosion existed. That this was, not the case, and that this assumption, explicit or implicit, was not realistic, is amply demonstrated by the graphical representation of the external measurements in the attached figures.
As a consequence I think that AmerGen avoided the real question judge Barrata asked: How can one model the real surface on the basis of the very small available data density. This question has been discussed with a number of structural, metallurgical engineers and statisticians. The answer unanimously was that the available information is not sufficient for the task. All the bays should be surveyed with modern methods to properly assess the residual wall thickness and the variations thereof. That this can be done effectively with modern automated UT and MFL (magnetic flux leakage) equipment has been amply demonstrated in the literature and in pertinent company brochures.
Overall, I have come to the conclusion that AmerGen overestimates the remaining wall thickness of the drywell liner in the sandbed areaby 10 to 15% for what they call the base case. As pointed out above the proposed sensitivity analyses are quite unrealistic as well because they do not mirror the actual nature of the corrosion suffered by the drywell liner in the sand bed area where up to 40% of wall thickness loss has been observed by point measurements without having been further explored.
6/18/2008
- 7 of 7 sensitivity analyses v. 2
m-m m
m-m mm m
m m
Table1 External Data Internal Data Nominal WT (mils) 1154 Comparison between External and Total Extent of Bay Average Std Dev No of Points Bay Average Std Dev No of Points Internal UT Measurements [int-Corrosion from ext.
Sextj/[int]
averages Bay 1 801 135 23 iD
- 1087 87 7
26%
31%
Bay 3 865 85 8
3D
- 1180 14 7
27%
25%
Bay 5 960 39 8
5D 1185 5
7 19%
17%
Bay 7 1007 28 5
7D 1133 16 7
11%
13%
Bay 9 905 88 10 9D 988 78 49 8%
22%
9A 1154 10 7
22%
Bay 11 783 48 8
- 11C, 898 88 49 13%
32%
11A 846 123 49 7%
Bay 13 784 111 22 13C 1143 8
7 31%
32%
13A 846 57 49 7%
13D 968 174 49 19%
Bay 15 788 65 11 15A 1121 41 7
30%
32%
15D 1064 62 49 26%
Bay 17 890 95 10 17D 833 87 49
-7%
23%
17/19 969 28 49 8%
17A 1015 106 49 12%
Bay 19 801 76 9
19A 822 94 49 3%
31%
19B 849 59 49 6%
I 19C 839 103 49 5%
Comments:
- The (*) indicates that the internal measurements. reflect the nominal wall thickness and. The template was set too high above the sandbed
- The difference between internal and external averages where nominal wallthicknes was measured internally indicates greater corrosion further down in the sandbed or, alternatively that the sandbed did not reach as high as the design might have required
M M
M M
M-M-M M
M M
M M
M Figure 1 Templates used for Internal UT Measurements 1 inch diameter holes spaced 1 inch center to center 7-hole template used in some instances (see table 1)
Ioo00oo0 o
m-m-m-
-m mmn-
-m
-m m
Scnematic Cross Section througn SanoDea Area (not to size, actual drywell liner wall is slanted at about a 450 angle in this area)
Figure 2 Dimensions of Sandbed Area 15" by 3'3 1/4"
/
Curb Elev. 12'3" Biological Shield Concrete Containment Cutout to Elev. 11' Only around Vent lines Reactor Floor 7 Elev. 10'3" 20" Diameter Access Hole through concrete containment for Sandbed removal
/
Area of UT Measurements Below and to the Side of Vent Lines about 6" to 8" Sandbed Floor Elev. 8' 11 3/4" I
m m
m m
m m
m m
m m
m m
m m
Contour Plot for Bay 1 External UT Measurements 2006 Approximate size a$ndposition of 1x7 grd for inten Figure 3
- i. measurements U
-10 0
0*
-20
-30 Area less than 725 Mil about 6" to 7" Wide and 80" long.
Area less than 725 Mil about 8.7" by 7"
-40
-50
---w 40
-60
-40
-20 0
20 Horizontal Position
=<= 675
<= 700
<= 725
<= 750
<= 775
> 775
m m
m m
m
-m m m
m Figure 4 Contour Plot for Bay 3 Measurements 2006
-10
-15 0
-20
-30 Approx. pos. and size of 1 x 7 inch grid used for internal UrT measurements 01 Note: Ave. remaining wall Thickness from internal UT Measurements was 1180 mils
-i.
A. 75
-50
-25 0
25 Horizontal Pos S<= 800.0= <= 850.0
<= 900.0 ' <= 950.0= > 950.0 50 75
m m
m m
m m
m m
m Contour Plot for Bay 5 Measurements 2006 Figure 5
-37.5
-40.0-
= -42.5-l.
, -45.0 a)
-47.5-Note: These measurements are more than 36 inches belowthe 1 x 7 grid measurementswhich showed and average remaining wall thickness of 1185 Mil U
-- U.U-40
-30
-20
-10 0
10 Horizontal Position 20 0<=
900.0
<= 975.0 R2.
<= 950.0
> 1000.0 1000.0
m-
-m-m m-m
-m-m Vertical Corrosion Profiles in the Trench of Bay 5 Figure 5B 1200 1150-1100-1050-E 1
I,..
1000-950 900 0
5 10 15 20 25 30 depth from the bottom to the top (inches) 35 40 45
SM M M
M m
M M M M-M M
M Figure 6 Contour Plot for Bay 7 2006 data Est. position of 1 x 7 grid measurements I
I
-10.0
-12.5-
-o -15.0-
-17.5 -
-20.0 -
-22.5
-1*
-40
-20 0
20 Horizontal Position
<= 925.0
<= 950.0 m > 1000.0 40
<= 975.0 2006 Measurements
<= 900.0
-<=
1000.0
m m9 u s
-mn m
m Contour Plot for Bay 9 using 2006 Data Fgr m---
-7U 0.25
-30 I i Approx. location for 1x7 inch Grid for internal UT measurements
-35T
-75
-50
-25 I
I 0
25 50 Horizontal Position Measurements
< 800.0
<= 850.0
<= 900.0
<= 950.0
<= 1000.0
> 1000.0
Contour Plot for Bay 11 with 2006 data Approx placement of 7x7 inch grid for internal measurements
-20 I
Figure 8
Contour Plot for Bay 13 External Corrosion 2006 Data Figure 9
m m
m m
m-m m
m Contour Plot Bay 15 Figure 10
%MrNV 0 "* -40 A pprox. size and location of 7x7 grid fo Internal measurements A
-50
-75
-25 0
25 50 Horizontal Position 2006 Wall Thickness
-<=
750.0
> 900.0
<= 800.0
<= 850.0
<= 900.0
M M---- M-M-Contour Plot for Bay 17 usina 2006 data Figure 11 0
Approx. location and size of 7x7 inch grid for internal UT measurements
-10
"-20 0.
-30
-40
-50
-25 0
25 50 horizontal Pos
<= 700.0 M <= 750.0
<= 850.0
<= 900.0
> 950.0
<= 800.0
-<=
950.0
m--
m m
-m -
Figure 12 Comparison of Various Thickness Measurements in Bay 17 2006 data 1200 1100 1000 900 800 7nn CJ 7(3(
M
= w M M M M M M M M = M M M M mý M
M M
=
M M-WWa1-m*4 m
II
'W'ý m
m 7
- 1*
- 4
/
/
0 600 f-
-4e--Ave Wall. Thickness Measured in Trench Nominal Wall Thickness Average External Wall Thickness Measurements Horizontal averages for Internal Grid Data 17 A
-mGrand average of internal grid data Horizontal averages for Grid Data 17 D 500 0
5 10 15 20 25 30 35 40 45 Elevation from Bottom of Trench (inches)
Bay19Extrnl 006 UT Measurements, Minim um Vle iue1
-100 000
Exhibit CR 5
EXHIBIT CR 5 UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION BEFORE THE COMMISSION In the Matter of
)
AMERGEN ENERGY COMPANY, LLC
)
Docket No. 50-219-LR (Oyster CreekNuclear Generating Station)
))
)
DECLARATION OF J. KIRK BROWNLEE P.E.
- 1.
My name is J. Kirk Brownlee, P.E. Citizens have retained me and my colleague Richard C. Biel P.E. as a expert witnesses in proceedings concerning the application of AmerGen Energy Company LLC to renew its operating license for the Oyster Creek Nuclear Generating Station ("Oyster Creek") for twenty years beyond the current expiration date of April 9, 2009.
- 2.
Mr. Biel and I are experts on determining the structural integrity of pressure vessels.
- 3.
The attached memorandum dated June 17, 2008 represents our current opinion regarding the topics it covers.
I declare under penalty of perjury that the foregoing and the attached memorandum, dated June 17, 2008 is true and correct.
Executed this 17th day of June, 2008 at Houston, Texas J. Kirk Brownlee, P.E.
2
I STRESS ENGINEERING I
SERVICES INC.
13800 Wesffair East Drve, Houston, Texas 77041-1101 Phone: (281) 955-2900 Fax: (281) 955-2638 Website: www.stress.com HOUSTON CINCINNATI NEW ORLEANS a
CHICAGO SENIOR PRINCIPALS President Joe R. Fowler, Ph.D,, PE.
Senior VMos President W. Thomas Asbill,,E.
Vice Presidents Ronald D. Young, Ph.D.. PE, Clinton P. Haynes Jack E. Miller, RE.
J. Randy Long, FE PRINCIPALS James W. Albert, PE.
Claudio Allevato, Corp. LIII Kenneth Bhaela, Ph.D.
Mark A, Bennett, RE.
Richatd 8, Boswell,.E.
Helen Chan, C.P.A John F. Chappell. FE.
i S Allen Fox, FE Andreas Katsourua Paul J. Kovach, FE.
Terry M. Lechinger Douglas L. Marriott, PhD.
Christopher Malice, Ph.D., PE.
I Charles A Milter,.E.
George Ross, Ph, D, Ten Sharckelford David A Tekamp, P.E.
Kurt DAlVndervort, Ph.D.,,E.
Kenneth R. Waeber,,E, Robert E. Wink, FE.
SENIOR ASSOCIATES/
STAFF CONSULTANTS Christopher.Alexender Glen A. Aucoin, P.E:
I Richard C. BieL, FE.
Michael J. Effenberger. PE.
Kimberly 0. Flesner, FE.
Greg Garic, FE.
David L. Garrett, Ph.D.
Robert B. Gordon, PhND., PE, SDavid P. Huey. PE, Kenneth R. Riggs, Ph.D., RE.
BobbyW tight, RPE.
SENIOR ASSOCIATES Refik Boubenider, Ph.D Donnle Cuuiglon Steven A Garcie Mark Hamilton
¶Mlllam A Miller John M. Moore Ronald A. Morrison, RE.
SThomas L Power, Ph.D.
Brian S. Royer Mahmod Samman, Ph.D., PE.
Ram6n L, Sen Pedro, PE.
Daniel A. Pills, PE.
Matthew J, Stahl. D.Eng, P.E.
I Lane E. Wilson STAFF CONSULTANTS Ray R. Ayers, Ph.D., RE J. Kirk Brownlee. PE.
Clinton H. (Clint) Britt, PE.
I Yusong Cao, Ph0D.
Joe Frey, PE.
Mike W Guillot, Ph.D., RE.
Lori C. Hesselbring, Ph.D., RE.
Daniel Krzywicki, P.E., CSP Charlie Ribardo, Jr., Ph.D.
I Jackie E. Smith, RE.
ASSOCIATES Lyle E. Breaux, RE.
P. James Buchanan Roger D. Cordes, Ph.D-I riedu Dulls, Ph.D., FE.
Kenny T Farrow, Ph.D.
Brett A Hormbefg Stuart J. Herbert, PhD-David Renzi rSeay, Ph.D Obaldugah Syed, RE.
Leo Vega Kevin V"nQ, Ph.D.
SENIOR ANALYSTS Irfen Balg, Ph.D.
Lixin Gong, Ph,D.
DilipManiar, Ph.D.
Bo Yang, Ph.D.
ANALYSTS Julian Bedoya Rhett Dotseon LNapoleon F. Douglas, Jr.
David Etwood chaelL. Ge Karen Lucio June 17, 2008 Mr. Richard Webster Legal Director Eastern Environmental Law Center 744 Broad Street, Suite 1525 Newark NJ, 07102 Tel. 973 424-1166 Fax 973 710-4653 rwebstergkinoy.rutgers.com SES Project No.: 131377
Subject:
Technical Commentary on Structural Analyses, Oyster Creek Drywell Vessel
Dear Mr. Webster:
In July 2006, you requested that Stress Engineering Services, Inc. consider several documents that you provided as well as others that were made available to us through internet link references from the U. S. Nuclear Regulatory Commission (NRC).
These documents were concerned with the condition of the Oyster Creek Nuclear Generating Station drywell shell, its structural adequacy, and with license renewal for the facility, which is owned and operated by AmerGen Energy Company, LLC (AmerGen).
Specifically, you asked Stress Engineering Services, Inc. (Stress) to comment on the appropriateness of the drywell structural analyses that was performed previously by General Electric (GE).
Since our 2006 report, the license renewal process has progressed significantly, and various organizations have provided the NRC and related entities with technical commentaries and testimony on the original GE analysis, including updated estimates of the current condition of the drywell shell.
For example, analysts at Sandia National Laboratory (Sandia) analysts have questioned GE's utilization of enhanced capacity reduction factors in their analysis. Others, such as Dr. Rudolf Hausler have questioned AmerGen's estimates of remaining thickness in what has been termed the "bathtub ring section" of the drywell shell. Combined, these questions have resulted in significant uncertainty (by some) regarding the remaining margin of safety against buckling of the lower, spherical section of the drywell shell. This uncertainty was echoed
'in an Additional Statement
. issued by Technical
- Judge, Hon. Anthony J. Baratta following a recent hearing on Citizens' challenge to the license renewal.
In his statement, Judge Baratta questioned whether AmerGen had provided reasonable assurance that the factor of safety required by the regulations will be met throughout the next period of extended operation.. In connection with this statement, Judge Baratta asked AmerGen to provide a conservative best estimate analysis of the remaining (actual) thickness of the drywell shell.
He also asked that AmerGen DESIGN
- TESTING
- ANALYSIS
Mr. Richard Webster Rutgers Environmental Law Clinic.
June 17, 2008 perform a three-dimensional (3-D) finite element analysis using modem methods and the current thickness of the drywell shell, which AmerGen agreed to perform. The analysis ordered by Judge Baratta was also to include some sensitivity analyses to determine the degree to which uncertainties in the size(s) of thinned areas affect Code margins for the drywell shell.
Both AmerGen and the NRC Staff prepared responses to the Judge's requests in which they indicate that the base case 3-D finite element analysis and the sensitivity analyses that AmerGen has already performed "matches or bounds" the scope of Judge Baratta's order. As such, you asked Stress Engineering Services, Inc. (Stress) to review the AmerGen and NRC Staff briefs and to prepare additional technical commentary on the following items:
I. You asked Stress to confirm whether Sandia's decision not to use enhanced capacity reduction factors (CRFs) was appropriate for the type of analysis they performed.
- 2. You asked Stress to amplify upon the briefs related to the reliance on Code margins to offset analytical uncertainties in the analysis.
- 3. You asked Stress to discuss the necessity of performing an uncertainty analysis whenever a best estimate analysis is used to assess structural integrity.
- 4. You asked Stress to reiterate our previous position that the best approach would be to take more measurements of the drywell's remaining thickness and current shape to improve existing estimates of the factor of safety on buckling.
Following are our responses to these requests:
Item 1 - Sandia's Decision Against Using Enhanced Capacity Reduction Factors Stress has only conducted a severely limited technical review of the Sandia analyses of the drywell shell. However, based upon our understanding of finite element analysis techniques and shell buckling, we tend to agree that Sandia's decision not to use enhanced CRFs was appropriate in this instance, provided the Sandia model included the effects of internal pressure on shell loading.
Item 2 - Reliance on Code Safety Margins Still at issue is whether the ASME Code', which establishes rules of safety relating only to pressure integrity and governing the construction2 of boilers, pressure vessels, transport tanks, and nuclear components, is the best tool available for determining the drywell's continued fitness for service.
The safety margin on buckling in the Code is based, at least in part, on knowledge of the original shell thickness and other variables to one degree of certainty or another, as embodied in the CRFs. Due to the documented external corrosion of the drywell shell as well as to the limited number of measurements of remaining thickness that have been made on the drywell shell to date, the degree of uncertainty with which the remaining thickness of the drywell shell is known ASME Boiler and Pressure Vessel Code,Section III, Nuclear Components, and Section VIII, Rules for Construction of Pressure Vessels, American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016 2 Construction, as used in the Code, is an all-inclusive term comprising materials, design, fabrication, examination, inspection, testing, certification, and pressure relief.
Stress Engineering Services, Inc..
Page 2 SES Project No.: 131377.
Mr. Richard Webster Rutgers Environmental Law Clinic June 17, 2008 has increased significantly since the drywell was first commissioned. Moreover, this degree of uncertainty may continue to increase during the next extended period of operation, either due to additional metal loss or to deformations in the bathtub region due to the combination of corrosion and operational loads.
Therefore, it is certainly arguable whether the degree of conservatism represented by the use of Code-mandated safety margins is still adequate for the drywell shell. A buckling analysis conducted in accordance with API 579/ASME FFS 13 rules along with a risk assessment such as the one described by Reinert and Apostolakis 4 may prove to be the most effective approach for revealing the actual remaining resistance to buckling of the Oyster Creek Nuclear Generating Station drywell shell.
Item 4 - Necessity of Performing Uncertainty Analyses and Required Level of Uncertainty Due to the financial and time constraints imposed on this study, Stress is unable to address whether the levels of uncertainty associated with the analyses that have been performed on the drywell shell to date meet consensus and other standards utilized in the nuclear industry.
Nevertheless, it is clear that significantdifferences exist between the safety margins predicted by Sandia and GE, and we believe these differences should be resolved. Since a major portion of the differences appear to be the result of different assumptions about the extent of drywell shell corrosion and remaining drywell shell thickness, perhaps the best way to resolve these differences is to accurately map the extent and depth of corrosion using a combination of laser, scanning and automated ultrasonic thickness measurement techniques. Stress believes that utilization of so-called "point cloud surface mapping" techniques along with ultrasonic thickness measurements that represent the remaining wall thickness of the shell will give the most accurate structural analysis results possible, with the lowest uncertainty, using current technology.
Item 5 - Reiteration and Amplification of Recommended Approach to Improve Estimates of Margin of Safety on Buckling The structural analysis results presented by AmerGen and the NRC 'as matching or bounding Judge Baratta's order utilized analytical techniques that were typical for the period of time in which the original analysis was performed. Due mainly to the limited computational power that was readily available in the early 1990s, GE utilized relatively small slices of the vessel along with idealized geometries (perfect spheres, cylinders, etc.) and other computationally efficient techniques. Calculated buckling load behaviors for the idealized slices of the drywell geometry were subsequently adjusted using assumptions or "capacity reduction factors" to account for surface irregularities, plasticity, and local buckling; and the resulting adjusted values were taken as representative of the actual buckling load. GE compared the calculated buckling loads with the imposed loads, and safety margins were determined for comparison to ASME Code minimum requirements. Thus, GE's original use of CRFs was probably equally related to the levels of uncertainty in drywell shape and remaining thickness (structural stiffness) and the need for computational efficiency. Primarily because of these computational limitations, the original finite element analysis performed by GE on the drywall vessel may not be adequate to capture its global behavior, which may be some combination of symmetrical and asymmetrical buckling.
API 579-1/ASME FFS-1, Fitness-for-Service, June 5, 2007 Ed., (API 579 Second Edition), American Petroleum Institute.
4 Reinert, Joshua M. and Apostolakis, George E., Including -model uncertainty in risk-informed decision making, Annals of Nuclear, Energy, 33, 2006, pp. 354-369.
Stress Engineering Services, Inc.
Page 3 SES Project No.: 131377
Mr. Richard Webster Rutgers Environmental Law Clinic June 17, 2008 The state-of-the-art has progressed far beyond the methods available to structural analysts in the early 1990s. Today, when structural analysts are engaged to perform fitness-for-service analyses of existing structures such as the drywell shell, it is routine to use laser devices to generate "point clouds", i.e., groups of points in space, that fully define the surfaces in question, including any irregularities. Provided one can generate sufficient data about the surfaces in question, there is no longer any need to "guess" about how these surface irregularities might affect buckling behavior.
Since 2006, Stress has performed at least five structural analyses of pressure vessels utilizing laser-generated point clouds. A brief description of the process followed by Stress follows:
Generate point cloud(s) for surface(s) of interest,
- Generate remaining thickness data,
- Convert point cloud(s) and remaining thickness data into mathematical representation(s) of actual surface shape(s),
- Utilize shape(s) to build three-dimensional model,
- Mesh the model, i. e., convert it into a form that is suitable for further processing using finite element analysis (FEA),.
" Assign corroded thicknesses and future corrosion allowance to specific points (nodes) or areas where they occur,
- Select a FEA mesh density as fine as needed to capture the stiffness that resists buckling (locally and globally, as required),
Apply combinations of simulated loads as required by applicable fitness for service (FFS) codes Increase the loads on a rational basis until the structure buckles i.e. the structure is no longer "statically admissible"
" Compare the design (or actual loads) to the largest statically admissible or buckling load to detennine the resulting margin of safety.
Elastic, or more commonly elastic-plastic, material properties are used in these analyses. The analyst calculates the buckling load and the collapse shape directly, without imposed perturbations or adjustments for anything except the measured geometry and thicknesses. Since the model already accounts for actual surface waviness, unevenness, bulges, facets, and other potentially deleterious geometric surface conditions, there is no need to resort to the use of CRFs or other approximations, either enhanced or otherwise, to determine buckling loads for vessels such as the drywall shell, as the GE analysts were apparently forced to do. Therefore, utilization of point cloud surface mapping techniques along with measurements that represent the actual.
wall thickness is still thought to give the most accurate structural analysis results possible, with the lowest uncertainty, using current technology. Three-dimensional thin shell analyses can be done today with few assumptions concerning stiffness and in a way that complies with Case N-284-1-1320.
Stress Engineering Services, Inc.
Page 4 SES ProjectNo.: 131377 Stress Engineering Services, inc.
Page 4 SES Project No.: 131377
Mr. Richard Webster Rutgers Environmental Law Clinic June 17, 2008 Respectfully Submitted:
Richard C. Biel, P. E.
Staff Consultant Stress Engineering Services, Inc.
J. Kirk Brownlee, P. E.
Staff Consultant Stress Engineering Services, Inc.
Stress Engineering Services, Inc.
Pg E
rjc o:117 Page 5 SES Project No.: 131377
UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION BEFORE THE COMMISSION In the Matter of
))
AMERGEN ENERGY COMPANY, LLC
))
(License Renewal for the Oyster Creek
)
Nuclear Generating Station)
))
Docket No. 50-0219-LR June 18, 2008 CERTIFICATE OF SERVICE I, Richard Webster, of full age, certify as follows:
I hereby certify that on June 18, 2008, I caused Citizens' Reply to NRC Staff and Amergen Responses to Commission Order dated May 28, 2008 to be served via email and U.S. Postal Service (as indicated) on the following:
Secretary of the Commission (Email and original and 2 copies via U.S Postal Service)
United States Nuclear Regulatory Commission Washington, DC 20555-0001 Attention: Rulemaking and Adjudications Staff E-mail: HEARINGDOCKET@a)NRC.GOV Office of Commission Appellate Adjudication (Email and U.S. Postal Service)
United States Nuclear Regulatory Commission Washington, DC 20555-0001 Attention: Rulemaking and Adjudications Staff E-mail: OCAAMailgnrc.gov Administrative Judge E. Roy Hawkens, Chair (Email and U.S. Postal Service)
Atomic Safety and Licensing Board Panel Mail Stop - T-3 F23 United States Nuclear Regulatory Commission Washington, DC 20555-0001 E-mail: erhgnrc.gov 1
Administrative Judge Dr. Paul B. Abramson (Email and U.S. Postal Service)
Atomic Safety and Licensing Board Panel Mail Stop - T-3 F23 United States Nuclear Regulatory Commission Washington, DC 20555-0001 E-mail: pba@nrc.gov Administrative Judge Dr. Anthony J. Baratta (Email and U.S. Postal Service)
Atomic Safety and Licensing Board Panel Mail Stop - T-3 F23 United States Nuclear Regulatory Commission Washington, DC 20555-0001 E-mail: ajb5@nrc.gov Law Clerk Emily Krause (Email and U.S. Postal Service)
Atomic Safety & Licensing Board Panel Mail Stop - T-3 F23 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 E-mail: DAW I @nrc.gov Office of General Counsel (Email and U.S. Postal Service)
United States Nuclear Regulatory Commission Washington, DC 20555-0001 E-mail: OGCMAILCENTER@aNRC.GOV James E. Adler (Email and U.S. Postal Service)
U.S. Nuclear Regulatory Commission Office of the General Counsel Mail Stop: 0-15 D21 Washington, DC 20555-0001 E-mail: jealna,'nrc.gov Mary C. Baty (Email and U.S. Postal Service)
U.S. Nuclear Regulatory Commission Office of the General Counsel Mail Stop: 0-15 D21 Washington, DC 20555-0001 E-mail: mcbl @(2nrc.gov Alex S. Polonsky, Esq. (Email and U.S. Postal Service)
Morgan, Lewis, & Bockius LLP 1111 Pennsylvania Avenue, NW Washington, DC 20004 E-mail: avolonskyvmorganlewis.com 2
Kathryn M. Sutton, Esq. (Email and U.S. Postal Service)
Morgan, Lewis, & Bockius LLP 1111 Pennsylvania Avenue, NW Washington, DC 20004 E-mail: ksutton(morganlewis.comi Donald Silverman, Esq. (Email and U.S. Postal Service)
Morgan, Lewis, & Bockius LLP 1111 Pennsylvania Avenue, NW Washington, DC 20004 E-mail: dsilvermangmorganlewis.corn J. Bradley Fewell (Email and U.S. Postal Service)
Exelon Corporation 200 Exelon Way, Suite 200 Kennett Square, PA 19348 E-mail: bradley.fewellgexceloncorp.com John Covino, DAG (Email and U.S. Postal Service)
State of New Jersey Department of Law and Public Safety Office of the Attorney General Hughes Justice Complex 25 West Market Street P.O. Box 093 Trenton, NJ 08625 E-mail: j oln.corvino gdol.lps.state.nij.us Valerie Gray (Email)
State of New Jersey Department of Law and Public Safety Office of the Attorney General Hughes Justice Complex 25 West Market Street P.O. Box 093 Trenton, NJ 08625 E-mail: valerie.gray@dol.lps. state.n n. us.
Paul Gunter (Email and U.S. Postal Service) c/o Nuclear Information and Resource Service 6930 Carroll Ave., Suite 340 Takoma Park, MD 20912-4446 E-mail: vaul(&,bevondnuclear.orz 3
Edith Gbur (Email)
Jersey Shore Nuclear Watch, Inc.
364 Costa Mesa Drive. Toms River, New Jersey 08757 E-mail: gburl@comcast.net Paula Gotsch, (Email)
GRAMMIES 205 61h Avenue Normandy Beach, New Jersey 08723 E-mail: paulagotschgverizon.net Jeff Tittel (Email)
New Jersey Sierra Club 139 West Hanover Street Trenton New Jersey 08618 E-mail: Jeff.Tittel @sierraclub. orp Peggy Sturmfels (Email)
New Jersey Environmental Federation 1002 Ocean Avenue Belmar, New Jersey 07319 E-mail: psturmfel s@cleanwater.org Michele Donato, Esq. (Email)
PO Box 145 Lavalette, NJ 08735 E-mail: mdonato 0amicheledonatoesq.com Signed:
Richard Webster Dated: June 18, 2008 4