ML073110500
| ML073110500 | |
| Person / Time | |
|---|---|
| Site: | Limerick (NPF-039) |
| Issue date: | 11/06/2007 |
| From: | NRC/NRR/ADRO/DORL/LPLI-2 |
| To: | |
| Bamford, Peter J., NRR/DORL 415-2833 | |
| Shared Package | |
| ML072760070 | List: |
| References | |
| TAC MD3710 | |
| Download: ML073110500 (9) | |
Text
(3)
Pursuant to the Act and 10 CFR Parts 30, 40 and 70, to receive, possess and use at any time any byproduct, source and special nuclear material as sealed neutron sources for reactor startup, sealed sources for reactor instrumentation and radiation monitoring equipment calibration, and as fission detectors in amounts as required; (4)
Pursuant to the Act and 10 CFR Parts 30, 40, 70, to receive, possess, and use in amounts as required any byproduct, source or special nuclear material without restriction to chemical or physical form, for sample analysis or instrument calibration or associated with radioactive apparatus or components; and (5)
Pursuant to the Act and 10 CFR Parts 30, 40 and 70, to possess, but not separate, such byproduct and special nuclear materials as may be produced by the operation of the facility, and to receive and possess, but not separate, such source, byproduct, and special nuclear materials as contained in the fuel assemblies and fuel channels from the Shoreham Nuclear Power Station.
C.
This license shall be deemed to contain and is subject to the conditions specified in the Commission's regulations set forth in 10 CFR Chapter I (except as exempted from compliance in Section 2.D. below) and is subject to all applicable provisions of the Act and to the rules, regulations, and orders of the Commission now or hereafter in effect; and is subject to the additional conditions specified or incorporated below:
(1)
Maximum Power Level Exelon Generation Company is authorized to operate the facility at reactoir core power levels not in excess of 3458 megawatts thermal (100% rated power) in accordance with the conditions specified herein and in Attachment 1 to this license. The items identified in Attachment 1 to this license shall be completed as specified. Attachment 1 is hereby incorporated into this license.
(2)
Technical Specifications The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised through Amendment No.189, are hereby incorporated into this license.
I -
Exelon Generation Company shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
Amendment No. 189
INDEX LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE REOUIREMENTS SECTION PAGE PLANT SYSTEMS (Continued) 3/4.7.2 CONTROL ROOM EMERGENCY FRESH AIR SUPPLY SYSTEM -
COMMON SYSTEM........................................................
3/4 7-6 3/4.7.3 REACTOR CORE ISOLATION COOLING SYSTEM.........................
3/4 7-9 3/4.7.4 SNUBBERS......................................................
3/4 7-11 Figure 4.7.4-1 Sample Plan 2)
For Snubber Functional Test..........................
3/4 7-16 3/4.7.5 SEALED SOURCE CONTAMINATION...................................
3/4 7-17 3/4.7.6 DELETED; Refer to note on page................................
3/4 7-19 3/4.7.7 DELETED; Refer to note on page................................
3/4 7-19 3/4.7.8 MAIN TURBINE BYPASS SYSTEM....................................
3/4 7-33 3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C.
SOURCES A.C. Sources - Operating...................................
3/4 8-1 Table 4.8.1.1.2-1 DELETED..............................
3/4 8-8 A.C. Sources - Shutdown....................................
3/4 8-9 3/4.8.2 D.C.
SOURCES D.C. Sources - Operating...................................
3/4 8-10 LIMERICK - UNIT I xiv Amendment No.
-34, 4-,
5, 4-g4,189
3/4.8 ELECTRTCAL POWER SYSTFMS
-3/4.8.1 A.C.
SOURCES A.C.
SOURCES - OPERATING LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:
- a.
Two physically independent circuits between the offsite transmission network and the onsite Class 1E distribution system, and
- b.
Four separate and independent diesel generators, each with:
- 1.
A separate day tank containing a minimum of 200 gallons of fuel,
- 2.
A separate fuel storage system containing a minimum of 33,500 gallons of fuel, and
- 3.
A separate fuel transfer pump.
APPLICABILITY:
OPERATIONALCONDITIONS 1, 2, and 3.
ACTION:
- a.
With one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C.
sources by performing Surveillance Requirement 4.8.1.1.1.a within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and at least once per 7 days thereafter.
If the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining operable diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4 for one diesel generator at a time, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, unless the absence of any potential common-mode failure for the remaining diesel generators is determined.
Restore the inoperable diesel generator to OPERABLE status within 30 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
See also ACTION e.
- b.
With two diesel generators of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C.
sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.
If either of the diesel generators became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4 for one diesel generator at a time, within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the absence of any potential common-mode failure for the remaining diesel generators is determined.
Restore at least one of the inoperable diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
See also ACTION e.
LIMERICK - UNIT 1 3/4 8-1 Amendment No.
3-2, 44G, 189
3/4.8 ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION (Continued)
ACTION:
(Continued)
- c.
With three diesel generators of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and perform Surveillance Requirement 4.8.1..1.2.a.4 for the remaining diesel generator, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
Restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
See also ACTION e.
- d.
With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.
If the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4 for one diesel generator at a time, within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the absence of any potential common-mode failure for the remaining diesel generators is determined.
Restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial lossor be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
See also ACTION e.
LIMERICK - UNIT 1 3/4 8-1a Amendment No.
42, 4-, 189
FIFCTRTCAI POWER SYSTEMS LIMITING CONDITION FOR OPERATION (Continued)
ACTION:
(Continued)
- f.
With one offsite circuit of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.
Restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
- g.
With two of the above required offsite circuits inoperable, restore at least one of the inoperable offsite circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
With only one offsite circuit restored to OPERABLE status, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
- h. With one offsite circuit and two diesel generators of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance, Requirements 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.
If either of the diesel generators became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4 for one diesel generator at a time, within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the absence of any potential common-mode failure for the remaining diesel generators is determined.
Restore at least one of the above required inoperable A.C. sources to OPERABLE status withi~n 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in a at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
Restore at least two offsite circuits and at least three of the above required diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
See also ACTION e.
- i.
Specification 3.0.4.b is not applicable to diesel generators.
LIMERICK - UNIT 1 3/4 8-2a Amendment No.
4-,
4-64,189
F1 FflTRTC.AI PnWFR SYSTFMSý
.SURVEILLANCE REOUIREMENTS 4.8.1.1.1 Each of the above required independent circuits between the offsite transmission network and the onsite Class 1E distribution system shall be:
- a.
Determined OPERABLE in accordance with the Surveillance Frequency Control Program by verifying correct breaker alignments and indicated power availability, and.
- b.
Demonstrated OPERABLE in accordance with the Surveillance Frequency Control Program by transferring, manually and automatically, unit power supply from the normal circuit to the alternate circuit.
4.8.1.1.2 Each of the above required diesel generators shall be demonstrated OPERABLE:
- a.
In accordance with the Surveillance Frequency Control Program on a STAGGERED TEST BASIS by:
- 1.
Verifying the fuel level in the day fuel tank.
- 2.
Verifying the fuel level in the fuel storage tank.
- 3.
Verifying the fuel transfer pump starts and transfers fuel from the storage system to the day fuel tank.
- 4.
Verify that the diesel can start* and gradually accelerate to synchronous speed with generator voltage and frequency at 4280 +/- 120 volts and 60 +/- 1.2 HZ.
- 5.
Verify diesel is synchronized, gradually loaded* to an indicated 2700-2800 KW** and operates with this load for at least 60 minutes.
- 6.
Verifying the diesel generator is aligned to provide standby power to the associated emergency busses.
- 7.
Verifying the pressure in all diesel generator air start receivers to be greater than or equal to 225 psig.
- This test shall be conducted in accordance with the manufacturer's recommendations regarding engine pre-lube and.warmup procedures, and as applicable regarding loading and shutdown recommendations.
- This band is meant as guidance to avoid routine overloading of the engine.
Loads in excess of this band for special testing under direct monitoring by the manufacturer or momentary variations due to changing bus loads shall not invalidate the test.
LIMERICK - UNIT I 3/4 8-3 Amendment No. *,-7,4-O,48.,189
ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)
- b. By removing accumulated water:
- 1) From the day tank in accordance with the Surveillance Frequency Control Program and after each occasion when the diesel is operated for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, and
- 2)
From the storage tank in accordance with the Surveillance Frequency Control Program.
- c.
By sampling new fuel oil in accordance with ASTM D4057-81 prior to addition to the storage tanks and:
- 1) By verifying in accordance with the tests specified in ASTM D975-81 prior to addition to the storage tanks that the sample has:
a)
An API Gravity of within 0.3 degrees at 60'F or a specific gravity of within 0.0016 at 60/60 0 F, when compared to the supplier's certificate or an absolute specific gravity at 60/60'F of greater than or equal to 0.83 but less than or equal to 0.89 or an API gravity at 60'F of greater than or equal to 27 degrees but less than or equal to 39 degrees.
b)
A kinematic viscosity at 40 0 C of greater than or equal to 1.9 centistokes, but less, than or equal to 4.1 centistokes, if gravity was not determined by comparison with the supplier's certification.
c)
A flash point equal to or greater than 125°F, and d)
A clear and bright appearance with proper color when tested in accordance with ASTM D4176-82.
- 2) By verifyihg within 31 days of obtaining the sample that the other properties specified in Table 1 of ASTM D975-81 are met when tested in accordance with ASTM D975-81 except that the analysis for sulfur may be performed in accordance with ASTM D1552-79 or ASTM D2622-82.
- d.
In accordance with the Surveillance Frequency Control Program by obtaining a sample of fuel oil from the storage tanks in accordance with ASTM D2276-78, and verifying that total particulate contamination is less than 10 mg/liter when checked in accordance with ASTM D2276-78, Method A, except that the filters specified in ASTM D2276-78, Sections 5.1.6 and 5.1.7, may have a nominal pore size of up to three (3) microns.
- e.
In accordance with the Surveillance Frequency Control Program by:
- 1.
Deleted
- 2.
Verifying each diesel generator's capability to reject a load of greater than or equal to that of its single largest post-accident load, and:
I a)
Following load rejection, the frequency is
- 66.5 Hz; b) Within 1.8 seconds following the load rejection, voltage is 4285
+/- 420 volts, and frequency is 60 +/- 1.2 Hz; and c) After steady-state conditions are reached, voltage is maintained at 4280 +/- 120 volts.
LIMERICK UNIT 1 3/4 8-4 Amendment No. 21-,4,4-44,-1-24-,
4,4--3,4-,8, 189
-L-CT-,CA T(-
E SY!STEMS1F
-A SURVEILLANCE REOUIREMENTS (Continued)
- h.
In accordance with the Surveillance Frequency Control Program the diesel generator shall be started* and verified to accelerate to synchronous speed in less than or equal to 10 seconds.
The generator voltage and frequency shall reach 4280 +/- 120 volts and 60 +/- 1.2 Hz within 10 seconds after the start signal.
The diesel generator shall be started for this test by using one of the following signals:
a)
Manual***
b)
Simulated loss-of-offsite power by itself.
c)
Simulated loss-of-offsite power in conjunction with an ECCS actuation test signal.
d)
An ECCS actuation test signal by itself.
The generator shall be manually synchronized to its appropriate emergency bus, loaded to an indicated 2700-2800 KW**
and operate for at least 60 minutes.
This test, if it is perfori,,ed so iL coincides with the testing required by Surveillance Requirement 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5, may also serve to concurrently meet those requirements as well.
4.8.1.1.3 Deleted
- This test shall be conducted in accordance with the manufacturer's J.mm) i i..
1/4 prellube and.,rmup pr e,,
and as applicable regarding loading and shutdown recommendations.
- This band is meant as guidance to avoid routine overloading of the engine.
Loads in excess of this band for special testingkunder dire'ct monitoring by the manufacturer or momentary variations due to changing bus loads shall not invalidate the test.
- If diesel generator started manually from the control room, 10 seconds after the automatic prelube period.
`MýýDTýV - INTT I 3/4 8-7a Amendment No.
-a,
, go,189
INFORMATION ON THIS PAGE HAS BEEN DELETED LIMERICK - UNIT 1 3/4 8-8 Amendment No.
-32,, 189