Technical Specifications, Issuance of Amendment Replacement of Containment Sump Buffer
ML072760004
Person / Time
Site: Palisades Entergy icon.png
Issue date: 10/02/2007
From:
NRC/NRR/ADRO/DORL/LPLIII-1
To:
Chawla M, NRR/DORL/LPL3-1, 301-415-8371
Shared Package
ML072530656 List:
References
TAC MD5893
Download: ML072760004 (2)


Text

TABLE OF CONTENTS TECHNICAL SPECIFICATIONS 3.4 PRIMARY COOLANT SYSTEM (PCS) 3.4.1 PCS Pressure, Temperature, and Flow Departure from Nucleate Boiling (DNB) Limits 3.4.2 PCS Minimum Temperature for Criticality 3.4.3 PCS Pressure and Temperature (P/T) Limits 3.4.4 PCS Loops - MODES 1 and 2 3.4.5 PCS Loops - MODE 3 3.4.6 PCS Loops - MODE 4 3.4.7 PCS Loops - MODE 5, Loops Filled 3.4.8 PCS Loops - MODE 5, Loops Not Filled 3.4.9 Pressurizer 3.4.10 Pressurizer Safety Valves 3.4.11 Pressurizer Power Operated Relief Valves (PORVs) 3.4.12 Low Temperature Overpressure Protection (LTOP) System 3.4.13 PCS Operational LEAKAGE 3.4.14 PCS Pressure Isolation Valve (PIV) Leakage 3.4.15 PCS Leakage Detection Instrumentation 3.4.16 PCS Specific Activity 3.4.17 Steam Generator (SG) Tube Integrity 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 3.5.1 Safety Injection Tanks (SITs) 3.5.2 ECCS - Operating 3.5.3 ECCS - Shutdown 3.5.4 Safety Injection Refueling Water Tank (SIRWT) 3.5.5 Containment Sump Buffering Agent and Weight Requirements 3.6 CONTAINMENT SYSTEMS 3.6.1 Containment 3.6.2 Containment Air Locks 3.6.3 Containment Isolation Valves 3.6.4 Containment Pressure 3.6.5 Containment Air Temperature 3.6.6 Containment Cooling Systems 3.7 PLANT SYSTEMS 3.7.1 Main Steam Safety Valves (MSSVs) 3.7.2 Main Steam Isolation Valves (MSIVs) 3.7.3 Main Feedwater Regulating Valves (MFRVs) and MFRV Bypass Valves 3.7.4 Atmospheric Dump Valves (ADVs) 3.7.5 Auxiliary Feedwater (AFW) System 3.7.6 Condensate Storage and Supply 3.7.7 Component Cooling Water (CCW) System 3.7.8 Service Water System (SWS) 3.7.9 Ultimate Heat Sink (UHS) 3.7.10 Control Room Ventilation (CRV) Filtration 3.7.11 Control Room Ventilation (CRV) Cooling 3.7.12 Fuel Handling Area Ventilation System 3.7.13 Engineered Safeguards Room Ventilation (ESRV) Dampers 3.7.14 Spent Fuel Pool (SFP) Water Level 3.7.15 Spent Fuel Pool (SFP) Boron Concentration 3.7.16 Spent Fuel Assembly Storage 3.7.17 Secondary Specific Activity Palisades Nuclear Plant ii Amendment No. 489, 224, 223, 227

STB 3.5.5 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 3.5.5 Containment Sump Buffering Agent and Weight Requirements LCO 3.5.5 Buffer baskets shall contain > 8,186 lbs and 510,553 lbs of Sodium Tetraborate Decahydrate (STB) Na2 B4 O. 10H 20.

APPLICABILITY: MODES 1, 2, and 3.

ACTIONS COMPLETION CONDITION REQUIRED ACTION TIME A. STB not within limits. A.1 Restore STB to within limits. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> B. Required Action and B.1 Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met. AND B.2 Be in MODE 4. 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.5.5.1 Verify the STB baskets contain _>8,186 lbs and 18 months

<10,553 lbs of equivalent weight sodium tetraborate decahydrate.

SIR 3.5.5.2 Verify that a sample from the STB baskets provides -18 months

- adequate- pH adjustment of_ borated water.. . .....

Palisades Nuclear Plant 3.5.5-1 Amendment No. 44&, 227