Attachment 3 to PLA-6124 EC-RADN-1128, Revision I

NUCLEAR ENGINEERING CALCULATION COVER SHEET NEPM-QA-0221-1

1. Page 1 of 86 Total Pages 88

-2. TYPE:

CALC J3. NUMBER:

EC-RADN-1128

-4. REVISION:

  • 5 UNIT 3
  • -6 QUALITY CLASS:

Q

7. DESCRIPTION

Steam Line Break Accident CRHE and Off Site Doses - AST 1

8. SUPERSEDED BY:
9. Alternate Number:
10. Cycle:.
11. Computer Code/Model used:

RADTRAD V3.03

12. Discipline:

R

-13. Are any results of this calculation described in the Licensing Documents?

Z

  • Yes, Refer to NDAP-QA-0730 and NDAP-QA-0731 El No

,14.

Is this calculation changing any method of evaluation described in the FSAR and using the results to support or change the FSAR? (Refer to PPL Resource Manual for Definition of FSAR)

Yes, 50.59 screen or evaluation required.

[] No

'15.

Is this calculation Prepared by an External Organization?

EYes IlNo EG771 Qualifications may not be required for individuals from external orgnizations (see Section 7.4.3).

.- 16. Prepared by:

, 17. Reviewed by:

I p18. Verified by:

,-19. Approved by:

,-20. Accepted by:

K.

Weise)

Print Name(EG 771 Qualification Requireal,

Signature Date P. L. Bunker Print Name(EG771 Qualification Required)

Signature Date P. L. Bunker Print Name(EG771 Qualification Required)

Signature Date M. M. Waseluse/-

e dperNEPM,---02414, *a*n Sigte Print Name(Qualified per NEPM-QA-0241 and v.*2 Signature comply with Section 7.8 of NEPM-QA-0221)

Date Print Name(EG771 Qualification Required) and comely with Section 7.9 of NEPM-OA -0221 Signature 0

Date TO BE COMPLETED BY DCS DCS SIGNATURE/DATE ADD A NEW COVER PAGE FOR EACH REVISION FORM NEPM-QA-0221-1, Revision 8, Page 1 of 1, ELECTRONIC FORM

  • Verified Fields

- REQUIRED FIELDS

Page la CALCULATION REVISION DESCRIPTION SHEET NEPM-QA-0221-2 REVISION NO:

1 CALCULATION NUMBER:

EC-RADN-1128 SFULL REVISION III SUPERSEDED FII PAGE FOR PAGE E--

VOIDED A

R R

Revised d

P m

Description Pages d

1 v

of Revision on the Listed Pages All D

Calculation reprinted in entirety.

la, lb E-D Air intake location on reactor building at Elev. 810'-3".

1,2, 16, 17, 18, 20, Tables 1, 6, 7, &

E E

0 Air intake location on reactor building at Elev. 810'-3" with 8

corresponding changes in dispersion characteristics and CRHE doses.

11, Table 3 D

0 E

Minor editorial Attachments 5 & 6 E

F 1 RADTRAD output for CRHE doses F-1 l

Eli El l

Eli El W

El W

ElD

_-1 IEl1 EI E-I I-!

E-I

[El lI El E

LIDI DD] r]

DDD3 FORM NEPM-OA-0221-2. Revision 5, Page I of 1 ELECTRONIC FORM

Page lb TECHNICAL CHANGE

SUMMARY

PAGE NEPM-QA-0221-5 Calculation Number:

EC-RADN-1128 Revision No. 1 This form shall be used to (1) record the Technical Scope of the revision and (2) record the scope of verification if the calculation was verified. It should not be more than one page. Its purpose is to provide summary information to the reviewer, verifier, approver, and acceptor about the technical purpose of the change. For non-technical revisions, state the purpose or reason for the revision.

Scope of Revision: Revision 1 re-calculates the CRHE accident doses for the air intake on the reactor building south wall at Elev 810'-3" near the intersection of column lines U and 37.4. The calculation does not credit an elevation difference between the blowout panel release and air intake locations. With zero difference in elevations, the calculated exposures at the intake are maximized for the steam line break "puff' release. The zero elevation difference is consistent with Regulatory Guide 1.194 guidance and supports the SSES response to AST RAI #3, dated October 18, 2006.

Scope of Verification (If verification applies): Verify changes in design input, assumptions, methodology, arithmetic, computer code input/output, results and conclusions.

NEPM-QA-0221-5, Revision 0 Page 1 of 1 ELECTRONIC FORM

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

2 Checked By P. L. Bunker TABLE OF CONTENTS 1.0 PU R P O SE...................................................................................................

.......................................... 3

2.0 CONCLUSION

S AND RECOMMENDATIONS............................................................................

3 3.0 INPUT and ASSUMPTIONS.......................................................................................................

4 3.1 Reactor Core and Coolant Source Parameters....................................................................................

4 3.2 Accident Scenario Parameters.........................................................................................................

5 3.3 Control Room Habitability Design Parameters....................................................

.................................. 6 3.4 D ose P aram eters.......................................................................................................................................

6 3.5 D ispersion Param eters..................................................................

6 4.0 METHOD...................................................................................................

....... 8 4.1 N oble G as A ctivity..................................................................................................................................

8 4.2 Iodine Activity in Reactor Coolant..................................................................................................

9 4.3 Iodine Activity Released in Steam Line Break..............................................................................

11 4.4 Effective Relative Concentration at the CRHE Air Intake...............................................................

13 4.5 Puff Expansion and Initial Standard Deviation...............................................................................

15 4.6 Calculation of CRHE Relative Concentration x/Q..........................

15 4.7 Radiological and Transport Model...................................................................................................

17 5.0 R E SU L T S............................................................................................................................................

18 6.0 R E FE R EN C E S............................................................................................................

....................... 19 RADTRAD Control File Release Fraction and Timing SLB.rft............................................

21 RADTRAD Control File Dose Conversion File SLB_Phase 2.inp......................................

23 RADTRAD Control File Inventory File SLB_4mc.nif........................................................

27 RADTRAD Control File Inventory File SLBpt2mc.nif....................................................

31 RADTRAD Output TBMST_500cfm_4mcDE_1 128.out..................................................

35 RADTRAD Output TBMST_500cfin2ptmcDE_1 128.out...............................................

61

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

3 Checked By P. L. Bunker STEAM LINE BREAK ACCIDENT CRHE and OFFSITE DOSES - AST 1.0 PURPOSE This calculation documents the design basis evaluation of the Control Room Habitability Envelope (CRHE) and offsite radiological doses at the exclusion area boundary and the low population zone following a postulated steam line break using the Alternate Source Term (AST) methodology described in USNRC Regulatory Guide 1.183 (Reference 1).

The break is assumed to occur in the main steam tunnel and be released to the environment via a turbine or reactor building steam tunnel blowout panel. Reactor water and steam iodine specific activities are specified using dose equivalent 1-131 (DE 1-131) based on the TEDE dose conversion. The doses are calculated using the RADTRAD computer code (Reference 7).

2.0 CONCLUSION

S AND RECOMMENDATIONS The offsite dose acceptance criterion for the steam line break is provided in Regulatory Guide 1.183, Table 6.

The CRHE dose acceptance criterion for the main steam line accident is provided in 10CFR50.67, Accident Source Term, subsection 10CRF50.67(b)(2)(iii).

The offsite dose acceptance criteria at the exclusion area boundary (EAB) and the low population zone (LPZ) are 25 Rem TEDE for a steam line break with fuel damage or pre-accident iodine spike and 2.5 Rem TEDE for a steam line break with maximum equilibrium iodine activity. The CRHE dose acceptance criterion is 5 Rem TEDE.

The reported steam line break doses using AST methodology are:

Dose Summary for Steam Line Break Accident Acceptance Criterion - Offsite EAB LPZ Acceptance Criterion - CRHE CRHE Pre-accident Spike 4 jtCi/gm DE 1-131, TEDE, Rem 25 2.0 0.12 Maximum Equilibrium Iodine Activity 0.2 jtCi/gm DE 1-131, TEDE, Rem 2.5 0.10 0.006 5.0 0.93

'5.0 0.05

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

4 Checked By P. L. Bunker 3.0 INPUT and ASSUMPTIONS

.The input data and assumptions used in this analysis are summarized in Table 1.

3.1 Reactor Core and Coolant Source Parameters

1. Core thermal power used for this accident is 4032 MWt (Reference 12). The thermal power is taken as 102% of the 3952 MWt uprate power. The core thermal power is not directly used in this analysis since there is no fuel damage postulated for this event. The core power is used to confirm that the reactor coolant and steam activity concentrations are conservative for extended power uprate conditions.
2. The design basis noble gas source term is 100,000 pCi/s after 30 minutes decay and is shown in Table 2. Short lived isotopes (half lives less than one minute) are excluded due to radiological decay. The concentrations shown have been determined to be conservative for extended power uprate with and without hydrogen water chemistry (Reference 14, Appendix E).
3. A total off gas release rate of 403,000 pCi/sec after 30 minutes delay is used for the noble gas source with a core power of 4032 MWt. The individual noble gas concentrations are then scaled from the 100,000 pCi/sec rate data in Table 2 by applying a factor of 4.03.

The scaling of the 100,000 pCi/sec is similar to the approach in Regulatory Guide 1.98 for analyzing postulated failures in off gas systems. Regulatory Guide 1.98 assumes a release rate of 100 pCi/MWt after 30 minute delay at the steam jet air ejector. For a given fuel design basis defect fraction, the rate of fission product releases through the defects is proportional to the number of fissions or core power.

The observed off gas rate is proportional to the fission product release rate (or alternatively core power) assuming no change in cladding defects. Hence, the observed off gas rate may be directly scaled from one power level to another as prescribed in Regulatory Guide 1.98. The same approach is used for setting SSES's main condenser offgas rate in Improved Technical Specification 3.5.7 (Reference 19).

4. The main steam flow rate is 1.418E+07 Ibm/h, which corresponds to the flow used to establish the original GE design basis reactor water and steam activities (Reference 14).

Reference 14 shows that the activity concentrations at extended power uprate with the anticipated steam flow (1.654E+07 Ibm/h) are bounded by the original design basis concentrations.

Because the original activity concentrations have been retained for the SSES design basis (Reference 14), this analysis uses the original steam flow rate of 1.418E+07 Ibm/h to determine the noble gas activities released to the environs.

The approach is consistent with the design basis and covers existing and power uprate steam flows.

5. The design basis iodine specific activities are shown in Table 3 for the reactor water and main steam. The water concentrations are maximized by the use of a 2% steam carryover (corresponding to normal water chemistry operation) while the steam concentrations are maximized using an 8% steam carryover (corresponding to operation with hydrogen water

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

5 Checked By P.L. Bunker chemistry).

This approach bounds normal and hydrogen water chemistry operation (Reference 14).

3.2 Accident Scenario Parameters

1. No fuel damage is postulated for the main steam line break. Therefore, the released activity is based on the maximum coolant activity allowed by Improved Technical Specification 3.4.7 (Reference 18). Two activity cases are analyzed consistent with Regulatory Guide 1.183, Appendix D guidance:
1. Iodine activities based on a pre-accident spike with a concentration of 4 pCi/g DE 1-131.
2. Iodine activities based on the maximum equilibrium value for full power operation with a concentration of 0.2 pCi/g DE 1-131.
2. For the design basis accident, the reactor is assumed to be in hot standby prior to the break (Reference 13, Task A.28). This condition maximizes the liquid mass release and hence activity releases.
3. The mass releases for the design basis (hot standby) cases are (Reference 13, Table A.28-3):

Liquid release 84,840 Ibm Steam release from flashed liquid 6,480 Ibm Steam from steam dome 6,650 Ibm From the above, the total amount of coolant as water exiting the vessel is 91,320 Ibm. The total mass release is 97,970 Ibm.

4. The above mass releases are increased by 20% to provide additional margin. Evaluations of steam line break masses for other extended power uprate plants determined that the increases in mass releases were small compared to the pre-uprate main steam line break masses while at power.
5. Main steam line valves are assumed to start to close at 0.5 seconds on a high flow signal and are fully closed at 5.5 seconds (Reference 20). The closure time ensures that the steam, water and, radioactivity releases to the environs are over a relatively short duration.
6. All of the radioactivity in the liquid and steam is assumed to be released instantaneously as a ground level release consistent with Regulatory Guide 1.183, Appendix D. No hold-up or dilution is assumed in the reactor or turbine building steam tunnels.
7. The instantaneous release of all the activity within a short period (less than one minute) is modeled as a puff release consistent with the guidance in Regulatory Guide 1.194. This approach is reasonable since the MSIVs rapidly isolate the break and all the activity is immediately assumed to be released into the environment.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE CaIc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

6 Checked By P. L. Bunker

8. The iodine species released from the main steam line are 95% Csl as aerosol, 4.85% as elemental iodine, and 0.15% as organic iodine in accordance with Regulatory Guide 1.183, Appendix D.

3.3 Control Room Habitability Design Parameters

1. No credit is given for filtration of radioiodine in the CRHE. The control room emergency outside air filtration system (CREOAS) does not automatically actuate for this accident.

Manual operation is not credited because the accident occurs rapidly with the release moving away from the control room within minutes.

2. The CRHE's nominal air intake flow rate is 5810 cfm. This analysis uses 6391 cfm, the maximum value for which the system is in compliance with Technical Specification 5.5.7 (Reference 17). The use of the maximum flow rate results in the greatest uptake of activity during the accident.
3. Unfiltered inleakage is 500 cfm. This amount bounds the leakages and error bands from the December 2004 CRHE tracer gas tests.

Unfiltered ingress/egress leakage through doors of 10 cfm is assumed based on NUREG-0800, chapter 6.4 (Reference 10).

4. The control structure habitability envelope volume is 518,000 cu ft (Reference 16).

The control room with volume of 110,000 ft3 is located within this volume. The CRHE and control room are served by CREOAS.

3.4 Dose Parameters

1. CRHE and offsite breathing rates are 3.5E-04 m3/s.

Both rates are consistent with Regulatory Guide 1.183, section 4.1.

2. Control room occupancy is based on a maximum exposed individual.

The individual is assumed present in the control room 100% of the time during this short duration accident.

The occupancy is consistent with Regulatory Guide 1.183, section 4.2, and NUREG-0800, chapter 6.4.

3. Doses are calculated in terms of the TEDE as required by Regulatory Guide 1.183, section 4.1. The dose conversion factors for the CEDE are based on Federal Guidance Report 11 and the EDE is based on Federal Guidance Report 12. The dose conversion factors appear in Reference 7, Table 11.4.3.3-2. EDEs for additional nuclides were added and included Kr-83m, Kr-85m, Kr-85, Xe-131m, Xe-133m, Xe-135m and Xe-138.

The dose conversion factors were compiled into a RADTRAD.inp file for SSES's AST analyses and are included as Attachment 2.

3.5 Dispersion Parameters

1. Offsite x/Q values are 8.3E-04 s/m3 (0 - 2 hr) for the EAB and 4.9E-05 s/m3 <0 - 8 hr) for the LPZ (Reference 15, Tables 2.3-92 and 2.3-105).
2. The CRHE x/Q is based on Regulatory Guide 1.194 methods for instantaneous releases with duration less than one minute.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

7 Checked By P. L. Bunker Table I Steam Line Break Analysis Input and Assumptions Summary Description Core Thermal Power Level Noble Gas Design Source Term Design Offgas Release Rate Design Reactor Water and Steam Iodine Specific Activities Design Main Steam Flow Iodine Carryover Fraction Pre-accident Iodine Spike Maximum Equilibrium Iodine Activity Radioiodine Chemical Species Liquid Release Steam Release from Flashed Liquid Steam Release from the Steam Dome MSIV Closure Time Failed Fuel Resulting From MSLB Holdup in TB CRHE Volume CRHE Isolation and CREOAS Start-up CRHE Air Intake Flow CRHE Unfiltered Inleakage CRHE Ingress/egress Flow Operator and Offsite Breathing Rates Operator Occupancy Factors CRHE x/Q Offsite x/Q Value 4032 MWt Table 2 100,000 gtCi/s after 30 minutes 403,000 gCi/s after 30 minutes Table 3 1,418,000 Ibm/h 8%

4.0 pCi/gm DE 1-131 0.2 gtCi/gm DE 1-131 95% CsI, 4.85% Elemental 12, 0.15% Organic I 84,840 Ibm 6,480 Ibm 6,650 Ibm 5.5 seconds 0

None 518,000 ft3 None 6391 cfm (max) 500 cfm 10 cfm 3.5E-04 m3/sec 1.0, 24 hrs 0.6, 1-4 days 0.4, 4-30 days Puff:

6.3E-04 s/m3 EAB:

8.3E-04 s/m 3, 0-2 hr LPZ:

4.9E-05 s/m 3, 0-8 hr Source Reference 12 Reference 6, Table 11.1-1 See section 3.1, item 3 Reference 6, Table 11.1-2 Reference 6, Appendx B Reference 6 Reference 18; RG 1.183 Reference 18, RG1.183 RG 1.183 Reference 13, Task A.28 Reference 13, Task A.28 Reference 13, Task A.28 See section 3.2, item 5 See section 3.2, item 1 RG 1.183 Reference 16 See section 3.3, item 1 Reference 17 See section 3.3, item 3 Reference 6 RG 1.183 Reference 6, RG 1.183 Table 7 Reference 15

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE CaIc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

8 Checked By P. L. Bunker 4.0 METHOD The offsite and CRHE doses are calculated using the RADTRAD computer code with the input and assumptions listed in Table 1. The activity released to the environment is provided on Tables 3 and 5. The resulting offsite and CRHE doses are provided in Attachments 5 and 6 for the cases of 4 pCi/gm DE 1-131 and 0.2 pCi/gm DE 1-131, respectively.

A maximum unidentified unfiltered inleakage of 500 cfm plus 10 cfm ingress/egress unfiltered inleakage is used in the analysis.

4.1 Noble Gas Activity The noble gas activity released to the environment is based on the pre-accident noble gas off gas release rate of 403,000 pCi/sec after 30 minutes delay. The steam's noble gas specific activity (pCi/g) is determined from the off-gas activity source rate accounting for the 30 minute delay.

The specific activities are then used to determine the noble gas release to the environment. The noble gas activity in the reactor water is conservatively taken the same as the steam activity since some water exiting the break will flash to steam. The activities Ai for the noble gases are given by:

Ai = 4.03 C (M*s+

Mw) exp (Ai *1800 s)

Fs where -

C = noble gas nuclide source rate, pCi/s Mr= mass of steam released, Ibm Mw = mass of liquid released, Ibm Fs = steam flow rate used to establish noble gas equilibrium concentration, Ibm/h A1 = decay rate for noble gas nuclide i, s-1 4.03 = multiplier accounting for the maximum noble gas source rate of 362,000 pCi/s relative to the design basis rate of 100,000 pCi/s used to specify the noble gas source rates.

The calculated activities Ai available for release during the accident are shown in Table 2.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

9 Checked By P. L. Bunker Table 2 Noble Gas Activity Released from MSLB Steam mass (dome) M,, Ibm Liquid mass M,, Ibm Steam flow rate Fs, Ibm/h 30 minute decay, s Conversion - s-Ci/hr-uCi 403,000 uCi/s rate factor Isotope Kr-83m Kr-85m Kr-85 Kr-87 Kr-88 Kr-89 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Xe-137 Xe-138 Half Life, sec 6.840E+03 1.570E+04 3.383E+08 4.680E+03 9.972E+03 1.896E+02 1.036E+06 1.987E+05 4:553E+05 9.360E+02 3.287E+04 2.298E+02 8.478E+02 7980 109584 1.42E+07 1800 3.60E-03 4.03 Source Rate, Ci

@T = 30min uCi/sec 2.90E+03 5.60E+03 2.OOE+01 1.50E+04 1.80E+04 1.80E+02 1.50E+01 2.80E+02 8.20E+03 6.90E+03 2.20E+04 6.70E+02

2. 1OE+04 Activity Release Ai,

. Ci 4.19E-01 7.29E-01 2.4 1E-03 2.36E+00 2.45E+00 1.56E+01 1.81E-03 3.39E-02 9.89E-01

3. *5E+00 2.75E+00 1.84E+01 1.1 OE+0 1 Notes:
1. GE "1971" design activity rates for Reference 14, Table 11.1-1.

100,000 uCi/s source rate from

2. Noble gas activties are based on 403,000 uCi/s measured at 30 minutes.
3. Activity releases are immediate with no hold up in the core or main steam system.

4.2 Iodine Activity in Reactor Coolant The design basis equilibrium halogen activity concentrations in the reactor water and main steam are shown in Table 3.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

10 Checked By P. L. Bunker Table 3 Iodine Specific Activities Isotope 1-131 1-132 1-133 1-134 1-135 Reactor Water Specific Activity uCi/gm 1.30E-02 1.20E-0 1 8.90E-02 2.40E-01 1.30E-01 Reactor Steam Specific Activity uCi/gm 3.40E-04 3.90E-03 2.40E-03 9.70E-03 3.70E-03 Notes:

1. Reference 14, Table 11. 1-2
2. Values bound normal and hydrogen water chemistry operation. See Input 3. 1, Item #5.

The iodine activity in the reactor coolant is based on the maximum DE 1-131 activity permitted by the technical specifications. Concentration limits (TSiim) of 0.2 pCi/g and 4.0 pCi/g DE 1-131 are considered.

The specific activities CRc-i of DE 1-131 in the reactor coolant are given by:

CRc-i = TSiim

  • CDB-i
  • DCFI-131 I (CDB-i
  • DCFi) where -

TSijm = the technical specification limiting concentrations 0.2 pCi/g and 4.0 pCi/g DE 1-131 CDB-i = design basis reactor coolant iodine specific activities in Table 3 DCFi = total effective dose equivalent (TEDE) dose conversion factors for iodine isotopes.

The DCFj are derived from the CEDE (from FGR 11, Reference 8) and EDE (from FGR 12, Reference 9) dose conversion factors. A breathing rate of 3.5E-04 m3/s (Input 3.4, item #1),

applicable to control room personnel and workers, is used with the CEDE. The TEDE's DCFj for the iodine isotopes are given by:

DCFi = DCFcEDE,i

  • BR + DCF.EDE, i

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

11 Checked By P. L. Bunker Observe that the DCFO are given on a per Bq basis whereas the reactor water and steam concentrations are specified using pCi. No unit conversions are needed since the DCFj are used only as weighting factors, which dimensionally cancel out in the normalization process.

The calculated DCFj and specific activities for the reactor coolant are shown in Table 4:

Table 4 Reactor Water Iodine Specific Activities at Technical Specification Limits DE 1-131 Limit TSlim, uCi/g DE 1-131 Limit TSlim, uCi/g Breathing Rate, m3/s 4

0.2 3.5E-04 Isotope 1-131 1-132 1-133 1-134 1-135 Design Basis Reactor Water Concentration CD_i (uCi/gm) 1.30E-02 1.20E-01 8.90E-02 2.40E-01 1.30E-01 (Sv/Bq) 8.89E-09 1.03E-10 1.58E-09 3.55E-1 1 3.32E-10 CEDE EDE Dose Conversion Dose Conversion (Sv/Bq-s/m 3) 1.82E-14 1.12E-13 2.94E-14 1.30E-13 7.98E-14 TEDE Dose Conversion DCFi (Sv/Bq-s/m 3) 3.13E-12 1.48E-13 5.82E-13 1.42E-13 1.96E-13 Concentration

@ 4 uCi/gm DE 1-131 Ci (uCi/gm) 0.96 8.84 6.56 17.68 9.58 Concentration

@ 0.2 uCi/gm DE 1-131 Ci (uCi/gm) 0.048 0.442 0.328 0.884 0.479 Notes:

1. Design reactor water specific activities from Table 3.
2. CEDE h Effective from FGR 11 and EDE h E from FGR 12.

4.3 Iodine Activity Released in Steam Line Break The iodine releases are based on the reactor coolant activity, carryover to steam, and the coolant and steam masses released from the break. Coolant concentrations are set by the allowable activity limits in accordance with the technical specifications.

The iodine activity Ai released from the steam line break for a coolant to steam carryover fraction of 0.08 is Ai = CRC-i * (Mw + 0.08*Ms) where -

CRC-i = iodine specific activity of the reactor coolant Mw= mass of liquid released from the reactor, Ibm Ms= mass of steam released from the reactor dome, Ibm

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1 128 Designed By K Weise and Offsite Doses - AST Sh. No.

12 Checked By P. L. Bunker The calculated iodine activity released is summarized in Table 5.

Observe that the 8%

carryover to the steam results in much greater concentrations than the steam's design basis activities in Table 3. Because of the large water inventory exiting the break at hot standby, the iodine available for release to the environment is dominated by the reactor water concentrations as shown in Table 5.

Table 5 Iodine Released from Steam Line Break Steam mass (dome) M,, Ibm Liquid mass M,, Ibm Carryover to steam fraction Conversion, gm-Ci/(lbm-uCi) 7980 109584 0.08 4.54E-04 Iodine Activity Release with Reactor Coolant at 4 uCi/am DE 1-131 Isotope 1-131 1-132 1-133 1-134 1-135 DE 1-131 RC Concentration, uCi/gm 0.96 8.84 6.56 17.68 9.58 Steam Concentration, uCi/gm 0.08 0.71 0.52 1.41 0.77 Iodine Activity

Release, Ci 4.79E+01 4.42E+02 3.28E+02 8.85E+02 4.79E+02 Iodine Activity Release with Reactor Coolant at 0.2 uCi/gm DE 1-131 Isotope 1-131 1-132 1-133 1-134 1-135 DE 1-131 RC Concentration, uCi/gm 0.048 0.442 0.328 0.884 0.479 Steam Concentration, uCi/gm 0.00 0.04 0.03 0.07 0.04 Iodine Activity
Release, Ci 2.40E+00 2.2 1E+01 1.64E+01 4.42E+01 2.40E+0 1 Notes:
1. DE 1-131 specific activities from Table 4.
2. Steam concentration is based on DE 1-131 concentration with 8%

carryover.

3. Steam and liquid masses include 20% margin.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Caic. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

13 Checked By P. L. Bunker 4.4 Effective Relative Concentration at the CRHE Air Intake The main steam line break is a double ended break in the steam tunnel. The release of steam and activity occurs over a very short time until closure of the MSIVs. The MSIV signal plus closing time is 5.5 seconds.

All the activity is assumed released to the atmosphere instantaneously as a ground level release without holdup or dilution in the steam tunnel. The duration is short enough (less than one minute) to consider the release as an instantaneous puff release in accordance with Regulatory Guide 1.194.

SSES does not have an automatic CRHE intake isolation or start-up of the CREOAS for a main steam line break. CRHE intake flow is taken as the normal service flow. No credit is taken for isolation of the CRHE intake or filtration of the radioiodine, especially in view of the short duration of the exposure.

Therefore, calculations of the CRHE X/Qs are amenable to the closed form solution given below. If CRHE isolation or filtration occurs, then numerical methods would be required to determine appropriate X/Qs.

The concentration X (x, u, t) for a puff ground level release with the center of the puff passing directly over the intake air location is X(x, u, h, t) =

2 Q

  • exp {-0.5(x - ut)2 +

-0.5 h2

}

(2Tr)3/2 (Crz2 + 02)1/2 (ox2 + 0v2)

(Ox2 + uv2)

(Oz2 + Yv2) where -

Q activity release, Ci x = release point to receptor (air intake) distance, m u - windspeed, m/s h = difference in elevation between release point and control room intake, m

=x-standard deviation of the puff in the horizontal along the wind direction and cross-wind direction at the CRHE intake location, m uz = standard deviation of the vertical cross wind direction at the intake location, m cv = initial standard deviation of the volumetric expansion of the puff, m The above diffusion equation follows from Reference 5, Eq 10 and Reference 10, Eq 3.154.

The units of X(x, u, h, t) are Ci/m 3.

The total exposure during passage of the puff is obtained by integrating over the time of the puff's passage. The total exposure XT is XT = f X(X, u, h, t) dt for 0 < t < T

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE CaIc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

14 Checked By P. L. Bunker Regulatory Guide 1.194 advises that the integration be carried out to the time T that it takes the trailing edge to pass the CRHE intake.

The puff is a Gaussian distribution. The exposure time is typically the time that it takes about 99.8% of the puff distribution to pass beyond the horizontal distance x0 to the air intake.

Approximately 99.8% of the distribution passes the intake when the center of puff travels downwind of the intake by a distance of three standard deviations in the horizontal direction.

The time T at which the puff has passed the intake is then given by:

T = x + 3 (0x2 + Y2j/

u where -

x0 = horizontal distance in x direction to intake location, m u = windspeed, m/s ax = standard deviation of the puff in the horizontal along the wind direction at the CRHE control intake location, m a= initial standard deviation of the volumetric expansion of the puff, m A simplification is made by considering the entire tail of the puff. The above equation for XT is integrated over all time (i.e., T -o

) instead of up to T1. The total exposure XT then follows directly from Reference 10, Eq 3.158 in that X(x, u, h) =

Q

  • exp{

-0.5h 2

}

(01 + av2)

Tr u (cy, 2 + cv2) 1/2 (ic),2 + T21/

Thus, the equation has the same form as the equation for a continuous plum concentration.

For example, the above equation can be compared to Reference 10, Eq 3.116 or Reference 4, Eq 1. Observe that oz and ax are functions of the distance x to the intake.

The x/Q for the duration of the puff passage T is then taken as X/Q = X(x, u, h)/Q where Q and X(x, u, h) are defined above.

1 The difference in exposures is negligible since 99.8% of the puff's distribution is considered. The specification of T, however, is beneficial since it can provide insight into the air intake exposure time.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

15 Checked By P. L. Bunker 4.5 Puff Expansion and Initial Standard Deviation The activity released from the steam line break is assumed uniformly distributed in a puff volume expanded to atmospheric pressure.

The size of the puff is set by the fluid mass released during the steam line break.

The volume V of the puff is V = (MS +Mw) *Vsp where -

Ms = mass of steam released, Ibm Mw= mass of liquid released, Ibm/s Vsp= specific volume of saturated steam at 14.7 psia, 26.8 ft3/lbm The standard deviation of the puff av is obtained by setting the initial ground level concentration X(O, u, 0, 0) equal to the puff's concentration after expansion, QN. The resulting equation is (Reference 5, p. 19):

=Y 2 V " 1/3 where V is the initial volume of the puff after expansion.

In determining the volume, the entire mass of fluid from the break is used consistent with the assumption of instantaneously releasing the entire inventory of noble gas and iodine.

The masses from section 3.2, items #3 and #4, are used to maximize the release of water and hence available radioiodine.

At power, a greater amount of steam and flashing can be expected than in hot standby.

Therefore, the use of entire fluid inventory is reasonable.

Calculated results are shown in Table 6.

4.6 Calculation of CRHE Relative Concentration xlQ The CRHE x/Qs associated with a release from each blowout panel are calculated and shown in Tables 6 and 7. x/Qs are calculated in accordance with Sections 4.4 and 4.5 above.

Table 6 identifies the main steam blowout panel locations, elevations, horizontal distances to CRHE air intake, and relative heights to the intake. The normal standard deviations ax and az of the puff are functions of horizontal distance to the intake and are also shown. These values are determined from Regulatory Guide 1.194, Figures 4 and 5.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

16 Checked By P. L. Bunker Table 6 MST Blowout Panel Locations, Distances and Dispersion Coefficients Elevation,

Distance, Aheight,
sigmax,

-sigma z, Release Point

.ft m

m m

Im RB Unit 2 Air Intake 810.3 n/a n/a n/a n/a TB Unit 1MST blowout panel 717.5 115 28 5.2 2.5 TB Unit 2 MST blowout panel 717.5 41 28 2.1 1.1 RB Unit 1 MST blowout panel 802.5 88 2

4.1 2.0 RB Unit 2 MST blowout panel 802.5 52 2

2.6

1.3 Notes

1. Aheight is the difference between intake and blowout panel elevations.
2. sigmax and sigma z are from Reg Guide 1.194, Figures 4 and 5, for class F stability.
3. Reference drawings:

E-105004, Sh. 3; E-105004, Sh. 6; E-105618; E-105670; E296155, Shs. l and 3.

Several release masses are shown in Table 7 to ensure a bounding exposure is used to determine doses at the CRHE. The time integrated exposures X(x, u, h) at the CRHE inlet are calculated using the equation developed in Section 4.4 with the distances tabulated in Table 6.

The exposures were determined for a wind speed of 1 m/s with class F stability. The difference in elevation between intake and release locations (shown in Table 6 for information) is taken as zero in Table 7. This practice essentially maximizes the exposure at the air intake2.

Table 7 shows that the maximum exposures at the CRHE air intake occur for the case (d) mass release. The corresponding x/Q value for use in the dose calculation is x/Q 73.8 Ibm-s/mi3 /(117,654 Ibm) = 6.3E-04 s/m 3 Table 7 also shows the maximum X/Qs for cases (a) to (c).

In general, these cases have greater X/Qs than case (d); however, the exposures (which also consider the size of the steam releases) are less. Case (d) will yield the greatest CRHE doses since the combined activity (or mass) and dispersion gives the largest exposures. Case (d) will also give the largest offsite doses for continuous releases assumed for the EAB and LPZ analyses.

Inspection of Table 7 reveals that dispersion is dominated by the initial expansion of the puff rather than the normal dispersion. The dispersion is relatively insensitive to horizontal distance for each release case because the puff's radius is smaller than the distance to the intake. After 2 The exposure is maximized because the puff equations in Section 4.4 and RG 1.194 are for neutrally buoyant gases. The exposure is maximized when the source and receiver are at the same elevation. Steam puffs are buoyant. The concentrations at the receiver location are typically less than the neutrally buoyant releases near the source because the center of the puff has moved above the receiver elevation as it passes by.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE CaIc. No. EC-RADN-1 128 Designed By K Weise and Offsite Doses - AST Sh. No.

17 Checked By P. L. Bunker initial expansion, the exposure at the intake is due to the entire puff as it travels by. The times T for the puff releases to have moved beyond the intake are also shown. Three minutes is a typical exposure duration.

Table 7 CRHE Effective X/Qs For Steam Line Breaks Windspeed, m/s Vapor sp. volume, f13/lbm Aheight, m 1.0 26.8 0

Puff Mass and Expansion (a)

(b)

(c) 13,130 35,000 97,970 (d) 117,564 Puff mass, Ibm 3

Volume, m Sigmapuff, m Release Point TB Unit 1 MST blowout panel TB Unit 2 MST blowout panel RB Unit I MST blowout panel RB Unit 2 MST blowout panel Maximum Effective x/Qs, s/m 3 Time T, s 9,964 26,561 74,349 89,218 10.8 15.0 21.1 22.5 Exnosure v(x. I m/s. 0 m). ibm-s/m 3 31.4 34.9 32.9 34.5 46.2 49.0 47.4 48.7 67.4 69.4 68.3 69.2 71.9 73.8 72.7 73.6 2.7E-03 1.4E-03 7.1E-04 6.3E-04 151 163 180 184 Notes:

1. Puff masses based on the following:

(a) steam mass release at hot standby, (b) steam plus flashed liquid similar to FSAR Table 3.6A MST analysis, (c) total steam plus liquid mass release at hot standby, (d) 20% margin added to case (c).

2. X /Qs are for ground level release and intake ( Ah = 0 m).
3. T is the time for >99.8% of the puff to pass the intake for each case.

4.7 Radiological and Transport Model RADTRAD 3.03 is used for the dose models and calculations. The model consists of steam tunnel, CRHE and environment nodes with four interconnecting pathways.

All the steam activity from the line break is released in 5.5 seconds into the tunnel. The activity is purged from the tunnel to the environment within seconds using an arbitrarily high flow rate pathway. Offsite and CRHE doses are calculated using the parameters described in sections 3.3, 3.4 and 3.5.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise

  • and Offsite Doses - AST Sh. No.

18 Checked By P. L. Bunker The CRHE dose calculation uses case (d)'s worst case x/Q from Table 7 with the activities from Tables 2 and 5 corresponding to a hot standby mass release (with 20% margin). The total CRHE unfiltered inleakage is 510 cfm. The air intake is 6391 cfm throughout the accident with CREOAS not credited.

Nuclide release and dose conversion factor files are shown in Attachments 1 and 2.

Nuclide inventories are developed from Tables 3 and 5. Two files corresponding to the 4 pCi/gm and 0.2 pCi/gm DE 1-131 cases are shown in Attachments 3 and 4, respectively. The physical and flow models are shown as part of the RADTRAD input in Attachments 5 and 6.

5.0 RESULTS The reported offsite and CRHE doses based on the results of the RADTRAD calculations are listed in Table 8.

Table 8 Offsite and CRHE Dose Results - Steam Line Break Pre-existing Iodine Spike 4 pCi/gm DE 1-131 TEDE, Rem Acceptance Criterion - Offsite EAB LPZ Acceptance Criterion - CRHE CRHE 25 2.0 0.12 5.0 0.93 Maximum Equilibrium Activity 0.2 pCi/gm DE 1-131 TEDE, Rem 2.5 0.10 0.006 5.0 0.05 I

Notes:

1. RADTRAD output files are in Attachments 5 and 6.
2. CRHE dose includes 30 day exposure in building after puff passage.

The EDE doses included in the TEDE are based on the CRHE volume of 518,000 ft3 used in RADTRAD. No additional finite cloud reduction for the actual control room volume of 110,000 ft3 is applied since the EDE contribution is an insignificant contributor to the reported CRHE TEDE dose.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1128 Designed By K Weise and Offsite Doses - AST Sh. No.

19 Checked By P. L. Bunker

6.0 REFERENCES

1. USNRC Regulatory Guide 1.183, "Alternative Radiological Source Terms For Evaluating Design Basis Accidents At Nuclear Power Reactors", July 2000.
2. USNRC Regulatory Guide 1.5, "Assumptions Used For Evaluating the Potential Radiological Consequences of a Steam Line Break Accident for Boiling Water Reactors", 3/71.
3. USNRC Regulatory Guide 1.98, "Assumptions Used For Evaluating The Potential Radiological Consequences Of A Radioactive Offgas System Failure In A Boiling Water Reactor", March 1976.
4. USNRC Regulatory Guide 1.145, "Atmospheric Dispersion Models for Potential Accident Consequence Assessments at Nuclear Power Plants", February 1983.
5. USNRC Regulatory Guide 1.194, "Atmospheric Relative Concentrations for Control Room Radiological Habitability Assessments at Nuclear Power Plants", June 2003.
6. NUREG-0800, USNRC Standard Review Plan Section 6.4, Control Room Habitability System, Revision 2.
7. NUREG/CR-6604, RADTRAD: A Simplified Model for RADionuclide Transport and Removal And Dose Estimation, and Supplement 1, 6/8/99.
8. Federal Guidance Report No. 11, "Limiting Values of Radionuclide Intake and Air Concentration and Dose Conversion Factors for Inhalation, Submersion, and Ingestion",

1988.

9. Federal Guidance Report No. 12, "External Exposures to Radionuclides in Air; Water; and Soil Based on the 1987 Federal Radiation Protection Guidance", 1993.
10. USAEC, Meteorology and Atomic Energy 1968.

11.ASME Steam Properties for Industrial Use, Version 1.0.1.

12. EPUMELLLA+ Design Input Request T0200Core Design, Rev. 0.
13. PPL Calculation EC-PUPC-1001, NEDC-32161 P, General Electric Power Uprate Engineering Report For Susquehanna Steam Electric Station, Revision 6, 5/24/04.
14. PPL Calculation EC-RADN-1 038, Radioactive Material Source Term Evaluation for Normal Conditions with Hydrogen Water Chemistry, Revision 1.
15. PPL Calculation EC-ENVR-1 057, Offsite X/Q Values for SSES Based on 1999 - 2003 Meteorological Data, Revision 0, April 4, 2005.
16. PPL Calculation EC-030-502, Control Structure Bldg. Volume, Revision 0, 12/17/93.
17. SSES Improved Technical Specification 5.5.7, "Ventilation Filter Testing Program",

Amendments 178 and 186.

18. SSES Improved Technical Specification 3.4.7, "Reactor Coolant System, Specific Activity";

Amendments 178 and 195. Bases for Improved Technical Specifications B 3.4.7.

19. SSES Improved Technical Specification 3.7.5, "Main Condenser Off Gas", Amendments 151 and 178. Bases for Improved Specification B 37.5.

PP&L CALCULATION SHEET Dept.

0341 Rad & Eff Tech PROJECT:

Date November 9, 2006 Steam Line Break Accident CRHE Calc. No. EC-RADN-1 128.

Designed By K Weise and Offsite Doses - AST Sh. No.

20 Checked By P. L. Bunker

20. SSES Improved Technical Specification 3.6.1.3, "Primary Containment Valves (PCIVs)", SR 3.6.1.3.7, Amendments 193 and 168.
21. Reference SSES Drawings:

E-105004, Sh. 3, Rev 26.

-E-105004, Sh. 6, Rev 22.

E-105618, Rev 1.

E-105670, Rev 8.

E-296155, Sh. 1, 10/26/2006.

E-296155, Sh. 3, 10/26/2006.

EC-RADN-1 128 Page 21 RADTRAD Control File Release Fraction and Timing SLB.rft

EC-RADN-1 128 Page 22 Release Fraction and Timing Name: SSES MSLB - Release Break Activity In 5.5 Secs Sources Duration (h):

Design Basis Accident

0. 1528E-06 Noble Gases:

1.fOOOE+00 Iodine:

1.OOOOE+00 Cesium:

o.OOOOE+00 Tellurium:

o.OOOOE+00 Strontium:

o.OOOOE+00 Barium:

o.OOOOE+00 Ruthenium:

o.OOOOE+00 Cerium:

o.OOOOE+00 Lanthanum:

o.OOOOE+00 O.OOOOE+00 O.OOOOE+00 0.0000E+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 0o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 0.0000E+00 0.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 0.OOOOE+00 o.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Non-Radioactive Aerosols (kg):

O.OOOOE+00 O.OOOOE+0O 0.OOOOE+00 O.OOOOE+00 End of Release File

EC-RADN-l 128 Page 23 RADTRAD Control File Dose Conversion File SLBPhase 2.inp

EC-RADN-1 128 Page 24 FGR11&12 edited+TID 30.inp Kr83m Xel31m 133m 135m Implicit daughter halflives (m) less than 90 and 9 ORGANS DEFINED IN THIS FILE:

ICRP-30 138 beta-test version 1.10 less than 0.100 of parent GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN(FGR) 1E 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 1-131 GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN(FGR) 1-132 GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN(FGR) 1-133 GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN (FGR) 1-134 GONADS BREAST LUNGS RED MARR NUCLIDES DEFINED IN THIS FILE:

D D

D D

D Including:Xe-135m CLOUDSHINE 1.780E-14 2.040E-14 1.760E-14 1.680E-14 3.450E-14 11.810E-14 1.670E-14 1.820E-14 2.980E-14 1.090E-13 1.240E-13 1.090E-13 1.070E-13 1.730E-13 1.120E-13 1.050E-13 1.120E-13 1.580E-13 2.870E-14 3.280E-14 2.860E-14 2.770E-14 4.870E-14 2.930E-14 2.730E-14 2.940E-14 5.830E-14 1.270E-13 1.440E-13 1.270E-13 1.250E-13

.GROUND GROUND GROUND INHALED SHINE 8HR SHINE.7DAY SHINE RATE ACUTE 1.119E-11 1.082E-11 1.016E-11 1.022E-11 1.675E-11

1. 053E-11
9. 908E-12
1. 067E-11 1.825E-11 2.523E-11 2.414E-I1
2. 305E-11 2.360E-11 3.327E-11 2.381E-11 2.283E-11 2.403E-11 8.199E-11 1.585E-11 1.519E-11 1.446E-11 1.466E-11
2. 161E-11
1. 502E-11 1.418E-11 1.509E-11 1.150E-10 1.200E-11
1. 145E-11 1.100E-II
1. 127E-11
1. 789E-10 1.730E-10 1.626E-10
1. 635E-10 2.679E-10 1.685E-10 1.585E-10 1.707E-10
2. 920E-10 2.771E-11 2.652E-11 2.532E-11 2.592E-11 3.655E-11 2.616E-11 2.509E-11 2.640E-11
9. 007E-11
6. 748E-11 6.468E-1l 6.156E-11 6.242E-11 9.202E-11 6.393E-11 6.038E-11 6.425E-11
4. 897E-10 1.202E-11
1. 147E-11
1. 102E-11
1. 129E-11 3.940E-16-1.OOOE+00 3.810E-16-1.000E+00 3.580E-16-1.OOOE+00 3.600E-16-1.000E+00 5.900E-16-1.000E+00 3.710E-16-1.000E+00 3.490E-16-1.000E+00 3.760E-16-1.OOOE+00 6.430E-16-1.000E+00 2.320E-15-1.000E+00 2.220E-15-1.000E+00 2.120E-15-1.000E+00 2.170E-15-1.000E+00 3.060E-15-1.000E+00 2.190E-15-1.000E+00 2.100E-15-1.OOOE+00 2.210E-15-1.000E+00 7.540E-15-1.OOOE+00 6.270E-16-1.OOOE+00 6.010E-16-1.OOOE+00 5.720E-16-1.OOOE+00 5.800E-16-1.000E+00 8.550E-16-1.000E+00 5.940E-16-1.OOOE+00 5.610E-16-1.OOOE+00 5.970E-16-1.000E+00 4.550E-15-1.OOOE+00 2.640E-15-1.OOOE+00 2.520E-15-1.OOOE+00 2.420E-15-1.OOOE+00 2.480E-15-1.000E+00 INHALED CHRONIC 2.530E-11 7.880E-11 6.570E-10 6.260E-11 5.730E-11 2.920E-07 8.030E-11 8.890E-09 0.000E+00 9.950E-12 1.410E-11 2.710E-10 1.400E-11 1.240E-11 1.740E-09 3.780E-11 1.030E-10 0.OOOE+00 1.950E-11 2.940E-11 8.200E-10 2.720E-11 2.520E-11 4.860E-08 5.OOOE-1I 1.580E-09 0.OOOE+00 4.250E-12 6.170E-12 1.430E-10 6.080E-12 INGESTION 4.070E-11 1.210E-10 1.020E-10 9.440E-11 8.720E-11 4.760E-07 1.570E-10 1.440E-08 0.OOOE+00 2.330E-11 2.520E-11 2.640E-11 2.460E-11 2.190E-11 3.870E-09 1.650E-10 1.820E-10 0.OOOE+00 3.630E-11 4.680E-11 4.530E-11 4.300E-11 4.070E-11 9.100E-08 1.550E-10 2.800E-09 0.OOOE+00 1.100E-11 1.170E-11 1.260E-11 1.090E-11

EC-RADN-1 128 BONE SUR THYROID REMAINDER EFFECTIVE SKIN (FGR) 1-135 GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN(FGR)

Xe-131m GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN (FGR)

Xe-133m GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN (FGR)

Xe-133 GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN(FGR)

Xe-135m GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE

'SKIN (FGR)

Xe-135 GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN (FGR)

Kr-83m 1 ;960E-13 1.300E-13 1.220E-13 1.300E-13

1. 870E-13 8.078E-14
9. 143E-14 8.145E-14 8.054E-14
1. 184E-13 8.324E-14
7. 861E-14 8.294E-14 1.156E-13 4.570E-16 6.020E-16
2. 670E-16 2.270E-16 1.060E-15
3. 910E-16 2.710E 1 16 3.378E-16
4. 820E-15
1. 420E-15
1. 700E-15
1. 190E-15
1. 100E-15 3.230E-15
1. 360E-15
1. 150E-15 1.370E-15 1.040E-14
  • 1.

610E-15

1. 960E-15 1.320E-15
1. 070E-15
5. 130E-15 1.510E-15 1.240E-15
1. 560E-15
4. 970E-15 2. OOOE-14 2.290E-14
1. 980E-14
1. 910E-14
3. 500E-14
2. 040E-14 1.890E-14 2.040E-14
2. 970E-14 1.170E-14 1.330E-14 1.130E-14 1.070E-14 2.570E-14 1.180E-14 1.080E-14 1.190E-14 3.12OE-14 1.568E-11

-1.127E-11 1.091E-11 1.150E-11 4.477E-11

.3.113E-11 2.971E-11 2.886E-11

2. 965E-11 3.983E-11
2. 852E-11 2.883E-11
2. 989E-11 9.826E-11
7. 872E-13 8.471E-13 3.565E-13
2. 792E-13 1.677E-12 5.220E-13
3. 993E-13 5.876E-13 1.266E-12 1.337E-12 1.383E-12 8.609E-13
7. 844E-13 2.599E-12
1. 028E-12 8.855E-13
1. 112E-12
1. 894E-12 1.465E-12 1.505E-12
1. 045E-12
8. 791E-13 4.254E-12
1. 181E-12
1. 042E-12
1. 299E-12
1. 953E-12
5. 929E-13 5.691E-13 5.347E-13 5.400E-13 8.246E-13 5.612E-13 5.241E-13 5.612E-13 1.866E-12 5.455E-12
5. 325E-12
4. 959E-12
4. 959E-12
9. 120E-12 5.023E-12 4.829E-12 5.217E-12 4.506E-11 1.571E-11 1.129E-11 1.093E-11 1.152E-11 4.485E-11 5.489E-11 5.240E-11 5..089E-11 5.228E-11 7.024E-11
5. 030E-11 5.084E-11 5.271E-11
1. 733E-10 1.371E-11 1.475E-11 6.209E-12
4. 863E-12
2. 920E-11
9. 089E-12
6. 954E-12
1. 023E-11 2.205E-11 1.188E-11 1.230E-11 7.656E-12
6. 975E-12 2.311E-11
9. 138E-12
7. 874E-12
9. 892E-12 1.684E-11
2. 052E-11
2. 107E-11 1.464E-11
1. 231E-11
5. 958E-11 1.653E-11 1.460E-11 1.819E-11 2.734E-11
5. 929E-13 5.691E-13
5. 347E-13 5.400E-13 8.246E-13
5. 612E-13 5.241E-13
5. 612E-13
1. 866E-12 1.194E-11
1. 166E-11 1.086E-11 1.086E-11 1.997E-11 1.100E-11 1.058E-11 1.142E-11 9.867E-11 3.450E-15-1.OOOE+00 2.480E-15-1.OOOE+0o 2.400E-15-1.OOOE+00 2.530E-15-1.000E+00 9.8'50E-15-1.000E+00 1.599E-15-1.OOE+00 1.526E-15-1.000E+00 1.482E-15-1.OOOE+00 1.523E-15-1.OOOE+00 2.046E-15-1.OOOE+00 1.465E-15-1.OOOE+00 1.481E-15-1.OOOE+00 1.535E-15-1.OOOE+00 5.047E-15-1.OOOE+00 2.760E-17-1.OOOE+00 2.970E-17-1.OOOE+00 1.250E-17-1.000E+00 9.790E-18-1.OOOE+00 5.880E-17-1OOOE+00 1.830E-17-1.OOOE+00 1.400E-17-1.OOOE+00 2.060E-17-1.OOOE+00 4.440E-17-1.OOOE+00 4.890E-17-1.OOOE+00 5.060E-17-1.OOOE+00 3.150E-17-1.OOOE+00 2.870E-17-1.OOOE+00 9.510E-17-1.OOOE+00 3.760E-17-1.OOOE+00 3.240E-17-1.OOOE+00 4.070E-17-1.OOOE+00 6.930E-17-1.OOOE+00 5.200E-17-1.OOOE+00 5.340E-17-1.OOOE+00 3.710E-17-1.OOOE+00 3.120E-17-1.000E+00 1.510E-16-1.OOOE+00 4.190E-17-1.OOOE+00 3.700E-17-1.000E+00 4.610E-17-1.OOOE+00 6.930E-17-1.OOOE+00 4.480E-16-1.OOOE+00 4.300E-16-1.OOOE+00 4.040E-16-1.OOOE+00 4.080E-16-1.OOOE+00 6.230E-16-1.OOOE+00 4.240E-16-1.OOOE+00 3.960E-16-1.00OE+00 4.240E-16-1.OOOE+00 1.410E-15-1.OOOE+00 2.530E-16-1.OOOE+00 2.470E-16-1.000E+00 2.300E-16-1.OOOE+00 2.300E-16-1.OOOE+00 4.230E-16-1.000E+00 2.330E-16-1.OOOE+00 2.240E-16-1.OOOE+00 2.420E-16-1.OOOE+00 2.090E-15-1.OOOE+00 Page 25 5.310E-12 2.880E-10 2.270E-11 3.550E-11 O.OOOE+00
1. 700E-11 2.340E-11 4.410E-10 2.240E-11 2.01OE-11 8.460E-09
4. 700E-11 3.320E-10 o.OOOE+00 o.OOOE+00 o.OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 o.OOOE+00 0. OOOE+00
0. OOOE+00 0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 o.OOOE+00
0. OOOE+00 0. OOOE+00
0. OOOE+00
0. OOOE+00 0. OOOE+00 o.OOOE+00 o.OOOE+00 0. OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 o.OOOE+00
0. OOOE+00
0. OOOE+00
9. 320E-12 6.210E-10 1.340E-10 6.660E-11 o.O0OE+00 3.610E-11 3.850E-11
3. 750E-11 3.650E-11 3.360E-11 1.790E-08 1.540E-10 6.080E-10 o.OOOE+00 o.000E+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 0.OOOE+00
0. OOOE+00
0. OOOE+00
0. 000E+00 0. OOOE+00
0. OOOE+00
0. OOOE+00 o.OOOE+00
0. OOOE+00 o.OOOE+00 o.OOOE+00
0. OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.000E+00 o.OOOE+00 o.OOOE+00 O0000E+O0 o.OOOE+00
0. 000E+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 o..OOOE+00
0. OOOE+00 o.OOOE+00 0. OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 o.OOOE+00 0. OOOE+00

EC-RADN-1 128 Page 26 GONADS 1.710E-18 5.572E-15 5.855E-15 6.160E-19-1.OOOE+00 O.OOOE+00 O.OOOE+00 BREAST 5.050E-18 9.498E-15 9.980E-15 1.050E-18-1.OOOE+00 O.OOOE+00 O.OOOE+00 LUNGS 1.640E-19 1.266E-16 1.331E-16 1.400E-20-1.OOOE+00 O.OOOE+00 O.OOE+00 RED MARR 3.830E-19 5.617E-16 5.902E-16 6.210E-20-1.OOOE+00 0.OOOE+00 O.OQOE+00 BONE SUR 2.250E-18 3.437E-15 3.612E-15 3.800E-19-1.000E+00 O.OOOE+00 O.OOOE+00 THYROID 6.430E-19 7.698E-16 8.088E-16 8.510E-20-1.OOOE+00 O.OOOE+00 O.OOOE+00 REMAINDER 5.300E-19 1.393E-15 1.464E-15 1.540E-19-1.OOOE+00 O.OOQE+00 O.OOOE+00 EFFECTIVE 1.500E-18 3.437E-15 3.612E-15 3.800E-19-1.OOOE+00 O.OOOE+00 O.OOOE+00 SKIN(FGR) 3.560E-17 1.167E-13 1.226E-13 1.290E-17-1.OOOE+00 O.OOOE+00 O.OOOE+00 Kr-85m GONADS 7.310E-15 2.594E-12 3.653E-12 1.570E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 BREAST 8.410E-15 2.527E-12 3.560E-12 1.530E-16-1.OOOE+00 0.OOOE+00 O.OOOE+00 LUNGS 7.040E-15 2.379E-12 3.351E-12 1.440E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 RED MARR 6.430E-15 2.346E-12 3.304E-12 1.420E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 BONE SUR 1.880E-14 5.286E-12 7.446E-12 3.200E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 THYROID 7.330E-15 2.395E-12 3.374E-12 1.450E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 REMAINDER 6.640E-15 2.313E-12 3.257E-12 1.400E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 EFFECTIVE 7.480E-15 2.511E-12 3.537E-12 1.520E-16-1.OOOE+Oo 0.OOOE+00 O.OOOE+00 SKIN(FGR) 2.240E-14 2.247E-11 3.164E-11 1.360E-15-1.000E+00 O.OOOE+00 O.OOOE+00 Kr-87 GONADS 4.OOOE-14 4.962E-12 5.026E-12 7.610E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 BREAST 4.500E-14 4.740E-12 4.802E-12 7.270E-16-1.OOOE+00 O.OOE+00 O.OOOE+00 LUNGS 4.040E-14 4.603E-12 4.663E-12 7.060E-16-1.O0OE+00 O.OOOE+00 O.OOOE+00 RED MARR 4.OOOE-14 4.708E-12 4.769E-12 7.220E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 BONE SUR 6.020E-14 6.514E-12 6.598E-12 9.990E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 THYROID 4.130E-14 4.473E-12 4.531E-12 6.860E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 REMAINDER 3.910E-14 4.590E-12 4.650E-12 7.040E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 EFFECTIVE 4.120E-14 4.773E-12 4.835E-12 7.320E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 SKIN(FGR) 1.370E-13 8.802E-11 8.916E-11 1.350E-14-1.OOOE+00 O.OOOE+00 O.OOOE+00 Kr-88 GONADS 9.900E-14 2.278E-11 2.655E-11 1.800E-15-1.000E+00 O.OOOE+00 O.OOOE+00 BREAST 1.110E-13 2.177E-11 2.537E-11 1.720E-15-1.OOOE+00 0.000E+oo O.OOOE+00 LUNGS 1.010E-13 2.139E-11 2.493E-1I 1.690E-15-1.OOOE+00 0.000E+00 O.OOOE+00 RED MARR 1.OOOE-13 2.190E-11 2.552E-1I 1.730E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 BONE SUR 1.390E-13 2.886E-11 3.363E-11 2.280E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 THYROID 1.030E-13 2.012E-11 2.345E-11 1.590E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 REMAINDER 9.790E-14 2.139E-11 2.493E-11 1.690E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 EFFECTIVE 1.020E-13 2.202E-11 2.567E-11 1.740E-15-1.OOOE+00 O.OQOE+00 O.OOOE+00 SKIN(FGR) 1.350E-13 5.607E-11 6.534E-11 4.430E-15-1.OOOE+00 O.OOOE+00 O.OOE+00 Kr-85 GONADS 1.170E-16 8.121E-14 1.704E-12 2.820E-18-1.OOOE+00 O.OOOE+00 O.OOE+00 BREAST 1.340E-16 7.891E-14 1.656E-12 2.740E-18-1.OOOE+00 O.OOOE+00 O.OOOE+00 LUNGS 1.140E-16 7.056E-14 1.481E-12 2.450E-18-1.OOOE+00 O.OOOE+00 O.OOOE+00 RED MARR 1.090E-16 6.998E-14 1.469E-12 2.430E-18-1.OOOE+00 O.OOOE+00 O.OOOE+00 BONE SUR 2.200E-16 1.287E-13 2.702E-12 4.470E-18-1.OOOE+00 O.OOE+00 O.OOOE+00 THYROID 1.180E-16 7.459E-14 1'565E-12 2.590E-18-1.OOOE+00 O.OOOE+00 O.OOOE+00 REMAINDER 1.090E-16 6.941E-14 1.457E-12 2.410E-18-1.OOOE+00 O.OOOE+00 O.OOOE+00 EFFECTIVE.1.190E-16 7.603E-14 1.596E-12 2.640E-18-1.OOOE+00 O.OOOE+00 0.000E+00 SKIN(FGR) 1.320E-14 2.304E-11 4.835E-10 8.000E-16-1.000E+00 O.OOE+00 O.OOE+00 xe-138 GONADS 5.590E-14 O.OOOE-14 O.OOOE-12 1.070E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 BREAST 6.320E-14 O.OOOE-14 0.OOOE-12 1.020E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 LUNGS 5.660E-14 O.OOOE-14 0.OOOE-12 9.970E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 RED MARR 5.600E-14 O.OOOE-14 0.OOOE-12 1.020E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 BONE SUR 8.460E-14 O.OOOE-13 0.OOOE-12 1.410E-15-1.OOOE+00 O.OOOE+00 O.OQOE+00 THYROID 5.770E-14 O.OOOE-14 O.OOOE-12 9.550E-16-1.OOOE+00 0.000E+00 O.OOOE+00 REMAINDER 5.490E-14 O.OOOE-14 O.OOOE-12 9.940E-16-1.OOOE+00 O.OOOE+00 O.OOOE+00 EFFECTIVE 5.770E-14 O.OOOE-14 O.OOOE-12 1.030E-15-1.OOOE+00 O.OOOE+00 O.OOOE+00 SKIN(FGR) 1.070E-13 O.OOOE-11 O.OOOE-10 7.650E-15-1.OOOE+00 O.OQOE+00 O.OOOE+00

EC-RADN-1128 Page 27 RADTRAD Control File Inventory File SLB_4mc.nif

EC-RADN-1 128 Page 2,8 Nuclide Inventory Name:SSESSLB 4mc.nif SSES SLB Power Level:4032 0.1000E+01 Nuclides:

16 Nuclide 001:

1-131 2

0.6956000000E+06 0.1310E+03 0.4790E+02 Xe-131m 0.1100E-01 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 002:

1-132 2

0.8390000000E+04 0.1320E+03 0.4420E+03 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 003:

1-133 2

0.7533000000E+05 0.1330E+03 0.3280E+03 Xe-133m 0.2900E-01 Xe-133 0.9700E+00 none 0.OOOOE+00 Nuclide 004:

1-134 2

0.3150000000E+04 0.1340E+03 0.8850E+03 none 0.OOOOE+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 005:

1-135 2

0.2423100000E+05 0.1350E+03 0.4790E+03 Xe-135m 0.1500E+00 Xe-135 0.8500E+00 none 0.OOOOE+00 Nuclide 006:

Xe-131m 1

0.1036000000E+07 0.1310E+03 0.1810E-02 none 0.OOOOE+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 007:

Xe-133m 1

0.1987032000E+06 0.1330E+03 0.3390E-01

EC-RADN-1 128 Page 29 Xe-133 none none Nuclide Xe-133 1

0. 1000E+01 0.0000E+00 0.0000E+00 008:
0. 4 5 5 3380000E+06 0.1330E+03

'0.9890E+00

.none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 009:

Xe-135m 1

0.

9 3 6 0 000000E+03

0. 1350E+03 0.3150E+01 Xe-135 0.1000E+01 Cs-135 0.4500E-04 none 0.0000E+00 Nuclide 010:

Xe-135 1

0. 3 2 8 6 800000E+05 0.1350E+03 0.2750E+01 Cs-135 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 011:

Kr-83m 1

0.684 0 000000E+04 0.8300E+02 0.4190E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 012:

Kr-85m 1

0.1 5 6 9 600000E+05 0.8500E+02 0.7290E+00 Kr-85 0.2100E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 013:

Kr-87 1

0.

4 6 8 0 000000E+04 0.8700E+02 0.2360E+01 Rb-87 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 014:

Kr-88 1

0.

9 9 7 2 400000E+04 0.8800E+02 O.02450E+01 Rb-,88 0.1000E+01 none 0.0000E+00 none 0.-000E+0,

EC-RADN-1 128.

Page 30 Nuclide 015:

Kr-85 1

0.3382974720E+09 0.8500E+02 0.2430E-02 none O.OOOOE+00 none O.OOOOE+00 none 0.OOOOE+00 Nuclide 016:

Xe-138 1

0.8490000000E+03 0.1380E+03 0.1100E+02 Cs-138 0.1000E+01 none 0.0000E+00 none 0.OOOOE+00.

End of Nuclear Inventory File

EC-RADN-1 128 Page 31 RADTRAD Control File Inventory File SLBpt2mc.nif

EC-RADN-1128 Page 32 Nuclide Inventory Name:SSESSLBpt2mc.nif SSES SLB Power Level:4032 0.1000E+01 Nuclides:

16 Nuclide 001:

1-131 2

0.6956000000E+06 0.1310E+03 0.2400E+01 Xe-131m 0.1100E-01 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 002:

1-132 2

0.8390000000E+04 0.1320E+03 0.2210E+02 none 0.0000E+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 003:

1-133 2

0.7533000000E+05 0.1330E+03 0.1640E+02 Xe-133m 0.2900E-01 Xe-133 0.9700E+00 none 0.OOOOE+00 Nuclide 004:

1-134 2

0.3150000000E+04 0.1340E+03 0.4420E+02 none 0.OOOOE+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 005:

1-135 2

0.2423100000E+05 0.1350E+03 0.2400E+02 Xe-135m 0.1500E+00 Xe-135 0.8500E+00 none 0.OOOOE+00 Nuclide 006:

Xe-131m 1

0.1036000000E+07 0.1310E+03 0.1810E-02 none 0.OOOOE+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 007:

Xe-133m 1

0. 1987,03200OE+06 0.133:OE+03 0.3390E-01

EC-RADN-1 128.

Page 33 Xe-133 0.1000E+01 none 0.0000E+00-none 0.OOOOE+00 Nuclide 008:

Xe-133 1

0.4553380000E+06 0.1330E+03 0.9890E+00 none 0.0000E+00 none 0.0000E+00 none 0.OOOOE+00 Nuclide 009:

Xe-135m 1

0.9360000000E+03 0.1350E+03 0.3150E+01 Xe-135 0.1000E+01 Cs-135 0.4500E-04 none 0.OOOOE+00 Nuclide 010:

Xe-135

  • 1 0.3286800000E+05 0.1350E+03 0.2750E+01 Cs-135 0.1000E+01 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 011:

Kr-83m 1

0.6840000000E+04 0.8300E+02 0.4190E+00 none 0..OOOOE+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 012:

Kr-85m 1

0.1569600000E+05 0.8500E+02 0.7290E+00 Kr-85 0.2100E+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 013:

Kr-87 1

0.4680000000E+04 0.8700E+02 0.2360E+01 Rb-87 0.1000E+01 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 014:

Kr-88 1

0.9972400000E+04 0.8800E+02 0.2450E+01 Rb-88 0.1000E+01 none 0.OOOOE+00 none 0.OOOOE+00

EC-RADN-1 128 Page 34 Nuclide 015:

Kr-85 1

0.3382974720E+09 0.8500E+02 0.2430E-02 none 0.OOOOE+00 none 0.OOOOE+00 none 0.OOOOE+00 Nuclide 016:

Xe-138 1

0.8490000000E+03 0.1380E+03 0.1100E+02 Cs-138 0.1000E+01 none 0.OOOOE+00 none 0.OOOOE+00 End of Nuclear Inventory File

EC-RADN-1 128 Page 35 RADTRAD Output TBMST_500cfm_4mcDE_1 128.out

EC-RADN-1128 Page 36 RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 12:59:23 File information

                                                                                                                1. 4##############

Plant file

= C:\\Program Files\\radtrad3.03\\EC-RADN-1128_RiRADTRAD\\TBMSTO50cfm_4mcDE_1l28.psf Inventory file

= c:\\programfiles\\radtrad3.03\\ec-radn-1128_rlradtrad\\slb,4mc.nif Release file

= c:\\program files\\radtrad3.03\\ec-radn-1128_rl radtrad\\slb.rft Dose Conversion file = c:\\program files\\radtrad3.03\\ec-radn-1128_rl radtrad\\slb_phase 2.inp

  • ata 3.03 4/15/420401 Radtad303E 415/00 Compartments:

3 Compartment 1:

SSES TB MS Tunnel 3

4.4000E+04 0

0 0

0 0

Compartment 2:

Environment 2

0.OOOOE+00 0

.0 0

0 0

Compartment 3:

SSES CR 1

5. 1800E+65

.0 0

0 0,

Pathways:

4

EC-RADN-1 128 Page 37 Pathway 1:

SSES MST to Environs 1

2 2

Pathway 2:

Environment 2

3 2

Pathway 3:

Environment 2

.3 2

to SSES CR - 6391 cfm Normal Intake to SSES CR -500+10 cfm Unfiltered Inleakage Pathway 4:

'SSES CR to Environment 3

2 2

CR Exhaust End of Plant Model File Scenario Description Name:

Plant Model Filename:

Source Term:

1 1

1.0000E+00 c:\\program files\\radtrad3.03\\ec-radn-1128 rl radtrad\\slbphase 2.inp c:\\program files\\radtrad3.03\\ec-radn-1128 rl radtrad\\slb.rft 0.0000E+00 1

9.5000E-01 4.8500E-02 1.5000E-03 1.0000E+00 Overlying Pool:

0 0.0000E+00 0

0 0

0 Compartments:

3 Compartment 1:

1 1

0 0

0 0

0 0

0 Compartment 2:

0 1

0 0

0 0

0 0

0 Compartment 3:

1 1

0

EC-RADN-1 128 Page 38 0

0 0

0 0

0 Pathways:

4 Pathway 1:

0 0

0 0

0 1

o.OOOOE+00 3.3300E-02

7. 2000E+02 0

0 0

0 0

0 Pathway 2:

0 0

0 0

0 1

3 o.OOOOE+00

6. 6600E-02 7.2000E+02 0.

0 0

0 0

Pathway 3:

0 0

0 0

0 1

3 o.OOOOE+00

6. 6600E-02
  • 7.2000E+02 0

0 0

0 0

0 Pathway 4:

0 0

0 0

0 1

2.2000E+06 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 0.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 6.3910E+03 6.3910E+03 0.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 1.OOOOE+02 o.OOOOE+00 o.OOOOE+00 1.OOOOE+02 o.OOOOE+00

5. 1000E+02
5. 1000E+02 0.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 0.OOOOE+00 1.OOOOE+02 0.OOOOE+00 0.OOOOE+00 1.OOOOE+02 0.OOOOE+00

EC-RADN-I 128 Page 39 3

0.0000E+00

5. OOOOE-01 7.2000E+02 0

0 0

6. 9010E+03
6. 9010E+03 0.OOOOE+00 o.OOOOE+OO o.000E+00 0.0000E+00 o.OOOOE+OO o.OOOOE+00 o.OOOOE+0O O.OOOOE+OO o.OOOOE+00 o. 000E+00 0

00 Dose Locations:

3 Location 1:

EAB -

MST Release 2

1 3

0.0000E+00 2.0000E+00 7.2000E+02 1

4 o.0000E+00 8.0000E+00 2.4000E+01 7.2000E+02 0

Location 2:

MSLB @ LPZ -

2 1

5 o.OOOOE+00 8.0000E+00 2.4000E+01 9.6000E+01 7.2000E+02 1

4 o.OOOOE+00 8.OOOOE+00 2.4000E+01 7.2000E+02 0

Location 3:

MSLB @ CR -

3 0

1 2

0.0000E+00 7.2000E+02 1

  • 8.3000E-04 8.3000E-04 o.OOOOE+00 3.5000E-04 1.8000E-04 2.3000E-04 o.OOOOE+00 MST Release 4.9000E-05 3.50OOE-05 1.7000E-05
6. 1000E-06 0.0000E+00 3.50OOE-04 1.8000E-04 2.3000E-04 o.OOOOE+00 MST Release 3.4700E-04 0.OOOOE+00 4

O.OOOOE+00 1.OOOOE+00 2.4000E+01 6.OOOOE-01 9.6000E+01 4.OOOOE-01 7.2000E+02 0.OOOOE+00 Effective Volume Location:

1 3

0.OOOOE+00 6.3000E-04

-6.66OOE-02 0.OOOOE+00 7.200'OE+02 O.OOOE+00 Simulation Parameters:

4

EC-RADN-t 128 O.OOOE+00 I.000OE-04 1.O000E-02 1.0000E-03 1.000E-01 1.OOOOE-02 7.2000E+02 O.OOOOE+00 Output Filename:

C:\\Program Files\\radtrad3.o5 1

1 1

0 1

End of Scenario File Page 40

EC-RADN-1 128 Page 41 RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 12:59:23

                                                                          1. 4##################################

Plant Description Number of Nuclides =

16 Inventory Power 1.OOOOE+00 MWth Plant Power Level =

1.OOOOE+00 MWth Number of compartments

=

3 Compartment information Compartment number 1

(Source term fraction =

1.OOOOE+00 Name: SSES TB MS Tunnel Compartment volume

=

4.4000E+04 (Cubic feet)

Compartment type is Normal Pathways into and out of compartment 1

Exit Pathway Number 1: SSES MST to Environs Compartment number 2

Name: Environment Compartment type is Environment Pathways into and out of compartment 2

Inlet Pathway Number 1: SSES MST to Environs Inlet Pathway Number 4: SSES CR to Environment -

CR Exhaust Exit Pathway Number 2: Environment to SSES CR - 6391 cfm Normal Intake Exit Pathway Number 3: Environment to SSES CR -500+10 cfm Unfiltered Inle Compartment number 3

Name: SSES CR Compartment volume =

5.1800E+05 (Cubic feet)

Compartment type is Control Room Pathways into and out of compartment 3

Inlet Pathway Number 2: Environment to SSES CR - 6391 cfm Normal Intake Inlet Pathway Number

. 3: Environment to SSES CR -500+10 cfm Unfiltered Inle Exit Pathway Number 4: SSES CR to Environment -

CR Exhaust Total number of pathways =

4

EC-RADN-1128 Page 42

                                                                                                                  1. 4##############

RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 12:59:23 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Release Fractions and Timings GAP EARLY IN-VESSEL 0.000000 hr 0.0000 hrs NOBLES 1.OOOOE+00 0.OOOOE+00 IODINE 1.0000E+00 0.OOOOE+00 CESIUM 0.OOOOE+00 0.OOOOE+00 TELLURIUM 0.OOOOE+00 0.OOOOE+00 STRONTIUM 0.OOOOE+00 0.OOOOE+00 BARIUM 0.OOOOE+00 0.OOOOE+00 RUTHENIUM 0.OOOOE+00 0.OOOOE+00 CERIUM 0.OOOOE+00 0.OOOOE+00 LANTHANUM 0.OOOOE+00 0.OOOOE+00 LATE RELEASE 0.0000 hrs

0. 0000E+00
0. OOE+00 0.OOOOE+00 0.OOOOE+00 0 OOOOE+00 0.OOOOE+00 0 OOOOE+00 0 OOOOE+00
0. O00OE+00 RELEASE MASS (gm) 1.322E-05
8. 936E-04 0.OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 Inventory Power =
1.

MWt Nuclide Name 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 Nuclide 1-131 i-133 1-135 Xe-133m Xe-135m Xe-135 Kr-85m Kr-87 Kr-88 Xe-138 Group Specific Inventory (Ci/MWt) 2 4.790E+01 2

4.420E+02 2

3.280E+02 2

8.850E+02 2

4.790E+02.

1 1.810E-03 1

3.390E-02 1

9.890E-01 1

3.150E+00 1

2.750E+00 1

4.190E-01 1

7.290E-01 1

2.360E+00 1

2.450E+00 1

2.430E.-03 1

1.100E+01 half life (s) 6 956E+05 8.390E+03 7.533E+04 3.150E+03 2.423E+04 1.036E+06

1. 987E+05
4. 553E+05
9. 360E+02 3.287E+04
6. 840E+03
1. 570E+04 4.680E+03
9. 972E+03 3.383E+08 8.490E+02 Whole Body DCF (Sv-m3/Bq-s) 1.820E-14 1.120E-13 2.940E-14 1.300E-13
8. 294E-14 3.378E-16 1.370E-15
1. 560E-15
2. 040E-14
1. 190E-14
1. 500E-18 7.480E-15
4. 120E-14
1. 020E-13
1. 190E-16
5. 770E-14 Inhaled Thyroid (Sv/Bq)
2. 920E-07
1. 740E-09
4. 860E-08
2. 880E-10
8. 460E-09
0. OOOE+00 0 OOOE+00 0 OOOE+00
0. OOOE+00 0. OOOE+00 0 OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 0 OOOE+00 Daughter none none none none none none none none none none Inhaled Effective (Sv/Bq) 8.890E-09 1.030E-10 1.580E-09 3.550E-11 3.320E-10 0.OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00
0. OOOE+00
0. OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00 Fraction 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Daughter Xe-131m Xe-133m Xe-135m Xe-133 Xe-135 Cs-135 Kr-85 Rb-87 Rb-88 Cs-138 Fraction 0.01

.0.03 0.15 1.00 1.00 1.00 0.21 1.00 1.00 1.00 Daughter none Xe-133 Xe-135 none Cs-135 none none none none none Fractior 0.00 0.97 0.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Iodine fractions Aerosol Elemental Organic COMPARTMENT DATA

9. 50OOE-01 4.8500E-02 1.50OOE-03

EC-RADN-1128

-Compartment number 1: SSES TB MS Tunnel Compartment number 2: Environment Compartment number 3: SSES CR PATHWAY DATA Pathway number 1: SSES MST to Environs Pathway Filter:

Removal Data Page 43 Time (hr) 0.0000E+00 3.3300E-02 7.2000E+02 Flow Rate (cfm) 2.2000E+06 o.0000E+00 o.0000E+00 Filter Efficiencies (%)

Aerosol Elemental Organic 0.0000E+00 0.OOOOE+00 0.0000E+00 0.0000E+00 0.OOOOE+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 2: Environment to SSES CR -

6391 cfm Normal Intake Pathway Filter:

Removal Data Time (hr) 0.0000E+00 6.6600E-02 7.2000E+02 Flow Rate (cfm) 6.3910E+03

  • 6.3910E+03 o.0000E+00 Filter Efficiencies (%)

Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.OOOOE+00 0.0000E+00 1.0000E+02 1.OOOOE+02 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Environment to SSES CR -500+10 cfm Unfiltered Inle Pathway Filter:

Removal Data Time (hr) 0.0000E+00 6.6600E-02 7.2000E+02 Flow Rate (cfm)

5. 1000E+02
5. 1000E+02 0.0000E+00 Filter Efficiencies (%)

Aerosol Elemental Organic 0.0000E+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 1.0000E+02 1.0000E+02 0.0000E+00 0.0000E+00 0.OOOOE+00 Pathway number 4: SSES CR to Environment CR Exhaust Pathway Filter:

Removal Data Time (hr) 0.0000E+00

5. 0000E-01 7.2000E+02 Flow Rate (cfm) 6.9010E+03
6. 9010E+03 0.0000E+00 Filter Efficiencies (%)

Aerosol Elemental Organic O.0000E+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 LOCATION DATA Location EAB -

MST Release is in compartment 2

Location X/Q Data Time (hr) 0.OOOOE+00 2.OOOOE+00 7.2000E+02 X/Q (s

  • m -3) 8.3000E-04 8.3000E-04 0.OOOOE+00 Location Breathing Rate Data Time (hr)

Breathing 0.OOOOE+00 8.OOOOE+00 2.4000E+01 7.2000E+02 Location MSLB 4 LPZ MST Rel Rate (m'3

  • sec^-l) 3.5000E-04 1.8000E-04 2.3000E-04 0.0o0oE+00 ease is in comp artment 2

Location X/Q Data

EC-RADN-1 128 Time -(hr) 0.0000E+00 8.0000E+00 2.4000E+01 9.6000E+01 7.2000E+02 Location Breath Time (hr) 0.0000E+00 8.0000E+00 2.4000E+01 7.2000E+02 Location MSLB @

Location X/Q Da Time (hr) o.0000E+00 6.6600E-02 7.2000E+02 Location Breath Time (hr)

.0.0000E+00 7.2000E+02 Location Occupa Time (hr) 0.0000E+00 2.4000E+01 9.6000E+01 7.2000E+02 USER SPECIFIED TIME Time 0.0000E+00 1.OOOOE-02 1.OOOOE-01 7.2000E+02 X/Q (s

  • m^-3) 4.9000E-05 3.5000E-05 1.7000E-05 6.1000E-06 0.OOOOE+00 Ling Rate Data Breathing Rate (m'3
  • sec'-1) 3.5000E-04

.1.8000E-04 2.3000E-04 0.0000E+00 CR MST Release is in compartmen

.ta X/Q (s

  • m'-3) 6.3000E-04 0.0000E+00 0.0000E+00 Ling Rate Data Breathing Rate (mW3
  • sec^-1) 3.4700E-04 0.0000E+00
  • ncy Factor Data Occupancy Factor 1.OOOOE+00 6.OOOOE-01 4.OOOOE-01 0.000OE+00 STEP DATA -

SUPPLEMENTAL TIME STEPS Time step 1.OOOOE-04 1.OOOOE-03 1.OOOOE-02 0.OOOOE+00 Page 44 t

3

EC-RADN-1 128 Page 45 RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 12:59:23 44 ##4#444#4444#4#4444# 44# 44## 444# 44#4#44####44444tft 444

  1. 44 444 #

4 4#4

  1. 1
  1. 1 44 ft ft ft 4

ft 4

  1. 44
  1. 444 ft 4

ft 4

4 ft 4

4.

4 4

4 4

4444 4

Dose, Detailed model and Detailed Inventory Output Detailed model information at time (H)

=

0.0000 EAB -

MST Release Doses:

Time (h)

=

0.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 1.5193E-04 1.5193E-04 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

0.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 8.9694E-06 8.9694E-06 Thyroid

8. 6221E-03 8.6221E-03 Thyroid 5.0901E-04
5. 0901E-04 Thyroid 3.9624E-10 3.9624E-10 TEDE 4.4260E-04 4.4260E-04 TEDE 2.6129E-05 2.6129E-05 TEDE 1.3871E-11 1.3871E-11 MSLB @ CR -

MST Release Doses:

Time (h)

=

0.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 5.1270E-13 5.1270E-13 SSES TB MS Time (h)

=

1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 Tunnel Compartment Nuclide Inventory:

0.0000 Ci

4. 7889E+01 4.4190E+02 3.2792E+02 8.8480E+02 4.7889E+02 1.8096E-03 3.3892E-02
9. 8877E-01 3.1493E+00 2.7494E+00 4.1890E-01 7.2883E-01 2.3595E+00 2.4494E+00

.2.4294E-03 1.0997E+01 kg 3.8681E-07 4.3379E-08

2. 9122E-07 3.3104E-08 1.3886E-07
2. 1769E-11
7. 9393E-11
5. 3077E-09 3.5274E-11 1.0814E-09
2. 1080E-11
8. 6191E-11
8. 5154E-11
1. 9053E-10
6. 1923E-09.
1. 1421E-10 Inventory:

Sump 0.0000E+00 0.OOOOE+00 0.0000E+00 Atoms 1.7782E+18 1.9791E+17 1.3186E+18 1.4878E+17

6. 1942E+17
1. 0007E+14 3.5949E+14 2.4033E+16 1.5735E+14 4.8237E+15
1. 5295E+14 6.1065E+14 5.8943E+14 1.3039E+15 4.3871E+16 4.9840E+14 Decay 9.7468E+08 8.9939E+09 6.6742E+09 1.8008E+10 9.7468E+09 3.6830E+04 6.8981E+05 2.0124E+07 6.4097E+07 5.5958E+07 8.5259E+06 1.4834E+07 4.8022E+07 4.9853E+07 4.9447E+04 2.2383E+08

'SSES TB MS Tunnel Transport Group Time (h)

=

0.0000 Atmosphere Noble gases (atoms) 7.6500E+16 Elemental I (atoms) 1.9705E+17 Organic I (atoms) 6.0943E+15

EC-RADN-1 128 Aerosols (kg)

Dose Effective Dose Effective Total I (Ci)

Page 46 8.4870E-07 0.0000E+00 (Ci/cc) 1-131 (Thyroid)

(Ci/cc) 1-131 (ICRP2.Thyroid) 9.6191E-08 1.6567E-07 2.1814E+03 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.0000E+00 0.OOOOE+00 0.OOOOE+00 Transported 1.7535E+13 4.5167E+13 1.3969E+12 1.9454E-10 SSES CR Compartment Nuclide Inventory:

Time (h)

=

1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 0.0000 Ci 2.2523E-05 2.0783E-04 1.5423E-04 4.1614E-04 2.2523E-04 8.5109E-10 1.5940E-08 4.6504E-07 1.4812E-06 1.2931E-06 1.9702E-07 3.4279E-07 1.1097E-06 1.1520E-06 1.1426E-09 5.1723E-06 kg 1.8192E-13 2.0402E-14 1.3697E-13 1.5570E-14

6. 5307E-14
1. 0238E-17
3. 7340E-17 2.4963E-15 1.6590E-17
5. 0858E-16
9. 9144E-18
4. 0537E-17
4. 0050E-17
8. 9612E-17
2. 9124E-15
5. 3715E-17 Atoms
8. 3631E+11
9. 3080E+10
6. 2017E+11
6. 9972E+10
2. 9132E+11 4.7066E+07
1. 6907E+08
1. 1303E+10
7. 4005E+07 2.2687E+09
7. 1935E+07
2. 8720E+08 2.7722E+08
6. 1325E+08
2. 0634E+10
2. 3441E+08 Decay 4.5841E+02 4.2300E+03 3.1390E+03 8.4696E+03 4.5841E+03 1.7322E-02
3. 2443E-01 9.4650E+00 3.0146E+01 2.6318E+01 4.0099E+00 6.9767E+00 2.2586E+01 2.3447E+01 2.3256E-02 1.0527E+02 SSES CR Transport Group Inventory:

Time (h)

=

0.0000 Atmosphere Sump Noble gases (atoms) 3.5980E+10 0.0000E+00 Elemental I (atoms) 9.2677E+10 0.OOOOE+00 Organic I (atoms) 2.8663E+09 0.OOOOE+00 Aerosols (kg) 3.9916E-13 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 3.8428E-15 6.6186E-15 1.0260E-03 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 3.3321E+10 8.5828E+10 2.6545E+09 3.6966E-13 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 2.6590E+09 6.8490E+09 2.1183E+08 2.9499E-14 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Pathway Filtered Transported Time (h)

=

0.0000

EC-RADN-1 128 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Page 47 1.4648E+03 3.7732E+03

1. 1670E+02 1.6251E-20 0.OOOOE+00 0.OOOOE+00 0.0000E+00 0.OOOOE+00 Detailed model information at time (H) =

EAB -

MST Release Doses:

0.0333 Time (h)

=

0.0333 Delta dose (rem)

Accumulated dose (rem)

Whole Body 6.6273E-01 6.6288E-01 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

0.0333 Delta dose (rem)

Accumulated dose (rem)

Whole Body 3.9125E-02 3 9134E-02 Thyroid

3. 7615E+01 3.7624E+01 Thyroid 2.2206E+00 2.2211E+00 Thyroid 7.3581E-01 7.3581E-01 TEDE 1.9308E+00 1.9312E+00 TEDE 1.1399E-01 1.1401E-01 TEDE 2.5742E-02 2.5742E-02 MSLB @ CR MST Release Doses:

Time (h)

=

0.0333 Whole Body Delta dose (rem) 9.4493E-04 Accumulated dose (rem) 9.4493E-04 SSES TB MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

0.0333 Ci kg Atoms Decay SSES TB MS Tunnel Transport Group Inventory:

Time (h)

=

, 0.0333 Atmosphere Sump Noble gases (atoms) 3.2899E-27 0.OOOOE+00 Elemental I (atoms) 8.0858E-27 0.OOOOE+00 Organic I (atoms) 2.5008E-28 0.OOOOE+00 Aerosols (kg) 3.4825E-50 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 3.9512E-51

6. 7883E-51 8.8515E-41 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported.

7.6518E+16 1.9701E+17 6.0932E+15 8.4855E-07

'SSES CR Compartment Nuclide Inventory:

Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-8'5

=

0.0333 Ci 9.5716E-02 8.7463E-01 6.5478E-01 1.7226E+00

9. 5400E-01 3.7014E-06 7.5664E-05
2. 0921E-03 1.7949E-02 7.5635E-03 8.2726E-04 1.4492E-03 4.6334E-03 4.8557E-03 4.8564E-06 kg
7. 7311E-10 8.5859E-11 5.8149E-10 6.4451E-11 2.7662E-10 4.4527E-14 1.7724E-13
1. 1230E-11 2.0104E-13
2. 9748E-12 4.1629E-14
1. 7138E-13 1.6722E-13
3. 7771E-13 1.2378E-11 Atoms 3.5540E+15 3.9171E+14 2.6329E+15 2.8965E+14 1.2339E+15 2.0469E+11 8.0255E+11 5.0851E+13
8. 9680E+II 1.3270E+13 3.0205E+ll 1.2142E+12
1. 1575E+12 2.5848E+12
8. 7698E+13 Decay 4.2641E+11
3. 9155E+12
2. 9185E+12
7. 7755E+12
4. 2571E+12
1. 6298E+07 3.1912E+08
9. 0578E+09 5 3889E+10
2. 9000E+10 3.7076E+09
6. 4729E+09
2. 0824E+10
2. 1721E+10
2. 1634E+07

EC-RADN-1 128 Page 48 Xe-138 1.9934E-02 2.0701E-13 9.0338E+11 9.3271E+10 SSES CR Transport Group Inventory:

Time (h)

=

0.0333 Atmosphere Sump Noble gases (atoms) 1.5988E+14 0.OOOOE+00 Elemental I (atoms) 3.9296E+14 0.OOOOE+00 Organic I (atoms) 1.2153E+13 0.OOOOE+00 Aerosols (kg) 1.6925E-09 O.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 1.6311E-11

2. 8023E-11 4.3017E+00 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 O.OOOOE+00 0.0000E+00 0.OOOOE+00 Transported 1.4546E+14 3.7452E+14 1.1583E+13 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered

4. 1748E+12 1.0505E+13 3.2491E+11 4.5247E-II Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

EAB -

MST Release Doses:

0.0666 Time (h)

=

0.0666 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 6.6288E-01 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

0.0666 Delta dose (rem).

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.9134E-02 Thyroid 0.OOOOE+00 3.7624E+01 Thyroid 0.OOOOE+00 2.2211E+00 Thyroid 7.2291E-01 1.4587E+00 TEDE 0.OOOOE+00 1.9312E+00 TEDE 0.OOOOE+00 1.1401E-01 TEDE 2.5259E-02 5.1001E-02 MSLB @ CR -

MST Release Doses:

Time (h)

=

0.0666 Delta dose (rem)

Accumulated dose (rem)

Whole Body 9.1445E-04 1.8594E-03

,SSES TB MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

0.0666 Ci kg Atoms Decay

'SSES TB MS Tunnel Transport Group Time (h)

=

0.066-6 Atmosphere Noble gases <atoms) 3.4328E-27 Inventory:

'Sump 0.000OE+O0

EC-RADN-1 128 Page 49 Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci) 8.0669E-27 0.0000E+00 2.4949E-28 0.0000E+00 3.4743E-50 0.0000E+00 1-131 (Thyroid) 1-131 (I-CRP2 Thyroid) 3.9458E-51 6.7626E-51 8.7333E-41 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

  • Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 Transported 7.6518E+16 1.9701E+17 6.0932E+15 8.4855E-07 SSES CR Compartment Nuclide Inventory:

Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 0.0666 Ci

9. 3191E-02 8.4.326E-01 6.3688E-01 1.6337E+00
9. 2576E-01 3.6861E-06 8.1372E-05
2. 1496E-03 2.7825E-02 9.3935E-03 7.9580E-04 1.4037E-03 4.4323E-03 4.6889E-03 4.7289E-06 1.7600E-02 kg
7. 5271E-10 8.2780E-11 5.6559E-10
6. 1124E-I1 2.6843E-10 4.4343E-14 1.9062E-13 1.1539E-11 3.1165E-13 3.6945E-12
4. 0046E-14 1.6600E-13 1.5996E-13 3.6474E-13 1.2053E-11 1.8278E-13 Atoms 3.4603E+15 3. 7766E+14 2.5610E+15 2.7470E+14
1. 1974E+15 2.0385E+II 8.6309E+11 5.2248E+13 1.3902E+12 1.6481E+13 2.9056E+11 1.1761E+12 1.1073E+12 2.4960E+12 8.5396E+13
7. 9764E+11 Decay 8.4518E+11
7. 7235E+12
5. 7818E+12
1. 5214E+13
8. 4240E+12 3.2671E+07
6. 6688E+08
1. 8456E+10
1. 5510E+11
6. 6488E+10
7. 3053E+09
1. 2797E+10
4. 0919E+10 4.2878E+10
4. 2882E+07
1. 7637E+11 SSES CR Transport Group Inventory:

Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 1.6245E+14 0.OOOOE+00 3.8174E+14 0.OOOOE+00 1.1806E+13 0.OOOOE+00 1.6441E-09 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid)

1. 5861E-11 2.7183E-11 4.1328E+00 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4546E+14 3.7452E+14 1.1583E+13 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

EC-RADN-1 128 Page 50 Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 8.4627E+12 2.0816E+13 6.4378E+11 8.9651E-11 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

EAB -

MST Release Doses:

0.5000 Time (h)

=

  • 0.5000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 6.6288E-01 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

0.5000 Whole Body Delta dose (rem) 0.OOOOE+00 Accumulated dose (rem) 3.9134E-02 MSLB @ CR -

MST Release Doses:

Thyroid 0.OOOOE+00 3.7624E+01 Thyroid 0.OOOOE+00 2..2211E+00 Thyroid 7.7797E+00 9.2384E+00 TEDE 0.OOOOE+00 1.9312E+00 TEDE 0.OOOOE+00 1.1401E-01

  • TEDE 2.6984E-01 3.2084E-01 Time (h)

=

0.5000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 8.9523E-03 1.0812E-02 SSES TB MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

0.5000 Ci kg Atoms Decay SSES TB MS Tunnel Transport Group Inventory:

Time (h)

=

0.5000 Atmosphere Sump Noble gases (atoms) 5.2536E-27 0.OOOOE+00 Elemental I (atoms) 7.8418E-27 0.OOOOE+00 Organic I (atoms) 2.4253E-28 0.OOOOE+00 Aerosols (kg) 3.3765E-50 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 3.8797E-51 6.4621E-51 7.4097E-41 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6518E+16 1.9701E+17 6.0932E+15 8.4855E-07 SSES CR Compartment Nuclide Inventory:

Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 0.5000 Ci 6.5803E-02 5.2423E-01 4.4398E-01 8.1962E-01 6.2612E-01 3.3599E-06 1.2763E-04 2.5459E-03 7.2562E-02 2.5681E-02 4.8049E-04 9.2660E-04 2.4878E-03 kg 5.3150E-I0

5. 1462E-11
3. 9429E-10
3. 0666E-11
1. 8155E-10
4. 0419E-14
2. 9897E-13 1.3666E-11 8.1273E-13 1.0101E-11 2.4179E-14 1.0958E-13
8. 9786E-14 Atoms 2.4433E+15 2 3478E+14
1. 7853E+15
1. 3782E+14
8. 0986E+14 1.8581E+11
1. 3537E+12
6. 1879E+13
3. 6255E+12 4. 5058E+13
1. 7543E+11
7. 7635E+11 6.2150E+11 Decay 5.3720E+12 4.6327E+13 3.6533E+13 8.3101E+13 5.2494E+13 2.3570E+08 6.8483E+09 1.5551E+11
3. 5081E+12
1. 1237E+12 4.3251E+10
7. 8866E+10 2.3459E+11

EC-RADN-1 128 Page 51 Kr-88 Kr-85 Xe-138 2.9752E-03 3.3449E-06 3.4822E-03 2.3143E-13 1.5838E+12 8.5257E-12 6.-0404E+13 3.6163E-14 1.5781E+11 2. 5957E+11 2.7278E+08 6.7765E+ll SSES CR Transport Group Inventory:

Time (h) =

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 1.7582E+14 0.0000E+00 2.6244E+14 0.OOOOE+00 8.1166E+12 0.OOOOE+00 1.1300E-09 0.0000E+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 1.1029E-11 1.8370E-11 2.4798E+00 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h) =

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4546E+14 3.7452E+14 1.1583E+13 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 6.7737E+13 1.3111E+14 4.0549E+12 5.6461E-10 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

EAB -

MST Release Doses:

2.0000 Time (h)

=

2.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 6.6288E-01 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

2.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.9134E-02 Thyroid 0.OOOOE+00 3.7624E+01 Thyroid 0.OOOOE+00 2.2211E+00 Thyroid 1.2732E+01

2. 1970E+01 TEDE 0.OOOOE+00
1. 9312E+00 TEDE 0.OOOOE+00 1.1401E-01 TEDE 4.3247E-01
7. 5331E-01 MSLB @ CR -

MST Release Doses:

Time (h)

=

2.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 1.0685E-02 2.1497E-02 SSES TB MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

2.0000 Ci kg Atoms Decay SSES TB MS Tunnel Transport Group Inventory:

EC-RADN-1128 Page 52 Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 1.0907E-26 0.OOOOE+00 7.2681E-27 0.OOOOE+00 2.2479E-28 0.OOOOE+00 3.1273E-50 0.0000E+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 3.6826E-51

5. 7404E-51
4. 8101E-41 SSES MST to Environs Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6518E+16 1.9701E+17 6.0932E+15 8.4855E-07 SSES CR Compartment Nuclide Inventory:

Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 2.0000 Ci 1.9732E-02 1.0117E-01 1.2737E-01 7.5307E-02 1.6175E-01 1.7942E-06 1.0843E-04 1.7988E-03 2.5429E-02 2.5626E-02

8. 3811E-05 2.2009E-04 3.3709E-04
6. 1629E-04
1. 0090E-06 1.2778E-05 kg 1.5938E-I0
9. 9314E-12
1. 1311E-10
2. 8176E-12
4. 6901E-11 2.1584E-14 2.5399E-13
9. 6562E-12 2.8482E-13
1. 0079E-11 4.2176E-15 2.6028E-14 1.2166E-14 4 7940E-14
2. 5719E-12
1. 3270E-16 Atoms 7.3268E+14 4.5309E+13
5. 1216E+14 1.2663E+13
2. 0922E+14
9. 9224E+10
1. 1501E+12 4.3722E+13 1.2705E+12 4.4961E+13 3.0601E+10
1. 8440E+11 8.4212E+10 3.2807E+11
1. 8221E+13 5.7907E+08 Decay 1.2984E+13
9. 7503E+13 8.6991E+13 1.4515E+14 1.2077E+14 7.4533E+08 3.2529E+10
6. 1076E+11 1.3160E+13
6. 9798E+12 8.8456E+10
1. 7667E+11 4.4871E+11
5. 5774E+11 6.6066E+08
8. 0076E+11 SSES CR Transport Group Inventory:

Time (h)

=

2.0000 Atmosphere Sump Noble gases (atoms) 1.1005E+14 0.OOOOE+00 Elemental I (atoms) 7.3334E+13 0.OOOOE+00 Organic I (atoms) 2.2680E+12 0.OOOOE+00 Aerosols (kg) 3.1554E-10 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 3.1562E-12 4.9198E-12 4.8533E-01 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4546E+14 3.7452E+14 1.1583E+13 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

-organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10

EC-RADN-1 128 Page 53 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 2.4520E+14 3.0859E+14 9.5441E+12 1.3286E-09 Transported 0.OOOOE+00 0.0000E+00 0.0000E+00 0.0000E+00 Detailed model information at time (H)

=

EAB MST Release Doses:

8.0000 Time (h)

=

8.0000 Whole Body Delta dose (rem) 0.OOOOE+00 Accumulated dose (rem) 6.6288E-01 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

8.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.9134E-02 Thyroid 0.OOOOE+00

3. 7624E+01 Thyroid 0.OOOOE+00 2.2211E+00 Thyroid 5.1015E+00
2. 7072E+01 TEDE 0.OOOOE+00 1.9312E+00 TEDE 0.OOOOE+00
1. 1401E-01 TEDE 1.6864E-01 9.2195E-01 MSLB @ CR -

MST Release Doses:

Time (h)

=

8.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 2.4730E-03 2.3970E-02 SSES TB MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

8.0000 Ci kg Atoms Decay SSES TB MS Tunnel Transport Group Inventory:

Time (h)

=

8.0000 Atmosphere Sump Noble gases (atoms) 2.5589E-26 0.OOOOE+00 Elemental I (atoms) 6.0442E-27 0.OOOOE+00 Organic I (atoms) 1.8693E-28 0.OOOOE+00 Aerosols (kg) 2.5957E-50 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 3.1276E-51

4. 3828E-51 2.2652E-41 SSES MST to Environs Transport Group Inventory:

Time (h)

=

8.0000 Noble gases,(atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6518E+16 1.9701E+17 6.0932E+15 8.4855E-07 SSES CR Compartment Nuclide Inventory:

Time (h)

=

1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m 8.0000 Ci 1.5956E-04 1.4033E-04 8.6267E-04 5.3669E-06 7.2045E-04 4.0067E-08 2.8372E-06 4.4372E-05 1.1391E-04 4.9287E-04 7.7585E-08 kg 1.2888E-12 1.3776E-14 7.6610E-13

2. 0080E-16 2.0890E-13
4. 8200E-16 6.6462E-15 2.3819E-13 1.2759E-15 1.9385E-13 3.9042E-18 Atoms
5. 9247E+12 6.2847E+10 3. 4689E+12 9.0243E+08 9.3186E+ll 2.2158E+09 3.0094E+10
1. 0785E+12 5.6915E+09 8.6474E+11 2.8328E+07 Decay
1. 6218E+13 1.0972E+14 1.0715E+14
1. 5142E+14 1.4445E+14 1.1420E+09 5.8790E+10 1.0328E+12 1.6851E+13 1.2847E+13 9.7999E+IOl

EC-RADN-1 128 Page 54 Kr-85m Kr-87 Kr-88 Kr-85 7.0055E-07 1.1363E-07 1.1346E-06 8.3474E-09 8.2846E-17 5.8695E+08 4.1008E-18 2.8386E+07 8.8260E-17 6.0400E+08 2.1276E-14 1.5074E+11 2. 0705E+11 4.8226E+11 6.3550E+11 8.2680E+08 SSES CR Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 2.1332E+12 0.0000E+00 5.0387E+11 0.0000E+00 1.5584E+10 0.0000E+00 2.1639E-12 0.0000E+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 2.2147E-14 3.1035E-14 1.8884E-03 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Transported 1.4546E+14 3.7452E+14 1.1583E+13 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h) =

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms),

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h) =

8.0000 Noble gases (atoms)

Elemental I *(atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 3.9054E+14 3.7824E+14 1.1698E+13 1.6281E-09 Transported 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Detailed model information at time (H)

=

24.0000 EAB -

MST Release Doses:

Time (h)

=

24.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.0000E+00 6.6288E-01 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

24.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.0000E+00 3.9134E-02 Thyroid 0.0000E+00 3.7624E+01 Thyroid 0.0000E+00 2.2211E+00 Thyroid 3.6358E-02 2.7108E+01 TEDE 0.0000E+00 1.9312E+00 TEDE 0.0000E+00 1.1401E-01 TEDE 1.1688E-03 9.2312E-01 MSLB @ CR -

MST Release Doses:

Time (h)

=

24.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 8.2942E-06 2.3978E-02 SSES TB MS Tunnel Compartment Nuclide Inventory:

Time *(h) =

24.0000 Ci kg Atoms Decay

EC-RADN-1 128 Page 55 SSES TB MS Tunnel Transport 'Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 3.7977E-26 0.OOOOE+00 4.5471E-27 0.0000E+00 1.4063E728 0.0000E+00 1.9466E-50 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 2.3029E-51

2. 8688E-51 9.5762E-42 SSES MST to Environs! Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 Transported 7.6518E+16 1.9701E+17

6. 0932E+15 8.4855E-07 SSES CR Compartment Nuclide Inventory.:

Time (h)

=

24.0000 1-131 1-133 1-135 Xe-131m Xe-133m Xe-133 Xe-135 Kr-85 Ci 4.2033E-10 1.4166E-09

3. 8691E-10.
2. 8744E-13 1.6250E-11 2.6602E-10 1.0001E-09 2.3303E-14 kg 3.3951E-18 1.2581E-18 1.1219E-19 3.4578E-21 3.8066E-20 1.4280E-18
3. 9334E-19 5.9397E-20 Atoms 1.5607E+07 5.6964E+06 5.0044E+05 1.5896E+04 1.7236E+05 6.4658E+06 1.7546E+06 4.2082E+05 Decay
1. 6245E+13
1. 0729E+14
1. 4455E+14
1. 1495E+09
5. 9315E+10
1. 0410E+12 1.2931E+13
8. 2819E+08 SSES CR Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 8.8327E+06 0.OOOOE+00 1.0576E+06 0.OOOOE+00 3.2709E+04 0.OOOOE+00 4.5274E-18 0.0000E+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 4.5496E-20 5.6675E-20 2.2272E-09 Environment to SSES CR -.6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4546E+14

3. 7452E+14 1.1583E+13 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10 SSES CR to Environment CR Exhaust Transport Group Inventory:

Time (h) =

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Pathway Filtered 3.9282E+14 3. 7873E+14 1.1713E+13 Transported 0.OOOOE+00 0.OOOOE+00 0.0000E+O0

EC-RADN-1 128 Aerosols (kg)

Page 56 1.6303E-09 0.OOOOE+00 Detailed model information at time (H) =

96.0000 EAB -

MST Release Doses:

Time (h)

=

96.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body o.OOOOE+00 6.6288E-01 MSLB @ LPZ -

MST Release Doses:

Time (h) =

96.0000 Whole Body Delta dose (rem) 0.OOOOE+00 Accumulated dose (rem) 3.9134E-02 MSLB @ CR - MST Release Doses:.

Thyroid 0.OOOOE+00 3.7624E+01 Thyroid 0.OOOOE+00 2.2211E+00 Thyroid 4.5228E-08 2.7108E+01 TEDE 0.OOOOE+00 1.9312E+00 TEDE

0. 000E+00 1.1401E-01 TEDE 1.4197E-09 9.2312E-01 Time (h)

=

96.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 4.4223E-12 2.3978E-02 SSES TB MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

96.0000 Ci kg Atoms Decay SSES TB MS Time (h) =

Tunnel Transport Group Inventory:

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms).

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 3.8638E-26 0.OOOOE+00 2.6232E-27 0.OOOOE+00 8.1131E-29 0.OOOOE+00 1.1184E-50 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 1.1953E-51 1.2407E-51 1.9578E-42 SSES MST to Environs Transport Group Inventory:

Time (h) =

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6518E+16 1.9701E+17 6.0932E+15 8.4855E-07 SSES CR Compartment Nuclide Inventory:

Time (h)

=

96.0000 Ci kg Atoms Decay SSES CR Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 9.0939E-19 0.OOOOE+00 6.1741E-20 0.OOOOE+00 1.9095E-21 0.OOOOE+00 2.6324E-43 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 2.3896E-45 2.4805E-45 4.6079E-35 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

-Organic I (atoms)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4546E+14 3.7452E+14 1.1583E+13

EC-RADN-1128 Aerosols (kg)

Page 57 0.OOOOE+00 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 3.9282E+14 3.7873E+14 1.1713E+13 1.6303E-09 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

720.0000 EAB 7 MST Release Doses:

Time (h)

= 720.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00

MST Release Doses:

Time (h)

= 720.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.9134E-02 Thyroid 0.OOOOE+00 3.7624E+01 Thyroid 0.OOOOE+00 2.2211E+00 Thyroid 1.6032E-33

2. 7108E+01 TEDE 0.OOOOE+00 1.9312E+00 TEDE 0.0000E+00 1.1401E-01 TEDE 4.9044E-35
9. 2312E-01 MSLB @ CR -

MST Release Doses:

Time (h)

= 720.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 3.4235E-38 2.3978E-02 SSES TB MS Tunnel Compartment Nuclide Inventory:

Time (h)

= 720.0000 Ci kg Atoms Decay SSES TB MS Tunnel Transport Group Inventory:

Time (h)

= 720.0000 Atmosphere Sump Noble gases (atoms) 3.3513E-27 0.OOOOE+00 Elemental I (atoms) 2.6802E-28 0.OOOOE+00 Organic I (atoms) 8.2893E-30 0.OOOOE+00 Aerosols (kg) 1.1420E-51 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 1.1945E-52 1.1945E-52 1.4883E-43 SSES MST to Environs Transport Group Inventory:

Time (h) = 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6518E+16 1.9701E+17 6.0932E+15 8.4855E-07 SSES-CR Compartment Nuclide Inventory.:

Time (h)

= 720.0000 Ci kg Atoms Decay

EC-RADN-1 128 Page 58 SSES CR Transport Group Inventory:

Time (h)

= 720.0000 Atmosphere Sump Noble gases (atoms) 1.8837-236 0.OOOOE+00 Elemental I (atoms) 1.5065-237 0.OOOOE+00 Organic I (atoms) 4.6593-239 0.OOOOE+00 Aerosols (kg) 6.4191-261 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 5.7032-263 5.7032-263 8.3656-253 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.0000E+00 0.OOOOE+00 Transported 1.4546E+14 3.7452E+14 1.1583E+13 1.6130E-09 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1607E+13 2.9886E+13 9.2432E+11 1.2872E-10 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

.Pathway Filtered 3.9282E+14 3.7873E+14 1.1713E+13 1.6303E-09 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 72185 1-131 Summary Time (hr) 0.000 0.033 0.067 0.330 0.500 0.750 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.250 3.500 3.750 4.000 4.250 SSES TB MS Tunnel 1-131 (Curies) 4.7889E+01 1.9695E-42 1.9693E-42 1.9674E-42 1.9662E-42 1.9645E-42 1.9627E-42 1.9609E-42 1.9592E-42 1.9574E-42 1.9557E-42 1.9539E-42 1.9522E-42 1.9504E-42 1.9487E-42 1.9469E-42 1.9452E-42 1.9434E-42 1.9417E-42 1.9400E-42 Environment 1-131 (Curies) 1.0977E-02 4.7900E+01

4. 7900E+01
4. 7900E+01
4. 7900E+01
4. 7900E+01
4. 7900E+01
4. 7900E+01 4.7900E+01
4. 7900E+01
4. 7900E+01 4.7900E+01
4. 7900E+01 4.7900E+01 4.7900E+01
4. 7900E+01 4.7900E+01
4. 7900E+01 4.7900E+01
4. 7900E+01 SSES CR 1-131 (Curies) 2.2523E-05
9. 5716E-02 9.3191E-02
7. 5426E-02
6. 5803E-02
5. 3835E-02 4.4044E-02 3.6034E-02 2.9480E-02 2.4119E-02 1.9732E-02 1.6144E-02 1.3208E-02 1.0806E-02 8.8404E-03 7.2326E-03 5.9172E-03 4.8411E-03 3.9606E-03 3.2403E-03

EC-RADN-1 128 Page 59 4.500 4.750 5.000 5.250 5.500 5.750 6.000 6.250 6.500 6.750 7.000 7.250 7.500 7.750 8.000 8.250 8.500 8.750 9.000 9.250 9.500 9.750 10.000 10.250 24.000 96.000 720.000 1.9382E-42 1.9365E-42 1.9347E-42 1.9330E-42

1. 9313E-42 1.9295E-42
1. 9278E-42
1. 9261E-42 1.9244E-42 1.9226E-42
1. 9209E-42 1.9192E-42
1. 9175E-42
1. 9157E-42
1. 9140E-42
1. 9123E-42
1. 9106E-42 1.9089E-42 1.9072E-42 1.9055E-42 1.9038E-42 1.9020E-42 1.9003E-42 1.8986E-42
1. 8073E-42 1.3959E-42 1.4883E-43 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01
4. 7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4 7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.79.00E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 4.7900E+01 2.6510E-03 2.1629E-03 1.7744E-03 1.4517E-03 1.1877E-03
9. 7168E-04 7.9496E-04
6. 5038E-04 5.3210E-04 4.3533E-04 3.5615E-04 2.9138E-04 2.3839E-04 1.9503E-04 1.5956E-04 1.3054E-04 1.0680E-04 8.7377E-05 7.1486E-05 5.8485E-05 4.7848E-05

.3.9146E-05 3.2027E-05 2.6202E-05 4.2033E-10 3.2854E-35 8.3656-253 Cumulative Dose Summary EAB -

MST Release Time (hr) 0.000 0.033 0.067 0.330 0.500 0.750 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.250 3.500 3.750 4.000 4.250 4.500 4.750 5.000 5.250 5.500 5.750 6.000 6.250 6.500

-6.750 7.000 Thyroid (rem) 0.0000E+00 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 TEDE (rem) 0.0000E+00

1. 9312E+00 1.9312E+00 1.9312E+00 1.9312E+00 1.9312E+00
1. 9312E+00
1. 9312E+00
1. 9312E+00
1. 9312E+00 1.9312E+00 1.9312E+00
1. 9312E+00 1.9312E+00
1. 9312E+00
1. 9312E+00
1. 9312E+00 1.9312E+00
1. 9312E+00 1.9312E+00
1. 9312E+00 1.9312E+00
1. 9312E+00 1.9312E+00 1.9312E+00 1.9312E+00 1.9312E+00
1. 9312E+00
1. 9312E+00 1.9312E+00 1.9312E+00 MSLB @ LPZ Thyroid (rem) 0.0000E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00
2. 2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 MST Rele TEDE (rem)
0. OOOE+00 1.1401E-01
1. 1401E-01
1. 1401E-01 1.1401E-01 1.1401E-01 1.1401E-01 1.1401E-01
1. 1401E-01 1.1401E-01 1.1401E-01 1.1401E-01 1.1401E-01 1.1401E-01 1.1401E-01 1.1401E-01 1.1401E-01
1. 1401E-01
1. 1401E-01
1. 1401E-01
1. 1401E-01 1.1401E-01 1.1401E-01 1.1401E-01
1. 1401E-01 1.1401E-01 1.1401E-01 1.1401E-01
1. 1401E-01 1.1401E-01 1.1401E-01 MSLB @ CR Thyroid (rem) 0.0000E+00 7.3581E-01 1.4587E+00 6 5184E+00 9.2384E+00 1.2597E+01 1.5322E+01 i.7533E+01
1. 9329E+01 2.0787E+01
2. 1970E+01 2.2932E+01 2.3713E+01 2.4348E+01 2.4864E+01 2.5283E+01 2.5624E+01 2. 5901E+01 2.6127E+01 2.6310E+01 2.6459E+01 2.6580E+01 2.6678E+01 2.6758E+01 2.6824E+01 2.6877E+01 2.6920E+01 2.6955E+01 2.6983E+01 2.7007E+01 2.7026E+01 MST Relea TEDE (rem) 0.0000E+00 2.5742E-02
5. 1001E-02 2.2693E-01 3.2084E-01 4.3612E-01 5.2906E-01 6.0407E-01 6.6468E-01
7. 1367E-01 7.5331E-01
7. 8540E-01
8. 1139E-01 8.3245E-01 8.4953E-01 8.6337E-01
8. 7460E-01 8.8371E-01 8.9111E-01
8. 9711E-01
9. 0199E-01 9.0594E-01
9. 0916E-01
9. 1177E-01
9. 1389E-01 9.1562E-01 9.1702E-01 9.1816E-01 9.1909E-01 9.1984E-01 9.2045E-01

EC-RADN-1128 Page 60 7.250 7.500 7.750 8.000 8.250 8.500 8.750 9.000 9.250 9.500

.9.750 10.000 10.250 24.000 96.000 720.000 3.7624E+01 3 7624E+01 3 7624E+01 3 7624E+01 3 7624E+01 3 7624E+01 3 7624E+01 3.7624E+01 3. 7624E+01

3. 7624E+01
3. 7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3.7624E+01 3. 7624E+01 1.9312E+00 1.9312E+00 1.9312E+00 1.9312E+00 1.9312E+00
1. 9312E+00 1 9312E+00 1.9312E+00
1. 9312E+00
1. 9312E+00 1.9312E+00 1.9312E+00
1. 9312E+00
1. 9312E+00
1. 9312E+00
1. 9312E+00
2. 2211E+00 2.2211E+0.0 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 2.2211E+00
2. 2211E+00
2. 2211E+00
2. 2211E+00
2. 2211E+00 2.2211E+00 2.2211E+00 2.2211E+00 1.1401E-01 1.1401E-01 1.1401E-01
1. 1401E-01
1. 1401E-01
1. 1401E-01 1.1401E-01
1. 1401E-01
1. 1401E-01
1. 1401E-01 1.1401E-01 1.1401E-01 1.1401E-01 1.1401E-01
1. 1401E-01
1. 1401E-01 2.7041E+01 2.7053E+01 2.7064E+01 2.7072E+01 2.7079E+01
2. 7084E+01
2. 7089E+01 2.7092E+01
2. 7095E+01
2. 7098E+01 2.7100E+01
2. 7101E+01
2. 7103E+01
2. 7108E+01
2. 7108E+01
2. 7108E+01 9.2095E-01 9.2135E-01 9.2168E-01 9.2195E-01 9.2217E-01 9.2235E-01 9.2249E-01 9.2261E-01 9.2270E-01 9.2278E-01 9.2284E-01 9.2289E-01 9.2294E-01 9.2312E-01 9.2312E-01
9. 2312E-01 Worst Two-Hour Doses EAB -

MST Time (hr) 0.0 Release Whole Body (rem) 6.6288E-01 Thyroid (rem) 3.7624E+01 TEDE (rem) 1.9312E+00

EC-RADN-1128 Page 61 RADTRAD Output TBMST_500cfm.2ptmcDE_1 128.out

EC-RADN-1 128 Page 62

                        1. it##########################################################

RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 13:01:07

    1. i#####it
                                        1. i#####i################itit#####
                                                                                1. 4###############################

File information Plant file

= C:\\Program Files\\radtrad3.03\\EC-RADN-1128 R1 RADTRAD\\TBMST_500cfmpt2mcDEll28.psf Inventory file

= C:\\Program Files\\radtrad3.03\\EC-RADN-l128_RiRADTRAD\\SLBspt2mc.nif Release file

= C:\\Program Files\\radtrad3.03\\EC-RADN-1128_RiRADTRAD\\SLB;RFT Dose Conversion file

= C:\\Program Files\\radtrad3.03\\EC-RADN-1128_RiRADTRAD\\SLBPhase 2.inp Radtrad 3.03 4/15/2001

  • SSES MSLB Nuclide Inventory File:

C:\\Program Files\\radtrad3.03\\EC-RADN-1128_RiRAflTRAD\\SLB-pt2mc.nif Plant Power Level:

1. 0000E+00*

Compartments:

3 Compartment 1:.

SSES MS Tunnel 4.AOOO0E+04 0

0 0

0 0

Compartment 2:

Environment 2

0. OOOOE+00 0

0 0

0 0

Compartment 3:

SSES CR 1

S. 1800E+05 0

0 0

0 Pathways:

4 Pathway 1:

EC-RADN-1128 Page 63 SSES MST to Environs 1

22 Pathway 2:

Environment to SSES CR 2

3 2

Pathway 3:

Environment to SSES CR 2

3 2

Pathway 4:

SSES CR to Environment 3

6391 cfm Normal Intake

-500+10 cfm Unfiltered Inleakage CR Exhaust 2

2 End of Plant Model File Scenario Description Name:

Plant Model Filename:

Source Term:

1 1

1.OOOOE+00 C:\\Program Files\\radtrad3.03\\EC-RADN-1128 R1 RADTRAD\\SLBPhase 2.inp C:\\Program Files\\radtrad3.03\\EC-RADN-1128_RIRADTRAD\\SLB.RFT 0.OOOOE+00 1

9.5000E-01 4.8500E-02 1.5000E-03 1.OOOOE+00 Overlying Pool:

0 o.OOOOE+00 0

0 0

Compartments:

3 Compartment 1:

1 1

0 0

0 0

0 0

0 Compartment 2:

0 1

0 0

0 0

0 0

0

--Compartment 3:

1 1

ý0.

0

EC-RADN-1 128 Page 64 0

0 0

0 0

Pathways:

4 Pathway 1:

0 0

0 0

0 1

3 o. 000E+00 3.3300E-02

7. 2000E+02 0

0 0

0 0

Pathway 2:

0 0

0 0

0 1

3 o.OOOOE+00 6.6600E-02

7. 2000E+02 0

0 0

0 0

0 Pathway 3:

0 0

0 0

0 1

3 o.OOOOE+00

6. 6600E-02 7.2000E+02 0

0 0

0 0*

0 Pathway 4:

0 0

0 0

0 1

3 2.2000E+06 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+O0 o0.0006E+00 o.OOOOE+0O O.OOOOE+O0 O.OOOOE+00 O.OOOOE+00 6.3910E+03 6.3910E+03 o.OOOOE+00

5. 1000E+02
5. 1000E+02 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 o.OOOOE+00 1.OOOOE+02 o.OOOOE+00 0.OOOOE+00 1.OOOOE+02 o.OOOOE+00 0.OOOOE+00 1.OOOOE+02 0.OOOOE+00 0.OOOOE+00 1.OOOOE+02 0.OOOOE+00

EC-RADN-. 128 Page 65 o.0000E+00

5. 0000E-01 7.2000E+02 0

0 0

0 0

6. 9010E+03
6. 9010E+03 0.OOOOE+00 O. 0000E+00 o.0000E+00 o.0OOOE+00 o.O000E+00 o.OOOOE+00 o.OOOOE+00 o.0000E+00 o.OOOOE+00 o.0000E+00 0

Dose Locations:

3 Location 1:

EAB -MST Release 2

1 3

o.OOOOE+00 2.OOOOE+00 7.2000E+02 1

4 o.OOOOE+00 8.OOOOE+00 2.4000E+01 7.2000E+02 0

Location 2:

MSLB @ LPZ 2

1

.5 o.OOOOE+00 8.OOOOE+00 2.4000E+01 9.6000E+01 7.2000E+02 8.3000E-04 8.3000E-04 o.OOOOE+00 3.5000E-04 1.8000E-04 2.3000E-04 0.OOOOE+00 MST Release 4

.0.0000E+00 8.OOOOE+00 2.4000E+01 7.2000E+02 0

Location 3:

MSLB @ CR -

TB 3

0 1

2 0.OOOOE+00 7.2000E+02 1

4 4.9000E-05 3.5000E-05 1.7000E-05

6. 10OOE-06 0.OOOOE+00 3.5000E-04 1.8000E-04 2.3000E-04 0.OOOOE+00 MST Release 3.4700E-04 0.OOOOE+00 0.OOOOE+00 1.OOOOE+00 2.4000E+01 6.OOOOE-01 9.6000E+01 4.OOOOE-01 7.2000E+02 0.OOOOE+00 Effective Volume Location:

1

.3 0.OOOOE+00 6.300OOE-04 6.6600E-02 0.OOOOE+00 7.2000E+02 0.OOOOE+00 Simulation Parameters:

4 0.OOOOE+00 1.OOODE-04

EC-RADN-1128 Page 66 1.0000E-02

.4OOO0E-03 1.0000E-O1 1.OOOOE-02 7.2000E+02 o.oooOE+00 Output Filename:

C:\\Program Files\\radtrad3.o7 1

1 1

0 1

End of Scenario File

EC-RADN-1 128 Page 67 RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 13:01:07

                      1. 4############################################################
                                                                                1. 4###############################

Plant Description Number of Nuclides =

16 Inventory Power =

1.OOOOE+00 MWth Plant Power Level =

1.OOOOE+00 MWth Number of compartments 3

Compartment information Compartment number 1

(source term fraction =

1.OOOOE+00 Name: SSES MS Tunnel Compartment volume =

4.4000E+04 (Cubic feet)

Compartment type is Normal Pathways into and out of compartment 1

Exit Pathway Number 1: SSESMST to Environs Compartment number 2

Name: Environment Compartment.type is Environment Pathways into and out of compartment 2

Inlet Pathway Number 1: SSES MST to Environs Inlet Pathway Number 4: SSES CR to Environment -

CR Exhaust Exit Pathway Number 2: Environment to SSES CR - 6391 cfm Normal Intake Exit Pathway Number 3: Environment to SSES CR -500+10 cfm Unfiltered Inle Compartment number 3

Name: SSES CR Compartment volume =

5.1800E+05 (Cubic feet)

Compartment type is Control Room Pathways into and out of compartment 3

Inlet Pathway Number 2: Environment to SSES CR - 6391 cfm Normal Intake Inlet Pathway Number 3: Environment to SSES CR -500+10 cfm Unfiltered Inle Exit Pathway Number 4: SSES CR to Environment -

CR Exhaust Total number of pathways =

4

EC-RADN-1 128 Page 68

                                                                                                                  1. 4##############

RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 13:01:07

                                                                                                      1. 4####################

Scenario Description

                                                                                                            1. 4#################

Radioactive Decay is enabled Calculation of Daughters is enabled Release Fractions and Timings GAP EARLY IN-VESSEL 0.000000 hr 0.0000.hrs NOBLES 1.OOOOE+00 0.OOOOE+00 IODINE 1.OOOOE+00 0.OOOOE+00 CESIUM 0.OOOOE+00 0.OOOOE+00 TELLURIUM 0.OOOOE+00 0.OOOOE+00 STRONTIUM 0.OOOOE+00 0.0000E+00 BARIUM 0.OOOOE+00 0.OOOOE+00 RUTHENIUM 0.OOOOE+00 0.OOOOE+00 CERIUM 0.OOOOE+00 0.OOOOE+00 LANTHANUM 0.ooo0E+00 0.OOOOE+00 LATE RELEASE 0.0000 hrs 0.OOOOE+00 0.OOOOE+00 0.0000E+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 0.OOOOE+00 0.OOOOE+00 RELEASE MASS (gm) 1.322E-05 4.473E-05

0. OOOE+00 0.OOOE+00
0. OOOE+00
0. 000E+00
0. OOOE+00 0.OOOE+00
0. OOOE+00 Inventory Power =
1. MWt Nuclide Name 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe -135.

Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 Nuclide 1-131 1-133 1-135 Xe-133m Xe-135m Xe-135 Kr-85m Kr-87 Kr-88 Xe-138 Group Specific Inventory (Ci/MWt) 2 2.400E+00 2

2.210E+01 2

1.640E+01 2

4.420E+01 2

2.400E+01 1

1.810E-03 1

3.390E-02 1

9.890E-01 1

3.150E+00 1

2.750E+00 1

4.190E-01 1

7.290E-01 1

2.360E+00 1

2.450E+00 1

2.430E-03 1

1.100E+01 half life (s) 6 956E+05 8.390E+03

7. 533E+04
3. 150E+03 2.423E+04
1. 036E+06
1. 987E+05 4. 553E+05 9.360E+02 3.287E+04
6. 840E+03 1.570E+04 4.680E+03
9. 972E+03 3. 383E+08 8.490E+02 Whole Body DCF (Sv-m3/Bq-s) 1.820E-14 1.120E-13 2.940E-14 1.300E-13 8.294E-14 3.378E-16 1.370E-15 1.560E-15 2.040E-14 1.190E-14 1.500E-18 7.480E-15 4.120E-14 1.020E-13 1.190E-16 5.770E-14 Inhaled Thyroid (Sv/Bq)
2. 920E-07
1. 740E-09
4. 860E-08
2. 880E-I0 8.460E-09
0. OOOE+00 0 OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00
0. OOOE+00 Inhaled Effective (Sv/Bq)
8. 890E-09
1. 030E-10
1. 580E-09 3.550E-11 3.320E-10 0 OOOE+00 0 OOOE+00 0.OOOE+00
0. OOOE+00 0 OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00 0.OOOE+00 Daughter Xe-131m Xe-133m Xe-135m Xe-133 Xe-135 Cs-135 Kr-85 Rb-87 Rb-88 Cs-138 Fraction 0.01 0.03 0.15 1.00 1.00 1.00 0.21 1..00 1.00 1.00
9. 5000E-01 4.8500E-02 1.5000E-03 Daughter none Xe-133 Xe-135 none Cs-135 none none none none none Fraction 0.00 0.97 0.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Daughter Fraction none 0.00 none 0.00 none 0.00 none 0.00 none 0.00 none 0.00 none 0.00 none 0.00 none 0.00 none 0.00 Iodine fractions Aerosol Elemental Organic COMPARTMENT DATA

EC-RADN-1128 Compartment number 1: SSES MS Tunnel Compartment number 2: Environment Compartment number 3: SSES CR PATHWAY DATA Pathway number 1: SSES MST to Environs Pathway Filter:

Removal Data Page 69 Time (hr) 0 0000E+00 3.3300E-02 7.2000E+02 Flow Rate (cfm) 2.2000E+06 o.OOOOE+00 o.0000E+00 Filter Efficiencies (%)

Aerosol Elemental Organic 0.0000E+00 0.OOOOE+00 0.0000E+00 0.0000E+00 0.0OOOE+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 2: Environment to SSES CR -

6391 cfm Normal Intake Pathway Filter:

Removal Data Time (hr) 0.0000E+00 6.6600E-02 7.2000E+02 Flow Rate (cfm) 6.3910E+03 6.3910E+03 0.0000E+00 Filter Efficiencies (%)

Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.OOOOE+00 0.0000E+00 1.0000E+02 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Environment to SSES CR -500+10 cfm Unfiltered Inle Pathway Filter:

Removal Data Time (hr) 0.0000E+00 6.6600E-02 7.2000E+02 Flow Rate (cfm)

5. 1000E+02 5.1000E+02 0.OOOOE+00 Filter Efficiencies (%)

Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.OOOOE+00 0.OOOOE+00 1.OOOOE+02 1.0000E+02 0.OOOOE+00 0.0000E+00 0.OOOOE+00 Pathway number 4: SSES CR to Environment -

CR Exhaust Pathway Filter:

Removal Data Time (hr) 0.0000E+00 5.0000E-01 7.2000E+02 LOCATION DATA Location EAB Flow Rate (cfm)

6. 9010E+03
6. 9010E+03 0.OOOOE+00 MST Release Filter Efficiencies (%)

Aerosol Elemental Organic 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 0.OOOOE+00 0.OOOOE+00 is in.compartment 2

Location X/Q Data Time (hr) 0.00OOE+/-00 2.OOOOE+00 7.2000E+02 X/Q (s

  • m'-3) 8.3000E-04 8.3000E-04 0.OOOOE+00 Location Breathing Rate Data Time (hr)

Breathing 0.OOOOE+00 8.0000E+00 2.4000E+01 7.2000E+02 Location MSLB @ LPZ -

MST Rel Rate (m'3

  • sec^-l) 3.5000E-04 1.8000E-04 2.3000E-04 0.OOOOE+00

.ease is in compartment 2

Location X/Q Data

EC-RADN-1 128 Page 70 Time (hr) 0.0000E+00 8.OOOOE+00 2.4000E+01 9.6000E+01 7.2000E+02 X/Q (s

  • m'-3) 4.9000E-05 3.5000E-05 1.7000E-05
  • 6.1000E-06 o.OOOOE+00 Location Breathing Rate Data Time (hr)

Breathing 0.OOOOE+00 8.OOOOE+00 2.4000E+01 7.2000E+02 Location MSLB @ CR -

TB MST Rate (mW3

  • sec'-1) 3.5000E-04 1.8000E-04 2.3000E-04 0.0000E+00 Release is in co mpartment 3

Location X/Q Data Time (hr) 0.OOOOE+00 6.6600E-02 7.2000E+02 Location Breathing Time (hr) o.OOOOE+00 7.2000E+02 Location Occupancy Time (hr) o.0000E+00 2.4000E+01

9. 6000E+01 7.2000E+02 X/Q (s
  • m'-3) 6.3000E-04 o.0000E+00 0.0000E+00 Rate Data Breathing Rate (mW3
  • sec"-1) 3.4700E-04

.0.0000E+00 Factor Data Occupancy Factor 1.0000E+00 6.0000E-01 4.0000E-01 0.0000E+00 USER SPECIFIED TIME STEP DATA -

SUPPLEMENTAL TIME STEPS Time 0.0000E+00 1.0000E-02 1.0000E-01 7.2000E+02 Time step 1.0000E-04 1.OOOOE-03 1.0000E-02 0.OOOOE+00

EC-RADN-1 128 Page 71

                                                                                      1. 44##############################

RADTRAD Version 3.03 (Spring 2001) run on 10/24/2006 at 13:01:07

  1. 4
  1. 4
  1. 4
  1. 4 44
  1. 4
  • #4#
  1. t
  1. 4#
        1. 4 t#####

4 4

  1. 4#

4 t

4 44#

It 4*4##

4 4

It 4

  1. I It #####

4.

It It It It

  1. 4###################################################################

Dose, Detailed model and Detailed Inventory Output Detailed model information at time (H)

=

0.0000 EAB -

MST Release Doses:

Time (h)

=

0.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 8.3209E-06 8.3209E-06 MSLB @ LPZ - MST Release Doses:

Time (h)

=

0.0000 Whole Body Delta dose (rem) 4.9124E-07 Accumulated dose (rem) 4.9124E-07 MSLB @ CR-TB MST Release Doses:

Time (h)

=

0.0000 Whole Body Delta dose (rem) 2.8079E-14 Accumulated dose (rem) 2.8079E-14 Thyroid 4.3156E-04 4.3156E-04 Thyroid 2.5478E-05 2.5478E-05 Thyroid 1.9833E-11 1.9833E-11

'SSES MS Tunnel Compartment Nuclide Inventory:

TEDE 2.2869E-05 2.2869E-05 TEDE 1.3501E-06 1.3501E-06 TEDE 6.9666E-13

6. 9666E-13 Atoms 8.9094E+16
9. 8953E+15
6. 5931E+16 7.4304E+15 3 1036E+16
1. 0007E+14 3.5949E+14 2.4033E+16
1. 5735E+14
4. 8237E+15
1. 5295E+14
6. 1065E+14
5. 8943E+14 1.3039E+15 4.3871E+16
4. 9840E+14 Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 0.0000 Ci 2.3995E+00 2.2095E+01 1.6396E+01 4.4190E+01 2.3994E+01 1.8096E-03 3.3892E-02
9. 8877E-01
3. 1493E+00 2.7494E+00 4..1890E-01 7.2883E-01 2.3595E+00 2.4494E+00 2.4294E-03 1.0997E+01 kg 1.9381E-08
2. 1690E-09 1.4561E-08
1. 6533E-09
6. 9573E-09
2. 1769E-11
7. 9393E-11
5. 3077E-09
3. 5273E-11
1. 0813E-09
2. 1080E-11
8. 6191E-11
8. 5154E-11
1. 9053E-10.
6. 1923E-09
1. 1421E-10 Decay 4.8836E+07 4.4970E+08 3.3371E+08 8.9939E+08 4.8836E+08 3.6830E+04 6.8981E+05 2. 0124E+07 6.4097E+07 5.5958E+07 8.5259E+06 1.4834E+07 4.8022E+07 4.9853E+07 4.9447E+04 2.2383E+08 SSES MS Tunnel Transport Group Inventory:

Time (h)

=

0.0000 Atmosphere Sump Noble gases (atoms) 7.6500E+16

'0.00ýE+00 Elemental I (atoms) 9.8642E+15 O.OOOOE+00

EC-RADN-1 128 Page 72 Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci) 3.0508E+14 0.OOOOE+00 4.2485E-08 0.000.OE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 4.8147E-09 8.2902E-09 1.0907E+02 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.0000E+00 0.OOOOE+00 Transported 1.7535E+13 2.2611E+12 6.9929E+10 9.7383E-12 SSES CR Compartment Nuclide Inventory:

Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 0.0000 Ci 1.1285E-06 1.0392E-05 7.7115E-06 2 0783E-05

1. 1285E-05 8.5109E-10
1. 5940E-08 4.6504E-07 1.4812E-06 1.2931E-06
1. 9702E-07 3.4279E-07 1.1097E-06 1.1520E-06 1.1426E-09 5.1723E-06 kg
9. 1151E-15
1. 0201E-15
6. 8483E-15
7. 7760E-16 3.2722E-15
1. 0238E-17 3.7340E-17 2.4963E-15 1.6590E-17
5. 0858E-16
9. 9144E-18 4.0537E-17
4. 0050E-17
8. 9612E-17
2. 9124E-15 5.3715E-17 Atoms.
4. 1903E+10 4.6540E+09
3. 1009E+10 3.4946E+09 1.4597E+10 4.7066E+07 1.6907E+08 1.1303E+10 7.4004E+07 2.2687E+09
7. 1935E+07 2.8720E+08 2.7722E+08 6.1325E+08
2. 0634E+10 2.3441E+08 Decay 2.2969E+01 2.1150E+02 1.5695E+02 4.2300E+02 2.2969E+02 1.7322E-02 3.2443E-01 9.4650E+00 3.0146E+01 2.6318E+01 4.0099E+00 6.9767E+00 2.2586E+01 2.3447E+01 2.3256E-02 1.0527E+02

'SSES CR Transport Group Inventory:

Time (h)

=

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 3.5980E+10 0.OOOOE+00 4.6393E+09 0.OOOOE+00 1.4348E+08 0.OOOOE+00 1.9982E-14 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 1.9235E-16 3.3119E-16 5.1300E-05 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 3.3321E+10 4.2965E+09 1.3288E+08 1.8505E-14 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

.Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 2.6590E+09 3.4286E+08 1.0604E+07 1.4767E-15 SSES CR to Environment -

CR Exhaust Transport -Group Inventory:

Pathway

EC-RADN-1 128 Time (h) =

0.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Page 73 Filtered 1.4648E+03 1.8888E+02 5.8417E+00

8. 1352E-22 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

EAB -

MST Release Doses:

0.0333 Time (h)

=

0.0333 Delta dose (rem)

Accumulated dose (rem)

Whole Body 3.6295E-02 3.6303E-02 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

0.0333 Whole Body Delta dose (rem) 2.1427E-03 Accumulated dose (rem) 2.1432E-03 MSLB.@ CR -

TB MST Release Doses:

Thyroid 1.8828E+00 1.8832E+00 Thyroid

1. 1I15E-01 1.1118E-01 Thyroid 3.6830E-02 3.6830E-02 TEDE
9. 9761E-02 9.9784E-02 TEDE 5.8895E-03 5.8909E-03 TEDE 1.2927E-03 1.2927E-03 Time.(h) =

0.0333 Delta dose (rem)

Accumulated dose (rem)

Whole Body

5. 1646E-05 S. 1646E-05 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

0.0333 Ci kg Atoms Decay SSES MS Tunnel Transport Group Inventory:

Time (h)

=

0.0333 Atmosphere Sump Noble gases (atoms) 3.1503E-27 0.OOOOE+00 Elemental I (atoms) 4.0477E-28 0.OOOOE+00 Organic I (atoms) 1.2519E-29 0.OOOOE+00 Aerosols (kg) 1.7433E-51 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 1.9777E-52 3.3969E-52 4.4260E-42 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6489E+16 9.8625E+15 3.0503E+14 4.2478E-08 SSES CR Compartment Nuclide Inventory:

Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-.85m Kr-87 Kr-88 0.0333 Ci

4. 7958E-03
4. 3731E-02 3.2739E-02
8. 6034E-02
4. 7800E-02
3. 6212E-06
6. 8118E-05
1. 9820E-03
6. 3712E-03 5.6007E-03 8.2726E-04 1.4492E-03
4. 6334E-03 4.85'57E-03 kg
3. 8736E-11
4. 2929E-12
2. 9074E-11 3.2189E-12
1. 3860E-11
4. 3562E-14
1. 5957E-13
1. 0639E-11
7. 1360E-14 2.2028E-12
4. 1629E-14
1. 7138E-13
1. 6722E-13
3. 7771E-13 Atoms 1.7807E+14
1. 9585E+13 1.3165E+14 1.4466E+13 6.1826E+13 2. 0026E+11 7.2250E+11 4.8173E+13 3.1833E+11 9.8264E+12 3.0205E+11 1.2142E+12
1. 1575E+12 2.5848E+12 Decay
2. 1365E+10
1. 9577E+11 1.4592E+11 3.8833E+11 2.1330E+11 1.6123E+07 3. 0261E+08 8.8167E+09 2.8186E+10 2.4711E+10 3.7076E+09 6.4729E+09
2. 0824E+10 2.1721E+10

EC-RADN-1 128 Page 74 Kr-85 Xe-138 4.8564E-06 1.9934E-02 1.2378E-11

2. 0701E-13 8.7698E+13 2.1634E+07 9.0338E+11 9.3271E+10 SSES CR Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 1.5310E+14 0.0000E+00 1.9671E+13 0.OOOOE+00 6.0840E+11 0.OOOOE+00 8.4723E-11 0.00O0E+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid)

8. 1641E-13 1.4023E-12
2. 1510E-01 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 Transported 1.4540E+14 1.8748E+13 5.7984E+11 8.0748E-11 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

0.0333 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 4.0856E+12 5.2590E+11 1.6265E+10 2.2650E-12 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

EAB -

MST Release Doses:

0.0666 Time (h)

=

0.0666 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.6303E-02 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

0.0666 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 2.1432E-03 Thyroid 0.OOOOE+00 1.8832E+00 Thyroid 0.OOOOE+00 1.1118E-01 Thyroid 3.6184E-02

7. 3014E-02 TEDE 0.OOOOE+00 9.9784E-02 TEDE 0.OOOOE+00 5.8909E-03 TEDE 1.2683E-03 2.5610E-03 MSLB @ CR TB MST Release Doses:

Time (h)

=

0.0666 Whole Body Delta dose (rem) 4.9784E-05 Accumulated dose (rem) 1.0143E-04 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

0.0666 Ci kg Atoms Decay SSES MS Tunnel Transport Group Inventory:

Time (h)

=

0.0666 Atmosphere Sump

EC-RADN-1 128 Page 75 Noble gases (atoms),

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (.Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci) 3.1542E-27 0.OOOOE+00 4.0383E-28 0*0000E+00 1.2489E-29 0.0000E+00 1.7392E-51 0.OOOOE+00 1-131 (Thyroid).

1-131 (ICRP2 Thyroid) 1.9750E-52 3.3841E-52 4.3669E-42 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 Transported 7.6489E+16 9.8625E+15 3.0503E+14 4.2478E-08 SSES CR Compartment Nuclide Inventory:

Time (h)

=

1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 0.0666 Ci 4.6693E-03 4.2163E-02 3.1844E-02 8.1593E-02 4.6385E-02 3.5299E-06 6.6687E-05 1.9352E-03 6.2696E-03 5.5553E-03 7.9580E-04 1.4037E-03 4.4323E-03 4.6889E-03 4.7289E-06 1.7600E-02 kg 3.7714E-11

4. 1390E-12
2. 8280E-11 3.0528E-12 1.3449E-11 4.2464E-14 1.5622E-13
1. 0388E-11 7.0223E-14 2.1849E-12 4.0046E-14 1.6600E-13 1.5996E-13 3.6474E-13 1.2053E-11
1. 8278E-13 Atoms
1. 7337E+14
1. 8883E+13
1. 2805E+14
1. 3719E+i3
5. 9996E+13
1. 9521E+11
7. 0733E+11
4. 7036E+13 3.1325E+11
9. 7467E+12
2. 9056E+11
1. 1761E+12
1. 1073E+12 2.4960E+12
8. 5396E+13 7..9764E+II Decay 4.2347E+10 3.8617E+11
2. 8909E+11 7.5986E+11 4.2208E+11 3.1975E+07

.6.0142E+08 1.7500E+10

5. 6171E+10
4. 9436E+10 7.3053E+09 1.2797E+10
4. 0919E+10 4.2878E+10 4.2882E+07 1.7637E+11 SSES CR Transport Group Inventory:

Time (h)

=

0.0666 Atmosphere Sump Noble gases (atoms) 1.4926E+14 0.OOOOE+00 Elemental I (atoms) 1.9110E+13 0.OOOOE+00 Organic I (atoms) 5.9103E+11 0.OOOOE+00 Aerosols (kg) 8.2303E-II 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid).

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci)

7. 9389E-13 1.3603E-12
2. 0665E-01 Environment to SSES CR 6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4540E+14 1.8748E+13 5.7984E+11 8.0748E-11 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0'.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

EC-RADN-1 128 Page 76 Time (h)

=

0.0666 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 8.1095E+12 1.0420E+12 3.2228E+10 4.4879E-12 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

EAB -

MST Release Doses:

0.5000 Time (h)

=

0.5000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.6303E-02 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

0.5000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 2.1432E-03 Thyroid 0.OOOOE+00 1.8832E+00 Thyroid 0.OOOOE+00 1.1118E-01 Thyroid 3.8940E-01 4.6241E-01

. TEDE 0.OOOOE+00 9.9784E-02 TEDE 0.OOOOE+00 5.8909E-03 TEDE 1.3537E-02 1.6098E-02 MSLB @ CR -

TB MST Release Doses:

Time (h)

=

0.5000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 4.7893E-04 5.8036E-04 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

0.5000 Ci kg Atoms Decay SSES MS Tunnel Transport Group Inventory:

Time (h)

=

0.5000 Atmosphere Sump Noble gases (atoms) 3.2135E-27 0.OOOOE+00 Elemental I (atoms) 3.9257E-28 0.OOOOE+00 Organic I (atoms) 1.2141E-29 0.OOOOE+00 Aerosols (kg) 1.6903E-51 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc).1-131 (ICRP2 Thyroid)

Total I (Ci) 1.9419E-52 3..2338E-52 3.7056E-42 SSES MST to Environs Transport Group Inventory:

Time (h)

=

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6489E+16 9.8625E+15 3.0503E+14 4.2478E-08 SSES CR Compartment Nuclide Inventory:

Time (h) 1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m

=

0.5000 Ci 3.2970E-03 2..6212E-02 2.2199E-02 4.0935E-02 3.1372E-02 2.5316E-06 5.0425E-05 1.4169E-03

4. 7215E-03 4.8322E-03 4.8049E-04 9.2660E-04 kg 2.6630E-11 2.5731E-12 1.9714E-11 1.5316E-12 9.0963E-12 3.0455E-14 1 1812E-13 7.6059E-12 5.2883E-14 1.9005E-12 2.4179E-14 1.0958E-13 Atoms
1. 2242E+14 1.1739E+13 8.9265E+13
6. 8830E+12 4.0577E+13 1.4000E+11 5.3484E+11 3.4439E+13 2.3590E+11 8.4780E+12
1. 7543E+11 7.7,635E+11 Decay
2. 6916E+11
2. 3164E+12
1. 8267E+12
4. 1504E+12 2 6302E+12
2. 0468E+08 3.9467E+09
1. 1310E+11
3. 6933E+11 3.4833E+11 4.3251E+10
7. 8866E+10

EC-RADN-1 128 6.2150E+11 1.5838E+12

6. 0404E+13 1.5781E+11 Page 77 Kr-87 Kr-88 Kr-85 Xe-138 2.4878E-03 2.9752E-03 3.3449E-06 3.4822E-03 8.9786E-14 2.3143E-13 8.5257E-12 3.6163E-14 2.3459E+11 2.5957E+11 2.7278E+08 6.7765E+11 SSES CR Transport Group Inventory:

Time (h)

=

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 1.0755E+14 0.OOOOE+00 1.3138E+13 0.OOOOE+00 4.0633E+11 0.0000,+00 5.6568E-ll 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 5.5203E-13

9. 1928E-13 1.2401E-01 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic. I (atoms)

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.OOOOE+00 0.0oooE+00 0.OOOOE+00 Transported 1.4540E+14

1. 8748E+13 5.7984E+I1 8.0748E-11 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

0.5000 Noble gases,(atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

0.5000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 5.2177E+13 6.5634E+12 2.0299E+11 2.8264E-11 Transported 0.OOOOE+00 O.OOOOE+00 O.OOOOE+00 O.OOOOE+00 Detailed model information at time (H)

=

EAB -

MST Release Doses:

2.0000 Time (h).=

2.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.6303E-02 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

2.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 2.1432E-03 Thyroid 0.OOOOE+00 1.8832E+00 Thyroid 0.OOOOE+00 1.1118E-01 Thyroid 6.3730E-01 1.0997E+00 TEDE 0.OOOOE+00 9.9784E-02 TEDE 0.0000E+00 5.8909E-03 TEDE

2. 1671E-02 3.7769E-02 MSLB @ CR -

TB MST Release Doses:

Time (h)

=

2.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 5.5960E-04 1.1400E-03 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

2.,0000 Ci kg Atoms Decay

EC-RADN-1 128 Page 78 SSES MS Tunnel Transport Group Inventory:

Time (h)

=

2.0000 Atmosphere Sump Noble gases (atoms) 3.4347E-27 0.OOOOE+00 Elemental I (atoms) 3.6387E-28 0.OOOOE+00 Organic I (atoms) 1.1254E-29 0.OOOOE+00 Aerosols (kg) 1.5656E-51 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 1.8433E-52 2.8729E-52 2.4065E-42 SSES MST to Environs Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6489E+16 9.8625E+15

3. 0503E+14 4.2478E-08 SSES CR Compartment Nuclide Inventory:

Time (h)

=

1-131 1-132 1-133 1-134 1-135 Xe-131m Xe-133m Xe-133 Xe-135m Xe-135 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 Xe-138 2.0000 Ci 9.8868E-04 5.0585E-03 6.3684E-03 3.7611E-03

8. 1045E-03 7.9984E-07 1.8452E-05 4.7567E-04 1.2801E-03 2.2462E-03 8.3811E-05 2.2009E-04 3.3709E-04 6.1629E-04 1.0090E-06 1.2778E-05 kg.

7.9857E-12 4.9657E-13 5.6556E-12 1.4072E-13 2.3499E-12 9.6219E-15 4.3225E-14 2.5534E-12 1.4338E-14 8.8347E-13 4.2176E-15 2.6028E-14 1.2166E-14 4.7940E-14 2.5719E-12 1.3270E-16 Atoms 3.6711E+13 2.2655E+12 2.5608E+13 6.3241E+11 1.0483E+13 4.4232E+10

1. 9572E+11
1. 1562E+13
6. 3960E+10 3.9410E+12 3 0601E+10 1.8440E+11 8.4212E+10 3.2807E+11 1.8221E+13 5.7907E+08 Decay 6.5057E+11 4.8751E+12 4.3496E+12 7.2491E+12 6.0511E+12 5.0380E+08 1.0298E+10
2. 8490E+11
8. 9427E+11
1. 0369E+12
8. 8456E+10 1.7667E+11 4.4871E+11 5.5774E+11 6.6066E+08 8.0076E+11 SSES CR Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 3.4656E+13 0.0000E+00 3.6714E+12 0.0000E+00 1.1355E+11 0.0000E+00 1.5797E-11 0.0000E+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 1.5798E-13 2.4622E-13 2.4281E-02 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Transported 1.4540E+14 1.8748E+13 5.7984E+11 8.0748E-11 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.0000E+00 0.0000E+00 0.0000E+00 0.-000OE+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12

EC-RADN-1 128 Page 79 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

2.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 1.2939E+14 1.5449E+13 4.7780E+11 6.6511E-11 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.0000OE+00 Detailed model information at time (H)

=

EAB MST Release Doses:

8.0000 Time (h)

=

8.0000 Whole Body Delta dose (rem) 0.OOOOE+00 Accumulated dose (rem) 3.6303E-02 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

8.0000 Whole Body Delta dose (rem) 0.OOOOE+00 Accumulated dose (rem) 2.1432E-03 MSLB @ CR -

TB MST Release Doses:

Thyroid 0.OOOOE+00 1.8832E+00 Thyroid

0. OOOOE+00
1. 1118E-01 Thyroid 2.5536E-01 1.3551E+00 TEDE 0.OOOOE+00 9.9784E-02 TEDE 0.OOOOE+00 5.8909E-03 TEDE 8.4465E-03
4. 6215E-02 Time (h)

=

8.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 1.2919E-04 1.2692E-03 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

8.0000 Ci kg Atoms Decay SSES MS Tunnel Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 4.0353E-27 0.0000E+00 3.0263E-28 0.OOOOE+00 9.3596E-30 0.OOOOE+00 1.2996E-51 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 1.5656E-52

2. 1936E-52 1.1337E-42 SSES MST to Environs Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6489E+16 9.8625E+15 3.0503E+14 4.2478E-08 SSES CR Compartment Nuclide Inventory:

Time (h)

=

1-131 1-132 1-133

.1-134 1-135 Xe-131m Xe-133m Xe-133 xe-135m Xe-135 8.0000 Ci 7.9948E-06

7. 0164E-06 4.3133E-05 2.6804E-07 3.6097E-05
7. 7891E-09 2.4171E-07 5.3059E-06 5.7076E-06 2.9738E-05 kg 6.4575E-14
6. 8878E-16 3.8305E-14 1.0029E-17 1.0467E-14 9.3701E-17 5.6621E-16 2.8482E-14 6.3928E-17 1.1696E-14 Atoms
2. 9685E+11 3.1424E+09
1. 7344E+11
4. 5071E+07 4.6690E+10 4.3075E+08 2.5638E+09 1.2896E+11 2.8517E+08 5.2174E+10 Decay 8.1260E+11 5.4862E+12
5. 3576E+12
7. 5626E+12
7. 2374E+12
6. 4020E+08
1. 3724E+10
3. 6909E+11
1. 0794E+12 1.4759E+12

EC-RADN-1 128 Kr-83m Kr-85m Kr-87 Kr-88 Kr-85 7.7585E-08 7.0055E-07 1.1363E-07 1.1346E-06 8.3474E-09 3.9042E-18 8.2846E-17 4.1008E-18 8.8260E-17 2.1276E-14 2.8328E+07 5.8695E+08 2 8386E+07 6.0400E+08 1.5074E+1I Page 80

9. 7999E+10 2.0705E+11 4.8226E+11 6.3550E+11 8.2680E+08 SSES CR Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 3.3640E+11 0.OOOOE+00 2.5228E+10 0.OOOOE+00 7.8026E+08 0.OOOOE+00 1.0834E-13 0.OOOOE+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 1.1086E-15 1.5533E-15 9.4510E-05 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4540E+14 1.8748E+13 5.7984E+11 8.0748E-11 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I. (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

8.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 1.6524E+14 1.8936E+13 5.8564E+11 8.1509E-11 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H)

=

24.0000 EAB MST Release Doses:

Time (h)

=

24.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.6303E-02 MSLB @ LPZ -

MST Release Doses:

Time (h)

=

24.0000 Whole Body Delta dose (rem) 0.OOOOE+00 Accumulated dose (rem) 2.1432E-03 MSLB @ CR TB MST Release Doses:

Time (h)

=

24.0000 Whole Body Delta dose (rem) 4.2770E-07 Accumulated.dose (rem) 1.2696E-03 Thyroid 0.OOOOE+00 1.8832E+00 Thyroid 0.OOOOE+00 1.1118E-01 Thyroid 1.8200E-03 1.3569E+00 TEDE 0.OOOOE+00 9.9784E-02 TEDE 0.OOOOE+00 5.8909E-03 TEDE 5.8519E-05 4.6274E-02 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Decay

EC-RADN-1128 Page 81 SSES MS Tunnel Transport Group Inventory:

Time (h)

=

24.0000 Atmosphere Sump Noble gases (atoms) 4.4915E-27 0.OOOOE+00 Elemental I (atoms)

.2.2771E-28 0.OOOOE+00 Organic I (atoms) 7.0425E-30 0.OOOOE+00 Aerosols (kg) 9.7479E-52 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 1.1530E-52 1.4360E-52 4. 7917E-43 SSES MST to Environs Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway

.Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6489E+16 9.8625E+15 3.0503E+14 4.2478E-08 SSES CR Compartment Nuclide Inventory:

Time.(h) =

24.0000 1-131 1-133 1-135 Xe-133m Xe-133 Xe-135 Kr-85 Ci

2. 1061E-1I
7. 0831E-11
1. 9386E-11
1. 0404E-12
2. 1212E-11 5.4284E-11 2.3303E-14 kg
1. 7011E-19 6.2903E-20
5. 6210E-21 2.4371E-21
1. 1387E-19
2. 1350E-20
5. 9397E-20 Atoms 7.8200E+05 2.8482E+05 2.5074E+04 1.1035E+04
5. 1558E+05 9.5240E+04 4.2082E+05 Decay
8. 1393E+11 5.3645E+12 7.2427E+12 1.3767E+10
3. 7001E+11 1.4809E+12 8.2819E+08 SSES CR Transport Group Inventory:

Time (h)

=

24.0000 Atmosphere Sump Noble gases (atoms) 1.0446E+06 0.OOOOE+00 Elemental I (atoms) 5.2960E+04 0.0060E+00 Organic I (atoms) 1.6380E+03 0.OOOOE+00 Aerosols (kg) 2.2672E-19 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci) 2.2779E-21 2.8370E-21 1.1145E-10 Environment to SSES CR 6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4540E+14 1.8748E+13 5.7984E+11 8.0748E-11 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 O.OOOOE+00 0.OOOOE+00 0.0000E+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

24.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Pathway Filtered 1.6558E+14 1.8960E+13 5.8640E+11 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+O0

EC-RADN-1 128 Aerosols (kg)

Page 82 8.1614E-11 0.OOOOE+00 Detailed model information at time. (H) =

96.0000 EAB -

MST Release Doses:

Time (h) =

96.0000 Whole Body Delta dose (rem) 0.OOOOE+00 Accumulated dose (rem) 3.6303E-02 MSLB @ LPZ - MST Release Doses:

Time (h)

=

96.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 2.1432E-03 Thyroid 0.OOOOE+00 1.8832E+00 Thyroid 0.OOOOE+00

1. 1118E-01 Thyroid 2.2645E-09 1.3569E+00 TEDE 0.OOOOE+00 9.9784E-02 TEDE 0.OOOOE+00 5.8909E-03 TEDE
7. 1085E-11 4.6274E-02 MSLB @ CR -

TB MST Release Doses:

Time (h)

=

96.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 2.2450E-13 1.2696E-03 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h)

=

96.0000 Ci kg Atoms Decay SSES MS Tunnel Transport Group Inventory:

Time (h) =

96.0000 Atmosphere Sump Noble gases. (atoms) 4.2196E-27 0.OOOOE+0 Elemental I (atoms) 1.3142E-28 0.OOOOE+0 Organic I (atoms) 4.0647E-30 0.OOOOE+0 Aerosols (kg) 5.6034E-52 0.OOOOE+0 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 0 0

0 0

5.9882E-53 6.2154E-53 9.8035E-44 Total I (Ci)

SSES MST to Environs Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6489E+16 9.8625E+15 3.0503E+14 4.2478E-08 SSES CR Compartment Nuclide Inventory:

Time (h)

=

96.0000 Ci kg Atoms Decay SSES CR Transport Group Inventory:

Time (h) =

96.0000 Atmosphere Sump Noble gases (atoms) 9.9314E-20 0.OOOOE+00 Elemental I (atoms) 3.0932E-21 0.OOOOE+00 Organic I (atoms) 9.5666E-23 0.OOOOE+00 Aerosols (kg) 1.3188E-44 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci)

1. 1972E-46 1.2426E-46 2.3074E-36 Environment to SSES CR - 6391 cfm Normal Intake Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.4540E+14 1.8748E+13 5.7984E+11

EC-RADN-1128 Aerosols (kg)

Page 83 0.00-OOE+00 8..0748E-11 Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered.

0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12 SSES CR to Environment -

CR Exhaust Transport Group Inventory:

Time (h)

=

96.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 1.6558E+14 1.8960E+13 5.8640E+11 8.1614E-11 Transported 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Detailed model information at time (H) =

720.0000 EAB -

MST Release Doses:

Time (h)

= 720.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 3.6303E-02 MSLB @ LPZ -

MST Release Doses:

Time (h)

= 720.0000 Delta dose (rem)

Accumulated dose (rem)

Whole Body 0.OOOOE+00 2.1432E-03 Thyroid 0.OOOOE+00 1.8832E+00 Thyroid 0.OOOOE+00 1.1118E-01 Thyroid 8.0315E-35 1.3569E+00 TEDE 0.OOOOE+00 9..9784E-02 TEDE 0.OOOOE+00 5.8909E-03 TEDE 2.4570E-36 4.6274E-02 MSLB @ CR -

TB MST Release Doses:

Time (h)

= 720.0000 Whole Body Delta dose (rem) 1.7428E-39 Accumulated dose (rem) 1.2696E-03 SSES MS Tunnel Compartment Nuclide Inventory:

Time (h)

= 720.0000 Ci kg Atoms Decay SSES MS Tunnel Transport Group Inventory:

Time (h)

= 720.0000 Atmosphere Sump Noble gases (atoms) 1.8971E-27 0.OOOOE+00 Elemental I (atoms) 1.3429E-29 0.OOOOE+00 Organic I (atoms) 4.1533E-31 0.OOOOE+00 Aerosols (kg) 5.7220E-53 0.OOOOE+00 Dose Effective (Ci/cc) 1-131 (Thyroid)

Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid)

Total I (Ci)

5. 9851E-54
5. 9851E-54 7.4570E-45 SSES MST to Environs Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I *(atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 7.6489E+16.

9.8625E+15 3.0503E+14 4.2478E-08

'SSES CR Compartment Nuclide Inventory:

Time (h)

= 720.4DOOO Ci kg Atoms Decay

EC-RADN-1 128 Page 84 SSES CR Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Dose Effective (Ci/cc)

Dose Effective (Ci/cc)

Total I (Ci)

Atmosphere Sump 1.0663-236 0.OOOOE+00 7.5483-239 0.00OOE+00 2.3345-240 0.0000E+00 3.2163-262 0.0000E+00 1-131 (Thyroid) 1-131 (ICRP2 Thyroid) 2.8576-264 2.8576-264 4.1915-254 Environment to SSES CR -

6391 cfm Normal Intake Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.0000E+00 Transported 1.4540E+14 1.8748E+13

5. 7984E+11 8.0748E-II Environment to SSES CR -500+10 cfm Unfiltered Inle Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

.Pathway Filtered.

0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 Transported 1.1603E+13 1.4961E+12 4.6271E+10 6.4437E-12 SSES CR to Environment CR Exhaust Transport Group Inventory:

Time (h)

= 720.0000 Noble gases (atoms)

Elemental I (atoms)

Organic I (atoms)

Aerosols (kg)

Pathway Filtered 1.6558E+14 1.8960E+13 5.8640E+11 8.1614E-11 Transported 0..OOOOE+00 0.OOOOE+00 0.OOOOE+00 0.OOOOE+00 72185 1-131 Summary Time (hr) 0.000 0.033 0.067 0.330 0.500 0.750 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.250 3.500 3.750 4.000 4.250 SSES MS Tunnel 1-131 (Curies) 2.3995E+00

9. 8681E-44
9. 8670E-44
9. 8577E-44
9. 8516E-44
9. 8428E-44 9.8340E-44
9. 8252E-44
9. 8164E-44
9. 8076E-44
9. 7988E-44 9.7900E-44 9.7812E-44 9.7724E-44 9.7637E-44 9.7549E-44 9.7462E-44 9.7375E-44 9.7287E-44 9.7200E-44

. Environment 1-131 (Curies) 5.50OOE-04 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00

2. 4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2,.4000E+00 2.4-00E+00 2.4000E+00

.2.4000E+00 SSES CR 1-131 (Curies)

1. 1285E-06
4. 7958E-03
4. 6693E-03
3. 7792E-03 3.2970E-03
2. 6974E-03 2.2068E-03
1. 8055E-03 1.4771E-03
1. 2085E-03 9.8868E-04
8. 0887E-04.
6. 6176E-04.

5.4141E-04 4.4294E-04

3. 6239E-04
2. 9648E-04 2.4256E-04
1. 9844E-04 1.6235E-04

EC-RADN-1 128 Page 85 4.500 4.750 5.000 5.250 5.500 5.750 6.000 6.250 6.500 6.750 7.000 7.250 7.500 7.750 8.000 8.250 8.500 8.750 9.000 9.250 9.500 9.750 0.000 10.250 24.000 96.000 720.000

9. 7113E-44 9.7026E-44 9.6939E-44 9.6852E-44 9.6765E-44 9.6678E-44 9.6592E-44 9.6505E-44
9. 6419E-44 9.6332E-44
9. 6246E-44
9. 6160E-44 9.6073E-44
9. 5987E-44
9. 5901E-44
9. 5815E-44 9.5729E-44 9.5644E-44 9.5558E-44
9. 5472E-44 9.5387E-44
9. 5301E-44
9. 5216E-44
9. 5130E-44 9.0552E-44 6.9940E-44 7.4570E-45 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4'000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 2.4000E+00 1.3283E-04 1.0867E-04 8.8906E-05 7.2737E-05 5.9508E-05 4.8685E-05
3. 9831E-05 3.2587E-05 2.6660E-05
2. 1812E-05 1.7845E-05 1.4599E-05 1.1944E-05 9.7720E-06 7.9948E-06 6.5408E-06 5.3512E-06 4.3780E-06 3.5818E-06 2.9304E-06 2.3974E-06
1. 9614E-06 1.6047E-06 1.3128E-06 2.1061E-11 1.6461E-36 4.1915-254 Cumulative Dose Summary EAB MST Re Time Thyroid (hr) 0.000 0.033 0.067 0.330 0.500 0.750 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.250 3.500 3.750 4.000 4.250 4.500 4.750 5.000 5.250 5.500 5.750 6.000 6.250 6.500 6.750 7.000 (rem) 0.0000E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00
1. 8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 0.0 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 lease MSLB @ LPZ TEDE Thyroid (rem)

(rem) 000E+00 0.0000E+00 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784E-02 1.1118E-01 784,E-02 1.1118E-01 784E-02 1.1118E-01 MST Rele TEDE (rem) 0.0000E+00 5.8909E-03 5.8909E-03 5.8909E-03

5. 8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 MSLB @ CR -

TB MST Re Thyroid TEDE (rem)

(rem) 0.0000E+00 0.0000E+00 3.6830E-02 1.2927E-03 7.3014E-02 2.5610E-03 3.2627E-01 1.1389E-02 4.6241E-01 1.6098E-02 6.3052E-01 2.1876E-02 7.6691E-01 2.6533E-02 8.7761E-01 3.0292E-02 9.6748E-01 3.3328E-02 1.0404E+00 3.5783E-02 1.0997E+00 3.7769E-02 1.1478E+00 3.9376E-02 1.1870E+00 4.0678E-02 1.2187E+00 4.1733E-02 1.2446E+00 4.2588E-02 1.2655E+00 4.3281E-02 1.2826E+00 4.3844E-02 1.2965E+00 4.4300E-02 1.3077E+00 4.4671E-02 1.3169E+00 4.4971E-02 1.3244E+00 4.5215E-02 1.3304E+00 4.5414E-02 1.3354E+00 4.5575E-02 1.3394E+00 4.5705E-02 1.3426E+00 4.5812E-02 1.3453E+00 4.5898E-02 1.3474E+00 4.5968E-02 1.3492E+00 4.6025E-02 1.3506E+00 4.6072E-02 1.3518E+00 4.6109E-02 1.3527E+00 4.6140E-02

EC-RADN-1 128 Page 86 7.250 7.500 7.750 8.000 8.250 8.500 8.750 9.000 9.250 9.500

.9.750 10.000 10.250 24.000 96.000 720.000 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E+00 1.8832E-00 1.8832E+00 1.8832E+00 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 9.9784E-02 1.1118E-01 1.1118E-01

1. 1118E-01 1.1118E-01
1. 1118E-'01 1.1118E-01 1.1118E-01 1.1l18E-01 1.1118E-01 1.1118E-01 1.1118E-01 1.1118E-01 1.1118E-01 1.1118E-01 1.1118E-01 1.1118E-01 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 5.8909E-03 1.3535E+00 1.3541E+00 1.3547E+00 1.3551E+00 1.3554E+00 1.3557E+00 1.3559E+00 1.3561E+00 1.3562E+00 1.3564E+00 1.3565E+00 1.3565E+00 1.3566E+00 1.3569E+00 1.3569E+00 1.3569E+00 4.6165E-02 4.6185E-02 4.6202E-02 4.6215E-02 4.6226E-02 4.'6235E-02 4.6242E-02 4.6248E-02 4.6253E-02 4.6257E-02 4.6260E-02 4.6262E-02 4.6264E-02 4.6274E-02 4.6274E-02 4.6274E-02
                                                                                                                        1. W#######

Worst Two-Hour Doses EAB -

MST Time (hr) 0.0 Release Whole Body (rem) 3.6303E-02 Thyroid (rem) 1.8832E+00 TEDE (rem) 9.9784E-02 to PLA-6124 PPL Drawings E-105004, Sheets 3 and 6

THIS PAGE IS AN OVERSIZED DRAWING OR

FIGURE, THAT CAN BE VIEWED AT THE RECORD TITLED:

DRAWING-NO. E105004, SHEET NO. 3 REV. 26, GENERAL FLOOR PLANS ELS 683-0,699-0,714-0 & 716-3" WITHIN THIS PACKAGE...

D-01

THIS PAGE IS AN OVERSIZED DRAWING OR

FIGURE, THAT CAN BE VIEWED AT THE RECORD TITLED:

DRAWING NO. E105004, SHEET NO. 6 REV. 23, SUSQUEHANNA S.E.S.

UNIT 1/ UNIT 2, GENERAL FLOOR PLAN EL'S 779'-1", 799'-1" & 806'-0" WITHIN THIS PACKAGE... OR D-02