MONTHYEARML0610105472006-04-10010 April 2006 Technical Specifications Pages Re Relocation of the Component Identification from the Overcurrent Protective Device Lists in TS 3/4.8.4.1, Primary Containment Penetration Conductor Overcurrent Protective Devices, and TS 3/4.8.4.5 Project stage: Other ML0608903882006-04-10010 April 2006 License Amendment, Issuance of Amendment Deletion of Component Identification for Overcurrent Protective Devices Project stage: Approval 2006-04-10
[Table View] |
|
---|
Category:Technical Specifications
MONTHYEARML23341A1372024-01-16016 January 2024 Issuance of Amendment No. 235 Revise Trip and Standby Auto-Start Logic Associated with Safety Related Heating, Ventilation and Air Conditioning ML23192A8212023-08-14014 August 2023 and Salem Nuclear Generating Station, Unit Nos. 1 and 2 - Issuance of Amendment Nos. 234, 347, and 329 Revise Technical Specifications to Delete Meteorological Tower Location ML21050A0022021-03-12012 March 2021 Issuance of Amendment No. 227 Revise Technical Specifications to Adopt Technical Specifications Task Force Traveler TSTF-582, RPV WIC Enhancements ML21047A3132021-03-10010 March 2021 Issuance of Amendment No. 226 Revise Emergency Core Cooling System Technical Specification for High Pressure Coolant Injection System Inoperability (Non-Proprietary) ML20281A6132020-11-0909 November 2020 Issuance of Amendment No. 225 Revise Technical Specification Actions for Suppression Pool Cooling ML20231A6322020-09-29029 September 2020 Issuance of Amendment No. 224 Regarding Adoption of 10 CFR 50.69, Risk Informed Categorization and Treatment of Structures, Systems and Components of Nuclear Power Reactors ML20034E6172020-02-27027 February 2020 and Salem Nuclear Generating Station, Unit Nos. 1 and 2 - Issuance of Amendment Nos. 222, 333, and 314 Deletion of Facility Operating License Conditions Related to Decommissioning Trust Provisions and License Transfer ML19186A2052019-08-0606 August 2019 Issuance of Amendment No. 217 Remote Shutdown System ML19065A1562019-03-27027 March 2019 Issuance of Amendment No. 215 Inverter Allowed Outage Time Extension ML17317A6052017-12-13013 December 2017 Issuance of Amendment, License Amendment Request to Adopt Technical Specifications Task Force (TSTF) Traveler TSTF-535 ML17047A0202017-03-21021 March 2017 Issuance of Amendment to Delete Technical Specification Action Statement 3.4.2.1.b Associated with Stuck Open Safety/Relief Valves ML17053A1782017-03-15015 March 2017 Issuance of Amendment to Permit Operability of Low Pressure Coolant Injection While Aligned to Shutdown Cooling ML16270A0382016-10-13013 October 2016 Issuance of Amendment No. 200 Safety Limit Minimum Critical Power Ratio Change ML15286A0912015-11-30030 November 2015 Issuance of Amendment Adoption of Technical Specifications Task Force Traveler-522 ML15141A2712015-06-17017 June 2015 and Salem Nuclear Generating Station, Unit Nos.1 and 2, Issuance of Amendments Update of Appendix B to the Renewed Facility Operating Licenses ML14108A3992014-12-18018 December 2014 Issuance of Amendment Request to Relocate Flood Protection Technical Specification to the Technical Requirements Manual LR-N14-0189, License Amendment Request to Revise Technical Specifications to Adopt TSTF-522, Revision 0, Revise Ventilation System Surveillance Requirements to Operate for 10 Hours Per Month Using the Consolidated Line Item Improvement Process2014-11-25025 November 2014 License Amendment Request to Revise Technical Specifications to Adopt TSTF-522, Revision 0, Revise Ventilation System Surveillance Requirements to Operate for 10 Hours Per Month Using the Consolidated Line Item Improvement Process ML14108A3122014-07-29029 July 2014 Issuance of Amendment Request to Relocate Safety Relief Valve Position Instrumentation to Technical Requirements Manual LR-N13-0155, License Amendment Request to Relocate the Flood Protection Technical Specification to the Technical Requirements Manual2013-09-0505 September 2013 License Amendment Request to Relocate the Flood Protection Technical Specification to the Technical Requirements Manual LR-N13-0143, License Amendment Request to Relocate Safety/Relief Valve Position Instrumentation to the Technical Requirements Manual2013-07-30030 July 2013 License Amendment Request to Relocate Safety/Relief Valve Position Instrumentation to the Technical Requirements Manual LR-N12-0067, License Amendment Request to Correct Technical Specification and Facility Operating License Editorial Items2012-03-0101 March 2012 License Amendment Request to Correct Technical Specification and Facility Operating License Editorial Items LR-N12-0028, Supplement to Application for Tech Spec Change TSTF-477 Rev. 3, Add Action for Two Inoperable Control Room AC Subsystems to the Tech Specs Using Consolidated Line Item Improvement Process2012-01-26026 January 2012 Supplement to Application for Tech Spec Change TSTF-477 Rev. 3, Add Action for Two Inoperable Control Room AC Subsystems to the Tech Specs Using Consolidated Line Item Improvement Process ML0527202982011-07-20020 July 2011 Current Facility Operating License NPF-57, Tech Specs, Revised 12/18/2017 ML11116A1482011-07-20020 July 2011 Issuance of Renewed Facility Operating License No. NPF-57 for Hope Creek Generating Station LR-N11-0208, Revised License Condition- Salem-Hope Creek Cyber Security Plan Supplement Submittal2011-07-0606 July 2011 Revised License Condition- Salem-Hope Creek Cyber Security Plan Supplement Submittal ML1109801512011-04-19019 April 2011 Correction to Amendment No. 187 Regarding Relocation of Specific Surveillance Frequencies to a Licensee-Controlled Program Based on Technical Specification Task Force (TSTF) Change TSTF-425 LR-N11-0098, Format and Editorial Corrections to Technical Specification Pages Issued with Amendment 1872011-04-0404 April 2011 Format and Editorial Corrections to Technical Specification Pages Issued with Amendment 187 LR-N11-0068, Application for Technical Specification Change TSTF-477, Revision 3, Add Action for Two Inoperable Control Room AC Subsystems to the Technical Specifications Using Consolidated Line Item Improvement Process2011-02-28028 February 2011 Application for Technical Specification Change TSTF-477, Revision 3, Add Action for Two Inoperable Control Room AC Subsystems to the Technical Specifications Using Consolidated Line Item Improvement Process LR-N10-0310, Supplement to License Amendment Request H09-06 to Adopt TSTF-460, Rev. 0, Control Rod Scram Times.2010-08-19019 August 2010 Supplement to License Amendment Request H09-06 to Adopt TSTF-460, Rev. 0, Control Rod Scram Times. ML1015907132010-07-21021 July 2010 Issuance of Amendment Control Rod Notch Testing Frequency LR-N10-0097, License Amendment Request: Emergency Diesel Generators a and B Allowed Outage Time Extension2010-03-29029 March 2010 License Amendment Request: Emergency Diesel Generators a and B Allowed Outage Time Extension LR-N10-0015, Application for Technical Specification Change Regarding Risk-Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program2010-03-19019 March 2010 Application for Technical Specification Change Regarding Risk-Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program ML0932700232009-12-0808 December 2009 Issuance of Amendment Mode Change Limitations ML0934302422009-12-0101 December 2009 License Amendment Request to Adopt TSTF-460, Revision 0, Control Rod Scram Times. ML0916006832009-07-15015 July 2009 Issuance of Amendment Technical Specification Requirements Related to Snubbers LR-N09-0001, License Amendment Request to Eliminate Unnecessary Reporting Requirements in the Operating License and the Administrative Controls Section of the Technical Specifications2009-01-0505 January 2009 License Amendment Request to Eliminate Unnecessary Reporting Requirements in the Operating License and the Administrative Controls Section of the Technical Specifications LR-N08-0150, Relief Request for Third Interval Inservice Inspection Program for Examinations and Tests of Snubbers and Associated License Amendment Request2008-07-30030 July 2008 Relief Request for Third Interval Inservice Inspection Program for Examinations and Tests of Snubbers and Associated License Amendment Request LR-N08-0071, License Amendment Request - Hydrogen Water Chemistry Low Power Restriction2008-04-25025 April 2008 License Amendment Request - Hydrogen Water Chemistry Low Power Restriction ML0734500402008-01-24024 January 2008 Tech Spec Pages for Amendment 173 Control Room Habitability LR-N08-0003, Supplement to License Amendment Request for Extended Power Uprate2008-01-16016 January 2008 Supplement to License Amendment Request for Extended Power Uprate ML0728500372007-10-16016 October 2007 Technical Specifications, Issuance of Amendment Removal of Turbine First Stage Pressure Values from Technical Specifications ML0724003042007-08-27027 August 2007 Tech Spec Pages for Amendment 171 Relocate Component Lists for Primary Containment Isolation Valves from Technical Specifications LR-N07-0215, Supplement to License Amendment Request for Extended Power Uprate2007-08-27027 August 2007 Supplement to License Amendment Request for Extended Power Uprate ML0724805722007-06-15015 June 2007 Gnf S-0000-0068-2643, Gnf Additional Information Regarding the Requested Changes to the Technical Specification Slmcpr. Hope Creek (KT1) Cycle 15 LR-N07-0061, Application to Revise Technical Specifications (LCR H07-01) Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3, Using the Consolidated Line Item Improvement Process2007-04-17017 April 2007 Application to Revise Technical Specifications (LCR H07-01) Regarding Control Room Envelope Habitability in Accordance with TSTF-448, Revision 3, Using the Consolidated Line Item Improvement Process ML0630704822006-10-31031 October 2006 Tech Spec Pages for Amendment 170 Regarding Clarification of Requirements During Handling of Irradiated Fuel Core Alterations, and Operations with the Potential for Draining the Reactor Vessel ML0624101882006-08-28028 August 2006 Technical Specifications - Fuel Storage and Handling ML0621403972006-08-0101 August 2006 Technical Specifications, Issuance of Amendment Ultimate Heat Sink, MC8054 LR-N06-0259, Supplement to Request for License Amendment Ultimate Heat Sink2006-07-18018 July 2006 Supplement to Request for License Amendment Ultimate Heat Sink ML0610105472006-04-10010 April 2006 Technical Specifications Pages Re Relocation of the Component Identification from the Overcurrent Protective Device Lists in TS 3/4.8.4.1, Primary Containment Penetration Conductor Overcurrent Protective Devices, and TS 3/4.8.4.5 2024-01-16
[Table view] |
Text
TABLE 3.8.4.1-1 PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES
- 1. 4160-VOLT CIRCUIT BREAKERS CIRCUIr SYSTEMS OR BREAKER NO. LOCATION EQUIPMENT POWERED 1AN205 1AN205 Reactor Recirculation Pump 1AP201 IBN205 1BN205 Reactor Recirculation Pump 1BP201 1CN205 ICN205 Reactor Recirculation Pump 1AP201 lDN205 lDN205 Reactor Recirculation Pump 1BP201
- 2. 480-VOLT MOLDED CASE CIRCUIT BREAKERS Primary and backup breakers have the same device numbers and are located in the same Motor Control Center cubicle.
CIRCUI= SYSTEMS OR BREAKER NO. LOCATION TYPES EQUIPMENT POWERED 52-411t(65 10B411 IM RHR Head Spray Valve TM 1BC-HV-F022 52-451C61 10B451 IM RHR Shutdown Cooling Suction TM Inboard Valve 1BC-HV-F009 52-212C21 10B212 IM RWCU Suction Isolation Inboard TM Valve 1BG-HV-F001 52-212101 10B212 IM PCIGS Drywell Supply Header A TM Isolation Valve 1KL-HV-5152A 52-212181 1OB212 IM Main Steam Line Drain Inboard TM Valve IAB-HV-F016 52-212183 10B212 IM PCIGS Drywell Suction TM Inboard Valve IKL-HV-5148 52-232061 10B232 IM Drywell Supply Header A TM Isolation Valve 1KL-HV-5124A 52-232103 10B232 IM Drywell Equip. Drain Sump TM Isolation Valve 1HB-HV-F019 52-232134 10B232 IM HPCI Warmup Bypass Line TM Isolation Valve 1FD-HV-F100 52-2321;31 10B232 IM Chilled Water Loop A Supply TM Isolation Valve 1GB-HV-9531Bl 52-232132 10B232 IM Chilled Water Loop A Return TM Isolation Valve lGB-HV-9531B2 52-2321:33 10B232 IM Chilled Water Loop B Supply TM Isolation Valve 1GB-HV-9531B3 HOPE CREEK 3 /4 8-2 6 Amendment No.167
TABLE 3.8.4.1-1 (Continued)
PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES
- 2. 480-VOLT MOLDED CASE CIRCUIT BREAKERS (Continued)
CIRCUIT SYSTEMS OR BREAKER NO. LOCATION TYPES EQUIPMENT POWERED 52-232193 10B232 IM Chilled Water Loop B Return TM Isolation Valve lGB-HV-9531B4 52-232203 10B232 IM HPCI Turbine Steam Supply TM Isolation Valve 1FD-HV-F002 52-242)21 10B242 IM Drywell Floor Drain Sump TM Isolation Valve lHB-HV-F003 52-2420)61 10B242 IM Drywell Supply Header B TM Isolation Valve lKL-HV-5124B 52-242:101 10B242 IM PCIGS Drywell Supply Header B TM Isolation Valve 1KL-HV-5152B 52-242:.02 10B242 IM RCIC Turbine Steam Supply TM Isolation Valve lFC-HV-F007 52-2422.03 10B242 IM RCIC Warmup Bypass Line TM Isolation Valve 1FC-HV-F076 52-2422.72 10B242 IM Reactor Recirc Pumps Cooling TM Supply Isolation IED-HV-2554 52-242173 10B242 IM Reactor Recirc Pumps Cooling TM Return Isolation 1ED-HV-2556 52-252021 10B252 IM Drywell Cooler A Fan 1AlV212 TM 52-252022 10B252 IM Drywell Cooler B Fan 1B1V212 TM 52-252031 10B252 IM Drywell Cooler C Fan 1C1V212 TM 52-252032 10B252 IM Drywell Cooler D Fan ID1V212 TM 52-252041 10B252 IM Drywell Cooler E Fan 1E1V212 TM 52-252042 10B252 IM Drywell Cooler F Fan 1FlV212 TM 52-252051 10B252 IM Drywell Cooler G Fan 1GlV212 TM 52-252052 10B252 IM Drywell Cooler H Fan lHlV212 TM HOPE CRE'EK 3 /4 8-27 Amendment No. 167
TABLE 3.8.4.1-1 (Continued)
PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES
- 2. 480-VOLT MOLDED CASE CIRCUIT BREAKERS (Continued)
CIRCUIr SYSTEMS OR BREAKER NO. LOCATION TYPES EQUIPMENT POWERED 52-252)63 10B252 IM Drywell Equip Drain Sump Pump TM 1AP267 52-2524)64 10B252 IM Drywell Floor Drain Sump Pump TM 1CP267 52-252073 10B252 IM Feedwater Inlet A Shutoff TM lAE-HV-FO11A 52-262021 10B262 IM Drywell Cooler A Fan 1A2V212 TM 52-262022 1OB262 IM Drywell Cooler B Fan 1B2V212 TM 52-262tC31 1OB262 IM Drywell Cooler C Fan 1C2V212 TM
.52-262C32 10B262 IM Drywell Cooler D Fan 1D2V212 TM 52-262041 1OB262 IM Drywell Cooler E Fan lE2V212 TM 52-262042 10B262 IM Drywell Cooler F Fan 1F2V212 TM 52-262051 10B262 IM Drywell Cooler G Fan 1G2V212 TM 52-262052 10B262 IM Drywell Cooler H Fan 1H2V212 TM 52-262053 1OB262 IM Drywell Equip Drain Sump Pump TM 1BP267 52-2620'54 10B262 IM Drywell Floor Drain Sump Pump TM lDP267 52-2530:L2* 10B253. IM Recirc Pump Motor Hoist 1AH201 TM Disconnect Switch IAS204 52-253021 10B2253 IM Recirc Pump 1BP201 Suction TM Valve IBB-HV-F023B 52-253031 10B253 IM Recirc Pump 1BP201 Discharge TM Valve 1BB-HV-FO31B 52-253053 10B253 IM Reactor Vessel Head Vent TM Inboard Isolation lBB-HV-F001 HOPE CRE.EK 3 /4 8-28 Amendment No.167
TABLE 3.8.4.1-1 (Continued)
PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES
- 2. 480-VOLT MOLDED CASE CIRCUIT BREAKERS (Continued)
CIRCUIr SYSTEMS OR BREAKER NO. LOCATION TYPES EQUIPMENT POWERED 52-253)64 10B253 IM Reactor Vessel Head Vent to TM Steam Line IBB-HV-F005 52-263011 10B263 IM Reactor Vessel Head Vent TM Outboard Isolation 1BB-HV-F002 52-263012* 10B263 IM Recirc Pump Motor Hoist IBH201 TM Disconnect Switch lBS204 52-263042* 10B263 IM Main Steam Relief Valve Hoist TM 10H202 Disconnect Switch 10S207 52-263054 10B263 IM RWCU Suction from Recirc TM Loop A lBG-HV-FlOO 52-263081 10B263 IM RWCU Suction from RPV Drain TM Valve 1BG-HV-Fl01 52-263C82 10B263 IM RWCU Suction Valve 1BG-HV-Fl02 TM 52-263083 10B263 IM RWCU Suction from Recirc Loop TM B Valve 1BG-HV-Fl06 52-264053 10B264 IM Recirc Pump A Discharge Valve TM 1BB-HV-F031A 52-264062 1OB264 IM Feedwater Inlet B Shutoff TM Valve 1AE-HV-FO11B 52-264071 10B264 IM Reactor Recirc Pump 1AP201 TM Space Heater 1AS220 52-264072 10B264 IM Reactor Recirc Pump IBP201 TM Space Heater lBS220 52-264033 10B264 IM Recirc Pump A Suction Valve TM 1BB-HV-F023A
- These breakers shall be administratively maintained open in OPERATIONAL CONDITIONS 1, 2 and 3 and are not required to be tested.
HOPE CR1EEK 3 /4 8-29 Amendment No.167
TABLE 3.8.4.5-1 CLASS lE ISOLATION BREAKER OVERCURRENT PROTECTIVE DEVICES (BREAKER TRIPPED BY A LOCA SIGNAL) 480 VAC POWER CIRCUIT BREAKERS 1.
I Class 1E Circuit Class lE Breaker No. Bus Non-Class 1E Load Description 52-41011 10B410 Reactor Auxiliaries Cooling System Pump IAP209 52-41014 10B410 Radwaste and Service Area MCC 1OB313 52-41024 10B410 Reactor Building Supply Air Handling Unit lBVH300 52-42011 10B420 Reactor Auxiliaries Cooling System Pump 1BP209 52-42014 10B420 Radwaste and Service Area MCC 10B323 52-42024 1OB420 Reactor Building Exhaust Fan 1BV301 52-413024 10B430 Reactor Building Supply Air Handling Unit 1CVH300 52-4'3014 10B430 Control Rod Drive Pump IAP207 52-44014 1OB440 Control Rod Drive Pump 1BP207 52-44024 10B440 Reactor Building Supply Air Handling Unit 1AVH300 52-44034 10B440 Radwaste Area Supply Fan OBV316 52-45011 10B450 Reactor Area MCC 10B252 52-45014 10B450 Radwaste Area Exhaust Fan OAV305 52-45024 10B450 Emergency Instrument Air Compressor 1OK100 HOPE CR:EEK 3/4 8-42 Amendment No. 167
TABLE 3.8.4.5-1 (Continued) 480 VA.C POWER CIRCUIT BREAKERS
- 1. (Continued)
I Class lE Circuit Class 1E Breaker No. Bus Non-Class lE Load Description 52-45034 10B450 Reactor Building Exhaust Fan 1CV301 52-46011 10B460 Reactor Area MCC 10B262 52-46014 10B460 Radwaste Area Exhaust Fan OBV305 52-47011 10B470 Reactor Area MCC 10B272 52-17014 10B470 Radwaste Area Exhaust Fan 0CV305 52-47024 10B470 Radwaste Area Supply Fan OAV316 52-47031 10B470 Technical Support Center MCC 00B474 52-48011 10B480 Reactor Area MCC 10B282 52-48024 10B480 Reactor Building Exhaust Fan 1AV301 480 VAC MOLDED CIRCUIT BREAKERS 1.
I Class lE Circuit Class 1E Breaker No. Bus Non-Class 1E Load Description 52-441043 10B441 NSSS Computer Inverter 10D485 52-4.51023 10B451 Public Address System Inverter 10D496 52-471023 10B471 Security System Inverter OAD495 HOPE CREEK 3/4 8-43 Amendment No.167