05000528/LER-2005-001-01, Re Actuation of an Unit 1 Emergency Diesel Generator (EDG) and Plant Shutdown Required by TS

From kanterella
(Redirected from ML060240357)
Jump to navigation Jump to search
Re Actuation of an Unit 1 Emergency Diesel Generator (EDG) and Plant Shutdown Required by TS
ML060240357
Person / Time
Site: Palo Verde Arizona Public Service icon.png
Issue date: 01/06/2006
From: Eubanks C
Arizona Public Service Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
102-05396-CE/SAB/DJS LER 05-001-01
Download: ML060240357 (8)


LER-2005-001, Re Actuation of an Unit 1 Emergency Diesel Generator (EDG) and Plant Shutdown Required by TS
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
5282005001R01 - NRC Website

text

I OCFR50.73 hA~

A subsidiary of Pinnacle West Capital Corporation Cliff Eubanks Mail Station 7602 Palo Verde Nuclear Vice President Tel (623) 393-6116 PO Box 52034 Generating Station Nuclear Operations Fax (623) 393-6077 Phoenix, Arizona 85072-2034 102-05396-CE/SAB/DJS January 6, 2006 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001

Dear Sirs:

Subject:

Palo Verde Nuclear Generating Station (PVNGS)

Unit I Docket No. STN 50-528 License No. NPF 41 Licensee Event Report 2005-001-01 Attached please find a supplemental Licensee Event Report (LER) 50-528/2005-001-01 prepared and submitted pursuant to 10 CFR 50.73. This LER reports an event resulting in the actuation of one of the Unit 1 emergency diesel generators, and the subsequent Technical Specification required unit shutdown.

In accordance with 10 CFR 50.4, a copy of this LER is being forwarded to the NRC Region IV Office and the Senior Resident Inspector. Revisions of this report are identified by side bars in the left hand margin. If you have questions regarding this submittal, please contact Daniel G. Marks, Section Leader, Regulatory Affairs, at (623) 393-6492.

Arizona Public Service Company makes no commitments in this letter.

Sincerely, lCE/SAB/DJS/ca A member of the STARS (Strategic Teaming and Resource Sharing) Alliance Callaway

  • Comanche Peak 0 Diablo Canyon Palo Verde South Texas Project
  • Wolf Creek

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 06/30/2007 (6-2004)

, the NRC may sfor each block) not conduct or sponsor, and a person Is not required to respond to, the digits/characters frecblk)information collection.

3. PAGE Palo Verde Nuclear Generating Station (PVNGS) Unit 1 05000528 1 OF 7
4. TITLE Actuation of an Unit I Emergency Diesel Generator (EDG) and Plant Shutdown required by TS
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH SEUNILRVFCLT NAME DAY YEAR YEAR NUMBER REV MONTH DAY YEAR 1

FACILITY NAME DOCKET NUMBER 02 06 2005 2005 - 001 -

01 01 06(

2006

9. OPERATING MODE 11 THIS REPORT IS SUBMITTED PUIRSUANT TO THE REQUIREMENTS OF 10 CFR§: (Checkall that apply)

O 20.2201(b) 0 20.2203(a)(3)(i) 0 50.73(a)(2X))(C) 0 50.73(a)(2)(vii) 1 0 20.2201(d) 0 20.2203(a)(3)(ii)

El 50.73(a)(2)(ii)(A) 0 50.73(a)(2)(viii)(A) o 20.2203(a)(1) 0 20.2203(a)(4)

[I 50.73(aX2)(iiXB)

[l 50.73(a)(2)(viii)(B) o 20.2203(a)(2)(i) 0 50.36(c)(1)(i)(A)

E 50.73(a)(2)(iii)

El 50.73(a)(2)(ix)(A)

10. POWER LEVEL 0

20.2203(a)(2)(ii) 0 50.36(c)(1)(i)(A) 0 50.73(a)(2)(iv)(A)

El 50.73(a)(2)(x) o 20.2203(a)(2)(iii)

El 50.36(c)(2)

El 50.73(a)(2)(v)(A)

Dl 73.71(a)(4)

El 20.2203(aX2Xiv)

El 50.46(aX3)(fi)

El 50.73(a)(2)(v)(B) a 73.71(a)(5) 100 E 20.2203(aX2Xv) 0 50.73(aX2)(i)(A)

El 50.73(a)(2)(v)(C)

El OTHER El 20.2203(aX2)(vi)

E 50.73(a)(2)(i)(B)

El 50.73(a)(2)(v)(D)

Specify In Abstract below or in (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of (If more space is required, use additional copies of NIRC Form 366A)

9.

PREVIOUS SIMILAR EVENTS

Switchyard and EHV grid events that have affected PVNGS have been reported in LERs 50-528/2004-006-00, 50-529/2004-003-00 and 50-530/2003-004-00. However, these previous events or conditions did not involve the same underlying concern or reason as this event, such as the same root cause, failure, or sequence of events.

There have been no previous similar events in the past three years that had a similar failure mechanism or that should have prevented this event from previously implemented corrective actions.

NRC

-(R RF..

1A -7n1 I I

k I II