L-2005-237, Refueling Outage SL2-15 Steam Generator Tube Inservice Inspection Special Report

From kanterella
(Redirected from ML053410482)
Jump to navigation Jump to search

Refueling Outage SL2-15 Steam Generator Tube Inservice Inspection Special Report
ML053410482
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 11/28/2005
From: Jefferson W
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-2005-237, SL2-15
Download: ML053410482 (101)


Text

0 FPL Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 November 28, 2005 L-2005-237 10 CFR 50.55a 10 CFR 50.36 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 Re:

St. Lucie Unit 2 Docket No. 50-389 Refueling Outage SL2-15 Steam Generator Tube Inservice Inspection Special Report Attached is the Steam Generator Tube Inservice Inspection Special Report required by sections 4.4.5.5.b and 6.9.2 of the St Lucie Unit 2 Technical Specifications for the January 2005 refueling outage (SL2-15).

The report is to be submitted within one year of completing the refueling outage steam generator inservice inspection.

Should there be any questions, please contact us.

Willia effe rb Vice President St. Lucie Plant WJ/GRM Enclosure A -1(-

an FPL Group company

St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure Enclosure Steam Generator Tube Inservice Inspection Special Report (98 pages)

FORM NIS-BB Attachment Title Pages 1

S/G 2A - Tubes with bobbin indications 40-100% TW and RPC 23 repairable 2

S/G 2A - Tubes with bobbin indications 20-39% TW 6

3 S/G 2A - Tubes with bobbin indications 1-19 % TW 8

4 S/G 2B - Tubes with bobbin indications 40-100% TW and RPC 24 repairable 5

S/G 2B - Tubes with bobbin indications 20-39% TW 4

6 S/G 2B - Tubes with bobbin indications 1-19 % TW 7

7 S/G 2A - Tubes with bobbin indications 1-39% TW left in service 14 8

S/G 2B - Tubes with bobbin indications 1-39% TW left in service 10 Through Wall (TW)

Rotating Pancake Coil (RPC)

St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure In accordance with Plant Technical Specification Section 4.4.5.5 (b), the attached information provides a summary of the results for the inservice examination of steam generator (S/G) tubing, and is to be submitted to the Commission within 12 months of the examination completion date.

1. Inservice examination and plugging of the St. Lucie Unit 2 steam generators was completed between January 11, 2005 and January 29, 2005. The specific scope of examination for all techniques is provided below. This is also shown under Total Tubes Inspected on the attached FORM NIS-BB, Owners' Data Report For Eddy Current Examination Results.

Planned Examination Scope Bobbin colt examination:

  • 100% full-length in Rows 3 and higher. Row 1 and 2 examinations were limited to the hot leg and cold leg straight sections.
  • Screening of dings/dents <5 volts in straight lengths (including horizontal runs).

+PoinT rotating probe examination:

100% of active hot leg tubes +3 inches/-13 inches as referenced from the top of tubesheet

  • All cold leg tubes in peripheral high flow regions for foreign object wear +3 inches/-2 inches as referenced from the top of tubesheet
  • Full depth tubesheet inspection of all hot & cold leg tubes with no tube expansion
  • 35% of Row 1 and 2 U-bends
  • All wear indications at the hot leg (H/L) diagonal support structures
  • All wear indications at horizontal eggcrate tube supports
  • 20% of wear indications at vertical supports in the U-bend region
  • 20% of wear indications at the cold leg (C/L) diagonal supports
  • Dings/Dents
  • All dings/dents between TSH +0.00 inches and 01 H +1.00 inch
  • All dings/dents >= 5.00 volts between 01H +1.00 inch and DHB -0.01 inches
  • All dings/dents in the H/L and C/L square bends for Rows 19 - 140 e All dings/dents >= 5.00 volts in the horizontal runs of tubes in Rows 19 - 140
  • All dings/dents in the U-bend region for tubes in Rows 1 - 18
  • 20% of dings/dents > 5.00 volts in the cold leg straight sections Visual Examination
  • 100% of all previously installed tube plugs

St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure

5. The attached listings for SIGs 2A and 2B are included as source documents for the preparation of FORM NIS-BB.
  • S/G 2A - Tubes with Bobbin Indications 40 - 100% TW and rotating pancake coil (RPC) repairable codes (Attachment 1 )
  • S/G 2A - Tubes with Bobbin Indications 20 - 39% TW (Attachment 2)
  • S/G 2A - Tubes with Bobbin Indications 1 - 19% TW (Attachment 3)
  • S/G 2B - Tubes with Bobbin Indications 40 - 100% TW and RPC repairable codes (Attachment 4)
  • S/G 2B - Tubes with Bobbin Indications 20 - 39% TW (Attachment 5)
  • S/G 2B - Tubes with Bobbin Indications 1 - 19% TW (Attachment 6)
  • S/G 2A - Tubes with Bobbin Indications 1 - 39% TW Left in service (Attachment 7)
  • S/G 2B - Tubes with Bobbin Indications 1 - 39% TW Left in service (Attachment 8)

St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure

.ZJ EWDY,'URREN-TECAMIN'ATitl;N;EsULTS::

Planl:

St. Lucle Unit 2 Exam Dalts:

January 11. 2005 to January 29. 2005 Total Tues

_Total Tubs Tubes as Tubes Tot P*ugged Steam Total Tubes 20%-39%

T.W.

Preventie Pu~

ue nec Genrerator Inspected TThises TtlTue es

~

~

Puge ue SInGac (5)

C~ro. & Mxal Malnienance (PTP)

OutageSG A

7740 233 798(ip 0

798 1489 B

7539 144 35 2

837(4) 1709 4,,,,......................

,;r PthX r,

.,gg r

00%.C, &~fA1 Partial U BENDS EGGCRATES Supports Top of Tube Shoot to Total Total Indications Stearn DHB to I to 7 8 and 9

  1. 1 EGGOCRATE Indications

>=40% T.W.

Generator DOB (7)

(7)

(7) 20%-39%

Cirh. & Axil 7)(8

_-W

_--(5)

(7 W-L' CIL.

MR Cit.

HL CIL.

2 1181 2

1 0

22 0

1208 307 1

3 5

I O

O 317 9

1247 9

7 3

15 0

1291M B

176 4

4 2

0 0

0 1868 Total EGOCRATES PaSial Top of Tube Sheet to Indications Total Indications Steatr U

7 Supports

  1. 1 EGGCRATE M119' 1%439% Left In U BENDS I to 7 8 a id 9 Sevice for Cycle MM to HIL CIL CIL WIL CIL (A

(5)

A 383 30 10 10 7

0 1

421 701 B

267 30 21 a

0 0

330 490 Refer to ghe Remarks Section on the Following Page

St. Lucie Uni( 2 Docket No. 5!'-389 L-2005-237 Enclosure

zFp, NIS-BB OWNErS EDATA E

T FOR DY fENT EXAMINATION RESULt+".

b-'toAs M

blh provslbnd of the AkMECOD30 RULES

.':,.GURRENT, EXAINATINESUL&'

Plant:

St. Lucie Unit 2 Exam Dates:

January 11, 2005 to January 29, 2005 Remarks:

(1) Six (6) tubes were plugged due to circumferential hdications at the hot leg expansion ransition hi SG 2A.

(2) Ten (10) tubes were plugged due to circumferential Indications at the hot leg expansion transition in SG 28.

(3) Two (2) tubes were preventalively plugged. One (1) due to the presence of wear (WAR) associated with a PUP at the 1I hot leg eggcrate support. One (1) due to a non-quantiflable Indication (NO) In the froespan ragian between the cold leg expansion transition and 1 eggcrate In which RPC results were inconclusive.

(4) The total number of tubes plugged excludes tube R50L132 that was do-plugged and rn-plugged with a Long Poll Plug in both egs as well as t-length tsabilization during this outage.

(5) Percent through-wall penetration Is givenponly for mechanical wear Indications at structures. (SA) Numbers are cumulative and Include indications In tubes that are plugged for other reasons.

(6) This total Includes One (1) tube, R491L67 that has a SCI indication at TEH +0.32. and Is not counted In any of the categories listed In this section.

(7) The upper number In these live columns represents the number of non-wear type or 3-41% TW Indications reported (SAi, MAI, SCI, etc). The lower number represents the number of mechanical wear Indications reported at the structures that ranged from 20-39% throughwall.

(6) In SG 2A, One (1) tube R47iL77 was reported with a cold leg diagonal strap (DCT) wear Indication measuring 42%

throughwall by bobbin coil and was plugged and One (1) tube was Identified with a single axial Indication (SAI) at the hot leg diagonal top (DHT) and was plugged.

In SG 2B. Nlne () single axial IndIcations (SAt) were reported at the edges of (7) hot leg and (2) cold leg diagonal straps.

Acronyms: SM-Single Axial Indication SCI - Single Circumferential Indication, PP - Preventative Tube Plug. TSH - Hot leg tubesheet Expansion, TSC -Cold leg Tubesheet expanslon VOL - Volumsetrc Indication. PLP - Possitbe Lwse Part. TEH - Tube End Hot, TEC - Tube End Cold

Framatome ANP Inc.

1/22/2005 14:30 Attachm nt I CSI-NDE-05-020 Page 1 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 6

4 0.28 0.20 8

4 0.16 0.15 12 4

0.22 22 4

0.43 0.13 12 6

0.50 16 6

0.23 32 6

0.27 7

7 0.19 2

8 0.27 6

8 0.17 0.44 10 8

0.17 7

9 0.18 0.33 0.15 13 9

0.14 0.52 12 10 0.33 0.35 1

11 0.14 9

11 0.32 0.15 13 11 0.22 45 11 0.37 0.29 8

12 0.16 10 12 0.27 7

13 0.16 0.34 13 13 0.21 10 14 0.19 7

15 0.17 9

15 0.50 6

16 0.15 0.17 14 16 0.22 0.27 34 16 0.30 66 16 0.36 5

17 0.31 7

17 0.36 0.27 9

17 0.55 0.38 0.41 65 17 0.17 0.23 6

18 0.23 0.17 0.29 8

18 0.25 DEG 81 98 81 70 109 102 92 105 114 105 112 90 57 107 77 86 117 94 64 99 102 101 64 90 46 86 79 83 71 83 59 85 60 79 68 103 100 95 109 76 83 91 93 106 112 112 92 88 96 105 116 100 101 78 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SAI MAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI

%TW LOCATION 03H

-0.17 03H

+0.80 03H

-0.42 03H

+0.81 01H

+0.88 02H

+0.28 02H

+0.89 03H

+0.68 03H

+0.80 03H

+0.81 03H

-0.35 03H

+0.73 03H

-0.35 03H

+0.55 03H

+0.86 01H

+0.88 03H

+0.87 05H

+0.77 05H

-0.17 03H

+0.06 03H

+0.42 04H

+0.79 03H

+0.85 03H

-0.13 05H

+0.54 03H

+0.73 02H

-0.49 04H

-0.49 02H

-0.74 05H

-0.50 03H

+0.90 04H

+0.75 07H

+0.53 03H

+0.64 02H

-0.75 02H

+0.56 01H

+0.87 03H

+0.67 03H

+0.83 04H

-0.75 02H

+0.89 03H

+0.33 05H

-0.23 01H

+0.45 05H

+0.68 01H

+0.31 03H

-0.95 03H

+0.07 04H

-0.38 02H

-0.35 01H

+0.79 02H

-0.90 02H

+0.33 02H

-0.65 EXT 03H 03H 03H 03H 01H 02H 02H 03H 03H 03H 03H 03H 03H 03H 03H 01H 03H 05H 05H 03H 03H 04H 03H 03H 05H 03H 02H 04H 02H 05H 03H 04H DCB 03H 02H 02H 01H 03H 03H 04H 02H 03H 05H 01H 05H 01H 03H 03H 04H 02H 01H 02H 02H 02H EXT 03H 03H 03H 03H 01H 02H 02H 03H 03H 03H 03H 03H 03H 03H 03H 01H 03H 05H 05H 03H 03H 04H 03H 03H 05H 03H 02H 04H 02H 05H 03H 04H 07H 03H 02H 02H 01H 03H 03H 04H 02H 03H 05H 01H 05H 01H 03H 03H 04H 02H 01H 02H 02H 02H CAL # LEG 173 HOT 173 HOT 173 HOT 173 HOT 95 HOT 63 HOT 63 HOT 63 HOT 63 HOT 63 HOT 173 HOT 69 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 129 HOT 63 HOT 95 HOT 63 HOT 69 HOT 173 HOT 173 HOT 63 HOT 63 HOT 63 HOT 173 HOT 173 HOT 173 HOT 173 HOT 171 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 95 HOT 63 HOT 63 HOT 63 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 63 HOT 95 HOT 173 HOT 173 HOT 173 HOT 173 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602 P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attachment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 2 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 10 18 0.28 0.16 0.20 7

19 0.17 0.21 13 19 0.19 6

20 0.23 0.18 0.37 0.21 10 20 0.32 0.10 8

22 0.18 0.17 0.08 44 22 0.24 0.21 66 22 0.27 0.23 0.20 5

23 0.30 0.26 0.38 7

23 0.15 0.19 0.29 13 23 0.23 47 23 0.31 6

24 0.33 8

24 0.24 0.16 0.13 10 24 0.32 0.14 0.17 0.38 12 24 0.21 0.14 44 24 0.21 46 24 0.29 0.18 7

25 0.15 0.20 0.13 65 25 0.19 0.18 8

26 0.23 0.19 0.16 10 26 0.16 0.25 12 26 0.24 0.39 24 26 0.18 DEG 88 182 80 61 69 113 94 96 106 111 93 85 68 93 86 84 123 102 61 83 70 97 95 83 63 90 139 99 104 80 81 45 84 79 86 94 72 79 108 108 88 64 93 66 76 102 53 104 53 61 120 62 103 114 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND %TW LOCATION SAI 01H

-0.46 SAI 03H

-0.51 SAI 03H

+0.86 SAI 01H

+0.24 SAI 02H

+0.60 KAI 03H

+0.80 SAI 01H

+0.21 SAI 03H

-0.64 SAI 03H

+0.49 SAT 05H

+0.69 SAI 03H

+0.79 SAI 04H

-0.92 MAI 02H

-0.41 SAI 03H

+0.78 SAI 04H

-0.56 SAI 04H

-0.85 SAI 03H

-0.94 SAI 02H

-0.46 SAI 04H

-0.80 SAI 06H

+0.79 SAI 02H

-0.61 SAI 03H

+0.86 SAI 05H

+0.69 SAI 01H

-0.92 SAI 03H

+0.84 SAI 05H

+0.43 MAI 03H

+0.71 SAI 03H

+0.83 SAI 03H

+0.61 MAI 01H

-0.97 SAI 02H

+0.95 SAI 03H

-0.29 MAI 02H

+0.55 SAI 05H

+0.07 SAI 05H

+0.54 SAI 07H

+0.25 SAI 02H

-0.70 SAI 03H

+0.84 SAI 01H

-0.61 SAI 03H

+0.71 SAI 01H

+0.83 SAI 01H

-0.77 SAI 03H

+0.87 SAI 05H

+0.78 SAI 02H

-0.82 SAI 01H

-0.66 SAI 01H

-0.69 SAI 05H

+0.65 SAI 07H

-0.07 SAI 01H

-0.59 SAI 03H

+0.77 SAI 02H

+0.49 SAI 03H

+0.67 SAI 03H

-0.94 EXT 01H 03H 03H 01H 02H 03H 01H 03H 03H 05H 03H 04H 02H 03H 04H 04H 03H 02H 04H 06H 02H 03H 05H 01H 03H 05H 03H 03H 03H 01H 02H 03H 02H 05H 05H 07H 02H 03H 01H 03H 01H 01H 03H 05H 02H 01H 01H 05H 07H 01H 03H 02H 03H 03H EXT 01H 03H 03H 01H 02H 03H 01H 03H 03H 05H 03H 04H 02H 03H 04H 04H 03H 02H 04H 06H 02H 03H 05H 01H 03H 05H 03H 03H 03H 01H 02H 03H 02H 05H 05H DHT 02H 03H 01H 03H 01H 01H 03H 05H 02H 01H 01H 05H DHT 01H 03H 02H 03H 03H CAL # LEG 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 155 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 63 HOT 95 HOT 95 HOT 95 HOT 95 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 155 HOT 63 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 95 HOT 63 HOT 63 HOT 63 HOT 95 HOT 173 HOT 173 HOT 173 HOT 63 HOT 95 HOT 173 HOT 173 HOT 173 HOT 173 HOT 173 HOT 95 HOT 63 HOT 95 HOT PROBE 5803=P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attach-ent I CSI-NDE-05-020 Page 3 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION 0.18 0.16 0.09 64 26 0.41 0.21 66 26 0.24 0.32 0.20 7

27 0.31 9

27 0.18 15 27 0.36 0.37 61 27 0.24 65 27 0.19 0.31 67 27 0.26 0.24 83 27 0.24 0.33 6

28 0.14 8

28 0.14 10 28 0.34 14 28 0.16 0.38 30 28 0.37 66 28 0.44 0.31 68 28 0.23 76 28 0.28 0.27 0.18 0.17 15 29 0.29 21 29 0.58 0.18 39 29 0.19 69 29 0.28 0.32 87 29 0.22 6

30 0.31 8

30 0.25 10 30 0.24 24 30 0.27 0.36 28 30 0.17 54 30 0.32 0.19 0.17 66 30 0.36 78 30 0.14 9

31 0.14 23 31 0.29 55 31 0.28 67 31 0.28 101 P 6 80 P 6 68 P 6 103 P 6 100 P 6 93 P 6 100 P 6 88 P 6 96 P 6 108 P 6 85 P 6 105 P 6 84 P 6 84 P 6 63 P 6 85 P 6 99 P 6 85 P 6 269 P 6 87 P 6 149 P 6 101 P 6 61 P 6 104 P 6 104 P 6 99 P 6 60 P 6 85 P 6 94 P 6 106 P 6 49 P 6 70 P 6 109 P 6 101 P 6 91 P 6 97 P 6 83 P 6 79 P 6 77 P 6 89 P 6 105 P 6 94 P 6 104 P 6 86 P 6 116 P 6 83 P 6 81 P 6 82 P 6 94 P 6 89 P 6 70 P 6 92 P 6 104 P 6 81 P 6 MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI 05H 03H 03H 02H 06H 03H 02H 02H 03H 03H DHT 05H 04H 02H 03H 03H 02H 02H 02H 01H 07H 01H 02H 03H 02H 03H 02H 02H 02H 02H 03H 04H 03H 03H 04H 01H 02H 03H 03H 03H 03H 01H 03H 05H 02H 04H 01H 02H 01H 01H 03H 03H 01H 02H

+0.77

-0.16

+0.89

+0.59

+0.71

+0.84

+0.04

+0.75

+0.57

+0.87

-0.15

+0.64

+0.83

+0.85

+0.48

+0.59

-0.78

+0.70

-0.80

+0.19

+0.90

-0.37

+0.19

+0.32

-0.51

+0.90

-0.57

+0.81

-0.65

+0.81

-0.25

+0.85

+0.82

+0.63

+0.81

-0.69

+0.78

+0.73

+0.82

+0.85

+0.79

+0.85

+0.80

+0.81

-0.75

+0.71

+0.52

+0.85

+0.44

+0.82

+0.79

+0.40

-0.34

+0.89 EXT EXT CAL # LEG PROBE 05H 05H 63 HOT 5803P 03H 03H 95 HOT 5803P 03H 03H 95 HOT 5803P 02H 02H 63 HOT 5803P 06H 06H 63 HOT 5803P 03H 03H 63 HOT 5803P 02H 02H 95 HOT 5803P 02H 02H 95 HOT 5803P 03H 03H 173 HOT 5803P 03H 03H 173 HOT 5803P 07C 07H 165 HOT 5602P 05H 05H 63 HOT 5803P 04H 04H 63 HOT 5803P 02H 02H 63 HOT 5803P 03H 03H 63 HOT 5803P 03H 03H 63 HOT 5803P 02H 02H 95 HOT 5803P 02H 02H 129 HOT 5803P 02H 02H 129 HOT 5803P 01H 01H 173 HOT 5803P 07H DHT 173 HOT 5803P 01H 01H 173 HOT 5803P 02H 02H 95 HOT 5803P 03H 03H 63 HOT 5803P 02H 02H 155 HOT 5803P 03H 03H 63 HOT 5803P 02H 02H 95 HOT 5803P 02H 02H 63 HOT 5803P 02H 02H 63 HOT 5803P 02H 02H 63 HOT 5803P 03H 03H 63 HOT 5803P 04H 04H 63 HOT 5803P 03H 03H 63 HOT 5803P 03H 03H 63 HOT 5803P 04H 04H 63 HOT 5803P 01H 01H 63 HOT 5803P 02H 02H 63 HOT 5803P 03H 03H 63 HOT 5803P 03H 03H 129 HOT 5803P 03H 03H 173 HOT 5803P 03H 03H 173 HOT 5803P 01H 01H 173 HOT 5803P 03H 03H 63 HOT 5803P 05H 05H 63 HOT 5803P 02H 02H 63 HOT 5803P 04H 04H 63 HOT 5803P 01H 01H 95 HOT 5803P 02H 02H 95 HOT 5803P 01H 01H 63 HOT 5803P 01H 01H 63 HOT 5803P 03H 03H 173 HOT 5803P 03H 03H 63 HOT 5803P 01H 01H 63 HOT 5803P 02H 02H 63 HOT 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 4 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 71 31 0.17 24 32 0.16 0.17 32 32 0.23 66 32 0.41 80 32 0.30 0.17 0.22 82 32 0.29 0.21 11 33 0.16 15 33 0.46 37 33 0.23 71 33 0.25 10 34 0.82 0.17 32 34 0.23 0.34 58 34 0.45 66 34 0.18 76 34 0.54 0.25 0.28 37 35 0.27 0.28 71 35 0.18 83 35 0.42 0.16 0.21 87 35 0.44 0.25 4

36 0.21 8

36 0.16 24 36 0.16 30 36 0.48 58 36 0.27 76 36 0.14 0.13 0.25 9

37 0.15 65 37 0.17 0.24 0.20 32 38 0.11 0.13 0.32 0.20 0.20 54 38 0.19 0.25 64 38 0.33 76 38 0.27 88 38 0.18 3

39 0.29 DEG 68 92 58 140 91 76 68 78 93 71 85 80 68 82 104 73 77 110 93 86 102 101 105 68 106 76 96 109 66 103 89 93 90 102 100 80 62 108 83 72 69 78 73 85 71 111 92 90 93 77 102 78 88 61 CHN P 6 P 6 P 6 2

P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SM=

SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI

%TW LOCATION 04H

+0.80 01H

-0.55 03H

+0.93 03H

-0.35 05H

+0.72 03H

+0.81 02H

-0.45 02H

+0.63 02H

+0.77 03H

+0.93 01H

-0.58 01H

+0.40 03H

+0.65 02H

+0.90 01H

+0.58 07H

+0.88 01H

-0.41 03H

-0.14 02H

+0.87 04H

+0.74 03H

+0.35 02H

-0.70 02H

+0.56 01H

+0.80 03H

+0.51 01H

-0.82 03H

-0.12 04H

-0.51 04H

+0.90 05H

-0.29 06H

+0.84 07H

+0.72 01H

+0.68 05H

-0.24 01H

+0.67 02H

+0.79 01H

-0.63 01H

-0.38 01H

+0.70 01H

+0.27 02H

-0.13 02H

+0.78 01H

-0.57 02H

-0.67 02H

+0.72 03H

+0.30 04H

-0.16 04H

+0.76 02H

+0.79 05H

+0.98 01H

-0.52 03H

+0.51 02H

+0.91 07H

+0.25 EXT 04H 01H 03H 03H 05H 03H 02H 02H 02H 03H 01H 01H 03H 02H 01H 07H 01H 03H 02H 04H 03H 02H 02H 01H 03H 01H1 03H 04H 04H 05H 06H 07H 01H 05H 01H 02H 01H 01H 01H 01H 02H 02H 01H 02H 02H 03H 04H 04H 02H 05H 01H 03H 02H 07H EXT 04H 01H 03H 03H 05H 03H 02H 02H 02H 03H 01H 01H 03H 02H 01H DHT 01H 03H 02H 04H 03H 02H 02H 01H 03H 01H 03H 04H 04H 05H 06H DHT 01H 05H 01H 02H 01H 01H 01H 01H 02H 02H 01H 02H 02H 03H 04H 04H 02H 05H 01H 03H 02H DHT CAL #

63 95 63 63 63 63 95 95 129 129 155 63 63 63 173 173 95 63 129 66 66 95 95 95 63 66 129 129 129 129 129 173 173 129 63 66 66 66 66 69 66 66 95 95 95 63 63 63 95 95 66 66 129 155 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Page 5 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG 71 39 0.41 0.23 0.22 105 39 0.20 10 40 0.14 30 40 0.38 58 40 0.37 74 40 0.24 78 40 0.18 82 40 0.32 0.23 0.27 7

41 0.16 15 41 0.75 17 41 0.21 25 41 0.34 37 41 0.27 0.22 0.28 0.25 41 41 0.34 61 41 0.38 83 41 0.18 6

42 0.34 42 42 0.17 72 42 0.18 76 42 0.26 9

43 0.15 15 43 0.12 37 43 0.43 71 43 0.20 0.14 0.19 0.13 0.21 103 43 0.21 0.29 0.20 4

44 0.18 8

44 0.26 0.16 12 44 0.70 0.22 14 44 0.32 0.13 24 44 0.33 40 44 0.36 0.68 0.30 0.29 0.40 46 44 0.20 0.21 0.30 87 72 77 72 81 95 100 85 74 98 65 96 68 100 98 282 103 94 79 108 86 85 80 99 92 92 75 109 31 90 78 74 66 77 51 102 123 71 71 117 88 102 86 92 68 106 100 102 111 96 85 77 64 87 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND %TW LOCATION SAI 03H

+0.58 SAI 04H

+0.79 SAI 02H

+0.86 SAI 03H

+0.94 SAI 01H

+0.36 SAI 03H

+0.65 MAI 01H

-0.69 SAI 03H

+0.65 SAI 03H

+0.50 SAI 01H

-0.36 SAI 03H

-0.10 SAI 03H

+0.98 SAI 01H

-0.39 SAI 03H

+0.71 SAI 07C

+0.86 SAI 03H

-0.39 SAI 02H

+0.13 SAI 01H

-0.45 SAI 03H

+0.75 MAI 03H

-0.24 SAI 01H

-0.52 SAI 02H

+0.57 SAI 01H

-0.74 SAI 01H

-0.66 SAI 01H

+0.44 SAI 03H

+0.41 MAI 03H

+0.66 SAI 03H

+0.85 SAI 03H

-0.22 SAI 02H

+0.53 MAI 02H

+0.68 SAI 04H

+0.75 SAI 01H

+0.09 SAI 01H

+0.60 SAI 03H

+0.73 SAI 01H

-0.45 SAI 01H

+0.81 SAI 02H

-0.41 SAI 06H

-0.15 SAI 01H

+0.69 SAI 01H

-0.77 SAI 01H

+0.65 SAI 01H

-0.45 SAI 01H

+0.62 SAI 03H

+0.87 SAI 01H

+0.39 SAI 04H

+0.86 SAI 01H

-0.59 SAI 01H

+0.78 MAI 02H

+0.71 SAI 03H

+0.84 SAI 01H

-0.41 SAI 02H

+0.89 SAI 03H

-0.34 EXT EXT CAL # LEG 03H 04H 02H 03H 01H 03H 01H 03H 03H 01H 03H 03H 01H 03H 07C 03H 02H 01H 03H 03H 01H 02H 01H 01H 01H 03H 03H 03H 03H 02H 02H 04H 01H 01H 03H 01H 01H 02H 06H 01H 01H 01H 01H 01H 03H 01H 04H 01H 01H 02H 03H 01H 02H 03H 03H 04H 02H 03H 01H 03H 01H 03H 03H 01H 03H 03H 01H 03H 07C 03H 02H 01H 03H 03H 01H 02H 01H 01H 01H 03H 03H 03H 03H 02H 02H 04H 01H 01H 03H 01H 01H 02H 06H 01H 01H 01H 01H 01H 03H 01H 04H 01H 01H 02H 03H 01H 02H 03H 66 66 95 129 155 63 66 95 66 129 129 129 155 63 85 63 95 63 63 63 63 66 129 155 63 66 66 155 63 63 66 66 95 95 95 129 129 129 69 155 155 63 63 95 63 63 127 63 63 63 63 63 63 63 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 6 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 54 44 0.50 80 44 0.27 0.20 104 44 0.25 7

45 0.25 15 45 0.17 0.24 19 45 0.16 41 45 0.51 55 45 0.29 67 45 0.41 0.18 71 45 0.14 73 45 0.28 103 45 0.21 113 45 0.31 0.13 10 46 0.40 54 46 0.56 27 47 0.42 37 47 0.18 67 47 0.43 75 47 0.31 105 47 0.24 0.29 32 48 0.35 36 48 0.21 35 49 0.26 71 49 0.16 73 49 0.25 8

50 0.68 0.20 82 50 0.27 110 50 0.21 0.18 122 50 0.34 13 51 0.27 41 51 0.24 0.18 69 51 0.12 97 51 0.33 113 51 0.27 8

52 0.17 32 52 0.32 38 52 0.30 82 52 0.42 118 52 0.33 15 53 0.20 43 53 0.79 97 53 0.25 0.25 8

54 0.24 14 54 0.31 16 54 0.27 DEG CHN 92 P 6 83 P 6 77 P 6 89 P 6 86 P 6 74 P 6 91 P 6 107 P 6 90 P 6 89 P 6 102 P 6 95 P 6 33 P 6 82 P 6 91 P 6 76 P 6 64 P 6 106 P 6 104 P 6 88 P 6 92 P 6 106 P 6 79 P 6 81 P 6 69 P 6 75 P 6 76 P 6 82 P 6 81 P 6 89 P 6 108 P 6 114 P 6 86 P 6 95 P 6 106 P 6 98 P 6 115 P 6 85 P 6 115 P 6 127 P 6 113 P 6 104 P 6 77 P 6 92 P 6 72 P 6 95 P 6 112 P 6 115 P 6 105 P 1 74 P 6 98 P 6 101 P 6 94 P 6 121 P 6 IND SA=

SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SCI SAI SAI SAI SAI SAI

%TW LOCATION EXT 01H

-0.45 01H 01H

+0.03 01H 02H

+0.80 02H 01H

-0.20 01H 07H

+0.86 07H 01H

+0.63 01H 02H

+0.92 02H 03H

-0.68 03H 02H

+0.56 02H 01H

-0.47 01H 01H

-0.38 01H 01H

+0.74 01H 03H

+0.86 03H 01H

-0.56 01H 02H

-0.89 02H 03H

+0.54 03H 03H

-0.26 03H 01H

+0.92 01H 02H

+0.35 02H 01H

+0.23 01H 05H

+0.90 05H 01H

-0.14 01H 05H

-0.16 05H 02H

+0.84 02H 03H

+0.76 03H 01H

+0.71 01H 01H

+0.80 01H 02H

+0.89 02H 01H

-0.25 01H 01H

-0.63 01H 02H

+0.04 02H 02H

-0.81 02H 02H

+0.92 02H 01H

+0.47 01H 01H

+0.28 01H 02H

+0.82 02H 07H

+0.97 07H O1H

+0.75 01H 02H

+0.91 02H 03H

+0.94 03H 02H

-0.96 02H 01H

-0.54 01H 05H

+0.80 05H 01H

+0.45 01H 02H

+0.90 02H 01H

-0.62 01H 01H

-0.80 01H 07H

-0.32 07H TSH

-0.14 TSH 01H

-0.52 01H 01H

+0.84 01H 05H

+0.80 05H 01H

+0.78 01H 07H

+0.22 07C EXT 01H 01H 02H 01H DHT 01H 02H 03H 02H 01H 01H 01H 03H 01H 02H 03H 03H 01H 02H 01H 05H 01H 05H 02H 03H 01H 01H 02H 01H 01H 02H 02H 02H 01H 01H 02H 07H 01H 02H 03H 02H 01H 05H 01H 02H 01H 01H 07H TSH 01H 01H 05H 01H 07H CAL # LEG 63 HOT 95 HOT 66 HOT 129 HOT 155 HOT 95 HOT 63 HOT 63 HOT 63 HOT 63 HOT 66 HOT 66 HOT 66 HOT 66 HOT 129 HOT 129 HOT 129 HOT 155 HOT 63 HOT 63 HOT 63 HOT 66 HOT 66 HOT 129 HOT 129 HOT 63 HOT 63 HOT 63 HOT 95 HOT 95 HOT 155 HOT 155 HOT 129 HOT 129 HOT 129 HOT 129 HOT 162 HOT 95 HOT 63 HOT 66 HOT 129 HOT 129 HOT 155 HOT 63 HOT 63 HOT 129 HOT 129 HOT 162 HOT 123 HOT 129 HOT 129 HOT 155 HOT 63 HOT 162 HOT PROBE 5803=P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5602P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 7 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 66 54 0.62 96 54 0.22 102 54 0.21 106 54 0.24 67 55 0.54 75 55 0.40 111 55 0.32 6

56 0.23 8

56 0.19 0.30 14 56 0.40 44 56 0.11 70 56 0.54 80 56 0.37 0.27 82 56 0.29 102 56 0.52 0.14 0.19 106 56 0.31 75 57 0.59 93 57 0.33 103 57 0.35 113 57 0.23 0.34 8

58 0.26 12 58 0.13 16 58 0.17 0.21 0.15 0.30 64 58 0.19 0.18 0.40 102 58 0.18 0.29 0.15 110 58 0.34 0.36 0.27 126 58 0.23 71 59 0.26 101 59 0.27 103 59 0.41 8

60 0.26 0.19 40 60 0.42 0.32 44 60 0.59 110 60 0.36 27 61 0.43 43 61 0.23 103 61 0.63 111 61 0.30 DEG 94 80 98 102 99 80 100 129 109 88 91 141 82 94 89 ill 113 62 70 92 127 103 85 93 82 109 87 82 77 81 91 111 68 104 62 98 55 97 110 112 85 92 79 86 106 66 92 98 98 95 94 79 96 65 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI

%TW LOCATION 01H

-0.31 01H

-0.69 02H

+0.88 02H

+0.87 01H

-0.72 02H

+0.31 02H

+0.74 07C

-0.92 07H

-0.13 07H

+0.87 02H

+0.89 TSH

+0.22 01H

-0.60 02H

+0.57 01H

-0.78 04H

+0.91 02H

-0.70 02H

+0.61 03H

-0.04 01H

-0.34 01H

-0.33 01H

-0.47 05H

+0.83 01H

-0.69 03H

+0.14 02H

-0.48 02H

+0.84 02H

+0.91 05H

-0.18 07H

-0.06 07H

+0.88 03H

-0.41 03H

+0.21 03H

+0.82 01H

+0.91 03H

+0.64 03H

-0.43 02H

+0.70 03H

+0.53 03H

-0.85 02H

+0.62 01H

+0.92 04H

+0.95 02H

+0.79 01H

+0.89 02H

+0.83 01H

-0.12 06H

+0.79 02H

-0.63 02H

+0.58 02H

+0.79 02H

+0.76 01H

-0.51 02H

+0.26 EXT 01H 01H 02H 02H 01H 02H 02H 07C 07H 07H 02H TSH 01H 02H 01H 04H 02H 02H 03H 01H 01H 01H 05H 01H 03H 02H 02H 02H 05H 07H 07H 03H 03H 03H 01H 03H 03H 02H 03H 03H 02H 01H 04H 02H 01H 02H 01H 06H 02H 02H 02H 02H 01H 02H EXT 01H 01H 02H 02H 01H 02H 02H 07C DHT DHT 02H TSH O1H 02H 01H 04H 02H 02H 03H 01H 01H 01H 05H 01H 03H 02H 02H 02H 05H 07H 07H 03H 03H 03H 01H 03H 03H 02H 03H 03H 02H 01H 04H 02H 01H 02H 01H 06H 02H 02H 02H 02H 01H 02H CAL 66 129 129 129 66 66 129 85 155 155 63 123 95 66 95 129 129 129 129 129 95 129 129 129 129 155 63 95 95 63 63 66 66 66 129 129 129 129 129 129 179 69 129 129 155 155 127 127 127 129 127 127 129 129 LEG HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Page 8 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 30 62 0.27 40 62 0.30 0.40 0.54 0.33 0.30 70 62 0.25 82 62 0.15 88 62 0.36 0.19 106 62 0.42 21 63 0.33 0.22 41 63 0.20 43 63 0.18 109 63 0.34 0.16 111 63 0.35 0.14 121 63 0.28 133 63 0.08 34 64 0.24 40 64 0.34 70 64 0.10 0.21 80 64 0.57 88 64 0.28 0.27 50 66 0.37 66 66 0.26 0.21 88 66 0.22 0.17 0.54 0.38 110 66 0.52 0.37 93 67 0.25 105 67 0.30 0.27 66 68 0.39 0.13 0.17 0.51 88 68 0.37 110 68 0.26 0.27 118 68 0.27 122 68 0.41 0.22 123 69 0.40 0.18 135 69 0.18 70 70 0.18 DEG 80 94 89 97 99 92 94 106 93 94 94 97 80 82 86 95 44 79 63 84 98 142 266 75 58 95 89 80 106 126 86 96 49 104 91 104 102 77 78 89 109 93 80 110 103 70 83 94 78 73 102 46 142 59 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SA=

SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI

%TW LOCATION 02H

+0.81 01H

-0.76 01H

+0.36 02H

-0.33 02H

+0.72 03H

+0.41 02H

+0.84 TSH

+0.54 05H

+0.19 05H

+0.94 01H

+0.49 02H

+0.52 03H

-0.66 02H

+0.81 01H

+0.83 02H

+0.55 02H

-0.82 05H

-0.26 05H

+0.39 02H

+0.37 01H

-0.99 02H

+0.31 06H

+0.82 03H

-0.01 03H

+0.76 01H

+0.02 01H

+0.44 02H

+0.89 01H

-0.10 01H

-0.90 07H

+0.76 02H

+0.91 02H

-0.69 03H

+0.90 01H

-0.28 03H

+0.76 05H

+0.81 03H

+0.84 02H

-0.94 05H

+0.85 03H

-0.48 03H

+0.22 03H

+0.58 05H

+0.27 01H

-0.81 03H

+0.84 05H

+0.44 03H

+0.97 02H

+0.69 02H

-0.77 02H

+0.81 02H

-0.91 01H

-0.75 05H

-0.29 EXT EXT CAL # LEG 02H 01H 01H 02H 02H 03H 02H TSH 05H 05H 01H 02H 03H 02H 01H 02H 02H 05H 05H 02H 01H 02H 06H 03H 03H 01H 01H 02H 01H O1H 07H 02H 02H 03H 01H 03H 05H 03H 02H 05H 03H 03H 03H 05H 01H 03H 05H 03H 02H 02H 02H 02H 01H 05H 02H 01H 01H 02H 02H 03H 02H TSH 05H 05H 01H 02H 03H 02H 01H 02H 02H 05H 05H 02H 01H 02H 06H 03H 03H 01H 01H 02H 01H 01H 07H 02H 02H 03H 01H 03H 05H 03H 02H 05H 03H 03H 03H 05H 01H 03H 05H 03H 02H 02H 02H 02H 01H 05H 127 127 127 127 127 127 69 83 129 129 129 127 127 179 127 129 129 129 129 129 149 127 127 69 69 69 129 129 127 69 69 129 129 129 173 129 129 129 129 129 69 69 69 69 129 129 129 129 129 129 129 129 149 69 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 9 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 0.15 124 70 0.47 55 71 0.47 93 71 0.21 103 71 0.25 72 72 0.19 96 72 0.21 85 73 0.20 103 73 0.30 0.26 50 74 0.26 66 74 0.14 0.38 0.23 0.33 80 74 0.18 0.16 88 74 0.10 69 75 0.26 0.35 0.57 0.24 85 75 0.22 123 75 0.21 0.36 54 76 0.31 104 76 0.25 110 76 0.21 0.13 124 76 0.25 0.20 132 76 0.20 47 77 1.71 65 77 0.22 97 77 0.23 105 77 0.28 0.35 72 78 0.16 78 78 0.17 82 78 0.27 106 78 0.19 118 78 0.21 0.14 122 78 0.33 65 79 0.15 83 79 0.24 87 79 0.38 111 79 0.16 133 79 0.22 54 80 0.24 0.25 74 80 0.15 98 80 0.35 102 80 0.46 DEG 96 89 104 90 31 54 117 41 91 91 85 54 85 112 83 52 53 102 102 106 82 76 98 72 99 80 82 79 77 82 77 97 89 76 100 105 90 87 108 94 74 81 77 85 67 84 88 56 108 89 106 95 112 100 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 4 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND %TW LOCATION SAI 05H

+0.73 MAI 02H

+0.63 SAI 01H

+0.11 SAI 05H

+0.90 SAI 02H

+0.71 SAI 02H

-0.29 SAI 01H

+0.94 SAI 02H

+0.85 SAI 01H

-0.45 SAI 05H

+0.98 SAI 05H

+0.74 SAI 01H

-0.72 SAI 01H

-0.26 SAI 03H

-0.71 SAI 03H

+0.70 SAI 03H

-0.88 SAI 03H

-0.17 SAI TSH

+1.11 SAI 01H

+0.80 SAI 02H

-0.90 SAI 02H

+0.61 SAI 03H

+0.78 SAI 05H

+0.91 SAI 02H

-0.53 SAI 03H

-0.53 SAI 02H

+0.76 SAI 02H

+0.84 SAI 03H

+0.89 SAI 05H

+0.80 SAI 02H

-0.15 SAI 02H

+0.79 SAI 02H

+0.54 TWD 42 DCT

+0.00 SAI 04H

+0.02 SAI 01H

-0.68 SAI 02H

+0.77 SAI 05H

+0.21 SAI TSH

+0.50 SAI TSH

+0.16 SAI 01H

-0.85 SAI 01H

+0.13 SAI 01H

-0.73 SAI 01H

+0.93 SAI 01H

+0.07 SAI TSH

+0.52 SAI 06H

+0.83 SAI 01H

+0.42 SAI 02H

+0.88 SAI 01H

+0.50 MAI 05H

-0.47 SAI 05H

+0.77 SAI TSH

+0.52 SAI 05H

+0.58 SAI 01H

-0.53 EXT 05H 02H 01H 05H 02H 02H 01H 02H 01H 05H 05H 01H 01H 03H 03H 03H 03H TSH 01H 02H 02H 03H 05H 02H 03H 02H 02H 03H 05H 02H 02H 02H TEC 04H 01H 02H 05H TSH TSH 01H 01H 01H 01H 01H TSH 06H 01H 02H 01H 05H 05H TSH 05H 01H EXT 05H 02H 01H 05H 02H 02H 01H 02H 01H 05H 05H 01H 01H 03H 03H 03H 03H TSH 01H 02H 02H 03H 05H 02H 03H 02H 02H 03H 05H 02H 02H 02H TEH 04H 01H 02H 05H TSH TSH 01H 01H 01H 01H 01H TSH 06H 01H 02H 01H 05H 05H TSH 05H 01H CAL 69 129 69 153 153 69 153 153 153 153 69 69 69 69 69 69 69 72 69 69 69 69 153 129 129 69 153 153 153 129 129 149 3

69 153 153 153 60 59 153 153 132 132 129 60 153 153 153 149 69 69 60 153 170 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 60OUL 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attachbmnt 1 CSI-NDE-05-020 Page 10 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 0.34 0.35 67 81 0.13 81 81 0.21 83 81 0.25 95 81 0.25 103 81 0.54 115 81 0.44 0.29 133 81 0.20 0.12 0.19 0.21 66 82 0.16 0.44 0.15 116 82 0.24 0.15 0.19 79 83 0.17 89 83 0.24 131 83 0.29 139 83 0.17 66 84 0.32 0.22 70 84 0.34 0.20 82 84 0.14 110 84 0.32 114 84 0.24 91 85 0.26 121 85 0.16 123 85 0.31 68 86 0.45 0.20 72 86 0.11 110 86 0.39 124 86 0.29 103 87 0.31 121 87 0.54 0.21 129 87 0.54 0.17 80 88 0.20 0.52 0.22 114 88 0.36 122 88 0.24 0.16 77 89 0.08 58 90 0.21 0.20 70 90 0.21 0.25 DEG 100 99 83 52 79 75 107 104 106 42 71 53 79 107 96 91 117 127 94 65 103 97 103 93 82 106 104 64 94 87 103 78 98 93 66 114 89 81 92 91 110 106 60 68 87 64 78 98 60 97 86 102 78 86 CHN P=6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI MAI SAI MAI SAI SAI SAI SAI SAI SAI SAI

%TW LOCATION 03H

+0.33 05H

+0.15 TSH

+0.59 06H

+0.85 03H

-0.51 01H

-0.22 01H

-0.50 01H

-0.71 03H

+0.90 01H

-0.95 02H

-0.76 02H

+0.58 03H

+0.83 06H

+0.84 07H

-0.62 07H

+0.33 01H

+0.83 02H

+0.92 03H

+0.94 02H

+0.79 01H

+0.56 01H

+0.16 01H

+0.91 02H

-0.27 02H

-0.54 03H

-0.11 TSH

+0.53 02H

+0.81 01H

-0.30 01H

-0.84 01H

-0.45 03H

-0.29 01H

-0.58 03H

+0.56 04H

+0.88 TSH

+0.40 01H

+0.34 01H

-0.32 01H

+0.24 01H

-0.63 01H

+0.61 01H

+0.52 05H

+0.73 01H

-0.59 01H

+0.72 07H

+0.67 01H

-0.84 01H

-0.54 01H

+0.66 TSH

+0.34 01H

-0.67 01H

+0.78 03H

+0.86 05H

+0.83 EXT EXT CAL # LEG 03H 03H 153 HOT 05H 05H 153 HOT TSH TSH 59 HOT 06H 06H 153 HOT 03H 03H 153 HOT 01H 01H 153 HOT 01H O1H 153 HOT 01H 01H 153 HOT 03H 03H 153 HOT 01H 01H 180 HOT 02H 02H 180 HOT 02H 02H 180 HOT 03H 03H 180 HOT 06H 06H 69 HOT 07H 07H 69 HOT 07H 07H 69 HOT 01H 01H 153 HOT 02H 02H 153 HOT 03H 03H 153 HOT 02H 02H 69 HOT 01H 01H 153 HOT 01H 01H 149 HOT 01H 01H 149 HOT 02H 02H 69 HOT 02H 02H 69 HOT 03H 03H 69 HOT TSH TSH 59 HOT 02H 02H 153 HOT 01H 01H 153 HOT 01H 01H 153 HOT 01H 01H 178 HOT 03H 03H 132 HOT 01H 01H 132 HOT 03H 03H 69 HOT 04H 04H 69 HOT TSH TSH 60 HOT 01H 01H 149 HOT 01H 01H 132 HOT 01H 01H 149 HOT 01H 01H 153 HOT 01H 01H 153 HOT 01H 01H 153 HOT 05H 05H 153 HOT 01H 01H 69 HOT 01H O1H 69 HOT 07H 07H 69 HOT 01H 01H 149 HOT 01H 01H 153 HOT 01H 01H 153 HOT TSH TSH 60 HOT 01H 01H 69 HOT 01H 01H 69 HOT 03H 03H 69 HOT 05H 05H 69 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attachment I CSI-NDE-05-020 Page 11 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 80 90 0.26 0.33 114 90 0.24 122 90 0.29 49 91 0.39 69 91 0.19 0.16 123 91 0.31 52 92 0.26 76 92 0.19 82 92 0.16 86 92 0.28 0.27 122 92 0.21 49 93 0.28 0.45 71 93 0.27 105 93 0.37 121 93 0.29 133 93 0.29 60 94 0.28 92 94 0.33 102 94 0.35 0.27 118 94 0.16 0.19 124 94 0.30 61 95 0.31 69 95 0.26 103 95 0.41 133 95 0.39 86 96 0.14 116 96 0.25 65 97 0.31 0.20 0.22 0.26 0.52 69 97 0.22 0.35 0.18 77 97 0.15 81 97 0.13 89 97 0.15 103 97 0.47 109 97 0.30 129 97 0.27 133 97 0.22 40 98 0.18 0.16 0.24 102 98 0.25 59 99 0.29 0.14 DEG CHN IND %TW LOCATION 63 55 86 81 84 74 75 88 97 84 80 95 108 84 103 79 105 79 77 104 141 68 92 84 92 93 99 82 60 92 98 142 103 98 82 92 95 88 87 100 68 87 122 78 97 102 69 103 114 97 62 62 78 89 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI MAI SAI SAI SAI SAI SAI SAI 02H

+0.79 03H

+0.78 01H

+0.39 03H

+0.83 02H

+0.53 01H

+0.81 01H

-0.31 02H

+0.92 06H

-0.39 05H

+0.72 05H

+0.89 01H

-0.87 02H

-0.80 TO+1.00 01H

-0.77 02H

+0.84 03H

+0.54 03H

+0.84 01H

+0.44 01H

-0.12 01H

+0.63 03H

-0.21 01H

-0.25 02H

+0.74 02H

-0.28 01H

-0.04 01H

+0.85 01H

-0.15 05H

+0.84 01H

-0.80 01H

+0.51 02H

-0.65 02H

+0.78 01H

+0.52 01H

-0.50 01H

+0.17 01H

+0.77 06H

-0.74 06H

+0.59 01H

-0.38 01H

+0.76 06H

-0.91 05H

+0.85 04H

-0.62 02H

+0.91 01H

-0.75 02H

+0.86 03H

+0.91 01H

+0.76 06H

+0.94 06H

-0.47 07H

-0.50 02H

+0.07 01H

+0.78 01H

-0.56 EXT 02H 03H 01H 03H 02H 01H 01H 02H 06H 05H 05H 01H 02H 01H 02H 03H 03H 01H 01H 01H 03H 01H 02H 02H 01H 01H 01H 05H 01H 01H 02H 02H 01H 01H 01H 01H 06H 06H 01H 01H 06H 05H 04H 02H 01H 02H 03H 01H 06H 06H 07H 02H 01H 01H EXT 02H 03H 01H 03H 02H 01H 01H 02H 06H 05H 05H 01H 02H 01H 02H 03H 03H 01H 01H 01H 03H 01H 02H 02H 01H 01H 01H 05H 01H 01H 02H 02H 01H 01H 01H 01H 06H 06H 01H 01H 06H 05H 04H 02H 01H 02H 03H 01H 06H 06H 07H 02H 01H 01H CAL # LEG 69 HOT 69 HOT 149 HOT 153 HOT 69 HOT 140 HOT 140 HOT 153 HOT 69 HOT 69 HOT 153 HOT 153 HOT 153 HOT 153 HOT 69 HOT 69 HOT 69 HOT 149 HOT 149 HOT 149 HOT 69 HOT 153 HOT 149 HOT 149 HOT 149 HOT 149 HOT 149 HOT 69 HOT 69 HOT 149 HOT 149 HOT 153 HOT 149 HOT 69 HOT 69 HOT 69 HOT 69 HOT 69 HOT 69 HOT 69 HOT 69 HOT 69 HOT 153 HOT 153 HOT 149 HOT 149 HOT 149 HOT 149 HOT 155 HOT 155 HOT 155 HOT 149 HOT 69 HOT 69 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Page 12 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 75 99 0.17 0.40 0.23 111 99 0.24 133 99 0.43 52 100 0.19 62 100 0.10 68 100 0.21 86 100 0.18 88 100 0.23 92 100 0.35 98 100 0.28 108 100 0.21 110 100 0.21 118 100 0.21 124 100 0.27 53 101 0.34 0.31 0.30 61 101 0.32 0.20 0.37 65 101 0.35 0.24 0.29 0.15 67 101 0.20 0.24 69 101 0.23 0.57 71 101 0.21 75 101 0.18 0.14 83 101 0.28 30 102 0.28 52 102 0.18 0.30 0.21 54 102 0.18 62 102 0.16 66 102 0.26 68 102 0.37 0.18 70 102 0.49 74 102 0.13 94 102 0.29 106 102 0.12 108 102 0.24 122 102 0.12 29 103 0.24 51 103 0.21 53 103 0.21 55 103 0.17 61 103 0.58 68 101 77 83 105 80 110 86 80 252 90 102 83 52 84 97 96 91 102 95 66 85 110 103 104 80 53 69 109 95 90 65 82 67 87 57 94 83 73 84 110 114 70 106 77 98 59 85 67 12 54 64 60 85 P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 1 SCI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI 2

SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI 02H =

0.56 02H 02H

+0.83 02H 05H

+0.83 05H 01H

+0.29 01H 01H

+0.84 01H 02H

+0.93 02H TSH

+0.08 TSH 05H

+0.77 05H 05H

+0.72 05H 05H

+0.71 05H 01H

+0.59 01H 01H

-0.15 01H 01H

+0.81 01H 01H

-0.66 01H 01H

-0.40 01H 01H

+0.67 01H 02H

+0.71 02H 03H

-0.54 03H 04H

+0.47 04H 02H

+0.39 02H 07H

+0.25 07H 06H

+0.61 06H 01H

-0.38 01H 02H

+0.64 02H 03H

+0.54 03H 03H

-0.54 03H O1H

-0.76 01H 02H

+0.82 02H 03H

+0.93 03H 04H

+0.53 04H 05H

+1.00 05H 01H

-0.44 01H 01H

-0.02 01H 02H

+0.88 02H 03H

+0.05 03H 01H

-0.23 01H 02H

+0.74 02H 05H

+0.69 05H 03H

+0.02 03H 01H

+0.88 01H 02H

+0.67 02H 01H

-0.33 01H 02H

+0.90 02H 02H

+0.59 02H 02H

+1.00 02H 01H

+0.11 01H 01H

-0.82 01H 01H

-0.17 01H 01H

+0.24 01H TSH

-1.43 TSH 03H

+0.84 03H 01H

-0.25 01H 04H

+0.53 04H 02H

+0.81 02H 02H 02H 05H 01H 01H 02H TSH 05H 05H 05H 01H 01H 01H 01H 01H 01H 02H 03H 04H 02H 07H 06H 01H 02H 03H 03H 01H 02H 03H 04H 05H 01H 01H 02H 03H 01H 02H 05H 03H 01H 02H 01H 02H 02H 02H 01H 01H 01H 01H TSH 03H 01H 04H 02H 69 69 69 149 149 150 97 151 133 133 133 133 136 136 136 136 150 150 150 151 151 170 151 151 151 151 151 151 151 151 151 151 151 135 150 150 150 150 150 151 151 151 151 151 151 133 136 136 136 97 150 150 150 151 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803=P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Page 13 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 0.30 65 103 0.22 67 103 0.31 109 103 0.26 113 103 0.18 24 104 0.20 32 104 0.28 0.17 52 104 0.24 96 104 0.12 0.14 114 104 0.59 118 104 0.69 49 105 0.37 57 105 0.10 65 105 0.43 0.22 0.41 81 105 0.16 0.20 103 105 0.21 113 105 0.15 18 106 0.31 0.29 0.33 0.30 0.23 40 106 0.34 0.40 0.15 0.26 50 106 0.21 52 106 0.33 108 106 0.19 0.12 110 106 0.35 118 106 0.18 7

107 0.37 13 107 0.18 0.14 19 107 0.27 21 107 0.26 0.22 35 107 0.15 55 107 0.25 0.19 0.19 0.08 0.12 57 107 0.17 0.16 0.18 0.14 59 107 0.19 DEG CHN 87 P 6 85 P 6 104 P 6 86 P 6 101 P 6 81 P 6 99 P 6 62 P 6 78 P 6 108 P 6 90 P 6 108 P 6 101 P 6 103 P 6 76 P 1 107 P 6 82 P 6 73 P 6 82 P 6 71 P 6 91 P 6 74 P 6 59 P 6 257 P 6 92 P 6 91 P 6 86 P 6 89 P 6 91 P 6 65 P 6 101 P 6 80 P 6 110 P 6 91 P 6 51 P 6 97 P 6 73 P 6 105 P 6 59 P 6 85 P 6 74 P 6 272 P 6 96 P 6 48 P 6 79 P 6 81 P 6 71 P 6 69 P 1 131 P 1 67 P 6 74 P 6 122 P 6 92 P 6 156 P 6 IND SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SCI SAI SAI MAI SAI SAI SAI SAI SAI MAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SCI SCI SAI SAI SAI SAI SAI

%TW LOCATION 05H

+0.83 01H

+0.23 01H

-0.12 01H

-0.24 01H

-0.28 04H

+0.51 O1H

+0.34 03H

+0.69 05H

+1.12 01H

+0.57 01H

+0.16 01H

-0.36 01H

-0.48 01H

+0.65 TSH

-0.07 01H

+0.92 02H

+0.89 05H

+0.82 01H

+0.29 02H

+0.15 01H

-0.77 01H

-0.69 01H

-0.60 02H

-0.53 03H

+0.79 04H

-0.38 05H

+0.17 01H

-0.24 02H

+0.76 02H

+0.02 05H

+0.14 01H

+0.61 02H

+0.52 02H

+0.75 02H

-0.79 02H

+0.76 02H

+0.81 01H

+0.20 02H

+0.56 03H

-0.81 04H

+0.86 01H

+0.32 01H

-0.66 04H

+0.88 01H

-0.18 01H

+0.91 02H

+0.37 TSH

-0.10 TSH

+0.08 01H

-0.34 01H

+0.86 02H

-0.20 04H

+1.15 TSH

+0.18 EXT EXT CAL # LEG 05H 01H 01H 01H 01H 04H 01H 03H 05H 01H 01H 01H 01H 01H TSH 01H 02H 05H 01H 02H 01H 01H 01H 02H 03H 04H 05H 01H 02H 02H 05H 01H 02H 02H 02H 02H 02H 01H 02H 03H 04H 01H 01H 04H 01H 01H 02H TSH TSH 01H 01H 02H 04H TSH 05H 01H 01H 01H 01H 04H 01N 03H 05H 01H 01H 01H 01H 01H TSH 01H 02H 05H 01H 02H 01H 01H 01H 02H 03H 04H 05H 01H 02H 02H 05H 01H 02H 02H 02H 02H 02H 01H 02H 03H 04H 01H 01H 04H 01H 01H 02H TSH TSH 01H 01H 02H 04H TSH 151 151 151 136 136 150 150 150 150 135 135 136 136 150 97 150 150 150 133 133 136 136 148 148 148 148 148 150 150 150 150 178 150 135 135 135 135 148 148 148 148 148 148 150 150 150 150 96 96 150 150 150 150 96 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 14 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 63 107 0.56 0.34 0.26 0.25 65 107 0.20 71 107 0.29 87 107 0.15 129 107 0.30 8

108 0.25 12 108 0.68 16 108 0.18 0.41 24 108 0.24 0.40 40 108 0.39 0.26 54 108 0.15 56 108 0.24 0.10 60 108 0.18 68 108 0.26 84 108 0.14 86 108 0.22 90 108 0.38 0.14 104 108 0.38 116 108 0.16 118 108 0.36 1

109 0.17 9

109 0.32 23 109 0.58 27 109 0.22 31 109 0.22 43 109 0.16 49 109 0.34 51 109 0.09 67 109 0.16 71 109 0.18 97 109 0.18 103 109 0.35 0.19 121 109 0.22 10 110 0.25 0.22 0.19 12 110 0.18 0.23 14 110 0.24 0.27 18 110 0.26 24 110 0.30 0.27 0.36 0.29 DEG 106 109 89 57 69 97 76 67 87 89 67 109 88 88 102 84 73 105 133 74 103 100 83 82 63 78 95 106 111 97 88 77 63 75 105 41 80 65 87 77 46 86 104 94 87 54 60 74 90 100 87 100 85 105 CHN IND P 6 SA=

P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAT P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI

%TW LOCATION EXT 01H

+0.27 01H 03H

+0.77 03H 05H

-0.49 05H 05H

+0.86 05H 04H

+1.01 04H 01H

+0.57 01H 04H

+0.80 04H 01H

-0.75 01H 02H

-0.46 02H 01H

-0.38 01H 01H

+0.85 01H 06H

+0.70 06H 04H

+0.91 04H 05H

+0.75 05H 01H

+0.83 01H 06H

-0.50 06H TSH

+0.13 TSH 02H

+0.56 02H TSH

+0.23 TSH 03H

+0.79 03H 01H

+0.88 01H 02H

+0.79 02H 02H

-0.41 02H 01H

-0.97 01H 03H

+0.85 03H 01H

+0.62 01H 01H

+0.75 01H 01H

-0.53 01H 01H

-0.81 TSH 02H

+0.87 02H 02H

+0.78 02H 02H

+0.79 02H 02H

+0.87 02H 02H

+0.90 02H 01H

+0.48 01H 04H

+0.68 04H 02H

+0.97 02H 02H

+0.83 02H 01H

-0.18 01H 02H

+0.33 02H 02H

-0.48 02H 02H

+0.83 02H 05H

+0.46 05H 06H

+0.11 06H 06H

-0.86 06H 02H

+0.92 02H 04H

+0.92 04H 02H

-0.36 02H 04H

+0.82 04H 01H

-0.90 TO+1.00 01H 01H

-0.45 01H 02H

+0.55 02H 04H

+0.71 04H 06H

+0.93 06H EXT 01H 03H 05H 05H 04H 01H 04H 01H 02H 01H 01H 06H 04H 05H 01H 06H TSH 02H TSH 03H 01H 02H 02H 01H 03H 01H 01H 01H 01H 02H 02H 02H 02H 02H 01H 04H 02H 02H 01H 02H 02H 02H 05H 06H 06H 02H 04H 02H 04H 01H 01H 02H 04H 06H CAL # LEG 150 HOT 150 HOT 150 HOT 150 HOT 150 HOT 140 HOT 135 HOT 135 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 150 HOT 150 HOT 97 HOT 150 HOT 96 HOT 150 HOT 150 HOT 135 HOT 135 HOT 135 HOT 135 HOT 135 HOT 135 HOT 135 HOT 164 HOT 148 HOT 148 HOT 148 HOT 148 HOT 150 HOT 150 HOT 150 HOT 150 HOT 150 HOT 135 HOT 135 HOT 135 HOT 135 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 15 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG 0.16 30 110 0.12 0.30 36 110 0.28 46 110 0.17 62 110 0.64 0.42 64 110 0.20 70 110 0.43 110 110 0.37 9

111 0.51 15 lll 0.39 17 111 0.37 0.39 23 111 0.18 27 111 0.36 0.28 35 111 0.20 37 111 0.25 39 111 0.49 43 111 0.37 0.22 47 111 0.18 57 111 0.33 59 111 0.22 63 111 0.23 65 111 0.35 71 111 0.35 0.22 lll 111 0.35 0.17 6

112 0.27 8

112 0.39 14 112 0.23 0.21 0.24 28 112 0.19 40 112 0.31 0.20 44 112 0.22 48 112 0.16 58 112 0.20 64 112 0.14 70 112 0.32 80 112 0.31 0.24 118 112 0.29 0.24 9

113 0.18 11 113 0.15 0.49 0.30 59 113 0.11 61 113 0.20 80 65 88 41 83 99 90 88 96 92 113 84 110 97 74 84 85 59 60 94 102 104 79 88 38 78 74 104 86 87 48 110 85 99 48 55 69 102 107 62 257 71 51 82 96 81 89 98 101 88 104 87 65 73 CHN IND P 6 SA=

P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI

%TW LOCATION EXT 06H

-0.76 06H 03H

+0.93 03H 04H

+0.15 04H 02H

+0.80 02H 02H

+0.79 02H 04H

+0.47 04H 08H

+0.82 08H 06H

-0.18 06H 04H

+0.79 04H 02H

+0.63 02H 06H

-0.39 06H 01H

-0.26 01H 01H

-0.65 01H 02H

+0.68 02H 01H

+0.24 01H 01H

+0.88 01H 04H

+0.23 04H 06H

+0.83 06H 02H

+0.33 02H 01H

-0.03 01H 02H

+0.16 02H 04H

+0.22 04H 06H

+0.93 06H 02H

+0.97 02H 04H

+0.47 04H 06H

+0.79 06H 04H

+0.75 04H 01H

-0.49 01H 02H

+0.89 02H 01H

+0.77 01H 03H

+0.69 03H 05H

-0.31 05H 02H

-0.62 02H 01H

+0.38 01H 02H

+0.97 02H 04H

+1.00 04H 04H

-0.30 04H 01H

+0.71 01H 07H

+0.96 07H 02H

+0.35 02H 02H

+0.71 02H 02H

+0.97 02H 02H

+0.93 02H 02H

+0.68 02H 01H

+0.55 01H 01H

-0.72 01H 02H

-0.46 02H 02H

+0.63 02H 01H

+0.73 01H 01H

-0.57 01H 01H

+0.40 01H 03H

+0.82 03H 02H

+0.84 02H 02H

+0.34 02H EXT 06H 03H 04H 02H 02H 04H 08H 06H 04H 02H 06H 01H 01H 02H 01H 01H 04H 06H 02H 01H 02H 04H 06H 02H 04H 06H 04H 01H 02H 01H 03H 05H 02H 01H 02H 04H 04H 01H 07H 02H 02H 02H 02H 02H 01H 01H 02H 02H 01H 01H 01H 03H 02H 02H CAL 148 148 148 148 148 148 148 148 148 135 147 147 147 147 147 147 147 147 170 147 147 147 148 148 148 148 148 148 148 135 135 147 147 147 147 147 147 147 147 147 147 147 147 147 147 147 135 135 147 147 147 147 147 147 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbhent 1 CSI-NDE-05-020 Page 16 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 69 113 0.34 97 113 0.23 0.18 0.16 121 113 0.25 129 113 0.19 6

114 0.19 10 114 0.36 14 114 0.20 0.18 20 114 0.25 24 114 0.26 0.42 0.25 0.34 44 114 0.36 64 114 0.13 70 114 0.36 0.22 82 114 0.18 106 114 0.34 118 114 0.19 0.21 0.17 120 114 0.33 0.21 9

115 0.28 11 115 0.16 0.26 15 115 0.29 0.14 29 115 0.16 39 115 0.28 59 115 0.40 0.37 0.22 63 115 0.23 0.20 0.18 65 115 0.18 67 115 0.36 0.12 0.15 93 115 0.15 103 115 0.53 121 115 0.95 0.37 16 116 0.19 18 116 0.36 46 116 0.25 48 116 0.14 0.17 0.09 0.15 DEG 109 108 73 90 96 106 86 93 100 117 104 80 104 91 87 164 72 108 90 96 105 77 74 94 111 86 71 72 93 105 118 38 52 87 84 42 86 54 62 66 88 81 57 77 92 96 91 59 112 105 52 84 35 46 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 1 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 1 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SAI SAI MAI MAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SCI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SCI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI

%TW LOCATION 01H

-0.74 01H

-0.72 02H

-0.21 04H

+0.86 02H

+0.75 01H

+0.65 01H

+0.87 03H

-0.17 01H

-0.11 01H

+0.71 01H

+0.78 01H

-0.53 01H

+0.89 03H

+0.83 04H

+0.98 TSH

-0.04 02H

+0.99 02H

+0.86 04H

+0.86 01H

-0.28 01H

-0.52 01H

+0.83 02H

-0.21 02H

+0.20 02H

-0.60 02H

+0.64 02H

+0.65 03H

-0.22 05H

+0.71 01H

-0.69 01H

+0.43 02H

+0.19 TSH

-0.06 02H

+0.33 04H

+0.33 05H

+0.77 01H

+0.77 01H

+0.07 03H

+0.76 04H

+0.37 01H

+0.33 03H

+0.25 03H

+0.69 01H

-0.72 02H

-0.34 02H

-0.66 02H

+0.73 01H

-0.18 01H

+0.24 02H

+0.66 01H

-0.03 01H

+0.70 02H

+0.22 02H

+0.82 EXT EXT CAL # LEG 01H 01H 02H 04H 02H 01H 01H 03H 01H 01H 01H 01H 01H 03H 04H TSH 02H 02H 04H 01H 01H 01H 02H 02H 02H 02H 02H 03H 05H 01H 01H 02H TSH 02H 04H 05H 01H 01H 03H 04H 01H 03H 03H 01H 02H 02H 02H 01H 01H 02H 01H 01H 02H 02H 01H 01H 02H 04H 02H 01H 01H 03H 01H 01H 01H 01H 01H 03H 04H TSH 02H 02H 04H 01H 01H 01H 02H 02H 02H 02H 02H 03H 05H 01H 01H 02H TSH 02H 04H 05H 01H 01H 03H 04H 01H 03H 03H 01H 02H 02H 02H 01H 01H 02H 01H 01H 02H 02H 147 135 135 135 135 135 147 170 147 147 178 147 147 147 147 91 147 147 147 170 135 133 133 133 133 133 146 146 146 146 146 146 92 146 146 146 146 146 146 146 146 146 146 135 135 133 133 146 146 146 146 146 146 146 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803 P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attachment.

CSI-NDE-05-020 Page 17 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL #

52 116 0.18 116 116 0.13 0.27 0.14 120 116 0.15 9

117 0.23 0.45 21 117 0.25 0.24 27 117 0.19 45 117 0.17 47 117 0.17 0.31 49 117 0.26 0.30 0.16 63 117 0.20 65 117 0.25 0.26 71 117 0.23 79 117 0.16 115 117 0.61 0.30 10 118 0.20 0.24 12 118 0.34 16 118 0.29 38 118 0.13 0.32 46 118 0.47 0.24 48 118 0.17 0.16 56 118 0.35 58 118 0.42 64 118 0.19 70 118 0.21 84 118 0.21 114 118 0.21 118 118 0.18 9

119 0.19 0.16 11 119 0.36 15 119 0.23 43 119 0.25 47 119 0.37 0.17 0.24 49 119 0.55 57 119 0.21 67 119 0.43 75 119 0.20 93 119 0.27 0.21 49 95 91 98 88 94 103 86 83 129 59 113 78 70 99 55 82 95 101 89 130 98 80 110 69 106 86 72 102 94 91 43 62 79 101 82 56 114 104 96 95 55 92 88 73 90 62 73 93 55 99 83 79 62 P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI 01H 01H 02H 02H 01H 01H 02H 01H 01H 01H 03H 01H 02H 02H 03H 05H 02H 01H 01H 02H 02H 02H 02H 04H 07H 03H 07H 01H 02H 01H 05H 02H 05H 01H 01H 03H 06H 01H 02H 01H 01H 02H 03H 05H 01H 04H 05H 05H 02H 02H 01H 01H 02H 02H

+0.74

+0.68

-0.53

+0.28

+0.73

+0.56

-0.91

-0.70

+0.70

-0.81

+0.66

-0.24

+0.34

-0.34

+0.50

+0.93

+0.85

-0.15

+0.45

+0.77

+0.23

+0.82

-0.16

+0.20

+0.44

-0.17

+0.17

+0.70

+0.26

+0.28

+0.72

+0.53

+0.46

-0.45

+0.57

+0.77

+0.75

-0.86

-0.05

+0.77

-0.19

+0.77

+0.85

+0.53

+0.79

+0.70

-0.14

+0.70

+0.59

+0.76

+0.19

-0.34

+0.80

-0.48 01H 01H 01H 01H 02H 02H 02H 02H 01H 01H 01H 01H 02H 02H 01H 01H 01H 01H 01H 01H 03H 03H 01H 01H 02H 02H 02H 02H 03H 03H 05H 05H 02H 02H 01H 01H O1H 01H 02H 02H 02H 02H 02H 02H 02H 02H 04H 04H 07H 07H 03H 03H 07H 07H 01H 01H 02H 02H 01H 01H 04H 05H 02H 02H 05H 05H 01H 01H 01H 01H 03H 03H 06H 06H 01H 01H 02H 02H 01H 01H 01H 01H 02H 02H 03H 03H 05H 05H 01H 01H 04H 04H 05H 05H 05H 05H 02H 02H 02H 02H 01H 01H 01H 01H 02H 02H 02H 02H 146 133 133 133 133 146 146 146 146 146 146 146 146 146 146 146 146 146 146 146 146 133 133 146 146 146 146 146 146 146 146 146 146 146 146 146 146 135 178 133 145 145 145 145 145 146 146 146 146 146 146 146 135 135 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attachment.

CSI-NDE-05-020 Page 18 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 121 119 0.47 0.26 8

120 0.27 0.23 0.37 36 120 0.24 40 120 0.25 0.21 48 120 0.18 0.20 112 120 0.22 0.23 13 121 0.38 0.20 27 121 0.13 49 121 0.46 0.23 0.35 55 121 0.56 57 121 0.22 67 121 0.26 0.20 69 121 0.20 101 121 0.19 0.46 121 121 0.38 8

122 0.30 14 122 0.18 18 122 0.24 0.26 20 122 0.20 0.32 24 122 0.21 30 122 0.26 40 122 0.23 0.19 46 122 0.19 58 122 0.19 70 122 0.27 88 122 0.15 116 122 0.21 9

123 0.19 11 123 0.21 19 123 0.21 29 123 0.12 37 123 0.28 41 123 0.19 49 123 0.21 0.19 0.25 63 123 0.18 0.22 65 123 0.21 0.19 DEG CHN 95 P 6 93 P 6 122 P 6 82 P 6 93 P 6 85 P 6 86 P 6 72 P 6 56 P 6 90 P 6 118 P 6 86 P 6 93 P 6 55 P 6 77 P 6 96 P 6 68 P 6 83 P 6 97 P 6 83 P 6 101 P 6 65 P 6 64 P 6 70 P 6 96 P 6 93 P 6 72 P 6 81 P 6 89 P 6 91 P 6 84 P 6 72 P 6 61 P 6 68 P 6 78 P 6 135 P 6 88 P 6 51 P 6 92 P 6 87 P 6 84 P 6 65 P 6 111 P 6 47 P 6 54 P 6 69 P 6 63 P 6 45 P 6 66 P 6 90 P 6 53 P 6 121 P 6 59 P 6 56 P 6 IND SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI

%TW LOCATION 02H

+0.52 04H

+0.66 02H

-0.67 06H

+0.81 03H

-0.39 05H

+0.44 03H

+0.64 05H

+0.56 01H

+0.83 04H

+0.70 01H

+0.51 02H

-0.14 03H

-0.27 07H

-0.30 02H

+0.87 01H

+0.10 05H

+0.67 06H

+0.71 01H

+0.77 02H

-0.16 01H

-0.24 02H

+0.42 02H

+0.69 01H

+0.77 02H

-0.37 02H

-0.37 02H

+0.51 04H

+0.74 O1H

+0.69 05H

+0.72 02H

+0.72 03H

-0.68 01H

+0.60 03H

+0.59 01H

+0.55 04H

+0.18 01H

+0.10 03H

+0.85 01H

+0.48 02H

+0.90 04H

+0.81 01H

-0.15 02H

-0.20 05H

+0.32 01H

-0.03 02H

+0.76 02H

+0.90 01H

-0.64 02H

+0.72 03H

-0.35 02H

-0.14 03H

+0.88 02H

-0.39 02H

+0.33 EXT 02H 04H 02H 06H 03H 05H 03H 05H 01H 04H 01H 02H 03H 07H 02H 01H 05H 06H 01H 02H 01H 02H 02H 01H 02H 02H 02H 04H 01H 05H 02H 03H 01H 03H 01H 04H 01H 03H 01H 02H 04H 01H 02H 05H 01H 02H 02H 01H 02H 03H 02H 03H 02H 02H EXT 02H 04H 02H 06H 03H 05H 03H 05H 01H 04H 01H 02H 03H 07H 02H 01H 05H 06H 01H 02H 01H 02H 02H 01H 02H 02H 02H 04H 01H 05H 02H 03H 01H 03H 01H 04H 01H 03H 01H 02H 04H 01H 02H 05H 01H 02H 02H 01H 02H 03H 02H 03H 02H 02H CAL # LEG 133 HOT 133 HOT 145 HOT 145 HOT 170 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 133 HOT 133 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 133 HOT 133 HOT 133 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 135 HOT 133 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT 144 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attachzxmt I CSI-NDE-05-020 Page 19 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION 79 123 0.19 81 123 0.24 93 123 0.24 18 124 0.33 24 124 0.34 0.17 0.39 0.13 46 124 0.30 0.21 0.25 0.63 0.23 48 124 0.22 0.37 50 124 0.24 56 124 0.24 62 124 0.22 70 124 0.21 0.36 78 124 0.51 9

125 0.20 0.26 11 125 0.22 17 125 0.22 19 125 0.15 0.45 25 125 0.18 0.13 33 125 0.18 45 125 0.24 49 125 0.20 51 125 0.20 0.18 55 125 0.23 0.39 57 125 0.35 63 125 0.26 67 125 0.26 0.31 71 125 0.29 79 125 0.33 81 125 0.50 0.31 0.23 6

126 0.25 0.25 10 126 0.18 30 126 0.15 0.18 40 126 0.27 0.12 46 126 0.19 0.25 92 P 6 84 P 6 92 P 6 92 P 6 92 P 6 95 P 6 97 P 6 84 P 6 89 P 6 78 P 6 93 P 6 93 P 6 71 P 6 57 P 6 86 P 6 89 P 6 90 P 6 77 P 6 88 P 6 86 P 6 97 P 6 74 P 6 82 P 6 99 P 6 87 P 6 35 P 6 87 P 6 86 P 6 75 P 6 72 P 6 71 P 6 80 P 6 93 P 6 62 P 6 84 P 6 95 P 6 89 P 6 76 P 6 84 P 6 95 P 6 98 P 6 82 P 6 89 P 6 94 P 6 83 P 6 88 P 6 83 P 6 90 P 6 55 P 6 92 P 6 84 P 6 171 P 6 82 P 6 70 P 6 SA=

SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI MAI SAI SAI SAI SAI MAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI 01H

+0.91 02H

+0.68 01H

-0.74 05H

-0.27 01H

+0.34 03H

-0.19 05H

-0.14 05H

+0.75 01H

-0.47 02H

+0.55 04H

+0.82 05H

+0.63 05H

-0.65 03H

+0.87 04H

+0.70 01H

-0.39 01H

+0.46 01H

-0.62 01H

-0.27 02H

+0.85 01H

-0.71 01H

+0.65 05H

+0.81 01H

-0.24 04H

+0.25 02H

-0.58 02H

+0.40 03H

-0.26 03H

+0.82 05H

+0.07 04H

+0.58 01H

+0.84 02H

-0.49 02H

+0.95 01H

-0.38 01H

+0.82 02H

+0.44 02H

+0.74 01H

-0.61 01H

+0.29 01H

-0.68 01H

-0.62 02H

-0.02 03H

+0.21 04H

+0.62 01H

+0.79 07H

+0.51 01H

+0.27 03H

+0.48 07H

-0.24 02H

+0.86 02H

-0.40 01H

+0.69 03H

+0.78 EXT 01H 02H 01H 05H 01H 03H 05H 05H 01H 02H 04H 05H 05H 03H 04H 01H 01H 01H 01H 02H 01H 01H 05H 01H 04H 02H 02H 03H 03H 05H 04H 01H 02H 02H 01H 01H 02H 02H 01H 01H 01H 01H 02H 03H 04H 01H 07H 01H 03H 07H 02H 02H 01H 03H EXT 01H 02H 01H 05H 01H 03H 05H 05H 01H 02H 04H 05H 05H 03H 04H 01H 01H 01H 01H 02H 01H 01H 05H 01H 04H 02H 02H 03H 03H 05H 04H 01H 02H 02H 01H 01H 02H 02H 01H 01H 01H 01H 02H 03H 04H 01H 07H 01H 03H 07H 02H 02H 01H 03H CAL #

144 133 133 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 144 133 133 133 144 144 144 144 144 144 144 144 144 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 20 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.44 95 P 6 SAI 04H

+0.50 04H 04H 144 HOT 5803P 0.18 84 P 6 SAI 05H

+0.95 05H 05H 144 HOT 5803P 0.29 79 P 6 SAI 06H

-0.21 06H 06H 144 HOT 5803P 58 126 0.30 99 P 6 SAI 01H

+0.53 01H 01H 143 HOT 5803P 0.14 66 P 6 SAI 02H

+0.78 02H 02H 143 HOT 5803P 0.16 60 P 6 SAI 04H

+0.80 04H 04H 143 HOT 5803P 66 126 0.39 94 P 6 MAI 01H

+0.06 01H 01H 143 HOT 5803P 0.22 63 P 6 MAI 02H

-0.06 02H 02H 143 HOT 5803P 70 126 0.43 114 P 6 SAI 01H

+0.56 01H 01H 143 HOT 5803P 0.22 45 P 6 SAI 02H

-0.37 02H 02H 143 HOT 5803P 0.31 96 P 6 SAI 03H

+0.85 03H 03H 143 HOT 5803P 92 126 0.29 101 P 6 SAI 02H

+0.85 02H 02H 133 HOT 5803P 118 126 0.22 121 P 6 SAI 01H

+0.71 01H 01H 133 HOT 5803P 11 127 0.13 117 P 6 SAI 02H

-0.86 02H 02H 143 HOT 5803P 0.16 39 P 6 SAI 02H

-0.50 02H 02H 143 HOT 5803P 13 127 0.20 70 P 6 SAI 01H

-0.24 01H 01H 143 HOT 5803P 0.23 78 P 6 SAI 04H

+0.78 04H 04H 143 HOT 5803P 37 127 0.19 65 P 6 SAI 01H

-0.38 01H 01H 143 HOT 5803P 39 127 0.14 63 P 6 SAI 02H

-0.44 02H 02H 143 HOT 5803P 0.18 115 P 6 SAI 02H

+0.55 02H 02H 143 HOT 5803P 0.19 39 P 6 SAI 03H

+0.54 03H 03H 143 HOT 5803P 49 127 0.16 61 P 6 SAI 01H

-0.85 01H 01H 143 HOT 5803P 55 127 0.14 88 P 6 SAI 01H

-0.78 01H 01H 143 HOT 5803P 59 127 0.19 95 P 6 SAI 02H

+0.53 02H 02H 143 HOT 5803P 63 127 0.34 103 P 6 MAI 01H

+0.19 01H 01H 143 HOT 5803P 65 127 0.31 85 P 6 SAI 02H

+0.63 02H 02H 143 HOT 5803P 71 127 0.19 66 P 6 SAI 06H

+0.86 06H 06H 143 HOT 5803P 85 127 0.25 85 P 6 SAI 02H

+0.70 02H 02H 133 HOT 5803P 101 127 0.17 98 P 6 SAI 02H

+0.22 02H 02H 133 HOT 5803P 6

128 0.40 84 P 6 SAI 03H

-0.44 03H 03H 143 HOT 5803P 12 128 0.28 94 P 6 SAI 03H

+0.69 03H 03H 178 HOT 5803P 14 128 0.14 56 P 6 SAI 03H

-0.32 03H 03H 143 HOT 5803P 0.16 69 P 6 SAI 04H

+0.75 04H 04H 143 HOT 5803P 0.14 65 P 6 SAI 05H

-0.94 05H 05H 143 HOT 5803P 20 128 0.10 87 P 6 SAI 03H

+0.87 03H 03H 143 HOT 5803P 40 128 0.24 75 P 6 SAI 01H

-0.29 01H 01H 143 HOT 5803P 0.34 81 P 6 SAI 02H

-0.42 02H 02H 143 HOT 5803P 0.28 92 P 6 SAI 04H

+0.81 04H 04H 143 HOT 5803P 0.16 79 P 6 SAI 05H

+0.91 05H 05H 143 HOT 5803P 46 128 0.14 103 P 6 SAI 01H

+0.08 01H 01H 143 HOT 5803P 0.47 90 P 6 SAI 02H

+0.87 02H 02H 143 HOT 5803P 60 128 0.19 110 P 6 SAI 01H

+0.35 01H 01H 143 HOT 5803P 62 128 0.18 86 P 6 SAI 01H

-0.44 01H 01H 143 HOT 5803P 74 128 0.16 89 P 6 SAI 01H

-0.92 01H 01H 143 HOT 5803P 78 128 0.32 105 P 6 SAI 01H

-0.75 01H 01H 143 HOT 5803P 0.16 99 P 6 MAI 02H

+0.25 02H 02H 143 HOT 5803P 86 128 0.24 125 P 6 SAI 03H

-0.30 03H 03H 131 HOT 5803P 5

129 0.20 74 P 6 SAI 02H

-0.68 02H 02H 143 HOT 5803P 41 129 0.25 95 P 6 SAI 01H

-0.20 01H 01H 143 HOT 5803P 47 129 0.13 58 P 6 SAI 02H

+0.85 02H 02H 143 HOT 5803P 51 129 0.22 83 P 6 SAI 01H

-0.46 01H 01H 143 HOT 5803P 81 129 0.26 76 P 6 MAI 02H

-0.29 02H 02H 131 HOT 5803P 0.26 66 P 6 SAI 03H

+0.83 03H 03H 131 HOT 5803P 83 129 0.29 107 P 6 SAI 01H

-0.34 01H 01H 131 HOT 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attachment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 21 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 0.20 0.16 0.19 6

130 0.27 8

130 0.24 0.24 16 130 0.61 0.21 56 130 0.25 66 130 0.67 13 131 0.33 0.29 23 131 0.20 31 131 0.45 91 131 0.23 12 132 0.42 0.16 14 132 0.20 66 132 0.28 88 132 0.22 11 133 0.24 13 133 0.18 0.10 0.51 67 133 0.30 79 133 0.23 0.17 85 133 0.31 8

134 0.28 10 134 0.34 40 134 0.28 0.17 86 134 0.23 7

135 0.14 15 135 0.19 49 135 0.45 79 135 0.40 46 136 0.25 0.26 66 136 0.24 78 136 0.25 86 136 0.20 0.35 7

137 0.19 23 137 0.22 6

138 0.18 0.27 10 138 0.15 0.17 18 138 0.20 0.37 0.21 0.24 94 138 0.18 DEG CHN IND %TW LOCATION 112 55 90 79 92 87 94 58 90 98 118 111 86 97 98 96 60 63 101 117 171 58 57 88 95 100 65 94 82 102 92 90 67 87 102 100 113 87 80 106 108 88 97 99 74 80 88 49 44 79 103 67 75 102 P 61SA P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 MAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI 01H

+0.42 02H

-0.79 02H

+0.92 01H

-0.17 01H

-0.90 02H

+0.92 01H

-0.35 01H

+0.45 01H

-0.87 01H

-0.71 01H

-0.32 02H

+0.51 01H

+0.40 01H

+0.49 01H

+0.74 01H

+0.12 01H

-0.40 01H

+0.93 01H

-0.78 01H

+0.86 03H

-0.38 07H

+0.36 07H

-0.83 05H

+0.78 01H

+0.64 01H

-0.43 01H

+0.49 02H

-0.44 01H

-0.64 01H

+0.66 01H

-0.46 01H

+0.21 03H

+0.82 02H

-0.38 03H

+0.79 01H

-0.70 01H

+0.46 02H

-0.86 01H

-0.81 01H

-0.32 01H

-0.76 02H

-0.13 02H

+0.28 02H

-0.86 02H

+0.79 01H

+0.48 04H

+0.84 02H

-0.16 03H

+0.90 01H

+0.68 03H

+0.76 05H

+0.79 07H

-0.17 01H

+0.50 EXT EXT CAL #

01H 01H 131 02H 02H 131 02H 02H 131 01H 01H 128 01H 01H 128 02H 02H 128 01H 01H 152 01H 01H 152 01H 01H 131 01H 01H 131 01H 01H 152 02H 02H 152 01H 01H 128 01H 01H 152 01H 01H 131 01H 01H 128 01H 01H 128 01H 01H 140 01H 01H 131 01H 01H 131 03H 03H 128 DCB 07H 159 DCB 07H 159 05H 05H 128 01H 01H 131 01H 01H 131 01H 01H 131 02H 02H 131 01H 01H 128 01H 01H 128 01H 01H 131 01H 01H 131 03H 03H 131 02H 02H 128 03H 03H 152 01H 01H 131 01H 01H 131 02H 02H 152 01H 01H 170 01H 01H 131 01H 01H 131 02H 02H 131 02H 02H 131 02H 02H 128 02H 02H 130 01H 01H 128 04H 04H 128 02H 02H 128 03H 03H 128 01H 01H 152 03H 03H 152 05H 05H 152 07H 07H 152 01H 01H 133 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22J2005 14:30 CSI-NDE-05-020 Page 22 of 23 Customer Name: St. Lucie Unit 2 Component: S/G A Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 4

140 0.21 24 140 0.37 84 140 0.26 5

141 0.35 6

142 0.13 10 142 0.17 26 142 0.28 58 142 0.20 70 142 0.19 78 142 0.16 0.22 92 142 0.39 7

143 0.34 0.36 19 143 0.38 0.22 23 143 0.30 27 143 0.26 0.14 4

144 0.29 10 144 0.11 0.19 0.15 24 144 0.28 0.36 36 144 0.43 5

145 0.08 13 145 0.14 15 145 0.29 18 146 0.41 34 146 0.25 54 146 0.29 9

147 0.24 13 147 0.26 17 147 0.76 6

148 0.20 16 148 0.32 7

149 0.22 0.25 9

149 0.38 11 149 0.15 0.38 0.20 2

150 0.31 6

150 0.18 8

150 0.25 0.28 10 150 0.17 14 150 0.80 5

151 0.19 15 151 0.22 6

152 0.20 8

152 0.20 0.29 DEG CHN IND 89 96 122 109 61 77 93 97 106 109 109 99 77 96 92 82 74 79 65 79 72 84 98 98 107 102 53 67 82 94 69 90 47 85 101 54 88 75 84 87 254 101 71 106 82 83 67 81 103 65 102 82 82 89 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 SA=

SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI MAI SAI SAI SAI SAI

%TW LOCATION 03H

+0.65 02H

-0.74 01H

+0.74 02H

-0.43 03H

+0.31 03H

+0.49 03H

+0.75 01H

+0.32 01H

+0.92 01H

+0.83 01H

+0.34 01H

-0.25 02H

+0.50 03H

+0.57 01H

+0.89 01H

-0.19 02H

-0.78 02H

+0.83 02H

-0.47 03H

+0.53 02H

-0.56 02H

+0.84 03H

+0.68 01H

+0.81 04H

+0.61 02H

-0.53 02H

-0.90 07H

-0.53 02H

+0.86 04H

+0.64 03H

+0.92 01H

-0.61 02H

+0.49 04H

+0.92 02H

+0.57 02H

+0.52 05H

+0.75 02H

+0.85 04H

+0.82 01H

+0.60 02H

-0.71 03H

-0.71 02H

+0.49 03H

+0.83 03H

+0.82 01H

-0.58 07H

-0.48 05H

+0.77 03H

+0.12 04H

+0.89 01H

+0.80 02H

+0.93 01H

+0.79 02H

-0.56 EXT EXT CAL # LEG 03H 02H 01H 02H 03H 03H 03H 01H 01H 01H 01H 01H 02H 03H 01H 01H 02H 02H 02H 03H 02H 02H 03H 01H 04H 02H 02H 07C 02H 04H 03H 01H 02H 04H 02H 02H 05H 02H 04H 01H 02H 03H 02H 03H 03H 01H 07H 05H 03H 04H 01H 02H 01H 02H 03H 02H 01H 02H 03H 03H 03H 01H 01H 01H 01H 01H 02H 03H 01H 01H 02H 02H 02H 03H 02H 02H 03H 01H 04H 02H 02H 07H 02H 04H 03H 01H 02H 04H 02H 02H 05H 02H 04H 01H 02H 03H 02H 03H 03H 01H 07H 05H 03H 04H 01H 02H 01H 02H 128 130 131 128 128 181 130 131 131 131 131 133 128 128 128 128 128 170 170 128 181 181 181 128 128 130 128 157 128 128 130 131 128 128 128 128 128 128 128 128 128 128 128 130 130 130 130 130 128 128 130 130 130 130 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 23 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL #

0.20 5

153 0.13 7

153 0.53 9

153 0.47 0.21 11 153 0.64 8

154 0.32 0.28 10 154 0.17 0.24 16 154 0.22 8

156 0.19 10 156 0.22 19 157 0.28 10 158 0.19 7

159 0.23 17 159 0.47 8

160 0.15 23 161 0.28 7

165 0.17 82 83 99 106 102 106 85 115 48 66 89 80 74 72 81 109 103 79 105 78 P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI 03H 01H 02H 04H 04H 02H 03H 04H 03H 04H 04H 02H 02H 02H 02H 03H 02H 03H 02H 03H

+0.40

+0.92

+0.49

-0.01

-0.89

+0.79

-0.20

+0.88

-0.58

-0.55

+1.01

-0.78

+0.39

+0.82

-0.76

+0.76

+0.28

+0.74

+0.77

-0. 19 03H 01H 02H 04H 04H 02H 03H 04H 03H 04H 04H 02H 02H 02H 02H 03H 02H 03H 02H 03H 03H 01H 02H 04H 04H 02H 03H 04H 03H 04H 04H 02H 02H 02H 02H 03H 02H 03H 02H 03H 130 128 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 131 LEG PROBE HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P HOT 5803P Total Tubes

798 Total Records: 1208

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 1 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS 72 20 0.37 88 20 0.46 87 21 0.50 89 21 0.39 86 22 1.00 1.19 90 24 0.64 61 25 0.44 92 26 0.39 0.58 88 28 0.44 0.42 98 28 0.61 81 29 0.74 0.42 0.75 0.85 96 30 0.29 0.44 97 31 0.45 105 33 0.33 94 34 0.35 96 34 0.64 51 35 0.41 82 40 0.37 0.29 0.28 43 41 0.32 95 41 0.47 82 44 1.04 94 44 0.35 122 44 0.41 3

49 0.37 48 50 0.51 124 50 0.42 0.67 125 51 0.44 78 52 0.45 84 52 0.91 85 53 0.54 49 55 0.34 95 57 0.24 129 57 0.51 90 58 0.28 130 58 0.36 132 58 0.36 0.45 93 59 0.38 95 59 0.35 0.40 127 59 0.32 82 60 0.27 128 60 0.31 130 60 0.40 DEG 130 123 114 61 84 122 134 153 137 122 79 42 116 115 58 99 104 146 16 151 92 145 136 124 142 151 144 129 28 94 160 147 59 114 154 90 23 138 100 51 156 100 74 84 119 151 98 136 108 131 81 146 120 38 CHN P 2 P 2 P 2 P 2 P 2 P 4 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD IWD TWD TWD TWD TWD TWD TWD TWD TND IWD TWD TWD IWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 25 28 20 26 34 35 29 27 22 28 24 23 32 27 23 31 33 21 27 24 20 21 29 25 24 21 21 20 26 31 22 24 25 25 24 30 25 26 29 28 20 20 30 21 24 27 29 27 23 25 24 21 22 25 LOCATION EXT V=2

-0.49 TEC VS2

-0.89 TEH VS2

+0.90 TEH VS2

+0.73 TEH VS2

+0.86 TEH VS3

-0.88 TEH VS3

-0.78 TEH VS4

+0.78 TEC VS4

-0.80 TEH VS4

+0.45 TEH VS4

-0.84 TEH VS4

-0.25 TEH VS4

+0.57 TEH VS4

-0.90 TEH VS3

-0.97 TEH VS3

-0.21 TEH VS3

+0.68 TEH VS2

+0.91 TEH DCT

+0.00 TEH VS2

+0.86 TEH VS2

+0.10 TEH VS2

-0.94 TEH VS2

-0.84 TEH VS3

-0.92 TEC VS3

-0.82 TEH VS4

-0.84 TEH VS4

+0.54 TEH VS3

+0.71 TEH DHT

-0.24 TEH VS2

+0.68 TEH DCT

+0.00 TEH DCT

+0.00 TEH 02C

-0.71 07H VS3

-0.76 TEH VS1

+0.78 TEH VS2

-0.92 TEH DHB

+2.13 TEH VS4

+0.77 TEH VS3

+0.06 TEH 08H

+0.61 TEH VS3

-0.92 TEH VS2

+0.92 TEH DCT

+0.00 TEH VS3

-0.69 TEH DCB

+0.16 TEH DCB

+0.28 TEH DHB

+0.08 TEH VS4

+0.70 TEH VS2

+0.87 TEH VS3

+0.57 TEH VS1

+0.81 TEH VS3

-0.79 TEH DHB

+0.02 TEH DHT

-0.06 TEH EXT TEH TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL #

20 63 13 14 13 13 13 30 13 13 13 13 14 13 13 13 13 14 14 13 13 13 13 35 17 17 17 5

16 15 16 16 67 9

16 16 16 10 15 16 9

20 20 17 17 53 53 18 17 17 18 18 17 17 LEG HOT COLD COLD COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 60OUL 60OUL 600UL 60OUL 580SF 600UL 600UL 600UL 60OUL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 60OUL 600UL 600UL 600UL

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 2 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS 129 61 0.33 78 62 0.61 96 62 0.33 134 62 0.21 0.22 19 63 0.56 133 63 0.46 135 63 0.47 0.35 0.95 0.37 94 64 0.80 128 64 0.53 132 64 0.43 31 67 0.57 79 67 0.31 0.44 133 67 0.35 34 68 0.35 35 69 0.79 0.50 37 69 0.40 0.83 40 70 0.27 42 70 0.83 44 70 0.54 50 70 0.30 84 70 0.28 136 70 0.74 0.62 39 71 0.39 43 71 0.41 45 71 0.55 51 71 0.26 42 72 0.71 1.07 44 72 0.41 50 72 0.49 126 72 0.35 134 72 0.40 43 73 0.47 49 73 0.51 51 73 0.32 53 73 0.33 135 73 0.81 0.32 0.61 1.11 46 74 0.40 48 74 0.33 54 74 0.30 82 74 0.50 45 75 0.37 0.58 DEG CHN 17 P 2 106 P 2 103 P 2 149 P 2 138 P 2 41 P 2 93 P 2 128 P 2 85 P 2 61 P 2 87 P 2 70 P 2 125 P 2 97 P 2 91 P 2 128 P 2 121 P 2 79 P 2 117 P 2 86 P 2 120 P 2 124 P 2 101 P 2 70 P 2 108 P 2 112 P 2 98 P 2 150 P 2 142 P 2 104 P 2 126 P 2 43 P 2 132 P 2 65 P 2 101 P 2 84 P 2 134 P 2 101 P 2 64 P 2 49 P 2 81 P 2 121 P 2 96 P 2 51 P 2 59 P 2 121 P 2 24 P 2 132 P 2 71 P 2 105 P 2 154 P 2 124 P 2 118 P 2 101 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD IWD TWD TWD TD TWD TKD TWD TWD TWD TWD IWD TWD TWD TWD TWD TW@D TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TD TD TWD TWD TWD TWD TWD TWD

%TW 23 28 23 20 21 27 25 30 26 37 27 29 23 24 27 20 24 26 21 34 27 26 35 21 35 28 21 20 31 29 24 25 27 20 31 35 23 27 21 23 25 28 20 22 32 20 28 35 25 20 21 27 23 29 LOCATION DHT

+0.00 VS2

+0.65 VS3

-0.69 VS3

+0.68 DHT

+0.00 VS3

-0.90 VS1

+0.74 09H

+0.73 DHB

+0.00 VS1

-0.90 VS1

+0.86 VS2

+0.76 VS1

+0.69 DHT

+0.00 DCB

+0.00 VS2

-0.83 VS4

+0.63 VS1

+0.62 DHB

+0.00 DCB

+0.67 DHB

+0.25 DHB

+0.37 DCB

+0.47 DHB

+0.43 DCB

+0.28 DCB

+0.00 DCB

+0.00 07H

+0.89 VS1

-0.84 VS3

-0.74 DCB

+0.35 DCB

+0.00 DCB

+0.47 DCT

+0.00 DCT

+0.00 DHB

+0.00 DHB

+0.35 DCB

+0.00 08H

+0.90 VS1

+0.82 DHB

+0.37 DCB

+0.00 DCB

+0.21 DCB

+0.00 VS1

+0.80 VS2

+0.66 VS3

+0.70 VS4

+0.78 DHB

+0.00 DCT

-0.25 DCT

+0.00 VS2

-0.76 DCT

+0.00 DHT

+0.00 EXT TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEN TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEN TEH TEC TEC TEC TEC TEN TEH TEH TEH TEC TEC TEC TEH TEC TEC EXT CAL # LEG TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEH TEC TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH TEC TEC TEN TEH TEH TEH TEC TEC TEC TEC TEH TEH TEH TEC TEH TEH 17 11 17 53 53 11 52 53 53 53 53 19 19 52 11 11 11 53 12 64 64 64 64 64 64 4

4 21 52 52 64 4

3 4

4 4

3 4

22 52 3

4 3

4 52 52 52 52 4

3 4

21 3

3 COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT HOT COLD COLD COLD COLD NOT HOT HOT HOT HOT HOT HOT COLD COLD HOT NOT HOT HOT COLD COLD COLD COLD HOT HOT HOT COLD HOT HOT PROBE 60.UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attacm^ent 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 3 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS 57 75 0.44 93 75 0.48 133 75 0.32 46 76 0.48 0.72 0.83 48 76 0.34 0.35 58 76 0.37 136 76 0.31 47 77 0.52 0.55 51 77 1.25 53 77 1.34 0.91 0.37 57 77 0.43 73 77 0.30 93 77 0.31 133 77 0.20 48 78 0.54 56 78 1.05 72 78 0.52 96 78 0.79 49 79 0.76 1.12 0.77 0.86 51 79 0.95 0.44 53 79 0.35 61 79 0.91 54 80 0.36 0.43 0.44 0.37 62 80 0.94 53 81 0.77 0.31 0.53 59 81 0.38 50 82 0.57 56 82 0.40 60 82 0.65 51 83 0.46 0.56 85 83 0.34 135 83 0.21 52 84 0.54 56 84 0.51 61 85 0.37 77 85 0.27 54 86 0.33 0.60 DEG 89 81 123 116 71 94 86 87 104 134 11 97 97 19 93 115 123 82 86 138 29 90 128 86 103 81 56 82 104 152 117 102 101 150 130 112 69 75 159 50 110 79 46 119 112 108 89 137 107 77 95 33 121 83 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWID TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 25 27 25 27 32 33 22 21 24 20 27 28 37 38 34 21 25 21 20 20 28 35 28 33 32 36 32 33 34 26 21 34 22 24 24 22 34 32 20 27 23 28 24 30 25 28 22 20 27 27 24 20 22 29 LOCATION VS3

-0.60 VS2

-0.39 VS1

+0.66 DCT

+0.00 DHT

+0.00 DHB

+0.00 DCB

+0.00 DHB

+0.19 DCB

+0.00 DCT

+0.00 DHT

+0.00 DHB

+0.00 DCT

+0.00 DHT

+0.00 DHB

+0.00 DCT

+0.00 DCT

+0.00 VS2

-0.86 DCB

+0.46 VS5

+0.77 DHB

+0.00 DCB

+0.00 VS4

+0.85 VS3

-0.83 DCT

+0.00 VS3

+0.97 VS3

-0.10 DHT

+0.00 DCT

+0.00 DHT

+0.00 DCT

+0.00 DCB

+0.00 DCB

+0.00 DCT

+0.00 DHT

+0.00 DHB

+0.00 DCB

+0.00 DCT

+0.00 DHT

+0.00 DHB

+0.00 DCB

+0.00 DCB

+0.00 DCT

+0.00 DHB

+0.00 DCB

+0.00 DHB

+0.00 VS2

-1.38 VS1

-0.77 DCT

+0.00 DCB

+0.00 DCB

+0.00 VS4

+0.82 DCT

+0.00 VS3

-0.69 EXT TEC TEH TEH TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC EXT TEH TEC TEC TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEH CAL # LEG 3

HOT 21 COLI 53 COLI 4

HOT 4

HOT 4

HOT 3

HOT 3

HOT 4

HOT 52 COLI 3

HOT 3

HOT 4

HOT 3

HOT 3

HOT 3

HOT 3

HOT 4

HOT 54 COLD 53 COLD 3

HOT 4

HOT 4

HOT 54 COLE 5

HOT 5

HOT 5

HOT 5

HOT 6

HOT 6

HOT 5

HOT 6

HOT 5

HOT 5

HOT 5

HOT 5

HOT 5

HOT 5

HOT 5

HOT 5

HOT 5

HOT 5

HOT 6

HOT 6

HOT 5

HOT 5

HOT 25 COLD 53 COLD 5

HOT 6

HOT 6

HOT 6

HOT 6

HOT 6

HOT

)= =

PROBE 60 OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG A Page 4 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 0.31 56 86 1.11 58 86 0.93 60 86 0.33 62 86 0.34 92 86 0.56 1.19 0.30 49 87 1.36 0.49 51 87 0.85 0.59 55 87 0.49 0.49 0.51 57 87 0.68 59 87 0.47 93 87 0.40 0.29 97 87 0.38 0.31 50 88 0.97 0.89 52 88 0.54 0.59 56 88 0.48 94 88 0.28 0.35 53 89 0.56 95 89 0.41 46 90 0.30 0.58 0.34 48 90 0.33 0.35 50 90 0.29 82 90 0.32 45 91 0.75 0.36 0.66 47 91 0.53 51 91 0.40 139 91 0.26 0.75 1.25 52 92 0.72 0.65 56 92 0.62 58 92 0.38 132 92 0.36 43 93 0.32 0.61 45 93 0.38 97 93 0.37 79 110 125 84 152 135 130 149 107 82 55 136 55 125 80 119 103 47 134 82 124 87 99 99 139 138 106 117 131 118 143 118 85 139 122 96 75 86 60 173 57 78 133 95 17 20 157 8

102 127 93 131 85 137 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD)

TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 21 36 34 21 22 28 36 20 37 27 33 28 26 26 27 31 25 24 20 23 21 34 34 27 28 26 20 23 28 24 21 29 22 21 22 21 21 31 22 30 28 24 23 35 39 31 30 30 23 22 20 29 24 26 DHB

+0.00 DCB

+0.00 DCB

+0.00 DHB

+0.00 DCB

+0.00 VS2

+0.88 VS3

-0.84 VS4

-0.86 DCT

+0.00 DHB

+0.00 DCT

+0.00 DHB

+0.00 DCT

+0.00 VS3

-0.85 DHB

+0.00 DCB

+0.00 DHB

+0.00 VS2

-0.98 VS4

+1.00 VS2

-0.66 VS3

+0.78 DCB

+0.00 DHT

+0.00 DCB

+0.00 DCT

+0.00 DCT

+0.00 VS2

-0.80 VS4

+0.74 DHB

+0.00 VS4

-0.60 DCB

+0.00 DCT

+0.00 DHT

+0.00 DCT

+0.00 DCB

+0.00 DCB

+0.00 VS3

-0.64 DHB

+0.04 DCT

+0.00 DHT

+0.00 DHB

+0.00 DHB

+0.00 VS5

+0.72 DHT

+0.00 DCT

+0.00 DCT

+0.00 VS3

+0.99 DHT

+0.00 DCB

+0.00 VS1

+0.98 DHB

+0.00 DCB

+0.00 DCB

+0.00 VS3

+0.67 TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEH TEC TEH TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEH TEN TEH TEC TEC TEC TEC TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEC TEN TEC TEH TEC TEH TEH TEH TEH TEC TEH TEC TEH TEH TEH TEC TEC TEC TEN TEN TEH TEH TEC TEH TEH TEH TEC 6

5 6

5 6

25 25 25 6

6 5

5 5

5 5

6 5

25 25 25 25 6

6 5

5 5

26 26 5

25 6

6 6

5 5

6 25 5

5 5

6 6

56 56 56 6

6 6

5 55 5

5 6

28 HOT HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD HOT HOT HOT HOT HOT COLD COLD NOT COLD HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT COLD HOT HOT HOT COLD PROBE 60 OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 5 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS 44 94 0.50 43 95 0.28 49 95 0.39 0.49 38 96 1.00 0.37 0.65 42 96 0.84 48 96 0.44 0.37 54 96 0.42 94 96 0.73 0.47 41 97 0.27 43 97 0.39 45 97 0.39 47 97 0.40 0.59 135 97 0.48 0.60 0.41 42 98 0.31 50 98 0.31 134 98 0.45 138 98 0.96 37 99 0.35 39 99 0.19 45 99 0.39 137 99 0.29 46 100 0.60 54 100 0.46 137 101 0.51 0.29 40 102 0.22 48 102 0.20 134 102 0.54 91 103 0.43 129 103 0.32 95 105 0.46 126 106 0.27 96 108 0.46 0.65 0.34 132 108 0.34 133 109 0.21 46 112 0.31 82 112 0.28 51 113 0.32 53 113 0.23 123 113 0.29 0.26 0.31 84 114 0.34 47 115 0.30 DEG 114 92 50 125 99 122 84 94 130 132 97 82 153 106 144 90 112 129 48 63 107 91 82 109 121 114 100 71 101 41 67 45 156 163 72 140 130 47 90 97 122 114 101 34 145 59 140 111 132 50 138 147 77 118 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 27 20 23 26 35 24 30 33 25 22 25 31 26 20 23 24 23 28 25 28 23 22 20 30 37 23 20 25 24 28 24 31 25 22 22 32 25 21 26 20 28 33 23 21 21 24 24 24 20 24 23 25 21 23 LOCATION DHB

+0.00 VS3

+1.04 DCT

-0.06 VS3

-0.60 DCB

+0.00 DCT

+0.00 DHT

+0.00 DHT

+0.00 VS3

-0.99 VS3

+0.77 VS3

-0.70 VS2

-0.90 VS4

+0.68 DHB

+0.00 DCB

+0.00 DCT

+0.00 DCB

+0.00 VS3

+1.07 VS1

-0.82 VS3

+0.94 VS5

+0.04 DCB

+0.00 VS3

-0.78 VS3

-0.54 DHT

+0.06 DCB

+0.00 DCB

+0.00 VS3

+0.85 VS5

-0.82 VS3

+0.71 VS3

+0.77 09H

+1.00 DHT

+0.00 VS3

-0.93 DCB

+0.12 DCT

+0.00 VS4

-0.99 VS5

-0.96 VS3

+0.76 VS1

-0.86 VS2

-0.72 VS3

-0.68 VS4

+0.68 DCB

+0.00 DHT

+0.00 VS3

+0.67 VS4

+0.62 VS3

+0.87 VS3

+0.99 VS1

-0.74 VS3

+0.78 VS4

+1.02 VS4

-0.88 VS3

+0.97 EXT TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH EXT TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL # LEG 6

HOT 6

HOT 5

HOT 5

HOT 6

HOT 6

HOT 6

HOT 6

HOT 5

HOT 5

HOT 6

HOT 27 COLE 27 COLE 6

HOT 5

HOT 6

HOT 5

HOT 5

HOT 55 COLE 55 COLE 55 COLE 62 COLE 5

HOT 56 COLE 56 COLE 62 COLE 62 COLE 62 COLE 56 COLE 43 COLD 43 COLD 56 COLD 56 COLD 44 COLD 44 COLD 56 COLD 35 COLD 35 COLD 35 COLD 35 COLD 36 COLD 36 COLD 36 COLD 55 COLD 56 COLD 42 COLD 34 COLD 41 COLD 41 COLD 34 COLD 34 COLD 34 COLD 33 COLD 41 COLD I

I I

I I

I I

I I

I I

I I

I I

I I

I I

PROBE 60=OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 6 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 0.41 92 116 0.22 94 116 0.34 127 117 0.38 86 118 0.24 37 119 0.32 51 119 0.26 84 120 0.38 94 120 0.57 0.27 0.30 102 120 0.26 126 120 0.50 97 121 0.41 125 121 0.39 38 124 0.24 42 124 0.26 38 126 0.20 44 126 0.24 94 126 0.24 53 127 0.74 57 127 0.33 97 127 0.67 54 128 0.32 96 128 0.23 53 129 0.20 91 131 0.20 93 131 0.20 0.72 92 132 0.26 57 133 0.56 93 133 0.27 97 133 0.48 0.26 96 134 0.24 0.31 96 138 0.49 97 139 0.50 85 141 0.33 87 143 0.40 0.63 56 152 0.75 44 156 0.30 51 157 0.48 0.67 2

166 0.34 14 166 0.39 154 131 37 66 142 88 34 128 112 147 99 98 62 85 40 115 124 144 160 125 81 54 72 148 101 150 164 86 48 49 139 153 80 e8 142 74 110 51 106 32 52 127 91 103 91 83 55 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2

=WD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD IWD TWD TWD TWD TqD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 26 21 21 23 20 21 20 23 32 22 24 22 26 28 27 23 24 21 21 20 30 20 30 20 20 21 21 21 35 24 29 25 31 24 23 26 30 26 21 24 29 26 20 26 30 23 24 VS3

-0.79 TEH VS2

-0.68 TEH VS4

-0.88 TEH VS1

+0.74 TEH VS3

-0.74 TEH VS3

+0.97 TEH VS3

+0.83 TEH VS4

-0.88 TEH VS2

+0.62 TEH VS3

-0.88 TEH VS4

-0.90 TEH VS3

-0.77 TEH 08H

-0.95 TEH 08C

+0.88 TEH DCT

+0.08 TEH VS3

+0.73 TEH VS3

-0.67 TEH VS3

+0.75 TEH VS3

-0.73 TEH VS2

-0.90 TEH VS3

-0.77 TEH VS3

-0.72 TEH VS3

+0.92 TEH VS3

-0.94 TEH VS2

-0.94 TEH VS3

-0.77 TEH VS3

+1.26 TEH VS2

-0.80 TEH VS2

+0.72 TEH VS2

+0.70 TEH VS3

+0.78 TEC VS2

+0.80 TEH VS2

-0.68 TEH VS4

-0.60 TEH VS2

+0.92 TEH VS3

-0.86 TEH VS3

-0.60 TEH VS2

-0.92 TEH VS3

+0.64 TEH VS2

-0.98 TEH VS3

+0.38 TEH VS3

-0.65 TEC VS3

-0.83 TEC VS3

+0.84 TEC VS3

-0.55 TEC 01C

-0.84 07C 01C

-1.04 TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEH TEH TEH TEC TEH 41 COLD 34 COLD 33 COLD 31 COLD 32 COLD 39 COLD 40 COLD 31 COLD 32 COLD 32 COLD 32 COLD 32 COLD 31 COLD 32 COLD 32 COLD 37 COLD 37 COLD 37 COLD 38 COLD 32 COLD 47 COLD 47 COLD 31 COLD 47 COLD 32 COLD 37 COLD 30 COLD 30 COLD 30 COLD 30 COLD 25 HOT 30 COLD 30 COLD 30 COLD 30 COLD 30 COLD 28 COLD 27 COLD 27 COLD 27 COLD 27 COLD 44 HOT 48 HOT 48 HOT 48 HOT 59 COLD 47 HOT PROBE 60=OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL Total Tubes

233 Total Records: 317

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 1 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 16 4

0.08 27 5

0.11 35 5

0.17 55 9

0.18 41 15 0.10 74 16 0.09 86 20 0.18 87 21 0.32 86 22 0.43 0.32 72 24 0.19 90 24 0.29 92 26 0.32 0.27 98 26 0.17 37 27 0.17 91 27 0.16 0.18 99 27 0.28 101 27 0.24 88 28 0.31 98 28 0.13 81 29 0.08 96 30 0.17 98 30 0.29 0.21 47 31 0.08 95 31 0.08 24 32 0.17 92 32 0.24 108 32 0.09 91 33 0.12 5

35 0.09 93 35 0.25 111 35 0.19 88 36 0.17 103 37 0.23 85 39 0.25 103 39 0.19 40 40 0.19 9

41 0.12 63 41 0.26 119 41 0.17 44 42 0.18 0.17 72 42 0.27 75 43 0.21 0.23 117 43 0.17 64 44 0.13 82 44 0.36 94 44 0.26 0.23 102 44 0.20 DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 14 148 140 20 125 121 123 149 100 116 118 150 114 92 13 141 151 24 149 78 101 143 143 165 44 130 22 22 122 162 148 168 9

153 40 143 97 126 171 147 169 97 44 29 46 125 122 87 159 117 126 140 64 69 P 2 TWD 9 P 2 TWD 12 P 2 TWD 17 P 2 TWD 16 P 2 TWD 10 P 2 TWD 11 P 2 TWD 16 P 2 TWD 14 P 2 TWD 18 P 2 TWD 14 P 2 TWD 17 P 2 TWD 18 P 2 TWD 14 P 2 TWD 17 P 2 TWD 15 P 2 TWD 16 P 2 TWD 14 P 2 TWD 15 P 2 TWD 18 P 2 TWD 19 P 2 TWD 19 P 2 TWD 12 P 2 TWD 6 P 2 TWD 15 P 2 TWD 18 P 2 TWD 15 P 2 TWD 10 P 2 TWD 9 P 2 TWD 17 P 2 TWD 19 P 2 TWD 9 P 2 TWD 12 P 2 TWD 9 P 2 TWD 16 P 2 TWD 16 P 2 TWD 15 P 2 TWD 18 P 2 TWD 16 P 2 TWD 16 P 2 TWD 14 P 2 TWD 11 P 2 TWD 17 P 2 TWD 13 P 2 TWD 13 P 2 TWD 13 P 2 TWD 18 P 2 TWD 15 P 2 TWD 16 P 2 TWD 13 P 2 TWD 11 P 2 TWD 15 P 2 TWD 18 P 2 TWD 17 P 2 TWD 15 05H 01H 01H 01H VS3 VS2 VS2 VS2 VS3 VS4 VS4 VS2 VS3 VS2 08H VS3 VS2 VS4 VS1 02H VS3 VS2 VS4 VS3 VS2 VS3 DHT VS2 VS3 VS2 VS2 VS4 04H 05H 07H VS4 DCB VS2 DCB VS3 04H VS2 VS1 VS3 VS3 VS3 VS2 VS4 VS4 VS3 VS3 VS2 VS2 DCB

-1.02

+0.81

-1.00

-0.83

+0.83

+0.27

-0.84

-0.92

+0.68

+0.86

-0.52

-0.92

-0.84

+0.84

-0.94

-0.97

-0.71

-0.91

-0.55

+0.00

-0.94

+0.83

+0.86

+0.79

+0.51

+0.94

+0.00

+0.87

+0.65

-0.79

+0.82

+0.93

+0.90

-1.02

-0.93

+0.79

+0.00

-0.94

+0.00

+0.69

+0.87

+0.70

-0.63

+0.14

+0.64

+0.73

+0.82

-1.04

+0.92

+0.89

-0.88

-0.95

+0.54

+0.00 TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEH TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 10 9

9 10 10 9

63 13 13 13 30 13 13 13 14 30 14 14 13 14 13 14 13 14 13 13 36 14 36 14 14 14 68 13 14 14 14 13 14 5

68 5

16 5

5 5

5 5

16 5

15 16 16 16 HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD HOT COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 2 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 122 44 0.13 66 46 0.24 124 46 0.21 49 47 0.18 123 47 0.18 125 47 0.30 41 49 0.23 75 49 0.16 0.30 121 49 0.25 123 49 0.19 125 49 0.16 48 50 0.23 122 50 0.23 124 50 0.25 126 50 0.36 0.46 39 51 0.24 61 51 0.12 77 51 0.15 127 51 0.15 0.13 46 52 0.16 78 52 0.14 84 52 0.20 0.45 128 52 0.43 126 54 0.20 0.20 128 54 0.37 51 55 0.06 117 55 0.14 123 55 0.27 129 55 0.16 78 56 0.20 0.20 83 57 0.16 87 57 0.17 89 57 0.20 93 57 0.21 0.12 95 57 0.22 123 57 0.22 127 57 0.22 24 58 0.10 90 58 0.15 96 58 0.20 0.12 0.18 126 58 0.11 95 59 0.08 125 59 0.11 0.17 127 59 0.23 DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 12 108 160 156 118 80 125 102 118 170 161 72 28 33 54 134 117 149 92 152 36 130 152 159 154 135 22 99 142 105 120 28 134 127 99 159 143 72 18 12 166 95 151 49 161 140 64 101 97 139 149 18 13 66 P 2 TWD 11 P 2 TWD 19 P 2 TWD 9 P 2 TWD 15 P 2 TWD 8 P 2 TWD 13 P 2 TWD 18 P 2 TWD 13 P 2 TWD 19 P 2 TWD 18 P 2 TWD 9 P 2 TWD 7 P 2 TWD 16 P 2 TWD 10 P 2 TWD 18 P 2 TWD 15 P 2 TWD 18 P 2 TWD 16 P 2 TWD 11 P 2 TWD 13 P 2 TWD 7 P 2 TWD 6 P 2 TWD 14 P 2 TWD 12 P 2 TWD 9 P 2 TWD 18 P 2 TWD 17 P 2 TWD 18 P 2 TWD 18 P 2 TWD 17 P 2 TWD 6 P 2 TWD 14 P 2 TWD 14 P 2 TWD 15 P 2 TWD 15 P 2 TWD 15 P 2 TWD 14 P 2 TWD 14 P 2 TWD 11 P 2 TWD 11 P 2 TWD 7 P 2 TWD 19 P 2 TWD 12 P 2 TWD 11 P 2 TWD 8 P 2 TWD 13 P 2 TWD 16 P 2 TWD 6 P 2 TWD 13 P 2 TWD 10 P 2 TWD 7 P 2 TWD 10 P 2 TWD 14 P 2 TWD 18 DCB 03H DCT VS3 VS2 DCT VS3 VS2 VS3 DCT VS1 VS1 VS3 DHT DHT 08H VS1 VS3 VS2 VS4 09H 04H VS3 VS4 VS2 VS4 DHT VS1 VS1 DHT 07C VS1 VS1 DCB VS3 VS4 VS2 VS2 VS2 DHT VS4 DHT VS1 VS1 VS3 DHT VS3 VS3 VS4 09H VS3 VS1 DCT VS1

+0.00

+0.97

-0.04

-0.63

+0.56

+0.00

-0.88

-0.72

-0.16

+0.00

+0.74

+0.85

-0.04

-0.24

+0.00

-0.14

+0.85

+0.72

-0.28

+0.75

+0.85

-0.92

-1.00

-0.51

-0.97

+0.49

+0.14

+0.22

+1.29

+0.00

-0.06

+0.74

-0.95

+0.00

+0.77

+0.97

+0.91

+0.85

+0.95

+0.00

-0.83

+0.00

+0.66

+0.76

-0.70

+0.00

-0.70

+0.92

-0.14

+0.97

-0.83

+0.88

+0. 00

-0.27 TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEN TEH TEH TEH TEH TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 16 6

15 6

15 15 10 7

7 16 15 15 9

15 16 15 15 9

10 10 15 15 10 10 15 15 15 20 20 19 10 20 19 20 11 11 17 17 19 19 19 20 19 19 12 17 18 18 18 17 17 17 17 18 COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 60tUL 60OUL 60OUL 60OUL 60OUL 600UL

Framatome ANP Inc.

1/22/2005 14:30 Attacloint 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 3 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 0.19 24 60 0.17 96 60 0.16 128 60 0.11 41 61 0.17 24 62 0.21 36 62 0.17 44 62 0.11 50 62 0.20 78 62 0.17 0.16 134 62 0.15 0.16 0.17 21 63 0.30 39 63 0.24 79 63 0.15 0.18 0.15 129 63 0.20 20 64 0.23 24 64 0.12 94 64 0.31 0.40 0.36 0.34 130 64 0.18 132 64 0.14 27 65 0.30 47 65 0.24 38 66 0.19 52 66 0.15 124 66 0.17 33 67 0.23 37 67 0.10 0.17 57 67 0.10 89 67 0.18 91 67 0.18 93 67 0.20 64 68 0.11 80 68 0.08 88 68 0.19 132 68 0.17 35 69 0.17 137 69 0.19 40 70 0.23 42 70 0.23 50 70 0.25 136 70 0.21 0.14 41 71 0.20 89 71 0.22 95 71 0.31 90 30 9

164 130 153 136 164 69 339 172 113 33 157 87 143 114 26 42 58 58 50 142 154 92 90 99 160 109 155 114 17 165 98 121 152 150 160 64 146 156 10 35 135 23 164 120 22 119 139 165 122 118 39 P 2

==D P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TND P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD 15 13 14 10 13 15 13 9

9 13 12 16 17 18 19 17 12 14 12 18 19 10 15 19 17 17 16 10 19 17 14 12 9

16 8

13 8

10 17 11 9

7 17 13 13 19 19 19 19 15 11 17 16 19 DCT

+0.00 TEH VS3

-0.68 TEH DHB

+3.36 TEH VS5

-0.90 TEH VS3

-0.85 TEH VS3

+0.98 TEH VS3

-0.94 TEH VS3

+0.80 TEH VS3

-0.51 TEH VS3

-0.75 TEH VS4

+0.73 TEH 08H

-0.99 TEH DCT

+0.00 TEH 07H

+0.78 TEH VS3

-0.87 TEH VS3

-0.93 TEH VS2

+0.89 TEH VS3

-0.74 TEH VS4

+0.89 TEH VS1

+0.65 TEH VS3

-0.81 TEH VS3

-0.62 TEH VS2

-0.89 TEH VS3

+0.82 TEH VS4

-0.87 TEH VS4

-0.36 TEH VS1

+0.70 TEH 07H

+0.57 TEH DHB

+0.02 TEH VS3

-0.70 TEH VS3

+0.74 TEH VS3

-0.90 TEH VS1

+0.79 TEH DCB

+0.00 TEH VS3

+0.73 TEH DCB

+0.00 TEH VS3

+0.82 TEH VS4

+0.99 TEH VS2

+0.73 TEH VS3

-0.89 TEH VS3

+0.83 TEH VS4

+0.89 TEH VS2

-0.87 TEH VS2

-1.00 TEH DHT

-0.18 TEH 07H

+0.65 TEH DCT

-0.24 TEH DCT

-0.14 TEH VS3

-0.71 TEC VS2

+0.92 TEH VS5

-0.90 TEH DCB

+0.57 TEH VS2

+0.98 TEH VS2

+0.79 TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 18 11 17 17 11 12 12 12 11 11 11 53 53 53 12 11 11 11 11 20 63 12 19 19 19 19 20 52 11 12 11 11 19 12 12 12 12 19 20 19 11 11 20 52 64 53 64 64 4

52 52 64 21 22 COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD PROBE 60=OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 600UL 60OUL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 600UL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 4 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 135 71 0.27 42 72 0.20 0.16 46 72 0.20 48 72 0.21 0.22 52 72 0.15 54 72 0.19 64 72 0.19 82 72 0.23 94 72 0.11 0.12 126 72 0.18 43 73 0.20 0.31 49 73 0.18 55 73 0.16 0.20 75 73 0.16 83 73 0.18 133 73 0.14 135 73 0.15 0.20 52 74 0.22 54 74 0.20 56 74 0.19 62 74 0.24 126 74 0.13 45 75 0.18 0.24 49 75 0.16 54 76 0.19 94 76 0.23 112 76 0.13 134 76 0.11 73 77 0.25 79 77 0.12 48 78 0.15 52 78 0.25 56 78 0.15 60 78 0.10 0.15 116 78 0.17 63 79 0.16 125 79 0.22 131 79 0.15 61 81 0.19 95 81 0.13 50 82 0.16 0.21 0.21 60 82 0.16 51 83 0.19 61 83 0.12 DEG 47 115 104 85 28 137 147 160 140 161 171 168 31 43 93 76 156 109 156 163 149 19 62 66 118 163 62 36 137 104 162 135 25 65 56 150 156 120 108 147 132 142 157 60 108 159 139 78 97 20 101 71 151 14 CHN P=2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 18 16 14 17 16 17 7

16 13 17 8

9 13 15 19 15 12 14 13 15 15 12 15 17 17 15 18 9

14 17 13 16 18 9

9 19 10 12 17 14 9

13 12 13 14 9

15 11 13 16 16 13 15 10 LOCATION VS1

-0.90 VS3

+0.75 VS3

-0.83 DCB

+0.00 DCT

+0.00 VS3

+0.66 DCT

+0.00 VS3

+0.88 VS4

-0.82 VS3

-0.78 VS2

+0.86 VS4

+0.92 09H

+0.10 DHT

+0.00 DCB

+0.26 DCT

+0.00 DCB

+0.35 VS3

-0.12 VS3

+0.83 05H

+1.02 VS1

-0.56 VS5

+0.80 VS1

-0.76 DCT

+0.00 VS3

-0.92 VS3

+0.70 VS4

-0.71 VS2

+0.89 DCB

+0.00 DHB

+0.00 DHB

+0.00 DCB

+0.00 VS3

-0.42 VS2

-0.67 VS5

-1.00 VS2

+0.84 VS2

-0.79 DHT

+0.00 DHB

+0.23 VS3

+0.77 VS4

-0.66 VS3

+0.78 VS1

-0.73 DCB

+0.00 VS1

-0.85 VS4

-0.90 DCB

+0.00 VS2

+0.77 DCT

+0.00 DHT

+0.00 DHB

+0.00 DCB

+0.00 DCT

+0.00 DCB

+0.00 EXT EXT CAL # LEG TEH TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEC TEH TEH TEC TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEH TEH TEH TEH TEC TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEC TEH TEC TEC TEH TEC TEH TEH TEH TEH TEH TEH 52 4

4 4

3 3

3 4

3 21 22 22 22 3

3 4

3 3

3 21 53 52 52 3

4 3

4 22 3

3 3

4 21 22 52 4

3 3

3 4

4 4

23 5

23 54 6

26 5

5 5

6 5

6 COLD HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD HOT HOT HOT HOT COLD HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT COLD HOT COLD COLD HOT COLD HOT HOT HOT HOT HOT HOT PROBE 60 OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 600UL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 5 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 79 83 0.16 85 83 0.21 76 84 0.28 82 84 0.20 75 85 0.29 54 86 0.24 62 86 0.24 92 86 0.24 126 86 0.12 51 87 0.17 55 87 0.26 93 87 0.24 111 87 0.11 50 88 0.14 54 88 0.22 94 88 0.12 49 89 0.27 51 89 0.21 53 89 0.24 57 89 0.14 73 89 0.18 83 89 0.22 0.17 0.23 0.24 95 89 0.21 0.26 50 90 0.13 54 90 0.24 0.23 92 90 0.22 114 90 0.16 57 91 0.29 43 93 0.19 49 93 0.18 55 93 0.23 97 93 0.21 0.19 0.12 44 94 0.10 48 94 0.15 52 94 0.17 82 94 0.15 0.16 86 94 0.13 49 95 0.27 51 95 0.16 53 95 0.14 135 95 0.26 38 96 0.17 42 96 0.19 44 96 0.22 94 96 0.26 41 97 0.26 128 137 142 122 128 159 98 51 152 150 157 170 55 109 51 139 114 45 102 122 88 86 83 115 130 93 22 90 130 76 144 54 107 63 145 132 157 62 91 141 125 104 154 140 35 137 154 123 140 90 155 80 113 108 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD~

13 16 19 16 19 18 18 18 10 13 18 18 10 12 17 10 19 17 17 11 14 17 14 17 18 16 19 11 18 18 17 13 19 14 15 16 18 17 12 9

13 14 12 13 11 18 13 11 17 14 15 17 18 19 VS2

-0.77 TEC VS3

+0.63 TEH VS3

+0.81 TEC VS4

-0.67 TEH VS3

+0.75 TEC VS3

+1.04 TEC VS3

-0.80 TEC VS4

+0.82 TEH 09H

-0.84 TEH DCB

+0.00 TEC DCB

+0.00 TEC VS2

+0.58 TEH VS2

-0.93 TEH DCT

+0.00 TEC DCB

+0.00 TEC VS3

-0.96 TEH DCB

+0.00 TEC DCB

+0.00 TEC DCT

+0.00 TEC 04H

+0.93 TEC VS3

+0.65 TEC VS2

+0.74 TEH VS3

-0.90 TEH VS4

-0.68 TEH VS3

+0.92 TEH VS2

-0.94 TEH VS2

+0.50 TEH 05H

+0.96 TEC DCB

+0.00 TEC VS3

-0.62 TEC VS2

+0.80 TEH VS1

+0.59 TEH DHB

+0.00 TEC VS3

+1.00 TEC VS3

-0.85 TEC DCB

+0.06 TEC VS2

-0.81 TEH VS4

+0.63 TEH VS2

+0.22 TEH DCB

+0.00 TEC VS3

-0.87 TEC VS3

+0.00 TEC VS2

+0.97 TEH VS4

+0.93 TEH VS4

+0.84 TEH VS3

+1.09 TEC DCB

+0.00 TEC DCB

-0.19 TEC VS1

-0.94 TEH DHB

+0.00 TEC VS3

-0.87 TEC DCT

+0.00 TEC VS3

-0.54 TEH DCB

+0.00 TEC TEH TEC TEH TEC TEH TEH TEH TEC TEC TEH TEH TEC TEC TEH TEH TEC TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEH TEH TEH TEC TEC TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEC TEC TEC TEH TEH TEH TEC TEH TEH TEH TEC TEH 5

HOT 25 COLD 5

HOT 25 COLD 5

HOT 6

HOT 6

HOT 25 COLD 26 COLD 5

HOT 5

HOT 25 COLD 25 COLD 6

HOT 6

HOT 26 COLD 5

HOT 6

HOT 5

HOT 5

HOT 5

HOT 25 COLD 25 COLD 25 COLD 25 COLD 25 COLD 25 COLD 6

HOT 6

HOT 6

HOT 25 COLD 26 COLD 5

HOT 5

HOT 6

HOT 5

HOT 28 COLD 28 COLD 28 COLD 6

HOT 6

HOT 6

HOT 55 COLD 55 COLD 27 COLD 5

HOT 6

HOT 5

HOT 55 COLD 6

HOT 6

HOT 5

HOT 27 COLD 6

HOT PROBE 60=OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attac1nent 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 6 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 43 97 0.20 45 97 0.15 0.25 57 97 0.12 87 97 0.13 137 97 0.06 48 98 0.09 64 98 0.19 106 98 0.23 136 98 0.13 43 99 0.22 57 99 0.23 0.11 125 99 0.17 133 99 0.06 135 99 0.17 0.11 38 100 0.18 46 100 0.20 48 100 0.35 50 100 0.24 54 100 0.27 78 100 0.15 134 100 0.17 41 101 0.20 51 101 0.23 87 101 0.17 91 101 0.15 115 101 0.06 92 102 0.24 132 102 0.15 136 102 0.17 91 103 0.13 24 104 0.26 126 104 0.20 134 104 0.19 47 105 0.15 0.13 119 105 0.22 125 105 0.10 32 106 0.09 82 106 0.15 94 106 0.11 53 107 0.26 125 107 0.20 127 107 0.20 42 108 0.13 48 108 0.13 84 108 0.14 96 108 0.22 100 108 0.13 39 109 0.09 101 109 0.24 129 109 0.23 108 121 125 146 15 142 42 62 142 160 45 84 154 170 74 165 121 79 118 51 63 49 29 154 119 121 141 129 18 138 120 156 124 126 147 36 161 12 93 70 168 161 146 110 82 17 157 164 150 157 144 111 33 153 P 2 TWD 15 P 2 TWD 13 P 2 TWD 19 P 2 TWD 10 P 2 TWD 13 P 2 TWD 9 P 2 TWD 8 P 2 TWD 15 P 2 TWD 17 P 2 TWD 10 P 2 TWD 17 P 2 TWD 18 P 2 TWD 10 P 2 TWD 18 P 2 TWD 9 P 2 TWD 13 P 2 TWD 9 P 2 TWD 13 P 2 TWD 14 P 2 TWD 19 P 2 TWD 16 P 2 TWD 18 P 2 TWD 18 P 2 TWD 19 P 2 TWD 14 P 2 TWD 14 P 2 TWD 19 P 2 TWD 17 P 2 TWD 8 P 2 TWD 19 P 2 TWD 12 P 2 TWD 18 P 2 TWD 12 P 2 TWD 15 P 2 TWD 16 P 2 TWD 14 P 2 TWD 19 P 2 TWD 18 P 2 TWD 13 P 2 TWD 10 P 2 TWD 14 P 2 TWD 13 P 2 TWD 10 P 2 TWD 15 P 2 TWD 16 P 2 TWD 17 P 2 TWD 14 P 2 TWD 14 P 2 TWD 12 P 2 TWD 18 P 2 TWD 12 P 2 TWD 11 P 2 TWD 17 P 2 TWD 17 DCT DCB VS3 VS3 VS4 DCB DHB VS4 VS4 VS1 DHB VS3 VS3 09C TSC VS5 DCB VS3 VS3 DCB VS3 DHT VS2 VS4 DCT VS3 VS4 08C 05H VS2 DCT VS1 VS2 VS3 VS2 05H VS3 VS3 03H 08C VS3 VS3 VS2 VS3 VS1 DCT VS3 VS3 VS3 VS2 DCT VS3 VS3 VS1

+0.00

+0.00

+0.85

+0.68

-0.56

+0.40

+0.10

-0.90

-0.85

-0.84

+0.00

+0.56

-0.75

-0.88

+2.15

-0.82

+0.30

+0.87

-0.83

+0.02

-0.81

+0.00

-0.06

-0.76

+0.00

+0.85

-0.58

+0.90

+0.86

+0.91

+0.00

-0.78

-0.95

+0.89

+0.90

+0.86

-0.81

+0.26

+0.92

+0.70

+0.56

+0.76

+0.95

+0.79

+0.94

-0.02

+0.10

-0.83

+0.99

+0.81

+0.00

+0.93

+0.87

-0.88 TEC TEC TEC TEC TEH TEH TEC TEC TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 5

6 6

6 28 56 6

6 27 55 62 6

6 56 56 55 55 43 43 44 43 43 44 56 43 44 37 37 37 36 55 56 35 44 36 55 44 44 36 35 44 36 36 44 35 36 41 42 36 36 36 41 33 33 HOT HOT HOT HOT COLD COLD HOT HOT COLD COLD COLD HOT HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 7 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 133 109 0.13 8

110 0.16 78 110 0.10 132 110 0.15 33 111 0.20 45 111 0.13 87 111 0.27 40 112 0.10 82 112 0.15 0.15 88 112 0.16 0.26 0.18 92 112 0.12 31 113 0.13 123 113 0.09 41 115 0.10 125 115 0.12 54 116 0.08 76 116 0.07 0.10 92 116 0.09 128 116 0.11 41 117 0.10 53 117 0.11 77 117 0.15 93 117 0.13 40 118 0.13 88 118 0.29 53 119 0.14 123 119 0.10 84 120 0.27 37 121 0.12 53 121 0.14 125 121 0.14 37 123 0.17 39 123 0.12 41 123 0.12 53 123 0.21 37 125 0.12 41 125 0.17 54 126 0.13 21 127 0.15 41 127 0.16 79 127 0.14 87 127 0.17 91 127 0.18 95 127 0.16 97 127 0.17 0.24 80 128 0.20 96 128 0.19 41 129 0.16 45 129 0.14 DEG CHN 166 P 2 41 P 2 11 P 2 161 P 2 77 P 2 20 P 2 156 P 2 167 P 2 100 P 2 161 P 2 28 P 2 155 P 2 160 P 2 116 P 2 18 P 2 28 P 2 167 P 2 166 P 2 194 P 2 155 P 2 168 P 2 156 P 2 145 P 2 168 P 2 17 P 2 159 P 2 46 P 2 119 P 2 134 P 2 25 P 2 161 P 2 132 P 2 156 P 2 44 P 2 37 P 2 171 P 2 60 P 2 140 P 2 44 P 2 59 P 2 24 P 2 96 P 2 92 P 2 73 P 2 123 P 2 147 P 2 153 P 2 155 P 2 29 P 2 130 P 2 32 P 2 154 P 2 32 P 2 40 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 1WD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TD TD TWD TWD TWD TWD TWD TWD

%TW 15 13 10 17 18 13 18 11 17 16 13 18 14 10 14 12 11 14 9

9 12 12 14 12 12 14 13 11 19 12 11 19 10 12 14 19 13 14 15 15 19 10 17 18 13 16 17 16 13 17 15 18 18 16 LOCATION 07C

-0.94 06H

+0.69 06H

+0.96 VS5

-0.87 VS3

+0.85 VS3

+0.89 VS3

-0.86 VS3

+0.91 VS2

-0.02 VS2

+0.76 VS4

-0.93 VS3

-0.95 VS2

+0.87 VS3

-1.00 VS3

-0.34 VS5

+1.00 VS3

+0.99 VS1

+0.98 VS3

-0.73 VS3

+0.63 08C

+0.88 08C

+1.15 VS2

+1.04 VS3

+0.81 VS3

+0.95 VS3

+0.98 VS3

+0.62 VS3

+0.87 08H

+0.89 VS3

+0.83 VS4

-0.96 VS2

-0.74 VS3

+0.81 VS3

-0.85 07H

+0.77 VS3

-0.52 VS3

+0.91 VS3

+1.00 VS3

+0.92 VS3

-0.70 VS3

-0.62 VS3

-0.86 VS3

+0.89 VS3

-0.73 VS2

-0.77 VS2

+0.52 VS2

-0.84 VS2

-0.88 VS4

+0.90 VS2

-0.64 VS4

-0.95 VS4

-0.82 VS3

-0.69 VS3

-0.61 EXT EXT TEN TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC CAL # LEG 56 COLD 50 COLD 46 COLD 56 COLD 42 COLD 42 COLD 33 COLD 41 COLD 34 COLD 34 COLD 55 COLD 55 COLD 55 COLD 33 COLD 42 COLD 34 COLD 41 COLD 34 COLD 40 COLD 45 COLD 45 COLD 34 COLD 34 COLD 40 COLD 40 COLD 46 COLD 32 COLD 39 COLD 31 COLD 39 COLD 32 COLD 31 COLD 39 COLD 39 COLD 32 COLD 37 COLD 38 COLD 37 COLD 48 COLD 37 COLD 37 COLD 47 COLD 37 COLD 37 COLD 47 COLD 32 COLD 32 COLD 32 COLD 31 COLD 31 COLD 47 COLD 32 COLD 37 COLD 37 COLD PROBE 60=OUL 600UL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 8 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 89 129 0.23 91 129 0.27 45 133 0.28 91 133 0.31 42 134 0.16 50 134 0.14 6

138 0.14 42 138 0.28 46 138 0.14 96 138 0.19 102 138 0.22 104 138 0.15 53 139 0.22 81 139 0.21 95 139 0.15 101 139 0.10 48 140 0.27 102 140 0.18 97 141 0.22 66 142 0.06 86 142 0.17 0.14 96 142 0.09 81 143 0.19 87 143 0.15 95 143 0.23 94 144 0.12 46 146 0.12 85 147 0.18 53 151 0.22 47 155 0.26 57 155 0.23 49 161 0.24 38 162 0.12 29 163 0.06 30 164 0.16 32 164 0.20 36 164 0.11 15 165 0.21 27 165 0.22 29 165 0.12 0.18 20 166 0.13 DEG 69 131 139 146 47 23 38 107 157 151 153 13 106 158 131 133 135 20 71 170 169 150 166 103 38 78 163 65 120 141 129 143 102 139 156 32 158 7

32 133 149 154 142 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

'ND

'WD

'ND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD T'D TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 18 19 15 13 12 9

16 9

17 16 14 15 16 15 9

18 17 16 5

14 12 10 14 12 17 10 11 17 10 19 17 18 11 7

13 16 10 17 17 11 15 12 LOCATION EXT VS2

+0.91 TEH VS2

-0.78 TEH VS3

+0.78 TEC 08C

+1.34 TEH VS3

-0.92 TEC DCT

+0.00 TEC 07C

-0.57 TEH 05H

+0.92 TEC VS3

-0.63 TEC VS2

+0.84 TEH VS2

-0.96 TEH 08H

+0.79 TEH VS3

-0.55 TEC 06C

+0.83 TEH VS2

-0.90 TEH VS2

-0.95 TEH VS3

+0.80 TEC 09H

-0.95 TEH 07C

-0.26 TEH VS2

+1.12 TEC VS4

-0.88 TEH VS3

+1.06 TEH VS4

-0.88 TEH 08C

+0.86 TEH VS4

+0.66 TEH VS2

-0.92 TEH 01C

+0.95 TEH VS3

+0.61 TEH VS2

+0.92 TEH VS3

-0.85 TEC VS3

-0.73 TEC VS3

+0.80 TEC VS3

-0.79 TEC 01H

+1.07 TEC 01C

-1.00 TEC 01H

-0.92 TEC 01C

+0.92 TEC 01H

+0.94 TEC 01H

-0.78 TEC 01C

-0.93 TEC 01C

-0.99 TEC 01H

-1.03 TEC 01H

+0.93 TEC EXT TEC TEC TEH TEC TEH TEH TEC TEH TEH TEC TEC TEC TEH TEC TEC TEC TEH TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH CAL # LEG 31 COLD 31 COLD 27 HOT 29 COLD 27 HOT 27 HOT 50 COLD 37 HOT 37 HOT 28 COLD 27 COLD 28 COLD 37 HOT 27 COLD 28 COLD 27 COLD 37 HOT 28 COLD 27 COLD 41 HOT 27 COLD 27 COLD 28 COLD 27 COLD 27 COLD 27 COLD 27 COLD 62 COLD 28 COLD 44 HOT 47 HOT 48 HOT 48 HOT 47 HOT 48 HOT 47 HOT 48 HOT 47 HOT 48 HOT 48 HOT 47 HOT 47 HOT 47 HOT PROBE 60=OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL Total Tubes

364 Total Records: 421

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND 4

2 0.22 0.21 12 2

0.15 15 3

0.15 12 4

0.16 7

5 0.30 9

5 0.19 4

8 0.17 0.31 7

9 0.35 9

9 0.19 0.14 0.32 12 10 0.32 1

11 0.38 15 11 0.29 43 11 0.10 4

12 0.14 6

12 0.27 12 12 0.28 3

13 0.58 5

13 0.28 0.50 7

13 0.17 0.24 0.45 0.24 4

14 0.17 0.15 0.13 0.33 6

14 0.30 16 14 0.28 5

15 0.28 0.25 9

15 0.42 0.16 0.19 21 15 0.20 6

16 0.20 5

17 0.15 0.39 15 17 0.69 29 17 0.27 7

19 0.26 0.24 0.16 0.30 9

19 0.57 0.16 0.23 0.22 13 19 0.29 71 19 0.24 84 100 100 96 125 97 128 143 106 105 90 47 82 114 103 93 77 99 106 115 101 58 45 91 54 110 88 91 89 135 103 87 102 104 108 101 67 73 107 113 96 91 106 96 105 104 73 94 96 82 91 99 100 108 P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI

%TW LOCATION 01H

+0.86 03H

+0.79 01H

+0.83 01H

+0.78 01H

+0.84 03H

+0.69 03H

-0.11 03H

-0.14 04H

+0.81 01H

-0.57 01H

+0.35 05H

-0.17 07H

+0.56 03H

+0.64 03H

+0.81 03H

+0.73 01H

+0.47 03H

+0.67 03H

+0.39 02H

-0.77 03H

+0.84 02H

-0.29 05H

+1.33 05H

+0.92 06H

-0.90 03H

+0.72 01H

+0.22 01H

+0.78 03H

+0.81 03H

+0.50 05H

+1.08 01H

-0.13 03H

+0.70 03H

+0.81 03H

-0.34 01H

+0.38 02H

-0.60 05H

+0.91 05H

+0.56 03H

+0.46 01H

+0.27 05H

+0.20 03H

-0.10 05H

-0.12 01H

+0.37 05H

+0.84 05H

-0.23 DCB

+0.20 01H

+0.57 03H

+0.70 05H

+0.29 05H

+0.76 01H

+0.17 02H

+0.87 EXT 01H 03H 01H 01H 01H 03H 03H 03H 04H 01H 01H 05H 07H 03H 03H 03H 01H 03H 03H 02H 03H 02H 05H 05H 06H 03H 01H 01H 03H 03H 05H 01H 03H 03H 03H 01H 02H 05H 05H 03H 01H 05H 03H 05H 01H 05H 05H 07C 01H 03H 05H 05H 01H 02H EXT 01H 03H 01H 01H 01H 03H 03H 03H 04H 01H 01H 05H DHT 03H 03H 03H 01H 03H 03H 02H 03H 02H 05H 05H 06H 03H 01H 01H 03H 03H 05H 01H 03H 03H 03H 01H 02H 05H 05H 03H 01H 05H 03H 05H 01H 05H 05H DCT 01H 03H 05H 05H 01H 02H CAL # LEG 161 HOT 161 HOT 118 HOT 118 HOT 118 HOT 161 HOT 161 HOT 161 HOT 161 HOT 160 HOT 173 HOT 160 HOT 160 HOT 118 HOT 160 HOT 118 HOT 118 HOT 173 HOT 157 HOT 118 HOT 157 HOT 157 HOT 157 HOT 157 HOT 157 HOT 173 HOT 157 HOT 157 HOT 157 HOT 157 HOT 157 HOT 157 HOT 118 HOT 157 HOT 157 HOT 157 HOT 157 HOT 157 HOT 118 HOT 173 HOT 157 HOT 157 HOT 118 HOT 118 HOT 157 HOT 157 HOT 157 HOT 73 COLD 157 HOT 157 HOT 157 HOT 157 HOT 118 HOT 118 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 2 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 75 19 0.35 10 20 0.26 0.32 22 20 0.32 26 20 0.37 28 20 0.35 0.28 30 20 0.31 0.20 34 20 0.41 48 20 0.26 60 20 0.36 12 22 0.38 28 22 0.36 68 22 0.20 5

23 0.21 7

23 0.17 0.12 0.34 9

23 0.31 15 23 0.37 45 23 0.25 4

24 0.34 68 24 0.22 0.15 0.20 3

25 0.38 9

25 0.22 49 25 0.18 4

26 0.30 0.27 10 26 0.21 26 26 0.20 0.48 52 26 0.43 7

27 0.18 37 27 0.30 75 27 0.26 0.23 0.28 4

28 0.24 10 28 0.18 0.26 7

29 0.24 61 29 0.29 6

30 0.24 10 30 0.41 0.45 30 30 0.17 38 30 0.29 17 31 0.28 41 31 0.32 67 31 0.20 8

32 0.29 DEG 102 92 100 62 92 80 89 105 63 94 91 92 107 65 86 90 85 47 94 108 99 79 104 102 118 90 80 93 99 91 94 75 89 105 99 101 97 106 68 100 80 89 99 91 97 109 100 113 94 106 101 119 99 53 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND %TW LOCATION SAI 02H

-0.77 MAI 03H

+0.66 SAI 07H

+0.72 SAI 02H

-0.47 SAI 03H

+0.72 SAI 01H

-0.75 SAI 03H

+0.76 SAI 01H

+0.42 MAI 03H

+0.87 SAI 02H

-0.29 SAI 01H

-0.70 SAI 06H

+0.74 SAI 01H

+0.28 SAI 03H

+0.66 SAI 04H

+0.69 SAI 01H

-0.62 SAI 03H

+0.82 SAI 03H

-0.39 SAI 05H

+0.77 SAI 03H

+0.67 SAI 03H

+0.86 MAI 02H

+0.70 SAI 05H

+0.80 SAI 04H

+0.74 SAI 01H

-0.78 SAI 01H

+0.73 SAI 01H

+0.45 SAI 05H

+0.73 SAI 01H

+0.32 SAI 02H

+0.49 SAI 03H

+0.77 SAI 05H

+0.45 SAI 05H

-0.51 SAI 05H

+0.90 SAI 01H

-0.33 SAI 01H

+0.30 SAI 01H

-0.68 SAI 02H

-0.76 SAI 02H

+0.25 SAI 03H

+0.17 SAI 06H

+0.83 SAI 05H

+0.81 SAI 07H

+0.85 SAI 05H

+0.82 MAI 01H

+0.47 SAI 05C

+0.72 SAI 01H

-0.25 SAI 04H

+0.51 SAI 03H

+0.76 MAI 01H

+0.19 SAI 05H

+0.67 SAI 01H

-0.77 SAI 04H

+0.63 SAI 01H

-0.48 EXT EXT CAL # LEG 02H 03H 07H 02H 03H 01H 03H 01H 03H 02H 01H 06H 01H 03H 04H 01H 03H 03H 05H 03H 03H 02H 05H 04H 01H 01H 01H 05H 01H 02H 03H 05H 05H 05H 01H 01H 01H 02H 02H 03H 06H 05H 07H 05H 01H 05C 01H 04H 03H 01H 05H 01H 04H 01H 02H 03H 07H 02H 03H 01H 03H 01H 03H 02H 01H 06H 01H 03H 04H 01H 03H 03H 05H 03H 03H 02H 05H 04H 01H 01H 01H 05H 01H 02H 03H 05H 05H 05H 01H 01H 01H 02H 02H 03H 06H 05H 07H 05H 01H 05C 01H 04H 03H 01H 05H 01H 04H 01H 118 157 157 118 118 178 118 118 118 118 118 118 118 118 47 173 181 181 161 157 118 47 161 47 77 77 161 161 47 161 161 157 118 118 47 161 47 50 50 50 161 161 161 161 47 73 161 161 47 47 47 47 47 161 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 3 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 10 32 0.26 22 32 0.26 0.21 34 32 0.46 0.22 0.17 0.18 0.17 0.45 0.47 62 32 0.18 0.11 0.24 0.32 64 32 0.23 88 32 0.43 7

33 0.44 21 33 0.15 27 33 0.20 41 33 0.26 0.13 45 33 0.21 59 33 0.85 61 33 0.26 75 33 0.20 0.10 87 33 0.19 26 34 0.30 0.32 0.51 0.14 0.21 0.30 30 34 0.38 0.16 0.20 0.43 68 34 0.21 39 35 0.18 0.25 87 35 0.16 4

36 0.21 0.25 30 36 0.53 0.19 0.18 0.13 0.21 0.24 0.35 56 36 0.46 0.29 60 36 0.31 0.14 DEG 120 77 110 101 85 80 91 75 102 40 132 67 99 93 77 91 106 77 74 104 76 77 100 76 73 60 92 80 106 105 88 88 91 122 83 76 93 88 98 100 93 104 89 104 56 95 31 82 76 102 92 87 98 74 CHN IND P 6=SA P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI

%TW LOCATION EXT 01H

+0.52 01H 05H

+0.14 05H 05H

+0.79 05H 05H

+0.54 05H 07H

+0.55 07H 01H

-0.62 01H 01H

+0.39 01H 02H

+0.73 02H 03H

+0.37 03H 04H

+0.62 04H 03H

-0.60 03H 03H

+0.18 03H 03H

+0.46 03H 04H

+0.69 04H 02H

+0.78 02H 02H

+0.78 02H 01H

-0.23 01H 01H

-0.86 01H 03H

+0.69 03H 01H

+0.08 01H 01H

-0.38 01H 02H

+0.64 02H 02H

+0.45 02H 03H

+0.11 03H 04H

+0.91 04H 04H

-0.66 04H 02H

+0.89 02H 01H

-0.61 01H 01H

+0.06 01H 04H

+0.64 04H 02H

-0.73 02H 02H

+0.45 02H 03H

+0.97 03H 05H

+0.53 05H 05H

-0.25 05H 01H

+0.66 01H 04H

+0.78 04H 05H

+0.66 05H 01H

-0.69 01H 01H

+0.34 01H 02H

-0.23 02H 07H

-0.22 07H 07H

+0.82 07H 06H

-0.50 06H 01H

-0.82 01H 01H

+0.78 01H 02H

-0.70 02H 02H

+0.88 02H 03H

+0.92 03H 04H

-0.10 04H 01H

-0.21 01H 02H

+0.60 02H 01H

-0.65 01H 02H

-0.52 02H EXT 01H 05H 05H 05H 07H 01H 01H 02H 03H 04H 03H 03H 03H 04H 02H 02H 01H 01H 03H 01H 01H 02H 02H 03H 04H 04H 02H 01H 01H 04H 02H 02H 03H 05H 05H 01H 04H 05H 01H 01H 02H DHT DHT 06H 01H 01H 02H 02H 03H 04H 01H 02H 01H 02H CAL #

161 118 118 47 47 77 77 77 77 77 47 47 47 47 47 122 161 118 118 47 47 77 47 47 50 50 122 47 47 47 77 77 77 47 47 77 100 47 47 47 124 161 161 47 77 77 77 77 77 77 47 47 47 47 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 4 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.48 99 P 6 SAI 02H

+0.14 02H 02H 47 HOT 5803P 62 36 0.24 86 P 6 SAI 04H

+0.63 04H 04H 47 HOT 5803P 0.18 79 P 6 SAI 05H

+0.74 05H 05H 47 HOT 5803P 7

37 0.25 88 P6 SAI 01H

+0.78 01H 01H 161 HOT 5803P 0.41 105 P 6 SAI 03H

+0.86 03H 03H 161 HOT 5803P 0.31 89 P 6 MAI 06H

+0.11 06H 06H 161 HOT 5803P 0.29 76 P 6 SAI 07H

-0.78 07H DHT 161 HOT 5803P 0.58 110 P 6 SAI 07H

+0.88 07H DHT 161 HOT 5803P 0.33 111 P 6 SAI 07C

-0.36 07C DCT 73 COLD 5803P 23 37 0.19 73 P 6 SAI 05H

+0.34 05H 05H 47 HOT 5803P 0.24 107 P 6 SAI 05H

+0.70 05H 05H 47 HOT 5803P 0.19 43 P 6 SAI 03H

-0.73 03H 03H 77 HOT 5803P 0.13 75 P 6 SAI 03H

+0.71 03H 03H 77 HOT 5803P 27 37 0.37 78 P 6 SAI 03H

+0.65 03H 03H 47 HOT 5803P 53 37 0.14 98 P 6 SAI 01H

+0.30 01H 01H 47 HOT 5803P 0.13 75 P 6 SAI 01H

-0.15 01H 01H 47 HOT 5803P 61 37 0.13 102 P 6 SAI 01H

-0.68 01H 01H 47 HOT 5803P 71 37 0.19 73 P 6 SAI 02H

+0.85 02H 02H 47 HOT 5803P 75 37 0.22 86 P 6 SAI 02H

+0.87 02H 02H 47 HOT 5803P 83 37 0.13 91 P 6 SAI 05H

+0.81 05H 05H 124 HOT 5803P 4

38 0.30 97 P 6 SAI 05H

+0.87 05H 05H 161 HOT 5803P 56 38 0.25 73 P 6 SAI 02H

+0.72 02H 02H 47 HOT 5803P 0.20 56 P 6 SAI 02H

-0.67 02H 02H 47 HOT 5803P 60 38 0.24 110 P 6 SAI 01H

-0.37 01H 01H 47 HOT 5803P 0.40 85 P 6 SAI 01H

+0.40 01H 01H 47 HOT 5803P 68 38 0.26 111 P6 SAI 01H

-0.67 01H 01H 47 HOT 5803P 0.52 97 P 6 SAI 01H

+0.44 01H 01H 47 HOT 5803P 7

39 0.41 111 P 6 SAI 01H

+0.56 01H 01H 161 HOT 5803P 0.26 71 P 6 SAI 04H

+0.56 04H 04H 161 HOT 5803P 0.37 117 P 6 SAI 06H

+0.87 06H 06H 161 HOT 5803P 9

39 0.30 78 P 6MAI 06H

-0.17 06H 06H 161 HOT 5803P 17 39 0.20 67 P6 SAI 03H

+0.72 03H 03H 47 HOT 5803P 87 39 0.22 114 P 6 SAI 01H

-0.83 01H 01H 161 HOT 5803P 2

40 0.29 88 P6 SAI 06H

-0.46 06H 06H 161 HOT 5803P 20 40 0.14 74 P6 SAI 01H

+0.80 01H 01H 47 HOT 5803P 56 40 0.83 90 P 6 MAI 01H

-0.73 01H 01H 47 HOT 5803P 62 40 0.42 103 P 6 SAI 01H

-0.16 01H 01H 47 HOT 5803P 0.35 117 P 6 SAI 01H

+0.33 O1H 01H 47 HOT 5803P 9

41 0.17 91 P 6 SAI 06H

+0.87 06H 06H 161 HOT 5803P 11 41 0.21 103 P 6 SAI 02H

+0.78 02H 02H 47 HOT 5803P 0.21 79 P 6 SAI 05H

-0.23 05H 05H 47 HOT 5803P 0.10 73 P 6 SAI 05H

+0.66 05H 05H 47 HOT 5803P 33 41 0.33 84 P6 SAI 06H

+0.68 06H 06H 47 HOT 5803P 0.15 59 P 6 SAI 01H

-0.31 01H 01H 77 HOT 5803P 0.09 47 P 6 SAI 01H

+0.65 01H 01H 77 HOT 5803P 81 41 0.23 101 P 6 SAI 01H

+0.44 01H 01H 124 HOT 5803P 14 42 0.24 82 P 6 SAI 02H

+0.33 02H 02H 47 HOT 5803P 0.25 69 P 6 SAI 01H

-0.37 01H 01H 77 HOT 5803P 0.22 63 P 6 SAI 01H

+0.53 01H 01H 77 HOT 5803P 20 42 0.16 162 P 6 SAI 01H

-0.26 01H 01H 47 HOT 5803P 56 42 0.30 103 P 6 SAI 01H

+0.27 01H 01H 50 HOT 5803P 58 42 0.27 66 P 6 SAI 01H

+0.20 01H 01H 50 HOT 5803P 0.19 68 P 6 SAI 01H

-0.92 01H 01H 50 HOT 5803P 66 42 0.34 100 P 6 SAI 01H

-0.30 01H 01H 50 HOT 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 5 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 10 44 0.22 81 P 6 SAX 03H

+0.93 03H 03H 157 HOT 5803P 0.23 97 P 6 MAI 05H

+0.63 05H 05H 157 HOT 5803P 28 44 0.29 85 P 6 SAX 01H

+0.65 01H 01H 47 HOT 5803P 48 44 0.29 254 P 6 SAX 02H

+0.79 02H 02H 50 HOT 5803P 56 44 0.34 90 P 6 SAX 01H

-0.27 01H 01H 50 HOT 5803P 0.37 86 P 6 SAX 02H

+0.90 02H 02H 50 HOT 5803P 90 44 0.17 79 P 6 SAX 05H

+0.85 05H 05H 125 HOT 5803P 7

45 0.19 99 P 6 SAX 04H

+0.39 04H 04H 157 HOT 5803P 0.22 109 P 6 SAX 06H

+0.68 06H 06H 157 HOT 5803P 0.58 89 P 6 SAI 06H

-0.72 06H 06H 157 HOT 5803P 61 45 0.11 138 P 6 SAX 08C

-1.02 08C 08C 73 COLD 5803P 69 45 0.41 100 P 6 MAI 01H

+0.41 01H 01H 50 HOT 5803P 0.28 50 P 6 SAl 08C

-0.55 08C 08C 73 COLD 5803P 10 46 0.31 96 P 6 MAI 05H

+0.43 05H 05H 161 HOT 5803P 54 46 0.64 106 P 6 SAX 01H

+0.85 01H 01H 50 HOT 5803P 96 46 0.10 65 P 6 SAI 03H

-0.71 03H 03H 125 HOT 5803P 102 46 0.20 81 P 6 SAX 04H

+0.88 04H 04H 125 HOT 5803P 7

47 0.28 92 P 6 MAI 06H

+0.77 06H 06H 161 HOT 5803P 0.17 80 P 6 SAX 06H

-0.30 06H 06H 161 HOT 5803P 0.38 116 P 6 MAI 05H

-0.30 05H 05H 161 HOT 5803P 9

47 0.34 84 P 6 SAl 05H

+0.56 05H 05H 161 HOT 5803P 11 47 0.32 101 P 6 SAl 01H

+0.43 01H 01H 47 HOT 5803P 13 47 0.20 65 P 6 SAI DHB

+0.52 07C 07H 149 HOT 5602P 0.14 75 P 6 SAl 07H

+0.23 07C 07H 149 HOT 5602P 0.10 48 P 6 SAl 03H

-0.59 03H 03H 47 HOT 5803P 17 47 0.23 127 P 6 SAl 03H

-0.64 03H 03H 47 HOT 5803P 0.26 106 P 6 SAl 03H

-0.42 03H 03H 47 HOT 5803P 0.22 113 P 6 SAl 03H

+0.50 03H 03H 47 HOT 5803P 0.26 83 P 6 SAl 06H

-0.33 06H 06H 47 HOT 5803P 0.23 110 P 6 SAl 06H

+0.56 06H 06H 47 HOT 5803P 69 47 0.34 95 P 6 MAI 01H

+0.52 01H 01H 50 HOT 5803P 79 47 0.62 102 P 6 SAl 01H

-0.09 01H 01H 50 HOT 5803P 20 48 0.08 110 P 6 SAX 07H

+0.09 07H 07H 47 HOT 5803P 0.31 98 P 6 SAl 07H

+0.42 07H 07H 47 HOT 5803P 0.19 64 P 6 MAI 01H

-0.01 01H 01H 77 HOT 5803P 0.18 105 P 6 SAl 06H

+0.48 06H 06H 77 HOT 5803P 28 48 0.33 96 P 6 SAl 02H

+0.50 02H 02H 161 HOT 5803P 42 48 0.31 119 P 6 SAX 01H

-0.43 01H 01H 161 HOT 5803P 56 48 0.22 101 P 6 MAI 01H

+0.88 01H 01H 161 HOT 5803P 120 48 0.12 86 P 6 SAl 01H

+0.21 01H 01H 125 HOT 5803P 9

49 0.35 83 P 6 SAl 06H

+0.78 06H 06H 161 HOT 5803P 63 49 0.38 90 P 6 SAl 05H

+0.78 05H 05H 160 HOT 5803P 4

50 0.33 95 P 6 SAI 05H

+0.75 05H 05H 161 HOT 5803P 0.39 91 P 6 SAI 06H

-0.84 06H 06H 161 HOT 5803P 10 50 0.19 66 P 6 SAl 01H

+0.19 01H 01H 161 HOT 5803P 0.32 99 P 6 SAl 06H

+0.86 06H 06H 161 HOT 5803P 16 50 0.15 57 P 6 SAl 01H

-0.25 01H 01H 47 HOT 5803P 46 50 0.62 93 P 6 SAl 02H

+0.52 02H 02H 161 HOT 5803P 86 50 0.20 117 P 6 SAl 01H

-0.83 01H 01H 125 HOT 5803P 126 50 0.37 85 P 6 SAX 02H

-0.85 02H 02H 125 HOT 5803P 7

51 0.30 86 P 6 SAl 05H

-0.24 05H 05H 161 HOT 5803P 9

51 0.15 87 P 6 SAl 07H

-0.23 07C 07H 149 HOT 5602P 17 51 0.30 101 P 6 SAX 06H

+0.64 DHT 06H 149 HOT 5602P 0.20 66 P 6 SAl 06H

-0.52 DHT 06H 149 HOT 5602P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 6 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 53 51 0.24 0.18 99 51 0.16 101 51 0.22 10 52 0.23 28 52 0.28 54 52 0.10 60 52 0.48 88 52 0.16 23 53 0.53 49 53 0.23 59 53 0.22 0.19 73 53 0.28 87 53 0.32 0.19 0.27 101 53 0.18 117 53 0.23 4

54 0.59 0.54 58 54 0.33 94 54 0.24 98 54 0.14 118 54 0.24 122 54 0.38 7

55 0.30 0.41 9

55 0.23 17 55 0.32 47 55 0.18 53 55 0.23 0.39 55 55 0.22 59 55 0.27 61 55 0.31 0.23 0.43 0.20 65 55 0.48 69 55 0.30 85 55 0.26 97 55 0.35 101 55 0.19 0.13 107 55 0.38 14 56 0.29 0.20 16 56 0.24 0.33 0.26 18 56 0.29 0.15 20 56 0.48 DEG CHN 94 P 6 53 P 6 81 P 6 91 P 6 103 P 6 79 P 6 71 P 6 86 P 6 99 P 6 104 P 6 89 P 6 59 P 6 58 P 6 80 P 6 93 P 6 94 P 6 60 P 6 80 P 6 93 P 6 108 P 6 102 P 6 98 P 6 79 P 6 69 P 6 80 P 6 81 P 6 115 P 6 114 P 6 87 P 6 97 P 6 71 P 1 123 P 6 88 P 6 65 P 6 111 P 6 105 P 6 77 P 6 69 P 6 93 P 6 92 P 6 92 P 6 93 P 6 106 P 6 104 P 6 99 P 6 114 P 6 83 P 6 75 P 6 85 P 6 97 P 6 89 P 6 96 P 6 60 P 6 111 P 6 IND %TW SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI MAI MAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SCI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI MAI SAI LOCATION 01H

+0.59 01H

-0.38 01H

-0.48 01H

-0.77 05H

+0.78 01H

+0.77 01H

-0.40 07H

+0.75 01H

+0.77 05H

+0.85 02H

+0.09 02H

+0.83 05H

+0.82 01H

-0.04 01H

-0.74 06H

+0.88 07H

+0.63 02H

-0.34 01H

-0.59 03H

-0.25 05H

+0.41 02H

+0.84 01H

+0.43 01H

-0.64 02H

+0.84 02H

+0.69 04H

-0.33 06H

+0.15 05H

+0.76 05H

+0.73 TSH

-0.06 01H

-0.41 04H

+0.61 06H

+0.80 02H

+0.79 DHB

+2.26 01H

-0.30 05H

-0.36 05H

+0.79 01H

-0.25 01H

-0.48 01H

-0.55 01H

-0.79 01H

+0.39 01H

-0.35 01H

+0.87 05H

-0.48 05H

+0.54 02H

+0.85 07H

+0.68 07H

-0.31 07H

+0.63 07H

-0.49 07H

+0.22 EXT EXT CAL #

01H 01H 161 01H 01H 161 O1H 01H 125 01H 01H 125 05H 05H 161 01H 01H 161 01H 01H 161 07H 07H 161 01H 01H 127 05H 05H 161 02H 02H 161 02H 02H 161 05H 05H 161 01H 01H 50 01H 01H 127 06H 06H 127 07H 07H 127 02H 02H 127 01H 01H 127 03H 03H 161 05H 05H 161 02H 02H 161 01H 01H 127 01H 01H 127 02H 02H 127 02H 02H 127 04H 04H 161 06H 06H 161 05H 05H 161 05H 05H 50 TSH TSH 102 01H 01H 161 04H 04H 161 06H 06H 161 02H 02H 161 DHT 08H 151 01H 01H 50 05H 05H 50 05H 05H 50 01H 01H 50 01H 01H 50 01H 01H 127 01H 01H 127 01H 01H 178 01H 01H 178 01H 01H 127 05H 05H 50 05H 05H 50 02H 02H 50 07H 07H 50 07H 07H 50 07H 07H 50 07H 07H 50 07H 07H 50 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 7 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 98 56 0.20 100 56 0.51 0.18 0.17 0.23 120 56 0.23 0.18 9

57 0.27 17 57 0.57 53 57 0.54 87 57 0.14 97 57 0.82 101 57 0.16 0.43 105 57 0.30 10 58 0.20 20 58 0.43 0.22 22 58 0.21 54 58 0.46 60 58 0.17 62 58 0.30 0.27 0.27 66 58 0.51 0.33 68 58 0.55 94 58 0.22 124 58 0.21 7

59 0.22 0.23 0.22 0.58 9

59 0.27 29 59 0.28 0.23 31 59 0.15 0.39 59 59 0.55 69 59 0.19 83 59 0.29 0.16 101 59 0.27 103 59 0.34 0.17 105 59 0.47 0.16 111 59 0.23 6

60 0.24 26 60 0.19 28 60 0.33 40 60 0.17 60 60 0.32 84 60 0.19 DEG CHN IND %TW LOCATION 88 101 81 74 78 89 68 91 99 105 127 103 98 112 64 79 103 87 59 101 57 96 44 77 99 106 104 78 51 93 81 101 102 79 70 65 103 104 104 91 98 98 124 81 84 101 96 54 96 109 86 65 98 88 P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 MAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI 01H

+0.50 01H

+0.92 01H

-0.74 03H

+0.28 08H

+0.77 02H

+0.66 02H

-0.55 07H

+0.43 07H 07 02H

+0.03 01H

-0.68 01H

-0.04 01H

-0.29 04H

+0.85 01H

-0.46 01H

+0.79 03H

-0.20 04H

+0.71 02H

+0.91 02H

+0.38 02H

+0.91 01H

-0.23 01H

+0.83 02H

+0.80 01H

+0.70 01H

-0.42 01H

-0.46 02H

+0.79 01H

+0.43 03H

+0.87 05H 93 05H

+0.31 07H

+0.53 06H

+0.10 01H

+0.84 02H

+0.83 01H

+0.69 02H

+0.83 01H

+0.79 05H

+0.76 01H

-0.48 01H

+0.30 01H

-0.45 01H

+0.09 01H

+0.89 01H

+0.47 01H

-0.24 02H

+0.64 03H

+0.84 02H

+0.79 03H

+0.88 02H

+0.70 02H

+0.85 01H

-0.40 EXT 01H 01H 01H 03H 08H 02H 02H 07H 07H 02H 01H 01H 01H 04H 01H 01H 03H 04H 02H 02H 02H 01H 01H 02H 01H 01H 01H 02H 01H 03H 05H 05H 07H 06H 01H 02H 01H 02H 01H 05H 01H 01H 01H 01H 01H 01H 01H 02H 03H 02H 03H 02H 02H 01H EXT 01H 01H 01H 03H 08H 02H 02H DHT 07H 02H 01H 01H 01H 04H 01H 01H 03H 04H 02H 02H 02H 01H 01H 02H 01H 01H 01H 02H 01H 03H 05H 05H 07H 06H 01H 02H 01H 02H 01H 05H 01H 01H 01H 01H 01H 01H 01H 02H 03H 02H 03H 02H 02H 01H CAL 127 127 127 127 127 127 127 173 50 161 128 128 128 128 128 161 161 161 161 161 50 50 50 50 50 50 50 128 128 161 161 161 161 161 161 161 161 161 161 50 128 128 128 128 128 128 128 128 161 161 161 161 161 128 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803 P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 8 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 106 60 0.18 0.36 0.19 17 61 0.29 83 61 0.22 95 61 0.71 22 62 0.29 104 62 0.26 29 63 0.20 49 63 0.30 59 63 0.55 61 63 0.52 0.23 0.18 69 63 0.32 101 63 0.26 129 63 0.17 40 64 0.40 0.39 124 64 0.17 35 65 0.31 83 65 0.23 0.18 95 65 0.30 82 66 0.21 106 66 0.33 0.22 118 66 0.19 49 67 1.49 0.51 65 67 0.25 101 67 0.38 111 67 0.22 137 67 0.68 66 68 0.28 74 68 0.19 98 68 0.16 104 68 0.25 110 68 0.25 118 68 0.19 0.15 47 69 0.14 0.14 61 69 0.19 67 69 0.41 83 69 0.33 95 69 0.29 99 69 0.24 0.30 101 69 0.24 105 69 0.24 48 70 0.33 0.19 68 70 0.34 DEG CHN 86 P 6 89 P 6 79 P 6 105 P 6 85 P 6 103 P 6 105 P 6 115 P 6 51 P 6 51 P 6 100 P 6 101 P 6 113 P 6 75 P 6 56 P 6 93 P 6 65 P 6 102 P 6 112 P 6 77 P 6 91 P 6 76 P 6 87 P 6 105 P 6 91 P 6 90 P 6 69 P 6 103 P 6 22 P 1 96 P 6 97 P 6 106 P 6 86 P 6 41 P 6 274 P 6 73 P 6 68 P 6 94 P 6 48 P 6 68 P 6 63 P 6 45 P 6 58 P 6 81 P 6 292 P 6 105 P 6 92 P 6 92 P 6 71 P 6 96 P 6 103 P 6 75 P 6 58 P 6 94 P 6 IND SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SCI MAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI MAI

%TW LOCATION 01H

-0.43 02H

+0.43 02H

-0.32 07H

+0.69 O1H

-0.89 O1H

-0.53 02H

+0.79 01H

+0.33 01H

+0.74 01H

+0.63 07H

+0.16 01H

-0.53 03H

+0.38 03H

+0.81 01H

-0.29 01H

-0.47 02H

-0.65 01H

-0.46 02H

+0.64 02H

+0.72 02H

+0.73 01H

-0.69 01H

+0.33 01H

-0.36 01H

-0.23 01H

+0.39 02H

+0.88 O1H

-0.32 TEH

+0.32 01H

-0.15 05H

+0.72 01H

-0.31 02H

+0.81 TSH

+0.89 05H

+0.19 08H

+0.32 01H

-0.88 01H

-0.27 04H

+0.65 01H

-0.78 02H

+0.86 03H

+0.79 03H

-0.53 05H

+0.64 03H

+0.74 01H

-0.48 01H

-0.27 01H

-0.82 01H

+0.74 01H

-0.80 01H

-0.32 01H

-0.70 04H

-0.32 03H

-0.07 EXT EXT CAL # LEG 01H 02H 02H 07H 01H 01H 02H 01H 01H 01H 07H 01H 03H 03H 01H 01H 02H 01H 02H 02H 02H 01H 01H 01H 01H 01H 02H 01H TEH 01H 05H 01H 02H TSH 05H 08H 01H 01H 04H 01H 02H 03H 03H 05H 03H 01H 01H 01H 01H 01H 01H 01H 04H 03H 01H 02H 02H 07H 01H 01H 02H 01H 01H 01H 07H 01H 03H 03H 01H 01H 02H 01H 02H 02H 02H 01H 01H 01H 01H 01H 02H 01H TSH 01H 05H 01H 02H TSH 05H 08H 01H 01H 04H 01H 02H 03H 03H 05H 03H 01H 01H 01H 01H 01H 01H 01H 04H 03H 128 128 128 161 128 128 161 128 161 161 50 50 50 50 50 128 128 161 161 130 161 130 130 130 130 130 130 130 173 161 50 130 130 117 50 161 130 130 130 130 130 163 163 148 50 130 130 130 130 130 130 163 163 50 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 9 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 80 70 0.25 94 70 0.13 102 70 0.20 59 71 0.41 65 71 0.17 69 71 0.26 0.18 101 71 0.19 70 72 0.16 0.23 94 72 0.22 100 72 0.34 59 73 0.35 89 73 0.16 101 73 0.43 58 74 0.16 68 74 0.42 94 74 0.27 100 74 0.36 116 74 0.29 49 75 0.37 0.26 0.29 53 75 0.22 61 75 0.18 0.39 117 75 0.25 108 76 0.18 112 76 0.61 77 77 0.19 105 77 0.40 109 77 0.33 94 78 0.43 116 78 0.14 120 78 0.32 122 78 0.14 124 78 0.39 0.27 0.68 59 79 0.18 0.72 105 79 0.50 68 80 0.20 102 80 0.19 0.19 108 80 0.21 0.15 110 80 0.24 114 80 0.33 122 80 0.69 0.18 0.25 124 80 0.35 134 80 0.33 DEG 88 73 67 78 76 258 66 98 74 76 74 86 80 113 101 67 268 85 83 1.07 106 96 96 69 72 86 102 63 97 134 99 78 118 73 83 90 89 99 107 77 98 110 77 98 76 78 42 65 103 98 99 84 79 73 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 1 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SAI SAI SAI SAI SAI SAI SAI SAI SAI NAI NAI SAI MAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI NAI SAI SAI SAI SCI SAI SAI MAI SAI MAI SAI SAI SAI MAI SAI SAI MAI SAI SAI SAI MAI SAI MAI SAI SAI SAI MAI SAI SAI

%TW LOCATION EXT 01H

-0.49 01H 01H

+0.34 01H 01H

-0.72 01H 05H

-0.75 05H 02H

+0.70 02H 03H

-0.07 03H 03H

+0.91 03H 01H

-0.82 01H 08H

-0.08 08H 08H

+0.91 08H 01H

-0.40 01H 01H

+0.09 01H 01H

+0.19 01H 01H

-0.37 01H 01H

+0.35 01H 04H

-0.54 04H 03H

+0.30 03H 02H

+0.86 02H 01H

-0.82 01H 01H

-0.43 01H 01H

+0.34 01H 06H

-0.29 06H 06H

+0.49 06H 03H

-0.51 03H 01H

+0.51 01H 07H

+0.11 07H 01H

-0.23 01H 02H

+0.77 02H 01H

-0.30 01H TSH

-0.18 TSH 01H

-0.23 01H 02H

+0.65 02H 01H

-0.64 01H 01H

+0.43 01H 02H

+0.87 02H 01H

+0.30 01H 03H

+0.86 03H 04H

+0.78 04H 05H

+0.29 05H 08C

-0.99 DCT 07H

+0.70 07H 01H

-0.55 01H 04H

+0.79 04H 01H

+0.79 01H 01H

+0.00 01H 01H

+0.95 01H 02H

+0.85 02H 01H

-0.34 01H 01H

-0.57 01H 02H

-0.69 02H 03H

+0.90 03H 05H

+0.75 05H 02H

+0.85 02H 02H

-0.68 02H EXT 01H 01H 01H 05H 02H 03H 03H 01H 08H 08H 01H 01H 01H 01H 01H 04H 03H 02H 01H 01H 01H 06H 06H 03H 01H 07H 01H 02H 01H TSH 01H 02H 01H 01H 02H 01H 03H 04H 05H 08C 07H 01H 04H 01H 01H 01H 02H 01H 01H 02H 03H 05H 02H 02H CAL 50 171 130 148 148 50 50 130 50 50 130 130 148 130 130 148 50 130 130 130 163 163 163 163 148 148 130 130 130 39 131 131 131 131 131 131 131 131 131 87 148 131 148 131 131 131 131 131 131 131 131 131 131 146 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 10 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 59 81 0.28 61 81 0.26 0.23 67 81 0.24 69 81 0.17 103 81 0.36 105 81 0.33 133 81 0.09 0.14 0.10 96 82 0.17 98 82 0.29 130 82 0.22 109 83 0.36 117 83 0.44 100 84 0.42 102 84 0.38 0.37 118 84 0.17 61 85 0.19 81 85 0.51 85 85 0.17 103 85 0.62 0.19 115 85 0.17 139 85 0.24 58 86 0.23 0.17 0.31 84 86 0.13 86 86 0.17 0.17 108 86 0.32 124 86 0.18 53 87 0.30 0.20 61 87 0.26 0.30 0.22 65 87 0.25 103 87 0.65 109 87 0.26 0.18 98 88 0.26 106 88 0.39 122 88 1.04 126 88 0.29 53 89 0.38 87 89 0.26 58 90 0.51 122 90 0.41 0.57 126 90 0.37 134 90 0.23 DEG 104 95 98 138 85 96 102 88 87 68 44 86 79 105 107 99 106 82 81 270 99 36 103 86 85 106 90 65 71 76 88 70 69 53 93 98 67 89 78 77 97 89 71 80 91 89 68 99 97 103 112 99 99 88 CHN P=6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND %TW LOCATION SAI 01H

-0.75 SAI 03H

-0.45 SAI 07H

+0.54 SAI 01H

-0.30 SAI 07H

+0.44 SAI 01H

-0.70 SAI 02H

+0.86 SAI 01H

-0.70 SAI 02H

+0.82 SAI 02H

-0.59 SAI 01H

-0.62 SAI 02H

+0.89 SAI 01H

+0.85 SAI 02H

-0.57 SAI 01H

-0.45 SAI 01H

+0.05 SAI 01H

-0.65 SAI 01H

+0.52 SAI 01H

-0.75 MAI 07H

-0.66 SAI 01H

+0.26 SAI 02H

+0.48 SAI 01H

-0.41 SAI 05H

+0.87 SAI 01H

+0.81 SAI 01H

+0.19 SAI 06H

+0.70 SAI 06H

+0.18 SAI 08H

+1.49 SAI 02H

+0.72 SAI 01H

-0.43 SAI 02H

+0.46 MAI 01H

-0.68 MAI 01H

-0.96 SAI 06H

-0.27 SAI 06H

+0.39 SAI 01H

+0.62 SAI 05H

-0.23 SAI 05H

+0.60 SAI 01H

+0.59 SAI 01H

-0.31 SAI 01H

-0.22 SAI 01H

+0.92 MAI 01H

-0.56 SAI 01H

-0.33 MAI 01H

-0.37 MAI 01H

-0.66 MAI 07H

+0.20 SAI 04H

+0.92 MAI 04H

+0.49 SAI 01H

-0.32 SAI 02H

+0.65 MAI 01H

+0.47 SAI 02H

+0.34 EXT EXT 01H 01H 03H 03H 07H 07H 01H 01H 07H 07H 01H 01H 02H 02H 01H 01H 02H 02H 02H 02H 01H 01H 02H 02H 01H 01H 02H 02H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 07H 07H 01H 01H 02H 02H 01H 01H 05H 05H 01H 01H 01H 01H 06H 06H 06H 06H DHT 08H 02H 02H 01H 01H 02H 02H 01H 01H 01H 01H 06H 06H 06H 06H 01H 01H 05H 05H 05H 05H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 01H 07H 07H 04H 04H 04H 04H 01H 01H 02H 02H 01H 01H 02H 02H CAL # LEG 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 131 HOT 131 HOT 146 HOT 146 HOT 146 HOT 131 HOT 131 HOT 131 HOT 131 HOT 131 HOT 131 HOT 131 HOT 131 HOT 131 HOT 148 HOT 131 HOT 133 HOT 133 HOT 133 HOT 171 HOT 146 HOT 148 HOT 148 HOT 162 HOT 133 HOT 171 HOT 171 HOT 133 HOT 133 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 148 HOT 133 HOT 133 HOT 133 HOT 133 HOT 133 HOT 133 HOT 133 HOT 148 HOT 133 HOT 148 HOT 133 HOT 133 HOT 133 HOT 146 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5402P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 11 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 47 91 0.45 77 91 0.25 103 91 0.36 107 91 0.23 135 91 0.15 0.24 0.10 58 92 0.29 0.24 60 92 0.23 0.23 66 92 0.36 98 92 0.28 0.28 114 92 0.14 122 92 0.32 0.12 134 92 0.16 0.20 53 93 0.30 0.31 55 93 0.27 0.37 57 93 0.37 65 93 0.43 77 93 0.29 0.32 117 93 0.36 62 94 0.43 0.51 0.26 66 94 0.30 0.28 0.24 0.23 86 94 0.54 102 94 0.41 0.27 0.27 118 94 0.23 122 94 0.32 134 94 0.18 47 95 0.42 0.37 49 95 0.31 69 95 0.21 81 95 0.46 87 95 0.33 103 95 0.46 0.35 0.26 0.21 0.41 105 95 0.32 DEG CHN 98 P 6 92 P 6 87 P 6 90 P 6 102 P 6 92 P 6 72 P 6 117 P 6 96 P 6 80 P 6 65 P 6 118 P 6 93 P 6 74 P 6 56 P 6 112 P 6 89 P 6 98 P 6 103 P 6 98 P 6 87 P 6 100 P 6 89 P 6 103 P 6 96 P 6 113 P 6 102 P 6 99 P 6 94 P 6 111 P 6 92 P 6 95 P 6 97 P 6 94 P 6 81 P 6 98 P 6 276 P 6 94 P 6 97 P 6 104 P 6 89 P 6 90 P 6 100 P 6 102 P 6 92 P 6 68 P 6 101 P 6 107 P 6 99 P 6 78 P 6 91 P 6 92 P 6 87 P 6 99 P 6 IND SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI MAI SAI MAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SAI

%TW LOCATION EXT 01H

+0.77 01H 04H

+0.46 04H 02H

+0.62 02H 01H

+0.82 01H 01H

+0.84 01H 02H

+0.79 02H 02H

-0.26 02H 02H

+0.93 02H 05H

+0.88 05H 05H

-0.13 05H 05H

+0.72 05H 03H

-0.71 03H 01H

+0.00 01H 01H

-0.76 01H 04H

+1.00 04H 01H

-0.62 01H 02H

+0.23 02H 02H

-0.73 02H 02H

+0.26 02H 02H

+0.47 02H 03H

+0.90 03H 02H

+0.94 02H 04H

+0.91 04H 03H

+0.65 03H 06H

+0.68 06H 01H

+0.75 01H 07H

+0.76 07H 02H

+0.25 02H 01H

-0.13 01H 02H

+0.78 02H 04H

-0.10 04H 01H

+0.41 01H 06H

+0.44 06H 08H

-0.16 08H 08H

+0.81 08H 01H

-0.20 01H 01H

-0.36 01H 01H

+0.46 01H 02H

+0.83 02H 01H

+0.60 01H 01H

+0.80 01H 02H

+0.68 02H 02H

+0.73 02H 02H

-0.33 02H 02H

+0.92 02H 02H

+0.88 02H 01H

+0.02 01H 01H

-0.32 01H 01H

-0.86 01H 01H

+0.81 01H 02H

+0.52 02H 04H

+0.86 04H 07H

+0.37 07H 01H

-0.39 01H EXT 01H 04H 02H 01H 01H 02H 02H 02H 05H 05H 05H 03H 01H 01H 04H 01H 02H 02H 02H 02H 03H 02H 04H 03H 06H 01H 07H 02H 01H 02H 04H 01H 06H 08H 08H 01H 01H 01H 02H 01H 01H 02H 02H 02H 02H 02H 01H 01H 01H 01H 02H 04H 07H 01H CAL 148 148 133 133 146 146 146 148 148 148 148 148 133 133 133 133 133 146 146 148 148 148 148 148 148 148 148 133 148 148 148 148 148 148 148 133 133 133 133 133 133 146 148 148 148 148 133 133 133 133 133 133 133 133 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 12 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 0.27 107 95 0.19 40 96 0.47 0.27 48 96 0.35 0.39 0.43 0.44 0.36 58 96 0.25 64 96 0.26 86 96 0.14 90 96 0.21 98 96 0.30 102 96 0.28 104 96 0.31 108 96 0.15 0.19 122 96 0.35 124 96 0.25 0.26 59 97 0.55 61 97 0.44 0.34 0.29 97 97 0.26 103 97 0.42 0.38 0.32 0.22 119 97 0.28 74 98 0.29 90 98 0.23 98 98 0.20 108 98 0.18 110 98 0.20 116 98 0.24 122 98 0.45 61 99 0.44 87 99 0.27 93 99 0.20 105 99 0.18 0.15 107 99 0.18 60 100 0.27 64 100 0.21 0.31 66 100 0.21 68 100 0.69 0.17 72 100 0.20 98 100 0.26 108 100 0.32 116 100 0.13 DEG 74 62 96 107 109 88 95 105 101 75 110 69 111 116 70 90 75 89 98 60 74 98 93 96 105 84 95 95 113 75 86 82 92 66 77 47 39 77 98 87 78 75 55 93 64 73 80 131 96 72 83 101 104 67 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SAX SAX SAX SAX SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI MAI SAI SAI SAI MAI

%TW LOCATION 02H

+0.69 06H

-0.44 04H

+0.73 06H

+0.93 01H

+0.23 02H

-0.67 04H

+0.74 05H

-0.37 05H

+0.78 03H

+0.96 02H

+0.63 O1H

-0.86 01H

-0.48 04H

+0.81 01H

-0.75 01H

+0.66 01H

+0.83 02H

+0.64 01H

-0.21 02H

-0.75 02H

+0.48 01H

-0.75 02H

+0.48 01H

+0.02 05H

-0.31 02H

+0.47 01H

-0.16 01H

+0.87 04H

+0.46 05H

+0.82 02H

+0.53 05H

+0.80 01H

+0.86 05H

+0.85 02H

+0.91 03H

+0.45 02H

+0.82 02H

-0.22 02H

+0.61 02H

+0.52 01H

+0.90 01H

-0.49 01H

+0.30 01H

-0.15 01H

+0.91 01H

-0.20 01H

+0.65 02H

+0.82 01H

+0.60 03H

+0.76 01H

+0.76 01H

-0.85 01H

+0.20 03H

+0.90 EXT 02H 06H 04H 06H 01H 02H 04H 05H 05H 03H 02H 01H 01H 04H 01H 01H 01H 02H 01H 02H 02H 01H 02H 01H 05H 02H 01H 01H 04H 05H 02H 05H 01H 05H 02H 03H 02H 02H 02H 02H 01H 01H 01H 01H 01H 01H 01H 02H 01H 03H 01H 01H 01H 03H EXT 02H 06H 04H 06H 01H 02H 04H 05H 05H 03H 02H 01H 01H 04H 01H 01H 01H 02H 01H 02H 02H 01H 02H 01H 05H 02H 01H 01H 04H 05H 02H 05H 01H 05H 02H 03H 02H 02H 02H 02H 01H 01H 01H 01H 01H 01H 01H 02H 01H 03H 01H 01H 01H 03H CAL

  • 133 133 148 148 148 148 148 148 148 148 148 135 135 135 163 135 135 135 135 135 135 148 163 148 148 135 135 135 135 135 135 148 135 135 135 135 135 135 148 135 135 171 171 135 140 171 171 140 140 140 140 145 145 145 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 13 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG 49 101 0.31 96 53 101 0.37 84 0.28 74 69 101 0.18 82 81 101 0.21 133 89 101 0.24 103 0.18 59 0.20 77 97 101 0.32 93 103 101 0.36 111 0.40 111 36 102 0.69 96 64 102 0.24 76 68 102 0.24 112 74 102 0.27 75 0.40 102 84 102 0.32 86 120 102 0.27 88 134 102 0.25 74 53 103 0.32 77 0.50 110 69 103 0.34 83 89 103 0.16 69 119 103 0.15 58 121 103 0.53 100 48 104 0.34 95 0.25 76 68 104 0.38 87 27 105 0.26 95 53 105 0.24 66 57 105 0.39 89 0.20 98 89 105 0.25 106 48 106 0.41 86 60 106 0.28 87 0.26 107 64 106 0.21 56 82 106 0.55 87 110 106 0.34 85 7

107 0.57 103 0.11 84 0.25 98 13 107 0.18 80 37 107 0.18 74 0.22 78 61 107 0.30 90 8

108 0.34 107 48 108 0.34 96 50 108 0.19 60 60 108 0.60 26 66 108 0.31 81 110 108 0.30 95 126 108 0.38 77 5

109 0.19 86 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 1 P 6 P 6 P 1 P 1 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 2

P 6 P 6 P 6 P 6 IND MAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SCI SAI SAI SCI SCI SAI SAI MAI MAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI

%TW LOCATION 01H

+0.79 01H

+0.22 07H

+0.31 01H

+0.88 02H

+0.86 01H

-0.22 02H

+0.80 04H

+0.70 01H

-0.50 01H

-0.43 01H

+0.33 05H

+0.26 01H

+0.84 02H

+0.83 04H

+0.69 01H

-0.09 01H

-0.62 02H

+0.96 02H

-0.95 06H

-0.21 01H

-0.44 01H

+0.78 05H

+0.88 02H

-0.48 02H

+0.68 01H

+0.43 02H

+0.64 01H

+0.82 07H

-0.41 01H

+0.25 01H

-0.23 TSH

-0.22 01H

-0.42 02H

-0.48 TSH

+0.08 TSH

-0.12 02H

+0.91 01H

+0.68 02H

+0.37 01H

-0.40 DHB

+0.00 07H

+0.45 06H

-0.06 07H

-0.77 07H

+0.67 02H

+0.83 06H

+0.46 02H

+0.72 02H

+0.95 TSH

-0.14 01H

-0.44 01H

-0.50 02H

+0.89 01H

-0.71 EXT 01H 01H 07H 01H 02H 01H 02H 04H 01H 01H 01H 05H 01H 02H 04H 01H 01H 02H 02H 06H 01H 01H 05H 02H 02H 01H 02H 01H 07H 01H 01H TSH 01H 02H TSH TSH 02H 01H 02H 01H 07H 07H 06H 07H 07H 02H 06H 02H 02H TSH 01H 01H 02H 01H EXT 01H 01H 07H 01H 02H 01H 02H 04H 01H 01H 01H 05H 01H 02H 04H 01H 01H 02H 02H 06H 01H 01H 05H 02H 02H 01H 02H 01H 07H 01H 01H TSH 01H 02H TSH TSH 02H 01H 02H 01H DHT DHT 06H 07H 07H 02H 06H 02H 02H TSH 01H 01H 02H 01H CAL I 140 140 140 140 145 171 171 171 145 145 145 140 140 140 140 165 145 145 146 140 165 140 145 145 145 140 140 140 129 140 140 82 145 140 83 83 140 145 145 123 123 123 129 129 129 140 123 140 140 81 140 145 143 123 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 14 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 0.17 7

109 0.16 0.23 0.27 0.43 9

109 0.42 0.42 47 109 0.15 8

110 0.38 38 110 0.31 54 110 0.28 102 110 0.32 114 110 0.20 126 110 0.22 1

111 0.38 17 111 0.33 23 111 0.30 25 111 0.39 49 111 0.15 57 111 0.12 0.35 63 111 0.26 101 111 0.29 4

112 0.29 0.14 6

112 0.36 0.31 0.27 0.38 44 112 0.38 56 112 0.35 88 112 0.32 102 112 0.27 112 112 0.16 0.17 120 112 0.18 5

113 0.36 7

113 0.53 9

113 0.31 0.14 0.26 0.23 0.16 17 113 0.14 0.19 0.16 0.21 0.22 27 113 0.18 29 113 0.37 43 113 0.11 47 113 0.16 49 113 0.35 0.08 DEG 91 76 97 68 90 110 91 86 103 101 76 87 63 108 88 88 96 78 22 63 81 84 112 96 86 94 99 100 99 95 91 96 99 64 80 70 100 95 62 72 83 86 263 41 75 73 79 57 63 109 125 87 54 39 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 1 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 1 P 1 2

P 6 IND SAI SAI SAI SAI SAI MAI MAI SAI MAI SAI SAI MAI MAI SAI SAI SAI SAI SAI SCI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI MAI SAI MAI MAI MAI SAI SAI SAI MAI SAI MAI SAI MAI SAI SAI SAI HAI SAI SAI SAI SCI SCI SAI SAI

%TW LOCATION EXT 01H

+0.58 01H 03H

-0.64 03H 03H

+0.80 03H 06H

-0.72 06H 06H

+0.10 06H 06H

+0.38 06H 07H

-0.26 07H DHB

+0.41 DHB 06H

-0.21 06H 04H

+0.58 04H 01H

+0.59 01H 04H

+0.78 04H 02H

-0.39 02H 01H

+0.72 01H 06H

+0.73 06H 02H

+0.87 02H 07H

-0.36 07H 02H

+0.54 02H TSH

-0.22 TSH 01H

-0.47 01H 01H

+0.83 01H 03H

+0.71 03H 01H

+0.35 01H 01H

-0.82 01H 01H

+0.69 01H 05H

-0.69 05H 05H

+0.86 05H 06H

-0.30 06H 06H

+0.36 06H 01H

+0.64 01H 01H

-0.25 01H 01H

+0.65 01H 01H

-0.61 01H 02H

+0.81 02H 04H

+0.81 04H 01H

+0.87 01H 01H

-0.52 01H 06H

+0.67 06H 01H

-0.28 01H 05H

-0.56 05H 05H

+0.30 05H 07H

-0.90 07C 07H

+0.20 07C 02H

-0.28 02H 05H

+0.19 05H 06H

+0.79 06H 07H

-0.11 07H 07H

+0.82 07H 01H

+0.83 01H 01H

-0.58 01H TSH

-0.08 TSH TSH

-0.05 TSH TSH

-0.22 TSH 01H

-0.27 01H EXT 01H 03H 03H 06H 06H 06H DHT DHB 06H 04H 01H 04H 02H 01H 06H 02H 07H 02H TSH 01H 01H 03H 01H 01H 01H 05H 05H 06H 06H 01H 01H 01H 01H 02H 04H 01H 01H 06H 01H 05H 05H 07H 07H 02H 05H 06H 07H 07H 01H 01H TSH TSH TSH 01H CAL 123 123 123 123 123 123 123 159 123 129 140 145 145 143 165 129 129 129 75 140 140 129 145 123 123 123 123 123 123 129 129 145 145 145 145 145 123 123 123 123 123 155 155 129 129 129 129 129 129 129 75 76 75 129 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5402P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 15 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 0.23 53 113 0.69 69 113 0.27 0.20 0.31 71 113 0.10 0.20 103 113 0.15 0.13 6

114 0.56 0.33 0.22 0.31 0.36 0.29 8

114 0.38 16 114 0.20 28 114 0.19 68 114 0.31 104 114 0.25 108 114 0.17 0.18 118 114 0.16 120 114 0.30 122 114 0.20 0.30 7

115 0.20 9

115 0.19 0.37 0.22 17 115 0.18 0.41 21 115 0.14 23 115 0.49 0.21 0.17 53 115 0.15 0.23 57 115 0.30 61 115 0.16 0.47 63 115 0.18 69 115 0.27 71 115 0.49 99 115 0.30 105 115 0.32 0.12 107 115 0.31 109 115 0.27 4

116 0.52 6

116 0.22 0.13 0.16 0.32 117 100 82 155 122 126 38 47 98 102 105 79 97 112 105 86 114 82 95 106 101 75 89 102 82 88 80 86 78 76 92 81 90 103 92 91 29 114 76 65 90 53 108 108 99 98 60 91 86 88 108 50 66 73 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI MAI MAI MAI SAI MAI MAI SAI MAI SAI SAI MAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI 01H

+0.81 02H

+0.51 02H

+0.47 03H

-0.86 03H

-0.34 02H

-0.87 02H

+0.89 02H

-0.31 02H

+0.91 01H

-0.84 01H

+0.72 03H

+0.73 05H

+0.65 07H

-0.07 07H

+0.84 05H

+0.63 07H

-0.54 02H

+0.92 01H

-0.73 04H

+0.68 02H

+0.80 04H

-0.42 01H

+0.79 02H

+0.54 01H

+0.71 02H

+0.91 01H

+0.31 01H

+0.64 04H

-0.16 06H

-0.22 01H

-0.54 01H

+0.39 07H

-0.60 04H

+0.11 06H

+0.17 DHB

+0.93 02H

-0.35 02H

+0.42 01H

+0.77 01H

-0.36 01H

+0.64 02H

-0.39 02H

+0.83 01H

+0.38 01H

-0.32 04H

-0.57 04H

+0.78 02H

+0.78 02H

+0.86 06H

+0.21 01H

-0.86 02H

-0.90 05H

-0.88 05H

+0.27 01H 02H 02H 03H 03H 02H 02H 02H 02H 01H 01H 03H 05H 07H 07H 05H 07H 02H 01H 04H 02H 04H 01H 02H 01H 02H 01H 01H 04H 06H 01H 01H 07H 04H 06H DHT 02H 02H 01H 01H 01H 02H 02H 01H 01H 04H 04H 02H 02H 06H 01H 02H 05H 05H 01H 02H 02H 03H 03H 02H 02H 02H 02H 01H 01H 03H 05H DHT DHT 05H 07H 02H 01H 04H 02H 04H 01H 02H 01H 02H 01H 01H 04H 06H 01H 01H 07H 04H 06H DHB 02H 02H 01H 01H 01H 02H 02H 01H 01H 04H 04H 02H 02H 06H 01H 02H 05H 05H 129 HOT 129 HOT 129 HOT 129 HOT 129 HOT 129 HOT 129 HOT 145 HOT 145 HOT 123 HOT 123 HOT 123 HOT 123 HOT 123 HOT 123 HOT 123 HOT 129 HOT 129 HOT 129 HOT 145 HOT 145 HOT 145 HOT 143 HOT 143 HOT 143 HOT 143 HOT 123 HOT 123 HOT 123 HOT 123 HOT 129 HOT 129 HOT 129 HOT 165 HOT 129 HOT 155 HOT 129 HOT 129 HOT 129 HOT 129 HOT 129 HOT 129 HOT 129 HOT 129 HOT 145 HOT 145 HOT 145 HOT 145 HOT 145 HOT 123 HOT 123 HOT 123 HOT 123 HOT 123 HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 16 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 10 116 0.26 30 116 0.27 48 116 0.44 0.61 0.35 62 116 0.32 104 116 0.70 114 116 0.47 0.17 124 116 0.27 9

117 0.14 0.14 0.39 0.33 29 117 0.37 0.18 41 117 0.18 45 117 0.24 53 117 0.30 0.17 0.19 0.63 57 117 0.27 59 117 0.25 101 117 0.22 103 117 0.20 0.40 107 117 0.16 6

118 0.11 0.23 10 118 0.29 12 118 0.20 0.47 0.24 28 118 0.58 34 118 0.23 42 118 0.08 66 118 0.25 72 118 0.27 108 118 0.17 7

119 0.30 0.24 0.25 29 119 0.27 37 119 0.15 0.21 0.35 49 119 0.23 57 119 0.33 0.16 63 119 0.52 69 119 0.18 0.51 0.35 DEG 104 84 91 98 96 63 101 90 66 93 72 85 71 86 77 50 101 142 103 100 79 90 58 89 79 66 97 76 74 104 105 79 85 94 77 95 116 84 74 109 100 72 74 82 132 83 100 44 74 94 95 50 98 111 CHN IND P 6 MAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 1 MCI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 MAI P 1 SCI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 MAI P 1 SCI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI

%TW LOCATION 06H

-0.40 07H

-0.69 01H

+0.71 02H

+0.69 06H

+0.76 01H

-0.57 01H

-0.04 02H

+0.75 04H

+0.66 02H

+0.57 07C

-0.06 05H

+0.33 06H

-0.44 06H

+0.63 03H

-0.34 03H

+0.34 02H

-0.23 TSH

-0.14 02H

-0.59 02H

+0.46 06H

-0.59 06H

+0.75 01H

+0.71 02H

+0.70 02H

+0.79 02H

+0.49 04H

+0.56 04H

+0.80 03H

+0.76 05H

+0.51 05H

+0.85 01H

-0.79 01H

+0.70 05H

+1.00 07H

-0.30 01H

+0.63 TSH

+0.06 02H

+0.48 01H

-0.53 01H

+0.90 01H

+0.88 03H

+0.79 06H

+0.17 02H

+0.85 TSH

+0.01 02H

+0.86 04H

+0.80 02H

+0.45 06H

+0.43 06H

-0.23 01H

-0.19 01H

-0.33 01H

+0.66 02H

+0.65 EXT 06H 07H 01H 02H 06H 01H 01H 02H 04H 02H 07C 05H 06H 06H 03H 03H 02H TSH 02H 02H 06H 06H 01H 02H 02H 02H 04H 04H 03H 05H 05H 01H 01H 05H 07H 01H TSH 02H 01H 01H 01H 03H 06H 02H TSH 02H 04H 02H 06H 06H 01H 01H 01H 02H EXT 06H 07H 01H 02H 06H 01H 01H 02H 04H 02H 07H 05H 06H 06H 03H 03H 02H TSH 02H 02H 06H 06H 01H 02H 02H 02H 04H 04H 03H 05H 05H 01H 01H 05H 07H 01H TSH 02H 01H 01H 01H 03H 06H 02H TSH 02H 04H 02H 06H 06H 01H 01H 01H 02H CAL # LEG 123 136 136 136 136 129 165 143 143 143 158 123 123 123 136 136 136 75 129 129 129 129 129 129 145 145 145 145 123 123 123 136 136 136 136 136 75 129 129 145 123 123 123 136 75 136 136 136 132 132 129 165 165 129 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 17 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 93 119 0.19 101 119 0.29 121 119 0.17 4

120 0.35 0.31 0.19 10 120 0.27 0.14 16 120 0.34 0.23 0.20 42 120 0.58 0.18 62 120 0.21 64 120 0.39 0.33 88 120 0.18 0.24 104 120 0.55 0.27 0.32 110 120 0.18 1

121 0.18 7

121 0.26 0.22 0.13 0.49 0.24 0.22 9

121 0.17 0.19 27 121 0.48 29 121 0.20 37 121 0.26 0.27 39 121 0.28 53 121 0.58 0.30 57 121 0.37 59 121 0.48 0.48 0.30 61 121 0.58 103 121 0.45 0.36 6

122 0.17 0.19 12 122 0.34 14 122 0.46 0.17 0.25 16 122 0.54 40 122 0.16 48 122 0.25 DEG 99 108 120 89 91 52 130 39 77 73 53 105 72 79 87 97 73 102 93 107 113 75 101 73 85 69 98 94 80 93 87 79 97 86 81 69 99 108 64 86 97 94 93 109 103 96 97 108 85 59 67 81 79 91 CHN P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI

%TW LOCATION 02H

+0.63 02H

+0.42 O1H

+0.38 05H

+0.25 06H

-0.47 06H

+0.78 02H

-0.30 02H

+0.78 03H

+0.75 01H

-0.03 04H

-0.71 02H

-0.11 02H

+0.54 01H

-0.86 01H

-0.06 01H

+0.79 01H

+0.74 01H

+0.20 01H

+0.44 02H

+0.74 04H

+0.38 02H

+0.15 DHB

+0.39 02H

-0.46 03H

-0.55 03H

+0.79 05H

+0.44 06H

+0.12 06H

+0.83 01H

+0.75 03H

+0.77 01H

+0.61 03H

+0.74 02H

+0.18 01H

+0.18 01H

+0.60 01H

-0.58 02H

-0.39 01H

-0.11 01H

-0.34 01H

+0.62 02H

+0.96 01H

-0.61 02H

+0.36 04H

+0.79 01H

+0.71 05H

-0.23 01H

+0.49 01H

+0.78 01H

-0.13 04H

+0.78 07H

-0.78 02H

+0.92 01H

-0.77 EXT EXT CAL # LEG 02H 02H 01H 05H 06H 06H 02H 02H 03H 01H 04H 02H 02H 01H 01H 01H 01H 01H 01H 02H 04H 02H 07H 02H 03H 03H 05H 06H 06H 01H 03H 01H 03H 02H 01H 01H 01H 02H 01H 01H 01H 02H 01H 02H 04H 01H 05H 01H 01H 01H 04H 07H 02H 01H 02H 02H 01H 05H 06H 06H 02H 02H 03H 01H 04H 02H 02H 01H 01H 01H 01H 01H 01H 02H 04H 02H 07C 02H 03H 03H 05H 06H 06H 01H 03H 01H 03H 02H 01H 01H 01H 02H 01H 01H 01H 02H 01H 02H 04H 01H 05H 01H 01H 01H 04H 07H 02H 01H 143 143 143 165 123 123 123 123 165 136 136 136 136 129 129 129 143 143 143 143 143 143 84 123 123 123 123 123 123 123 123 136 136 165 136 136 136 136 136 136 136 136 136 143 143 123 123 136 136 136 136 136 136 136 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803=P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 18 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Ax ROW LINE VOLTS DEG CHN IND %TW LOCATION

ial Indiccations 56 122 0.14 64 122 0.36 0.33 66 122 0.14 0.22 68 122 0.26 110 122 0.42 1

123 0.21 5

123 0.23 15 123 0.27 27 123 0.40 29 123 0.24 41 123 0.54 59 123 0.19 61 123 0.56 0.42 69 123 0.34 0.43 83 123 0.11 0.36 6

124 0.41 0.31 0.14 0.25 0.15 16 124 0.28 30 124 0.46 0.20 34 124 0.36 56 124 0.41 64 124 0.61 74 124 0.44 80 124 0.20 114 124 0.17 0.18 7

125 0.21 0.18 0.26 0.19 9

125 0.41 19 125 0.13 23 125 0.29 25 125 0.20 47 125 0.47 0.35 59 125 0.30 69 125 0.41 99 125 0.14 0.29 20 126 0.21 38 126 0.60 46 126 0.17 64 126 0.73 74 126 0.27 90 94 80 79 70 88 105 105 81 73 105 66 103 67 102 84 85 93 57 105 104 110 80 85 67 84 96 82 101 89 89 103 91 85 78 85 102 72 64 101 73 68 91 95 91 99 97 61 110 63 104 75 99 94 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI MAI MAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI 02H

+0.81 01H

-0.62 02H

+0.59 01H

-0.11 01H

+0.91 01H

-0.77 02H

-0.48 DCB

+1.33 06H

+0.75 04H

+0.07 03H

+0.60 04H

+0.69 01H

+0.68 02H

-0.13 01H

+0.55 05H

+0.69 01H

-0.32 01H

+0.50 02H

+0.15 03H

+0.74 01H

-0.74 01H

-0.20 01H

+0.75 03H

-0.46 03H

+0.69 04H

+0.72 05H

+0.65 05H

-0.64 02H

+0.60 01H

+0.40 01H

+0.44 01H

-0.34 01H

+0.71 02H

-0.34 02H

+0.28 01H

-0.63 01H

+0.70 02H

+0.08 02H

+0.77 03H

-0.27 01H

+0.80 02H

+0.73 03H

+0.66 01H

+0.44 01H

-0.48 01H

+0.79 01H

-0.24 02H

-0.22 02H

+0.45 02H

+0.84 03H

-0.25 01H

+0.88 02H

+0.63 01H

-0.11 EXT 02H 01H 02H 01H 01H 01H 02H 07H 06H 04H 03H 04H 01H 02H 01H 05H 01H 01H 02H 03H 01H 01H 01H 03H 03H 04H 05H 05H 02H 01H 01H 01H 01H 02H 02H 01H 01H 02H 02H 03H 01H 02H 03H 01H 01H 01H 01H 02H 02H 02H 03H 01H 02H 01H EXT 02H 01H 02H 01H 01H 01H 02H 07C 06H 04H 03H 04H 01H 02H 01H 05H 01H 01H 02H 03H 01H 01H 01H 03H 03H 04H 05H 05H 02H 01H 01H 01H 01H 02H 02H 01H 01H 02H 02H 03H 01H 02H 03H 01H 01H 01H 01H 02H 02H 02H 03H 01H 02H 01H CAL 136 165 129 129 129 129 143 84 123 136 136 136 136 136 136 136 129 129 143 143 123 123 123 123 123 136 136 136 136 136 136 129 129 143 143 123 123 123 123 123 136 136 136 136 136 136 129 143 143 136 136 136 136 129 LEG HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5601P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 19 of 24 Customer Name: St. Lucie Unit 2 Component: SIG B Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 0.22 108 126 0.26 7

127 0.54 0.29 0.80 0.31 0.26 19 127 0.14 25 127 0.21 45 127 0.41 0.18 47 127 0.66 57 127 0.23 0.19 61 127 0.42 0.53 0.34 101 127 0.11 107 127 0.19 6

128 0.32 0.39 0.31 0.32 0.34 16 128 0.31 0.20 24 128 0.19 34 128 0.15 0.47 38 128 0.21 58 128 0.19 0.45 84 128 0.35 100 128 0.27 5

129 0.18 0.25 0.11 23 129 0.20 35 129 0.41 45 129 0.47 53 129 0.36 0.23 61 129 0.71 63 129 0.29 75 129 0.32 0.17 87 129 0.21 99 129 0.27 10 130 0.23 0.22 16 130 0.25 0.18 0.34 0.35 DEG 107 90 100 79 102 86 96 88 90 105 71 90 84 79 92 101 80 89 66 98 96 103 78 96 98 106 76 66 99 83 75 106 103 85 45 84 68 101 79 99 84 96 92 86 106 67 118 121 96 152 78 66 89 79 CHN P=6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 P 6 IND %TW SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MAI MAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI LOCATION 01H

+0.71 02H

+0.80 01H

+0.65 02H

+0.37 03H

-0.40 03H

+0.84 07C

+0.44 02H

+0.62 02H

+0.70 01H

+0.83 01H

-0.30 02H

-0.49 01H

-0.19 01H

+0.82 01H

-0.78 01H

+0.55 02H

+0.49 02H

-0.71 02H

+0.84 02H

+0.44 03H

-0.33 03H

+0.42 05H

-0.83 05H

+0.49 03H

-0.46 03H

+0.80 02H

+0.42 03H

-0.68 03H

+0.73 01H

-0.44 01H

-0.61 04H

+0.64 02H

+0.13 01H

+0.48 03H

-0.50 03H

+0.81 04H

+0.85 02H

+0.82 02H

+0.78 01H

+0.34 01H

-0.38 02H

+0.01 01H

-0.74 01H

+0.83 01H

+0.25 01H

+0.97 02H

+0.44 01H

+0.48 01H

+0.48 02H

-0.60 04H

-0.75 04H

+0.64 05H

+0.86 05H

-0.51 EXT EXT CAL #

01H 02H 01H 02H 03H 03H 07C 02H 02H 01H 01H 02H 01H 01H 01H 01H 02H 02H 02H 02H 03H 03H 05H 05H 03H 03H 02H 03H 03H 01H 01H 04H 02H 01H 03H 03H 04H 02H 02H 01H 01H 02H 01H 01H 01H 01H 02H 01H 01H 02H 04H 04H 05H 05H 01H 02H 01H 02H 03H 03H 07C 02H 02H 01H 01H 02H 01H 01H 01H 01H 02H 02H 02H 02H 03H 03H 05H 05H 03H 03H 02H 03H 03H 01H 01H 04H 02H 01H 03H 03H 04H 02H 02H 01H 01H 02H 01H 01H 01H 01H 02H 01H 01H 02H 04H 04H 05H 05H 129 143 123 123 123 123 73 136 136 136 136 136 136 136 136 136 136 143 143 123 123 123 123 123 165 165 165 165 165 165 165 165 143 143 123 123 123 165 165 165 165 165 165 165 129 129 143 143 123 123 139 139 139 139 LEG HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 20 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 22 130 0.15 82 P 6 SAI O1H

+0.81 01H 01H 139 HOT 5803P 40 130 0.14 62 P 6 SAI 02H

+0.75 02H 02H 139 HOT 5803P 0.18 75 P 6 SAI 04H

+0.48 04H 04H 139 HOT 5803P 44 130 0.76 81 P 6 SAI DHT

+0.66 VS3 DHB 155 HOT 5602P 48 130 0.36 102 P 6 MAX 01H

-0.18 01H 01H 139 HOT 5803P 0.35 109 P 6 MAI 02H

+0.70 02H 02H 139 HOT 5803P 0.35 107 P 6 SAl 03H

-0.70 03H 03H 139 HOT 5803P 0.32 98 P 6 SAX 04H

+0.95 04H 04H 139 HOT 5803P 54 130 0.23 100 P 6 SAX 01H

+0.30 01H 01H 139 HOT 5803P 0.25 105 P 6 SAX 01H

-0.82 01H O1H 139 HOT 5803P 62 130 0.38 102 P 6 SAX 01H

+0.60 01H O1H 139 HOT 5803P 0.25 96 P 6 SAX 01H

+0.02 01H O1H 139 HOT 5803P 68 130 0.40 95 P 6 MAI 02H

+0.60 02H 02H 139

'HOT 5803P 72 130 0.35 99 P 6 MAI 01H

-0.32 01H 01H 129 HOT 5803P 3

131 0.26 79 P 6 SAX 03H

+0.84 03H 03H 123 HOT 5803P 5

131 0.22 45 P 6 SAI 03H

-0.40 03H 03H 123 HOT 5803P 0.13 56 P 6 SAI 03H

+0.89 03H 03H 123 HOT 5803P 11 131 0.33 94 P 6 SAl 04H

+0.43 04H 04H 139 HOT 5803P 13 131 0.17 257 P 6 SAI 02H

+0.95 02H 02H 139 HOT 5803P 0.60 101 P 6 MAI 01H

-0.69 01H 01H 165 HOT 5803P 53 131 0.66 98 P 6 SAl 01H

+0.83 01H 01H 140 HOT 5803P 0.59 102 P 6 SAl 02H

+0.82 02H 02H 140 HOT 5803P 57 131 0.18 115 P 6 SAl 01H

+0.29 01H 01H 140 HOT 5803P 0.68 98 P 6 SAl 01H

-0.77 O1H 01H 140 HOT 5803P 6

132 0.39 114 P 6 SAl 07C

-0.32 07C DCT 73 COLD 5803P 0.22 98 P 6 SAl 07C

+0.59 07C DCT 73 COLD 5803P 30 132 0.29 95 P 6 SAl 04H

+1.00 04H 04H 139 HOT 5803P 0.63 280 P 6 SAX 05H

+0.77 05H 05H 139 HOT 5803P 0.22 84 P 6 SAX 05H

-0.58 05H 05H 139 HOT 5803P 34 132 0.22 72 P 6 SAX 02H

+0.90 02H 02H 139 HOT 5803P 48 132 0.39 104 P 6 SAl 01H

-0.62 O1H 01H 140 HOT 5803P 0.45 93 P 6 SAI 01H

+0.62 O1H O1H 140 HOT 5803P 58 132 0.29 75 P 6 SAI O1H

-0.45 01H 01H 140 HOT 5803P 0.45 91 P 6 SAX 02H

-0.24 02H 02H 140 HOT 5803P 7

133 0.43 92 P6 SAX 06H

-0.20 06H 06H 123 HOT 5803P 0.66 96 P 6 SAl 06H

+0.66 06H 06H 123 HOT 5803P 23 133 0.14 51 P 6 SAl 02H

+0.90 02H 02H 139 HOT 5803P 51 133 0.15 85 P 6 SAX O1H

-0.81 01H 01H 140 HOT 5803P 63 133 0.18 114 P 6 SAX O1H

+0.30 O1H O1H 171 HOT 5803P 67 133 0.29 112 P 6 SAX 01H

+0.36 01H O1H 140 HOT 5803P 95 133 0.14 54 P6 SAl 02H

+0.39 02H 02H 143 HOT 5803P 6

134 0.18 99 P6 SAX 01H

+0.83 01H 01H 123 HOT 5803P 0.30 91 P 6 SAl 03H

-0.60 03H 03H 123 HOT 5803P 0.13 68 P 6 SAX 03H

+0.86 03H 03H 123 HOT 5803P 0.29 78 P 6 MAI 05H

+0.08 05H 05H 123 HOT 5803P 10 134 0.29 67 P 6 SAl 03H

-0.18 03H 03H 123 HOT 5803P 12 134 0.23 68 P 6 SAl 01H

+1.01 01H 01H 139 HOT 5803P 30 134 0.34 93 P 6 SAl 02H

+0.32 02H 02H 139 HOT 5803P 0.33 80 P 6 MAI 03H

+0.52 03H 03H 139 HOT 5803P 32 134 0.19 39 P6 SAI 03H

+0.42 03H 03H 139 HOT 5803P 50 134 0.36 100 P 6 SAX 03H

-0.30 03H 03H 140 HOT 5803P 15 135 0.17 62 P 6 SAI 03H

-0.16 03H 03H 139 HOT 5803P 61 135 0.21 45 P 6 SAl 02H

-0.56 02H 02H 140 HOT 5803P 0.26 89 P 6 SAl 02H

+0.91 02H 02H 140 HOT 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 21 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 69 135 0.30 50 136 0.20 82 136 0.27 7

137 0.20 0.32 0.32 0.37 9

137 0.57 13 137 0.27 87 137 0.18 2

138 0.23 12 138 0.26 52 138 0.25 0.15 94 138 0.16 5

139 0.17 11 139 0.16 0.38 0.16 21 139 0.15 0.34 43 139 0.34 10 140 0.13 12 140 0.28 0.28 40 140 0.16 42 140 0.19 74 140 0.36 13 141 0.25 15 141 0.22 0.26 23 141 0.17 25 141 0.29 0.14 35 141 0.37 45 141 0.15 47 141 0.23 61 141 0.28 63 141 0.20 10 142 0.23 12 142 0.22 0.20 16 142 0.50 28 142 0.23 0.19 30 142 0.18 0.12 0.41 0.34 0.57 34 142 0.18 48 142 0.26 66 142 0.23 13 143 0.24 DEG CHN IND %TW LOCATION

=========

EXT EXT CAL # LEG PROBE 86 79 78 86 72 86 97 92 67 90 100 72 72 93 81 81 52 101 66 48 90 99 55 97 120 31 87 94 87 90 54 75 76 61 79 53 71 91 105 66 101 149 104 60 74 57 83 97 103 98 49 86 50 101 P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAT P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 MAI P 6 SAI P 6 MAI P 6 SAI P 6 SAI P 6 SAI 02H 02H 02H 01H 02H 03H 03H 02H 07H 01H 06H 02H 01H 01H 01H 05H 02H 03H 04H 04H 05H 02H 02H 02H 02H 02H 02H 02H 03H 07H 03H 02H 02H 02H 02H 02H 02H 02H 01H 04H 02H 02H 02H 03H 04H 02H 02H 03H 03H 04H 02H 01H 02H 03H

+0.93

+0.62

+0.55

+0.75

+0.89

-0.38

+0.74

+0.62

+0.27

-0.61

+0.81

+0.93

-0.85

+0.58

+0.69

+0.75

+0.86

-0.22

+0.76

+0.39

-0.30

+0.72

+0.75

+0.26

-0.62

-0.59

+0.79

+0.79

+0.66

+0.66

+0.88

-0.05

+0.46

-0.45

+0.86

+0.72

+0.98

-0.10

+0.85

-0.21

+0.94

-0.33

+0.77

+0.82

+0.89

-0.52

+0.48

+0.87

-0.42

+0.53

-0.47

-0.85

-0.62

+1.00 02H 02H 02H 01H 02H 03H 03H 02H 07H 01H 06H 02H 01H 01H 01H 05H 02H 03H 04H 04H 05H 02H 02H 02H 02H 02H 02H 02H 03H DCB 03H 02H 02H 02H 02H 02H 02H 02H 01H 04H 02H 02H 02H 03H 04H 02H 02H 03H 03H 04H 02H 01H 02H 03H 02H 02H 02H 01H 02H 03H 03H 02H 07H 01H 06H 02H 01H 01H 01H 05H 02H 03H 04H 04H 05H 02H 02H 02H 02H 02H 02H 02H 03H 07H 03H 02H 02H 02H 02H 02H 02H 02H 01H 04H 02H 02H 02H 03H 04H 02H 02H 03H 03H 04H 02H 01H 02H 03H 140 140 143 123 123 123 123 123 139 143 123 139 140 140 143 123 139 139 139 139 139 140 123 139 139 171 139 140 139 158 139 139 139 139 139 119 140 140 140 123 139 139 139 139 139 139 139 139 139 139 139 140 140 139 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacmoent 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 22 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS 15 143 0.25 47 143 0.31 0.15 0.27 49 143 0.22 0.15 4

144 0.28 10 144 0.17 12 144 0.48 0.21 20 144 0.21 0.18 22 144 0.49 0.29 0.37 0.15 42 144 0.13 50 144 0.36 60 144 0.13 62 144 0.21 7

145 0.26 47 145 0.38 0.12 69 145 0.27 75 145 0.17 12 146 0.31 16 146 0.43 0.41 7

147 0.39 0.44 0.54 9

147 0.15 49 147 0.12 0.23 6

148 0.27 0.40 0.16 0.47 50 148 0.36 62 148 0.38 64 148 0.19 82 148 0.40 5

149 0.54 21 149 0.34 41 149 0.42 43 149 0.18 2

150 0.46 0.26 8

150 0.34 12 150 0.38 14 150 0.22 18 150 0.31 0.12 0.24 DEG CHN 63 P 6 91 P 6 50 P 6 76 P 6 88 P 6 87 P 6 97 P 6 81 P 6 103 P 6 71 P 6 114 P 6 84 P 6 96 P 6 85 P 6 109 P 6 76 P 6 75 P 6 85 P 6 74 P 6 49 P 6 99 P 6 101 P 6 84 P 6 93 P 6 86 P 6 78 P 6 111 P 6 107 P 6 104 P 6 109 P 6 103 P 6 90 P 6 90 P 6 73 P 6 101 P 6 86 P 6 91 P 6 279 P 6 93 P 6 93 P 6 56 P 6 112 P 6 102 P 6 280 P 6 101 P 6 91 P 6 94 P 6 116 P 6 81 P 6 98 P 6 92 P 6 83 P 6 92 P 6 100 P 6 IND %TW SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAr SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI LOCATION 02H

+0.87 02H

-0.28 03H

-0.27 05H

+0.70 02H

+0.09 03H

-0.60 03H

+0.66 02H

+0.78 02H

+0.02 02H

-0.83 03H

-0.24 03H

+0.91 03H

+0.84 04H

+0.85 05H

-0.20 05H

+0.48 02H

+0.79 02H

-0.33 03H

-0.39 02H

+0.58 07C

+0.91 02H

+0.76 02H

-0.18 04H

-0.29 02H

+0.46 05H

+0.93 02H

+0.95 04H

+0.81 02H

-0.77 05H

+0.73 07C

+0.36 04H

+0.70 01H

+0.54 02H

+0.94 02H

+0.61 03H

+0.37 03H

-0.23 06H

+0.37 02H

+0.91 02H

+0.73 02H

+0.57 01H

+0.83 03H

+0.33 02H

-0.48 03H

+0.60 02H

+0.93 05H

+0.74 07H

+0.28 05H

-0.41 05H

-0.45 02H

-0.26 02H

+0.79 03H

+0.91 03H

-0.21 EXT 02H 02H 03H 05H 02H 03H 03H 02H 02H 02H 03H 03H 03H 04H 05H 05H 02H 02H 03H 02H 07C 02H 02H 04H 02H 05H 02H 04H 02H 05H 07C 04H 01H 02H 02H 03H 03H 06H 02H 02H 02H 01H 03H 02H 03H 02H 05H 07H 05H 05H 02H 02H 03H 03H EXT 02H 02H 03H 05H 02H 03H 03H 02H 02H 02H 03H 03H 03H 04H 05H 05H 02H 02H 03H 02H 07C 02H 02H 04H 02H 05H 02H 04H 02H 05H 07C 04H 01H 02H 02H 03H 03H 06H 02H 02H 02H 01H 03H 02H 03H 02H 05H DHT 05H 05H 02H 02H 03H 03H CAL 139 140 140 140 140 140 126 126 139 139 139 139 139 139 139 139 139 140 140 140 158 139 139 140 139 139 139 139 126 126 74 126 139 139 126 126 126 126 139 140 140 143 126 139 139 139 126 126 126 139 139 139 139 139 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5602P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Page 23 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION 32 150 0.29 0.19 0.46 52 150 0.14 0.24 56 150 0.32 82 150 0.19 5

151 0.25 0.17 7

151 0.65 0.42 0.26 15 151 0.31 0.18 31 151 0.31 49 151 0.16 8

152 0.18 0.11 0.50 0.50 28 152 0.49 38 152 0.12 9

153 0.41 0.31 23 153 0.31 47 153 0.39 0.24 59 153 0.23 0.17 10 154 0.34 0.45 12 154 0.27 0.22 32 154 0.19 0.22 34 154 0.24 52 154 0.45 5

155 0.30 7

155 0.28 0.27 0.45 0.57 13 155 0.40 19 155 0.49 21 155 0.26 41 155 0.75 0.21 43 155 0.18 47 155 0.18 49 155 0.31 0.14 0.15 4

156 0.44 0.17 83 P 79 P

105 P 67 P

77 P

98 P

105 P 276 P 78 P

93 P

105 P 108 P 83 P

80 P

108 P 76 P

98 P

76 P

108 P 106 P 83 P

63 P

94 P

117 P 110 P 108 P 88 P

101 P 92 P

94 P

102 P 102 P 67 P

109 P 100 P 83 P

109 P 89 P 92 P 97 P

89 P 104 P 97 P

113 P 97 P

99 P

77 P

71 P

73 P

107 P 77 P

63 P

94 P

78 P

6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 MAI 6 MAI 6 SAI 6 SAI 6 MAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 SAI 6 MAI 6 SAI 6 SAT 6 SAI 6 SAI 6 SAI 6 MAI 6 SAI 6 SAI 6 SAI 6 SAI 6 MAI 6 SAI 6 SAI 6 MAI 6 MAI 6 SAI 6 SAI 6 MAI 6 MAI 6 MAI 6 MAI 6 MAI 6 MAI 6 SAI 6 MAI 6 SAI 6 SAI 6 SAI 6 SAI 03H

-0.51 03H

+0.60 05H

-0.57 02H

+0.49 04H

+0.66 02H

+0.51 03H

+0.68 02H

+0.84 03H

-0.67 02H

+0.65 03H

+0.34 04H

-0.33 04H

+0.73 05H

+0.86 03H

+0.63 04H

+0.69 02H

+0.05 02H

-0.85 03H

+0.03 05H

+0.06 03H

+0.58 03H

-0.51 02H

+0.03 04H

-0.94 02H

+0.66 04H

-0.18 04H

+0.55 02H

+0.71 04H

+0.54 02H

-0.61 03H

+0.36 02H

-0.31 02H

+0.65 02H

-0.26 02H

+0.84 02H

-0.75 02H

+0.78 02H

+0.80 02H

+0.41 03H

+0.48 04H

+0.39 05H

+0.43 03H

-0.53 02H

-0.43 02H

+0.76 02H

+0.34 04H

+0.51 02H

-0.81 TSH

+4.91 02H

+0.52 02H

-0.52 04H

+0.37 05H

+0.44 05H

-0.32 EXT EXT 03H 03H 03H 03H 05H 05H 02H 02H 04H 04H 02H 02H 03H 03H 02H 02H 03H 03H 02H 02H 03H 03H 04H 04H 04H 04H 05H 05H 03H 03H 04H 04H 02H 02H 02H 02H 03H 03H 05H 05H 03H 03H 03H 03H 02H 02H 04H 04H 02H 02H 04H 04H 04H 04H 02H 02H 04H 04H 02H 02H 03H 03H 02H 02H 02H 02H 02H 02H 02H 02H 02H 02H 02H 02H 02H 02H 02H 02H 03H 03H 04H 04H 05H 05H 03H 03H 02H 02H 02H 02H 02H 02H 04H 04H 02H 02H TSH TSH 02H 02H 02H 02H 04H 04H 05H 05H 05H 05H CAL #

139 139 139 139 139 139 143 126 126 126 126 126 139 139 139 139 126 126 126 126 139 119 126 126 134 139 139 139 139 126 126 134 134 134 134 134 134 126 126 126 126 126 134 134 134 165 134 134 134 134 134 134 126 126 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 24 of 24 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS 0.30 16 156 0.29 28 156 0.48 52 156 0.20 7

157 0.56 0.36 0.19 0.56 0.46 8

158 0.17 0.23 12 158 0.26 0.42 28 158 0.41 7

159 0.33 0.23 0.18 9

159 0.26 11 159 0.74 0.14 0.30 0.85 0.10 0.11 43 159 0.25 12 160 0.24 0.32 30 160 0.27 34 160 0.65 0.43 1

161 0.20 0.52 0.20 5

161 0.37 7

161 0.26 0.24 0.42 0.22 9

161 0.29 15 161 0.48 17 161 0.16 0.25 0.14 43 161 0.85 12 162 0.20 24 162 0.17 16 164 0.30 7

165 0.25 9

165 0.10 DEG 108 86 88 106 93 118 64 99 98 86 96 53 78 75 112 69 80 118 94 78 106 101 59 77 84 92 111 77 105 93 61 101 114 114 90 92 103 84 101 103 100 75 84 105 81 97 98 81 71 CHN IND %TW LOCATION EXT EXT CAL # LEG P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 P6 SAI MAI MAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI SAI MM SAI SAI MAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI MAI SAI SAI SAI SAI SAI SAI SAI SAI SAI 07H

-0.43 02H

-0.49 02H

+0.73 03H

+0.89 02H

+0.53 03H

-0.79 03H

+0.51 04H

+0.59 05H

-0.77 03H

-0.80 04H

+0.86 02H

-0.38 02H

+0.73 02H

+0.26 03H

+0.84 04H

-0.48 06H

+0.85 03H

-0.36 02H

+0.30 03H

+0.32 03H

+0.87 04H

-0.01 05H

+0.51 05H

-0.68 02H

-0.66 02H

-0.21 02H

+0.85 02H

+0.28 02H

-0.50 02H

+0.43 07C

+0.32 03H

+0.69 04H

-0.88 02H

-0.42 02H

+0.32 02H

+0.78 03H

-0.69 05H

-0.39 03H

+0.68 02H

+0.28 02H

-0.81 02H

+0.23 04H

-0.83 02H

+0.29 04H

+0.26 02H

+0.24 02H

+0.76 03H

-0.24 03H

+0.85 07H 02H 02H 03H 02H 03H 03H 04H 05H 03H 04H 02H 02H 02H 03H 04H 06H 03H 02H 03H 03H 04H 05H 05H 02H 02H 02H 02H 02H 02H 07H 03H 04H 02H 02H 02H 03H 05H 03H 02H 02H 02H 04H 02H 04H 02H 02H 03H 03H DHT 02H 02H 03H 02H 03H 03H 04H 05H 03H 04H 02H 02H 02H 03H 04H 06H 03H 02H 03H 03H 04H 05H 05H 02H 02H 02H 02H 02H 02H 07C 03H 04H 02H 02H 02H 03H 05H 03H 02H 02H 02H 04H 02H 04H 02H 02H 03H 03H 126 134 134 134 126 126 126 126 126 126 126 134 134 134 126 126 126 126 134 134 134 134 134 134 134 134 134 134 134 134 84 126 126 126 126 126 126 126 126 134 134 134 134 134 134 134 134 126 126 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5601P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P 5803P Total Tubes

835 Total Records: 1291

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 5 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 4 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 37 5

0.31 52 8

0.36 47 21 0.29 48 22 0.24 54 22 0.38 87 23 0.43 96 24 0.36 0.58 0.36 0.48 45 25 0.35 96 26 0.49 0.34 99 27 0.43 101 27 0.68 100 28 0.81 95 29 0.50 43 33 0.26 64 34 0.46 96 34 0.92 50 36 0.30 95 41 0.38 97 41 0.87 0.70 43 47 0.50 126 48 0.50 93 49 0.39 68 50 0.48 57 51 0.95 41 55 0.36 131 55 0.73 130 58 0.48 132 58 0.69 0.50 49 59 0.46 131 59 0.81 133 59 0.50 134 60 0.58 43 61 0.52 135 63 0.52 39 65 0.38 137 67 1.01 34 68 0.41 1.18 0.80 36 68 0.52 39 69 0.62 0.61 41 69 0.36 36 70 0.82 0.43 46 70 0.82 48 70 0.46 35 71 0.72 74 146 124 43 98 111 146 60 107 128 67 33 29 143 115 114 78 100 63 109 99 114 102 121 126 48 101 122 83 61 115 107 71 106 140 64 70 91 86 69 25 119 36 98 112 53 121 148 156 130 146 141 91 113 P 2 TWD 23 P 2 TWD 25 P 2 TWD 23 P 2 TWD 21 P 2 TWD 26 P 2 TWD 21 P 2 TWD 21 P 2 TWD 27 P 2 TWD 20 P 2 TWD 24 P 2 TWD 25 P 2 TWD 25 P 2 TWD 20 P 2 TWD 22 P 2 TWD 29 P 2 TWD 31 P 2 TWD 25 P 2 TWD 20 P 2 TWD 29 P 2 TWD 32 P 2 TWD 21 P 2 TWD 20 P 2 TWD 31 P 2 TWD 28 P 2 TWD 26 P 2 TWD 23 P 2 TWD 24 P 2 TWD 22 P 2 TWD 32 P 2 TWD 20 P 2 TWD 26 P 2 TWD 23 P 2 TWD 25 P 2 TWD 21 P 2 TWD 22 P 2 TWD 28 P 2 TWD 21 P 2 TWD 23 P 2 TWD 25 P 2 TWD 21 P 2 TWD 20 P 2 TWD 31 P 2 TWD 21 P 2 TWD 35 P 2 TWD 30 P 2 TWD 26 P 2 TWD 27 P 2 TWD 27 P 2 TWD 20 P 2 TWD 30 P 2 TWD 22 P 2 TWD 30 P 2 TWD 24 P 2 TWD 29 02H 01C VS3 VS3 VS3 VS2 07H 08H VS4 DCB VS3 VS4 DHT 08H DCT DCT DCT VS3 VS4 VS2 VS3 VS2 VS2 VS4 VS3 DHT VS2 VS3 VS3 VS3 DCB DCT VS1 DCB VS3 DCT DCB DHB VS3 DHT VS3 DHT DHB DCB DCT VS3 VS3 DHT 07C DCB DHB VS3 VS3 DCB

+0.80

-0.98

-0.70

+0.74

-0.66

+0.83

-0.22

-0.92

+0.79

+0.00

-0.88

+0.16

+0.00

-0.26

+0.00

+0.00

+0.00

+0.93

-0.24

-0.41

+0.76

+0.97

+0.63

+0.55

-0.78

+0.25

-0.87

-1.02

-0.80

+0.95

+0.00

+0.00

-0.80

+0.21

-0.89

+0.00

+0.00

+0.76

+0.67

+0.00

-1.01

-0.06

+0.00

+0.16

-0.08

+0.57

+0.51

+0.00

-0.89

+0.00

+0.00

+0.84

+0.68

+0.00 TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEC TEC TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEN TEH TEH TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEH TEH TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH 10 10 17 17 18 48 50 50 50 50 17 50 50 49 50 50 50 25 24 49 25 52 51 51 4

52 54 7

7 14 58 55 58 58 12 57 58 58 13 58 10 58 10 10 10 11 12 12 11 12 12 12 11 12 HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD HOT HOT COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT PROBE 60 OUL 60OUL 600UL 600UL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL

Framatome ANP Inc.

1J22/2005 14:30 Attacbment 5 CSI-NDE-05-020 Page 2 of 4 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS 0.51 37 71 0.83 45 71 0.69 0.49 97 71 0.62 48 72 0.48 43 75 0.43 45 75 0.42 44 76 1.12 46 76 0.38 52 76 0.67 54 76 0.49 0.45 56 76 0.88 0.46 55 77 1.02 107 77 0.33 52 78 0.58 0.39 1.46 54 78 0.76 0.76 88 78 0.64 96 78 0.40 0.78 0.33 51 79 0.51 0.56 50 80 0.37 0.74 52 80 0.44 0.64 0.47 1.47 60 80 0.45 51 81 0.63 53 81 1.25 48 82 0.68 50 82 0.42 98 82 0.44 51 83 0.78 87 83 0.35 89 83 1.75 48 84 1.69 1.08 50 84 1.02 52 84 1.88 57 85 0.57 54 86 0.42 88 86 0.58 53 87 0.42 55 87 1.20 52 88 0.87 0.52 DEG 52 84 82 145 55 91 75 114 94 70 78 152 141 103 145 148 26 127 139 144 132 84 34 43 87 31 94 150 138 108 88 145 126 100 87 129 26 37 74 22 100 104 112 110 103 118 111 125 43 64 98 93 108 79 CNN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWID TWD TWD TWD TWD TWD TWD TWD TWD

%TW 24 30 28 24 28 24 22 22 34 21 28 24 23 32 23 31 22 25 21 29 28 28 25 25 33 22 23 24 20 29 21 26 22 35 22 27 33 27 21 26 29 23 32 36 32 33 37 25 21 27 23 34 30 24 LOCATION D=T

+0.00 DHT

+0.00 DCT

+0.00 VS3

-0.77 VS4

+0.64 VS3

-0.74 DCB

+0.34 DCB

+0.00 DHB

+0.00 DHB

+0.00 VS3

+0.75 VS3

-0.81 VS3

+0.77 VS3

+0.68 VS3

-0.81 DCB

+0.00 04H

-0.42 DCT

+0.00 DCB

+0.00 VS3

+0.85 DCB

+0.00 DHB

+0.00 VS2

+0.76 VS4

+0.74 VS2

-0.76 VS3

+0.36 DCB

+0.00 DHT

+0.00 DCT

+0.00 DHB

+0.00 DCT

+0.00 VS3

+0.92 VS3

-0.63 DHB

+0.00 DCB

+0.00 DCB

+0.00 DHT

+0.00 DHT

+0.00 DCB

+0.00 VS3

+0.91 DCT

+0.00 VS3

-0.93 VS3

-0.87 DHB

+0.00 DCT

+0.00 DCT

+0.00 DCT

-0.25 DCB

+0.00 DCT

+0.00 VS3

+0.74 DCB

+0.00 DCT

+0.00 VS3

+0.89 DCB

+0.39 EXT TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEH TEH TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC EXT TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEN TEH TEH TEH TEH TEH TEC TEH TEC TEC TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH CAL #

12 11 11 11 42 11 12 11 12 11 12 11 11 12 12 5

39 6

6 6

5 5

44 39 39 39 5

5 6

6 5

5 5

5 5

6 5

5 6

39 6

39 41 5

5 6

5 5

5 38 3

4 4

4 LEG HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT COLD COLD COLD COLD NOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT COLD COLD HOT HOT NOT HOT HOT HOT COLD HOT HOT HOT HOT PROBE 60_OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 5 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 3 of 4 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 54 88 0.48 62 88 0.42 51 89 0.73 54 90 0.43 56 90 0.52 44 92 0.51 48 92 0.45 54 92 0.75 60 92 0.40 43 93 0.60 1.05 42 94 0.99 46 94 0.82 1.03 50 94 0.47 51 95 0.37 35 97 0.59 71 97 0.62 93 97 0.39 34 98 0.47 0.78 0.60 0.51 1.02 33 99 0.42 37 99 0.69 0.64 0.91 0.54 34 100 0.62 0.88 94 100 0.86 0.69 33 101 0.37 35 101 0.52 47 101 0.36 93 101 0.55 135 101 0.90 34 102 0.49 29 103 0.36 34 104 0.46 40 104 0.55 47 105 0.39 32 106 0.48 50 106 0.45 34 108 0.47 96 108 0.66 97 109 0.28 89 111 0.66 126 112 0.54 96 114 1.10 1.01 0.68 0.44 88 92 117 63 57 104 125 97 70 128 51 77 123 130 115 144 137 149 144 78 127 123 97 57 31 40 67 130 48 76 78 119 54 139 69 46 94 82 73 29 27 151 19 69 93 61 119 113 101 36 127 99 69 140 P2 P2 P2 P2 P2 P2 P2 P2 P,2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD T.WD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 22 21 28 21 23 23 21 28 20 27 32 32 30 32 24 21 25 27 20 24 29 27 25 27 21 27 26 31 24 27 32 31 28 21 25 20 25 29 24 20 24 25 21 22 23 23 30 20 29 24 36 35 29 22 VS3

+0.90 TEC VS3

-0.77 TEC DHB

+0.00 TEC DCB

+0.00 TEC DCT

+0.02 TEC DHB

+0.00 TEC DHB

+0.00 TEC VS3

+0.70 TEC VS3

+0.78 TEC DCB

+0.00 TEC DHT

+0.00 TEC DCB

+0.63 TEC VS3

-0.94 TEC DCB

+0.00 TEC VS3

-0.92 TEC 07H

+0.87 TEC DHB

+0.00 TEC VS4

-0.73 TEC VS2

+0.68 TEH VS3

+0.83 TEC VS3

-0.90 TEC DHB

+0.00 TEC DCB

+0.09 TEC DHT

-0.25 TEC DCB

+0.00 TEC DCB

+0.00 TEC VS3

-0.07 TEC VS3

-0.69 TEC DHB

+0.00 TEC DHB

+0.27 TEH DHT

-0.16 TEH VS2

-0.79 TEH VS2

+0.79 TEH DCT

+0.00 TEH VS3

-0.99 TEH VS3

+0.86 TEH VS2

-0.94 TEH VS1

+0.74 TEH VS3

+0.64 TEH VS3

-0.81 TEH VS3

-0.96 TEH VS3

-0.87 TEH VS3

+0.77 TEH VS3

-1.01 TEH VS3

+0.91 TEH VS3

-0.89 TEH VS2

-0.86 TEH VS2

-0.97 TEH VS4

-0.71 TEH VS1

-0.84 TEH VS2

-0.81 TEH VS2

-0.14 TEH VS2

+0.52 TER VS3

-0.89 TEH TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEN TEN TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 3

HOT 4

HOT 4

HOT 4

HOT 3

HOT 3

HOT 3

HOT 4

HOT 3

HOT 3

HOT 3

HOT 3

HOT 3

HOT 3

HOT 3

HOT 3

HOT 4

HOT 3

HOT 35 COLD 3

HOT 3

HOT 3

HOT 3

HOT 3

HOT 4

HOT 4

HOT 4

HOT 4

HOT 4

HOT 16 COLD 16 COLD 26 COLD 26 COLD 17 COLD 16 COLD 16 COLD 26 COLD 58 COLD 16 COLD 17 COLD 17 COLD 16 COLD 17 COLD 18 COLD 19 COLD 19 COLD 28 COLD 28 COLD 35 COLD 36 COLD 35 COLD 35 COLD 35 COLD 35 COLD PROBE 60=OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Page 4 of 4 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS 0.74 0.59 89 117 0.63 88 120 0.69 96 120 0.38 51 121 0.33 54 124 0.87 94 124 0.39 55 125 0.90 94 126 0.39 95 131 0.38 60 134 0.43 89 135 0.37 94 136 0.39 108 136 0.60 35 137 0.34 70 138 0.56 55 139 0.88 92 142 0.36 95 143 0.60 82 150 0.45 64 152 0.39 42 162 0.41 27 163 0.49 DEG 69 147 52 39 152 54 25 61 113 80 83 74 114 132 126 102 133 85 99 148 152 92 98 62 CHN P=2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 30 VS3

+0.18 27 VS4

+0.89 28 VS2

-0.85 29 VS4

-0.76 20 VS3

-0.89 21 VS3

+0.71 30 VS3

+0.00 20 VS2

-0.80 31 VS3

-0.99 21 VS2

-0.98 21 VS2

-0.51 23 VS3

-0.69 22 DCB

+0.00 21 VS4

+0.91 28 02C

-0.85 21 VS3

-0.87 26 VS3

+0.91 31 VS3

+0.98 21 VS2

+0.62 25 VS2

-0.65 21 VS3

+0.87 21 VS2

-0.53 20 01C

+0.91 22 VS3

+0.61 EXT TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEC TEC TEC TEH TEH TEH TEC TEC TEC EXT TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEH TEH TEC TEC TEC TEN TEH TEH CAL #

35 35 36 33 33 22 20 34 20 33 33 23 31 32 31 23 23 23 31 27 27 29 32 33 LEG COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD COLD COLD HOT HOT HOT COLD COLD COLD HOT HOT HOT PROBE 60 OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 600UL 60OUL Total Tubes

144 Total Records: 186

Framatome ANP Inc.

1/22/2005 14:30 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 1

3 0.11 32 4 0.25 34 4 0.24 31 5 0.35 60 10 0.08 62 12 0.17 39 15 0.09 55 15 0.07 40 18 0.17 62 18 0.16 46 22 0.14 48 22 0.13 93 23 0.24 88 24 0.32 0.19 92 24 0.30 94 24 0.25 96 24 0.26 81 25 0.30 91 25 0.31 95 25 0.35 0.08 44 26 0.11 94 26 0.32 0.28 0.37 91 27 0.30 95 27 0.20 97 27 0.21 34 28 0.08 92 28 0.16 0.13 98 28 0.17 100 28 0.21 53 29 0.17 67 29 0.17 89 29 0.27 91 29 0.28 95 29 0.19 0.13 42 30 0.24 92 30 0.30 0.28 0.15 96 30 0.21 104 30 0.19 107 31 0.24 0.28 108 32 0.25 27 33 0.12 105 33 0.28 30 34 0.18 82 34 0.28 92 34 0.18 DEG 161 140 153 48 155 109 171 168 55 93 33 51 93 58 140 58 72 135 63 122 130 16 15 110 149 133 98 81 40 163 30 121 110 120 119 136 11 98 49 35 28 139 152 121 26 56 51 70 149 33 78 165 87 63 CHN IND %TW LOCATION EXT P 2 TWD 8 01C

-0.96 07C P 2 TWD 13 02H

+0.99 TEH P 2 TWD 14 02H

-0.99 TEH P 2 TWD 18 01C

-0.93 TEC P 2 TWD 9 02H

+0.88 TEC P 2 TWD 15 01H

-0.94 TEC P 2 TWD 9 04H

+0.80 TEC P 2 TWD 8 04H

+0.86 TEC P 2 TWD 15 VS3

-0.96 TEC P 2 TWD 14 VS3

-0.87 TEC P 2 TWD 14 VS3

+0.97 TEC P 2 TWD 14 VS3

-1.00 TEC P 2 TWD 13 DCT

+0.00 TEH P 2 TWD 17 VS2

+0.89 TEH P 2 TWD 12 VS3

+0.58 TEH P 2 TWD 17 DCB

+0.00 TEH P 2 TWD 16 DCB

+0.00 TEH P 2 TWD 9 06H

+0.87 TEH P 2 TWD 18 DCT

+0.00 TEH P 2 TWD 18 DCT

-0.12 TEH P 2 TWD 19 VS4

-0.89 TEH P 2 TWD 3 05H

+0.67 TEH P 2 TWD 12 VS3

-0.88 TEC P 2 TWD 17 VS2

-1.01 TEH P 2 TWD 15 VS2

+0.95 TEH P 2 TWD 18 DHT

+0.00 TEH P 2 TWD 17 VS4

-0.99 TEH P 2 TWD 12 VS4

-0.93 TEH P 2 TWD 14 VS3

-0.93 TEH P 2 TWD 8 VS3

-1.13 TEC P 2 TWD 12 VS2

-0.59 TEH P 2 TWD 9 VS2

+0.83 TEH P 2 TWD 10 VS2

+0.81 TEH P 2 TWD 14 02H

+0.94 TEH P 2 TWD 17 VS3

+0.92 TEC P 2 TWD 17 VS2

-0.69 TEC P 2 TWD 17 DHT

+0.00 TEH P 2 TWD 15 DCT

+0.00 TEH P 2 TWD 13 VS2

+0.81 TEH P 2 TWD 10 06H

+0.95 TEH P 2 TWD 19 VS3

-0.86 TEC P 2 TWD 16 VS2

+0.65 TEH P 2 TWD 16 VS4

-0.91 TEH P 2 TWD 9 07H

+0.88 TEH P 2 TWD 13 VS4

+0.40 TEH P 2 TWD 10 VS3

-1.33 TEH P 2 TWD 15 02H

+0.76 TEH P 2 TWD 16 04C

-1.02 TEH P 2 TWD 15 02H

-0.86 TEH P 2 TWD 11 VS3

+0.76 TEC P 2 TWD 10 02H

-0.12 TEH P 2 TWD 19 VS3

-0.98 TEC P 2 TWD 10 VS4

-0.61 TEH P 2 TWD 11 08H

+1.02 TEH EXT TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEH TEC TEC CAL # LEG 46 COLD 47 COLD 48 COLD 9

HOT 9

HOT 10 HOT 14 HOT 14 HOT 14 HOT 14 HOT 18 HOT 17 HOT 47 COLD 49 COLD 49 COLD 49 COLD 50 COLD 50 COLD 50 COLD 49 COLD 49 COLD 49 COLD 19 HOT 49 COLD 49 COLD 49 COLD 49 COLD 49 COLD 50 COLD 20 HOT 50 COLD 50 COLD 49 COLD 50 COLD 19 HOT 19 HOT 50 COLD 49 COLD 50 COLD 50 COLD 20 HOT 49 COLD 49 COLD 49 COLD 49 COLD 49 COLD 49 COLD 49 COLD 49 COLD 25 HOT 49 COLD 24 HOT 50 COLD 49 COLD PROBE 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL 600UL

Framatome ANP Inc.

1/22/2005 14:30 Attaclheznt 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 2 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 96 34 0.24 108 34 0.15 94 36 0.25 96 36 0.35 100 36 0.29 87 37 0.13 0.17 68 38 0.21 92 38 0.22 112 38 0.23 116 38 0.33 81 39 0.23 83 39 0.15 0.19 117 39 0.29 81 41 0.33 85 41 0.16 95 41 0.22 97 41 0.36 0.22 116 42 0.15 121 43 0.19 46 44 0.13 94 44 0.20 0.25 120 44 0.17 29 45 0.29 123 45 0.32 62 46 0.27 124 46 0.15 125 47 0.31 86 48 0.24 126 48 0.14 68 50 0.28 107 51 0.13 113 51 0.35 121 51 0.27 127 53 0.30 0.30 0.18 94 54 0.31 83 55 0.21 0.27 95 55 0.24 131 55 0.20 28 56 0.15 81 57 0.29 121 57 0.14 48 58 0.10 49 59 0.25 127 59 0.35 129 59 0.27 102 60 0.21 132 60 0.40 86 100 148 106 12 20 167 90 102 97 52 22 105 14 44 86 152 63 57 138 114 10 20 162 52 138 69 41 50 29 108 47 149 45 65 104 161 75 132 156 162 60 43 48 103 15 56 63 143 25 220 14 99 101 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD T.D TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 15 10 15 19 17 9

11 14 13 14 18 14 10 12 16 18 10 13 19 14 10 12 9

12 15 11 17 17 16 10 17 14 9

15 10 19 16 18 17 12 17 13 16 14 10 11 17 11 7

14 19 16 13 18 VS3

+0.32 TEH 03C

-0.88 TEH VS2

-0.95 TEH VS2

-0.79 TEH 08H

+0.89 TEH VS2

-0.65 TEH VS2

+0.75 TEH VS2

-0.54 TEH 08H

-0.78 TEH VS4

-0.87 TEH VS3

+0.87 TEH VS4

+0.63 TEH VS2

+0.65 TEH VS4

+0.75 TEH DCT

-0.25 TEH VS3

-0.95 TEH VS4

-0.77 TEH VS4

+0.89 TEH VS3

-0.97 TEH VS4

-0.81 TEH 05C

+0.86 TEH DCT

+0.00 TEH VS3

+0.82 TEH VS2

-0.69 TEH VS4

-1.20 TEH 04H

+0.92 TEH VS3

-0.62 TEH DHT

+0.00 TEH VS2

+0.85 TEH DCT

+0.00 TEH 09C

+0.88 TEH VS2

+1.08 TEH 07H

-1.00 TEH VS2

+0.85 TEH 07C

+0.95 TEH 02H

-0.08 TEH 05H

+0.89 TEH DCB

-0.16 TEH 07H

+0.85 TEH 06H

-0.56 TEH VS3

+0.83 TEH VS4

+0.64 TEH VS3

-0.73 TEH DHB

+0.30 TEH 05H

-0.97 TEH VS3

-0.82 TEH VS4

-0.71 TEH VS1

+0.90 TEH VS3

+0.87 TEH VS3

+0.85 TEH 09H

+0.96 TEH DCT

+0.25 TEH VS4

-0.66 TEH DCT

+0.00 TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 49 52 51 52 52 51 51 3

52 52 52 51 51 51 52 51 51 52 51 51 52 51 4

52 52 51 3

52 3

52 52 51 52 7

54 53 53 53 53 53 55 56 56 55 58 15 55 54 13 12 55 56 56 57 COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60=OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 600UL 600UL 60O0UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 3 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 134 60 0.26 61 P 2 TWD 13 DCT

+0.00 TEN TEC 58 COLD 60===L 133 61 0.45 146 P 2 TWD 19 DHT

-0.25 TEH TEC 58 COLD 600UL 24 62 0.28 49 P 2 TWD 17 VS3

+0.82 TEH TEC 13 COLD 600UL 98 62 0.10 41 P 2 TWD 7 VS2

-0.89 TEH TEC 55 COLD 600UL 106 62 0.20 136 P 2 TWD 12 VS1

+0.12 TEH TEC 55 COLD 600UL 53 63 0.17 73 P 2 TWD 12 VS3

-0.61 TEH TEC 11 COLD 600UL 22 64 0.17 93 P 2 TWD 11 VS3

+0.72 TEH TEC 10 COLD 600UL 25 65 0.22 36 P 2 TWD 15 VS3

+0.68 TEH TEC 11 COLD 600uL 46 66 0.20 107 P 2 TWD 14 VS3

+0.79 TEH TEC 11 COLD 600UL 96 66 0.23 98 P 2 TWD 14 VS4

+0.88 TEH TEC 56 COLD 600UL 36 68 0.32 29 P 2 TWD 19 VS3

-0.80 TEH TEC 11 COLD 600UL 38 68 0.29 159 P 2 TWD 16 VS3

-0.78 TEH TEC 10 COLD 600UL 46 68 0.16 124 P 2 TWD 10 VS3

+0.93 TEH TEC 10 COLD 600UL 0.11 7

P 2 TWD 7 DCT

+0.00 TEH TEC 10 COLD 600UL 64 68 0.18 96 P 2 TWD 11 VS2

+0.79 TEH TEC 10 COLD 600UL 134 68 0.34 143 P 2 TWD 16 DHB

+0.00 TEH TEC 58 COLD 600UL 35 69 0.35 140 P 2 TWD 19 DCT

-0.21 TEC TEH 12 HOT 600UL 39 69 0.17 136 P 2 TWD 11 VS3

-0.61 TEC TEH 12 HOT 600UL 50 72 0.27 104 P 2 TWD 16 VS3

-0.70 TEC TEH 12 HOT 600UL 48 74 0.13 94 P 2 TWD 9 DHB

+0.11 TEC TEH 12 HOT 600UL 52 74 0.26 165 P 2 TWD 16 VS3

+0.97 TEC TEH 12 HOT 600UL 103 75 0.22 51 P 2 TWD 12 VS2

+1.00 TEH TEC 43 COLD 600UL 137 75 0.23 147 P 2 TWD 11 05H

.0.90 TEH TEC 57 COLD 600UL 53 77 0.24 111 P 2 TWD 15 DCB

+0.00 TEC TEH 6 HOT 600UL 57 77 0.33 130 P 2 TWD 18 VS3

-0.87 TEC TEH 6 HOT 600UL 0.16 130 P 2 TWD 11 VS3

+0.71 TEC TEH 6 HOT 600UL 0.31 158 P 2 TWD 18 DCB

+0.51 TEC TEH 6 HOT 600UL 52 78 0.46 58 P 2 TWD 14 VS3

-0.96 TEC TEH 6 HOT 600UL 54 78 0.29 102 P 2 TWD 17 DCT

+0.00 TEC TEH 5 HOT 600UL 88 78 0.31 104 P 2 TWD 15 VS2

-0.90 TEH TEC 44 COLD 600UL 96 78 0.17 28 P 2 TWD 15 DCT

-0.25 TEH TEC 39 COLD 600UL 59 79 0.30 87 P 2 TWD 17 DCB

+0.00 TEC TEH 6 HOT 600UL 61 79 0.26 112 P 2 TWD 15 DCB

+0.00 TEC TEH 5 HOT 600UL 63 79 0.25 136 P 2 TWD 15 DCB

+0.00 TEC TEH 5 HOT 600UL 132 80 0.18 153 P 2 TWD 9 VS1

+0.62 TEH TEC 57 COLD 600UL 51 81 0.31 141 P 2 TWD 17 DCT

+0.00 TEC TEH 6

HOT 600UL 53 81 0.30 26 P 2 TWD 17 DCT

+0.00 TEC TEH 5 HOT 600UL 116 82 0.16 113 P 2 TWD 8 VS4

-0.91 TEH TEC 41 COLD 600UL 51 83 0.33 32 P 2 TWD 18 DCB

+0.00 TEC TEH 6 HOT 600UL 53 83 0.24 28 P 2 TWD 14 DCB

+2.99 TEC TEH 5 HOT 600UL 50 84 0.23 23 P 2 TWD 14 DHB

+0.00 TEC TEH 6 HOT 600UL 54 84 0.17 108 P 2 TWD 12 DCT

+0.00 TEC TEH 6 HOT 600UL 64 84 0.28 165 P 2 TWD 16 VS3

-0.73 TEC TEH 5 HOT 600UL 88 84 0.31 159 P 2 TWD 17 VS2

+0.85 TEH TEC 59 COLD 600UL 98 84 0.11 39 P 2 TWD 11 VS5

-0.92 TEH TEC 39 COLD 600UL 61 85 0.25 67 P 2 TWD 15 DCB

+0.00 TEC TEH 6 HOT 600UL 95 85 0.25 102 P 2 TWD 19 VS2

-0.75 TEH TEC 39 COLD 600UL 60 86 0.14 168 P 2 TWD 9 VS3

-0.67 TEC TEH 3 HOT 600UL 122 86 0.13 79 P 2 TWD 9 06H

+0.87 TEH TEC 37 COLD 600UL 50 88 0.31 157 P 2 TWD 19 DHB

+0.00 TEC TEH 3 HOT 600UL 52 88 0.33 42 P 2 TWD 18 DHT

+0.07 TEC TEH 4 HOT 600UL 54 88 0.28 149 P 2 TWD 16 VS3

-0.79 TEC TEH 3 HOT 600UL 100 88 0.32 163 P 2 TWD 17 08C

-0.93 TEH TEC 37 COLD 600UL 122 88 0.20 101 P 2 TWD 14 VS1

+0.50 TEH TEC 38 COLD 600UL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 4 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 55 89 0.15 160 P 2 TWD 10 DHB

-0.05 TEC TEH 4 HOT 600UL 89 89 0.24 129 P 2 TWD 14 VS2

-0.69 TEH TEC 37 COLD 600UL 48 90 0.38 84 P 2 TWD 14 DHB

+0.00 TEC TEH 3 HOT 600UL 52 90 0.35 51 P 2 TWD 18 DCB

+0.00 TEC TER 3 HOT 600UL 56 90 0.34 38 P 2 TWD 18 VS3

-0.27 TEC TEH 3 HOT 600UL 100 90 0.42 30 P 2 TWD 15 06C

+0.04 TEN TEC 38 COLD 600UL 53 91 0.17 168 P 2 TWD 11 DCT

+0.00 TEC TEH 3 HOT 600UL 44 92 0.32 17 P 2 TWD 17 DCT

+0.00 TEC TEN 3

HOT 600UL 50 92 0.32 19 P 2 TWD 17 DHB

+0.00 TEC TEN 4

HOT 600UL 60 92 0.33 140 P 2 TWD 18 VS4

-0.93 TEC TEN 3 HOT 600UL 96 92 0.16 166 P 2 TWD 10 05C

+0.84 TER TEC 37 COLD 600UL 102 92 0.19 40 P 2 TWD 13 VS4

-0.65 TEN TEC 38 COLD 600UL 110 92 0.12 155 P 2 TWD 9 07C

-0.14 TEN TEC 38 COLD 600UL 87 93 0.33 97 P 2 TWD 17 VS3

-1.00 TEN TEC 37 COLD 600UL 44 94 0.35 33 P 2 TWD 18 DCB

+0.00 TEC TEH 4 HOT 600UL 66 94 0.20 159 P 2 TWD 14 VS3

+0.69 TEC TEN 3

HOT 600UL 39 95 0.31 62 P 2 TWD 17 DCT

+0.00 TEC TER 4 HOT 600UL 95 95 0.22 143 P 2 TWD 15 VS2

+1.01 TEN TEC 38 COLD 600UL 0.23 134 P 2 TWD 15 VS4

-0.64 TEN TEC 38 COLD 600UL 46 96 0.37 160 P 2 TWD 19 DHB

+0.00 TEC TEH 4 HOT 600UL 45 97 0.30 341 P 2 TWD 19 VS3

-1.02 TEC TER 3 HOT 600UL 71 97 0.21 163 P 2 TWD 15 VS2

+0.86 TEC TEH 3 HOT 600UL 89 97 0.35 70 P 2 TWD 18 VS4

-0.88 TEH TEC 35 COLD 600UL 93 97 0.29 60 P 2 TWD 14 VS4

+0.74 TEH TEC 35 COLD 600UL 34 98 0.27 32 P 2 TWD 15 DCT

-0.11 TEC TEH 3

HOT 600UL 56 98 0.24 152 P 2 TWD 16 VS3

+0.99 TEC TEH 3

HOT 600UL 62 98 0.20 147 P 2 TWD 15 VS3

-0.82 TEC TEH 3 HOT 600UL 88 98 0.40 60 P 2 TWD 15 06C

+0.85 TEN TEC 35 COLD 600UL 94 98 0.29 43 P 2 TWD 16 VS2

+0.67 TEN TEC 36 COLD 600UL 47 99 0.31 151 P 2 TWD 17 VS3

-0.83 TEC TEH 4 HOT 600uL 55 99 0.13 161 P 2 TWD 9 VS3

+1.19 TEC TEN 4 HOT 600UL 95 99 0.15 148 P 2 TWD 8 08C

+0.82 TEH TEC 36 COLD 600UL 137 99 0.27 129 P 2 TWD 13 VS1

+0.80 TER TEC 58 COLD 600UL 34 100 0.18 97 P 2 TWD 12 DCB

+0.47 TEN TEC 16 COLD 600UL 94 100 0.27 29 P 2 TWD 15 VS4

+0.87 TEN TEC 26 COLD 600UL 37 101 0.18 77 P 2 TWD 12 VS3

-0.87 TEN TEC 17 COLD 600UL 51 101 0.41 86 P 2 TWD 14 VS3

+0.80 TEN TEC 16 COLD 600UL 89 101 0.22 86 P 2 TWD 13 06H

+0.99 TEH TEC 26 COLD 600UL 91 101 0.18 117 P 2 TWD 9 VS2

-0.79 TEH TEC 25 COLD 600UL 93 101 0.28 30 P 2 TWD 15 VS3

-0.50 TEH TEC 26 COLD 600UL 97 101 0.31 70 P 2 TWD 11 05C

-0.20 TEN TEC 26 COLD 600UL 30 102 0.28 137 P 2 TWD 17 VS3

+0.88 TEN TEC 16 COLD 600UL 34 102 0.17 158 P 2 TWD 12 VS3

-0.84 TEN TEC 16 COLD 600UL 92 102 0.18 34 P 2 TWD 11 VS2

+0.83 TEH TEC 26 COLD 600UL 94 102 0.24 11 P 2 TWD 12 VS3

-0.80 TEH TEC 25 COLD 600UL 98 102 0.14 169 P 2 TWD 8 VS4

-0.97 TER TEC 25 COLD 600UL 27 103 0.24 153 P 2 TWD 15 VS3

-0.76 TEN TEC 16 COLD 600UL 31 103 0.26 138 P 2 TWD 16 VS3

-0.74 TEH TEC 16 COLD 600UL 35 103 0.27 62 P 2 TWD 17 VS3

-0.66 TER TEC 16 COLD 600UL 53 103 0.25 12 P 2 TWD 16 DCT

+0.00 TEN TEC 17 COLD 600UL 87 103 0.16 22 P 2 TWD 8 VS2

-0.92 TER TEC 25 COLD 600UL 89 103 0.35 111 P 2 TWD 18 VS2

-0.79 TER TEC 26 COLD 600UL 97 103 0.30 174 P 2 TWD 16 DHB

+3.71 TEH TEC 26 COLD 600UL 20 104 0.20 142 P 2 TWD 13 VS3

+0.90 TEH TEC 17 COLD 600UL

Framatome ANP Inc.

1/22/2005 14:30 kttacbment 6 CSI-NDE-05-020 Page 5 of 7 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 24 104 0.27 26 104 0,34 28 104 0.20 38 104 0.26 94 104 0.21 126 104 0.42 47 105 0.33 24 106 0.30 28 106 0.29 42 106 0.18 29 107 0.29 50 108 0.18 88 108 0.19 96 108 0.22 93 109 0.14 97 109 0.21 133 109 0.23 0.21 50 110 0.22 0.21 132 110 0.31 35 111 0.16 34 112 0.17 90 112 0.11 122 112 0.29 128 112 0.36 25 113 0.21 51 115 0.20 52 116 0.20 0.10 54 116 0.15 19 117 0.28 89 117 0.36 32 118 0.22 54 118 0.24 112 118 0.18 121 119 0.10 96 120 0.22 5

121 0.10 51 121 0.24 97 121 0.19 94 122 0.28 102 122 0.21 52 124 0.26 62 124 0.11 94 124 0.36 36 126 0.14 46 126 0.34 94 126 0.29 0.19 93 127 0.12 95 127 0.34 88 128 0.27 75 129 0.19 DEG 116 44 138 38 21 109 59 137 60 113 31 153 145 51 140 28 74 104 135 133 103 148 157 138 57 93 129 121 152 17 32 24 106 138 37 19 43 79 125 12 13 65 72 87 157 71 148 52 155 22 76 69 61 58 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 17 VS3

+0.72 19 VS3

+0.80 14 VS3

+0.80 16 VS3

+0.74 11 08C

+0.80 14 VS1

-0.83 19 VS3

-0.60 16 VS3

+0.72 16 VS3

+0.82 11 VS3

-0.32 16 VS3

+0.68 12 VS3

-0.81 16 05H

+0.93 18 VS4

+0.86 13 VS2

-0.92 17 VS2

+0.85 12 08H

+0.73 11 08H

-0.75 13 VS3

-0.89 12 VS3

+0.66 15 VS5

+0.85 11 VS3

-0.79 11 VS3

-0.73 6

06H

+0.87 15 VS4

-0.88 19 DCT

-0.10 10 VS3

-0.72 12 VS3

+0.85 10 VS3

+0.92 4

VS3

-0.92 10 VS3

+1.00 14 VS3

+0.82 12 07H

-0.88 13 VS3

+0.04 14 VS3

+0.97 10 VS1

+0.60 7

VS4

-0.76 14 VS3

+0.77 7

04C

+0.96 17 VS3

-0.83 11 VS2

-0.80 16 VS2

-0.95 12 VS1

-0.65 18 VS3

-0.95 7

05C

+0.98 19 VS3

-0.96 12 VS3

-0.93 18 VS3

-0.74 17 VS3

-0.84 12 VS4

+0.80 8

VS3

+0.60 19 VS2

-0.43 15 08C

-0.72 11 DHB

+0.00 EXT TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH EXT TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL #

16 17 16 17 25 25 17 18 18 19 18 19 28 28 28 28 58 58 18 18 58 19 24 36 36 35 23 24 23 23 24 23 36 24 24 36 33 33 61 22 34 34 34 22 20 34 22 20 33 33 34 33 34 18 LEG COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 600UL 600UL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Page 6 of 7 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS 85 129 0.21 95 129 0.11 1

131 0.12 87 131 0.21 39 133 0.18 111 133 0.24 54 134 0.25 0.27 88 134 0.15 104 134 0.26 55 135 0.21 87 135 0.28 0.15 89 135 0.14 0.15 42 136 0.27 94 136 0.15 35 137 0.25 57 137 0.17 103 137 0.14 56 138 0.20 0.19 80 138 0.22 88 138 0.29 92 138 0.18 94 140 0.18 39 141 0.40 77 141 0.29 44 142 0.27 56 142 0.38 63 143 0.22 54 144 0.22 94 144 0.37 0.13 0.30 53 145 0.15 69 145 0.23 52 146 0.13 0.14 0.34 0.15 76 146 0.21 0.34 0.15 85 147 0.27 33 151 0.11 53 151 0.16 60 152 0.24 0.16 64 152 0.21 69 153 0.26 54 154 0.37 61 155 0.10 62 158 0.10 DEG 65 52 171 157 8

32 45 106 27 130 30 124 72 15 147 40 51 34 55 14 151 164 143 139 24 15 159 30 125 156 147 63 130 156 25 162 115 32 66 28 168 16 59 137 69 53 22 25 36 39 28 30 8

68 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 12 DHB

+0.00 8

VS2

+0.77 8

04H

+0.91 13 VS2

-0.67 12 VS3

-0.99 16 05C

+0.14 15 VS3

-0.88 16 DCB

+3.72 10 VS2

-0.83 16 VS1

+0.70 13 DCT

+0.00 17 VS2

-0.89 10 VS3

-0.73 10 VS2

+0.86 11 VS2

-0.64 18 VS3

-0.71 10 VS4

-0.28 17 DHB

+0.78 11 VS3

+0.67 10 VS2

+0.60 13 VS3

-0.61 12 VS3

+0.94 15 08C

-1.08 19 DCB

+0.00 13 VS2

+0.83 12 VS2

+1.38 19 VS3

+0.87 17 DCT

+0.07 16 07C

-1.03 19 07C

-1.00 13 VS3

-0.77 13 DCT

+0.00 18 VS2

-0.87 7

VS3

-0.98 16 VS4

+0.81 10 DCB

+1.93 15 VS2

+0.76 9

07C

-0.91 10 VS3

+0.79 19 VS3

-0.76 10 06C

+0.16 14 VS3

+0.80 19 VS2

+0.85 10 VS4

-0.98 14 VS2

-0.99 8

VS3

+1.08 11 DCB

+0.00 15 VS3

+0.50 11 VS4

-0.91 14 VS4

-0.67 16 VS4

-0.87 11 VS3

+0.02 8

VS2

+0.64 7

VS3

-0.96 EXT TEH TEH 07H TEH TEC TEH TEC TEC TEH TEH TEC TEH TEH TEH TEH TEC TEH TEC TEC TEH TEC TEC TEC TEH TEH TEH TEC TEC TEC TEC TEC TEC TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC EXT TEC TEC TEH TEC TEH TEC TEH TEH TEC TEC TEH TEC TEC TEC TEC TEH TEC TEH TEH TEC TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH CAL # LEG 34 COLI 33 COLE 16 HOT 33 COLE 22 HOT 31 COLE 22 HOT 22 HOT 32 COLE 32 COLE 22 HOT 32 COLD 32 COLE 31 COLE 31 COLD 23 HOT 32 COLE 23 HOT 22 HOT 31 COLD 22 HOT 22 HOT 23 HOT 31 COLE 31 COLE 32 COLE 26 HOT 27 HOT 27 HOT 26 HOT 26 HOT 26 HOT 27 COLE 27 COLE 27 COLD 26 HOT 27 HOT 27 HOT 27 HOT 27 HOT 27 HOT 27 HOT 27 HOT 27 HOT 27 COLD 29 HOT 29 HOT 29 HOT 29 HOT 29 HOT 29 HOT 29 HOT 29 HOT 28 HOT

)

)

)

)

)

)

PROBE 60 OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Page 7 of 7 Customer Name: St. Lucie Unit 2 Component: S/G B Tubes with Bobbin 1-19% TWD Indications ROW 55 36 40 35 36 12 LINE 159 162 162 163 164 166 VOLTS 0.31 0.15 0.35 0.17 0.35 0.31 DEG 25 152 116 9

85 112 CHN P=2 P 2 P 2 P 2 P 2 P 2 IND

=WD TWD TWD TWD TWD TWD

%TW 18 10 17 10 18 16 LOCATION DHT

+0.00 01H

+0.83 01C

-0.93 01H

+0.78 01C

+0.02 01C

-0.98 EXT TEC TEC TEC TEC TEC TEC EXT TEH TEH TEH TEH TEH TEH CAL #

29 33 33 33 32 33 LEG HOT HOT HOT HOT HOT HOT PROBE 60=OUL 60OUL 60OUL 60OUL 600UL 60OUL Total Tubes

294 Total Records: 330

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 1 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 16 4

0.08 27 5

0.11 35 5

0.17 55 9

0.18 41 15 0.10 74 16 0.09 72 20 0.37 86 20 0.18 88 20 0.46 87 21 0.50 0.32 89 21 0.39 86 22 1.00 0.43 0.32 1.19 72 24 0.19 90 24 0.29 0.64 61 25 0.44 92 26 0.32 0.27 0.39 0.58 98 26 0.17 37 27 0.17 91 27 0.16 0.18 99 27 0.28 101 27 0.24 88 28 0.31 0.44 0.42 98 28 0.13 0.61 81 29 0.74 0.42 0.75 0.85 0.08 96 30 0.29 0.17 0.44 98 30 0.29 0.21 47 31 0.08 95 31 0.08 97 31 0.45 92 32 0.24 108 32 0.09 91 33 0.12 105 33 0.33 94 34 0.35 96 34 0.64 14 148 140 20 125 121 130 123 123 114 149 61 84 100 116 122 118 150 134 153 114 92 137 122 13 141 151 24 149 78 101 79 42 143 116 115 58 99 104 143 146 165 16 44 130 22 22 151 162 148 168 92 145 136 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P4 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 9

12 17 16 10 11 25 16 28 20 14 26 34 18 14 35 17 18 29 27 14 17 22 28 15 16 14 15 18 19 19 24 23 12 32 27 23 31 33 6

21 15 27 18 15 10 9

24 19 9

12 20 21 29 05H

-1.02 01H

+0.81 01H

-1.00 01H

-0.83 VS3

+0.83 VS2

+0.27 VS2

-0.49 VS2

-0.84 VS2

-0.89 VS2

+0.90 VS2

-0.92 VS2

+0.73 VS2

+0.86 VS3

+0.68 VS4

+0.86 VS3

-0.88 VS4

-0.52 VS2

-0.92 VS3

-0.78 VS4

+0.78 VS3

-0.84 VS2

+0.84 VS4

-0.80 VS4

+0.45 08H

-0.94 VS3

-0.97 VS2

-0.71 VS4

-0.91 VS1

-0.55 02H

+0.00 VS3

-0.94 VS4

-0.84 VS4

-0.25 VS2

+0.83 VS4

+0.57 VS4

-0.90 VS3

-0.97 VS3

-0.21 VS3

+0.68 VS4

+0.86 VS2

+0.91 VS3

+0.79 DCT

+0.00 VS2

+0.51 VS3

+0.94 DHT

+0.00 VS2

+0.87 VS2

+0.86 VS2

-0.79 VS2

+0.82 VS4

+0.93 VS2

+0.10 VS2

-0.94 VS2

-0.84 TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEC TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEN TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEN TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEC TEC TEC 10 9

9 10 10 9

20 63 63 13 13 14 13 13 13 13 30 13 13 30 13 13 13 13 14 30 14 14 13 14 13 13 13 14 14 13 13 13 13 13 14 14 14 13 13 36 14 13 14 14 14 13 13 13 HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD COLD HOT COLD COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60=OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Page 2 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 5

35 0.09 51 35 0.41 93 35 0.25 111 35 0.19 88 36 0.17 103 37 0.23 85 39 0.25 103 39 0.19 40 40 0.19 9

41 0.12 43 41 0.32 63 41 0.26 95 41 0.47 119 41 0.17 44 42 0.18 0.17 75 43 0.21 0.23 117 43 0.17 64 44 0.13 82 44 1.04 0.36 94 44 0.26 0.23 0.35 102 44 0.20 122 44 0.41 0.13 66 46 0.24 124 46 0.21 49 47 0.18 123 47 0.18 125 47 0.30 3

49 0.37 41 49 0.23 75 49 0.16 0.30 121 49 0.25 123 49 0.19 125 49 0.16 48 50 0.51 0.23 124 50 0.42 0.67 0.25 126 50 0.36 0.46 39 51 0.24 61 51 0.12 77 51 0.15 125 51 0.44 127 51 0.15 0.13 46 52 0.16 DEG 9

124 153 40 143 97 126 171 147 169 129 97 28 44 29 46 122 87 159 117 94 126 140 64 160 69 147 12 108 160 156 118 80 59 125 102 118 170 161 72 114 28 154 90 54 134 117 149 92 152 23 36 130 152 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 9

25 16 16 15 18 16 16 14 11 20 17 26 13 13 13 15 16 13 11 31 15 18 17 22 15 24 11 19 9

15 8

13 25 18 13 19 18 9

7 25 16 24 30 18 15 18 16 11 13 25 7

6 14 LOCATION EXT 04H

+0.90 TEH VS3

-0.92 TEC 05H

-1.02 TEH 07H

-0.93 TEH VS4

+0.79 TEH DCB

+0.00 TEH VS2

-0.94 TEH DCB

+0.00 TEH VS3

+0.69 TEH 04H

+0.87 TEH VS3

+0.71 TEH VS2

+0.70 TEH DHT

-0.24 TEH VS1

-0.63 TEH VS3

+0.14 TEH VS3

+0.64 TEH VS2

+0.82 TEH VS4

-1.04 TEH VS4

+0.92 TEH VS3

+0.89 TEH VS2

+0.68 TEH VS3

-0.88 TEH VS2

-0.95 TEH VS2

+0.54 TEH DCT

+0.00 TEH DCB

+0.00 TEH DCT

+0.00 TEH DCB

+0.00 TEH 03H

+0.97 TEH DCT

-0.04 TEH VS3

-0.63 TEH VS2

+0.56 TEH DCT

+0.00 TEH 02C

-0.71 07H VS3

-0.88 TEH VS2

-0.72 TEH VS3

-0.16 TEH DCT

+0.00 TEH VS1

+0.74 TEH VS1

+0.85 TEH VS3

-0.76 TEH VS3

-0.04 TEH VS1

+0.78 TEH VS2

-0.92 TEH DHT

+0.00 TEH 08H

-0.14 TEH VS1

+0.85 TEH VS3

+0.72 TEH VS2

-0.28 TEH VS4

+0.75 TEH DHB

+2.13 TEH 09H

+0.85 TEH 04H

-0.92 TEH VS3

-1.00 TEH EXT TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL #

68 35 13 14 14 14 13 14 5

68 5

5 16 16 5

5 5

5 16 5

15 15 16 16 16 16 16 16 6

15 6

15 15 67 10 7

7 16 15 15 9

9 16 16 16 15 15 9

10 10 16 15 15 10 LEG COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60=OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 600UL 580SF 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Page 3 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 78 52 0.14 0.45 84 52 0.20 0.91 0.45 128 52 0.43 85 53 0.54 126 54 0.20 0.20 128 54 0.37 49 55 0.34 51 55 0.06 117 55 0.14 123 55 0.27 129 55 0.16 78 56 0.20 0.20 83 57 0.16 87 57 0.17 89 57 0.20 95 57 0.24 0.22 123 57 0.22 127 57 0.22 129 57 0.51 24 58 0.10 90 58 0.15 0.28 96 58 0.20 0.12 0.18 130 58 0.36 132 58 0.36 0.45 93 59 0.38 95 59 0.35 0.08 0.40 125 59 0.11 0.17 127 59 0.23 0.32 0.19 24 60 0.17 82 60 0.27 96 60 0.16 128 60 0.31 0.11 130 60 0.40 41 61 0.17 129 61 0.33 24 62 0.21 36 62 0.17 44 62 0.11 159 138 154 100 135 22 51 99 142 105 156 120 28 134 127 99 159 143 72 18 100 95 151 49 74 161 140 84 64 101 97 119 151 98 136 108 149 131 18 13 66 81 90 30 146 9

120 164 38 130 17 153 136 164 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TW3D TWD TWD TWD TWD TWD TWD TWD 12 VS4

-0.51 26 VS4

+0.77 9

VS2

-0.97 29 VS3

+0.06 18 VS4

+0.49 17 DHT

+0.14 28 08H

+0.61 18 VS1

+0.22 18 VS1

+1.29 17 DHT

+0.00 20 VS3

-0.92 6

07C

-0.06 14 VS1

+0.74 14 VS1

-0.95 15 DCB

+0.00 15 VS3

+0.77 15 VS4

+0.97 14 VS2

+0.91 14 VS2

+0.85 11 VS2

+0.95 20 VS2

+0.92 19 DHT

+0.00 12 VS1

+0.66 11 VS1

+0.76 30 DCT

+0.00 8

VS3

-0.70 13 DHT

+0.00 21 VS3

-0.69 16 VS3

-0.70 6

VS3

+0.92 13 VS4

-0.14 24 DCB

+0.16 27 DCB

+0.28 29 DEB

+0.08 27 VS4

+0.70 23 VS2

+0.87 7

VS3

-0.83 25 VS3

+0.57 10 VS1

+0.88 14 DCT

+0.00 18 VS1

-0.27 24 VS1

+0.81 15 DCT

+0.00 13 VS3

-0.68 21 VS3

-0.79 14 DHB

+3.36 22 DHB

+0.02 10 VS5

-0.90 25 DHT

-0.06 13 VS3

-0.85 23 DHT

+0.00 15 VS3

+0.98 13 VS3

-0.94 9

VS3

+0.80 TE=

TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEB TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEE TEH TEH TEH TEH TEE TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 10 10 15 15 15 15 16 20 20 19 9

10 20 19 20 11 11 17 17 19 20 20 19 19 20 12 17 17 18 18 18 17 53 53 18 17 17 17 17 17 18 18 18 11 18 17 17 17 17 11 17 12 12 12 COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60:==L 60OUL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL

Framatome ANP Inc.

1/23/2005 08:32 Attacbment 7 CSI-NDE-05-020 Page 4 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of ROW LINE VOLTS 50 62 0.20 78 62 0.61 0.17 0.16 96 62 0.33 134 62 0.15 0.21 0.22 0.16 0.17 19 63 0.56 39 63 0.24 79 63 0.15 0.18 0.15 129 63 0.20 135 63 0.47 0.35 0.95 0.37 20 64 0.23 24 64 0.12 94 64 0.80 0.31 0.40 0.36 0.34 128 64 0.53 130 64 0.18 132 64 0.14 0.43 27 65 0.30 47 65 0.24 38 66 0.19 52 66 0.15 124 66 0.17 31 67 0.57 33 67 0.23 37 67 0.10 0.17 57 67 0.10 79 67 0.31 0.44 89 67 0.18 91 67 0.18 133 67 0.35 34 68 0.35 64 68 0.11 80 68 0.08 132 68 0.17 35 69 0.17 0.79 0.50 37 69 0.40 Bobbin 1-39% TWD Indications left in service for Cycle 15 DEG 69 106 339 172 103 113 149 138 33 157 41 143 114 26 42 58 128 85 61 87 58 50 70 142 154 92 90 125 99 160 97 109 155 114 17 165 91 98 121 152 150 128 121 160 64 79 117 156 10 135 23 86 120 124 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 9

VS3

-0.51 28 VS2

+0.65 13 VS3

-0.75 12 VS4

+0.73 23 VS3

-0.69 16 08H

-0.99 20 VS3

+0.68 21 DHT

+0.00 17 DCT

+0.00 18 07H

+0.78 27 VS3

-0.90 17 VS3

-0.93 12 VS2

+0.89 14 VS3

-0.74 12 VS4

+0.89 18 VS1

+0.65 30 09H

+0.73 26 DHB

+0.00 37 VS1

-0.90 27 VS1

+0.86 19 VS3

-0.81 10 VS3

-0.62 29 VS2

+0.76 15 VS2

-0.89 19 VS3

+0.82 17 VS4

-0.87 17 VS4

-0.36 23 VS1

+0.69 16 VS1

+0.70 10 07H

+0.57 24 DHT

+0.00 19 DHB

+0.02 17 VS3

-0.70 14 VS3

+0.74 12 VS3

-0.90 9

VS1

+0.79 27 DCB

+0.00 16 DCB

+0.00 8

VS3

+0.73 13 DCB

+0.00 8

VS3

+0.82 20 VS2

-0.83 24 VS4

+0.63 10 VS4

+0.99 17 VS2

+0.73 26 VS1

+0.62 21 DHB

+0.00 9

VS3

+0.83 7

VS4

+0.89 13 VS2

-1.00 13 DHT

-0.18 34 DCB

+0.67 27 DHB

+0.25 26 DHB

+0.37 EXT TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH EXT TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL #

11 11 11 11 17 53 53 53 53 53 11 11 11 11 11 20 53 53 53 53 63 12 19 19 19 19 19 19 20 52 52 11 12 11 11 19 11 12 12 12 12 11 11 19 20 53 12 11 11 52 64 64 64 64 LEG COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60=UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Page 5 of 14 Customer Name: St. Lucie Unit 2 Component: SIG A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL t LEG 0.83 137 69 0.19 40 70 0.27 0.23 42 70 0.23 0.83 44 70 0.54 50 70 0.30 0.25 84 70 0.28 136 70 0.74 0.21 0.62 0.14 39 71 0.39 41 71 0.20 43 71 0.41 45 71 0.55 51 71 0.26 89 71 0.22 95 71 0.31 135 71 0.27 42 72 0.71 1.07 0.20 0.16 44 72 0.41 46 72 0.20 48 72 0.21 0.22 50 72 0.49 52 72 0.15 54 72 0.19 64 72 0.19 82 72 0.23 94 72 0.11 0.12 126 72 0.35 0.18 134 72 0.40 43 73 0.20 0.31 0.47 49 73 0.51 0.18 51 73 0.32 53 73 0.33 55 73 0.16 0.20 75 73 0.16 83 73 0.18 133 73 0.14 135 73 0.81 0.32 101 164 70 120 22 108 112 98 119 150 142 139 104 165 126 122 43 132 65 118 39 47 101 84 115 104 134 85 28 137 101 147 160 140 161 171 168 64 31 49 43 93 81 121 76 96 51 156 109 156 163 149 59 121 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 T==

TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 35 19 21 1 9 19 35 28 21 19 20 31 15 29 11 24 17 25 27 20 16 19 18 31 35 16 14 23 17 16 17 27 7

16 13 17 8

9 21 13 23 15 19 25 28 15 20 22 12 14 13 15 15 32 20 DCB

+0.47 TEH 07H

+0.65 TEH DHB

+0.43 TEH DCT

-0.24 TEH DCT

-0.14 TEH DCB

+0.28 TEH DCB

+0.00 TEC DCB

+0.00 TEC VS3

-0.71 TEC 07H

+0.89 TEH VS1

-0.84 TEH VS2

+0.92 TEH VS3

-0.74 TEH VS5

-0.90 TEH DCB

+0.35 TEH DCB

+0.57 TEH DCB

+0.00 TEC DCB

+0.47 TEC DCT

+0.00 TEC VS2

+0.98 TEH VS2

+0.79 TEH VS1

-0.90 TEH DCT

+0.00 TEC DHB

+0.00 TEC VS3

+0.75 TEC VS3

-0.83 TEC DHB

+0.35 TEC DCB

+0.00 TEC DCT

+0.00 TEC VS3

+0.66 TEC DCB

+0.00 TEC DCT

+0.00 TEC VS3

+0.88 TEC VS4

-0.82 TEC VS3

-0.78 TEH VS2

+0.86 TEH VS4

+0.92 TEN 08H

+0.90 TEH 09H

+0.10 TEH VS1

+0.82 TEH DHT

+0.00 TEC DCB

+0.26 TEC DHB

+0.37 TEC DCB

+0.00 TEC DCT

+0.00 TEC DCB

+0.21 TEC DCB

+0.00 TEC DCB

+0.35 TEC VS3

-0.12 TEC VS3

+0.83 TEC 05H

+1.02 TEH VS1

-0.56 TEH VS1

+0.80 TEH VS2

+0.66 TEH TEC TEC TEC TEC TEC TEC TEN TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC 64 53 64 64 64 64 4

4 4

21 52 52 52 52 64 64 4

3 4

21 22 52 4

4 4

4 3

4 3

3 4

3 4

3 21 22 22 22 22 52 3

3 3

4 4

3 4

3 3

3 21 53 52 52 COLD COLD COLD COLD COLD COLD HOT HOT HOT COLD COLD COLD COLD COLD COLD COLD HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD PROBE 60.UL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60O0UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 600UL 600UL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60O0UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 AttacS-ent 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG A Page 6 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 0.61 1.11 0.15 0.20 46 74 0.40 48 74 0.33 52 74 0.22 54 74 0.30 0.20 56 74 0.19 62 74 0.24 82 74 0.50 126 74 0.13 45 75 0.18 0.37 0.58 0.24 49 75 0.16 57 75 0.44 93 75 0.48 133 75 0.32 46 76 0.48 0.72 0.83 48 76 0.34 0.35 58 76 0.37 94 76 0.23 112 76 0.13 134 76 0.11 136 76 0.31 51 77 1.25 53 77 1.34 0.91 0.37 57 77 0.43 73 77 0.25 0.30 79 77 0.12 93 77 0.31 133 77 0.20 48 78 0.15 0.54 52 78 0.25 56 78 1.05 0.15 60 78 0.10 0.15 96 78 0.79 116 78 0.17 49 79 0.76 1.12 0.77 0.86 24 132 19 62 71 105 66 154 118 163 62 124 36 137 118 101 104 162 89 81 123 116 71 94 86 87 104 25 65 56 134 97 19 93 115 123 150 82 156 86 138 120 29 108 90 147 132 142 86 157 103 81 56 82 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 28 VS3

+0.70 35 VS4

+0.78 12 VS5

+0.80 15 VS1

-0.76 25 DHB

+0.00 20 DCT

-0.25 17 DCT

+0.00 21 DCT

+0.00 17 VS3

-0.92 15 VS3

+0.70 18 VS4

-0.71 27 VS2

-0.76 9

VS2

+0.89 14 DCB

+0.00 23 DCT

+0.00 29 DHT

+0.00 17 DHB

+0.00 13 DHB

+0.00 25 VS3

-0.60 27 VS2

-0.39 25 VS1

+0.66 27 DCT

+0.00 32 DHT

+0.00 33 DHB

+0.00 22 DCB

+0.00 21 DHB

+0.19 24 DCB

+0.00 18 VS3

-0.42 9

VS2

-0.67 9

VS5

-1.00 20 DCT

+0.00 37 DCT

+0.00 38 DHT

+0.00 34 DHB

+0.00 21 DCT

+0.00 25 DCT

+0.00 19 VS2

+0.84 21 VS2

-0.86 10 VS2

-0.79 20 DCB

+0.46 20 VS5

+0.77 12 DHT

+0.00 28 DHB

+0.00 17 DHB

+0.23 35 DCB

+0.00 14 VS3

+0.77 9

VS4

-0.66 13 VS3

+0.78 33 VS3

-0.83 12 VS1

-0.73 32 DCT

+0.00 36 VS3

+0.97 32 VS3

-0.10 33 DHT

+0.00 TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEC TEC TEN TEH TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEC TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH 52 52 52 52 4

3 3

4 4

3 4

21 22 3

3 3

3 3

3 21 53 4

4 4

3 3

4 21 22 52 52 4

3 3

3 3

4 4

3 54 53 3

3 3

4 4

4 4

54 23 5

5 5

5 COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT COLD COLD NOT HOT HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD NOT HOT HOT HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT PROBE 60=OUL 600UL 600VL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attacbment 7 CSI-NDE-05-020 Page 7 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 51 79 0.95 0.44 53 79 0.35 61 79 0.91 63 79 0.16 125 79 0.22 131 79 0.15 62 80 0.94 53 81 0.77 0.31 0.53 59 81 0.38 61 81 0.19 50 82 0.57 0.16 0.21 0.21 56 82 0.40 60 82 0.16 0.65 51 83 0.46 0.19 0.56 61 83 0.12 85 83 0.34 0.21 135 83 0.21 52 84 0.54 56 84 0.51 76 84 0.28 61 85 0.37 75 85 0.29 77 85 0.27 54 86 0.33 0.24 0.60 0.31 56 86 1.11 58 86 0.93 60 86 0.33 62 86 0.34 0.24 92 86 0.56 1.19 0.30 0.24 126 86 0.12 49 87 1.36 0.49 51 87 0.85 0.17 0.59 55 87 0.26 0.49 104 152 117 102 60 108 159 69 75 159 50 110 139 79 97 20 101 46 71 119 112 151 108 14 89 137 137 107 77 142 95 128 33 121 159 83 79 110 125 84 152 98 135 130 149 51 152 107 82 55 150 136 157 55 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 34 26 21 34 13 14 9

34 32 20 27 23 15 28 13 16 16 24 13 30 25 15 28 10 22 16 20 27 27 19 24 19 20 22 18 29 21 36 34 21 22 18 28 36 20 18 10 37 27 33 13 28 18 26 DCT

+0.00 TEC DHT

+0.00 TEC DCT

+0.00 TEC DCB

+0.00 TEC DCB

+0.00 TEC VS1

-0.85 TEH VS4

-0.90 TEH DCB

+0.00 TEC DCT

+0.00 TEC DHT

+0.00 TEC DHB

+0.00 TEC DCB

+0.00 TEC DCB

+0.00 TEC DCB

+0.00 TEC DCT

+0.00 TEC DHT

+0.00 TEC DHB

+0.00 TEC DCT

+0.00 TEC DCB

+0.00 TEC DHB

+0.00 TEC DCB

+0.00 TEC DCT

+0.00 TEC DHB

+0.00 TEC DCB

+0.00 TEC VS2

-1.38 TEH VS3

+0.63 TEH VS1

-0.77 TEH DCT

+0.00 TEC DCB

+0.00 TEC VS3

+0.81 TEC DCB

+0.00 TEC VS3

+0.75 TEC VS4

+0.82 TEC DCT

+0.00 TEC VS3

+1.04 TEC VS3

-0.69 TEC DHB

+0.00 TEC DCB

+0.00 TEC DCB

+0.00 TEC DHB

+0.00 TEC DCB

+0.00 TEC VS3

-0.80 TEC VS2

+0.88 TEH VS3

-0.84 TEH VS4

-0.86 TEH VS4

+0.82 TEH 09H

-0.84 TEH DCT

+0.00 TEC DHB

+0.00 TEC DCT

+0.00 TEC DCB

+0.00 TEC DHB

+0.00 TEC DCB

+0.00 TEC DCT

+0.00 TEC TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEH TEH TEB TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH 6

6 5

6 5

23 54 5

5 5

5 5

6 5

5 5

5 6

6 6

5 5

5 6

25 25 53 5

6 5

6 5

6 6

6 6

6 5

6 5

6 6

25 25 25 25 26 6

6 5

5 5

5 5

HOT HOT HOT HOT HOT COLD COLD NOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT PROBE 60OOUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 600UL 600UL 600UL 600UL

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 8 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 0.49 0.51 57 87 0.68 59 87 0.47 93 87 0.40 0.24 0.29 97 87 0.38 0.31 111 87 0.11 50 88 0.97 0.14 0.89 52 88 0.54 0.59 54 88 0.22 56 88 0.48 94 88 0.28 0.12 0.35 49 89 0.27 51 89 0.21 53 89 0.24 0.56 57 89 0.14 73 89 0.18 83 89 0.22 0.17 0.23 0.24 95 89 0.21 0.26 0.41 46 90 0.30 0.58 0.34 48 90 0.33 0.35 50 90 0.29 0.13 54 90 0.24 0.23 82 90 0.32 92 90 0.22 45 91 0.75 0.36 0.66 47 91 0.53 51 91 0.40 57 91 0.29 139 91 0.26 0.75 1.25 56 92 0.62 125 80 119 103 47 170 134 82 124 55 87 109 99 99 139 51 138 106 139 117 114 45 102 131 122 88 86 83 115 130 93 22 118 143 118 85 139 122 96 90 130 76 75 144 86 60 173 57 78 107 133 95 17 8

P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TnD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 26 VS3

-0.85 27 DHB

+0.00 31 DCB

+0.00 25 DHB

+0.00 24 VS2

-0.98 18 VS2

+0.58 20 VS4

+1.00 23 VS2

-0.66 21 VS3

+0.78 10 VS2

-0.93 34 DCB

+0.00 12 DCT

+0.00 34 DHT

+0.00 27 DCB

+0.00 28 DCT

+0.00 17 DCB

+0.00 26 DCT

+0.00 20 VS2

-0.80 10 VS3

-0.96 23 VS4

+0.74 19 DCB

+0.00 17 DCB

+0.00 17 DCT

+0.00 28 DHB

+0.00 11 04H

+0.93 14 VS3

+0.65 17 VS2

+0.74 14 VS3

-0.90 17 VS4

-0.68 18 VS3

+0.92 16 VS2

-0.94 19 VS2

+0.50 24 VS4

-0.60 21 DCB

+0.00 29 DCT

+0.00 22 DHT

+0.00 21 DCT

+0.00 22 DCB

+0.00 21 DCB

+0.00 11 05H

+0.96 18 DCB

+0.00 18 VS3

-0.62 21 VS3

-0.64 17 VS2

+0.80 31 DHB

+0.04 22 DCT

+0.00 30 DHT

+0.00 28 DHB

+0.00 24 DHB

+0.00 19 DHB

+0.00 23 VS5

+0.72 35 DHT

+0.00 39 DCT

+0.00 30 DHT

+0.00 TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEN TEH TEH TEC TEC TEC TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEH TEH TEH TEC TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEC TEC TEC TEN TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEH TEC TEC TEC TEH 5

5 6

5 25 25 25 25 25 25 6

6 6

5 5

6 5

26 26 26 5

6 5

5 5

5 25 25 25 25 25 25 25 6

6 6

5 5

6 6

6 6

25 25 5

5 5

6 6

5 56 56 56 6

HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT HOT HOT COLD COLD COLD HOT PROBE 60:UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 6QOUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attac}ment 7 CSI-NDE-05-020 Page 9 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 58 92 0.38 132 92 0.36 43 93 0.19 0.32 0.61 45 93 0.38 55 93 0.23 97 93 0.21 0.37 0.19 0.12 44 94 0.10 0.50 48 94 0.15 52 94 0.17 82 94 0.15 0.16 86 94 0.13 43 95 0.28 49 95 0.39 0.27 0.49 51 95 0.16 53 95 0.14 135 95 0.26 38 96 1.00 0.37 0.17 0.65 42 96 0.19 0.84 44 96 0.22 48 96 0.44 0.37 54 96 0.42 94 96 0.73 0.26 0.47 41 97 0.26 0.27 43 97 0.20 0.39 45 97 0.15 0.39 0.25 47 97 0.40 0.59 57 97 0.12 87 97 0.13 135 97 0.48 0.60 0.41 137 97 0.06 42 98 0.31 DEG 102 127 63 93 131 85 132 157 137 62 91 141 114 125 104 154 140 35 92 50 137 125 154 123 140 99 122 90 84 155 94 80 130 132 97 82 113 153 108 106 108 144 121 90 125 112 129 146 15 48 63 107 142 91 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 23 22 14 20 29 24 16 18 26 17 12 9

27 13 14 12 13 11 20 23 18 26 13 11 17 35 24 14 30 15 33 17 25 22 25 31 18 26 19 20 15 23 13 24 19 23 28 10 13 25 28 23 9

22 LOCATION EXT DCB

+0.00 TEC VS1

+0.98 TEH VS3

+1.00 TEC DHB

+0.00 TEC DCB

+0.00 TEC DCB

+0.00 TEC DCB

+0.06 TEC VS2

-0.81 TEH VS3

+0.67 TEH VS4

+0.63 TEH VS2

+0.22 TEH DCB

+0.00 TEC DHB

+0.00 TEC VS3

-0.87 TEC VS3

+0.00 TEC VS2

+0.97 TEH VS4

+0.93 TEH VS4

+0.84 TEH VS3

+1.04 TEC DCT

-0.06 TEC VS3

+1.09 TEC VS3

-0.60 TEC DCB

+0.00 TEC DCB

-0.19 TEC VS1

-0.94 TEH DCB

+0.00 TEC DCT

+0.00 TEC DHB

+0.00 TEC DHT

+0.00 TEC VS3

-0.87 TEC DHT

+0.00 TEC DCT

+0.00 TEC VS3

-0.99 TEC VS3

+0.77 TEC VS3

-0.70 TEC VS2

-0.90 TEH VS3

-0.54 TEH VS4

+0.68 TEN DCB

+0.00 TEC DHB

+0.00 TEC DCT

+0.00 TEC DCB

+0.00 TEC DCB

+0.00 TEC DCT

+0.00 TEC VS3

+0.85 TEC DCB

+0.00 TEC VS3

+1.07 TEC VS3

+0.68 TEC VS4

-0.56 TEN VS1

-0.82 TEH VS3

+0.94 TEH VS5

+0.04 TEH DCB

+0.40 TEH DCB

+0.00 TEH EXT TEH TEC TEH TEH TEH TEH TEH TEC TEC TEC TEC TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC CAL #

5 55 5

5 5

6 5

28 28 28 28 6

6 6

6 55 55 27 6

5 5

5 6

5 55 6

6 6

6 6

6 5

5 5

6 27 27 27 6

6 5

5 6

6 6

5 5

6 28 55 55 55 56 62 LEG HOT COLD HOT HOT HOT HOT HOT COLD COLD COLD COLD HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD PROBE 60OOUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60O0UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL

Pramatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Page 11 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 125 107 0.20 127 107 0.20 42 108 0.13 48 108 0.13 96 108 0.46 0.22 0.65 0.34 100 108 0.13 132 108 0.34 39 109 0.09 101 109 0.24 129 109 0.23 133 109 0.21 0.13 8

110 0.16 78 110 0.10 132 110 0.15 33 111 0.20 45 111 0.13 87 111 0.27 46 112 0.31 82 112 0.15 0.15 0.28 88 112 0.16 0.26 0.18 92 112 0.12 31 113 0.13 51 113 0.32 53 113 0.23 123 113 0.29 0.26 0.31 0.09 84 114 0.34 41 115 0.10 47 115 0.30 0.41 125 115 0.12 54 116 0.08 76 116 0.07 0.10 92 116 0.09 0.22 94 116 0.34 128 116 0.11 41 117 0.10 53 117 0.11 77 117 0.15 93 117 0.13 127 117 0.38 40 118 0.13 DEG 82 17 157 164 122 157 114 101 144 34 111 33 153 145 166 41 11 161 77 20 156 59 100 161 140 28 155 160 116 18 111 132 50 138 147 28 77 167 118 154 166 194 155 168 156 131 37 145 168 17 159 46 66 119 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD IWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 16 VS1

+0.94 17 DCT

-0.02 14 VS3

+0.10 14 VS3

-0.83 28 VS2

-0.72 18 VS2

+0.81 33 VS3

-0.68 23 VS4

+0.68 12 DCT

+0.00 21 DCB

+0.00 11 VS3

+0.93 17 VS3

+0.87 17 VS1

-0.88 21 DHT

+0.00 15 07C

-0.94 13 06H

+0.69 10 06H

+0.96 17 VS5

-0.87 18 VS3

+0.85 13 VS3

+0.89 18 VS3

-0.86 24 VS3

+0.67 17 VS2

-0.02 16 VS2

+0.76 24 VS4

+0.62 13 VS4

-0.93 18 VS3

-0.95 14 VS2

+0.87 10 VS3

-1.00 14 VS3

-0.34 24 VS3

+0.87 20 VS3

+0.99 24 VS1

-0.74 23 VS3

+0.78 25 VS4

+1.02 12 VS5

+1.00 21 VS4

-0.88 11 VS3

+0.99 23 VS3

+0.97 26 VS3

-0.79 14 VS1

+0.98 9

VS3

-0.73 9

VS3

+0.63 12 08C

+0.88 12 08C

+1.15 21 VS2

-0.68 21 VS4

-0.88 14 VS2

+1.04 12 VS3

+0.81 12 VS3

+0.95 14 VS3

+0.98 13 VS3

+0.62 23 VS1

+0.74 11 VS3

+0.87 EXT TE=

TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH EXT TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL #

35 36 41 42 36 36 36 36 36 55 41 33 33 56 56 50 46 56 42 42 33 42 34 34 34 55 55 55 33 42 41 41 34 34 34 34 33 41 41 41 34 40 45 45 34 34 33 34 40 40 46 32 31 39 LEG COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60:UL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL

Framatome ANP Inc.

1/23/2005 08:32 Attacbment 7 CSI-NDE-05-020 Page 12 of 14 Customer Name: St. Lucie Unit 2 Component: SIG A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 86 118 0.24 88 118 0.29 37 119 0.32 51 119 0.26 53 119 0.14 123 119 0.10 84 120 0.38 0.27 94 120 0.57 0.27 0.30 102 120 0.26 126 120 0.50 37 121 0.12 53 121 0.14 97 121 0.41 125 121 0.14 0.39 39 123 0.12 53 123 0.21 38 124 0.24 42 124 0.26 37 125 0.12 41 125 0.17 38 126 0.20 44 126 0.24 54 126 0.13 94 126 0.24 21 127 0.15 41 127 0.16 53 127 0.74 57 127 0.33 79 127 0.14 87 127 0.17 91 127 0.18 95 127 0.16 97 127 0.67 0.17 0.24 54 128 0.32 80 128 0.20 96 128 0.23 0.19 45 129 0.14 53 129 0.20 89 129 0.23 91 129 0.27 93 131 0.20 0.72 92 132 0.26 45 133 0.28 57 133 0.56 91 133 0.31 93 133 0.27 DEG 142 134 88 34 25 161 128 132 112 147 99 98 62 156 44 85 37 40 60 44 115 124 59 24 144 160 96 125 92 73 81 54 123 147 153 155 72 29 130 148 32 101 154 40 150 69 131 86 48 49 139 139 146 153 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND

==D TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 20 19 21 20 12 11 23 19 32 22 24 22 26 10 12 28 14 27 13 15 23 24 15 19 21 21 10 20 17 18 30 20 13 16 17 16 30 13 17 20 15 20 18 16 21 17 18 21 35 24 19 29 15 25 LOCATION EXT EXT CAL #

VS3

-0.74 TEH TEC 32 08H

+0.89 TEH TEC 31 VS3

+0.97 TEH TEC 39 VS3

+0.83 TEH TEC 40 VS3

+0.83 TEH TEC 39 VS4

-0.96 TEH TEC 32 VS4

-0.88 TEH TEC 31 VS2

-0.74 TEH TEC 31 VS2

+0.62 TEH TEC 32 VS3

-0.88 TEH TEC 32 VS4

-0.90 TEH TEC 32 VS3

-0.77 TEH TEC 32 08H

-0.95 TEH TEC 31 VS3

+0.81 TEH TEC 39 VS3

-0.85 TEH TEC 39 08C

+0.88 TEH TEC 32 07H

+0.77 TEH TEC 32 DCT

+0.08 TEH TEC 32 VS3

+0.91 TEH TEC 38 VS3

+0.92 TEH TEC 48 VS3

+0.73 TEH TEC 37 VS3

-0.67 TEH TEC 37 VS3

-0.70 TEH TEC 37 VS3

-0.62 TEH TEC 37 VS3

+0.75 TEH TEC 37 VS3

-0.73 TEH TEC 38 VS3

-0.86 TEH TEC 47 VS2

-0.90 TEH TEC 32 VS3

+0.89 TEH TEC 37 VS3

-0.73 TEH TEC 37 VS3

-0.77 TEH TEC 47 VS3

-0.72 TEH TEC 47 VS2

-0.77 TEH TEC 47 VS2

+0.52 TEH TEC 32 VS2

-0.84 TEH TEC 32 VS2

-0.88 TEH TEC 32 VS3

+0.92 TEH TEC 31 VS4

+0.90 TEH TEC 31 VS2

-0.64 TEH TEC 31 VS3

-0.94 TEH TEC 47 VS4

-0.95 TEH TEC 47 VS2

-0.94 TEH TEC 32 VS4

-0.82 TEH TEC 32 VS3

-0.61 TEH TEC 37 VS3

-0.77 TEH TEC 37 VS2

+0.91 TEH TEC 31 VS2

-0.78 TEH TEC 31 VS2

-0.80 TEH TEC 30 VS2

+0.72 TEH TEC 30 VS2

+0.70 TEH TEC 30 VS3

+0.78 TEC TEH 27 VS3

+0.78 TEC TEH 25 08C

+1.34 TEH TEC 29 VS2

+0.80 TEH TEC 30 LEG COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT HOT COLD COLD PROBE 60=OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attach-mnt 7 CSI-NDE-05-020 Page 13 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 97 133 0.48 0.26 42 134 0.16 50 134 0.14 96 134 0.24 0.31 42 138 0.28 46 138 0.14 96 138 0.49 0.19 102 138 0.22 104 138 0.15 53 139 0.22 81 139 0.21 95 139 0.15 97 139 0.50 101 139 0.10 48 140 0.27 102 140 0.18 85 141 0.33 97 141 0.22 66 142 0.06 86 142 0.17 0.14 96 142 0.09 81 143 0.19 87 143 0.40 0.63 0.15 95 143 0.23 94 144 0.12 46 146 0.12 85 147 0.18 53 151 0.22 56 152 0.75 47 155 0.26 57 155 0.23 44 156 0.30 51 157 0.48 0.67 49 161 0.24 38 162 0.12 29 163 0.06 30 164 0.16 32 164 0.20 36 164 0.11 15 165 0.21 27 165 0.22 29 165 0.12 0.18 2

166 0.34 14 166 0.39 20 166 0.13 DEG 80 88 47 23 142 74 107 157 110 151 153 13 106 158 131 51 133 135 20 106 71 170 169 150 166 103 32 52 38 78 163 65 120 141 127 129 143 91 103 91 102 139 156 32 158 7

32 133 149 154 83 55 142 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 1WD 1WD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 31 24 13 12 23 26 16 9

30 17 16 14 15 16 15 26 9

18 17 21 16 5

14 12 10 14 24 29 12 17 10 11 17 10 26 19 17 20 26 30 18 11 7

13 16 10 17 17 11 15 23 24 12 LOCATION EXT VS2

-0.68 TEH VS4

-0.60 TEH VS3

-0.92 TEC DCT

+0.00 TEC VS2

+0.92 TEH VS3

-0.86 TEH 05H

+0.92 TEC VS3

-0.63 TEC VS3

-0.60 TEH VS2

+0.84 TEH VS2

-0.96 TEH 08H

+0.79 TEH VS3

-0.55 TEC 06C

+0.83 TEH VS2

-0.90 TEH VS2

-0.92 TEH VS2

-0.95 TEH VS3

+0.80 TEC 09H

-0.95 TEH VS3

+0.64 TEH 07C

-0.26 TEH VS2

+1.12 TEC VS4

-0.88 TEH VS3

+1.06 TEH VS4

-0.88 TEH 08C

+0.86 TEH VS2

-0.98 TEH VS3

+0.38 TEH VS4

+0.66 TEH VS2

-0.92 TEH 01C

+0.95 TEH VS3

+0.61 TEH VS2

+0.92 TEH VS3

-0.85 TEC VS3

-0.65 TEC VS3

-0.73 TEC VS3

+0.80 TEC VS3

-0.83 TEC VS3

+0.84 TEC VS3

-0.55 TEC VS3

-0.79 TEC 01H

+1.07 TEC 01C

-1.00 TEC 01H

-0.92 TEC 01C

+0.92 TEC 01H

+0.94 TEC 01H

-0.78 TEC 01C

-0.93 TEC 01C

-0.99 TEC 01H

-1.03 TEC 01C

-0.84 07C 01C

-1.04 TEC 01H

+0.93 TEC EXT TEC TEC TEH TEH TEC TEC TEH TEH TEC TEC TEC TEC TEH TEC TEC TEC TEC TEH TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH CAL # LEG 30 COLD 30 COLD 27 HOT 27 HOT 30 COLD 30 COLD 37 HOT 37 HOT 28 COLD 28 COLD 27 COLD 28 COLD 37 HOT 27 COLD 28 COLD 27 COLD 27 COLD 37 HOT 28 COLD 27 COLD 27 COLD 41 HOT 27 COLD 27 COLD 28 COLD 27 COLD 27 COLD 27 COLD 27 COLD 27 COLD 27 COLD 62 COLD 28 COLD 44 HOT 44 HOT 47 HOT 48 HOT 48 HOT 48 HOT 48 HOT 48 HOT 47 HOT 48 HOT 47 HOT 48 HOT 47 HOT 48 HOT 48 HOT 47 HOT 47 HOT 59 COLD 47 HOT 47 HOT PROBE 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Page 14 of 14 Customer Name: St. Lucie Unit 2 Component: S/G A Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE Total Tubes

490 Total Records: 701

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 1

3 0.11 32 4

0.25 34 4

0.24 31 5

0.35 37 5

0.31 52 8

0.36 60 10 0.08 62 12 0.17 39 15 0.09 55 15 0.07 40 18 0.17 62 18 0.16 47 21 0.29 46 22 0.14 48 22 0.24 0.13 54 22 0.38 87 23 0.43 93 23 0.24 88 24 0.32 0.19 92 24 0.30 94 24 0.25 96 24 0.36 0.58 0.36 0.48 0.26 45 25 0.35 81 25 0.30 91 25 0.31 95 25 0.35 0.08 44 26 0.11 94 26 0.32 0.28 0.37 96 26 0.49 0.34 91 27 0.30 95 27 0.20 97 27 0.21 99 27 0.43 101 27 0.68 34 28 0.08 92 28 0.16 0.13 98 28 0.17 100 28 0.81 0.21 53 29 0.17 67 29 0.17 89 29 0.27 91 29 0.28 DEG 161 140 153 48 74 146 155 109 171 168 55 93 124 33 43 51 98 111 93 58 140 58 72 146 60 107 128 135 67 63 122 130 16 15 110 149 133 33 29 98 81 40 143 115 163 30 121 110 114 120 119 136 11 98 CHN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 8

13 14 18 23 25 9

15 9

8 15 14 23 14 21 14 26 21 13 17 12 17 16 21 27 20 24 9

25 18 18 19 3

12 17 15 18 25 20 17 12 14 22 29 8

12 9

10 31 14 17 17 17 15 LOCATION 01C

-0.96 02H

+0.99 02H

-0.99 01C

-0.93 02H

+0.80 01C

-0.98 02H

+0.88 01H

-0.94 04H

+0.80 04H

+0.86 VS3

-0.96 VS3

-0.87 VS3

-0.70 VS3

+0.97 VS3

+0.74 VS3

-1.00 VS3

-0.66 VS2

+0.83 DCT

+0.00 VS2

+0.89 VS3

+0.58 DCB

+0.00 DCB

+0.00 07H

-0.22 08H

-0.92 VS4

+0.79 DCB

+0.00 06H

+0.87 VS3

-0.88 DCT

+0.00 DCT

-0.12 VS4

-0.89 05H

+0.67 VS3

-0.88 VS2

-1.01 VS2

+0.95 DHT

+0.00 VS4

+0.16 DHT

+0.00 VS4

-0.99 VS4

-0.93 VS3

-0.93 O0H

-0.26 DCT

+0.00 VS3

-1.13 VS2

-0.59 VS2

+0.83 VS2

+0.81 DCT

+0.00 02H

+0.94 VS3

+0.92 VS2

-0.69 DHT

+0.00 DCT

+0.00 EXT 07C TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEC TEC TEH TEH EXT TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEH TEH TEC TEC CAL # LEG 46 COLD 47 COLD 48 COLD 9

HOT 10 HOT 10 HOT 9

HOT 10 HOT 14 HOT 14 HOT 14 HOT 14 HOT 17 HOT 18 HOT 17 HOT 17 HOT 18 HOT 48 COLD 47 COLD 49 COLD 49 COLD 49 COLD 50 COLD 50 COLD 50 COLD 50 COLD 50 COLD 50 COLD 17 HOT 50 COLD 49 COLD 49 COLD 49 COLD 19 HOT 49 COLD 49 COLD 49 COLD 50 COLD 50 COLD 49 COLD 49 COLD 50 COLD 49 COLD 50 COLD 20 HOT 50 COLD 50 COLD 49 COLD 50 COLD 50 COLD 19 HOT 19 HOT 50 COLD 49 COLD PROBE 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL

Framatome ANP Inc.

1/23/2005 08:32 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG B Page 2 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 95 29 0.19 0.50 0.13 42 30 0.24 92 30 0.30 0.28 0.15 96 30 0.21 104 30 0.19 107 31 0.24 0.28 108 32 0.25 43 33 0.26 105 33 0.28 64 34 0.46 82 34 0.28 92 34 0.18 96 34 0.92 0.24 108 34 0.15 50 36 0.30 94 36 0.25 96 36 0.35 100 36 0.29 87 37 0.13 0.17 92 38 0.22 112 38 0.23 116 38 0.33 81 39 0.23 83 39 0.15 0.19 117 39 0.29 85 41 0.16 95 41 0.38 0.22 97 41 0.87 0.36 0.70 0.22 116 42 0.15 121 43 0.19 46 44 0.13 94 44 0.20 0.25 120 44 0.17 29 45 0.29 123 45 0.32 62 46 0.27 124 46 0.15 43 47 0.50 125 47 0.31 86 48 0.24 126 48 0.14 DEG 49 78 35 28 139 152 121 26 56 51 70 149 100 78 63 87 63 109 86 100 99 148 106 12 20 167 102 97 52 22 105 14 44 152 114 63 102 57 121 138 114 10 20 162 52 138 69 41 50 29 126 108 47 149 CNN P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 13 VS2

+0.81 25 DCT

+0.00 10 06H

+0.95 19 VS3

-0.86 16 VS2

+0.65 16 VS4

-0.91 9

07H

+0.88 13 VS4

+0.40 10 VS3

-1.33 15 02H

+0.76 16 04C

-1.02 15 02H

-0.86 20 VS3

+0.93 10 02H

-0.12 29 VS4

-0.24 10 VS4

-0.61 11 08H

+1.02 32 VS2

-0.41 15 VS3

+0.32 10 03C

-0.88 21 VS3

+0.76 15 VS2

-0.95 19 VS2

-0.79 17 08H

+0.89 9

VS2

-0.65 11 VS2

+0.75 13 08H

-0.78 14 VS4

-0.87 18 VS3

+0.87 14 VS4

+0.63 10 VS2

+0.65 12 VS4

+0.75 16 DCT

-0.25 10 VS4

-0.77 20 VS2

+0.97 13 VS4

+0.89 31 VS2

+0.63 19 VS3

-0.97 28 VS4

+0.55 14 VS4

-0.81 10 05C

+0.86 12 DCT

+0.00 9

VS3

+0.82 12 VS2

-0.69 15 VS4

-1.20 11 04H

+0.92 17 VS3

-0.62 17 DHT

+0.00 16 VS2

+0.85 10 DCT

+0.00 26 VS3

-0.78 17 09C

+0.88 14 VS2

+1.08 9

07H

-1.00 EXT TEN TEH TEN TEC TEN TEN TEN TEN TEH TEN TEH TEN TEC TEN TEC TEN TEN TEN TEN TEN TEC TEN TEH TEN TEN TEN TEN TEN TEH TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN TEN EXT TEC TEC TEC TEN TEC TEC TEC TEC TEC TEC TEC TEC TEN TEC TEN TEC TEC TEC TEC TEC TEN TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL #

50 50 50 20 49 49 49 49 49 49 49 49 25 49 24 50 49 49 49 52 25 51 52 52 51 51 52 52 52 51 51 51 52 51 52 52 51 51 51 51 52 51 4

52 52 51 3

52 3

52 4

52 51 52 LEG COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD HOT COLD COLD COLD COLD COLD HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60 OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attacbhent 8 CSI-NDE-05-020 Page 3 of 10 Customer Name: St. Lucie Unit 2 Component: SIG B Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 0.50 93 49 0.39 68 50 0.28 0.48 57 51 0.95 107 51 0.13 113 51 0.35 121 51 0.27 127 53 0.30 0.30 0.18 41 55 0.36 83 55 0.21 0.27 95 55 0.24 131 55 0.20 0.73 28 56 0.15 81 57 0.29 121 57 0.14 48 58 0.10 130 58 0.48 132 58 0.69 0.50 49 59 0.46 0.25 127 59 0.35 129 59 0.27 131 59 0.81 133 59 0.50 102 60 0.21 132 60 0.40 134 60 0.26 0.58 43 61 0.52 133 61 0.45 24 62 0.28 98 62 0.10 106 62 0.20 53 63 0.17 135 63 0.52 22 64 0.17 25 65 0.22 39 65 0.38 46 66 0.20 96 66 0.23 34 68 0.41 1.18 0.80 36 68 0.32 0.52 38 68 0.29 46 68 0.16 0.11 DEG 48 101 45 122 83 65 104 161 75 132 156 61 60 43 48 103 115 15 56 63 143 107 71 106 140 25 220 14 64 70 99 101 61 91 86 146 49 41 136 73 69 93 36 25 107 98 36 98 112 29 53 159 124 7

CH}

P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 23 24 15 22 32 10 19 16 18 17 12 20 13 16 14 10 26 11 17 11 7

23 25 21 22 14 19 16 28 21 13 18 13 23 25 19 17 7

12 12 21 11 15 20 14 14 21 35 30 19 26 16 10 7

LOCATION EXT DHT

+0.25 TEH VS2

-0.87 TEH VS2

+0.85 TEH VS3

-1.02 TEH VS3

-0.80 TEH 07C

+0.95 TEH 02H

-0.08 TEH 05H

+0.89 TEH DCB

-0.16 TEH 07H

+0.85 TEH 06H

-0.56 TEH VS3

+0.95 TEH VS4

+0.64 TEH VS3

-0.73 TEH DHB

+0.30 TEH 05H

-0.97 TEH DCB

+0.00 TEH VS3

-0.82 TEH VS4

-0.71 TEH VS1

+0.90 TEH VS3

+0.87 TEH DCT

+0.00 TEH VS1

-0.80 TEH DCB

+0.21 TEH VS3

-0.89 TEH VS3

+0.85 TEH 09H

+0.96 TEH DCT

+0.25 TEH DCT

+0.00 TEH DCB

+0.00 TEH VS4

-0.66 TEH DCT

+0.00 TEH DCT

+0.00 TEH DHB

+0.76 TEH VS3

+0.67 TEH DHT

-0.25 TEH VS3

+0.82 TEH VS2

-0.89 TEH VS1

+0.12 TEH VS3

-0.61 TEH DHT

+0.00 TEH VS3

+0.72 TEH VS3

+0.68 TEH VS3

-1.01 TEH VS3

+0.79 TEH VS4

+0.88 TEH DHB

+0.00 TEH DCB

+0.16 TEH DCT

-0.08 TEH VS3

-0.80 TEH VS3

+0.57 TEH VS3

-0.78 TEH VS3

+0.93 TEH DCT

+0.00 TEH EXT TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC CAL # LEG 52 COLD 54 COLD 7

COLD 7

COLD 7

COLD 54 COLD 53 COLD 53 COLD 53 COLD 53 COLD 53 COLD 14 COLD 56 COLD 56 COLD 55 COLD 58 COLD 58 COLD 15 COLD 55 COLD 54 COLD 13 COLD 55 COLD 58 COLD 58 COLD 12 COLD 12 COLD 55 COLD 56 COLD 57 COLD 58 COLD 56 COLD 57 COLD 58 COLD 58 COLD 13 COLD 58 COLD 13 COLD 55 COLD 55 COLD 11 COLD 58 COLD 10 COLD 11 COLD 10 COLD 11 COLD 56 COLD 10 COLD 10 COLD 10 COLD 11 COLD 11 COLD 10 COLD 10 COLD 10 COLD PROBE 600UL 60 OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 600UL 600UL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Page 4 of 10 Customer Name: St. Lucie Unit 2 Component: S/G B Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 64 68 0.18 134 68 0.34 35 69 0.35 39 69 0.62 0.17 0.61 41 69 0.36 36 70 0.82 0.43 46 70 0.82 35 71 0.72 0.51 37 71 0.83 45 71 0.69 0.49 97 71 0.62 48 72 0.48 50 72 0.27 48 74 0.13 52 74 0.26 43 75 0.43 45 75 0.42 103 75 0.22 137 75 0.23 44 76 1.12 46 76 0.38 52 76 0.67 54 76 0.49 0.45 56 76 0.88 0.46 53 77 0.24 55 77 1.02 57 77 0.33 0.16 0.31 107 77 0.33 52 78 0.58 0.39 1.46 0.46 54 78 0.76 0.76 0.29 88 78 0.31 0.64 96 78 0.40 0.17 0.78 0.33 51 79 0.51 0.56 61 79 0.26 63 79 0.25 96 143 140 121 136 148 156 130 146 141 113 52 84 82 145 55 91 104 94 165 75 114 51 147 94 70 78 152 141 103 145 111 148 130 130 158 26 127 139 144 58 132 84 102 104 34 43 28 87 31 94 150 112 136 P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 TWD P 2 IWD P 2 TWD P 2 TWD P 2 TWD 11 16 19 27 11 27 20 30 22 30 29 24 30 28 24 28 24 16 9

16 22 22 12 11 34 21 28 24 23 32 23 15 31 18 11 18 22 25 21 29 14 28 28 17 15 25 25 15 33 22 23 24 15 15 VS2

+0.79 TEH DHB

+0.00 TEH DCT

-0.21 TEC VS3

+0.51 TEC VS3

-0.61 TEC DHT

+0.00 TEC 07C

-0.89 TEC DCB

+0.00 TEC DHB

+0.00 TEC VS3

+0.84 TEC DCB

+0.00 TEC DHT

+0.00 TEC DHT

+0.00 TEC DCT

+0.00 TEC VS3

-0.77 TEC VS4

+0.64 TEH VS3

-0.74 TEC VS3

-0.70 TEC DHB

+0.11 TEC VS3

+0.97 TEC DCB

+0.34 TEC DCB

+0.00 TEC VS2

+1.00 TEH 05H

+0.90 TEH DHB

+0.00 TEC DHB

+0.00 TEC VS3

+0.75 TEC VS3

-0.81 TEC VS3

+0.77 TEC VS3

+0.68 TEC VS3

-0.81 TEC DCB

+0.00 TEC DCB

+0.00 TEC VS3

-0.87 TEC VS3

+0.71 TEC DCB

+0.51 TEC 04H

-0.42 TEH DCT

+0.00 TEC DCB

+0.00 TEC VS3

+0.85 TEC VS3

-0.96 TEC DCB

+0.00 TEC DHB

+0.00 TEC DCT

+0.00 TEC VS2

-0.90 TEH VS2

+0.76 TEH VS4

+0.74 TEH DCT

-0.25 TEH VS2

-0.76 TEH VS3

+0.36 TEH DCB

+0.00 TEC DHT

+0.00 TEC DCB

+0.00 TEC DCB

+0.00 TEC TEC TEC TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEC TEC TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEN TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEN TEH TEH TEH 10 58 12 12 12 12 11 12 12 12 12 12 11 11 11 42 11 12 12 12 12 11 43 57 12 11 12 11 11 12 12 6

5 6

6 6

39 6

6 6

6 5

5 5

44 44 39 39 39 39 5

5 5

5 COLD COLD COT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD HOT HOT HOT HOT PROBE 6

=OUL 600UL 600UL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 5 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 50 80 0.37 0.74 52 80 0.44 0.64 0.47 1.47 60 80 0.45 132 80 0.18 51 81 0.31 0.63 53 81 1.25 0.30 48 82 0.68 50 82 0.42 116 82 0.16 51 83 0.33 0.78 53 83 0.24 87 83 0.35 89 83 1.75 48 84 1.69 1.08 50 84 1.02 0.23 52 84 1.88 54 84 0.17 64 84 0.28 88 84 0.31 98 84 0.11 57 85 0.57 95 85 0.25 54 86 0.42 60 86 0.14 88 86 0.58 122 86 0.13 55 87 1.20 50 88 0.31 52 88 0.87 0.52 0.33 54 88 0.48 0.28 62 88 0.42 100 88 0.32 51 89 0.73 55 89 0.15 89 89 0.24 48 90 0.38 52 90 0.35 54 90 0.43 56 90 0.34 0.52 100 90 0.42 53 91 0.17 DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 138 108 88 145 126 100 87 153 141 129 26 26 37 74 113 32 100 28 104 112 110 103 118 23 111 108 165 159 39 125 102 43 168 64 79 93 157 108 79 42 88 149 92 163 117 160 129 84 51 63 38 57 30 168 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 20 29 21 26 22 35 22 9

17 27 33 17 27 21 8

18 29 14 23 32 36 32 33 14 37 12 16 17 11 25 19 21 9

27 9

34 19 30 24 18 22 16 21 17 28 10 14 14 18 21 18 23 15 11 DCT

+0.00 DHB

+0.00 DCT

+0.00 VS3

+0.92 VS3

-0.63 DHB

+0.00 DCB

+0.00 VS1

+0.62 DCT

+0.00 DCB

+0.00 DHT

+0.00 DCT

+0.00 DHT

+0.00 DCB

+0.00 VS4

-0.91 DCB

+0.00 DCT

+0.00 DCB

+2.99 VS3

-0.93 VS3

-0.87 DHB

+0.00 DCT

+0.00 DCT

+0.00 DHB

+0.00 DCT

-0.25 DCT

+0.00 VS3

-0.73 VS2

+0.85 VS5

-0.92 DCB

+0.00 VS2

-0.75 DCT

+0.00 VS3

-0.67 VS3

+0.74 06H

+0.87 DCT

+0.00 DHB

+0.00 VS3

+0.89 DCB

+0.39 DHT

+0.07 VS3

+0.90 VS3

-0.79 VS3

-0.77 08C

-0.93 DHB

+0.00 DHB

-0.05 VS2

-0.69 DHB

+0.00 DCB

+0.00 DCB

+0.00 VS3

-0.27 DCT

+0.02 06C

+0.04 DCT

+0.00 TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEH TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEH TEC TEC TEC TEC TEC TEH TEC TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEC TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEC TEH TEH TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEC TEH TEH TEH TEH TEH TEC TEH 6

6 5

5 5

5 5

57 6

6 5

5 5

6 41 6

6 5

39 41 5

5 6

6 5

6 5

59 39 5

39 5

3 38 37 4

3 4

4 4

3 3

4 37 4

4 37 3

3 4

3 3

38 3

HOT HOT HOT HOT NOT HOT HOT COLD HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT COLD COLD HOT HOT HOT NOT HOT HOT HOT COLD COLD HOT COLD HOT HOT COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT COLD HOT HOT HOT HOT NOT COLD HOT PROBE 600UL 60OOUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 600UL 600UL 60OUL 600UL 600UL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL

Framatome ANP Inc.

1/23/2005 08:32 Attacb ent 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 6 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 44 92 0.51 0.32 48 92 0.45 50 92 0.32 54 92 0.75 96 92 0.16 102 92 0.19 110 92 0.12 43 93 0.60 1.05 87 93 0.33 42 94 0.99 44 94 0.35 46 94 0.82 1.03 50 94 0.47 39 95 0.31 51 95 0.37 95 95 0.22 0.23 46 96 0.37 35 97 0.59 45 97 0.30 71 97 0.62 0.21 89 97 0.35 93 97 0.39 0.29 34 98 0.47 0.78 0.60 0.51 0.27 1.02 56 98 0.24 62 98 0.20 88 98 0.40 94 98 0.29 33 99 0.42 37 99 0.69 0.64 0.91 0.54 47 99 0.31 55 99 0.13 95 99 0.15 137 99 0.27 34 100 0.62 0.88 0.18 94 100 0.86 0.69 0.27 33 101 0.37 DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 104 17 125 19 97 166 40 155 128 51 97 77 33 123 130 115 62 144 143 134 160 137 341 149 163 70 144 60 78 127 123 97 32 57 152 147 60 43 31 40 67 130 48 151 161 148 129 76 78 97 119 54 29 139 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

TWD, TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 23 17 21 17 28 10 13 9

27 32 17 32 18 30 32 24 17 21 15 15 19 25 19 27 15 18 20 14 24 29 27 25 15 27 16 15 15 16 21 27 26 31 24 17 9

8 13 27 32 12 31 28 15 21 DHB

+0.00 DCT

+0.00 DHB

+0.00 DHB

+0.00 VS3

+0.78 05C

+0.84 VS4

-0.65 07C

-0.14 DCB

+0.00 DHT

+0.00 VS3

-1.00 DCB

+0.63 DCB

+0.00 VS3

-0.94 DCB

+0.00 VS3

-0.92 DCT

+0.00 07H

+0.87 VS2

+1.01 VS4

-0.64 DHB

+0.00 DHB

+0.00 VS3

-1.02 VS4

-0.73 VS2

+0.86 VS4

-0.88 VS2

+0.68 VS4

+0.74 VS3

+0.83 VS3

-0.90 DHB

+0.00 DCB

+0.09 DCT

-0.11 DHT

-0.25 VS3

+0.99 VS3

-0.82 06C

+0.85 VS2

+0.67 DCB

+0.00 DCB

+0.00 VS3

-0.07 VS3

-0.69 DHB

+0.00 VS3

-0.83 VS3

+1.19 08C

+0.82 VS1

+0.80 DHB

+0.27 DHT

-0.16 DCB

+0.47 VS2

-0.79 VS2

+0.79 VS4

+0.87 DCT

+0.00 TEC TEC TEC TEC TEC TEN TEH TEH TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEH TEH TEC TEC TEC TEC TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEB TEH TEH TEC TEC TEC TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC 3

3 3

4 4

37 38 38 3

3 37 3

4 3

3 3

4 3

38 38 4

4 3

3 3

35 35 35 3

3 3

3 3

3 3

3 35 36 4

4 4

4 4

4 4

36 58 16 16 16 26 26 26 17 HOT HOT HOT HOT HOT COLD COLD COLD NOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60OOUL 60OUL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 600UL 60O0UL

Framatome ANP Inc.

1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 7 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG 35 101 0.52 37 101 0.18 47 101 0.36 51 101 0.41 91 101 0.18 93 101 0.28 0.55 135 101 0.90 30 102 0.28 34 102 0.49 0.17 92 102 0.18 94 102 0.24 98 102 0.14 27 103 0.24 29 103 0.36 31 103 0.26 35 103 0.27 87 103 0.16 97 103 0.30 20 104 0.20 24 104 0.27 26 104 0.34 28 104 0.20 34 104 0.46 38 104 0.26 40 104 0.55 94 104 0.21 126 104 0.42 47 105 0.33 0.39 24 106 0.30 28 106 0.29 32 106 0.48 42 106 0.18 50 106 0.45 29 107 0.29 34 108 0.47 88 108 0.19 96 108 0.66 0.22 93 109 0.14 97 109 0.28 0.21 133 109 0.23 0.21 50 110 0.22 0.21 132 110 0.31 35 111 0.16 89 111 0.66 34 112 0.17 90 112 0.11 122 112 0.29 69 77 46 86 117 30 94 82 137 73 158 34 11 169 153 29 138 62 22 174 142 116 44 138 27 38 151 21 109 59 19 137 60 69 113 93 31 61 145 119 51 140 113 28 74 104 135 133 103 148 101 157 138 57 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2

==D TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 25 VS3

-0.99 12 VS3

-0.87 20 VS3

+0.86 14 VS3

+0.80 9

VS2

-0.79 15 VS3

-0.50 25 VS2

-0.94 29 VS1

+0.74 17 VS3

+0.88 24 VS3

+0.64 12 VS3

-0.84 11 VS2

+0.83 12 VS3

-0.80 8

VS4

-0.97 15 VS3

-0.76 20 VS3

-0.81 16 VS3

-0.74 17 VS3

-0.66 8

VS2

-0.92 16 DNB

+3.71 13 VS3

+0.90 17 VS3

+0.72 19 VS3

+0.80 14 VS3

+0.80 24 VS3

-0.96 16 VS3

+0.74 25 VS3

-0.87 11 08C

+0.80 14 VS1

-0.83 19 VS3

-0.60 21 VS3

+0.77 16 VS3

+0.72 16 VS3

+0.82 22 VS3

-1.01 11 VS3

-0.32 23 VS3

+0.91 16 VS3

+0.68 23 VS3

-0.89 16 05H

+0.93 30 VS2

-0.86 18 VS4

+0.86 13 VS2

-0.92 20 VS2

-0.97 17 VS2

+0.85 12 08H

+0.73 11 08H

-0.75 13 VS3

-0.89 12 VS3

+0.66 15 VS5

+0.85 11 VS3

-0.79 29 VS4

-0.71 11 VS3

-0.73 6

06H

+0.87 15 VS4

-0.88 TEN TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC 16 17 16 16 25 26 26 58 16 16 16 26 25 25 16 17 16 16 25 26 17 16 17 16 17 17 16 25 25 17 17 18 18 18 19 19 18 19 28 28 28 28 28 28 58 58 18 18 58 19 35 24 36 36 COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD PROBE 60 OUL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 600UL 600UL 60OUL 600UL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 600UL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attacbfent 8 CSI-NDE-05-020 Page 8 of 10 Customer Name: St. Lucie Unit 2 Component: S/G B Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS 126 112 0.54 128 112 0.36 25 113 0.21 96 114 1.10 1.01 0.68 0.44 0.74 0.59 51 115 0.20 52 116 0.20 0.10 54 116 0.15 19 117 0.28 89 117 0.63 0.36 32 118 0.22 54 118 0.24 112 118 0.18 96 120 0.38 0.22 5

121 0.10 51 121 0.24 0.33 97 121 0.19 94 122 0.28 102 122 0.21 52 124 0.26 54 124 0.87 62 124 0.11 94 124 0.39 0.36 55 125 0.90 36 126 0.14 94 126 0.39 0.29 0.19 93 127 0.12 95 127 0.34 88 128 0.27 85 129 0.21 95 129 0.11 1

131 0.12 87 131 0.21 95 131 0.38 39 133 0.18 111 133 0.24 54 134 0.25 0.27 60 134 0.43 88 134 0.15 104 134 0.26 55 135 0.21 87 135 0.28 DEG 36 93 129 127 99 69 140 69 147 121 152 17 32 24 52 106 138 37 19 152 79 125 12 54 13 65 72 87 25 157 61 71 113 148 80 155 22 76 69 61 65 52 171 157 83 8

32 45 106 74 27 130 30 124 C'HN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P 2 IND %TW LOCATION EXT EXT CAL # LEG

=WD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD 24 19 10 36 35 29 22 30 27 12 10 4

10 14 28 12 13 14 10 20 14 7

17 21 11 16 12 18 30 7

20 19 31 12 21 17 12 8

19 15 12 8

8 13 21 12 16 15 16 23 10 16 13 17 VS1

-0.84 DCT

-0.10 VS3

-0.72 VS2

-0.81 VS2

-0.14 VS2

+0.52 VS3

-0.89 VS3

+0.18 VS4

+0.89 VS3

+0.85 VS3

+0.92 VS3

-0.92 VS3

+1.00 VS3

+0.82 VS2

-0.85 07H

-0.88 VS3

+0.04 VS3

+0.97 VS1

+0.60 VS3

-0.89 VS3

+0.77 04C

+0.96 VS3

-0.83 VS3

+0.71 VS2

-0.80 VS2

-0.95 VS1

-0.65 VS3

-0.95 VS3

+0.00 05C

+0.98 VS2

-0.80 VS3

-0.96 VS3

-0.99 VS3

-0.93 VS2

-0.98 VS3

-0.84 VS4

+0.80 VS3

+0.60 VS2

-0.43 08C

-0.72 DHB

+0.00 VS2

+0.77 04H

+0.91 VS2

-0.67 VS2

-0.51 VS3

-0.99 05C

+0.14 VS3

-0.88 DCB

+3.72 VS3

-0.69 VS2

-0.83 VS1

+0.70 DCT

+0.00 VS2

-0.89 TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH 07H TEH TEH TEC TEH TEC TEC TEC TEH TEH TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEN TEC TEH TEH TEH TEC TEC TEH TEC 36 35 23 35 35 35 35 35 35 24 23 23 24 23 36 36 24 24 36 33 33 61 22 22 34 34 34 22 20 20 34 34 20 22 33 33 33 34 33 34 34 33 16 33 33 22 31 22 22 23 32 32 22 32 COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD COLD HOT COLD COLD HOT COLD HOT HOT HOT COLD COLD HOT COLD PROBE 6==OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 600UL 600UL 600UL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 60OUL 60OUL 600UL 600UL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Page 9 of 10 Customer Name: St. Lucie Unit 2 Component: SIG B Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN 0.15 89 135 0.14 0.15 0.37 42 136 0.27 94 136 0.39 0.15 108 136 0.60 35 137 0.34 0.25 57 137 0.17 103 137 0.14 56 138 0.20 0.19 70 138 0.56 80 138 0.22 88 138 0.29 92 138 0.18 55 139 0.88 94 140 0.18 39 141 0.40 77 141 0.29 44 142 0.27 56 142 0.38 92 142 0.36 63 143 0.22 95 143 0.60 54 144 0.22 94 144 0.37 0.13 0.30 53 145 0.15 52 146 0.13 0.14 0.34 0.15 76 146 0.21 0.34 0.15 85 147 0.27 33 151 0.11 53 151 0.16 60 152 0.24 0.16 64 152 0.39 0.21 69 153 0.26 54 154 0.37 61 155 0.10 62 158 0.10 55 159 0.31 36 162 0.15 40 162 0.35 42 162 0.41 72 15 147 114 40 132 51 126 102 34 55 14 151 164 133 143 139 24 85 15 159 30 125 156 99 147 148 63 130 156 25 162 32 66 28 168 16 59 137 69 53 22 25 36 92 39 28 30 8

68 25 152 116 98 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND

=WD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 10 10 11 22 18 21 10 28 21 17 11 10 13 12 26 15 19 13 31 12 19 17 16 19 21 13 25 13 18 7

16 10 9

10 19 10 14 19 10 14 B

11 15 11 21 14 16 11 8

7 18 10 17 20 LOCATION VS3

-0.73 VS2

+0.86 VS2

-0.64 DCB

+0.00 VS3

-0.71 VS4

+0.91 VS4

-0.28 02C

-0.85 VS3

-0.87 DHB

+0.78 VS3

+0.67 VS2

+0.60 VS3

-0.61 VS3

+0.94 VS3

+0.91 08C

-1.08 DCB

+0.00 VS2

+0.83 VS3

+0.98 VS2

+1.38 VS3

+0.87 DCT

+0.07 07C

-1.03 07C

-1.00 VS2

+0.62 VS3

-0.77 VS2

-0.65 DCT

+0.00 VS2

-0.87 VS3

-0.98 VS4

+0.81 DCB

+1.93 07C

-0.91 VS3

+0.79 VS3

-0.76 06C

+0.16 VS3

+0.80 VS2

+0.85 VS4

-0.98 VS2

-0.99 VS3

+1.08 DCB

+0.00 VS3

+0.50 VS4

-0.91 VS2

-0.53 VS4

-0.67 VS4

-0.87 VS3

+0.02 VS2

+0.64 VS3

-0.96 DHT

+0.00 01H

+0.83 01C

-0.93 01C

+0.91 EXT TEH TEH TEH TEH TEC TEH TEH TEH TEC TEC TEC TEH TEC TEC TEC TEC TEH TEH TEC TEH TEC TEC TEC TEC TEH TEC TEH TEC TEH TEH TEH TEC TEC TEC TEC TEC TEC TEC TEC TEH TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC TEC EXT TEC TEC TEC TEC TEH TEC TEC TEC TEH TEH TEH TEC TEH TEH TEH TEH TEC TEC TEH TEC TEH TEH TEH TEH TEC TEH TEC TEH TEC TEC TEC TEH TEH TEH TEH TEH TEH TEH TEH TEC TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH TEH CAL #

32 31 31 31 23 32 32 31 23 23 22 31 22 22 23 23 31 31 23 32 26 27 27 26 31 26 27 26 27 27 27 26 27 27 27 27 27 27 27 27 29 29 29 29 29 29 29 29 29 28 29 33 33 32 LEG COLD COLD COLD COLD HOT COLD COLD COLD HOT HOT HOT COLD HOT HOT HOT HOT COLD COLD HOT COLD HOT HOT HOT HOT COLD HOT COLD HOT COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 60=UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 600UL 600UL 600UL 600UL 60OUL 600UL 600UL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 60OUL 600UL 60OUL 60OUL

Framatome ANP Inc.

1/23/2005 08:32 Attacbernt 8 CSI-NDE-05-020 Page 10 of 10 Customer Name: St. Lucie Unit 2 Component: S/G B Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION 27 35 36 12 163 163 164 166 0.49 0.17 0.35 0.31 62 9

85 112 P=2 P 2 P 2 P 2 TWD TWD TWD TWD 22 10 18 16 VS3

+0.61 01H

+0.78 01C

+0.02 01C

-0.98 EXT TEC TEC TEC TEC EXT TEH TEH TEH TEH CAL #

33 33 32 33 LEG HOT HOT HOT HOT PROBE 60=OUL 60OUL 60OUL 60OUL Total Tubes

367 Total Records: 490