Technical Specifications, Issuance of Amendments 181 & 183 Revision to Standby Diesel Generator Fuel Oil Inventory TS (TACs MC4593 & MC4594)
ML051460211
Person / Time
Site: Diablo Canyon  
Issue date: 05/25/2005
From: Shukla G
NRC/NRR/DLPM/LPD4
To: Rueger G
Pacific Gas & Electric Co
SHUKLA G , NRR/DLPM/PD4, 415-8420
Shared Package
ML051520204 List:
References
TAC MC4593, TAC MC4594
Download: ML051460211 (2)


Text

Diesel Fuel Oil, Lube Oil, Starting Air, and Turbocharger Air Assist 3.8.3 3.8 ELECTRICAL POWER SYSTEMS 3.8.3 Diesel Fuel Oil, Lube Oil, Starting Air, and Turbocharger Air Assist LCO 3.8.3 The stored diesel fuel oil, lube oil, starting air, and turbocharger air assist subsystems shall be within limits for each required diesel generator (DG). The fuel level for the stored diesel fuel oil shall be within the following limits:

a.

Combined storage of 2 79,000 gal for two units in MODES 1, 2, 3, and 4; or

b.

Combined storage of

1.

2 41,000 gal for one unit (if any) in MODES 1, 2, 3, and 4; and

2.

2 31,000 gal for each unit in MODES 5 and 6.

nI--T-I I

I s

M v

, c_ _ _ _

The performance of diesel fuel oil tank cleaning requires one fuel oil storage tank to be removed from service to be drained and cleaned.

During this time, the fuel oil storage requirement for one unit operation in MODES 1, 2, 3, and 4 and one unit operation in MODE 6 with at least 23 feet of water above the reactor vessel flange or with the reactor vessel defueled is 2 41,000 gallons. The tank being cleaned may be inoperable for up to 10 days. For the duration of the tank cleaning, temporary onsite fuel oil storage of > 25,000 gallons will be maintained. Prior to removal of a tank from service, the offsite circuits required by LCO 3.8.1 or 3.8.2 will be verified to be OPERABLE.

I I

APPLICABILITY:

When associated DG(s) is required to be OPERABLE.

DIABLO CANYON UNITS 1 & 2 3.8-14 Unit 1 - Amendment No. 435, 181 Unit 2 - Amendment No. 435, 183

ACTIONS Diesel Fuel Oil, Lube Oil, Starting Air, and Turbocharger Air Assist 3.8.3 NOTE-----

Separate Condition entry is allowed for each DG or fuel oil storage tank, except for Condition A.

CONDITION REQUIRED ACTION COMPLETION TIME A. Combined fuel level in A.1.1 Verify combined fuel oil Immediately storage tanks not within level 2 36,000 gallons for limits.

each unit operating in MODES 1, 2, 3, or 4, AND A.1.2 Verify combined fuel oil Immediately level Ž 27,000 gallons for each unit operating in MODES 5 or 6.

AND A.2 Restore fuel oil level to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> within limits.

B. Both units in MODE 1, 2, 3, B.1 Restore lube oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or 4 with lube oil inventory <

inventory to within limits.

650 gal and > 610 gal.

OR One unit in MODE 1, 2, 3, or 4 and one unit in MODE 5 or 6 with lube oil inventory

< 590 gal and > 520 gal.

C. One or more fuel oil storage C.1 Restore fuel oil total 7 days tanks with stored fuel oil particulates within limits.

total particulates not within limit.

D. One or more fuel oil storage D.1 Restore stored fuel oil 30 days tanks with new fuel oil properties to within properties not within limits.

limits.

E. One or more DGs with both E.1 Restore one starting air 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> starting air receiver receiver pressure per pressures < 180 psig and DG to > 180 psig.

2 150 psig.

(continued)

I DIABLO CANYON UNITS 1 & 2 3.8-15 Unit 1 - Amendment No. 435, 181 Unit 2 - Amendment No. 435, 183