ML051360118
| ML051360118 | |
| Person / Time | |
|---|---|
| Site: | Quad Cities |
| Issue date: | 04/30/2005 |
| From: | Farahyar A, Hwang H, Schrag M General Electric Capital Corp |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| DRF 0000-0035-5078, Class I, GENE-0000-0034-6964-01R2-NP, Rev 2 | |
| Download: ML051360118 (68) | |
Text
ENCLOSURE 2 ATTACHMENT 3 "Structural Design Evaluation of Quad Cities New Dryer Instrumentation Mast," GENE-0000-0034-6964-01 R2-NP, Revision 2, Non-Proprietary, dated April 2005
GE Nuclear Energy General Electric Company 175 Curtner Avenue, San Jose, CA 95125 GENE-0000-0034-6964-01 R2-NP Revision 2 Class I April 2005 DRF 0000-0035-5078 Structural Design Evaluation of Quad Cities New Dryer Instrumentation Mast Prepared by:
Ayoub Farahyar Verified by:
Henry Hwang Approved by:
M. R. Schrag, Manager, Structural Analysis & Hardware Design
/
I 4
-
4
GENE-0000-0034-6469-01 R2-NP PROPRIETARY INFORMATION NOTICE This is a non-proprietary version of the document GENE-0000-0034-6964-01R2-P which has the proprietary information removed. Portions of the document that have been removed are indicated by an open and closed bracket as shown here ((
)).
IMPORTANT NOTICE REGARDING CONTENTS OF THIS REPORT Please Read Carefully The only undertaking of General Electric Company respecting information in this document are contained in the contract between Exelon Corporation and General Electric Company, and nothing contained in this document shall be construed as changing the contract. The use of this information by anyone other than Exelon Corporation or for any purpose other than that for which it is intended is not authorized; and with respect to any unauthorized use, General Electric Company makes no representation or warranty, and assumes no liability as to the completeness, accuracy, or usefulness of the information contained in this document.
ii
GENE-0000-0034-6469-01 R2-NP Revision Status Revision Date Description 0
Dec.
Issued 2004 1
Feb.
Issued with additional 2005 references 2
April Issued with additional 2005 information to response to customer's comments iii
GENE-0000-0034-6469-01 R2-NP Table of Contents 1.0 Introduction..................................................................
1 1.1 Description.................................................................. l 1.2 Scope................................................................. lI 1.3 Purpose................................................................... l FIGURE 1-1. Dryer Mast Pipe With Stabilizer Support Brackets...................................... 2 FIGURE 1-2. Penetration Assembly and Interface Area for 0.375 inch Conduit Pipe....... 3 2.0 Conclusions and Interface Requirements..................................................................
4 2.1 Code Compliance...................................................................
4 2.2 Design Margin..................................................................
4 Figure 2.3 Interface location for the Conduit Pipe With RPV................................ 5 2.3 Interface Requirements..................................................................
6 2.3.1 Penetration Bolt Force and Moments............................................................. 6 2.3.2 Conduit supports..................................................................
6 2.3.3 Dryer top hood support bolt loads.................................................................. 6 3.0
References:
6 4.0 Input Data...................................................................
6 4.1 Mechanical Properties...................................................................
7 4.2 Dryer Mast Configurations..................
7..........,..7 4.3 Operating and Design Temperatures............................
7 4.4 Loads............................
7 4.4.1 Design Pressure and Acoustic Pressure...........................................
7 4.4.2 Dead Weight...........................................
7 4.4.3 Drag Force and Vortex Shedding...........................................
7 4.4.4 Seismic Load...........................................
9 4.4.5 Thermnal Expansion Load...........................................
9 5.0 Load Combinations and Acceptance Criteria...........................................
9 6.0 Methods...........................................
9 6.1 Modeling Techniques...........................................
9 6.1.1 PISYS07D Modeling...........................................
9 6.1.2 ANSYS Modeling...........................................
9 iv
GENE-0000-0034-6469-01 R2-NP 6.1.3. Boundary Conditions...................................................................
10 6.2 Analysis..................................................................
10 6.3 Computer Programs..................................................................
10 6.3.1 PISYS07D...................................................................
11 6.3.2 ANS1713D..................................................................
11 7.0 Evaluation of Results..................................................................
11 7.1 Modal Analysis Results..................................................................
11 7.2 Stress Analysis Results..................................................................
11 7.2.1 Piping Stress Analysis Results................................................................... 11 7.2.1.1 Pressure Design..................................................................
11 7.2.1.2 Stress Analysis Results..................................................................
12 7.2.2 Stabilizer Bracket Stress Analysis Results................................................ 12 7.2.2 Weld Stress Analysis Results..................................................................
12 7.2.3 Support Bracket Bolt Stress Analysis Results........................................... 14 List of Tables...................................................................
15 Table 4.1 Material Properties...................................................................
15 Table 4.2 Dimensional Properties for Dryer and Conduit Pipes...................................... 16 Table 4.3 Definition of Loads..................................................................
17 Table 4.4 Nomenclature and Units for Appendices........................................................... 17 Appendices..................................................................
19 Appendix A: Isometric Diagram and ANSYS Model....................................................... 19 Figure A-I: Conduit Pipe Isometric..................................................................
20 Figure A-2: ANSYS Finite Element Model of Short Stabilizer Brackets (node Number)21 Figure A.3 ANSYS Finite Element Model of Long Stabilizer Bracket (node number).... 22 Figure A-4: ANSYS Finite Element Model..................................................................
23 Appendix B: Load Combinations and Acceptance Criteria....................................................
24 Table B-I Load Combination and Criteria for Dryer Mast Design................................... 24 Appendix C: Details of Piping Stress Analysis to Meet NC-3600............................................
26 Appendix C-I Pressure Boundary Conduit Pipe (0375 inch O.D.)................................. 26 Appendix C-2 Non-Pressure Boundary Conduit Pipe (0375 inch O.D.).......................... 35 Appendix C-3 Non-Pressure Boundary Conduit Pipe (4.0 inch O.D.)............................ 40 V
GENE-0000-0034-6469-01 R2-NP Appendix C-4 Pressure Boundary Conduit Pipe (0375 inch O.D.) Forces, moments and displacements..........................................................
46 Appendix D: Summary of Stresses to Meet NC-3600..........................................................
49 Arranged From Input Sequences..........................................................
49 Arranged From Highest Stress to Lowest stress..........................................................
50 Appendix E: List of Natural Frequencies..........................................................
52 List of natural frequencies..........................................................
52 Appendix F: External Forces and Moments..........................................................
54 F-1 External Forces and Moments on the Penetration Bolts Per Conduit......................... 54 F-2 Reaction Loads at Dryer Mast/Dryer Interface.......................................................... 55 Appendix G: Principal Stresses for Stabilizer Brackets.........................................................
58 Figure G-1, Location of Maximum Principal Stresses for Stabilizer Brackets................. 58 Figure G-2, Short Stabilizer Bracket (element no.).......................................................... 60 Figure G-3, Long Stabilizer Bracket (element no.).......................................................... 61 vi
GENE-0000-0034-6469-01 R2-NP 1.0 Introduction 1.1 Description The dryer mast is used to support the conduit tubes for instrumentation sensor wires. The dryer mast includes a 4 inch tube which is connected to the dryer top hood through 3 stabilizer support brackets as shown in Figure 1-1. There are 12 conduit tubes, which are attached to the dryer mast through the dryer stiffening plates. These conduit tubes are used to protect Inconel alloy sensor wires of ((
)) for the strain gauges and ((
)) for the pressure gauges and accelerometers.
1.2 Scope The scope of this analysis is the dryer mast from dryer top hood connecting plate, 4" mast tube and all the conduit tubes for instrumentation sensors to the seal weld at the tube sealing cap. The RPV flange and the penetration bolt analyses are excluded from the scope of this analysis. The pressure boundary as shown in Figure 1-2 is the ASME Class 1. Per ASME Section III paragraph NB-3630(d)(1), for Class 1 piping of 1 in. nominal pipe size or less may be analyzed in accordance with the NC-3600 Class 2 component. The conduit tube below the seal header is not a pressure boundary.
Since the mast is considered as a continuation of the dryer, it is considered as an ASME Class component, and this analysis will show that the NC-3600 requirements are satisfied. The stabilizer support brackets and the supporting plates to support the conduit tubes are under the jurisdiction boundary of the ASME Section NF Code.
1.3 Purpose During operation, differential thermal expansion due to the dryer mast having a higher coefficient of thermal expansion than the reactor pressure vessel (RPV) induces the load in the dryer mast. Also pressure and steam flow velocities acting across the dryer mast, as well as seismic acceleration, act to increase the load and stress.
The 0.375" diameter conduit tubes and the 4"diameter mast tube are in tube schedule. However, these tubes are called piping in the ASME code. Because the purpose of this analysis is to show that these components meet the NC-3600 piping code requirement, the conduit tube is referred to as a pipe throughout this report.
The purpose of this report is to analytically demonstrate the structural integrity of the dryer mast design including conduit pipes meeting NC-3600 design requirements. The load combinations for the design requirements and operating condition include gravitational, thermal, pressure, steady state drag forces, fluid-induced vibration, and earthquake loads.
Page 1 of 61
GENE-0000-0034-6469-01 R2-NP FIGURE 1-1. Dryer Mast Pipe With Stabilizer Support Brackets Page 2 of 61
GENE-0000-0034-6469-01 R2-NP Ft FIGURE 1-2. Penetration Assembly and interface Area for 0.375 inch Conduit Pipe Page 3 of 61
GENE-0000-0034-6469-01 R2-NP 2.0 Conclusions and Interface Requirements ANSYS finite element code and PISYS07D were used to evaluate the dynamic and static response of the dryer mast. ANSYS was used to evaluate the response of the stabilizer supports and PISYS07D was used for the piping system. The output from PISYSO7D program with ANSI713D program is used to calculate stresses in accordance with the ASME NC-3600 Piping code. Six load combinations were evaluated for each component as described in Table B-I.
2.1 Code Compliance Results of the analysis in Appendix C show that the requirements (equations) of ASME Section III Class II Components and NC-3600 have been met for all the pipe components.
A summary of pipe stresses for the dryer mast and conduit is presented in Appendix D. Two tables are provided for each section. The first table tabulates the summary of stresses in the ANSI7 joint input sequence. The second table arranges the stress ratios from the highest stress to the lowest stress value Within the scope of this report, design of the dryer mast meets the requirements of ASME Section III NF-3600. The stress ratios for each location are summarized in Appendix C. The dryer mast pipe, conduit pipes, and stabilizer supports have adequate margins for primary and secondary stresses.
2.2 Design Margin The maximum stress ratios (max calculated stress/allowable) for each load combination for the various component types are tabulated below from Appendix D. Load combination and acceptance criteria are presented in Table B-I Appendix B.
Level A Level B Thermal Thermal Level C Level D (Sustained)
(Ocasonal)
+FIV
+Sustained Conduit Pipe (Pressure Boundary)
Dryer Mast Pipe Stabilizer Support I
Page 4 of 61
GENE-0000-0034-6469-01 R2-NP Figure 2.3 Interface location for the Conduit Pipe With RPV Page 5 of 61
GENE-0000-0034-6469-01 R2-NP 2.3 Interface Requirements 2.3.1 Penetration Bolt Force and Moments The external forces and moments on top of the penetration bolt are summarized in Appendix F-1.
These external forces and moments are provided to the responsible engineering group to address the stresses in the penetration bolt and RPV flange.
Figure 2.3 presents the interface for the conduit pipe with RPV top flange including penetration bolt assembly. The forces and moments for the RPV top flange are calculated for the location of node 32 in Figure 2.3. Nodes 25 and 26 are for the coupling tube location in Figure 2.3.
2.3.2 Conduit supports As shown in Figure 1-1, these conduit pipes are laterally supported by the plates, which are welded to the 4" mast tube. Due to thermal expansion of the conduit from the top of the penetration bolt, the support plate should allow the conduit to move in the axial direction. Refer to the Figure A-1 in Appendix A, which shows that the conduit tube at the bottom should have a ((
)) to absorb the thermal movement, from node 1 to 2N in this figure.
2.3.3 Dryer top hood support bolt loads Refer to Figures A-2 and A-3 for the node number in the dryer mast model. All the support loads are tabulated in Appendix F-2.
3.0
References:
- 1. ASME Section III, Class II Components, NC-3600, 1995 Edition.
- 2.
Mechanics of Fluids, Merle C. Potter and David C. Wiggert, Prentice Hall, 1991.
- 3.
ANSYS Release 6.1, ANSYS, Incorporated, 2001.
4.0 Input Data The geometries of the dryer mast design with conduit pipe were obtained from the mast drawings.
Page 6 of 61
GENE-0000-0034-6469-01 R2-NP 4.1 Mechanical Properties The dryer mast, conduit pipes, and stiffening plates are composed of stainless steel alloy SA240, 304 L. The material properties for SA240, 304 L are presented in Tables 4.1. The dimensional properties of the piping system are presented in Table 4.2.
It should be mentioned that the plate material for the 4 inch dryer mast is specified as stainless steel alloy ASTM A312 type 304 L. This material is identical with the same heat treatment conditions as SA240,304 L.
4.2 Dryer Mast Configurations ANSYS finite element model and PISYS07D isometric joint diagrams showing the piping configurations are found in Appendix A.
4.3 Operating and Design Temperatures The operating and design temperatures for the dryer mast design are 550 F and 575 F, respectively.
4.4 Loads The static and dynamic loads acting on the dryer mast design are defined in Table 4.3.
4.4.1 Design Pressure and Acoustic Pressure The design pressure load acting on the dryer mast is 1250 psi (see Table 4.2). The acoustic differential pressure across the conduit and dyer mast piping is negligible. Also the peak frequency of the acoustic excitation force is significantly higher than the first mode frequency of the conduit pipe ((
)). Therefore, the acoustic pressure associated with FIV load is not considered in this analysis.
4.4.2 Dead Weight The dead weight loads acting on the dryer mast are defined in Table 4.2. The weight of conduit and dryer mast pipes and instrumentation wires are shown in Table 4.2.
4.4.3 Drag Force and Vortex Shedding Page 7 of 61
GENE-0000-0034-6469-01 R2-NP 1]
The flow over the cylinder creates unsteady Strouhal and buffeting lifting force (FL') perpendicular to the flow direction and Strouhal and buffeting drag force (FD') in the direction of the flow. These unsteady forces are a small fraction of the drag force.
The first natural frequency of the dryer mast is ((
)), which is significantly lower than the vortex shedding frequency at the top of the dryer. Therefore, the flow velocity does not have enough energy to cause significant fatigue damage.
Page 8 of 61
GENE-0000-0034-6469-01 R2-NP 4.4.4 Seismic Load The seismic coefficients are ((
)) in the horizontal directions and ((
)) in the vertical direction for the operating Base Earthquake (OBE). The seismic coefficients for safety shutdown (SSE) are twice of the OBE.
4.4.5 Thermal Expansion Load During operation, differential thermal expansion due to the dryer mast having a higher coefficient of thermal expansion than the reactor pressure vessel (RPV) induces the load in the dryer mast. Thermal expansion load is calculated from 75 deg. F-to design temperature of 575 deg. F. The relative anchor.
displacements between the top hood of the dryer and the RPV flange are also included in the analysis.
5.0 Load Combinations and Acceptance Criteria The load combination and acceptance criteria for the dryer mast design are shown in Table B-I Appendix B.
6.0 Methods 6.1 Modeling Techniques 6.1.1 PISYS07D Modeling 6.1.2 ANSYS Modeling Page 9 of 61
GENE-0000-0034-6469-01 R2-NP 6.1.3. Boundary Conditions
))
6.2 Analysis ANSYS finite element code and PISYS07D were used to calculate the dynamic and static response of the dryer mast. ANSYS was used to evaluate the response of the stabilizer supports and PISYS07D was used for the piping system. The output from PISYS07D program with ANSI713D program is used to calculate stresses in accordance with ASME NC-3600 code. Six load combinations were evaluated for each component as described in Table b-I Appendix B.
6.3 Computer Programs The computer programs used in the piping stress analysis are described below. All of these programs meet GE Quality Control Standards. All programs have been approved for production use after independent review and verification. Any changes to these programs require verification and approval in accordance with GE Quality Assurance Program. The programs listed below operate on a DEC/Alpha Station running DEC UNIX.
Page 10 of 61
GENE-0000-0034-6469-01 R2-NP 6.3.1 PISYS07D GE's proprietary computer program, PISYS07D, was used to calculate the response of the piping system to all of the static and dynamic loads.
6.3.2 ANSI713D The output from the PISYS07D program was evaluated by another GE proprietary computer program, ANSI713D. The ANSI713D program calculates stresses and cumulative usage factors, as applicable, for Class 1, 2 and 3 and ASME B31.1 piping components in accordance with applicable codes. This program also calculates combined loads on piping equipment and compares them with the allowable loads where applicable.
7.0 Evaluation of Results 7.1 Modal Analysis Results ANSYS finite element modal analysis is presented in Appendix E. Modal Analysis results indicate that the first bending mode occurs at ((
)). This bending mode is associated with the bending of conduit pipe at the mast dryer pipe attached area.
7.2 Stress Analysis Results 7.2.1 Piping Stress Analysis Results 7.2.1.1 Pressure Design The minimum wall requirement of NC-3133.8 for the 0.375 inch tube and 0.568 inch coupling tube under external pressure is determined in accordance with Fig. NC-3133.8-1. Based on this figure, the minimum wall tube and coupling wall tube under external pressure can be calculated below.
Page 11 of 61
GENE-0000-0034-6469-01 R2-NP The calculated required minimum pipe wall and nominal pipe wall values are provided in Table 4.2. It can be seen that the minimum thickness for these components are greater than the calculated minimum wall thickness. Thus the code requirement has been met.
7.2.1.2 Stress Analysis Results The piping was analyzed in accordance with the requirements of ASME NC-3600 Piping Code by the PISYS computer programs. This program produces structural solutions based on the applied loading, inputs, and modeling techniques described in the previous sections. The solutions are post-processed to be compared to the material allowable values. The interface loads (forces and moments) acting on the pipe are also generated.
The detailed stress analysis results meeting NC-3650 equations are listed in Appendix C. It is noted that the pressure stresses listed for each component are the longitudinal stress in the Code equations.
The pressure acting on the conduit is external pressure. Because the stress analysis from the NC-3600 equations uses an absolute sum, only positive values are listed. A summary of pipe stresses for the dryer mast and conduit are presented in Appendix D. Two tables are provided for each section. The first table tabulates the summary of stresses in the ANSI7 joint input sequence. The second table arranges the stress ratios from the highest stress to the lowest stress value. The external forces and moments on the top flange and the reaction loads at the dryer interface are summarized in Appendix F.
7.2.2 Stabilizer Bracket Stress Analysis Results The results of stress analysis for the stabilizer brackets are presented in Appendix G. The node number for theses brackets are presented in Figures A-2 and A-3.
7.2.2 Weld Stress Analysis Results 7.2.2.1 Support Bracket The support bracket is ((
)) and it is welded to the dryer mast tube (4 inch diameter) using a ((
]J weld. The weld strength capability is calculated as:
Page 12 of 61
GENE-0000-0034-6469-01 R2-NP Using the minimum weld shear strength of 30X0.3= 9 ksi with the combined bending and shear stress results in load capability of ((
)) for each side of the bracket. Each side of the bracket supports six conduit pipes. The actual loads for these six conduit pips at support bracket are significantly less than ((
)). Therefore, there is significant margin of safety for the welded region.
7.2.2.2 BASE Bracket The base bracket is I inch thick and it is welded to the dryer using ((
strength capability is calculated as:
((
)). The weld Page 13 of 61
GENE-0000-0034-6469-01 R2-NP Maximum combined shear and tension stress= ((
))
Using the minimum weld shear strength of 30x0.3= 9 ksi, there is significant margin of safety for the welded region 7.2.2.3 Short and Long Gussets The stresses for the short and long gussets are very small compared to weld strength capability.
7.2.3 Support Bracket Bolt Stress Analysis Results The support brackets are used to attach the dryer mast to the dryer using ((
)) bolts made of the ASTM A479, 304 L. The tensile strength capability of the ((
)) bolts in each bracket is:
The loads for the support bracket attached to the dryer are presented in Appendix F. These loads and combined resultant loads are significantly less than the tension capability of ((
)).
Page 14 of 61
GENE-0000-0034-6469-01 R2-NP List of Tables Table 4.1 Material Properties Ia(8) 1 Modulus of Material Temp X 10i6 l (7)
Sh(3)
Sy(4)
Elasticity Material No.
(0F)
(OF)
J (Ksi)
(Ksi)
(ksi)
(ksi)
SA213 and 240, 1
575(1) 9.45 14.1 14.6 25.9E+6(5 )
304L orASTM A312 type 304 L (Dryer Mast Pipe, 25 25.0 28.3E+6(6)
Conduit Pipes, 550(2)
Stabilizer Supports)
- 1. Design Temperature
- 2.
Operating Temperature
- 3.
Sh Allowable Stress at Design Temperature
- 4.
Sy= Yield stress
- 5.
Ec = Modulus of Elasticity at 70'F
- 6.
Eh Modulus of Elasticity at Operating Temperature
- 7.
Sc = Allowable stress at 70'F
- 8. a = Mean Coefficient of Expansion at Operating Temperature Page 15 of 61
GENE-0000-0034-6469-01 R2-NP Table 4.2 Dimensional Properties for Dryer and Conduit Pipes Pipe Line Conduit Pipe Dryer Mast Coupling Pipe Tube Pipe Line Tube Tube Tube Nom. tube Size - takeoff 0;375 4.0 0.568 (in)
Nom. tube OD (in) 0.375 4.0 0.568 Nom. tube ID (in) 0.275 3.364 0.440 Nom. Wall tnom (in) 0.050 0.318 0.064 Tube min. wall, 0.044 0.056 Tube Schedule Material Type 1
1 1
Required min. wall, tmc 0.035 0.053 per Code Design Press. (psi) 1250 0
1250 Design Temp. (0F) 575 575 575 Tube weight (Ibm/ft) 0.174 12.60 0.66 Wires Weight (Ibm/ft) for 3 0.520 1.06 wires Pipe Weight Total (Ibm/ft) 0.226 12.60 For material type, please see section 4.1.
Page 16 of 61
GENE-0000-0034-6469-01 R2-NP Table 4.3 Definition of Loads Load Type Cases3)l Ident(3) J Direction( J Description Pressure PD Design Pressure Thermal 1
TE1 Thermal Expansion Loads Weight l
1 VT1 Y
Dead Weight OBEI 1, 2 OBEI X, Z Operating Basis Earthquake - Inertia Effect SSEI 1,2 SSEI X, Z Safe Shutdown Earthquake - Inertia Effect
- 1) X, Y and Z directions correspond to the global X, Y and Z directions shown on the stress isometric diagrams in Appendix A.
Table 4.4 Nomenclature and Units for Appendices ANC
=
Anchor identification in structural analysis COMB
=
Service level equation number as shown on load combination table Dx, Dy, Dz
=
Global displacement in X, Y, Z directions (inch)
=
Local force A, B, C directions (Ibs)
F/M
=
Force (Newton) and moment (lbs-in)
FX, FY, FZ
=
Global force in X, Y, Z directions (Ibs)
GGD
=
Guide identification in structural analysis (Global coordinates)
GUD
=
Guide identification in structural analysis (Local coordinates)
HAN
=
Spring Hanger identification in structural analysis LOAD
=
Calculated load (Ibs)
MA, MB, MC* =
Local moment in A, B, C directions (lb-in)
MX, MY, MZ =
Global moment in X, Y, Z directions (lb-in)
There are two types of elements that the PISYS computer program uses to form the pipe model. One is the straight or tangent element and the other is a planar bend element. Each element has local coordinate axes that orient the element in the global coordinate system and identify force and moment components at a joint with respect to element axis. Joint displacements and rotations are in global coordinates. The convention for the orientation of local axes is as follows:
- 1. Tangent elements parallel to the global Y-axis (vertical axis) have their local B-axis diverted to and in the same direction as the global Z-axis.
Page 17 of 61
GENE-0000-0034-6469-01 R2-NP
- 2.
Tangent Elements not parallel to the global Y-axis have their local B-axis contained in a vertical (global) plane such that local B-axis projects positively on the positive global Y-axis.
- 3.
For bend elements, the local B-axis is directed positively toward and intersects the center of curvature of the bend (i.e., radius vector).
- 4. The local A-axis is tangent to the arc ofthe bend or straight element and is directed positively from the FROM joint to the TO joint.
Page 18 of 61
GENE-0000-0034-6469-01 R2-NP Appendices Appendix A: Isometric Diagram and ANSYS Model Page 19 of 61
GENE-0000-0034-6469-01 R2-NP Figure A-1: Conduit Pipe Iso-metric Page 20 of 61
GENE-0000-0034-6469-01 R2-NP Ff Figure A-2: ANSYS Finite Element Model of Short Stabilizer Brackets (node Number)
Page 21 of 61
GENE-0000-0034-6469-01 R2-NP Figure A.3 ANSYS Finite Element Model of Long Stabilizer Bracket (node number)
Page 22 of 61
GENE-0000-0034-6469-01 R2-NP Figure A-4: ANSYS Finite Element Model Page 23 of 61
GENE-0000-0034-6469-01 R2-NP Appendix B: Load Combinations and Acceptance Criteria Table B-1 Load Combination and Criteria for Dryer Mast Design 1
1 Acceptance Criteria Load Combination Condition PD + WT + FDRAG Service Level A EQ. 8 < 1.5 Sh PM + WT + FDRAG + OBEI Service Level B EQ. 9 < 1.8 Sh, but not greater than 1.5 Sy Thermal Expansion + FIV Thermal +FIV EQ. 10 < SA PD + VVT + FDRAG + Thermal Expansion Thermal+ Sustained EQ. 11 * (Sh + SA)
PM + WT + FDRAG + SSEI Service Level D EQ. 9 < 3.0 Sh, but not greater than 2.0 Sy PM + WT+ FDRAG Service Level C EQ. 9 < 2.25Sh But not greater than 1.8 Sy Page 24 of 61
GENE-0000-0034-6469-01 R2-NP FDRAG Steady state flow drag force due to 9.4 ft/sec flow.
PD= Design Pressure PM= Operating Pressure OBEI Operation Base Earthquake (Inertia Effect)
SSEI = Safe Shutdown Earthquake (Inertia Effect)
SA= Allowable Stress range for expansion stresses Sh= Basic Material Allowable Stress at Design Temperature Sy=Yield Strength Value, taken at average fluid temperature of transient under consideration WT=Dead Weight Page 25 of 61
GENE-0000-0034-6469-01 R2-NP Appendix C: Details of Piping Stress Analysis to Meet NC-3600 Appendix C-1 Pressure Boundary Conduit Pipe (0375 inch O.D.)
DATE 12-16-2004 RESUL1 0
QC dry mast conduit PAGE 9
QC dry mast conduit Page 26 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl 0
QC dry mast conduit PAGE 10 QC dry mast conduit Page 27 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl 0
QC dry mast conduit PAGE 11 QC dry mast conduit Page 28 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl 0
QC dry mast conduit PAGE 12 QC dry mast conduit Page 29 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESUL1 F
QC dry mast conduit PAGE 13 QC dry mast conduit Page 30 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl U
QC dry mast conduit PAGE 14 QC dry mast conduit
))
Page 31 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl 5
QC dry mast conduit PAGE 15 QC dry mast conduit Page 32 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl O
QC dry mast conduit PAGE 16 QC dry mast conduit
))
Page 33 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESUL1 U
QC dry mast conduit PAGE 17 QC dry mast conduit Page 34 of 61
GENE-0000-0034-6469-01 R2-NP Appendix C-2 Non-Pressure Boundary Conduit Pipe (0375 inch O.D.)
DATE 12-16-2004 RESULl 0
QC dry mast conduit PAGE 28 QC dry mast conduit
))
Page 35 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESUL1 0
QC dry mast conduit PAGE 29 QC dry mast conduit Page 36 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULt 0
QC dry mast conduit PAGE 30 QC dry mast conduit Page 37 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULI 0
QC dry mast conduit PAGE 31 QC dry mast conduit Page 38 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESUL1 E
QC dry mast conduit PAGE 32 QC dry mast conduit
))
Page 39 of 61
GENE-0000-0034-6469-01 R2-NP Appendix C-3 Non-Pressure Boundary Conduit Pipe (4.0 inch O.D.)
DATE 12-16-2004 RESULl 5
QC dry mast conduit PAGE 43 QC dry mast 4"-Tube Page 40 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULI 0
QC dry mast conduit PAGE 44 QC dry mast 4"-Tube
((
Page 41 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl 0
QC dry mast conduit PAGE 45 QC dry mast 4"-Tube
))
Page 42 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULt U
QC dry mast conduit PAGE 46 QC dry mast 4"-Tube Page 43 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESUL1 U
QC dry mast conduit PAGE 47 QC dry mast 4"-Tube Page 44 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 RESULl f
QC dry mast conduit PAGE 48 QC dry mast 4"-Tube Page 45 of 61
GENE-0000-0034-6469-01 R2-NP Appendix C-4 Pressure Boundary Conduit Pipe (0375 inch O.D.) Forces, moments and displacements FROM TO JOINT TYPE CASE FORCES MOMENTS DEFLECTIONS JOINT NO NO FA FB FC MA MB MC X
Y Z
NO
((
Page 46 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 COORD QC dry mast conduit FROM JOINT TYPE CASE NO NO FA
((1 PAGE 5
QC dry mast conduit FORCES FB FC MOMENTS MB DEFLECTIONS x
Y TO JOINT Z
NO MA MC Page 47 of 61
GENE-0000-0034-6469-01 R2-NP DATE 12-16-2004 COORD QC dry mast conduit FROM JOINT TYPE CASE NO NO FA
((
PAGE 6
QC dry mast conduit FORCES FB FC MOMENTS MB DEFLECTIONS x
Y TO JOINT Z
NO MA MC Page 48 of 61
GENE-0000-0034-6469-01 R2-NP Appendix D: Summary of Stresses to Meet NC-3600 Arranged From Input Sequences 0.375 inch Conduit Pipe Pressure Boundary
((
))
0.375 inch Conduit Pipe non Pressure Boundary DATE 12-16-2004 FINAL U
OC dry mast conduit QC dry mast conduit
((
PAGE 33 Page 49 of 61
GENE-0000-0034-6469-01 R2-NP Arranged From Highest Stress to Lowest stress 0.375 inch Conduit Pipe pressure boundary 0.375 inch Conduit Pipe non pressure boundary DATE 12-16-2004 FINAL 0
QC dry mast conduit QC dry mast conduit
((
PAGE 34 Page 50 of 61
GENE-0000-0034-6469-01 R2-NP 4 inch Dryer Mast pipe DATE 12-16-2004 FINAL QC dry mast conduit QC PAGE 50 0
dry mast 4"-Tube
((
1]
Page 51 of 61
GENE-0000-0034-6469-01 R2-NP Appendix E: List of Natural Frequencies List of natural frequencies
- FREQUENCIES FROM BLOCK LANCZOS MODE FREQUENCY (HERTZ)
FREQUENCY RANGE REQUESTED=
5.00000
((
ITERATION ***
5000.00 Page 52 of 61
GENE-0000-0034-6469-01 R2-NP BT Block Lanczos CP Time (sec) =
Block Lanczos ELAPSED Time (sec) =
0.437 0.437 Page 53 of 61
GENE-0000-0034-6469-01 R2-NP Appendix F: External Forces and Moments F-I External Forces and Moments on the Penetration Bolts Per Conduit
((
((
Page 54 of 61
GENE-0000-0034-6469-01 R2-NP F-2 Reaction Loads at Dryer Mast/Dryer Interface Page 55 of.61
GENE-0000-0034-6469-01 R2-NP Service Level A
((
Service Level B Lt Load Case 3, FIV + thermal expansion
))
Load Case 4, Sustained +thermal expansion
))
Page 56 of 61
GENE-0000-0034-6469-01 R2-NP Service Level C S
e Service Level D
))
Page 57 of 61
GENE-0000-0034-6469-01 R2-NP Appendix G: Principal Stresses for Stabilizer Brackets (See Figures G-1, G-2 and G-3 for location of maximum stresses)
((
))
Figure G-1, Location of Maximum Principal Stresses for Stabilizer Brackets Page 58 of 61
GENE-0000-0034-6469-01 R2-NP Service Level A MAXIMUM VALUE ELEM
((
))
VALUE Stress Ratio
((
Service Level B MAXIMUM VALUES ELEM
((
]
VALUE Stress Ratio
((
]
FIV+ thermal expansion MAXIMUM VALUES ELEM
((
))
VALUE
[
Stress Ratio
[
Thermal expansion +sustained MAXIMUM VALUES ELEM
((
))
VALUE Stress Ratio
((
Service Level C MAXIMUM VALUES ELEM
((
))
VALUE Stress Ratio
((
]
Service Level D MAXIMUM VALUES ELEM
((
))
VALUE Stress Ratio
((
Page 59 of 61
GENE-0000-0034-6469-01 R2-NP Figure G-2, Short Stabilizer Bracket (element no.)
Page 60 of 61
GENE-0000-0034-6469-01 R2-NP Figure G-3, Long Stabilizer Bracket (element no.)
Page 61 of 61