i-X Tennessee Valley Authority, Post Office Box 2000, Soddy-Daisy, Tennessee 37384-2000 September 20, 2004 U.S. Nuclear Regulatory Commission ATTN:
Document Control Desk Washington, D.C. 20555 Gentlemen:
In the Matter of
)
Docket No. 50-328 Tennessee Valley Authority SEQUOYAH NUCLEAR PLANT -
UNIT 2 CYCLE 12 (U2C12) 12-MONTH STEAM GENERATOR (SG) INSPECTION REPORT In accordance with the requirements of Sequoyah Unit 2 Technical Specification 4.4.5.5.b, TVA is submitting the 12-month SG Inspection Report that includes the results of inservice inspections performed during the U2C12 refueling outage.
There are no commitments contained in this letter.
Please direct questions concerning this issue to me at (423) 843-7170 or J. D. Smith at (423) 843-6672.
Sincerely, QD Paul Pace Licensing and Industry Affairs Manager Enclosure cc (Enclosure):
Mr. Robert J. Pascarelli, Senior Project Manager U.S. Nuclear Regulatory Commission Mail Stop O-7A15 One White Flint North 11555 Rockville Pike Rockville, Maryland 20852-2739 Pnted on,ecBd pxo
U.S. Nuclear Regulatory Commission Page 2 September 20, 2004 PP:JDS:DVG:KTS cc (Enclosure):
A. S. Bhatnagar, LP 6A-C R. J. Beecken, LP 6A-C J. R. Douet, OPS 4A-SQN J. C. Fornicola, LP 6A-C D. F. Helms, LP 6A-C D. A. Kulisek, POB 2B-SQN F. C. Mashburn, BR 4X-C T. J. Niessen, LP 6A-C NSRB Support, LP 5M-C K. W. Singer, LP 6A-C EDMS, WTC A-K I:License/Steam Generators/U2C12 12-Month SG Report
K 1
I ENCLOSURE TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT UNIT 2 CYCLE 12 REFUELING OUTAGE 12-MONTH STEAM GENERATOR INSPECTION REPORT
Seq~uoyah Nuclear Plant Unit 2 Cycle 12 Refueling Outage November 2003 12 Month Report Prepared By:
~AQv-t Q.
z3,4-,-z-
q Verified By:
fe/3/ai4 Approved By:
(I l/31/t 1I a.-
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 TABLE OF CONTENTS Table 1 Inspection Summary Table 2.1 SG1 List of Indications (Indicating Tubes Plugged)
Table 2.1 SG1 List of Indications (Indicating Tubes Plugged)
Table 2.1 SG1 Ust of Indications (Indicating Tubes Plugged)
Table 2.1 SG1 Ust of Indications (Indicating Tubes Plugged)
Table 3 Nomenclature 2
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 1
SUMMARY
OF SEQUOYAH UNIT 2 CYCLE 12 INSPECTION EDDY CURRENT EXAM TYPE SG 1 SG 2 SG 3 SG 4 Full Length Bobbin Coil 3321 3246 3288 3303 Low Row U-Bend Plus Point 345 328 343 357 High Row U-Bend Plus Point & MHI 803 1199 798 1206 Top of Tubesheet Plus Point 3321 3246 3288 3303 U-Bend Freespan Ding Plug Point 6
12 4
16 AVB Ding Plug Point 0
2 1
2 Freespan Plus Point 66 81 52 19 HOI Plus Point 16 17 30 3
H02 Plus Point 3
1 3
0 H03 Plus Point 6
11 1
1 H04 Plus Point 1
3 2
3 H05 Plus Point 21 8
2 4
H06 Plus Point 38 5
9 7
H07 Plus Point 84 23 93 33 C07 Plus Point 71 18 67 127 Diagnostic/PID Plus Point 68 109 124 160 Total Exams Completed 8170 8309 8105 8544 Total Tubes Examined 3321 3246 3288 3303 PLUGGING STATUS SG 1 SG 2 SG 3 SG 4 Previously Plugged Tubes 67 142 100 85 Damage Mechanism AVB WEAR 0
1 0
0 COLD LEG THINNING 0
1 0
2 ODSCC HTS AXIAL 0
2 1
0 1
2 5
8 ODSCC SLUDGE PILE AXIAL 0
1 0
0 PREVENTATIVE 1
0 0
0 PWSCC HTS AXIAL 1
4 3
1 3
0 PWSCC U-BEND AXIAL I
1 1
3 0
7 Plugged Cycle 12 4
16 14 26 TOTAL TUBES PLUGGED 71 158 114 111 3
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.1 SG 1 Indications The following indications are outside diameter stress corrosion cracking at tube support plates.
The eddy current call 'DSI" is a bobbin probe call with the associated voltage listed. The call
'SAI" is a plus point probe call with the associated voltage listed. If the bobbin voltage is less than I volt, the indication may remain in service via the ODSCC Generic Letter 95-05 Alternate Repair Criteria (ARC). Details of these indications were reported in the required 90-Day Report.
If the indication is greater than I volt but not confirmed with plus point probe, the indication may remain in service via the ARC.
SG I
1 1
I 1
1 1
1 1
I 1
1 1
1 1
1 1
1 I
I 1
I I
1 1
1 1
I 1
1 1
I 1
I 1
1 I
1 I
1 1
1 ROW 2
2 3
3 3
3 3
3 3
3 3
4 4
4 5
5 5
5 5
5 5
5 5
5 5
5 6
6 6
6 6
6 6
6 6
8 8
8 9
9 9
9 COL 10 12 16 16 16 20 34 42 46 46 47 6
11 15 7
7 11 13 26 26 33 43 46 72 72 80 2
4 15 21 35 38 45 54 91 3
3 33 25 30 32 34 Call I Volts LOCATION DSI 0.42 H01+.05 DSI 0.44 H02-.02 DSI 0.52 H01-.07 DSI 1.6 H02+.02 SAI 0.47 H02+.24 DSI 0.28 H02-.12 DSI 0.6 H01-.02 DSI 0.23 H01+.02 DSI 0.74 H01+.02 DSI 0.15 H02+.00 DSI 0.27 H02+.02 DSI 0.67 H02-.05 DSI 0.42 H01-.05 DSI 0.53 H01-.12 DSI 0.24 H01-.05 DSI 0.52 H02-.10 DSI 0.33 H01+.00 DSI 0.22 H02-.02 DSI 0.23 H01+.05 DSI 0.35 H02+.07 DSI 0.35 H01-.07 DSI 0.42 H02-.10 DSI 0.63 H01-.02 DSI 0.53 H02-.05 SAI 0.1 H02+.22 DSI 0.39 H02-.02 DSI 0.74 H03-.07 DSI 0.53 H01-.05 DSI 0.32 H02-.02 DSI 0.69 H01-.12 DSI 0.17 H01+.05 DSI 0.14 H01-.07 DSI 0.31 H01+.12 DSI 0.53 H02+.00 DSI 0.91 H02+.00 DSI 0.64 H02-.02 DSI 0.39 H03-.02 DSI 0.23 H01+.05 DSI 0.42 H02+.07 DSI 0.54 H02+.00 DSI 0.25 H01-.07 DSI 0.34 H04-.09 CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TPS AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TPS AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 4
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.1 SG 1 Indications SG ROW COL Call I Volts LOCATION 1
9 39 DSI 0.84 H01+.05 1
9 43 DSI 0.55 H03-.07 1
9 92 DSI 1.04 H01+.00 1
9 92 SAI 0.07 H01+.23 1
10 34 DSI 0.46 H01+.13 1
10 36 DSI 0.44 H01+.04 1
10 37 DSI 0.34 H01+.14 1
10 70 DSI 1.3 H03+.05 1
10 75 DSI 0.48 H02+.16 1
10 75 DSI 0.54 H06-.05 1
10 77 DSI 0.46 H01+.09 1
10 77 DSI 0.45 H02+.02 1
10 77 DSI 1.31 H04-.16 1
10 77 SAI 0.11 H04+.06 1
11 4
DSI 0.35 H06+.12 1
11 58 DSI 0.92 H02+.12 1
11 58 SAI 0.13 H02+.19 1
11 61 DSI 0.62 H02+.14 1
11 93 DSI 0.42 H02+.05 1
12 6
DSI 0.35 H04+.07 1
12 44 DSI 0.18 H02+.07 1
12 46 DSI 0.74 H02+.09 1
13 9
DSI 0.57 H01+.07 1
13 62 DSI 0.37 H05+.05 1
14 4
DSI 0.33 H01+.07 1
/14 5
DSI 0.33 H01+.16 1
15 5
DSI 0.27 H02+.02 1
15 14 DSI 0.11 H03+.06 1
15 18 DSI 0.95 H01-.13 1
15 31 DSI 0.96 H01+.09 1
16 29 DSI 0.91 H02+.07 1
16 30 DSI 0.25 H01+.11 1
16 86 DSI 0.54 H04+.02 1
17 4
DSI 0.53 H01+.14 1
17 4
DSI 0.78 H03+.11 1
17 4
DSI 0.31 H04+.09 1
17 4
DSI 0.43 H06-.02 1
17 16 DS1 0.36 H01+.11 1
17 20 DSI 0.61 H01+.04 1
17 21 DSI 0.16 H02+.02 1
17 24 DSI 0.69 H01+.11 1
17 33 SAI 0.14 H02-.08 1
17 33 SAI 0.1 H02-.11 1
17 33 DSI 1.1 H02-.14 1
17 82 DSI 0.28 H05+.05 1
18 8
DSI 0.57 H02+.11 1
18 57 DSI 0.28 H01+.12 1
18 82 DSI 0.24 H02-.02 1
18 89 DSI 0.54 H05+.19 1
19 8
DSI 0.64 H02+.04 (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXAIL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 5
e Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.1 SG ROW COL Call I Volts LOCATION 1
19 8
DSI 0.44 H05+.19 1
19 45 DSI 0.58 H01+.09 1
19 45 SAI 0.12 H01+.09 1
19 45 DSI 0.62 H02+.09 1
19 51 DSI 0.83 H01+.07 1
19 51 SAI 0.14 H01+.07 1
19 51 SAI 0.13 H01+.26 1
19 66 DSI 0.72 H01+.09 1
19 74 DS1 0.28 H02+.09 1
19 77 DSI 0.35 H03+.00 1
20 32 DSI 0.17 H01+.02 1
20 58 DSI 0.38 H01+.12 1
20 65 DSI 0.92 H02-.05 1
21 7
DSI 0.57 H01+.02 1
21 8
DS0 0.75 H01+.08 1
21 8
DSI 0.82 H02+.13 1
21 78 DSI 0.57 H02+.05 1
21 83 SAI 0.1 H02+.09 1
21 83 DSI 0.34 H02+.11 1
21 83 SAI 0.1 H02+.12 1
22 9
DSI 0.4 H01+.09 1
22 9
SAI 0.12 H01+.33 1
22 10 DSI 0.59 H02+.11 1
22 11 DSI 0.35 H03+.06 1
22 19 DSI 0.22 H01+.02 1
22 21 DSI 0.46 H01+.09 1
22 31 DSI 0.22 H01+.07 1
22 33 DSI 0.57 H02+.09 1
22 46 DSI 0.45 H04+.11 1
22 48 DSI 1.17 H01+.11 1
22 48 SAI 0.17 H01+.15 1
22 48 SAI 0.18 H01+.21 1
22 68 DSI 0.21 H02+.02 1
23 7
DSI 0.89 H01+.00 1
23 9
DSI 0.24 H01+.05 1
23 9
DSI 0.23 H02+.00 1
23 20 DSI 0.42 H02+.06 1
23 32 DSI 0.26 H04+.02 1
24 9
DSI 0.32 H01+.08 1
24 17 DS1 0.64 H02+.11 1
24 21 DSI 0.56 H01+.05 1
24 21 DSI 0.69 H02+.12 1
24 22 DSI 0.38 H01+.11 1
24 29 DSI 0.76 H01+.07 1
24 29 SAI 0.11 H01+.14 1
24 29 DSI 0.64 H02+.07 1
24 34 DSI 0.69 H01+.08 1
24 46 SAI 0.11 H01+.02 1
24 46 DSI 0.81 H01+.11 1
24 60 DSI 0.82 H01+.07 SG 1 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL 0DSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 6
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.1 SG 1
I 1
I 1
1 1
1 1
I 1
1 1
I I
I I
I 1
1 I
1 1
I I
1 1
1 1
1 1
1 I
I 1
I I
I I
1 1
I 1
1 I
1 1
1 1
1 ROW 24 25 25 25 25 25 25 26 26 26 27 27 27 27 27 27 27 27 27 27 27 27 27 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 29 29 29 29 30 30 30 30 30 COL 60 8
14 25 37 38 42 20 30 64 16 18 18 24 31 48 48 48 48 52 52 52 74 10 11 12 16 26 28 28 31 43 43 43 43 45 46 50 56 77 79 52 52 52 56 24 41 62 82 82 Call I Volts LOCATION SAI 0.14 H01+.24 DSI 0.43 H01+.07 DS 0.15 H02+.05 DSI 0.39 H01+.09 DSI 0.53 H01+.12 DSI 0.94 H02+.24 DSI 0.46 H02-.04 DSI 0.26 H02+.00 DSI 0.49 H02+.11 DSI 0.57 H01+.14 DSI 0.25 H02+.05 DSI 0.18 H01-.07 DSI 0.24 H02+.18 DSI 0.28 H02+.06 DSI 0.55 H03+.14 DSI 0.48 H01+.11 DSI 1.11 H02+.09 SAI 0.13 H02+.09 SAI 0.12 H02+.12 SAI 0.08 H01+.10 DSI 1.49 H01+.12 SAI 0.38 H01+.12 DSI 0.58 H02+.11 DSI 0.43 H02+.09 DSI 0.27 H01+.00 DSI 0.47 H01-.02 DSI 0.32 H01+.15 DSI 0.29 H02+.08 DSI 0.48 H04+.00 DSI 0.21 H06+.13 DSI 0.43 H02+.02 DSI 1.68 H02+.07 SAI 0.11 H02+.08 SAI 0.29 H02+.26 SAI 0.25 H02+.28 DSI 0.98 H02+.02 DSI 0.5 H02-.02 DSI 0.45 H02+.11 DSI 0.66 H02+.00 DSI 0.47 H02+.02 DSI 0.29 H01+.14 DSI 1.05 H02+.09 SAI 0.2 H02+.20 SAI 0.22 H02+.31 DSI 0.47 H03+.07 DSI 0.46 H06+.06 DSI 0.74 H02-.07 DSI 0.39 H02+.07 DSI 0.5 H01+.09 DSI 0.9 H02+.07 SG I Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 7
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.1 SG ROW COL Call / Volts LOCATION 1
31 19 DSI 0.55 H03+.11 1
31 64 DSI 0.36 H03+.04 1
32 42 DSI 0.71 H01+.12 1
32 42 DSI 0.42 H02+.00 1
32 44 DSI 0.39 H04+.09 1
32 44 SAI 0.1 H04+.10 1
32 48 DSI 0.5 H02+.06 1
32 53 DSI 0.54 H01+.09 1
32 59 DSI 0.46 H03+.05 1
32 68 DSI 1.21 HO1+.09 1
32 68 SAI 0.25 HO1+.29 1
32 73 DSI 0.62 H02+.02 1
32 74 DSI 0.71 H03+.07 1
33 27 DSI 0.5 H04+.07 1
33 50 DSI 0.9 H02+.04 1
33 72 DSI 0.41 H02+.00 1
33 75 DSI 0.54 H05+.11 1
34 28 DSI 0.34 H01+.11 1
34 30 DSI 0.31 H03+.00 1
35 17 DSI 0.71 H02+.08 1
35 19 DSI 0.42 H03+.00 1
35 21 DSI 0.36 H01+.09 1
35 21 DSI 0.47 H02+.07 1
35 22 DSI 0.57 H01+.06 1
35 22 DSI 0.35 H02+.08 1
35 22 DSI 0.96 H03+.06 1
35 23 DSI 0.74 H01+.13 1
35 30 DSI 0.7 HO1+.0O 1
35 30 DSI 0.62 H02+.07 1
35 30 DSI 0.5 H03+.02 1
35 32 DSI 0.34 HO1+.09 1
35 33 DSI 0.38 H02+.07 1
35 33 DSI 0.45 H03+.07 1
35 42 DSI 0.82 H02+.07 1
35 47 DSI 0.37 H02+.09 1
36 25 DSI 0.73 H04+.06 1
36 35 DSI 0.47 H04+.12 1
36 42 DSI 0.29 H02+.00 1
36 47 DSI 0.27 H02+.07 1
36 54 DSI 0.3 H02+.13 1
36 62 DSI 0.69 H02+.06 1
36 62 DSI 0.53 H03+.02 1
37 60 DSI 0.62 H05+.11 1
37 61 DSI 1.12 H02+.05 1
37 61 SAI 0.64 H02+.07 1
37 61 DSI 0.29 H03+.12 1
38 24 DSI 0.26 H02+.08 1
38 51 DSI 0.33 H02+.11 1
38 63 DSI 0.69 H02+.05 1
38 64 DSI 0.5 H03+.06 SG 1 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 8
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.1 SG ROW COL Call I Volts LOCATION 1
38 65 DSI 0.41 H02+.04 1
38 65 DSI 0.77 H04-.02 1
39 27 DSI 0.31 H04+.08 1
39 30 DSI 0.3 H05+.09 1
39 46 DSI 0.81 H01+.02 1
40 24 DSI 0.48 H01+.10 1
40 24 DSI 0.71 H02+.02 1
40 25 DSI 0.48 HO1+.02 1
40 25 DSI 0.48 H02+.09 1
40 25 DSI 0.35 H04+.12 1
40 26 DSI 0.26 H01+.10 1
40 26 DSI 0.57 H04+.13 1
40 26 DSI 0.42 HO5+.11 1
40 27 DSI 0.25 H02+.05 1
40 51 DSI 0.89 H03+.07 1
41 37 DSI 0.97 H02+.11 1
42 40 DSI 0.28 H01+.07 1
42 40 DSI 0.66 H02+.02 1
42 40 DSI 0.25 H07-.09 1
42 49 DSI 0.42 H02+.00 1
44 37 DSI 1.39 H02-.09 1
44 40 DSI 0.58 H02+.09 1
44 42 DSI 0.67 H02+.04 1
44 45 DSI 0.61 H02+.06 1
44 50 DSI 0.35 H02+.04 1
45 37 DSI 0.67 H02+.04 1
45 39 DSI 0.59 HO1+.11 1
45 39 SAI 0.16 HO1+.21 1
45 39 DSI 1.88 H06+.06 1
45 44 DSI 1.03 H03+.07 1
45 47 DSI 0.79 H04+.07 1
45 49 DSI 0.9 H02+.12 1
45 51 DSI 1.1 H02+.11 1
45 51 SAI 0.11 H02+.29 1
45 51 SAI 0.1 H02+.33 1
46 41 DSI 0.58 H03+.09 1
46 50 DSI 1.05 H03+.09 SG 1 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC The following indications were taken out of service by plugging. The 'DSI' call is a bobbin coil probe call with the associated voltage listed. The wSAI or 'SCI" call is a plus point coil call with the associated voltage listed.
SG 1
1 1
I 1
1 ROW 1
2 15 26 26 26 COL Call I Volts LOCATION 22 SAI 1.37 H07+4.15 93 TBP 0
+0.00 33 SAI 2.84 HTS-8.67 36 DSI 1.57 H02+.00 36 SAI 0.73 H02+.11 36 TBP 0
+0.00 CHARACTERIZATION PWSCC UBEND AXIAL PREVENTIVE PWSCC HTS AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL PREVENTIVE RESOLUTION Plugged Plugged Plugged Plugged Plugged Plugged 9
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.1 SG 1 Indications (Continued)
The following are anti vibration bar wear indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) with associated voltage.
SG 1
1 1
I I
I 1
I 1
I 1
ROW 19 19 27 27 32 32 32 36 37 37 39 COL 38 38 31 31 64 64 64 66 62 62 45 Call I Volts 29 0.5 17 0.33 27 0.39 25 0.33 23 0.42 25 0.49 19 0.33 23 0.42 17 0.25 33 0.78 15 0.23 LOCATION AV2-.09 AV3+.0O AV2-.02 AV3-.09 AV2+.02 AV3+.28 AV4-.17 AV3+.09 AV2-.09 AV3-.09 AV2-.09 CHARACTERIZATION AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
The following are cold leg thinning indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) with associated voltage.
SG I
1 1
1 1
1 1
I 1
I I
1 I
1 1
1 1
1 1
1 1
1 1
ROW 1
5 30 31 31 34 34 42 42 43 43 43 44 44 44 44 44 45 46 46 46 46 46 COL 1
1 83 79 82 19 79 30 62 31 32 62 36 39 45 58 61 41 43 44 50 52 53 Call / Volts 10 0.35 19 0.52 28 0.98
<20 0.58 3
0.89 20 1.59 10 0.4
<20 0.38 17 0.45 4
1.17 10 0.69 9
0.63 10 0.87 1
0.92 30 0.75 23 1.89 37 0.45 35 0.43 31 0.3 16 0.38 9
0.85
<20 0.66
<20 0.38 LOCATION CO1-.07 CO1+.13 CO1 +.20 C01-.31 CO1 +.07 C01+.12 C03-.18 C01+.18 C01-.35 C01+.11 C01-.09 C01-.22 CO1+.19 C02-.26 C02+.04 C01-.28 C01-.26 C02-.30 C02-.22 C02-.17 CO1 +.20 C02+.07 C01-.16 CHARACTERIZATION CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning C/L Thinning CAL Thinning CIL Thinning CAL Thinning CAL Thinning CIL Thinning CAL Thinning RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
10
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG 2 Indications The following indications are outside diameter stress corrosion cracking at tube support plates.
The eddy current call ODSI" is a bobbin probe call with the associated voltage listed. The call
'SAI' is a plus point probe call with the associated voltage listed. If the bobbin voltage is less than I volt, the indication may remain in service via the ODSCC Generic Letter 95-05 Alternate Repair Criteria (ARC). Details of these indications were reported in the required 90-Day Report.
If the indication is greater than 1 volt but not confirmed with plus point probe, the indication may remain in service via the ARC.
SG ROW COL Call / Volts LOCATION 2
2 14 DSI 0.53 H02+.00 2
2 22 DSI 0.33 H02+.04 2
2 37 DSI 0.21 H02+.02 2
2 42 DSI 0.31 H01+.02 2
2 45 DSI 0.94 H02+.00 2
2 48 DS1 0.37 H01-.04 2
2 49 DSI 0.48 H01+.04 2
2 50 DSI 0.53 H02+.00 2
2 55 DSI 0.7 H01-.02 2
2 55 DSI 0.6 H02+.04 2
2 58 DSI 0.75 H01+.00 2
2 58 DS0 1.36 H02+.09 2
2 58 SAI 0.25 H02+.14 2
2 73 DSI 0.47 H01-.15 2
2 73 DSI 0.54 H02-.07 2
2 76 DSI 0.61 H02-.11 2
2 77 DSI 0.32 H01-.09 2
2 82 DSI 0.7 H04-.02 2
2 83 DSI 0.62 H01-.15 2
2 84 DSI 0.41 H014.07 2
2 85 DSI 0.8 H01-.09 2
2 85 DSI 0.55 H02-.07 2
2 87 DSI 0.72 H01+.07 2
2 88 DSI 0.56 H01-.04 2
2 94 DSI 0.33 H02-.07 2
3 5 DSI 0.42 H02+.04 2
3 30 DSI 0.46 H02-.04 2
3 37 DSI 1.19 H02-.07 2
3 42 DSI 1.57 H02+.02 2
3 42 SAI 0.28 H02+.14 2
3 49 DSI 0.54 H02-.07 2
3 72 DSI 0.42 H01+.00 2
3 76 DSI 0.49 H02+.04 2
4 22 DSI 0.68 H02+.07 2
4 26 DSI 0.89 H02+.02 2
4 27 DSI 0.42 H02-.02 2
4 36 DSI 1.16 H01+.00 2
4 36 SAI 0.28 H01+.16 CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 11
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG 2 Indications (Continued)
SG ROW COL Call / Volts LOCATION CHARACTERIZATION RESOLUTION 2
4 45 DSI 0.84 H02+.00 2
4 50 DSI 0.65 H01+.00 2
4 54 DSI 0.59 H02-.02 2
4 56 DSI 1.01 H02+.07 2
4 56 SAI 0.16 H02+.13 2
4 56 SAI 0.13 H02+.18 2
4 61 DSI 0.35 H04-.04 2
4 64 DSI 0.49 H01+.00 2
4 92 DSI 0.73 H03-.04 2
4 94 DSI 0.36 H02-.09 2
5 59 DSI 0.32 H02+.00 2
5 65 DSI 0.45 H01+.02 2
5 92 DSI 0.5 H01+.09 2
5 93 DSI 0.26 H01+.00 2
5 94 DSI 0.6 H01-.07 2
6 1 DSI 0.37 H02-.02 2
6 13 DSI 0.31 H04-.04 2
6 16 DSI 0.26 H02-.04 2
6 38 DSI 0.84 H02-.09 2
6 39 DSI 0.23 H02-.04 2
6 40 DSI 0.54 H01+.04 2
6 43 DSI 1A6 H02+.00 2
6 57 DSI 0.36 H02-.07 2
6 68 DSI 0.39 H06-.02 2
6 84 DSI 0.5 H02-.02 2
6 94 DSI 0.45 H01+.07 2
7 4 DSI 0.35 H01+.04 2
7 4 DSI 0.88 H02+.20 2
7 13 DSI 0.35 H02-.02 2
7 21 DSI 0.34 H01+.00 2
7 43 DSI 0.8 H02+.00 2
7 72 DSI 0.65 H01-.04 2
7 89 DSI 0.75 H02+.00 2
8 11 DSI 0.19 H02+.02 2
8 13 DSI 0.26 H02+.02 2
8 34 DSI 0.22 H03-.04 2
8 38 DSI 0.48 H02-.09 2
8 42 DSI.
0.71 H02+.07 2
8 44 DSI 1.01 H01+.09 2
8 44 SAI 0.19 H01+.14 2
8 45 DSI 0.38 H02-.07 2
8 47 DSI 0.34 H02+.00 2
8 51 DSI 0.45 H02-.04 2
8 60 DSI 0.39 H01+.00 2
8 61 DSI 0.48 H02+.00 2
8 70 DSI 0.34 H03+.00 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 12
^
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG 2 Indications (Continued)
SG ROW COL Call / Volts LOCATION CHARACTERIZATION RESOLUTION 8
8 8
9 9
9 9
9 10 10 10 11 11 11 11 11 11 11 12 12 12 13 13 14 14 14 14 14 14 15 15 15 15 15 15 15 15 16 18 19 20 20 20 20 20 20 90 DSI 91 DSI 92 DSI 33 DSI 50 DSI 57 DSI 69 DSI 72 DSI 4 DSI 89 DSI 89 SAI 21 DSI 21 SAI 25 DSI 63 DS5 65 DSI 65 SAI 88 DSI 44 DSI 59 DSI 90 DSI 21 DSI 21 SAI 48 DSI 48 DSI 84 DSI 90 DSI 90 SAI 90 SAI 36 DSI 49 DSI 54 DSI 87 DSI 89 DSI 89 SAI 89 SAI 89 SAI 33 DSI 7 DSI 69 DSI 33 DSI 43 DSI 44 DSI 49 DSI 49 DSI 52 DSI 0.3 H02+.00 0.42 H01-.07 0.93 H01+.00 0.91 H01+.00 0.26 H04-.04 0.66 H02+.00 0.22 H02+.02 0.37 H02-.09 0.48 H02+.09 0.52 H02+.14 0.18 H02+.06 0.65 H01+.04 0.14 H01+.11 0.26 H02+.13 0.42 H02+.12 1.11 H02+.07 0.33 H02+.19 0.46 H02+.11 0.6 H02+.09 0.35 H02+.09 0.33 H02+.14 0.39 H02+.04 0.2 H02+.04 0.98 H01+.05 0.96 H02-.02 0.82 H01+.07 0.35 H01+.12 0.14 H01+.17 0.15 H01+.19 0.67 H01+.04 0.42 H02+.02 0.73 H02-.02 0.3 H02+.05 1.25 H01+.09 0.19 H01+.15 0.19 H01+.16 0.28 H01+.24 0.42 H03+.04 0.96 H02+.16 0.74 H01+.00 0.23 H04+.11 0.64 H05+.02 0.31 H02+.05 0.37 H01+.09 0.28 H02+.09 0.48 H01+.14 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 13
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG ROW COL Call / Volts LOCATION 2
20 56 DSI 0.71 H02+.09 2
20 57 DSI 0.41 H01+.07 2
20 58 DSI 0.56 H01+.00 2
20 62 DSI 0.38 H01+.05 2
21 20 DSI 0.13 H02+.07 2
21 20 SAI 0.15 H02+.19 2
21 61 DSI 0.35 H01+.12 2
21 64 DSI 0.29 H01-.02 2
21 87 DSI 0.37 H01+.09 2
22 34 DSI 0.47 H01+.11 2
22 37 DSI 0.3 H05+.09 2
22 58 DSI 0.55 H01+.18 2
23 17 DSI 0.58 H02+.09 2
23 22 DSI 0.63 H02+.13 2
23 44 DSI 0.69 H01+.02 2
23 44 DSI 0.35 H05+.00 2
23 49 DSI 1.42 H01+.23 2
23 49 SAI 0.29 H01+.21 2
23 49 SAI 0.41 H01+.22 2
23 55 DSI 0.29 H01+.07 2
23 72 DSI 0.25 H02+.00 2
24 37 DSI 0.77 H02+.11 2
24 37 DSI 1.18 H04+.15 2
24 37 SAI 0.25 H04+.19 2
24 38 DSI 0.42 H02+.02 2
24 43 DSI 0.81 H02+.28 2
24 60 DSI 0.74 H02+.07 2
24 60 SAI 0.14 H02+.16 2
24 87 DSI 0.71 H01+.09 2
24 87 DSI 0.3 H04+.07 2
25 9 DSI 0.29 H07+.00 2
25 22 DSI 0.46 H02+.07 2
25 56 DSI 0.7 H03+.07 2
25 56 SAI 0.26 H03+.23 2
25 72 DSI 0.51 H02+.07 2
26 59 DSI 0.59 H01+.00 2
26 59 DSI 0.33 H02+.09 2
27 53 DSI 0.68 H02+.05 2
27 68 DSI 0.88 H01+.09 2
27 68 DSI 0.45 H02+.11 2
27 84 DSI 0.93 H01+.05 2
27 84 DSI 0.65 H02+.14 2
28 17 DSI 0.58 H02+.02 2
28 66 DSI 0.44 H03+.07 2
28 69 DSI 0.59 H02+.07 2
28 79 DSI 0.65 H02+.12 SG 2 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 14
- C Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG 2 Indications (Continued)
CHARACTERIZATION RESOLUTION SG ROW COL Call / Volts LOCATION 2
29 16 DSI 0.73 H01+.12 2
29 16 DSI 0.83 H02+.09 2
29 17 DSI 0.42 H02+.06 2
29 20 DSI 0.82 H02+.09 2
29 21 DSI 0.41 H02+.11 2
29 61 DSI 0.31 H03+.09 2
29 67 DSI 0.78 Ho1+.07 2
30 19 DSI 0.15 H04+.04 2
30 22 DS1 1.16 H02+.09 2
30 55 DSI 1.15 H01+.16 2
30 55 SAI 0.4 H01+.22 2
30 55 DSI 0.39 H05+.07 2
30 70 DSI 0.31 H01+.05 2
30 74 DSI 1.38 H02+.07 2
30 74 SAI 0.21 H02+.06 2
30 77 DSI 0.53 H02+.07 2
30 79 DSI 0.56 H02+.07 2
30 81 DSI 0.82 H01+.07 2
30 81 DSI 0.59 H04+.05 2
30 82 DSI 0.66 H02+.12 2
31 38 DS1 0.36 H04+.02 2
31 39 DSI 0.28 H02+.06 2
31 47 DSI 0.63 H02+.02 2
31 66 DSI 0.5 H02+.02 2
31 67 DSI 0.6 H02+.09 2
31 67 DSI 0.25 H03+.09 2
31 70 DS1 1.26 H01+.11 2
31 70 SAI 0.25 H01+.10 2
31 70 SAI 0.25 H01+.12 2
31 70 DSI 1.14 H02+.07 2
31 70 SAI 0.29 H02+.09 2
31 70 SAI 0.32 H02+.25 2
31 74 DSI 0.6 H02+.09 2
32 20 DSI 1.15 H01+.11 2
32 20 SAI 0.21 H01+.14 2
32 20 SAI 0.18 H01+.18 2
32 20 DSI 0.86 H02+.00 2
32 23 DSI 0.35 H02+.09 2
33 25 DSI 0.47 H01+.04 2
33 25 DS1 0.57 H02-.02 2
33 25 DSI 0.41 H04+.07 2
33 31 DSI 0.82 H02+.00 2
35 45 DSI 0.41 H02+.12 2
36 36 DSI 1.03 H02+.16 2
36 42 DSI 0.74 H02+.07 2
36 64 DSI 1.05 H01+.11 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 15
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG 2 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION RESOLUTION 36 36 36 36 36 36 37 37 37 37 38 38 38 38 38 38 38 38 39 39 39 39 39 40 40 40 40 41 41 41 41 41 41 41 41 41 41 41 41 42 42 42 42 43 43 43 64 SAI 0.22 H01+.23 71 DSI 1.09 H01+.12 71 SAI 0.18 H01+.11 71 SAI 0.21 H01+.12 74 DSI 0.82 H02+.07 75 DSI 0.81 H02+.09 20 DSI 0.75 H01+.11 26 DSI 0.18 H02+.07 55 DSI 0.5 H02+.07 66 DSI 0.32 H01+.12 26 DSI 0.42 Ho01+.11 28 DSI 0.32 H02+.11 28 SAI 0.1 H02+.11 45 DSI 0.78 H02+.09 45 DSI 0.55 H03+.11 49 DSI 0.69 H02+.07 59 DSI 0.36 H02+.16 74 DSI 0.26 H04+.02 25 DSI 0.23 H01+.09 25 DSI 0.28 H02+.02 55 DSI 0.73 H02+.12 58 DSI 0.61 H04+.07 59 DSI 0.41 H02+.07 31 DSI 0.16 H02+.11 37 DSI 0.33 H02+.05 40 DSI 0.72 H03+.18 57 DSI 0.39 H02+.12 34 DSI 1.81 H02+.07 37 DSI 0.15 H04+.05 39 DSI 0.26 H02+.09 43 DSI 0.65 H02+.12 50 DSI 0.62 H01+.14 50 DSI 0.5 H02+.16 54 DSI 0.36 H01+.05 54 DSI 0.51 H02+.02 54 DSI 0.39 H03+.11 55 DSI 0.59 H03+.07 67 DSI 0.48 H01+.07 69 DSI 0.32 Ho01+.07 37 DSI 0.43 H05+.07 43 DSI 0.37 H03+.07 50 DSI 0.37 H02+.09 61 DSI 0.49 H01+.09 37 DSI 1.21 C01+.35 38 DSI 0.65 H02+.09 43 DSI 0.39 H02+.07 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 16
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG ROW COL Call/Volts LOCATION 2
43 43 DSI 0.21 H03+.09 2
43 44 DSI 0.4 H03+.02 2
43 49 DSI 0.31 H02+.02 2
43 50 DSI 0.33 H02+.09 2
43 52 DSI 0.19 H02+.05 2
43 52 SAI 0.15 H02+.04 2
43 52 DSI 0.17 H03+.14 2
43 53 DSI 0.59 H04+.17 2
44 39 DSI 0.29 H02+.02 2
44 52 DSI 1.22 H02+.09 2
44 52 SAI 0.11 H02+.04 2
45 39 DSI 0.24 H03+.07 2
45 39 DSI 0.26 H04+.00 2
45 51 DSI 0.81 H02+.09 2
45 52 DSI 0.59 H02+.07 SG 2 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC The following indications were taken out of service by plugging. The 'DSI call is a bobbin coil probe call with the associated voltage listed. The 'SAI", 'SCI", or "SVI' call is a plus point coil call with the associated voltage listed. The number call is a bobbin coil probe call of percent through-wall (maximum depth).
SG ROW COL Call I Volts LOCATION 2
4 47 DSI 0.29 H01-.11 2
4 47 SAI 0.79 H07+5.09 2
5 57 SAI 0.16 H01+.09 2
6 20 SCI 0.24 HTS-.02 2
6 85 SCI 0.6 H07+23.24 2
6 85 SCI 0.73 H07+24.67 2
6 85 SCI 0.37 H07+26.81 2
6 85 SCI 0.51 H07+29.86 2
6 85 SCI 1.65 H07+30.33 2
6 91 SCI 0.4 H07+19.69 2
6 93 SCI 1.04 H07+22.91 2
6 93 SCI 1.23 H07+27.19 2
6 93 SCI 0.44 H07+28.85 2
6 93 SCI 1.84 H07+30.27 2
6 9315 1.28C01+.11 2
10 23 SAI 0.1 HTS+.20 2
11 60 SAI 0.55 HTS-6.74 2
14 67 SAI 0.11 HTS+.21 2
16 57 SAI 0.13 HTS+.91 2
19 72 SAI 0.38 HTS-.79 2
20 60 SAI 0.38 HTS-.52 2
29 32 41 1.08 AV2+.00 2
29 32 31 0.62 AV3+.25 2
29 32 35 0.77 AV3-.36 CHARACTERIZATION ODSCC TSP AXIAL PWSCC UBEND AXIAL ODSCC TSP AXIAL PWSCC HTS CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC PWSCC UBEND CIRC C/L Thinning ODSCC HTS AXIAL PWSCC HTS AXIAL ODSCC HTS AXIAL SLUDGE PILE PWSCC HTS AXIAL PWSCC HTS AXIAL AVB WEAR AVB WEAR AVB WEAR RESOLUTION Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged 17
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG 2 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION RESOLUTION 2
29 32 22 0.36 AV4+.00 AVB WEAR Plugged 2
34 17 40 1.58 C01-.13 C/L Thinning Plugged 2
34 17 SVI 0.8 C01+.13 VOLUMETRIC Plugged 2
34 17 <20 0.5 C02-.28 CIL Thinning Plugged 2
35 40 SAI 1.23 HTS-7.25 PWSCC HTS AXIAL Plugged 2
35 40 SAI 0.35 HTS-7.96 PWSCC HTS AXIAL Plugged 2
35 40 DSI 0.54 H02+.20 ODSCC TSP AXIAL Plugged 2
35 40 SAI 2.44 HTS-6.75 PWSCC HTS AXIAL Plugged 2
35 55 DSI 0.36 H01+.16 ODSCC TSP AXIAL Plugged 2
35 55 DSI 1.56 H02-.07 ODSCC TSP AXIAL Plugged 2
35 55 SAI 0.48 H02+.11 ODSCC TSP AXIAL Plugged 2
35 55 SAI 0.41 H02+.22 ODSCC TSP AXIAL Plugged 2
35 55 TBP 0 +0.00 PREVENTIVE Plugged The following are anti vibration bar wear indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) With associated voltage.
SG ROW COL Call I Volts LOCATION CHARACTERIZATION RESOLUTION 17 28 17 17 28 35 17 64 18 17 64 19 17 64 23 18 42 16 18 72 14 19 28 20 22 41 17 23 69 28 23 69 26 24 6135 24 63 25 24 64 16 24 64 21 24 64 20 24 64 20 24 7118 26 70 24 27 4319 27 65 29 27 65 35 29 39 21 29 39 14 32 46 11 32 56 24 32 56 25 0.24 AVI+.03 0.77 AV3+.00 0.39 AV1+.00 0.41 AV2+.00 0.53 AV3+.00 0.34 AV2+.00 0.28 AV3+.00 0.3 AV1+.00 0.29 AV2+.00 OA5 AV2+.00 0.39 AV3+.00 0.79 AV2+.17 0.44 AV2-.31 0.23 AV1-.02 0.33 AV2+.26 0.3 AV3-.33 0.32 AV3+.26 0.26 AV3+.00 0.49 AV3+.00 0.26 AV3-.26 0.53 AV2+.00 0.79 AV3+.00 0.35 AV2+.52 0.21 AV3-.65 0.13 AV2+.00 0.46 AVI+.00 0.46 AV2+.00 AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
18
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG ROW COL Call I Volts LOCATION 2
2 2
2 2
2 2
2 2
2 2
2 2
32 32 32 33 33 33 33 34 38 38 38 39 39 56 18 6221 62 17 49 25 49 37 49 39 62 18 46 9 43 13 46 18 46 15 49 18 49 17 0.29 AV3+.00 0.4 AV2+.00 0.3 AV3+.0O 0.5 AV1+.O0 1.06 AV2+.00 1.19 AV3+.00 0.34 AV3+.00 0.1 AV3+.00 0.21 AV3+.00 0.4 AV3+.00 0.32 AV4+.00 0.27 AV3-.05 0.26 AV4-.07 SG 2 Indications (Continued)
CHARACTERIZATION AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVS WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
The following are cold leg thinning indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) with associated voltage.
SG ROW COL Call I Volts LOCATION 2
5 93 25 0.58 C01-.02 2
6 94 16 0.52 C01-.28 2
6 94 19 0.27 C03+.21 2
7 76 <20 0.86 C03-.33 2
10 92 5 0.81 C01-.21 2
19 6 20 1.05 C01-.05 2
24 8 20 1.39 C01-.21 2
24 9 17 0.9 C01+.02 2
28 11 26 1.42 C01-.21 2
28 12 34 1.19 C02-.25 2
32 17 1 0.5 C03-.15 2
33 16 <20 0.43 C03-.11 2
33 74 37 0.59 C02-.21 2
33 76 <20 0.82 C02-.25 2
33 78 34 1.12 C02-.25 2
34 78 19 0.7 C02-.21 2
36 18 25 1.78 C01+.11 2
36 20 27 2.24 C01-.20 2
36 22 17 0.45 C01-.22 2
36 76 20 1.21 C02-.23 2
38 2130 0.33 C01-.17 2
38 22 22 0.55 C03+.00 2
38 24 24 1.28 C01+.13 2
38 73 37 0.46 C02-.23 2
38 74 7 1.25 C02+.12 2
39 70 39 0.48 C02-.09 2
40 24 37 1.08 C01-.11 CHARACTERIZATION C/L Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/L Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning CQI Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/L Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning C/IL Thinning RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
19
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.2 SG ROW COL Call I Volts LOCATION 2
40 27 19 0.99 C01-.19 2
40 42 <20 0.2 C02-.02 2
40 67 9 1.21 C02+.09 2
40 68 20 0.71 C02-.09 2
40 71 11 0.47 C03-.28 2
41 29 29 0.55 C01-.06 2
41 36 8 0.79 C02-.24 2
41 50 <20 0.9 C02-.38 2
42 28 15 0.67 C01-.27 2
42 29 3 0.96 C01+.09 2
42 36 16 0.64 C01-.25 2
42 64 25 1.81 CO1+.14 2
42 66 22 0.7 C01+.05 2
43 3232 2.2 C01+.13 2
43 51 <20 0.8 C04-.33 2
43 57 3 0.86 C02+.19 2
43 62 12 0.81 CO1+.17 2
43 63 <20 0.53 C01-.05 2
44 39 20 1.07 C02-.19 2
44 39 25 0.97 C02-.17 2
44 394 0.4 C03+.16 2
44 39 4 0.36 C03+.17 2
45 40 <20 0.74 C01-.09 2
45 43 <20 0.67 C01-.31 2
45 46 17 0.34 C01-.23 2
45 59 14 0.59 C02-.23 2
46 48 7 0.89 C01+.09 SG 2 Indications (Continued)
CHARACTERIZATION CIL Thinning CIL Thinning CIL Thinning CIL Thinning C/IL Thinning CIL Thinning CIL Thinning C/IL Thinning CIL Thinning CIL Thinning CIL Thinning C/L Thinning CIL Thinning CIL Thinning CAL Thinning CAL Thinning CAL Thinning CAL Thinning CAL Thinning CIL Thinning CAL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CAL Thinning RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
20
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG 3 Indications The following indications are outside diameter stress corrosion cracking at tube support plates.
The eddy current call "DSI" is a bobbin probe call with the associated voltage listed. The call "SAl' is a plus point probe call with the associated voltage listed. If the bobbin voltage is less than 1 volt, the indication may remain in service via the ODSCC Generic Letter 95-05 Alternate Repair Criteria (ARC). Details of these indications were reported in the required 90-Day Report.
If the indication is greater than 1 volt but not confirmed with plus point probe, the indication may remain in service via the ARC.
1 76 DSI 0.62 3
1 79 DSI 0.88 3
1 79 DSI 1.36 3
2 16 DSI 0.5 3
2 25 DSI 0.36 3
2 31 DSI 0.58 3
2 35 DSI 0.77 3
2 38 DSI 0.17 3
2 39 DSI 0.61 3
2 73 DSI 0.37 3
2 79 DSI 0.48 3
3 1 DSI 0.49 3
3 2DSI 0.32 3
3 5DSI0.91 3
3 10 DSI 1.42 3
3 10 SAI 0.2 3
3 10 SAI 0.54 3
3 11DSI 0.8 3
3 29 DSI 0.83 3
3 49 DSI 0.12 3
3 51 DSI 0.71 3
3 94 DSI 0.22 3
3 94 DSI 0.15 3
4 34 DSI 0.32 3
4 51 DSI 0.66 3
4 55 DSI 0.45 3
5 1DSI 1.21 3
5 1 SAI 0.09 3
5 4DSI 0.7 3
5 10 DSI 0.92 3
5 12 DSI 0.67 3
5 22 DSI 0.92 3
6 10 DSI 1.06 3
6 10 SAI 0.15 3
6 38 DSI 1.13 3
6 38 SAI 0.19 3
6 38 DSI 0.31 3
6 48 DSI 1.6 LOCATION H03+.14 H02+.12 H03+.14 H01+.00 H03-.02 H03+.00 H01-.02 H02+.00 H02-.02 H02-.07 H01-.02 H01-.09 H01+.00 H01+.00 H01+.07 H01+.21 H01+.24 H01-.09 H01+.02 H02+.07 H02-.07 H02+.02 H04-.12 H01-.05 H01+.00 H02+.00 H02-.05 H02+.09 H01+.00 H01+.02 H01-.05 H01+.00 H01+.00 H01+.20 H01+.02 H01+.23 H03-.02 H01+.00 CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 21
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call / Volts LOCATION SAI SAI DSI DSI DSI SAI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSt DSI DSI SAI SAI DSI DS' DSI DSI DS1 DSI DSI DS1 DSI DSI DSI DSI DSI DSI DSI DSI SAI DSI DSI DSI DSI 0.44 0.47 0.18 0.84 0.38 0.17 0.73 0.49 0.24 0.37 0.17 0.51 0.43 0.53 0.68 0.45 0.55 0.78 0.26 0.6 0.22 0.85 1.07 0.12 0.15 0.31 0.41 0.17 0.69 0.89 0.34 0.43 0.42 0.29 0.4 0.6 0.44 0.9 0.3 0.19 1.04 0.74 0.5 0.84 0.85 0.56 H01+.16 H01+.34 H01+.05 H01+.00 H02-.09 H02+.17 H02+.00 H02+.00 H04+.05 H01-.12 H02+.05 H01-.12 H01+.00 H01-.14 H02-.09 H03+.02 H01+.02 H02-.02 H02+.05 H02-.05 HO1-.12 H03+.00 H02-.04 H02+.07 H02+.12 H03-.05 H03-.02 H02+.00 H05+.00 H03+.02 H01+.00 H01-.14 H01-.14 H04-.05 H01+.05 H01-.05 H01-.07 H01+.00 H03-.05 H05-.05 HO1+.00 H01+.34 H01+.05 H01-.02 H01-.05 HO +.00 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 22
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call I Volts LOCATION 12 13 14 16 23 41 48 48 48 48 50 51 51 52 6
16 17 17 17 36 36 37 27 35 3
3 7
10 24 29 29 36 44 53 54 4
14 18 20 39 39 39 39 52 3
3 DSI DSI DSI DSI DSI DSI DSI SAI SAI DSI DSI DSI SAI DSI DSI DSI DS1 SAI SAI DSI SAI DSI DSI DSI DSI DSI DSI DSI DS' DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI SAI SAI DSI DSI DSI SAI 0.63 0.55 0.64 0.66 0.77 0.68 1.57 0.58 0.53 0.44 0.77 1.06 0.21 0.5 0.43 0.17 1.14 0.13 0.18 1.16 0.24 0.83 0.25 0.54 0.62 0.37 0.39 0.54 1.16 0.67 0.76 0.77 0.35 0.35 0.43 0.88 0.42 0.9 0.46 1.23 0.19 0.25 0.7 0.29 1.23 0.26 H01+.00 H02+.00 H01-.02 H01-.05 H03-.07 H01+.02 H01+.07 H01+.10 H01+.28 H02-.09 H01+.07 H01+.14 H01+.22 H01-.07 H01+.00 H06+.09 H02+.07 H02+.12 H02+.21 H01+.07 H01+.31 H01+.14 H01-.02 H03+.09 H01+.05 H02+.07 H01+.02 H02+.09 H01+.11 H01+.12 H02+.07 H01+.02 H02+.07 H01-.09 H01+.14 H01+.09 H01+.19 H01+.02 H02+.00 H01-.12 H01+.16 H01+.29 H03+.12 H01+.09 H01+.05 H01+.21 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 23
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call /Volts LOCATION 3
6 6
7 15 16 18 29 37 4
4 5
24 41 54 6
12 13 20 22 22 47 47 18 21 35 38 10 13 22 22 22 22 12 28 28 28 29 29 29 29 30 31 31 31 31 DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI SAI DSI SAI DSI DS' DS' DSI DSI DSI DSI SAI DSI SAI DSI DSI SAI SAI DSI SAI SAI SAI DSI DSI SAI SAI SAI 0.64 0.93 0.51 0.33 0.59 0.36 0.4 0.96 0.27 0.78 0.67 0.34 0.76 0.63 0.68 0.6 0.35 0.29 0.29 0.68 0.21 1.06 0.5 0.8 0.51 0.88 0.9 0.79 0.81 0.7 0.22 0.65 0.15 0.82 1.22 0.19 0.23 1.42 0.13 0.1 0.45 0.99 1.12 0.16 0.34 0.17 H02+.09 H01+.00 H02+.00 H02-.02 HOI+.09 H01+.05 H02+.00 H02+.05 H01+.00 HOI+.07 H02+.12 H04+.05 H01-.02 HOI+.05 H01+.07 H02+.07 H01+.16 H01+.12 H01+.09 HO1+.14 H01+.26 H01+.02 H01+.23 HOI+.07 H01+.14 H01+.05 HOI+.05 H01+.12 HO1+.12 H01+.12 HO1+.20 H02+.05 H02+.04 H01+.07 HO1+.21 HOI+.25 H01+.26 H01+.07 HOI-.04 H01+.11 H01+.20 HO1+.21 H01+.09 H01+.06 H01+.14 H01+.14 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 24
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call / Volts LOCATION 20 20 20 20 20 20 20 20 20 20 20 20 21 21 21 21 21 21 21 22 22 22 23 23 23 23 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 25 25 25 25 32 32 32 35 39 39 39 42 47 80 80 88 15 24 24 24 81 81 84 21 52 68 13 14 44 60 10 12 12 16 16 21 21 23 24 24 24 25 29 29 29 35 14 18 24 26 DSI SAI SAI DSI DSI SAI SAI DS1 DSI DSI DSI DSI DSI DS0 SAI SAI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI SAI DSI DSI DSI DSI SAI SAI DSI DSI SAI SAI DSI DSI DSI DS1 DSI 1.63 0.2 0.42 0.63 1
0.28 0.13 0.31 1.21 0.77 0.34 0.6 0.29 1.15 0.22 0.58 0.85 0.2 0.26 0.41 0.89 0.31 0.67 0.67 0.65 0.34 0.38 0.79 0.58 1A8 0.34 0.49 0.78 0.82 1.25 0.26 0.35 0.49 1.09 0.15 0.38 0.6 0.56 0.86 0.26 1.06 H01+.14 H01+.12 HO1 +.22 H03+.1 0 H01-.12 H01+.03 H01+.16 H06-.37 H01+.07 H03+.02 H06+.09 H01+.09 H02+.07 H01+.02 HO1+.25 H01+.33 H02+.09 H03+.05 H04+.05 H01+.12 HO1 +.02 H02+.12 H01+.09 H03+.02 H01-.05 H02+.05 HOI+.05 H01+.09 H02+.12 H01+.12 HO1+.27 H03+.07 H05+.09 H03+.02 HO1+.05 H01+.13 HO1+.19 H01+.09 H01+.09 H01+.16 H01+.19 H01+.05 H04+.09 HO1+.02 HO1+.00 H02+.02 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 25
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call / Volts LOCATION 25 25 25 25 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 27 28 28 29 30 30 30 26 SAI 35 DSI 49 DSI 72 DSI 9 DSI 12 DSI 17 DSI 22 DSI 22 DSI 23 DSI 24 DSI 25 DSI 28 DSI 28 SAI 28 SAI 29 DSI 29 SAI 29 SAI 29 DSI 30 DSI 35 DSI 15 DSI 16 DSI 18 DSI 24 DSI 24 SAI 26 DSI 26 SAI 26 SAI 26 SAI 30 DSI 30 SAI 30 SAI 35 DSI 36 DSI 63 DSI 63 DSI 67 DSI 68 DSI 68 DSI 26 DSI 84 DSI 14 DSI 18 DSI 23 DSI 23 SAI 0.2 0.35 0.73 0.14 0.66 0.18 0.43 0.86 0.34 0.3 0.24 0.47 1.18 0.12 0.24 0.35 0.13 0.24 0.37 0.22 0.9 0.85 0.79 0.33 0.76 0.2 1.26 0.15 0.29 0.11 1.02 0.19 0.18 0.88 0.55 0.42 0.62 0.23 0.36 0.28 0.78 0.5 0.71 0.21 1.15 0.44 H02+.14 H01+.19 H01+.07 H02+.02 H01+.00 H01+.00 H02+.05 H04+.05 H05+.09 H01+.16 H01+.11 H02+.12 H01+.14 H01+.05 H01+.27 H01+.07 H01+.04 H01+.16 H03+.02 H02+.09 H01+.12 H01+.12 H01+.09 H03+.14 H02+.07 H02+.20 H02+.09 H02+.12 H02+.17 H02+.26 H02+.12 H02+.19 H02+.30 H01+.05 H02+.07 H02+.12 H03+.05 H02+.05 H02+.07 H05+.09 H01+.05 H01+.07 H01+.07 H01+.16 H01+.12 H01+.28 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 26
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call / Volts LOCATION 23 42 42 42 42 42 46 50 50 20 26 28 28 28 28 32 65 76 76 20 21 23 23 25 33 34 42 57 77 78 25 27 36 36 45 49 49 67 19 19 22 22 22 22 22 25 SAI DSI SAI SAI DSI SAI DSI DSI SAI DSI DSI DSI SAI SAI SAI DSI DSI DSI DSI DSI DSI DSI SAI DSI DSI DSI DSI DSI DSI DS1 DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI DSI SAI SAI SAI SAI DSI 0.56 0.47 0.14 0.11 0.4 0.12 0.75 1.03 0.3 0.39 0.41 0.88 0.17 0.12 0.23 1.03 0.94 0.71 0.5 0.3 0.32 1.39 0.45 0.43 0.64 0.46 0.7 0.53 0.4 0.53 0.57 0.68 0.33 0.31 0.4 0.53 0.82 0.15 0.73 0.36 1.16 0.12 0.14 0.2 0.13 0.33 H01+.30 H02+.05 H02+.04 H02+.22 H03+.05 H03+.12 H02+.12 H01+.05 H01+.15 H01+.00 H03+.07 H01+.12 HOI+.05 H01+.14 H01+.18 H02+.07 H02+.09 H01+.23 H02+.07 H01+.07 H01+.09 H01+.14 H01+.29 H02+.14 H02+.09 H02+.17 H02+.12 H03-.12 H01+.09 H01+.16 H04+.05 H01+.09 H02+.14 H03+.00 H02+.14 H02+.09 H03+.14 H04+.12 H02+.07 H03+.07 H01+.07 H01-.02 H01+.06 H01+.08 H01+.12 H01+.12 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC Jn Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 27
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call I Volts LOCATION 3
34 25 DSI 0.36 H04+.02 3
34 26 DSI 1.27 H01+.12 3
34 26 SAI 0.21 H01+.11 3
34 27 DSI 0.8 H03+.07 3
34 28 DSI 0.4 H04+.05 3
34 51 DSI 0.7 H02+.05 3
34 60 DSI 0.26 H04-.05 3
34 72 DSI 0.9 H02+.05 3
35 21 DSI 0.8 H01+.12 3
35 24 DSI 0.34 H03+.07 3
35 27 DSI 0.28 H01+.09 3
35 47 DSI 0.51 H03+.05 3
35 47 DSI 0.26 H04+.17 3
35 58 DSI 1.34 H02+.16 3
35 58 SAI 0.11 H02+.00 3
35 58 SAI 0.08 H02+.29 3
36 24 DSI 1.35 H01+.07 3
36 25 DSI 1.18 H02+.05 3
36 31 DSI 0.87 H05+.07 3
36 33 DSI 1.08 H03+.09 3
36 38 DSI 0.6 H02+.09 3
36 40 DSI 0.29 H04+.02 3
36 53 DSI 0.39 H03+.12 3
37 26 DSI 0.38 H02+.05 3
37 31 DSI 0.66 H03+.02 3
37 67 DSI 0.31 H02+.00 3
37 68 DSI 0.55 H02+.07 3
38 22 DSI 1.18 H01+.16 3
38 22 SAI 0.43 H01+.35 3
38 25 DSI 0.44 H01+.23 3
38 25 DSI 0.63 H03+.16 3
38 36 DSI 0.68 H02+.09 3
38 40 DSI 0.6 H03+.09 3
38 46 DSI 0.36 H02+.14 3
38 58 DSI 1.24 H02+.07 3
38 58 DSI 0.77 H03+.12 3
39 26 DSI 0.4 H01+.12 3
39 26 DSI 0.95 H02+.05 3
39 26 DSI 0.62 H03+.07 3
39 52 DSI 0.45 H02-.14 3
39 68 DSI 0.62 H04+.09 3
40 24 DSI 0.53 H02-.02 3
40 24 DSI 0.66 H03+.02 3
40 41 DSI 0.34 H03+.05 3
40 69 DSI 0.37 H02-.02 3
41 30 DSI 0.44 H01+.07 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL 0DSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 28
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call I Volts LOCATION 41 41 41 41 42 43 43 43 44 44 44 44 44 44 44 44 44 44 46 30 DSI 0.27 33 DSI 0.24 36 DSI 0.33 68 DSI 0.59 33 DS1 0.15 44 DSI 0.29 50 DSI 0.34 59 DSI 0.46 33 DSI 1.44 33 SAI 0.19 52 DSI 1.08 52 SAI 0.09 52 SAI 0.22 58 DSI 1.13 58 SAI 0.14 58 SAI 0.24 58 SAI 0.12 59 DSI 1.44 52 DSI 0.72 H03+.05 H02+.14 H04+.02 H02+.07 H01+.05 H04+.07 H04+.14 H01+.02 H01+.09 H01+.19 H02+.09 H02+.05 H02+.19 H01+.09 H01+.11 H01+.21 H01+.29 H02+.07 HOI+.09 SG 3 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC The following indications were taken out of service by plugging. The 'DSI' call is a bobbin coil probe call with the associated voltage listed. The USAI", 'SCI", or 'SVI' call is a plus point coil call with the associated voltage listed. The number call is a bobbin coil probe call of percent through-wall (maximum depth).
SG ROW COL Call / Volts LOCATION CHARACTERIZATION 1
5 5
5 5
5 8
8 8
8 8
8 12 12 15 18 18 21 24 10 19 19 19 19 19 23 56 56 56 58 58 12 12 22 49 49 30 31 SAI DSI SAI SAI SAI TBP
0.53 2.06 0.45 1.03 9.76 5.56 2.49 2.27 0.12 2.2 2.18 0.72 0.79 H07+10.75 H01+.09 H01+.20 HO1+.23 HO1+.32
+0.00 HTS-.03 H01+.09 H01+.23 H01+.36 H01-.05 HO1+.26 H01+.00 H01+.32 HTS+.00 H01+.00 HO1+.27 HTS-9.48 HTS-.22 PWSCC UBEND AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL PREVENTIVE PWSCC HTS CIRC ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC HTS CIRC ODSCC TSP AXIAL ODSCC TSP AXIAL PWSCC HTS AXIAL PWSCC HTS CIRC RESOLUTION Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged 29
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG 3 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 3
30 41 DSI 0.64 H02+.05 ODSCC TSP AXIAL 3
30 41 SAI 0.18 HTS-.14 ODSCC HTS AXIAL 3
31 62 SAI 0.24 HTS-.50 PWSCC HTS AXIAL 3
34 31 SCI 1.49 HTS-9.80 PWSCC HTS CIRC 3
35 31 SAI 1.84 HTS-9.42 PWSCC HTS AXIAL RESOLUTION Plugged Plugged Plugged Plugged Plugged The following are anti vibration bar wear indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) with associated voltage.
SG 3
3 3
3 3
3 3
3 3
3 3
3 3
3 3
3 ROW 18 19 23 23 28 28 28 32 33 33 34 35 35 38 38 40 COL Call / Volts 30 15 0.23 64 17 0.29 55 10 0.16 55 11 0.19 45 14 0.24 45 16 0.26 45 15 0.26 40 17 0.31 61 14 0.22 61 19 0.34 42 19 0.32 39 21 0.41 39 22 0.51 40 18 0.33 40 16 0.29 56 21 0.41 LOCATION AV2+.00 AV2-.37 AV3+.24 AV4+.00 AV1 +.00 AV2+.00 AV3+.00 AV3+.00 AV2+.00 AV3+.00 AV3+.00 AV1 +.07 AV2+.00 AV3+.09 AV4+.00 AV2+.00 CHARACTERIZATION AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR AVB WEAR RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
The following are cold leg thinning indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) with associated voltage.
SG 3
3 3
3 3
3 3
3 3
3 ROW 5
7 8
9 10 11 24 25 29 30 COL 1
1 87 2
93 92 87 9
83 81 Call I Volts 32 0.77 11 0.9
<20 0.25 11 0.57 33 2.1 24 0.75 29 0.77 7
0.4 37 0.53 10 0.5 LOCATION C01+.02 C01 +.07 C02-.02 C01-.16 C01+.02 CO1-.16 C01-.23 C01+.07 C01-.12 C01-.17 CHARACTERIZATION C/L Thinning CIL Thinning CIL Thinning C/L Thinning C/L Thinning C/L Thinning C/L Thinning C/L Thinning CIL Thinning CIL Thinning RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
30
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.3 SG ROW COL Call I Volts 3
30 83 16 1.12 3
30 83 15 0.23 3
31 82 30 1.06 3
33 78 4
0.66 3
33 79 34 1.75 3
34 16 31 0.56 3
34 16 4
0.44 3
34 78 12 0.26 3
34 79
<20 0.55 3
35 17 8
0.53 3
35 17
<20 0.34 3
35 78 3
1.6 3
36 74
<20 0.94 3
37 75 28 0.95 3
39 68 23 0.62 3
40 26 33 0.97 3
42 28 22 0.37 3
43 30 36 0.63 3
43 62 13 0.71 3
44 56 22 0.52 3
44 57 16 0.8 3
45 52 23 1.14 3
45 53 4
0.5 3
45 58
<20 0.32 Sc LOCATION CO1-.26 C02-.05 C01-.09 CO1-.19 CO1-.09 C01-.16 C02-.26 COI-.02 CO1 +.37 CO1-.07 C02-.14 C01+.05 CO1+.12 CO1-.05 C01 +.00 C02-.28 C01-.02 C01-.19 COl+.00 CO1 +.02 C01-.31 C01-.14 C03-.07 C01-.21 3 3 Indications (Continued)
CHARACTERIZATION RESOLUTION CIL Thinning CIL Thinning CIL Thinning CIL Thinning C/L Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning CIL Thinning C/L Thinning C/IL Thinning C/IL Thinning C/L Thinning C/IL Thinning C/IL Thinning CIL Thinning CIL Thinning C/L Thinning C/L Thinning C/L Thinning In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
31
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications The following indications are outside diameter stress corrosion cracking at tube support plates.
The eddy current call 'DSI1 is a bobbin probe call with the associated voltage listed. The call
'SAI' is a plus point probe call with the associated voltage listed. If the bobbin voltage is less than I volt, the indication may remain in service via the ODSCC Generic Letter 95-05 Alternate Repair Criteria (ARC). Details of these indications were reported in the required 90-Day Report.
If the indication is greater than 1 volt but not confirmed with plus point probe, the indication may remain in service via the ARC.
SG 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 ROW COL CallIVolts 2
14 DSI 0.37 2
15 DSI 0.49 2
15 DSI 0.73 2
25 DSI 0.63 2
38 DSI 0.55 2
38 DSI 0.66 2
53 DSI 0.71 2
53 DSI 0.61 2
55 DSI 1.09 2
55 SAI 0.26 2
55 SAI 0.36 2
56 DSI 0.42 2
57 DSI 0.55 2
67 DSI 1.12 2
67 SAI 0.5 2
67 SAI 0.36 2
72 DSI 0.6 2
74 DSI 0.64 2
74 DSI 0.7 2
75 DSI 0.42 2
76 DSI 1.37 2
76 SAI 0.43 2
76 SAI 0.54 2
84 DSI 0.34 2
86 DSI 0.57 2
90 DSI 0.49 2
92 DSI 0.39 2
94 DSI 0.4 3
16 DSI 0.37 3
18 DSI 0.27 3
18 DSI 0.9 3
25 DSI 0.73 3
25 DSI 0.69 3
25 DSI 0.5 3
34 DS1 0.29 3
43 DSI 0.74 3
71 DSI 0.81 3
71 DSI 0.18 LOCATION CHARACTERIZATION H03-.12 H02+.02 H03+.02 H01-.05 H02+.14 H03+.05 H01+.10 H02+.00 H01-.02 HOI+.28 H01+.34 H03+.17 HO1+.14 H01+.09 H01+.14 HOI+.19 H02+.00 H01-.17 H02-.12 HOI+.02 H01+.12 HO1+.21 HOI+.24 H01+.14 H02-.02 HO1-.02 HO1-.07 H01-.07 H02+.07 HO1+.02 H02-.05 HO1+.02 H02-.17 H03+.00 H02-.05 H01-.05 HO1-.14 H02+.05 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 32
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
3 88 DSI 0.6 4
3 88 DS[
0.45 4
3 92 DSI 0.49 4
4 8
DSI 0.41 4
4 12 DSI 0.62 4
4 14 DSI 0.51 4
4 19 DSI 0.51 4
4 22 DSI 0.34 4
4 23 DSI 0.8 4
4 25 DSI 0.61 4
4 27 DSI 0.4 4
4 28 DSI 0.39 4
4 40 DSI 0.83 4
4 47 DSI 0.49 4
4 74 DSI 0.5 4
4 77 DSI 0.36 4
4 78 DSI 0.71 4
4 78 DSI 0.28 4
4 82 DSI 1
4 4
82 SAI 0.24 4
4 82 SAI 0.33 4
4 82 DSI 0.48 4
4 84 DSI 0.63 4
4 86 DSI 0.78 4
4 87 DSI 0.75 4
4 87 DSI 0.5 4
4 89 DSI 0.83 4
4 90 DSI 1.06 4
4 90 SAI 0.21 4
4 90 DSI 0.85 4
4 90 DSI 0.31 4
4 90 DSI 0.41 4
4 91 DSI 0.25 4
4 92 DSI 0.79 4
4 93 DSI 0.33 4
4 94 DSI 1.07 4
4 94 SAI 0.15 4
5 1
DSI 0.26 4
5 1
DSI 0.29 4
5 26 DSI 0.64 4
5 28 DSI 1.15 4
5 28 SAI 0.4 4
5 28 SAI 0.17 4
5 30 DSI 0.74 4
5 33 DSI 0.7 H01+.00 H02+.00 H01-.07 H06+.00 H02+.09 H06-.14 H02+.05 H02+.00 H01+.07 H01+.02 H01-.02 H01+.02 H01-.10 H02-.02 H03+.00 H01+.00 H01+.12 H02-.02 H01-.02 H01+.13 H01+.18 H02+.02 H02-.02 H03+.02 H01+.12 H03-.05 H03+.05 H01+.19 H01+.24 H02+.05 H03+.02 H06-.05 H01+.00 H03+.05 H02+.02 H01-.02 H01+.20 H01+.05 H02+.02 H01-.07 H01+.00 H01+.25 H01+.25 H01+.00 H01+.10 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 33
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 4
5 34 DSI 0.81 H01+.00 4
5 35 DSI 0.61 H01-.05 4
5 37 DSI 0.31 H01-.02 4
5 38 DSI 0.8 H01+.00 4
5 38 SAI 0.25 H01+.05 4
5 39 DSI 1.03 HO1+.02 4
5 39 SAI 0.3 H01+.20 4
5 39 SAI 0.15 H01+.21 4
5 42 DSI 1.02 H01+.02 4
5 42 SAI 0.26 H01+.05 4
5 42 SAI 0.18 H01+.07 4
5 43 DSI 0.64 H01-.07 4
5 44 DSI 0.4 H01-.05 4
5 46 DSI 0.39 H01+.00 4
5 47 DSI 0.68 HO1-.05 4
5 71 DSI 0.83 H01+.00 4
5 74 DSI 0.7 H01-.17 4
5 76 DSI 0.35 H01-.05 4
5 78 DSI 0.4 H02-.07 4
5 79 DSI 0.36 H01+.12 4
5 80 DSI 1.11 HO1+.02 4
5 80 SAI 0.13 HO1+.19 4
5 83 DSI 0.41 H01+.00 4
5 89 DSI 0.83 HO1+.12 4
5 91 DSI 0.88 H01+.00 4
5 92 DSI 0.67 H01+.02 4
5 93 DSI 0.75 H01+.10 4
6 2
DSI 0.57 H02-.05 4
6 18 DSI 0.59 H03-.02 4
6 23 DSI 0.76 H02-.05 4
6 24 DSI 0.61 HO1-.05 4
6 25 DSI 0.37 H02-.09 4
6 28 DSI 0.6 H01+.07 4
6 32 DSI 0.28 H02-.10 4
6 45 DSI 0.39 HO1+.05 4
6 66 DSI 0.73 H01+.05 4
6 66 SAI 0.14 H01+.00 4
6 66 SAI 0.27 H01+.13 4
6 72 DSI 0.71 H01-.10 4
6 73 DSI 0.41 HO1+.00 4
6 74 DSI 0.83 H01+.07 4
6 75 DSI 0.6 HO1+.05 4
6 76 DSI 0.49 H01+.00 4
6 78 DSI 0.42 H01+.05 4
6 80 DSI 0.86 HO1+.02 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 34
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 81 84 87 87 88 88 90 90 90 90 91 92 94 18 46 48 48 48 54 55 56 58 58 58 59 64 3
3 3
3 3
4 8
12 12 17 25 27 27 27 27 27 27 28 28 DSI 0.29 DSI 0.55 DSI 0.69 DSI 0.22 DSI 0.96 SAI 0.15 DSI 0.91 DSI 0.4 DSI 0.59 DSI 0.69 DSI 0.72 DSI 0.33 DSI 0.28 DS0 0.53 DSI 0.49 DSI 1.65 SAI 0.63 SAI 0.32 DSI 1.02 DSI 0.94 DSI 0.54 DSI 0.8 SAI 0.54 SAI 0.16 DS1 0.75 DS1 0.29 DSI 1.03 SAI 0.04 SAI 0.46 DSI 0.71 DSI 0.26 DSI 0.35 DSI 0.26 DSI 0.53 DSI 0.53 DSI 0.98 DSI 0.62 DS1 0.65 SAI 0.23 SAI 0.3 DSI 0.5 DSI 0.99 SAI 0.21 DSI 0.53 SAI 0.22 H02-.10 HO1+.12 H02+.00 H03+.00 HO1-.02 HOI+.14 H01+.12 H02+.02 H03-.05 H04-.07 H01+.12 HO1+.00 H03-.02 H02-.02 H01-.07 H01-.02 HOI+.22 HOI+.22 H01-.02 H01-.07 HO1-.12 H01-.02 H01+.20 H01+.32 H01+.05 H01+.02 H02-.05 H02-.02 H02+.24 H03-.05 H04-.09 H02-.07 H02-.07 H01+.07 H03+.00 H02+.14 HO1+.21 HO1-.14 H01+.33 H01+.34 H02+.16 H03-.14 H03+.32 HOI-.02 HO1+.11 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 35
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG ROW COL Call I Volts 28 29 30 31 32 32 33 34 34 34 34 35 36 37 37 37 38 39 39 40 41 42 44 45 48 48 48 50 52 55 56 56 56 56 59 60 60 60 60 67 71 73 78 78 80 SAI DSI DSI DSI DSI SAI DSI DSI SAI SAI SAI DSI DSI DSI SAI SAI DSI DSI DSI DSI DSI DSI DSI DSI DSI SAI SAI DSI DSI DSI DSI SAI SAI SAI DSI DSI SAI SAI SAI DSI DSI DSI DSI DSI DSI 0.32 0.53 0.54 0.81 1.03 0.52 0.51 1.19 0.38 0.5 0.39 0.4 0.49 1.59 0.23 0.34 0.47 0.58 0.29 0.42 0.73 0.65 0.28 0.38 0.76 0.16 0.16 0.5 0.89 0.53 0.57 0.09 0.1 0.11 0.91 1.33 0.24 0.37 0.15 0.43 0.64 0.6 0.7 0.53 0.9 LOCATION H01+.30 H01-.02 H01-.02 H01+.07 H01+.02 H01+.22 H01-.02 H01+.14 H01+.03 H01+.22 H01+.25 H01-.05 H01-.14 H01+.02 H01+.27 H01+.34 H01-.02 H01-.02 H03+.07 H01+.14 H01+.02 H01-.02 H02-.07 H01-.05 H01-.07 H01-.01 H01+.00 H01+.05 H01-.02 H01+.02 H01+.00 H01+.18 H01+.34 H01+.34 H01-.05 H01-.10 H01+.10 H01+.19 H01+.26 H03+.07 H01+.00 H03+.00 H01+.07 H03-.12 H01-.02 SG 4 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 36
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
ROW COL Call I Volts 8
80 DSI 0.52 8
81 DSI 0.49 8
83 DSI 0.81 8
84 DS1 0.48 8
85 DSI 0.88 8
85 DSI 1.23 8
85 SAI 0.37 8
85 SAI 0.39 8
86 DSI 0.58 8
89 DSI 0.96 8
89 DSI 0.45 8
90 DSI 0.49 8
91 DSI 0.61 8
92 DSI 1.41 8
92 SAI 0.55 8
92 DSI 1.16 8
92 SAI 0.19 8
92 SAI 0.33 8
92 DSI 0.36 9
2 DSI 0.86 9
2 SAI 0.11 9
2 SAI 0.1 9
10 DSI 0.31 9
11 DSI 0.54 9
12 DSI 0.36 9
18 DSI 0.58 9
21 DSI 0.83 9
22 DSI 1.07 9
22 SAI 0.15 9
22 SAI 0.23 9
23 DS1 0.37 9
24 DSI 0.73 9
25 DSI 0.38 9
28 DSI 0.36 9
29 DSI 0.47 9
30 DSI 0.88 9
31 DSI 0.32 9
33 DSI 0.39 9
35 DSI 1.26 9
35 SAI 0.49 9
36 DSI 0.2 9
37 DSI 0.65 9
38 DSI 1.23 9
38 SAI 0.39 9
38 SAI 0.35 H02-.14 HO1+.00 H01-.07 H02+.00 HO1+.00 H02+.05 H02+.18 H02+.22 HO1+.00 H01+.12 H02+.07 H02+.05 H03-.07 H01+.07 H01+.29 H02+.19 H02+.25 H02+.25 H04-.05 H02-.02 H02+.02 H02+.26 H02-.05 H01+.07 H01+.00 H02+.14 H02+.14 H02+.10 H02+.21 H02+.23 H01+.02 H01-.02 H01+.05 H02-.10 HO1-.05 H01+.02 H01-.02 HO1-.10 HO1-.21 H01+.09 H01-.02 H01+.10 HO1-.05 HO1+.04 H01+.14 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 37
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 9
39 DSI 0.61 HO1+.07 9
42 DSI 1.19 H01+.07 9
42 SAI 0.31 H01+.09 9
42 SAI 0.26 HO1+.09 9
42 SAI 0.17 H01+.16 9
43 DSI 0.79 H01-.10 9
44 DSI 0.92 H01+.05 9
46 DSI 0.88 HO1+.00 9
46 DSI 0.45 H03-.10 9
47 DSI 0.53 HO1-.10 9
47 SAI 0.26 HO1+.08 9
48 DSI 0.83 HO1-.21 9
48 DSI 0.63 H03-.05 9
53 DSI 0.75 HO1+.00 9
57 DSI 1.02 H01+.00 9
57 SAI 0.11 HO1+.02 9
57 SAI 0.17 HO1+.11 9
57 SAI 0.21 H01+.16 9
61 DSI 0.46 H01+.02 9
70 DSI 0.57 H01-.02 9
74 DSI 0.34 H04-.05 9
83 DSI 0.3 H01-.02 9
89 DSI 0.71 H02+.00 10 3
DSI 0.64 H02+.05 10 31 DSI 0.34 H01+.05 10 35 DSI 0.73 H01-.07 10 52 DSI 0.44 H01+.09 11 42 DSI 0.39 HO1+.09 11 68 DSI 0.42 H07+.24 11 69 DSI 0.31 H03+.14 11 75 DSI 0.71 H02+.05 11 84 DSI 0.64 H04+.00 12 2
DSI 1.11 H02+.09 12 2
SAI 0.14 H02+.02 12 2
SAI 0.23 H02+.29 12 15 DSI 0.36 H04+.12 12 18 DSI 0.73 H02+.12 12 21 DSI 1.12 H01+.05 12 21 SAI 0.35 H01+.27 12 21 SAI 1.04 H01+.35 12 21 DSI 0.74 H02+.09 12 23 DSI 0.6 HO1+.09 12 24 DSI 1
H01+.26 12 24 SAI 0.14 H01+.33 12 24 SAI 0.28 H01+.36 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 38
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
12 24 DSI 0.83 4
12 26 DSI 0.3 4
12 26 DSI 0.3 4
12 27 DSI 0.39 4
12 31 DSI 0.47 4
12 32 DSI 1.12 4
12 32 SAI 0.3 4
12 32 SAI 0.18 4
12 32 SAI 0.26 4
12 35 DSI OA6 4
12 36 DSI 0.56 4
12 36 DSI 0.32 4
12 38 DSI 0.41 4
12 38 DSI 0.36 4
12 39 DSI 0.41 4
12 39 DSI 0.36 4
12 40 DSI 0.65 4
12 41 DSI 0.7 4
12 41 DSI 0.41 4
12 43 DSI 1
4 12 43 SAI 0.24 4
12 43 SAI 0.15 4
12 43 SAI 0.9 4
12 44 DSI 0.9 4
12 59 DSI 0.42 4
12 59 DSI 0.36 4
12 61 DSI 0.64 4
12 62 DSI 0.66 4
12 63 DSI 0.72 4
12 71 DSI 0.73 4
12 74 DSI 0.62 4
12 74 DSI 0.22 4
12 75 DSI 0.74 4
12 76 DSI 1.14 4
12 76 SAI 0.16 4
12 76 SAI 0.62 4
12 81 DSI 0.81 4
12 82 DSI 0.66 4
12 83 DSI 1.21 4
12 83 SAI 0.17 4
12 83 SAI 0.53 4
13 15 DSI 0.52 4
13 29 DSI 0.43 4
13 33 DSI 0.4 4
13 34 DSI 0.78 H02+.30 H01+.09 H02+.09 H01+.07 H03+.05 H01+.00 H01+.05 HOI+.08 H01+.18 H01+.12 H01+.09 H02+.19 H01-.02 H05+.14 H01+.07 H06+.09 H01+.09 H01+.05 H03+.16 H01+.07 H01-.02 H01+.14 H01+.29 H01+.19 H01+.14 H05+.09 H01+.05 H01-.09 H01-.07 H01+.00 H01-.09 H02+.00 HO1-.09 H01-.09 H01-.08 H01+.07 H101+.05 H01+.07 H01+.02 H01-.01 H01+.10 H02-.09 H02+.05 H01+.16 H01+.09 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 39
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
13 39 DSI 0.36 4
13 41 DSI 0.55 4
13 42 DSI 0.89 4
13 43 DSI 0.65 4
13 43 SAI 0.16 4
13 44 DSI 0.64 4
13 44 DSI 0.31 4
13 45 DSI 0.66 4
13 46 DSI 0.43 4
13 46 DSI 0.27 4
13 47 DSI 0.69 4
13 48 DSI 1.18 4
13 48 SAI 0.16 4
13 48 SAI 0.27 4
13 48 SAI 0.66 4
13 49 DSI 0.62 4
13 50 DSI 0.56 4
13 51 DSI 0.24 4
13 52 DSI 0.49 4
13 53 DSI 0.89 4
13 54 DSI 0.43 4
13 62 DSI 0.22 4
13 68 DSI 0.39 4
13 77 DSI 0.5 4
13 82 DSI 0.65 4
14 22 DSI 1.06 4
14 22 SAI 0.41 4
14 22 DSI 0.52 4
14 57 DSI 1.22 4
14 57 SAI 0.25 4
14 57 SAI 0.32 4
14 57 SAI 0.3 4
14 59 DSI 0.49 4
14 60 DSI 0.31 4
14 77 DSI 0.95 4
14 77 DSI 0.39 4
14 77 SAI 0.22 4
14 81 DSI 0.37 4
14 83 DSI 0.54 4
14 86 DSI 0.74 4
14 88 DSI 0.68 4
14 88 DSI 0.67 4
14 89 DSI 0.95 4
14 90 DSI 0.93 4
14 90 DSI 0.5 H02+.19 H03+.16 HO1+.09 H03+.07 H03+.18 H01+.05 H02+.07 HOI+.05 HOI+.05 H03-.05 H01-.05 H01-.02 HOI+.03 H01+.10 H01+.18 H01+.09 H03-.14 H01+.07 H01+.09 H01+.12 H01+.07 H01+.09 H02+.05 H01-.13 H02-.14 H01+.12 HOI+.20 H02-.05 H01+.05 H01+.20 H01+.28 H01+.32 H01+.14 H01+.09 HO1+.09 H02+.09 H02+.22 H02+.04 HO1+.04 H-01+.05 H01+.05 H03+.12 H01+.02 HO1+.02 H02+.07 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 40
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
ROW COL Call I Volts 14 92 DSI 1.2 14 92 SAI 0.25 15 4
DSI 0.4 15 48 DSI 0.46 15 49 DSI 0.35 15 49 DSI 0.37 15 50 DSI 0.93 15 50 DSI 0.53 15 51 DSI 0.89 15 52 DSI 1.14 15 52 SAI 0.11 15 52 SAI 0.38 15 53 DSI 0.91 15 54 DSI 0.75 15 62 DSI 0.38 15 63 DSI 0.31 15 64 DSI 0.53 15 65 DSI 0.51 15 66 DSI 0.28 15 67 DSI 0.57 16 35 DSI 0.34 16 43 DSI 0.26 16 45 DSI 0.37 16 80 DSI 0.5 16 91 DSI 0.56 17 9
DSI 0.12 17 13 DSI 0.54 17 21 DSI 0.58 17 26 DSI 1
17 26 SAI 0.14 17 26 SAI 0.14 17 27 DSI 0.62 17 29 DSI 0.25 17 30 DS0 0.23 17 31 DSI 0.51 17 32 DSI 0.41 17 55 DSI 0.43 17 56 DSI 0.7 17 56 DSI 0.3 17 57 DSI 0.53 17 58 DSI 0.51 17 58 DSI 0.39 17 61 DSI 0.61 17 62 DSI 0.41 17 80 DSI 0.32 H01-.12 H01+.21 H02+.09 H01+.02 H01+.02 H03+.12 H01-.02 H02-.07 H01+.00 H01+.00 H01+.22 H01+.23 H01+.09 H01+.02 H01+.02 H01+.09 H01+.21 H01+.09 H01+.00 H01+.16 H01+.12 H01+.09 H01+.07 H03+.07 H01+.02 H02+.12 H02+.19 H04+.09 H02+.26 H02-.10 H02+.18 H01+.07 H01+.07 H01+.09 H04-.02 H01+.12 H01+.00 H01+.00 H02+.07 H01+.00 H01+.05 H03+.02 H01+.02 H01+.05 H01-.07 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 41
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG ROW COL Call I Volts 17 17 17 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 19 19 19 19 19 19 19 19 19 19 19 20 20 20 20 20 20 20 20 82 87 91 11 15 15 15 16 21 21 32 33 36 38 40 40 42 46 46 51 57 58 61 64 67 69 35 42 43 51 53 63 71 76 84 87 90 19 20 25 25 25 25 26 31 DSI 0.78 DSI 0.97 DSI 0.5 DSI 0.19 DSI 0.17 DSI 0.25 DSI 0.18 DSI 0.44 DSI 0.52 DSI 0.47 DSI 0.46 DSI 0.48 DSI 0.39 DSI 0.4 DSI 0.36 DSI 0.21 DSI 0.26 DSI 1.04 SAI 0.3 DSI 0.3 DSI 0.93 DSI 0.85 DSI 0.86 DSI 0.43 DSI 0.7 DSI 0.39 DSI 0.62 DSI 0.31 DSI 0.4 DSI 0.87 DSI 0.26 DSI 0.8 DSI 0.73 DSI 0.35 DSI 0.94 DSI 0.33 DSI 0.3 DSI 0.42 DSI 0.26 DSI 1.04 SAI 0.16 SAI 0.34 DSI 0.48 DSI 0.92 DSI 0.37 LOCATION H01+.07 H01+.12 H01+.02 H04+.07 H02+.02 H03+.05 H04+.12 H05-.02 H01+.19 H02+.16 H03+.14 H05+.00 H03+.00 H03+.05 H01+.12 H05+.12 H04+.05 H01-.14 H01+.21 H05+.09 H01+.00 H01+.02 H01+.00 H01+.09 H01+.07 H02+.07 H01+.02 H01+.12 H02-.12 H01+.05 H04+.07 H01+.02 H01-.14 H02+.07 H01+.02 H03+.12 H02+.12 H02+.07 H04+.09 H01+.14 H01+.14 H01+.17 H02+.16 H02+.05 H03+.09 SG 4 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 42
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
20 32 DSI 0.38 4
20 34 DSI 0.28 4
20 34 DSI 0.73 4
20 39 DSI 0.9 4
20 39 DSI 0.29 4
20 40 DS1 1.01 4
20 40 SAI 0.2 4
20 40 SAI 0.48 4
20 40 DSI 0.25 4
20 42 DSI OA 4
20 44 DS1 0.59 4
20 44 DSI 0.69 4
20 46 DSI 0.75 4
20 46 DSI 0.89 4
20 46 DSI 0.48 4
20 46 DSI 0.41 4
20 47 DSI 0.4 4
20 47 SAI 0.38 4
20 47 DSI 0.39 4
20 47 DSI 0.49 4
20 48 DSI 1.11 4
20 48 SAI 0.28 4
20 49 DSI 0.28 4
20 50 DSI 0.79 4
20 51 DSI 0.77 4
20 52 DSI 0.88 4
20 53 DSI 0.39 4
20 54 DSI 0.75 4
20 55 DSI 0.51 4
20 56 DSI 0.39 4
20 57 DSI 0.47 4
20 57 SAI 0.12 4
20 57 SAI 0.2 4
20 57 SAI 0.1 4
20 58 DS1 0.48 4
20 59 DSI 0.88 4
20 60 DSI 1.04 4
20 60 SAI 0.13 4
20 60 SAI 0.18 4
20 61 DS0 0.48 4
20 62 DS1 0.36 4
20 63 DSI 0.91 4
20 64 DSI 0.49 4
20 64 DSI 0.48 4
20 65 DSI 0.55 H01+.24 H01+.14 H02+.19 H01+.14 H03+.02 HO1+.21 H01+.11 H01+.23 H05+.02 HOI+.02 H02-.02 H03+.05 H01+.05 H02-.16 H03+.07 H06+.05 H01+.05 HO1+.27 H02-.02 H03+.00 H01+.12 H01+.26 H01+.02 H01+.09 H01+.02 H01+.14 H03+.00 H01+.05 H02-.05 H01+.09 H01+.00 H01-.11 Hal+.05 H01+.24 HO1+.05 H01+.00 H01+.07 H01-.13 H01+.15 H01+.12 H01-.12 H01+.07 HO1+.07 H02-.02 H01+.07 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSPAXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 43
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG ROW COL Call/Volts 20 20 20 20 20 20 20 21 21 21 21 21 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 23 23 23 23 23 23 23 23 23 23 66 68 69 69 69 69 70 15 44 48 48 51 8
23 24 25 25 33 33 36 41 46 46 46 47 47 59 59 59 65 70 70 70 70 70 44 45 56 60 60 61 63 63 63 63 DSI 0.28 DSI 0.59 DSI 1.43 SAI 0.24 SAI 0.4 SAI 0.43 DSI 0.91 DSI 0.38 DSI 0.26 DSI 0.54 DSI 0.7 DSI 0.41 DSI 0.55 DSI 0.22 DSI 0.32 DSI 0.39 DSI 0.68 DSI 1.42 SAI 0.4 DSI 0.54 DSI 0.89 DSI 0.5 DSI 0.61 DSI 0.64 DSI 1.07 SAI 0.72 DSI 0.87 DSI 0.72 SAI 0.2 DSI 0.73 DSI 1.36 SAI 0.21 SAI 0.31 SAI 0.2 DSI 0.46 DSI 0.37 DSI 0.43 DSI 0.36 DSI 0.75 SAI 0.2 DSI 0.48 DSI 1.05 SAI 0.3 SAI 0.18 SAI 0.4 LOCATION H02+.05 HO1+.09 H01+.14 H01+.09 H01+.16 HO1+.22 H02-.02 H06+.00 H01+.07 HO1+.00 H02-.14 HO1+.05 H02+.14 H02+.09 H03+.00 H02+.21 H03+.05 H02-.12 H02+.24 H01+.36 HO1+.00 H01+.00 H02+.02 H03-.05 H02+.23 H02+.26 H01-.07 H02+.02 H02+.25 HO1-.11 H01+.09 H01-.04 H01+.20 HO1+.27 H02+.00 H03+.02 HO1+.05 H02-.02 H01+.05 HO1+.10 H02+.14 H01-.14 H01-.05 HO1+.22 H01+.27 SG 4 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 44
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
23 64 DSI 0.86 4
23 65 DSI 0.86 4
23 66 DSI 0.76 4
23 66 DSI 0.45 4
23 67 DSI 0.51 4
23 68 DSI 0.56 4
23 69 DS1 0.91 4
23 69 DSI 0.77 4
23 70 DSI 1.1 4
23 70 SAI 0.63 4
23 71 DSI 0.69 4
23 71 DSI 0.66 4
23 72 DSI 0.66 4
23 73 DSI 0.92 4
23 73 DSI 0.3 4
23 74 DSI 0.71 4
23 75 DSI 0.78 4
23 86 DSI 0.61 4
23 86 DSI 0.27 4
23 87 DS1 0.79 4
24 46 DSI 0.57 4
24 46 DSI 0.54 4
24 52 DSI 0.65 4
24 62 DSI 0.25 4
25 40 DSI 1
4 25 40 SAI 0.14 4
25 40 SAI 0.43 4
25 41 DS1 0.92 4
25 42 DSI 0.91 4
25 43 DSI 0.74 4
25 47 DSI 0.44 4
25 50 DSI 0.28 4
25 53 DSI 0.96 4
25 53 DSI 0.19 4
25 58 DSI 0.62 4
25 60 DSI 0.76 4
25 60 DSI 0.36 4
25 67 DSI 0.39 4
25 80 DSI 0.72 4
25 83 DSI 0.75 4
25 85 DSI 0.59 4
26 14 DSI 0.59 4
26 19 DSI 0.73 4
26 19 DSI 0.42 4
26 20 DSI 0.48 HO1+.05 H02+.09 HOI+.09 H02+.00 H02+.05 H01+.14 H01+.21 H02+.33 H01+.05 H01+.29 H-01+.05 H02+.00 H01+.07 H02+.07 H06+.05 HOI+.09 HO1+.00 H01+.12 H03+.05 H01+.05 H01+.05 H02+.37 H02+.26 H02+.07 H01+.07 HOI+.08 HO1+.19 H01+.14 H01-.02 H01+.14 H05-.07 HO1+.09 H01-.09 H02+.09 HO1+.02 H01-.05 H02+.00 H04+.00 H02+.07 HO1+.11 H01+.12 H03+.12 H02+.16 H03+.16 H02+.05 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 45
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
26 21 DSI 0.33 4
26 27 DSI 0.37 4
26 27 DSI 0.34 4
26 29 DSI 0.27 4
26 31 DSI 0.37 4
26 31 DSI 0.31 4
26 33 DSI 0.81 4
26 35 DSI 0.72 4
26 36 DSI 0.67 4
26 47 DSI 0.27 4
26 62 DSI 0.44 4
26 64 DSI 0.46 4
26 65 DSI 0.91 4
26 65 SAI 0.11 4
26 65 SAI 0.17 4
26 68 DSI 1.29 4
26 68 SAI 0.49 4
26 69 DSI 0.77 4
26 71 DSI 0.47 4
26 72 DSI 0.36 4
26 73 DSI 0.83 4
26 85 DSI 0.32 4
27 15 DSI 0.82 4
27 18 DSI 0.36 4
27 22 DSI 0.3 4
27 45 DSI 0.58 4
27 46 DSI 0.57 4
27 53 DSI 0.34 4
27 62 DSI 0.57 4
27 63 DSI 0.71 4
27 63 DS1 0.65 4
27 65 DSI 0.6 4
27 65 DSI 0.4 4
27 66 DSI 0.47 4
27 66 DSI 0.29 4
27 67 DSI 0.61 4
27 69 DSI 0.9 4
27 71 DSI 1.49 4
27 71 SAI 0.52 4
27 72 DSI 0.51 4
27 72 DSI 0.57 4
27 73 DSI 1.58 4
27 73 SAI 0.2 4
27 73 SAI 0.22 4
27 73 SAI 0.2 H03+.16 H03+.05 H06+.02 H02+.12 H03+.07 H06+.02 H02-.12 H01+.14 HO1-.12 H03+.02 H01+.05 HOI-.02 H02+.09 H02-.08 H02+.01 H01+.21 H01+.29 H01+.09 HOI+.05 H01+.07 H02-.05 HOI+.02 H02+.09 H02+.14 H04+.00 H01+.16 H01+.09 H01+.05 HO1+.07 H01+.02 H02+.05 H02-.02 H03-.09 H02+.07 H04+.09 H02-.05 H01+.12 H01+.00 HO1+.27 H02+.02 H03+.02 H02+.19 H02-.06 H02-.13 H02+.17 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSPAXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 46
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
27 73 SAI 0.47 4
27 73 DSI 0.43 4
27 74 DSI 0.81 4
27 74 DSI 0.64 4
27 75 DSI 1.15 4
27 75 SAI 0.12 4
27 75 SAI 0.18 4
27 75 SAI 0.11 4
27 75 DSI 0.78 4
27 75 DSI 0.41 4
27 76 DSI 0.29 4
27 77 DSI 0.81 4
27 77 DSI 0.67 4
27 77 DSI 0.96 4
27 78 DSI 0.48 4
27 78 DSI 0.95 4
27 79 DSI 0.73 4
27 80 DSI 0.43 4
27 80 DSI 0.69 4
27 81 DSI 0.6 4
27 82 DSI 0.85 4
27 82 DSI 0.51 4
27 83 DS[
0.52 4
27 83 DSI 0.2 4
27 84 DSI 0.26 4
27 84 DSI 0.87 4
28 20 DSI 0.45 4
28 28 DSI 0.26 4
28 35 DSI 0.48 4
28 40 DSI 0.39 4
28 45 DSI 0.45 4
28 47 DSI 0.31 4
28 48 DSI 0.71 4
28 48 DSI 0.49 4
28 62 DSI 0.43 4
28 63 DSI 0.44 4
28 64 DSI 0.48 4
28 65 DSI 0.78 4
28 66 DSI 0.58 4
28 66 DSI 0.65 4
28 67 DSI 1.31 4
28 67 SAI 0.2 4
28 67 SAI 0.15 4
28 67 SAI 0.15 4
28 68 DSI 0.76 H02+.25 H03+.00 H01+.09 H02+.07 HO1 +.09 H01+.04 H01+.10 H01+.18 H02+.22 H03+.00 H02+.09 H01+.02 H02+.11 H03+.16 H01+.12 H02-.05 H02+.05 H02+.02 H03+.12 H03+.07 H03+.00 H05+.14 H03+.02 H04+.07 HO1+.00 H02+.02 HOl+.02 H04+.00 H02+.19 H02+.12 H01+.07 H02+.09 H01+.02 H03+.02 H02+.07 H02+.05 H02+.00 H01+.05 H02+.07 H03-.09 HO1+.09 HO1+.01 HO1+.11 HO1+.14 HO1+.00 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 47
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG ROW COL Call I Volts 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 29 29 29 29 29 29 29 29 29 29 29 29 29 29 29 30 30 30 30 68 68 70 70 71 71 71 72 72 72 73 74 74 74 75 75 76 76 77 78 79 80 81 81 81 82 14 18 19 27 27 28 38 43 46 47 48 50 51 56 59 18 21 28 54 DSI 0.43 DSI 0.47 DSI 0.37 DSI 0.4 DSI 1.01 SAI 0.14 SAI 0.21 DS1 0.85 DSI 0.83 DSI 0.41 DSI 0.75 DSI 0.28 DSI 0.83 DSI 0.43 DSI 0.95 DSI 0.78 DSI 0.27 DS1 0.4 DSI 0.8 DSI 0.68 DSI 0.49 DSI 0.54 DSI 0.37 DSI 0.55 DSI 0.64 DSI 0.75 DSI 0.32 DSI 0.85 DSI 0.78 DS]
0.41 DSI 0.21 DSI 0.29 DSI 0.37 DSI 0.69 DSI 0.22 DSI OA4 DSI 0.64 DSI 0.44 DSI 0.66 DSI 0.35 DSI 0.52 DSI 0.36 DSI 0.41 DSI 0.13 DSI 0.29 LOCATION H02+.12 H05+.07 HO1+.09 H02+.19 HO1+.00 H01+.12 H01+.21 HO1-.05 H02+.21 H03+.09 H01-.09 H02+.09 H03+.16 H05+.02 HO1 +.04 H02+.11 HOI+.07 H02+.14 HOI+.04 H01+.09 H03+.11 H03+.09 HO1 +.02 H02+.00 H03+.02 H02+.02 H01+.05 H07+.19 H06+.17 H02+.00 H07+.02 H02+.07 HO1+.12 HO1+.19 H02+.07 H01+.05 H01+.09 H01+.05 HO1+.07 H02+.07 H06+.00 H02+.14 H02+.07 H04+.02 H01+.07 SG 4 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 48
e f-4 Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION SG ROW COL Call I Volts 4
30 81 DSI 0.32 4
31 39 DSI 0.47 4
31 40 DSI 0.35 4
31 54 DSI 0.48 4
31 55 DSI 0.57 4
31 58 DSI 0.3 4
31 59 DSI 0.36 4
31 71 DSI 0.92 4
31 71 SAI 0.19 4
31 71 SAI 0.11 4
31 71 SAI 0.19 4
31 71 DSI 0.74 4
31 71 DSI 0.54 4
31 72 DSI 0.67 4
32 20 DSI 0.3 4
32 39 DSI 0.35 4
32 44 DSI 0.56 4
32 49 DSI 0.41 4
32 62 DSI 0.65 4
32 62 SAI 0.11 4
32 62 SAI 0.08 4
32 62 DSI 0.69 4
32 64 DSI 0.58 4
32 64 DSI 0.69 4
32 65 DSI 0.35 4
32 65 DSI 0.35 4
32 66 DSI 0.57 4
32 67 DSI 1.08 4
32 67 SAI 0.16 4
32 67 DSI 0.48 4
32 68 DSI 0.61 4
32 69 DSI 0.87 4
32 70 DSI 0.73 4
32 70 DSI 0.71 4
32 70 DSI 0.27 4
32 71 DSI 0.29 4
32 71 DSI 0.36 4
32 74 DSI 0.7 4
32 75 DSI 0.5 4
32 77 DSI 0.5 4
33 51 DSI 0.5 4
33 54 DSI 0.28 4
33 67 DSI 0.34 4
33 68 DSI 0.5 4
34 25 DSI 0.98 H02+.02 H01+.07 H02+.07 H01+.07 H02+.09 H02+.07 H07+.00 HOI+.05 H01+.08 HO1+.17 HOI+.22 H02+.07 H03+.12 H01+.05 H02+.07 H01+.14 H04-.14 HOI+.07 H01+.07 HO1 +.02 H01+.17 H02+.09 HOI+.09 H02+.14 HO1+.00 H02+.07 H01-.05 H02+.09 H02+.25 H03+.09 H02+.02 H01-.07 HO1-.02 H02+.12 H03+.12 HO1+.16 H03+.07 H01+.07 H04+.07 H04+.12 H02+.14 H01+.12 H02+.02 H01-.02 H02+.05 ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCCTSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 49
S I
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG ROW COL CallIVolts 34 34 34 34 34 34 34 34 34 35 35 35 35 35 35 35 35 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 37 37 37 38 38 38 38 38 38 38 38 38 39 30 47 50 58 64 65 65 69 72 33 35 38 46 62 66 69 73 24 47 48 54 56 57 57 59 60 62 64 65 67 68 72 62 63 72 24 26 26 30 32 34 38 72 74 27 DSI 0.54 DSI 0.45 DSI 0.73 DSI 0.54 DSI 0.57 DSI 0.42 DSI 0.49 DSI 0.22 DSI 0.37 DSI 0.26 DSI 0.26 DSI 0.52 DS0 0.36 DSI 0.37 DSI 0.65 DSI 0.25 DSI 0.46 DSI 0.48 DSI 0.29 DSI 0.53 DSI 0.27 DSI 0.48 DSI 0.39 DSI 0.43 DSI 0.31 DSI 0.47 DSI 0.86 DSI 0.61 DSI 0.55 DSI 0.15 DSI 0.32 DSI 0.36 DSI 0.31 DSI 0.54 DSI 0.51 DSI 0.45 DS0 0.42 DSI 0.23 DSI 0.35 DSI 0.38 DSI 0.37 DSI 0.32 DSI 0.78 DSI 0.61 DSI 0.48 LOCATION H02+.14 H01+.14 H03+.00 H02+.12 H02-.05 H01+.09 H02+.12 H02+.14 H01+.12 H03+.07 H02+.07 H03-.02 H06+.14 H02+.02 H02+.25 H01+.07 H02+.09 H04+.07 H01+.07 H02-.09 H04+.12 H02+.12 H02+.19 H03+.07 H01+.02 H02+.00 H02+.00 H02+.23 H01+.12 H06+.02 H02+.07 H01+.09 H04+.00 H01+.07 H01+.07 H03+.02 H02+.02 H04+.09 H02+.12 H02+.14 H02+.09 H04+.09 H02+.09 H03+.12 H03+.09 SG 4 Indications (Continued)
CHARACTERIZATION ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC 50
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
ROW COL Call I Volts 39 37 DSI 0.42 39 41 DSI 0.28 39 42 DSI 0.57 39 42 DSI 0.3 39 49 DSI 0.69 39 50 DSI 0.37 39 64 DSI 0.4 39 66 DSI 0.33 39 70 DSI 0.62 40 29 DSI 0.35 40 57 DSI OA6 40 67 DSI 0.36 42 38 DSI 0.61 43 65 DSI 0.32 45 51 DSI 0.52 SG 4 Indications (Continued)
LOCATION CHARACTERIZATION H03+.09 ODSCC TSP AXIAL H03+.09 ODSCC TSP AXIAL H03+.00 ODSCC TSP AXIAL H04-.05 ODSCC TSP AXIAL H02+.12 ODSCC TSP AXIAL H02+.12 ODSCC TSP AXIAL H02+.09 ODSCC TSP AXIAL H01+.09 ODSCC TSP AXIAL H03-.12 ODSCC TSP AXIAL H03+.07 ODSCC TSP AXIAL H01+.12 ODSCC TSP AXIAL H01+.05 ODSCC TSP AXIAL H02+.07 ODSCC TSP AXIAL H01+.09 ODSCC TSP AXIAL H04-.12 ODSCC TSP AXIAL RESOLUTION In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC In Service via ARC The following indications were taken out of service by plugging. The 'DSI" call is a bobbin coil probe call with the associated voltage listed. The 'SAI", 'SCI", or 'SVI' call is a plus point coil call with the associated voltage listed. The number call is a bobbin coil probe call of percent through-wall (maximum depth).
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 73 73 73 73 72 72 72 72 72 5
5 5
5 31 31 31 31 31 6
6 6
TBP 0
+0.00 DSI 1.25 H01+.00 SAI 0.96 H01+.22 DSI 0.32 H02+.00 TBP 0
+0.00 DSI 1.14 H01+.00 SAI 0.17 H01+.09 SAI 0.76 H01+.12 SAI 0.44 H01+.24 SAI 0.22 HTS-.47 SAI 0.16 HTS-.47 SAI 0.2 HTS-.67 SAI 0.22 HTS-1.03 SAI 0.34 H07+2.32 SAI 0.64 H07+3.13 SAI 0.49 H07+3.71 SAI 0.64 H07+5.65 SAI 0.65 H07+6.97 DSI 0.18 H02-.05 DSI 0.41 H03+.02 SAI 0.1 HTS-.18 PREVENTIVE ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL PREVENTIVE ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC HTS AXIAL ODSCC HTS AXIAL ODSCC HTS AXIAL ODSCC HTS AXIAL PWSCC UBEND AXIAL PWSCC LUBEND AXIAL PWSCC UBEND AXIAL PWSCC UBEND AXIAL PWSCC UBEND AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC HTS AXIAL RESOLUTION Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged 51
i r,
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION RESOLUTION 4
5 6
SAI 0.12 HTS-.41 ODSCC HTS AXIAL Plugged 4
5 6
SAI 0.13 HTS-.65 ODSCC HTSAXIAL Plugged 4
6 6
SAI 0.17 HTS-.34 ODSCC HTS AXIAL Plugged 4
6 34 TBP 0
+0.00 PREVENTIVE Plugged 4
6 34 DSI 1.35 H01-.07 ODSCC TSP AXIAL Plugged 4
6 34 SAI 1.53 HO 1+.21 ODSCC TSP AXIAL Plugged 4
6 34 DSI 0.43 H02+.0O ODSCC TSP AXIAL Plugged 4
6 43 TBP 0
+0.00 PREVENTIVE Plugged 4
6 43 DSI 1.49 H01+.07 ODSCC TSP AXIAL Plugged 4
6 43 SAI 0.58 H01+.18 ODSCC TSP AXIAL Plugged 4
6 43 SAI 0.7 H01+.25 ODSCC TSP AXIAL Plugged 4
6 43 SAI 0.37 H01+.26 ODSCC TSP AXIAL Plugged 4
6 43 DSI 0.42 H02+.00 ODSCC TSP AXIAL Plugged 4
6 46 DSI 0.52 H01-.12 ODSCC TSP AXIAL Plugged 4
6 46 SAI 0.5 HTS-.68 PWSCC HTS AXIAL Plugged 4
6 83 SCI 0.64 H07+27.48 PWSCC UBEND CIRC Plugged 4
6 83 SCI 1.35 H07+29.77 PWSCC UBEND CIRC Plugged 4
6 85 SCI 0.8 H07+28.78 PWSCC UBEND CIRC Plugged 4
6 86 SCI 1.25 H07+28.76 PWSCC UBEND CIRC Plugged 4
6 86 SCI 1.18 H07+29.53 PWSCC UBEND CIRC Plugged 4
6 86 SCI 1.47 H07+29.93 PWSCC UBEND CIRC Plugged 4
6 89 DSI 0.73 H02+.00 ODSCC TSP AXIAL Plugged 4
6 89 DSI 0.99 H03+.00 ODSCC TSP AXIAL Plugged 4
6 89 SCI 0.65 H07+29.87 PWSCC UBEND CIRC Plugged 4
6 89 SCI 1.04 H07+5.44 PWSCC UBEND CIRC Plugged 4
7 6
SAI 0.64 HTS-.89 ODSCC HTS AXIAL Plugged 4
7 15 SCI 1.15 H07+32.17 PWSCC UBEND CIRC Plugged 4
7 16 SCI 1
H07+10.10 PWSCC UBEND CIRC Plugged 4
7 16 SCI 1.31 H07+11.87 PWSCC UBEND CIRC Plugged 4
7 16 SCI 1.49 H07+12.29 PWSCC UBEND CIRC Plugged 4
7 16 SCI 1.24 H07+12.79 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.3 H07+14.83 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.6 H07+15.82 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.52 H07+18.60 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.35 H07+19.32 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.75 H07+19.69 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.44 H07+20.33 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.82 H07+33.02 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.61 H07+4.69 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.88 H07+5.49 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.35 H07+5.81 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.84 H07+5.90 PWSCC UBEND CIRC Plugged 4
7 16 SCI 1.09 H07+7.04 PWSCC UBEND CIRC Plugged 4
7 16 SCI 0.7 H07+7.46 PWSCC UBEND CIRC Plugged 52
V S Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
SG 4 Indications (Continued)
ROW COL Call I Volts LOCATION CHARACTERIZATION 7
16 SCI 0.57 H07+7.73 PWSCC UBEND CIRC 7
16 SCI 1.14 H07+9.33 PWSCC UBEND CIRC 7
16 SCI 1.34 H07+9.79 PWSCC UBEND CIRC 7
16 SCI 0.77 H07+9.84 PWSCC UBEND CIRC 7
51 TBP 0
+0.00 PREVENTIVE 7
51 DSI 1.41 H014.07 ODSCCTSPAXIAL 7
51 SAI 0.09 H01+.11 ODSCC TSP AXIAL 7
51 SAI 0.38 H01+.28 ODSCCTSPAXIAL 7
51 SAI 0.63 H01+.32 ODSCC TSP AXIAL 7
69 SCI 1.14 H07+21.71 PWSCC UBEND CIRC 7
69 SCI 1.44 H07421.95 PWSCC UBEND CIRC 8
8 12 12 12 13 13 17 17 17 20 20 20 20 27 27 27 27 27 41 45 45 53 DSI 0.75 H01+.05 53 SCI 0.14 HTS-.09 72 DSI 2.42 H01-.05 72 SAI 0.37 H01+.03 72 SAI 1.02 H01+.08 32 DSI 0.27 H02+.09 32 SAI 0.38 HTS-.08 20 DSI 0.71 H01+.17 20 DSI 3.55 H02+.19 20 SAI 3.18 H02+.34 33 DSI 1.19 H01+.14 33 SAI 0.37 H01+.15 33 DSI 0.39 H05-.02 33 SAI 0.13 HTS-.02 70 TBP 0
+0.00 70 DSI 1.74 H01+.00 70 SAI 0.14 H01+.10 70 SAI 0.23 H01+.19 70 SAI 0.71 H01+.20 69 41 1.11 C01-.35 59 SVI 0.11 C01-.28 59 42 1.27 C01-.31 ODSCC TSP AXIAL ODSCC HTS CIRC ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC HTS AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC HTS AXIAL PREVENTIVE ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL ODSCC TSP AXIAL C/L Thinning VOLUMETRIC C/L Thinning RESOLUTION Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged Plugged The following are anti vibration bar wear indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) with associated voltage.
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 4
29 67 21 0.32 AV1+.00 AVB WEAR 4
29 67 10 0.13 AV2+.00 AVB WEAR 4
29 67 31 0.59 AV3+.00 AVB WEAR 4
29 67 19 0.27 AV4+.00 AVB WEAR 4
32 41 14 0.19 AV2+.00 AVB WEAR RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
53
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 4
32 41 14 0.19 AV3+.00 AVB WEAR 4
35 55 21 0.34 AV1+.38 AVB WEAR 4
35 55 16 0.22 AV2-.05 AVB WEAR 4
38 44 22 0.36 AV3+.00 AVB WEAR 4
38 47 23 0.32 AV3+.07 AVB WEAR 4
38 47 21 0.26 AV4+.07 AVB WEAR 4
38 49 21 0.32 AV3+.00 AVB WEAR 4
38 49 11 0.12 AV4+.05 AVB WEAR 4
38 52 19 0.31 AV3+.14 AVB WEAR 4
38 52 21 0.35 AV4+.00 AVB WEAR 4
38 65 10 0.13 AV1+.05 AVB WEAR 4
38 65 16 0.22 AV2+.12 AVB WEAR RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
The following are cold leg thinning indications that remain in service because they are less than 40% through wall. The bobbin coil call is the percent through wall (maximum depth) with associated voltage.
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 4
7 94 32 0.55 C01-.19 CIL Thinning 4
9 77
<20 0.44 C04-.02 CAL Thinning 4
11 3
17 0.9 C01-.26 C/L Thinning 4
18 13
<20 0.46 C05+.07 CAL Thinning 4
18 88 9
0.4 C01-.09 CIL Thinning 4
19 7
<20 0.85 C01-.31 C/L Thinning 4
22 17
<20 0.37 C04-.10 CAL Thinning 4
22 17
<20 0.37 C05-.12 CAL Thinning 4
22 35
<20 0.4 C04-.12 CAL Thinning 4
23 14
<20 0.47 C05+.00 CAL Thinning 4
24 15
<20 0.34 C05+.02 CAL Thinning 4
25 46
<20 0.35 C05-.02 CAL Thinning 4
27 11
<20 0.79 C01-.28 CIL Thinning 4
29 48
<20 0.36 C06-.05 CIL Thinning 4
30 14
<20 0.67 C01-.26 CAL Thinning 4
30 15
<20 0.82 C01-.33 C/L Thinning 4
30 76 10 0.46 C06-.09 CAL Thinning 4
31 13 26 1.98 C01-.28 CAL Thinning 4
34 76 13 0.77 C02+.14 CAL Thinning 4
34 79
<20 0.47 C04-.26 CAL Thinning 4
37 19 14 0.55 C01-.17 C/L Thinning 4
39 22 20 0.67 C02-.24 CIL Thinning 4
39 31
<20 0.65 C02-.23 CAL Thinning 4
40 63 30 0.58 C02-.09 CAL Thinning 4
40 71 20 0.62 C02-.26 CIL Thinning 4
41 30 36 0.63 C02-.33 CAL Thinning RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
54
8 b1.
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 2.4 SG 4 Indications (Continued)
SG ROW COL Call I Volts LOCATION CHARACTERIZATION 4
41 34
<20 0.55 C02-.35 C/L Thinning 4
41 58
<20 0.55 C02-.19 C/L Thinning 4
41 62 24 2.21 C02-.28 C/L Thinning 4
41 65
<20 0.56 C02-.31 C/IL Thinning 4
41 67
<20 0.71 C01-.28 CIL Thinning 4
42 44 21 0.6 C02-.26 CIL Thinning 4
43 35 7
0.88 C02+.09 C/L Thinning 4
43 54 24 0.83 C02-.21 C/I Thinning 4
44 34 25 1.48 C02-.31 C/IL Thinning 4
44 38 36 0.7 C02-.28 CIL Thinning 4
44 39 6
0.53 C02-.19 C/L Thinning 4
44 47
<20 0.65 C02-.35 C/IL Thinning 4
45 36
<20 0.44 C02+.05 C/IL Thinning 4
45 41
<20 0.59 C02-.33 C/IL Thinning 4
45 42 11 0.58 C02-.33 C/I Thinning 4
45 45 36 1.56 C02-.31 C/L Thinning 4
45 54 17 0.51 C02+.00 C/I Thinning 4
45 55
<20 0.68 C01-.21 C/I Thinning 4
45 57 33 1.84 C02-.21 C/L Thinning 4
46 53 28 0.87 C02+.19 C/L Thinning RESOLUTION In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
In Service <40%
55
Sequoyah Nuclear Plant Unit 2 Cycle 12 RFO Inspection November 2003 Table 3 Nomenclature C01 - First cold leg tube support plate intersection C02 - Second cold leg tube support plate intersection C03 - Third cold leg tube support plate intersection C04 - Fourth cold leg tube support plate intersection C05 - Fifth cold leg tube support plate intersection C06 - Sixth cold leg tube support plate intersection C07 - Seventh cold tube support plate intersection CTE - Cold leg tube end. (Primary side cold leg face of tubesheet)
CTS - Cold leg top-of-tubesheet. (Secondary side cold leg face of tubesheet)
C/L - Cold Leg H01 - First hot leg tube support plate intersection H02 - Second hot leg tube support plate intersection H03 - Third hot leg tube support plate intersection H04 - Fourth hot leg tube support plate intersection H05 - Fifth hot leg tube support plate intersection H06 - Sixth hot leg tube support plate intersection H07 - Seventh hot leg tube support plate intersection HTE - Hot leg tube end. (Primary side hot leg face of tubesheet)
HTS - Hot leg top-of-tubesheet. (Secondary side cold leg face of tubesheet)
ODSCC - Outside Diameter Stress Corrosion Cracking PWSCC - Primary Water Stress Corrosion Cracking RFO - Refuel Outage RPC - Literally 'Rotating Pancake Coil' eddy current probe. This term is also used to describe eddy current probes in which the coil face contacts the tube wall while rotating and being pulled through the tube axially such that the examination path is helical.
SAI - Single Axial Indication SCI - Single Circumferential Indication SVI - Single Volumetric Indication SQN - Sequoyah Nuclear Plant Stab - Tube was stabilized TBP - BTo-Be-Plugged' Analyst determined tube should be plugged (Majority of these were analysis of Axial ODSCC at TSPs bobbin vs +Pt comparison)
TSP - Tube Support Plate TTS - Top of Tubesheet 56