ML042110451

From kanterella
Jump to navigation Jump to search

Plant Shutdown Required by Technical Specifications - Oconee Units 1, 2 and 3
ML042110451
Person / Time
Site: Oconee  
(DPR-038, DPR-055)
Issue date: 07/29/2004
From: Carroll R
NRC/RGN-II/DRP/RPB1
To:
References
MR-II-04-0009
Download: ML042110451 (1)


Text

Morning Report Date: JUL 29, 2004 PRIORITY ATTENTION REQUIRED MORNING REPORT - REGION II Licensee/Facility:

Notification:

2-2004-0009 07/29/2004 MR Number:

DUKE ENERGY CORP.

[1] B&W-L-LP, [2] B&W-L-LP, [3] B&W-L-LP Date:

Oconee Call from Licensee Seneca, South Carolina 050-00269 050-00270 050-00287 Dockets:

PLANT SHUTDOWN REQUIRED BY TECHNICAL SPECIFICATIONS - OCONEE UNITS 1,2, AND 3

Subject:

This is an update to the 10 CFR 50.72 notification dated July 28, 2004, regarding loss of the switchyard (SWYD) 125 VDC battery chargers, which resulted in the initiation of a Technical Specification (TS) 3.0.3 required shutdown of all three Oconee units. Preliminary investigation indicates that rain water intrusion caused a fault in an AC power transfer switch, causing the loss of both AC sources to the switchyard 125 VDC battery chargers. The licensee promptly initiated additional actions to prevent a loss of offsite power.

The TS 3.0.3 required Unit shutdowns were terminated at approximately 12:05 p.m. after: (1) the fault was isolated; (2) both AC battery charger sources were restored; and (3) SWYD battery cell voltages were returned to their minimum TS required limits. The licensee is currently performing a root cause investigation. Information indicates that the emergency power systems remained operable during the incident.

Regional Action: The resident inspectors responded to the site and continue to monitor the licensee's recovery actions and investigation of the event. Region II plans to conduct additional detailed inspection of the licensee's activities and corrective actions.

Discussion:

Contact:

Email:

Phone No:

Org:

CARROLL, ROBERT E REC1@nrc.gov (404) 562-4511 R2