ML041250599

From kanterella
Jump to navigation Jump to search
Annual Radiological Environmental Operating Report for 2003
ML041250599
Person / Time
Site: Vogtle  
Issue date: 12/31/2003
From:
Southern Nuclear Operating Co
To:
Office of Nuclear Reactor Regulation
References
Download: ML041250599 (85)


Text

I I -

4

.- Ilk4 81 el' as;

-lr Vogtle Electric Generating Plant Annual Radiological Environmental Operating Report for 2003

SOUTHERN NUCLEAR COMPANY VOGTLE ELECTRIC GENERATING PLANT-UNITS 1 AND 2 NRC DOCKET NOS. 50-424 AND 50-425 FACILITY OPERATING LICENSE NOS. NPF-68 AND NPF-81 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT FOR JANUARY 12003 TO DECEMBER 31,2003 Page 1 of 84

VOGTLE ELECTRIC GENERATING PLANT RADIOACTIVE EFFLUENT RELEASE REPORT - 2003 TABLE OF CONTENTS SECTION TITLE PAGE 1.0 Liquid Effluents 8

1.1 Regulatory Requirements 8

1.1.1 Concentration Limits 8

1.1.2 Dose Limits 8

1.2 Effluent Concentration Limit 8

1.3 Measurement and Approximations of Total 9

Radioactivity 1.3.1 Total Radioactivity Determination 9

1.3.2 Total Error Estimation 11 1.4 Liquid Effluent Release Data 12 1.5 Radiological Impact Due to Liquid Releases 12 1.6 Liquid Effluents - Batch Releases 12 1.7 Liquid Effluents -Abnormal Releases 12 2.0 Gaseous Effluents 34 2.1 Regulatory Requirements 34 2.1.1.

Dose Rate Limits 34 Page 2 of 84

SECTION

.TITLE PAGE SECTION TITLE PAGE 2.1.2 Air Doses Due to Noble Gases In Gaseous Releases 34 2.1.3 Doses to a Member of the Public 34 2.2 Measurements and Approximation of Total 35 Radioactivity 2.2.1 Sample Collection and Analysis 35 2.2.2 Total Quantities of Radioactivity, Dose Rates and 35 Cumulative Doses 2.2.2.1 Fission andActivation Gases 35 2.2.2.2 Radiolodines, Tritium, and Particulate Releases 36 2.2.2.3 Gross Alpha Release 36 2.2.3 Total Error Estimation 36 2.3 Gaseous Effluent Release Data 38 2.4 Radiological Impact Due to Gaseous Releases 39 2.5 Gaseous Effluents - Batch Releases 39 2.6 Gaseous Effluents - Abnormal Releases 40 3.0 Solid Waste 72 3.1 Regulatory Requirements 72 3.1.1 Solid Radioactive Waste System 72 3.1.2 Reporting Requirements 72 3.2 Solid Waste Data 72 Page 3 of 84

SECTION TITLE PAGE SECTION TITLE PAGE 4.0 Doses to Members of the Public Inside the Site 77 Boundary 4.1 Regulatory Requirements 77 4.2 Demonstration of Compliance 77 5.0 Total Dose from Uranium Fuel Cycle (40CFR190) 81 5.1 Regulatory Requirements 81 5.2 Demonstration of Compliance 81 6.0 Meteorological Data 81 7.0 Program Deviations 81 7.1 Inoperable Liquid or Gaseous Effluent Monitoring 81 Instrumentation 7.1.1 Regulatory Requirement 81 7.1.2 Description of Deviations 81 7.2 Tanks Exceeding Curie Content Limits 82 7.2.1 Regulatory Requirements 82 7.2.2 Description of Deviations 82 8.0 Changes to the Vogtle Electric Generating Plant 82 Offsite Dose Calculation Manual (ODCM) 8.1 Regulatory Requirement 82 8.2 Description of Changes 82 9.0 Major Changes to the Liquid, Gaseous, or Solid 83 Radwaste Treatment System 9.1 Regulatory Requirements 83 9.2 Description of Major Changes 84 Page 4 of 84

VOGTLE ELECTRIC GENERATING PLANT RADIOACTIVE EFFLUENT RELEASE REPORT -2003 TABLE LIST OF TABLES PAGE 1-lA Liquid Effluents - Summation of All Releases Unit 1 13 (Quarters 1, 2, 3, and 4) 1-lB Liquid Effluents - Summation of All Releases Unit 2 15 (Quarters 1, 2, 3, and 4) 1-4C Liquid Effluents - Summation of All Releases Site 17 (Quarters 1, 2, 3, and 4) 1-2A Liquid Effluents - Unit 1 (Quarters 1, 2, 3, and 4) 19 1-2B Liquid Effluents - Unit 2 (Quarters 1, 2, 3, and 4) 21 1-2C Liquid Effluents - Site (Quarters 1, 2, 3, and 4) 23 1-3A Doses to a Member of the Public Due to Liquid 25 Releases Unit 1 (Quarters 1, 2, 3, and 4) 1-3B Doses to a Member of the Public Due to Liquid 27 Releases Unit 2 (Quarters 1, 2, 3, and 4) 1-4 Minimum Detectable Concentration Liquid Sample 29 Analysis 1-SA Liquid Effluents - Batch Release Summary Unit 1 30 1-5B Liquid Effluents - Batch Release Summary Unit 2 31 1-6A Liquid Effluents - Abnormal Release Summary Unit 1 32 Page 5 of 84

TABLE LIST OF TABLES PAGE TABLE LIST OF TABLES PAGE 1-6B Liquid Effluents - Abnormal Release Summary Unit 2 33 2-1A Gaseous Effluents - Summation of All Releases -

41 Unit 1 (Quarters 1, 2, 3, and 4) 2-1B Gaseous Effluents - Summation of All Releases -

43 Unit 2 (Quarters 1, 2, 3, and 4) 2-1C Gaseous Effluents - Summation of All Releases -

45 Site (Quarters 1, 2, 3, and 4) 2-2A Gaseous Effluents - Mixed Mode Releases Unit 1 47 (Quarters 1, 2.,3, and 4) 2-2B Gaseous Effluents - Mixed Mode Releases Unit 2 49 (Quarters 1, 2, 3, and 4) 2-2C Gaseous Effluents - Mixed Mode Releases Site 51 (Quarters 1, 2, 3, and 4) 2-3A Gaseous Effluents - Ground Level Releases Unit 1 53 (Quarters 1, 2,3, and 4) 2-3B Gaseous Effluents - Ground Level Releases Unit 2 55 (Quarters 1, 2, 3, and 4) 2-3C Gaseous Effluents - Ground Level Releases Site 57 (Quarters 1, 2, 3, and 4) 2-4A Air Doses Due to Noble Gases In Gaseous Releases 59 Unit 1 (Quarters 1, 2, 3, and 4) 2-4B Air Doses Due to Noble Gases In Gaseous Releases 61 Unit 2 (Quarters 1, 2, 3, and 4) 2-5A Doses to a Member of the Public Due to Radiolodines, 63 Tritium, and Particulates in Gaseous Releases Unit 1 (Quarters 1,2, 3, and 4)

Page 6 of 84

TABLE LIST OF TABLES PAGE TABLE LIST OF TABLES PAGE 2-5B Doses to a Member of the Public Due to Radiolodines, 65 Tritium, and Particulates in Gaseous Releases Unit 2 (Quarters 1, 2, 3, and 4) 2-6 Minimum Detectable Concentration - Gaseous Sample-67 Analysis 2-7A Gaseous Effluents - Batch Release Summary Unit 1 68 2-7B Gaseous Effluents - Batch Release Summary Unit 2 68 2-8A Gaseous Effluents - Abnormal Release Summary 70 Unit 1 2-8B Gaseous Effluents - Abnormal Release Summary 71 Unit 2 3-1 Solid Waste and Irradiated Fuel Shipments 73 4-1 Doses to a Member of the Public Due to Activities 79 Inside the Site Boundary Page 7 of 84

1.0 Liquid Effluents 1.1 Regulatory Requirements 1.1.1 Concentration Limits In accordance with Technical Specification 5.5.4.b, the concentration of radioactive material released in liquid effluents to UNRESTRICTED AREAS shall be limited at all times to ten times the concentrations specified in 10 CFR 20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 1 E-04 pCVml total activity.

1.1.2 Dose Limits The dose or dose commitment to a MEMBER OF THE PUBLIC from radioactive materials in liquid effluents released, from each unit, to UNRESTRICTED AREAS shall be limited as follows:

a.

During any calendar quarter to less than or equal to 1.5 mrems to the whole body and to less than or equal to 5 mrems to any organ, and

b.

During any calendar year to less than or equal to 3 mrems to the whole body and to less than or equal to 10 mrems to any organ.

1.2 Effluent Concentration Limit (ECL)

ECL values used for determining the allowable liquid radwaste release rates and concentrations for the principal gamma emitters, 1-131, tritium, Sr-89, Sr-90 and Fe-55 are taken from 10 CFR Part 20, Appendix B, Table 2, Column 2. A tolerance factor of up to 10 is utilized to allow flexibility in establishing practical monitor set points which can accommodate effluent releases at concentrations higher than the ECL values stated in 10 CFR 20, Appendix B, Table 2, Column 2.

For dissolved or entrained noble gases in liquid radwaste, the ECL is 1 E-04 pCVml total activity.

For gross alpha in liquid radwaste, the ECL is 2 E-09 pjCVml.

For all the above radionuclides or categories of radioactivity, the overall ECL fraction is determined in accordance with 10 CFR Part 20, Appendix B. The method utilizing the ECL fraction to determine release rates and liquid radwaste effluent radiation monitor set points is described in Subsection 1.3 of this report.

Page 8 of 84

1.3 Measurements and Approximations of Total Radioactivity 1.3.1 Total Radioactivity Determination Prior to the release of any tank containing liquid radwaste, and following the required recirculation, samples are collected and analyzed in accordance with the Offsite Dose Calculation Manual (ODCM) Table 2-3 "Radioactive Liquid Waste Sampling and Analysis Program". A sample from each tank which is planned for release is analyzed for principal gamma emitters, 1-131, and dissolved and entrained noble gases by gamma spectroscopy. Monthly and quarterly composites are prepared for analysis by extracting aliquots from each sample taken from the tanks, which are released. Liquid radwaste sample analyses are performed as follows:

MEASUREMENT

1. Gamma Isotopic
2. Dissolved or entrained noble gases
3. Tritium FREQUENCY METHOD Each Batch Each Batch Monthly Composite Gamma Spectroscopy with computerized data reduction.

Gamma Spectroscopy with computerized data reduction Distillation and liquid scintillation counting

4. Gross Alpha
5. Sr-89 & Sr-90
6. Fe-55 Monthly Composite Quarterly Composite Quarterly Composite Gas flow proportional counting Chemical separation and gas flow proportional or scintillation counting Chemical separation and liquid scintillation counting Page 9 of 84

1.3.1 Total Radioactivity Determination cont'd Gamma isotopic measurements are performed using germanium detectors with a resolution of 2.1 keV or lower. A peak search of the resulting gamma ray spectrum is performed by the computer system. Energy and net count data for all significant peaks are determined, and a quantitative reduction or MDC calculation is performed. This ensures that the MDC's are met for the nuclides specified in ODCM Chapter 10 (i.e., Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-1 34, Cs-137, Ce-141 and Ce-144). The quantitative calculations, corrections for counting time, decay time, sample volume, sample geometry, detector efficiency, baseline counts, branching ratio and MDC calculations, are made based on the counts at the location in the spectrum where the peak for that radionuclide would be located, if present.

Tritium, Gross Alpha, Sr-89, Sr-90 and Fe-55 are, in some cases, analyzed offsite.

ECL fraction is determined using radionuclide concentrations of a tank planned for release, the most current results available for tritium, gross alpha, Sr-89, Sr-90 and Fe-55 and the corresponding ECL values.

This ECL fraction is used, with appropriate safety factors, tolerance factors, and the minimum assured dilution stream flow to calculate maximum permissible release rates and a liquid effluent monitor setpoint. The monitor setpoint is calculated to assure that the limits of the Offsite Dose Calculation Manual (ODCM) are not exceeded.

A monitor reading in excess of the calculated setpoint results in an automatic termination of the liquid radwaste discharge. Liquid effluent discharge is also automatically terminated if the dilution stream flow rate falls below the minimum assured dilution flow rate used in the setpoint calculations and established as a setpoint on the dilution stream flow monitor.

Radionuclide concentrations, safety factors, dilution stream flow rate, and liquid effluent radiation monitor calibrations are entered into the computer and a pre-release printout is generated. If the release is not permissible, appropriate warnings will be displayed on the computer screen. If the release is permissible, it is approved by the Chemistry Department and sent to the Operations Department for approval and release. When the release is completed, the necessary data from the release (i.e., release volume, etc.) are provided by the Operations Department to the Chemistry Department. These data are input to the computer and a post-release printout is generated. The post release printout contains the actual release rates, release concentrations and quantities, actual dilution flow, and calculated doses to an individual.

Typically achieved liquid effluent sample analyses minimum detectable concentrations are reported in Table 1-4.

Page 10 of 84

1.3.2 Total Error Estimation The total or maximum error associated with the effluent measurement includes the cumulative errors resulting from the total operation of sampling and measurement. Because it may be very difficult to assign error terms for each parameter affecting the final measurement, detailed statistical evaluation of error is not suggested. The objective should be to obtain an overall estimate of the error associated with measurements of radioactive materials released in liquid effluents.

a.

Fission and activation total release was calculated from sample analysis results and release point flow rates.

Sampling and statistical error 10%

Counting Equipment Calibration 10%

Tank Volumes and System Flow Rates 20%

TOTAL ERROR 40%

b.

Total Tritium release was calculated from sample analysis results and release point volumes.

Sampling and statistical errors 10%

Counting equipment calibration 10%

Tank volumes and system flow rate 20%

TOTAL ERROR 40%

c.

Dissolved and entrained gases were calculated from sample analysis results and release point volumes.

Sampling and statistical error 20%

Counting equipment calibration 10%

Tank volumes and system flow rate 20%

TOTAL ERROR 50%

d.

Gross alpha radioactivity was calculated from sample analysis results and release point volumes.

Sampling and statistical error 10%

Counting Equipment calibration 10%

Tank volumes and system flowrates 20%

TOTAL ERROR 40%

Page 11 of 84

1.3.2 Total Error Estimation cont'd

e.

Volume of waste prior to dilution was calculated from level indicators on the tanks and pump discharge flow rates and times.

Level Indicator error 10%

Operator Interpretation of gauge 10%

TOTAL ERROR 20%

f.

Volume of dilution water used was calculated from flow totalizers and pump discharge flow rates and times.

Flow totalizer error 10%

Operator interpretation of gauge 10%

TOTAL ERROR 20%

g.

Gross alpha, Sr-89, Sr-90, Fe-55 and H-3 radioactivity has an additional error associated with sample. compositing.

Compositing sample error 5%

1.4 Liquid Effluent Release Data Regulatory Guide 1.21 Tables 2A and 2B are found in this report as Tables 1-1A, 1-1 B, 1-1C, 1-2A, 1-2B and 1-2C. Data is presented on a quarterly basis as required by Regulatory Guide 1.21 for all four quarters.

1.5 Radiological Impact Due to Liquid Releases Doses to an individual due to radioactivity in liquid effluent were calculated in accordance with the Offsite Dose Calculation Manual.

Results are presented in Table 1-3A for Unit 1 and 1-33 for Unit 2, for all four quarters.

1.6 Liquid Effluents - Batch Releases Batch release information for liquid effluents is presented in Table 1-5A for Unit 1 and Table 1-5B for Unit 2.

1.7 Liquid Effluents - Abnormal Releases There were no abnormal releases for this reporting period.

Page 12 of 84

TABLE 1-lA Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents -

Summation of All Releases Unit: 1 Starting : 1-Jan-2003 Ending : 30-Jun-2003 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA)

CURIES 4.49E-03 1.87E-02 40

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 3.35E-08 6.71E-08

3.

PERCENT OF APPLICABLE LIMIT B. TRITIUM

1. TOTAL RELEASE CURIES 7.85E+01 3.29E+02 40
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD lICi/ML 5.86E-04 1.18E-03

3. PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CURIES 1.14E-05 6.10E-04 50
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 8.48E-11 2.19E-09

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1.

TOTAL RELEASE CURIES O.00E+00 0.OOE+00 45 E. WASTE VOL RELEASED(PRE-DILUTION)

LITERS 4.21E+05 7.05E+05 20 F. VOLUME OF DILUTION WATER USED LITERS 1.34E+08 2.78E+08 20 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

Page 13 of 84

TABLE 1-lA Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents -

Summation of All Releases Unit: 1 Starting : 1-Jul-2003 Ending : 31-Dec-2003 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE (NOT INCLUDING

TRITIUM, GASES, ALPHA)

CURIES 1.84E-02 8.67E-03 40

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD viCi/ML 4.75E-08 2.55E-08

3. PERCENT OF APPLICABLE LIMIT B. TRITIUM
1. TOTAL RELEASE CURIES 4.62E+02 1.70E+02 40
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD liCi/ML 1.19E-03 5.OOE-04

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1.

TOTAL RELEASE CURIES 5.71E-05 3.18E-04 50

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 1.47E-10 9.33E-10

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1.

TOTAL RELEASE CURIES O.OOE+00 0.OOE+00 45 E. WASTE VOL RELEASED(PRE-DILUTION)

LITERS 9.83E+05 9.54E+05 20 F. VOLUME OF DILUTION WATER USED LITERS 3.87E+08 3.40E+08 20 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

Page 14 of 84

TABLE 1-lB Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents -

Summation of All Releases Unit: 2 Starting : l-Jan-2003 Ending : 30-Jun-2003 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA)

CURIES 1.76E-03 3.61E-03 40

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 2.22E-08 3.94E-08

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1. TOTAL RELEASE CURIES 9.05E+01 1.11E+02 40
2. AVERAGE DILUTED CONCENTRATION DURING PERIOD

'pCi/ML 1.14E-03 1.21E-03

3. PERCENT OF APPLICABLE LIMIT C. DISSOLVED AND ENTRAINED GASES
1. TOTAL RELEASE CURIES 2.13E-05 3.73E-04 50
2. AVERAGE DILUTED CONCENTRATION DURING PERIOD 1'Ci/ML 2.68E-10 4.06E-09
3. PERCENT OF APPLICABLE LIMIT D. GROSS ALPHA RADIOACTIVITY
1. TOTAL RELEASE CURIES O.00E+00 0.OOE+00 45 E. WASTE VOL RELEASED(PRE-DILUTION)

LITERS 2.41E+05 1.94E+05 20 F. VOLUME OF DILUTION WATER USED LITERS 7.93E+07 9.16E+07 20 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

Page 15 of 84

TABLE 1-lB Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents -

Summation of All Releases Unit: 2 Starting : 1-Jul-2003 Ending : 31-Dec-2003 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING
TRITIUM, GASES, ALPHA)

CURIES 4.13E-02 2.30E-03 40

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 7.40E-08 3.35E-08

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1.

TOTAL RELEASE CURIES 6.74E+02 1.33E+01 40

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 1.21E-03 1.94E-04

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1.

TOTAL RELEASE CURIES 7.99E-04 O.OOE+00 50

2. AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 1.43E-09 0.OOE+00
3. PERCENT OF APPLICABLE LIMIT D. GROSS ALPHA RADIOACTIVITY
1. TOTAL RELEASE CURIES 0.OOE+00 O.OOE+00 45 E. WASTE VOL RELEASED(PRE-DILUTION)

LITERS 1.39E+06 2.65E+05 20 F. VOLUME OF DILUTION WATER USED LITERS 5.57E+08 6.84E+07 20 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

Page 16 of 84

TABLE 1-iC Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents - Summation of All Releases Unit: Site Starting : 1-Jan-2003 Ending : 30-Jun-2003 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA)

CURIES 6.25E-03 2.23E-02 40

2. AVERAGE DILUTED CONCENTRATION DURING PERIOD

)ICi/ML 2.93E-08 6.02E-08

3.

PERCENT OF APPLICABLE LIMIT B. TRITIUM

1.

TOTAL RELEASE CURIES 1.69E+02 4.40E+02 40

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 7.92E-04 1.19E-03

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1.

TOTAL RELEASE CURIES 3.26E-05 9.83E-04 50

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD i1Ci/ML 1.53E-10 2.65E-09

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1. TOTAL RELEASE CURIES 0.00E+00 0.00E+00 45 E.

WASTE VOL RELEASED(PRE-DILUTION)

LITERS 6.62E+05 8.99E+05 20 F. VOLUME OF DILUTION WATER USED LITERS 2.13E+08 3.70E+08 20 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

Page 17 of 84

TABLE 1-iC Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents -

Summation of All Releases Unit: Site Starting : 1-Jul-2003 Ending : 31-Dec-2003 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE (NOT INCLUDING

TRITIUM, GASES, ALPHA)

CURIES 5.97E-02 1.10E-02 40

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 6.31E-08 2.68E-08

3. PERCENT OF APPLICABLE LIMIT B. TRITIUM
1. TOTAL RELEASE CURIES 1.14E+03 1.83E+02 40
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 1.20E-03 4.48E-04

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1.

TOTAL RELEASE CURIES 8.56E-04 3.18E-04 50

2. AVERAGE DILUTED CONCENTRATION DURING PERIOD pCi/ML 9.05E-10 7.76E-10
3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1.

TOTAL RELEASE CURIES 0.OOE+00 O.OOE+00 45 E. WASTE VOL RELEASED(PRE-DILUTION)

LITERS 2.37E+06 1.22E+06 20 F. VOLUME OF DILUTION WATER USED LITERS 9.43E+08 4.08E+08 20 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

Page 18 of 84

TABLE 1-2A*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents Unit: 1 Starting : 1-Jan-2003 Ending : 30-Jun-2003 l CONTINUOUS MODE BATCH MODE NUCLIDE I

UNIT lQUARTER 1 I QUARTER 2 l QUARTER 1 l QUARTER 2 l H-3 I

CURIES I O.OOE+00 I O.OOE+00 I 7.85E+01 I 3.29E+02 I

FISSION & ACTIVATION PRODUCTS AG-llOM CURIES 0.OOE+00 0.00E+00 9.10E-06 0.OOE+00 BE-7 CURIES 0.OOE+00 0.OOE+00 O.OOE+00 8.27E-06 CO-57 CURIES 0.OOE+00 0.OOE+00 0.OOE+00 6.21E-06 CO-58 CURIES 0.00E+00 0.OOE+00 2.41E-04 1.27E-03 CO-60 CURIES 0.OOE+00 0.OOE+00 4.87E-04 2.39E-03 CR-51 CURIES 0.OOE+00 0.OOE+00 0.OOE+00 4.88E-05 CS-134 CURIES 0.OOE+00 0.OOE+00 4.43E-05 8.66E-05 CS-137 CURIES 0.OOE+00 0.OOE+00 1.83E-04 4.02E-04 FE-55 CURIES 0.OOE+00 0.OOE+00 1.93E-03 1.35E-02 MN-54 CURIES O.OOE+00 0.OOE+00 4.53E-05 3.47E-04 NB-95 CURIES O.00E+00 O.OOE+00 9.10E-06 1.77E-04 NB-97 CURIES 0.OOE+00 0.OOE+00 1.20E-05 3.19E-05 SB-125 CURIES O.OOE+00 O.OOE+00 7.43E-04 3.93E-04 SR-89 CURIES O.OOE+00 0.OOE+00 2.73E-12 1.67E-05 SR-92 CURIES O.OOE+00 0.OOE+00 8.65E-07 O.OOE+00 TE-125M CURIES O.OOE+00 0.OOE+00 7.83E-04 0.OOE+00 ZR-95 CURIES O.OOE+00 0.OOE+00 0.OOE+00 5.53E-05 TOTALS I

CURIES I O.OOE+00 I 0.OOE+00 I 4.49E-03 l 1.87E-02 DISSOLVED AND ENTRAINED GASES XE-133 I

CURIES I 0.OOE+00 I 0.OOE+00 I 1.14E-05 I 6.10E-04 TOTALS l CURIES I O.OOE+00 I 0.00E+00Ol 1.14E-05 I 6.10E-04 I Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typical minimum detectable concentrations.

Page 19 of84

TABLE 1-2A*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents Unit: 1 Starting : 1-Jul-2003 Ending : 31-Dec-2003 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT lQUARTER 3 IQUARTER 4 IQUARTER 3 IQUARTER 4 H-3 I

CURIES I 0.OOE+00 0.OOE+00 I 4.62E+02 I 1.70E+02 l

FISSION & ACTIVATION PRODUCTS CO-57 CO-58 CO-60 CR-51 CS-134 CS-137 FE-55 FE-59 I-133 MN-54 NA-24 NB-95 NB-97 SB-124 c

o-CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES r'TIRTF!

0. OOE+00
0. OOE+00
0. OOE+00 O.OOE+00 0.OOE+00
0. OOE+00
0. OOE+00 0.OOE+O0 0.OOE+00 O. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 n nnrfLnnlf
0. OOE+00 0.OOE+00 0.OOE+00 O. OOE+00 O. OOE+00 O. OOE+00

.0.

OOE+00 O. OOE+00

0. OOE+O0 O. OOE+00
0. OOE+00 O. OOE+00
0. OOE+00
0. OOE+00 n nnp.Lnn 8.56E-06 2.66E-03 3.75E-03 0.OOE+00 1.58E-04 6.42E-04 5.39E-03 4.16E-06 0.OOE+00 5.89E-04 0.OOE+00 4.54E-05 0.OOE+00 1.65E-05

,, 1 av-na 2.21E-06 9.12E-04 1.62E-03 3.04E-04 1.99E-05 6.14E-05 3.43E-03 2.04E-05

-1.81E-06 1.16E-04 9.49E-06 5.99E-05 1.48E-05 0.OOE+00 7 Aw-nC SR-89 CURIES O.OOE+00 0.OOE+00 3.44E-05 2.64E-06 TE-125M CURIES 0.OOE+00 O.OOE+00 2.92E-03 1.99E-03 ZR-95 CURIES 0.OOE+00 0.OOE+00 2.63E-05 3.60E-05 TOTALS I

CURIES I O.OOE+00 I 0.OOE+00 I 1.84E-02 I 8.67E-03 DISSOLVED AND ENTRAINED GASES XE-133 CURIES I 0.OOE+00 I 0.OOE+00 5.71E-05 3.16E-04 XE-135 I

CURIES 0.OOE+00 0.OOE+00 IO.OOE+00 1.62E-06 TOTALS I CURIES I O.OOE+00 l 0.00E+00 I 5.71E-05 I 3.18E-04 I Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typical minimum detectable concentrations.

Page 20 of 84

9 TABLE 1-2B*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents Unit: 2 Starting : l-Jan-2003 Ending i 30-Jun-2003 l CONTINUOUS MODE BATCH MODE NUCLIDE I

UNIT lQUARTER 1 IQUARTER 2 IQUARTER 1 IQUARTER 2 l H-3 I

CURIES I O.OOE+00 I 0.OOE+00 I 9.05E+01 I 1.11E+02 I FISSION & ACTIVATION PRODUCTS AG-llOM CO-58 CO-60 CS-134 CS-137 FE-55 FE-59 MN-54 NB-95 NB-97 SB-124 SB-125 SR-89 SR-92 TE-125M ZR-95 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES 0.OOE+00

0. OOE+00 O. OOE+00 0.OOE+00
0. OOE+00 0.OOE+00 0.OOE+00 O.OOE+00

.0.OOE+00

0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00 0.OOE+00 O. OOE+O0 O. OOE+00 0.OOE+00
0. OOE+00 0.OOE+00 0.OOE+00
0. OOE+O0
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00 0.OOE+00
0. OOE+00 0.OOE+00 7.86E-06 1.60E-04 2.65E-04 9.06E-06 4.23E-05 4.75E-04 0.00E+00 1.34E-05 0.OOE+00 9.51E-06 0.OOE+00 1.30E-04 2.58E-06 3.82E-06 6.44E-04 0.OOE+00 0.OOE+00 3.95E-04 1.20E-03 2.25E-05 5.81E-05 1.66E-03 7.05E-06 1.09E-04 6.43E-05 9.75E-06 1.25E-05 5.92E-05 6.46E-06 0.OOE+00 O.OOE+00 1.57E-05 TOTALS I

CURIES I 0.OOE+00 I 0.OOE+00 I 1.76E-03 I 3.61E-03 DISSOLVED AND ENTRAINED GASES XE-133 CURIES I O.OOE+00 I O.OOE+00 l O.OOE+00 3.73E-04 XE-133M I

CURIES 0.OOE+00 0.OOE+00 I 2.13E-05 I 0.OOE+00 l

TOTALS I

CURIES I O.OOE+00 I O.OOE+00 I 2.13E-05 I 3.73E-04 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typical minimum detectable concentrations.

Page 21 of 84

TABLE 1-2B*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents Unit: 2 Starting : 1-Jul-2003 Ending : 31-Dec-2003 I CONTINUOUS MODE l

BATCH MODE I

NUCLIDE I

UNIT IQUARTER 3 IQUARTER 4 IQUARTER 3 lQUARTER 4 l H-3 I CURIES I 0.OOE+00 I 0.OOE+00 I 6.74E+02 I 1.33E+01 FISSION & ACTIVATION PRODUCTS CO-57 CO-58 CO-60 CR-51 CS-134 CS-137 FE-55 FE-59 MN-54 NA-24 NB-95 NB-97 SB-124 SB-125 SR-89 TE-125M TE-132 ZR-95 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES

0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+O0
0. OOE+00 0.OOE+00 0.OOE+O0 O.OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00 O.OOE+00
0. OOE+00
0. OOE+O0
0. OOE+00 O. OOE+00 0.OOE+00

.OE+OOg 0.OOE+0 0.OOE+00

0. OOE+00 0.OOE+O0 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 O.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00
0. OOE+00 O.OOE+00 0.OOE+00 3.13E-06 5.47E-03 5.19E-03
0. OOE+00 2.63E-05 1.48E-04 2.66E-02 0.OOE+00 8.94E-04 O.OOE+00 5.73E-05 0.OOE+00 9.16E-06 2.11E-03 2.22E-06 7.16E-04 3.88E-06 2.68E-05 0.OOE+00 1.63E-04 9.57E-04 5.90E-05 3.95E-06 3.34E-05 9.52E-04 1.65E-05 4.34E-05 1.73E-05 1.60E-05 1.23E-06 0.OOE+00 2.94E-05 2.33E-06 0.OOE+00 0.OOE+00 6.OOE-06 TOTALS I CURIES I 0.00E+00 I 0.OOE+00 I 4.13E-02 I 2.30E-03 DISSOLVED AND ENTRAINED GASES XE-133 I CURIES I 0.OOE+00 I 0.OOE+00 I 7.99E-04 I 0.OOE+00 TOTALS I

CURIES I O.OOE+00 I O.OOE+00 I 7.99E-04 I O.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typical minimum detectable concentrations.

Page 22 of 84

TABLE 1-2C*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents Unit: Site Starting : 1-Jan-2003 Ending : 30-Jun-2003 I CONTINUOUS MODE I

BATCH MODE I

NUCLIDE I

UNIT lQUARTER 1 lQUARTER 2 IQUARTER 1 IQUARTER 2 l H-3 I

CURIES I 0.OOE+00 I 0.OOE+00 I 1.69E+02 I 4.40E+02 l

FISSION & ACTIVATION PRODUCTS AG-llOM BE-7 CO-57 CO-58 CO-60 CR-51 CS-134 CS-137 FE-55 FE-59 MN-54 NB-95 NB-97 SB-124 SB-125 SR-89 SR-92 TE-125M ZR-95 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES O. OOE+00 0O.OOE+00 O.OOE+00

0. OOE+00 O. OOE+00 O. OOE+00
0. OOE+O0
0. OOE+00 O.OOE+00

.O.OOE+00

0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+O0 O. OOE+00 O. OOE+00 0.OOE+00
0. OOE+00 O.OOE+00
0. OOE+00 0.OOE+00
0. OOE+O0 O.OOE+00 0.OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+O0
0. OOE+O0
0. OOE+00 0.OOE+00 1.70E-05 0.OOE+00 0.OOE+00 4.01E-04 7.52E-04 0.OOE+00 5.34E-05 2.26E-04 2.40E-03 0.OOE+00 5.87E-05 9.10E-06 2.15E-05 0.00E+00 8.73E-04 2.58E-06 4.69E-06 1.43E-03 0.OOE+00 0.OOE+00 8.27E-06 6.21E-06 1.66E-03 3.59E-03 4.88E-05 1.09E-04 4.60E-04 1.51E-02 7.05E-06 4.56E-04 2.41E-04 4.17E-05 1.25E-05 4.52E-04 2.32E-05 0.OOE+00
0. OOE+00 7.10E-05 TOTALS I

CURIES I 0.OOE+00 I O.OOE+00 I 6.25E-03 I 2.23E-02 l DISSOLVED AND ENTRAINED GASES XE-133 CURIES I 0.OOE+00 I 0.OOE+00 l 1.14E-05 I 9.83E-04 l XE-133M CURIES O.OOE+00 l O.00E+00 I 2.13E-05 l O.OOE+O0 l TOTALS I

CURIES I O.OOE+00 I 0.OOE+00 I 3.26E-05 I 9.83E-04 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typical minimum detectable concentrations.

Page 23 of 84

TABLE 1-2C*

Vogtle Electric Generating Plant RALIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents Unit: Site Starting : 1-Ju1-2003 Ending 31-Dec-2003 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT lQUARTER 3 lQUARTER 4 IQUARTER 3 IQUARTER 4 H-3 I

CURIES I O.OOE+00 I 0.OOE+00 I 1.14E+03 I 1.83E+02 l FISSION & ACTIVATION PRODUCTS CO-57 CO-58 CO-60 CR-51 CS-134 CS-137 FE-55 FE-59 I-133 MN-54 NA-24.

NB-95 NB-97 SB-124 SB-125 SR-89 TE-125M TE-132 ZR-95 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00

0. OOE+00 1.17E-05 8.14E-03 8.94E-03 0.OOE+00 1.85E-04 7.90E-04 3.20E-02 4.16E-06 0.00E+00 1.48E-03 0.OOE+00 1.03E-04 0.OOE+00 2.56E-05 4.3OE-03 3.66E-05 3.63E-03 3.88E-06 5.30E-05 2.21E-06 1.08E-03 2.57E-03 3.63E-04 2.39E-05 9.47E-05 4.38E-03 3.70E-05 1.81E-06 1.60E-04 2.68E-05 7.59E-05 1.60E-05 0.OOE+00 1.04E-04 4.98E-06 1.99E-03 0.OOE+00 4.2OE-05 TOTALS I

CURIES I 0.OOE+00 I 0.OOE+00 I 5.97E-02 I 1.10E-02 l DISSOLVED AND ENTRAINED GASES XE-133 CURIES O.00E+00 I O.OOE+00 8.56E-04 3.16E-04 XE-135 CURIES 0.OOE+00 0.OOE+00 0.OOE+00 1.62E-06 TOTALS I

CURIES I O.OOE+00 I O.OOE+00 I 8.56E-04 I 3.18E-04 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typical minimum detectable concentrations.

Page 24 of 84

TABLE 1-3A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 1 Starting:

01-Jan-2003 Ending: 30-Jun-2003 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone 5.0 mrem 1.20E-03 2.40E-02 2.65E-03 5.30E-02 Liver 5.0 mrem 4.45E-03 8.91E-02 1.30E-02 2.60E-01 TBody 1.5 mrem 3.91E-03 2.60E-01 1.18E-02 7.84E-01 Thyroid 5.0 mrem 2.70E-03 5.39E-02 9.14E-03 1.83E-01 Kidney 5.0 mrem 3.37E-03 6.73E-02 1.04E-02 2.08E-01 Lung 5.0 mrem 4.10E-03 8.20E-02 1.03E-02 2.06E-01 GILLI 5.0 mrem 2.99E-03 5.97E-02 9.75E-03 1.95E-01 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 10.0 mrem 3.85E-03 3.85E-02 Liver 10.0 mrem 1.75E-02 1.75E-01 TBody 3.0 mrem 1.57E-02 5.22E-01 Thyroid 10.0 mrem 1.18E-02 1.18E-01 Kidney 10.0 mrem 1.38E-02 1.38E-01 Lung 10.0 mrem 1.44E-02 1.44E-01 GILLI 10.0 mrem 1.27E-02 1.27E-01 Page 25 of 84

TABLE 1-3A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 1 Starting: 01-Jul-2003 Ending: 31-Dec-2003 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone Liver TBody Thyroid Kidney Lung GILLI 5.0 5.0 1.5 5.0 5.0 5.0 5.0 mrem mrem mrem mrem mrem mrem mrem 5.99E-03 2.15E-02 1.88E-02 1.27E-02 1.62E-02 1.82E-02 1.46E-02 1.20E-01 4.31E-01 1.25E+00 2.54E-01 3.25E-01 3.64E-01 2.92E-01 5.89E-03 6.52E-03 5.82E-03 4.83E-03 5.55E-03 5.45E-03 6.57E-03 1.18E-01 1.30E-01 3.88E-01 9.66E-02 l.11E-01 1.09E-01 1.31E-01 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone Liver TBody Thyroid Kidney Lung GILLI 10.0 10.0 3.0 10.0 10.0 10.0 10.0 mrem mirem mrem mrem mrem mrem mrem 1.57E-02 4.55E-02 4.03E-02 2.93E-02 3.55E-02 3.81E-02 3.39E-02 1.57E-01 4.55E-01 1.34E+00 2.93E-01 3.55E-01 3.81E-01 3.39E-01 Page 26 of 84

Vogtle RADIOACTIVE DOSES TO A MEMBER Starting: 01-Jan-2003 TABLE 1-3B Electric Generating Plant EFFLUENT RELEASE REPORT -

2003 OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2 Ending: 30-Jun-2003 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone Liver TBody Thyroid Kidney Lung GILLI 5.0 5.0 1.5 5.0 5.0 5.0 5.0 mnrem mrem mrem mrem mrem mrem mrem 2.94E-04 3.38E-03.

3.26E-03 2.98E-03 3.20E-03 3.23E-03 3.13E-03 5.87E-03 6.77E-02 2.17E-01 5.97E-02 6.41E-02 6.45E-02 6.25E-02 5.60E-04 3.78E-03 3.53E-03 2.89E-03 3.18E-03 3.14E-03 3.14E-03 1.12E-02 7.57E-02 2.35E-01 5.79E-02 6.37E-02 6.28E-02 6.28E-02 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 10.0 mrem 8.54E-04 8.54E-03 Liver 10.0 mrem 7.17E-03 7.17E-02 TBody 3.0 mrem 6.78E-03 2.26E-01 Thyroid 10.0 mrem 5.88E-03 5.88E-02 Kidney 10.0 mrem 6.39E-03 6.39E-02 Lung 10.0 mrem 6.37E-03 6.37E-02 GILLI 10.0 mrem 6.26E-03 6.26E-02 Page 27 of 84

TABLE 1-3B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2 Starting: 01-Jul-2003 Ending: 31-Dec-2003 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone 5.0 mrem 1.92E-03 3.84E-02 3.02E-04 6.04E-03 Liver 5.0 mrem 2.15E-02 4.30E-01 7.83E-04 1.57E-02 TBody 1.5 mrem 2.06E-02 1.37E+00 6.48E-04 4.32E-02 Thyroid 5.0 mrem 1.90E-02 3.79E-01 3.54E-04 7.08E-03 Kidney 5.0 mrem 1.98E-02 3.97E-01 4.93E-04 9.86E-03 Lung 5.0 mrem 2.43E-02 4.86E-01 4.79E-04 9.57E-03 GILLI 5.0 mrem 2.08E-02 4.17E-01 5.12E-04 1.02E-02 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 10.0 mrem 3.08E-03 3.08E-02 Liver 10.0 mrem 2.95E-02 2.95E-01 TBody 3.0 mrem 2.81E-02 9.35E-01 Thyroid 10.0 mrem 2.52E-02 2.52E-01 Kidney 10.0 mrem 2.67E-02 2.67E-01 Lung 10.0 mrem 3.11E-02 3.11E-01 GILLI 10.0 mrem 2.76E-02 2.76E-01 Page 28 of 84

TABLE 1-4 VOGTLE ELECTRIC GENERATING PLANT RADIOACTIVE EFFLUENT RELEASE REPORT - 2003 MINIMUM DETECTABLE CONCENTRATIONS - LIQUID SAMPLE ANALYSES JANUARY 2003 - DECEMBER 2003 The values in this table represent a priori Minimum Detectable Concentrations (MDC) that are typically achieved in laboratory analyses of liquid radwaste samples.

RADIONUCLIDE MDC UNITS Mn-54 Fe-59 Co-58 Co-60 Zn-65 Mo-99 Cs-134 Cs-137 Ce-141 Ce-144 1-131 Xe-133 Xe-135 Fe-55 Sr-89 Sr-90 H-3 Gross Alpha 2.73E-08 8.33E-08 3.78E-08 6.76E-08 1.32E-07 4.31 E-07 3.06E-08 4.51 E-08 6.99E-08 2.95E-07 5.97E-08 9.11E-08 4.27E-08 1.OOE-06 5.OOE-08 7.OOE-09 2.OOE-06 7.OOE-08 lLCi/mI PCVml PCl/ml jLiC/ml P.CI/mI jiCVml jtCVmI

~i/~ml jiCVmI g4CLmI jxCimI PCi/ml ACl/mI pCi/ml tiCi/ml ljtiCml j~tcvml P~Ci/ml Page 29 of 84

TABLE 1-5A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents - Batch Release Summary Unit: 1 Starting :

1-Jan-2003 Ending: 30-Jun-2003 NUMBER OF BATCH RELEASES 33 TOTAL TIME PERIOD FOR BATCH RELEASES 5499.03 MAXIMUM TIME PERIOD FOR A BATCH RELEASE 355.00 AVERAGE TIME PERIOD FOR BATCH RELEASES 166.64 MINIMUM TIME PERIOD FOR A BATCH RELEASE 35.58 TABLE 1-5A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents - Batch Release Summary Unit: 1 Starting:

1-Jul-2003 Ending: 31-Dec-2003 MINUTES MINUTES MINUTES MINUTES NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME PERIOD FOR A BATCH RELEASE 55 13489.33 4692.00 245.26 23.80 MINUTES MINUTES MINUTES MINUTES The average flow rate of the Savannah River at Augusta for the Radioactive Effluent Release Report period was obtained from the U.S. Army Corps of Engineers Savannah District Historic Data web page http://water.sas.usace.army.mil/tdis.html.

The average flow rate for 2003 was 9413 cubic feet per sec.

Page 30 of 84

TABLE 1-5B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents -

Batch Release Summary Unit: 2 Starting :

1-Jan-2003 Ending : 30-Jun-2003 NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME PERIOD FOR A BATCH RELEASE 15 2168.00 345.00 144.53 36.53 MINUTES MINUTES MINUTES MINUTES TABLE 1-5B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents -

Batch Release Summary Unit: 2 Starting : 1-Jul-2003 Ending : 31-Dec-2003 NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME PERIOD FOR A BATCH RELEASE 40 9077.30 1327.00 226.93 21.67 MINUTES MINUTES MINUTES MINUTES The average flow rate of the Savannah River at Augusta for the Radioactive Effluent Release Report period was obtained from the U.S. Army Corps of Engineers Savannah District Historic Data web page http://water.sas.usace.army.mil/tdis.html.

The average flow rate for 2003 was 9413 cubic feet per sec.

Page 31 of 84

TABLE 1-6A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents - Abnormal Release Summary Unit: 1 Starting : 1-Jan-2003 Ending : 30-Jun-2003 NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 0.00 0.00 0.00 0.OOE+00 MINUTES MINUTES MINUTES MINUTES CURIES TABLE 1-6A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents - Abnormal Release Summary Unit: 1 Starting : 1-Jul-2003 Ending : 31-Dec-2003 NUMBER OF RELEASES 0

TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES 0.OOE+00 CURIES Page 32 of 84

TABLE 1-6B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents - Abnormal Release Summary Unit: 2 Starting : 1-Jan-2003 Ending : 30-Jun-2003 NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A.

MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 0.00 0.00 0.00 0.OOE+00 MINUTES MINUTES MINUTES MINUTES CURIES TABLE 1-6B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Liquid Effluents - Abnormal Release Summary Unit: 2 Starting :

1-Jul-2003 Ending : 31-Dec-2003 NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 0.00 0.00 0.00 0.OOE+00 MINUTES MINUTES MINUTES MINUTES CURIES Page 33 of 84

2.0 Gaseous Effluents 2.1 Regulatory Requirements The ODCM Specifications presented in this section are for Unit 1 and Unit 2.

2.1.1 Dose Rate Limits The dose rate due to radioactive materials released in gaseous effluents from the site to areas at and beyond the SITE BOUNDARY shall be limited to the following:

a.

For noble gases, Less than or equal to 500 mrems/yr. to the whole body and less than or equal to 3000 mrems/yr. to the skin and,

b.

For lodine-1 31, for lodine-1 33, for tritium and for all radionuclides in particulate form with half lives greater than 8 days: Less than or equal to 1500 mrems/yr. to any organ.

2.1.2 Air Doses Due to Noble Gases In Gaseous Releases The air dose due to noble gases released in gaseous effluents, from each unit, to areas at and beyond the SITE BOUNDARY shall be limited to the following:

a.

During any calendar quarter: Less than or equal to 5 mrads for gamma radiation and less than or equal to 10 mrads for beta radiation, and

b.

During any calendar year: Less than or equal to 10 mrads for gamma radiation and less than or equal to 20 mrads for beta radiation.

2.1.3 Doses to a Member of the Public The dose to a MEMBER OF THE PUBLIC from Iodine-131, Iodine-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released, from each unit, to areas at and beyond the SITE BOUNDARY shall be limited to the following.

a.

During any calendar quarter: Less than or equal to 7.5 mrems to any organ.

b.

During any calendar year: Less than or equal to 15 mrems to any organ.

Page 34 of 84

2.2 Measurements and Approximations of Total Radioactivity 2.2.1 Sample Collection and Analysis Gaseous Effluents at the Vogtle Electric Generating Plant are currently confined to six paths: plant vents (Unit 1 and Unit 2), the condenser air ejector, the steam packing exhauster systems (Unit 1 and Unit 2), Radwaste Processing Facility and the DAW (Dry Active Waste Building).

Waste gas decay tanks are batch released through the Unit 1 plant vent. The containment purges are released through their respective plant vents.

All of the paths with the exception of the DAW and RPF can be continuously monitored for gaseous radioactivity. The RPF is equipped with an integrated-type sample collection device for collecting particulates. Plant vent, containment, steam jet air ejector, steam-packing exhauster are equipped with an integrated-type sample collection device for collecting particulates and iodines. Samples of the DAW are collected using portable monitoring equipment during periods of operation. During this reporting period, there were no continuous radioactive releases through the condenser air ejector and the steam packing exhauster system vents. There were no releases from the DAW. Batch Waste Gas Decay Tank releases are analyzed for noble gases before each release. The containment atmosphere is analyzed for noble gases prior to each release and for tritium at least on a monthly basis.

Sample analyses results and release flow rates form the basis for calculating released quantities of radionuclide specific radioactivity, dose rates associated with gaseous releases, and cumulative doses for the current quarter and year.

With each release period and batch release, radioactivity, dose rates, and cumulative doses are calculated. Cumulative dose results are tabulated, along with the percent of the ODCM limits for each release for the current quarter and year.

Typically achieved minimum detectable concentrations for gaseous effluent sample analyses are reported in Table 2-6.

2.2.2 Total Quantities of Radioactivity, Dose Rates, and Cumulative Doses The methods for determining release quantities of radioactivity, dose rates, and cumulative doses are as follows:

2.2.2.1 Fission and Activation Gases The released radioactivity is determined from sample analyses results collected as described above and average release flow rates over the period represented by the collected sample. Dose rates due to noble gases, radiolodines, tritium, Page 35 of 84

2.2.2.1 Fission and Activation Gases cont'd and particulates are calculated. Calculated dose rates are compared to the dose rate limits specified in ODCM 3.1.2 for noble gases, radioiodines, tritium, and particulates. Dose rate calculation methodology is presented in the ODCM.

Beta and gamma air doses due to noble gases are calculated for the location in the unrestricted area with the potential for the highest exposure due to gaseous releases. Air doses are calculated for each release period and cumulative totals are kept for each unit for the calendar quarter and year. Cumulative air doses are compared with the dose limits specified in ODCM 3.1.3. Current percent of the ODCM limits are shown on the printout for each release period. Air dose calculation methodology is presented in the ODCM.

2.2.2.2 Radioiodines, Tritium and Particulate Releases The released quantities of radiolodines, tritium and particulates are determined using the weekly samples and release flow rates for the two plant vent release points.

After each quarter, the particulate filters from each plant vent are combined, for strontium analysis. Strontium concentrations are input to the composite file of the computer to be used for release dose rate and individual dose calculations.

Doses to a Member of the Public due to radioiodines, tritium and particulates are calculated for the controlling receptor, which is described in Table 3-7of the ODCM. Doses are calculated for each release period, and cumulative totals are kept for each unit for the current calendar quarter and year. Cumulative doses are compared to the dose limits specified in ODCM 3.1.4.

Current percent of ODCM limits are shown in this report for each release period.

2.2.2.3 Gross Alpha Release The gross alpha release is calculated each month by counting the particulate filters for each week for gross alpha activity. The four or five weeks' numbers are then recorded on a data sheet and the activity is summed at the end of the month. This concentration is used for release calculations.

2.2.3 Total Error Estimation The total or maximum error associated with the effluent measurement will include the cumulative errors resulting from the total operation of sampling and measurement. Because it may be very difficult to assign error terms for each parameter affecting the final measurement, detailed statistical evaluation of error are not suggested.

Page 36 of 84

2.2.3 Total Error Estimation cont'd The objective should be to obtain an overall estimate of the error associated with measurements of radioactive materials released in liquid and gaseous effluents and solid waste.

Estimated errors are based on errors in counting equipment calibration, counting statistics, vent-flow rates, vent sample flow rates, non-steady release rates, chemical yield factors, and sample losses for such items as charcoal cartridges.

a.

Fission and activation total release was calculated from sample analysis results and release point flow rates.

Sampling and statistical error in counting 10%

Counting equipment calibration 10%

Vent flow Rates 10%

Non-steady release rates 20%

TOTAL ERROR 50%

b.

1-131 releases were calculated from each weekly sample:

Statistical error in counting 10%

Counting equipment calibration 10%

Vent Flow Rates 10%

Vent Sample Flow Rates 50%

Non-Steady release rates 10%

Losses from charcoal cartridges 10%

TOTAL ERROR 100%

c.

Particulates with half-lives greater than 8 day releases were calculated from sample and analysis results and release point flow rates.

Statistical error at MDC concentration 10%

Counting equipment calibration 10%

Vent flow rates 10%

Vent sample flow rates 50%

Non steady release rates 10%

TOTAL ERROR 90%

d.

Total tritium releases were calculated from sample analysis results and release point flow rates.

Water vapor in sample stream determination 10%

Vent flow rates 10%

Counting calibration and statistics 10%

Non-steady release rates 10%

TOTAL ERROR 40%

2.2.3 Total Error Estimation cont'd Page 37 of 84

e.

Gross Alpha radioactivity was calculated from sample analysis results and release point flow rates.

Statistical error at MDC concentration 10%

Counting equipment calibration 10%

Vent flow rates 10%

Vent sample flow rates 50%

Non Steady release rates 10%

TOTAL ERROR 90%

2.3 Gaseous Effluent Release Data Regulatory Guide 1.21 Tables 1A, 1B, and 1C are found in this report as Tables 2-1 A, 2-1 B, 2-1 C, 2-2A, 2-2B, 2-2C, 2-3A, 2-3B, and 2-3C. Data are presented on a quarterly basis as required by Regulatory Guide 1.21.

To complete table 2-1 A, and 2-1 B, the total release for each of the four categories (fission and activation gases, iodines, particulates, and tritium) was divided by the number of seconds in the quarter to obtain a release rate in pCi/second for each category. However, the percent of the ODCM limits are not applicable because VEGP has no curie limits for gaseous releases. Applicable limits are expressed in terms of dose. Noble gases are limited as specified in ODCM 3.1.2. The other three categories (tritium, radiolodines, and particulates) are limited as a group as specified in ODCM 3.1.2; Dose rates due to noble gas releases and due to radioiodines, tritium, and particulate releases were calculated as part of the pre-release and post-release permits. No limits were exceeded for this reporting period.

Gross alpha radioactivity is reported in Table 2-1A, and 2-lB as curies released in each quarter.

Limits for cumulative beta and gamma air doses due to noble gases are specified in ODCM 3.1.3. Cumulative air doses are presented in Table 2-4A, and 2-4B along with the percent of the ODCM limits.

Limits for cumulative doses to a Member of the Public due to radioiodines, tritium and particulates, are specified in ODCM 3.1.4. Cumulative doses to a Member of the Public are presented in Table 2-5A, and 2-5B along with percent of ODCM limits.

Page 38 of 84

2.4 Radiological Impact Due to Gaseous Releases Dose rates due to the release of noble gases were calculated for the site in accordance with ODCM 3.4.1.1. Dose rates due to radiolodines, tritium, and particulates in gaseous releases were calculated in accordance with ODCM 3.4.1.2.

Dose rates were calculated as part of pre-release and post release permits, no limits were exceeded for this reporting period.

Cumulative air doses due to noble gas releases were calculated for each unit in accordance with ODCM 3.4.2. These results are presented in Tables 2-4A and 2-4B.

Cumulative doses to a Member of the Public were calculated for each unit in accordance with ODCM 3.4.3. These results are presented in Tables 2-5A and 2-5B.

Dose rates and doses were calculated using the methodology presented in the Vogtle Electric Generating Plant Offsite Dose Calculation Manual.

2.5 Gaseous Effluents - Batch Releases Other data pertinent to batch releases of radioactive gaseous effluent from Unit 1 and Unit 2 are listed in Table 2-7A and 2-7B.

Page 39 of 84

2.6 Gaseous Effluents - Abnormal Releases Condition Report # 2003000313 was written on 2/5/2003 for an unplanned release that happened on 2/5/2003. This resulted with a loss of 13 psig of WGDT #6 (2-1902-V6-006) contents. It was determined that the trouble shooting guide that was being utilized at the time gave a flow path for the waste gas decay tank through Waste Gas Decay Tank #6 vent to the plant vent by way of the auxiliary building. Once operations stopped the trouble shooting and returned the system to its normal configuration, the loss of pressure was ended. Plant Vent monitors had increased during this time which led chemistry to sample the plant vent. Historically, Unit #2 shows no noble gases. This release from the WGDT #6 showed Xe-1 33 and Xe-1 35 in the plant vent samples collected by chemistry. Plant Vent release permit 30029 covers this WGDT #6 Unit #2 unplanned release. Permit 30029 release duration is conservative with respect to the decay tank release duration. Subsequent sample from Unit #2 Plant Vent showed no noble gas activity, which confirms no more WGDT #6 release. Total curie release from this incident is 0.055. Dose and Dose Rates from this release were well within ODCM Limits.

Condition Report # 2003000751 was written on 3/18/2003 for an unplanned release that happened on 3/16/2003. This resulted with a loss of 17 psig of WGDT #5 (1-1902-V6-005) contents. It was determined that the Common Recombiner Analyzer Drain Valves drain valves A-1 902-U4-726 and A-1 902-U4-727 were left in the OPEN position which was in error. Once the valves were returned to the correct positions the release terminated and the loss of pressure ceased. This release, while unplanned, was monitored via the plant stack monitors. Permit 30110 was issued to cover this event. Total curie release from this incident is 0.841. Dose and Dose Rates from this release were well within ODCM Limits.

Page 40 of 84

TABLE 2-1A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Summation of All Releases Unit: 1 Starting : l-Jan-2003 Ending : 30-Jun-2003 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE CURIES 1.26E+00 7.84E-02 50

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 1.63E-01 9.98E-03

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1.

TOTAL IODINE-131 CURIES 0.OOE+00 0.OOE+00 100

2.

AVERAGE RELEASE RATE FOR PERIOD 'pCi/Sec 0.OOE+00 0.OOE+OO

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 0.OOE+00 0.OOE+00 90

2. AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 0.OOE+00 O.OOE+00
3.

PERCENT OF APPLICABLE LIMIT

4. GROSS ALPHA RADIOACTIVITY CURIES O.OOE+O0 0.OOE+O0 D. TRITIUM
1. TOTAL RELEASE CURIES 8.49E+00 4.13E+00 40
2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 1.09E+00 5.25E-01

3. PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

Page 41 of84

TABLE 2-1A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Summation of All Releases Unit: 1 Starting 1-Jul-2003 Ending : 31-Dec-2003 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 2.37E-01 1.02E-01 50
2. AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 2.99E-02 1.28E-02
3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1.

TOTAL IODINE-131 CURIES 0.OOE+00 O.OOE+00 100

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 0.OOE+00 0.OOE+00

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1.

PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 4.03E-07 8.08E-07 90

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 5.07E-08 1.02E-07

3.

PERCENT OF APPLICABLE LIMIT

4. GROSS ALPHA RADIOACTIVITY CURIES O.OOE+00 0.OOE+00 D. TRITIUM
1. TOTAL RELEASE CURIES 5.81E+00 2.07E+01 40
2. AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 7.31E-01 2.61E+00
3. PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

Page 42 of 84

TABLE 2-1B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Summation of All Releases Unit: 2 Starting : 1-Jan-2003 Ending : 30-Jun-2003 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 1.01E-01 4.24E-02 50
2. AVERAGE RELEASE RATE FOR PERIOD ViCi/Sec 1.29E-02 5.39E-03
3.

PERCENT OF APPLICABLE LIMIT B. RADIOIODINES

1. TOTAL IODINE-131 CURIES 0.OOE+00 0.OOE+00 100
2. AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 0.OOE+00 0.OOE+00
3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1.

PARTICULATES(HALF-LIVES>8 DAYS)

CURIES O.OOE+00 7.44E-08 90

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec O.OOE+00 9.46E-09

3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES 0.OOE+00 O.OOE+00 D.

TRITIUM

1.

TOTAL RELEASE CURIES 4.79E+00 4.OOE+00 40

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 6.16E-01 5.08E-01

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-SB of this report.

Page 43 of 84

TABLE 2-1B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Summation of All Releases Unit: 2 Starting : l-Jul-2003 Ending : 31-Dec-2003 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE CURIES 1.20E+00 6.88E-02 50

2. AVERAGE RELEASE RATE FOR PERIOD liCi/Sec 1.51E-01 8.65E-03
3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1.

TOTAL IODINE-131 CURIES O.00E+00 0.OOE+00 100

2.

AVERAGE RELEASE RATE FOR PERIOD 1.Ci/Sec 0.OOE+00 0.OOE+00

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1.

PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 4.61E-08 4.56E-07 90

2. AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 5.80E-09 5.73E-08
3. PERCENT OF APPLICABLE LIMIT
4. GROSS ALPHA RADIOACTIVITY CURIES 0.OOE+00 0.OOE+00 D. TRITIUM
1. TOTAL RELEASE CURIES 9.01E+00 5.70E-03 40
2. AVERAGE RELEASE RATE FOR PERIOD ViCi/Sec 1.13E+00 7.17E-04
3. PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

Page 44of 84

TABLE 2-1C Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Summation of All Releases Unit: Site Starting : 1-Jan-2003 Ending : 30-Jun-2003 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE CURIES 1.37E+00 1.21E-01 50

2.

AVERAGE RELEASE RATE FOR PERIOD liCi/Sec 1.76E-01 1;54E-02

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1. TOTAL IODINE-131 CURIES 0.OOE+00 0.OOE+00 100
2. AVERAGE RELEASE RATE FOR PERIOD ViCi/Sec 0.OOE+00 0.OOE+00
3. PERCENT OF APPLICABLE LIMIT C. PARTICULATES
1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 0.OOE+00 7.44E-08 90

2. AVERAGE RELEASE RATE FOR PERIOD jiCi/Sec 0.OOE+00 9.46E-09
3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES O.OOE+00 0.OOE+00 D.

TRITIUM

1.

TOTAL RELEASE CURIES 1.33E+01 8.13E+00 40

2.

AVERAGE RELEASE RATE FOR PERIOD jiCi/Sec 1.71E+00 1.03E+00

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

Page 45 of 84

TABLE 2-1C Vogtle Electric Generating Plant.

RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Summation of All Releases Unit: Site Starting :

-Jul-2003 Ending 31-Dec-2003 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A. FISSION & ACTIVATION PRODUCTS

1.

TOTAL RELEASE CURIES 1.44E+00 1.70E-01 50

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 1.81E-01 2.14E-02

3.

PERCENT OF APPLICABLE LIMIT B. RADIOIODINES

1.

TOTAL IODINE-131 CURIES 0.OOE+00 O.OOE+00 100

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec O.00E+00 0.OOE+00

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1.

PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 4.49E-07 1.26E-06 90

2. AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 5.65E-08 1.59E-07
3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES O.OOE+00 0.OOE+00 D. TRITIUM

1.

TOTAL RELEASE CURIES 1.48E+01 2.07E+01 40

2.

AVERAGE RELEASE RATE FOR PERIOD pCi/Sec 1.86E+00 2.61E+00

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

Page 46 of 84

TABLE 2-2A*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Mixed-Mode Level Releases Unit: 1 Starting : 1-Jan-2003 Ending : 30-Jun-2003 l

CONTINUOUS MODE I

BATCH MODE l

NUCLIDES RELEASED I

UNIT I QUARTER 1 I QUARTER 2 1 QUARTER 1 I QUARTER 2 FISSION GASES AR-41 l CURIES l 0.00E+00 0.OOE+00 l 5.58E-02 l 6.34E-02 l XE-135 l CURIES l 3.58E-01 i 0.OOE+00 l O.OOE+00 l 3.95E-05 l

XE-133 l CURIES l O.OOE+00 l 0.OOE+00 l 8.50E-01 l 9.65E-03 KR-85 l CURIES l O.OOE+00 l 0.OOE+00 l 0.OOE+00 l 5.39E-03 l

TOTAL FOR PERIOD I

CURIES I 3.58E-01 I 0.OOE+00 I 9.06E-01 I 7.84E-02 l

H-3 I

CURIES I 8.48E+00 I 4.12E+00 I 1.27E-02 I 1.51E-02 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 47 of 84

TABLE 2-2A*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Mixed-Mode Level Releases Unit: 1 Starting 1-Jul-2003 Ending i 31-Dec-2003 I

CONTINUOUS MODE I

BATCH MODE NUCLIDES RELEASED I

UNIT lQUARTER 3 lQUARTER 4 lQUARTER 3 IQUARTER 4 FISSION GASES AR-41 l CURIES 0.OOE+00 l.00E+00 l 6.52E-02 l 3.41E-02 XE-135 l CURIES 0.OOE+00 l 0.OOE+00 l 2.41E-03 l 2.78E-04 l XE-133M l CURIES l 0.00E+00 0.OOE+00 l 0.OOE+00 l 3.12E-04 XE-133 l CURIES l 0.OOE+00 l 0.OOE+00 l 3.96E-02 l 5.57E-.02 KR-85 l CURIES 0.OOE+00 0.OOE+00 l 1.29E-01 l O.OOE+00 TOTAL FOR PERIOD I

CURIES I O.OOE+00 I 0.OOE+00 I 2.36E-01 I 9.04E-02 PARTICULATES SR-89 l CURIES l 0.00E+00 l 2.93E-07 l 0.OOE+00 l O.OOE+00 l CO-58 l CURIES l 9.45E-08 l 5.16E-07 l 0.OOE+00 0.OOE+00 CO-60 l CURIES l 3.09E-07 l 0.OOE+00 l 0.OOE+00 l 0.OOE+00 SR-90 l CURIES l 0.OOE+00 l 6.66E-16 l 0.OOE+00 l O.OOE+00 TOTAL FOR PERIOD I

CURIES I 4.03E-07 I 8.08E-07 I 0.OOE+00 I 0.OOE+00 H-3 I

CURIES I 5.79E+00 I 2.05E+01 I 1.36E-02 I 2.15E-01 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 48 of 84

TABLE 2-2B*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Mixed-Mode Level Releases Unit: 2 Starting 1-Jan-2003 Ending : 30-Jun-2003 I

CONTINUOUS MODE I

BATCH MODE I

NUCLIDES RELEASED I

UNIT IQUARTER 1 IQUARTER 2 IQUARTER 1 IQUARTER 2 1 FISSION GASES AR-41 I CURIES I O.OOE+00 I 0.OOE+00 I 2.20E-02 I 3.46E-02 I XE-135 I CURIES I 1.58E-02 I 0.OOE+00 I 9.74E-04 I 6.85E-05 I XE-133 I CURIES I 3.92E-02 I O.00E+00 I 1.83E-02 I 7.43E-03 I KR-85

! CURIES I 0.OOE+00 I 0.OOE+00 I 4.36E-03 I 2.48E-04 I TOTAL FOR PERIOD I CURIES I 5.50E-02 I 0.OOE+00 I 4.56E-02 I 4.24E-02 I PARTICULATES SR-89 I CURIES I 0.00E+00 I 7.44E-08 I 0.00E+00 I 0.OOE+00 I TOTAL FOR PERIOD I CURIES I 0.OOE+00 I 7.44E-08 I 0.OOE+00 I 0.OOE+00 I H-3 I CURIES I 4.77E+00 I 3.98E+00 I 1.84E-02 I 1.29E-02 I Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 49 of 84

TABLE 2-2B*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Mixed-Mode Level Releases Unit: 2 Starting :-Jul-2003 Ending : 31-Dec-2003 l

CONTINUOUS MODE I

BATCH MODE I

NUCLIDES RELEASED I

UNIT I QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION GASES AR-41 l CURIES l O.OOE+00 l O.OOE+00 l 1.49E-01 l 2.75E-02 l XE-135 l CURIES l O.OOE+00 l 0.OOE+00 2.33E-03 l 1.86E-04 l XE-133 l CURIES l O.OOE+00 l 0.OOE+00 l 1.72E-01 l 2.51E-02 l KR-85 CURIES 0.OOE+00 l 0.OOE+00 l 8.76E-01 l 1.60E-02 l TOTAL FOR PERIOD I

CURIES I O.OOE+00 I O.OOE+00 I 1.20E+00 I 6.88E-02 I PARTICULATES SR-89 CURIES 1.25E-09 l 4.55E-07 l 0.OOE+00 l 0.OOE+00 l SR-90 l CURIES l 4.49E-08 l 1.78E-10 l O.OOE+00 l O.OOE+00 TOTAL FOR PERIOD l CURIES I 4.61E-08 I 4.56E-07 I O.OOE+00 I O.OOE+00 1 H-3 I

CURIES I 7.91E+00 I 0.00E+00 I 1.10E+00 I 5.70E-03 I Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 50 of 84

TABLE 2-2C*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting : 1-Jan-2003 Ending : 30-Jun-2003 l

CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED I

UNIT lQUARTER 1 l QUARTER 2 l QUARTER 1 I QUARTER 2 FISSION GASES AR-41 l CURIES l O.OOE+00 0.OOE+00 l 7.77E-02 9.80E-02 XE-135 l CURIES l 3.74E-01 l 0.OOE+00 l 9.74E-04 l 1.08E-04 XE-133 l CURIES l 3.92E-02 l 0.OOE+00 l 8.69E-01 l 1.71E-02 KR-85 l CURIES O.OOE+00 l 0.OOE+00 l 4.36E-03 l 5.63E-03 l TOTAL FOR PERIOD I

CURIES I 4.13E-01 I 0.OOE+00 I 9.52E-01 I 1.21E-01 PARTICULATES SR-89 I

CURIES I 0.OOE+00 I 7.44E-08 I O.OOE+00 I O.OOE+00 TOTAL FOR PERIOD I

CURIES I O.00E+00 I 7.44E-08 I O.OOE+00 l-°.00E+00 H-3 l CURIES l 1.33E+01 I 8.10E+00 I 3.11E-02 I 2.80E

  • Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 51 of 84

TABLE 2-2C*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting : 1-Jul-2003 Ending : 31-Dec-2003 l

CONTINUOUS MODE I

BATCH MODE I

NUCLIDES RELEASED I

UNIT lQUARTER. 3 l QUARTER 4 l QUARTER 3 l QUARTER-4 FISSION GASES AR-41 l CURIES O.OOE+00 O.OOE+00 2.15E-01 l 6.16E-02 l XE-135 l CURIES l O.OOE+00 l 0.OOE+00 l 4.73E-03 l 4.63E-04 XE-133M CURIES O.OOE+00 l 0.OOE+00 l 0.OOE+00 l 3.12E-04 l XE-133 l CURIES O.OOE+00 l O.OOE+00 2.11E-01 8.08E-02 l KR-85 l CURIES l 0.00E+00 l O.OOE+00 l 1.OOE+00 l 1.60E-02 l TOTAL FOR PERIOD l CURIES l 0.OOE+00 I O.OOE+00 I 1.44E+00 I 1.59E-01 l PARTICULATES SR-89 l CURIES l 1.25E-09 l 7.48E-07 l 0.OOE+00 l 0.OOE+00 l

CO-58 l CURIES l 9.45E-08 l 5.16E-07 l O.OOE+00 l O.OOE+00 l

Co-60 l CURIES l 3.09E-07 l 0.OOE+00 l 0.OOE+00 l O.OOE+00 l SR-90 l CURIES 4.49E-08 l 1.78E-10 l 0.OOE+00 l O.OOE+00 TOTAL FOR PERIOD I

CURIES I 4.49E-07 I 1.26E-06 I O.OOE+00 I 0.OOE+00 l H-3 I

CURIES I 1.37E+01 I 2.05E+01 I 1.12E+00 I 2.21E-01 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 52 of 84

TABLE 2-3A*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Ground Level Releases Unit: 1 Starting 1-Jan-2003 Ending : 30-Jun-2003 I

CONTINUOUS MODE I

BATCH MODE NUCLIDES RELEASED I

UNIT IQUARTER 1 1 QUARTER 2 J QUARTER 1 1 QUARTER 2 TOTAL FOR PERIOD I

CURIES I O.OOE+00 I O.OOE+00 I O.OOE+00 I O.OOE+00 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 53 of 84

TABLE 2-3A*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Ground Level Releases Unit: 1 Starting 1-Jul-2003 Ending : 31-Dec-2003 CONTINUOUS MODE I

BATCH MODE I

NUCLIDES RELEASED I

UNIT IQUARTER 3 IQUARTER 4 1QUARTER 3 IQUARTER 4 l FISSION GASES XE-133 l CURIES I O.OOE+00 I O.OOE+00 I 1.08E-03 I 1.11E-02 l

TOTAL FOR PERIOD I

CURIES I 0.OOE+00 I 0.OOE+00 I 1.08E-03 I 1.11E-02 I H-3 I

CURIES I O.OOE+00 I O.OOE+00 I 9.73E-04 I 1.88E-02 I

Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-6 for typical minimum detectable concentrations.

Page 54 of 84

TABLE 2-3B*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Ground Level Releases Unit: 2 Starting :

1-Jan-2003 Ending : 30-Jun-2003 I

CONTINUOUS MODE I

BATCH MODE l

NUCLIDES RELEASED I

UNIT I QUARTER 1 I QUARTER 2 1 QUARTER 1 1 QUARTER 2 l TOTAL FOR PERIOD I CURIES I 0.OOE+00 0.OOE+00 l 0.OOE+00 I 0.OOE+00 I Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 55 of 84

TABLE 2-3B*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT.RELEASE REPORT -

2003 Gaseous Effluents-Ground Level Releases Unit: 2 Starting : l-Jul-2003 Ending : 31-Dec-2003 CONTINUOUS MODE l

BATCH MODE NUCLIDES RELEASED I

UNIT I QUARTER 0 1 QUARTER 0 j QUARTER 0 1 QUARTER 0 TOTAL FOR PERIOD I CURIES I O.OOE+00 I O.OOE+00 I O.OOE+00 I O.OOE+00 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 56 of 84

TABLE 2-3C*

Vogtle Electric Generating..Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Ground Level Releases Unit: Site Starting 1-Jan-2003 Ending: 30-Jun-2003 I

CONTINUOUS MODE i

BATCH MODE I

NUCLIDES RELEASED I

UNIT 1QUARTER 1 lQUARTER 2 IQUARTER 1 lQUARTER 2 l TOTAL FOR PERIOD I CURIES I O.OOE+00 I 0.OOE+00 I O.OOE+00 I O.OOE+00 zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typical minimum detectable concentrations.

Page 57 of 84

TABLE 2-3C*

Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents-Ground Level Releases Unit: Site Starting : 1-Jul-2003 Ending : 31-Dec-2003 I

CONTINUOUS MODE I

BATCH MODE I

NUCLIDES RELEASED I

UNIT IQUARTER 3 1 QUARTER 4 1 QUARTER 3 1 QUARTER 4 FISSION GASES Xe-133 I

CURIES I O.OOE+00 I O.OOE+00 I 1.08E-03 I 1.11E-02 l TOTAL FOR PERIOD I

CURIES I 0.OOE+00 I 0.OOE+00 I 1.08E-03 I 1.11E-02 H-3 I

CURIES I 0.OOE+00 I -0.OOE+00 I 9.73E-04 I 1.88E-02 l Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-7 for typical minimum detectable concentrations.

Page 58 of 84

TABLE 2-4A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 AIR DOSES DUE TO GASEOUS RELEASES Unit: 1 Starting: 01-Jan-2003 Ending: 30-Jun-2003 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 1

ODCM 2

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 2.21E-05 4.41E-04 8.68E-06 1.74E-04 Beta 10.0 mrad 2.87E-05 2.87E-04 3.35E-06 3.35E-05 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 3.08E-05 3.08E-04 Beta 20.0 mrad 3.20E-05 1.60E-04 Page 59 of 84

TABLE 2-4A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 AIR DOSES DUE TO GASEOUS RELEASES Unit: 1 Starting: 01-Jul-2003 Ending: 31-Dec-2003 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 3

ODCM 4

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 9.22E-06 1.84E-04 5.26E 1.05E-04 Beta 10.0 mrad 7.60E-06 7.60E-05 3.46E-06 3.46E-05 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 4.09E-05 4.09E-04 Beta 20.0 mrad 3.01E-05 1.51E-04 Page 60 of 84

TABLE 2-4B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -.

2003 AIR DOSES DUE TO GASEOUS RELEASES Unit: 2 Starting: 01-Jan-2003 Ending: 30-Jun-2003 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 1

ODCM 2

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 3.76E-06 7.52E-05 4.76E-06 9.52E-05 Beta 10.0 mrad 2.67E-06 2.67E-05 1.79E-06 1.79E-05 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 8.52E-06 8.52E-05 Beta 20.0 mrad 4.46E-06 2.23E-05 Page 61 of 84

TABLE 2-4B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT - 2003 AIR DOSES DUE TO GASEOUS RELEASES Unit: 2 Starting: 01-Jul-2003 Ending: 31-Dec-2003 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 3

ODCM 4

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 2.15E-05 4.31E-04 3.88E-06 7.77E-05 Beta 10.0 mrad 3.49E-05 3.49E-04 2.17E-06 2.17E-05 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 3.39E-05 3.39E-04 Beta 20.0 mrad 4.15E-05 2.08E-04 Page 62 of 84

TABLE 2-5A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,

TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jan-2003 Ending: 30-Jun-2003 Cumulative Doses per Quarter Organ ODCM Unit Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone 7.5 mrem O.OOE+00 0.OOE+00 O.OOE+00 0.OOE+00 Liver 7.5 mrem 5.46E-05 7.28E-04 2.66E-05 3.54E-04 TBody 7.5 mrem 5.46E-05 7.28E-04 2.66E-05 3.54E-04 Thyroid 7.5 mrem 5.46E-05 7.28E-04 2.66E-05

  • 3.54E-04 Kidney 7.5 mirem 5.46E-05 7.28E-04 2.66E-05 3.54E-04 Lung 7.5 mrem 5.46E-05 7.28E-04 2.66E-05 3.54E-04 GILLI 7.5 mrem 5.46E-05 7.28E-04 2.66E-05 3.54E-04 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 15.0 mrem 0.OOE+00 0.OOE+00 Liver 15.0 mrem 8.12E-05 5.41E-04 TBody 15.0 mrem 8.12E-05 5.41E-04 Thyroid 15.0 mrem 8.12E-05 5.41E-04 Kidney 15.0 mrem 8.12E-05 5.41E-04 Lung 15.0 mrem 8.12E-05 5.41E-04 GILLI 15.0 mrem 8.12E-05 5.41E-04 Page 63 of 84

TABLE 2-5A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,

TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jul-2003 Ending: 31-Dec-2003 Cumulative Doses per Quarter

-Organ ODCM Unit Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone 7.5 mrem 4.21E-08 5.62E-07 7.05E-08 9.39E-07 Liver 7.5 mrem 3.74E-05 4.99E-04 1.33E-04 1.78E-03 TBody 7.5 mrem 3.74E-05 4.99E-04 1.33E-04 1.78E-03 Thyroid 7.5 mrem 3.74E-05 4.99E-04 1.33E-04 1.78E-03 Kidney 7.5 mrem 3.74E-05 4.99E-04 1.33E-04 1.78E-03 Lung 7.5 mrem 3.74E-05 4.99E-04 1.33E-04 1.78E-03 GILLI 7.5 mrem 3.74E-05 4.99E-04 1.33E-04 1.78E-03 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 15.0 mrem 1.13E-07 7.51E-07 Liver 15.0 mrem 2.52E-04 1.68E-03 TBody 15.0 mrem 2.52E-04 1.68E-03 Thyroid 15.0 mrem 2.52E-03 1.68E-02 Kidney 15.0 mrem 2.52E-04 1.68E-03 Lung 15.0 mrem 2.52E-04 1.68E-03 GILLI 15.0 mrem 2.52E-04 1.68E-03 Page 64 of 84

TABLE 2-5B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES, TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jan-2003 Ending: 30-Jun-2003 Cumulative Doses per Quarter Organ ODCM Unit Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone Liver TBody Thyroid Kidney Lung GILLI 7.5 7.5 7.5 7.5 7.5 7.5 7.5 mrem mrem mrem nirem nirem mnrem mrem O.OOE+O0 3.08E-05 3.08E-05 3.08E-05 3.08E-05 3.08E-05 3.08E-05 O.OOE+00 4.11E-04 4.11E-04 4.11E-04 4.11E-04 4.11E-04 4.11E-04 1.76E-08 2.57E-05 2.57E-05 2.57E-05 2.57E-05

.2.57E-05 2.57E-05 2.35E-07 3.43E-04.

3.43E-04 3.43E-04 3.43E-04 3.43E-04 3.43E-04 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone Liver TBody Thyroid Kidney Lung GILLI 15.0 15.0 15.0 15.0 15.0 15.0 15.0 mrem mrem mrem' mnrem mrem nirem mrem 1.76E-08 5.65E-05 5.65E-05 5.65E-05 5.65E-05 5.65E-05 5.65E-05 1.17E-07 3.77E-04 3.77E-04 3.77E-04 3.77E-04 3.77E-04 3.77E-04 Page 65 of 84

TABLE 2-5B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,

TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jul-2003 Ending: 31-Dec-2003 Cumulative Doses per Quarter Organ ODCM Unit Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone 7.5 mrem 3.60E-07 4.79E-06 1.09E-07 1.46E-06 Liver 7.5 mrem 5.79E-05 7.72E-04 3.66E-08 4.88E-07 TBody 7.5 mrem 5.80E-05 7.74E-04 4.OOE-08 5.33E-07 Thyroid 7.5 mrem 5.79E-05 7.72E-04 3.66E-08 4.88E-07 Kidney 7.5 mrem 5.79E-05 7.72E-04 3.66E-08 4.88E-07 Lung 7.5 mrem 5.79E-05 7.72E-04 3.78E-08 5.04E-07 GILLI 7.5 mrem 5.79E-05 7.72E-04 4.08E-08 5.44E-07 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 15.0 mrem 4.86E-07 3.24E-06 Liver 15.0 mrem 1.14E-04 7.63E-04 TBody 15.0 mrem 1.15E-04 7.64E-04 Thyroid 15.0 nrem 1.14E-04 7.63E-04 Kidney 15.0 mrem 1.14E-04 7.63E-04 Lung 15.0 mrem 1.14E-04 7.63E-04 GILLI 15.0 mrem 1.14E-04 7.63E-04 Page 66 of 84

TABLE 2-6 VOGTLE ELECTRIC GENERATING PLANT RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 MINIMUM DETECTABLE CONCENTRATIONS -

GASEOUS SAMPLE ANALYSES

JANUARY, 2003 THROUGH DECEMBER, 2003 The values in this table represent a priori Minimum Detectable Concentrations (MDC) that are typically achieved in laboratory analyses of gaseous radwaste samples.

RADIONUCLIDE MDC UNITS Kr-87 Kr-88 Xe-1 33 Xe-1 33m Xe-1 35 Xe-1 38 1-131 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Mo-99 Cs-134 Cs-137 Ce-141 Ce-1 44 Sr-89 Sr-90 H-3 Gross Alpha 1.82E-08 2.53E-08 2.05E-08 8.63E-08 7.12E-08 1.05E-07 7.93E-1 5*

3.94E-1 4*

2.45E-1 4*

1.39E-14*

1.75E-14*

2.82E-1 4*

9.57E-1 4*

1.12E-14*

8.71 E-15*

8.62E-1 5*

2.77E-14*

1.OOE-13 1.OOE-13 9.OOE-08 1.OOE-13 pCVml PCI/ml pCVml pCi/mI pCi/mI pCi/ml PCVml pCI/mI pCVmI pCi/mI pCi/mI pCi/ml pCi/ml pCVml uCVml gCVml pCVmI pCi/mI PCl/mI PsCVml pCimI Based on an estimated sample volume of 5.7E+08 ml.

Page 67 of 84

TABLE 2-7A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Batch Release Summary Unit: 1 Starting :

1-Jan-2003 Ending 30-Jun-2003 GASEOUS RELEASES NUMBER OF BATCH RELEASES 57 TOTAL TIME PERIOD FOR BATCH RELEASES 3642.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE :

152.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 63.89 MINUTES MINIMUM TIME FOR A BATCH RELEASE 14.00 MINUTES TABLE 2-7A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Batch Release Summary Unit: 1 Starting : 1-Jul-2003 Ending : 31-Dec-2003 GASEOUS RELEASES NUMBER OF BATCH RELEASES 69 TOTAL TIME PERIOD FOR BATCH RELEASES 37299.90 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 8523.98 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 540.58 MINUTES MINIMUM TIME FOR A BATCH RELEASE 10.00 MINUTES Page 68 of 84

TABLE 2-7B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Batch Release Summary Unit: 2 Starting : 1-Jan-2003 Ending : 30-Jun-2003 GASEOUS RELEASES NUMBER OF BATCH RELEASES 35 TOTAL TIME PERIOD FOR BATCH RELEASES 3447.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 1585.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 98.49 MINUTES MINIMUM TIME FOR A BATCH RELEASE 17.00 MINUTES TABLE 2-7B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents - Batch Release Summary Unit: 2 Starting : 1-Jul-2003 Ending : 31-Dec-2003 GASEOUS RELEASES NUMBER OF BATCH RELEASES 36 TOTAL TIME PERIOD FOR BATCH RELEASES 22954.83 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE :

7286.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 637.63 MINUTES MINIMUM TIME FOR A BATCH RELEASE 23.00 MINUTES Page 69 of 84

TABLE 2-8A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents - Abnormal Release Summary Unit: 1 Starting : 1-Jan-2003 Ending : 30-Jun-2003 NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 1

3620.00 3620.00 3620.00 3620.00 8.41E-01 MINUTES MINUTES MINUTES MINUTES CURIES TABLE 2-8A Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Abnormal Release Summary Unit: 1 Starting : 1-Jul-2003 Ending : 31-Dec-2003 NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 1

10.12 10.12 10.12

.10.12 1.20E-02 MINUTES MINUTES MINUTES MINUTES CURIES Page 70 of 84

TABLE 2-8B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents -

Abnormal Release Summary Unit: 2 Starting : 1-Jan-2003 Ending : 30-Jun-2003 NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 0.00 0.00 0.00 0.OOE+00 MINUTES MINUTES MINUTES MINUTES CURIE TABLE 2-8B Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 Gaseous Effluents - Abnormal Release Summary Unit: 2 Starting : 1-Jul-2003 Ending : 31-Dec-2003 NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

.0.00 0.00 0.00 0.00 0.OOE+00 MINUTES MINUTES MINUTES MINUTES CURIES Page7l of 84

3.0 Solid Waste 3.1 Regulatory Requirements The ODCM requirements presented in this section are stated in part for Unit 1 and Unit 2.

3.1.1 Solid Radioactive Waste System 10.2.1 Process Control Program (PCP)

Radioactive wastes shall be solidified or dewatered in accordance with the PCP to meet shipping and transportation requirements during transit and disposal site requirements when received at the disposal site.

3.1.2 Reporting Requirements 12.1 PCP states in part:

The Radioactive Effluent Release Report, submitted in accordance with Technical Specification 5.6.3, shall include a summary of the quantities of solid radwaste released from the units, as outlined in Regulatory Guide 1.21.

3.2 Solid Waste Data Regulatory Guide 1.21, Table 3 is found in this report as Table 3-1.

Page 72 of 84

TABLE 3-1 Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Units 1 and 2 JANUARY 1, 2003 THROUGH JUNE 30, 2003 Page 1 of 4 A.

SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (Not Irradiated Fuel)

1. Type of waste
a.

Spent resins, filter sludges, evaporator,bottoms, etc.

b.

Dry compressible waste, contaminated equip, etc.

c.

Irradiated components, control rods, etc.

d.

Other (describe)

2.

Estimate of major nuclide composition

a.

N/A N/A N/A N/A

b.

Ni-63 Cs-137 Cs-134 All others

c.

N/A N/A N/A N/A

d.

N/A N/A Unit m3 Ci m3 Ci m3 Ci m3 Ci (by 6-month Period None None 10.65 26.30 NONE NONE Est. Total Error, %

N/A 40 N/A N/A type of waste)

N/A N/A N/A N/A 50.54 21.82 11.17 16.47 N/A N/A N/A N/A N/A N/A Page 73 of 84

TABLE 3-1 Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Units 1 and 2 JANUARY 1, 2003 THROUGH JUNE 30, 2003 Page 2 of 4

3.

Solid Waste Disposition Number of Mode of

-_--_-- nyrt4 nat.4 ^"

5n1 IMncS arnatw r"-

7 1

Tractor/Trailer Cask/Tractor/Trailer Duratek, Oak Ridge, TN Studsvik, Erwin, TN B. IRRADIATED FUEL SHIPMENTS (Disposition)

Number of Mode of M-b-----

a.A-n n-n.n&4 bns nents-m avvff~v

-Xfi van-

-2 None None None ADDITIONAL INFORMATION REQUIRED BY ODCM:

Shipments to a Waste Processor Shipment No. Waste Class Taee Container

' Shipping Class Solidification Acrent RVRS-03-001 RVRS-03-002 RVRS-03-003 RVRS-03-004 RVRS-03-005 RVRS-03-006 RVRS-03-007 RVRS-03-008 B UNSTABLE

'A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT LSA LSA LSA LSA LQ LQ LQ LSA (2)

(2)

(2)

(2)

(2)

NONE NONE NONE NONE NONE NONE NONE NONE Page 74 of 84

TABLE 3-1 Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Units 1 and 2 JULY 1, 2003 THROUGH DECEMBER 31, 2003.

A.

SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (Not Irr

1.

Type of waste unit 6-m Per

a.

Spent resins, filter sludges, m3 NON evaporator bottoms, etc.

Ci NON

b.

Dry compressible waste, contaminated m3 10.

equip, etc.

Ci 12.

c.

Irradiated components, control m3 NON rods, etc.

Ci NON

d.

Other (describe) m3 Ci NON Page 3 of 4 adiated Fuel) onth Est. Total jiod Error, %

E E

30 80 40 rE rE N/A NE N/A

2.

Estimate of major nuclide composition (by

a.

N/A N/A N/A N/A

b.

Ni-63 Fe-55 Co-60 All others

c.

N/A N/A N/A N/A 9

d.

N/A N/A 9

N/A 9

type of waste)

N/A N/A N/A N/A 47.4 20.1 10.4 22.1 N/A N/A N/A N/A N/A N/A N/A Page 75 of 84

TABLE 3-1 Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Units 1 and 2 JULY 1, 2003 THROUGH DECEMBER 31, 2003 Page 4 of 4

3. Solid Waste Disposition Number of Shivments Mode of

-a%

f a--4.

aft 4-4 a4-4 o-ni

  • ~~~~

-m -; -ea -B -

-y -

15

.3 Tractor/Trailer Cask/Tractor/Trailer Duratek, Oak Ridge, TN Studsvik, Erwin, TN B. IRRADIATED FUEL SHIPMENTS (Disposition)

Number of Shipments None Mode of Transportation Destination None None ADDITIONAL INFORMATION REQUIRED BY ODC4:

Shipments Sent Directly to Disposal at Barnwell, SC Shipment NoI Waste Class Type Container Shipping Class Solidification Volume (Direct Agent disposal only)

NONE Shipments to a waste processor:

Shipment No.

RVRS-03-009 RVRS-03-010 RVRS-03-011 RVRS-03-012 RVRS-03-013 RVRS-03-014 RVRS-03-015 RVRS-03-016 RVRS-03-017 RVRS-03-018 RVRS-03-019 RVRS-03-020 RVRS-03-021 RVRS-03-022 RVRS-03-023 RVRS-03-024 RVRS-03-025 RVRS-03-026 Waste Class Type Container Shipping Class Solidification Agent B UNSTABLE B UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE A UNSTABLE B UNSTABLE STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG STRONG TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT TIGHT LSA LSA LSA LSA LSA LQ LQ LQ LQ LSA LSA LSA LSA LQ LQ LQ LQ LSA (2)

(2)

(2)

(2)

(2)

NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE (2)

(2)

(2)

(2)

(2)

Page 76 of 84

W 4.0 Doses to Members of the Public Inside the Site Boundary 4.1 Regulatory Requirements ODCM 7.2.2.3 states in part:

"The report shall also include assessment of the radiation doses from radioactive liquid and gaseous effluents to MEMBERS OF THE PUBLIC due to their activities inside the SITE BOUNDARY during the report period; this assessment must be performed in accordance with Chapter 6. All assumptions used in making these assessments ( i.e., specific activity, exposure time, and location) shall be included in the report".

4.2 Demonstration of Compliance The location of concern within the site boundary is the Visitors Center. The activities at the Visitor Center consist of occasional attendance at meetings and/or short visits for informational purposes.

There will be no radiation dose at this location due to radioactive liquid effluents.

Delineated in Table 4-1 for this location are the values of the basic data assumed in the dose assessment due to radioactive gaseous effluents. Listed in this table are distance and direction from a point midway between the center of Unit 1 and the Unit 2 reactors, the dispersion and deposition factors for any releases from the plant vent (mixed mode) and from the turbine building (ground level), and the estimated maximum occupancy factor for an individual and the assumed age group of this individual.

The source term is listed in Tables 2-2A, and 2-2B for the mixed mode releases.

Similarly, it is listed in tables 2-3A and 2-3B for the ground level releases.

Page 77 of 84

4.2 Demonstration of Compliance cont'd The maximum doses in units of mrem to a MEMBER OF THE PUBLIC due to*

their activities inside the site boundary during the reporting period were assessed to be as follows:

VISITOR CENTER Quarter 1 Quarter 2 Quarter 3 Quarter 4 Total Body:

(Direct Radiation from Plume) 1.73E-07 1.1 OE-07 1.76E-07 2.20E-07 VISITOR CENTER Quarter 1 Quarter 2 Quarter 3 Quarter 4 Maximum Organ (Thyroid) Quarters 1,2,3,4 (Inhalation Ground Plane) 1.73E-07 1.1 OE-07 1.76E-07 2.20E-07 Page 78 of 84

TABLE 4-1 Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jan-2003 Ending: 30-Jun-2003 Page:

1 Location Name Distance (kilometers)

Sector Occupancy Factor Age Group VISITOR CENTER 4.47E-01 SE 4.57E-04 (4

CHILD

.OOE+00 hr/yr)

Ground Level Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m.3)

Particulate D/Q (m-2)

Mixed Mode Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2)

Elevated Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2) 5.93E-06 5.58E-06 2.28E-08 7.12E-07 6.74E-07 5.77E-09 N/A N/A N/A Units Quarter 1 Quarter 2 Quarters

-1 and 2 Year to Ending Date Bone Liver TBody Thyroid Kidney Lung GI-LLI mrem 1.69E-08 mrem 1.73E-07 mrem 1.73E-07 mrem 1.73E-07 mrem 1.73E-07 mrem 1.73E-07 mrem 1.73E-07 8.99E-09 1.10E-07 l.1OE-07 1.10E-07

1. 1OE-07 1.10E-07 1.10E-07 2.58E-08 2.83E-07 2.83E-07 2.83E-07 2.83E-07 2.83E-07 2.83E-07 2.58E-08 2.83E-07 2.83E-07 2.83E-07 2.83E-07 2.83E-07 2.83E-07 Page 79 of 84

TABLE 4-1 Vogtle Electric Generating Plant RADIOACTIVE EFFLUENT RELEASE REPORT -

2003 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-2003 Ending: 31-Dec-2003 Page:

2 Location Name Distance (kilometers)

Sector Occupancy Factor Age Group VISITOR CENTER 4.47E-01 SE 4.57E-04 (4

CHILD

.OOE+00 hr/yr)

Ground Level Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2)

Mixed Mode Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2)

Elevated Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2) 5.93E-06 5.58E-06 2.28E-08 7.12E-07 6.74E-07 5.77E-09 N/A N/A N/A Units Quarter 3 Quarter 4 Quarters 3 and 4 Year to Ending Date Bone Liver TBody Thyroid Kidney Lung GI-LLI mrem mrem mrem mrem mrem mrem mrem 2.11E-08 1.76E-07 1.76E-07 1.76E-07 1.76E-07 1.76E-07 1.76E-07 6.17E-09 2.20E-07 2.20E-07 2.20E-07 2.20E-07 2.20E-07 2.20E-07 2.73E-08 3.97E-07 3.97E-07 3.97E-07 3.97E-07 3.97E-07 3.97E-07 5.04E-08 6.77E-07 6.77E-07 6.77E-07 6.77E-07 6.77E-07 6.77E-07 Page 80 of 84

5.0 Total Dose from Uranium Fuel Cycle (40CFR190) 5.1 Regulatory Requirements ODCM 5.1 states in part that the annual (calendar year) dose or dose commitment to any MEMBER OF THE PUBLIC due to releases of radioactivity and to radiation from uranium fuel cycle sources shall be limited to less than or equal to 25 mrems to the whole body or to any organ, except the thyroid, which shall be limited to less than or equal to 75 mrems.

5.2 Demonstration of Compliance The requirements of 40CFR1 90 were met.

6.0 Meteorological Data ODCM 7.2.2.2 states in part:

The Radioactive Effluent Release Report shall include an annual summary of hourly meteorological data collected over the previous year.

This annual summary may be either in the form of an hour-by-hour listing of wind speed, wind direction, atmospheric stability, and precipitation (if measured) on magnetic tape; or in the form of joint frequency distributions of wind speed, wind direction and atmospheric stability.

In lieu of submission with the Radioactive Effluent Release Report, the licensee has the option of retaining this summary of required meteorological data on site in a file that shall be provided to the NRC upon request.

7.0 Program Deviations 7.1 Inoperable Liquid or Gaseous Effluent Monitoring Instrumentation 7.1.1 Regulatory Requirement ODCM 7.2.2.6 states in part that the report shall include deviations from the liquid and gaseous effluent monitoring instrumentation operability requirements included in Sections 2.1.1 and 3.1.1, respectively. The report shall include an explanation as to why the inoperability of liquid or gaseous effluent monitoring instrumentation was not corrected within the specified time requirement.

7.1.2 Description of Deviations The inoperability of liquid and gaseous effluent monitors was corrected within the specified time for this reporting period.

Page 81 of 84

7.2 Tanks Exceeding Curie Content Limits 7.2.1 Regulatory Requirements ODCM 7.2.2.6 states in part that the report shall include a description of the events leading to liquid holdup tanks or gas storage tanks exceeding the limits of Technical Specifications 5.5.12.

7.2.2 Description of Deviations There were no outdoor liquid hold-up tanks used for radioactive liquids during this reporting period. Limits for the gas storage tanks were not exceeded during this reporting period.

8.0 Changes to the Vogtle Electric Generating Plant Offsite Dose Calculation Manual (ODCM) 8.1 Regulatory Requirements ODCM 7.2.2.5 states in part that changes to the ODCM shall be submitted with the Radioactive Effluent Release Report. These changes may be due to changes in the radiological environmental monitoring program sampling locations as required by ODCM 4.1.1.2.3 or changes to dose calculation locations as required by ODCM 4.1.2.2.2. Land uses and dose calculation locations within five miles of VEGP must be determined by a land use census as required by ODCM 4.1.2.

8.2 Description of Changes There were changes made to the Vogtle Electric Generating Plant ODCM for the period January 1, 2003 through December 31, 2003. Revision 20 and 21 became effective in 2003. Changes were that Table 2-1 step 3A, Table 2-2 Stepl, and Table 3-2 Step 3A&B was updated.

The Land Use Census was conducted November 11, 2003 by Georgia Power Company Environmental Lab personnel. The results of the census for 2003 require no changes to the REMP sampling locations or to the dose calculation locations.

Page 82 of 84

9.0 Major Changes to Liquidi Gaseous, or Solid Radwaste Treatment Systems 9.1 Regulatory Requirements ODCM 7.2.2.7 states in part:

As required by Sections 2.1.5 and 3.1.6, licensee initiated MAJOR CHANGES TO RADIOACTIVE WASTE TREATMENT SYSTEMS (liquid and gaseous) shall be reported to the Nuclear Regulatory Commission in the Radioactive Effluent Release Report covering the period in which the change was reviewed and accepted for implementation.

Note 1: In lieu of inclusion in the Radioactive Effluents Release Report, this same information may be submitted as part of the annual FSAR update.

PCP 12.1 states in part:

Licensee major initiated changes to the solid radioactive waste treatment system shall be reported to the Nuclear Regulatory Commission in the Radioactive Effluent Release Report for the period in which the change was implemented.

Page 83 of 84

9.2 Description of Major Changes Gaseous Radwaste System There were no major changes to the gaseous radwaste systems in the 2003 assessment period.

Liquid Radwaste System Major changes to the liquid radwaste facilities are those that contribute to significant changes in release; i.e., either decreases or increases In release volume or activity/dose. This is to indicate that no major changes to the liquid radwaste systems occurred during the 2003 assessment period.

Solid Radwaste System There were no major changes to the solid radwaste systems in the 2003 assessment period.

Page 84 of 84