Remote Shutdown System 3.3.4 3.3 INSTRUMENTATION 3.3.4 Remote Shutdown System LCO 3.3.4 The Remote Shutdown System Functions shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3.

ACTIONS NOTES------------------------------------

1.

LCO 3.0.4 is not applicable.

2.

Separate Condition entry is allowed for each Function.

-____I-______--_--------------------------------------------------------------

CONDITION A.

One or more required Functions inoperable.

B.

Required Action and associated Completion Time not met.

REQUIRED ACTION A.1 Restore required Function to OPERABLE status.

B.l Be in MODE 3.

AND B.2 Be in MODE 4.

COMPLETION TIME 30 days 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 12 hours HBRSEP Unit No. 2 3.3-33 Amendment No. 176

Remote Shutdown System 3.3.4 SURVEILLANCE REQUIREMENTS SURVEILLANCE SR 3.3.4.1 Perform CHANNEL CHECK for each required instrumentation channel that is normally energized.

SR 3.3.4.2 Verify each required control circuit and transfer switch is capable of performing the intended function.

SR 3.3.4.3


NOTE--------------------

Neutron detectors are excluded from CHANNEL CALIBRATION.

Perform CHANNEL CALIBRATION for each required instrumentation channel.

SR 3.3.4.4 Perform TADOT of the reactor trip breaker open/closed indication.

FREQUENCY 31 days 18 months 18 months 18 months HBRSEP Unit No. 2 3.3-34 Amendment No. 176