Text

RCS Pressure, Temperature, and Flow DNB Limits 3.4.1 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.1 RCS Pressure, Temperature, and Flow Departure from Nucleate Boiling (DNB) Limits LCO 3.4.1 APPLICABILITY:

RCS DNB parameters for pressurizer pressure, RCS average temperature, and RCS total flow rate shall be within the limits specified in Table 3.4.1-1.

MODE 1.


--------NOTE Pressurizer pressure limit does not apply during:

a.

THERMAL POWER ramp > 5% RTP per minute; or

b.

THERMAL POWER step > 10% RTP.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

Pressurizer pressure or A.1 Restore DNB parameter(s) 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> RCS average to within limit.

temperature DNB parameters not within limits.

B.

RCS total flow rate>

B.1 Reduce THERMAL 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 99%, but < 100% of the POWER to < 98% RTP.

limit specified in the COLR.

AND B.2 Reduce the Power Range 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Neutron Flux - High Trip Setpoint below the nominal setpoint by 2% RTP.

(continued)

McGuire Units I and 2 3.4.1-1 Amendment Nos.21 9 & 201