License Amendment Request, Change to the Testing Requirements for Containment Spray Nozzles
ML040500425
Person / Time
Site: Calvert Cliffs  Constellation icon.png
Issue date: 02/12/2004
From: Vanderheyden G
Constellation Energy Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TAC MC0030, TAC MC0031
Download: ML040500425 (6)


Text

George Vanderheyden Vice President Calvert Cliffs Nuclear Power Plant Constellation Generation Group, LLC 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 410 495-4455 410 495-3500 Fax Constellation Energy Group February 12, 2004 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

SUBJECT:

Document Control Desk Calvert Cliffs Nuclear Power Plant Unit Nos. I & 2; Docket Nos. 50-317 & 50-318 License Amendment Request: Change to the Testing Requirements for Containment Spray Nozzles

REFERENCES:

(a)

Letter from Mr. George Vanderheyden (CCNPP) to Document Control Desk (NRC), dated July 14, 2003, "License Amendment Request:

A Change to the Testing Requirements for Containment Spray Nozzles" (b)

Letter from Mr. Guy S. Vissing (NRC) to Mr. George Vanderhayden (CCNPP), undated, "Calvert Cliffs Nuclear Power Plant, Unit Nos. I and 2

- Request for Additional Information Related to the Changing of Test Requirements for Containment Spray Nozzles (TAC Nos. MC0030 and MC0031)

(c)

Letter from Mr. George Vanderheyden (CCNPP) to Document Control Desk (NRC), dated December 5, 2003, "License Amendment Request:

Change to the Testing Requirements for Containment Spray Nozzles; Response to Request for Additional Information" Reference (a) proposed a change to Technical Specification Surveillance Requirement 3.6.6.8.

Reference (c) responded to questions posed by Reference (b). This letter modifies the change proposed in Reference (a).

Instead of deleting the surveillance requirement for testing the containment spray nozzles, as proposed in Reference (a), we are now proposing to modify the surveillance requirement to require verification that spray nozzles are unobstructed following maintenance that could result in nozzle blockage (loss of Foreign Material Exclusion control). This change is shown on the attached markup of Surveillance Requirement 3.6.6.8 (Attachment 1).

The final Technical Specification page is provided in Attachment (2).

Appropriate details concerning the Surveillance Requirement will be added to the Technical Specification Bases.

The safety analysis and determination of significant hazards previously presented in Reference (a) remain valid for this proposed change.

'Aool

Document Control Desk February 12, 2004 Page 2 Should you have questions regarding this matter, we will be pleased to discu them with you.

Very tru STATE OF MARYLAND COUNTY OF CALVERT

TO WIT:

1, George Vanderheyden, being duly sworn, state that I am Vice President - Calvert Cliffs Nuclear Power Plant, Inc. (CCNPP), and that I am duly authorized to execute and file this License Amendment Request on behalf of CCNPP. To the best of my knowledge and belief, the statements contained in this document are true and correct. To the extent that these statements are not based on y personal knowledge, they are based upon information provided by other CCNPP employees and/or c nsultants. Such information has been reviewed in accordance with company practice and I believ to reliable.

Subscribed and sworn before me a Notary Public in and for the State of Maryland and County of

,5.

Y~a V

this _____

day o 2004.

WITNESS my.14and and Notarial Seal:

M Coisin_

Epe My Commission Expires:

Notary Pu WmcZa'~ a00r I

Date GV/EMT/bjd Attachments:

(1)

Technical Specification Marked-up Page -- Surveillance Requirement 3.6.6.8 (2)

Final Technical Specification Page cc:

J. Petro, Esquire J. E. Silberg, Esquire R. J. Laufer, NRC G. S. Vissing, NRC H. J. Miller, NRC Resident Inspector, NRC R. 1. McLean, DNR

ATTACHMENT (1)

TECHNICAL SPECIFICATION MARKED-UP PAGE --

SURVEILLANCE REQUIREMENT 3.6.6.8 Calvert Cliffs Nuclear Power Plant February 12,2004

Containment Spray and Cooling Systems 3.6.6 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.6.6.8 Verify each spray nozzle is unobstructed.

Itlo w ',l

mrck, Hon Gv

(__ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _l__ _ _ _ _

ro_5_

tHu_

4 CALVERT CLIFFS CALVERT CLIFFS

- UNIT 1

- UNIT 2 3.6.6-4 Amendment No.

Amendment No.

227 201

ATTACHMENT (2)

FINAL TECHNICAL SPECIFICATION PAGE 3.6.6-4 Calvert Cliffs Nuclear Power Plant February 12, 2004

Containment Spray and Cooling Systems 3.6.6 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.6.6.8 Verify each spray nozzle is unobstructed.

Following maintenance that could result in nozzle blockage CALVERT CLIFFS -

UNIT 1 CALVERT CLIFFS -

UNIT 2 3.6.6-4 Amendment No.

Amendment No.