SVPLTR 04-0001, Final Third 10-Year Interval Inservice Inspection (ISI) Summary Report

From kanterella
(Redirected from ML040490531)
Jump to navigation Jump to search

Final Third 10-Year Interval Inservice Inspection (ISI) Summary Report
ML040490531
Person / Time
Site: Dresden Constellation icon.png
Issue date: 02/09/2004
From: Bost D
Exelon Generation Co, Exelon Nuclear
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
SVPLTR #04-0001
Download: ML040490531 (40)


Text

Exekrnsa Exelon Generation www.exeloncorp.com Nuclear Dresden Generating Station 6500 North Dresden Road Morris, IL 60450-9765 Tel 815-942-2920 February 9, 2004 SVPLTR #04-0001 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Dresden Nuclear Power Station, Unit 2 Facility Operating License No. DPR-19 NRC Docket No. 50-237

Subject:

Final Third 10-Year Interval Inservice Inspection (ISI) Summary Report

References:

1) Letter from P. Swafford, (Exelon Generation Company, LLC) to U. S. NRC, "Inservice Inspection (ISI) Summary Report Fall 2001 Inservice Inspection Period," dated February 5, 2002
2) Letter from L. W. Rossbach (U. S. NRC) to 0. D. Kingsley (Exelon Generation Company, LLC); "Exemption from the Requirements of 10 CFR 50.55a(g)(6)(ii)(A)(2), Inservice Examination of the Reactor Pressure Vessel," dated September 28, 2001
3) Letter from A. J. Mendiola (U. S. NRC) to J. L. Skolds (Exelon Generation Company, LLC), Relief Request CR-25 for Third 10-Year Inservice Inspection Interval," dated July 1, 2003 Enclosed is the Dresden Nuclear Power Station (DNPS) Unit 2 final Inservice Inspection (ISI)

Summary Report for ISI examinations and repair/replacement activities conducted since the last report, (Reference 1) for the Third 10-Year Interval. This report is submitted in accordance with the requirements of American Society of Mechanical Engineers (ASME)

Boiler and Pressure Vessel Code Section XI, "Rules for Inservice Inspection of Nuclear Power Plant Components," 1989 Edition, Article IWA-6200, "Requirements."

The Unit's third 10-year ISI Interval began on March 1, 1992, and was completed on September 30, 2003. All scheduled ASME Section XI examinations were completed prior to September 30, 2003, with the exception of Examination Category B-A reactor vessel shell welds and Examination Category B-O control rod drive housing welds. Approval to delay both groups of welds was provided by the NRC in References 2 and 3 respectively. Examination ASSQO-6

February 9, 2004 U. S. Nuclear Regulatory Commission Page 2 Category B-A and B-O examinations were completed during the Unit 2 refueling outage (D2R18) which began on October 14, 2003, and was completed on November 11, 2003.

Should you have any questions concerning this letter, please contact Mr. Jeff Hansen, Regulatory Assurance Manager, at (815) 416 - 2800.

Resp'ectfully, Danny G4'ost Site Vi President.

Dresden Nuclear Power Station Attachment cc:

Regional Administrator - Region Ill NRC Senior Resident Inspector, Dresden Station

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 October 2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Table of Contents Introduction Form NIS-1 Owners Report for Inservice Inspections Scope of Inspection Abstract of ISI and Augmented Examinations Abstract of Corrective Measures Abbreviations Repairs and Replacements Since the Preceding Summary Report I

1l Ill lV V

1

Exelon Generation Company (EGC, LLC)

October 2003 Inservice Inspection 200 Exelon Way, Kennett Square, PA, 19348 Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Section I Introduction The eighteenth Inservice Inspection (ISI) of Dresden Unit 2 was performed during the D2R18 outage which began on October 14, 2003 and was completed on November 11, 2003. This was the final refueling outage of the unit's 3rd 10-year Inservice Inspection Interval which commenced on March 1, 1992. The third Inspection period commenced on October 1, 1999 and was completed on September 30, 2003. All of the scheduled ASME Section Xi examinations were completed on-line prior to September 30, 2003 with the exception of Examination Category B-A reactor vessel shell welds and Examination Category B-O CRD housing welds. The reactor vessel shell welds were completed during the D2R18 refuel outage in accordance with a schedular exemption. The CRD housing welds were completed during D2R1 8 in accordance with a relief request. This report summarizes the reactor vessel weld and CRD housing weld examinations completed during D2R1 8 and on-line examinations which were completed since the previous Unit 2 Summary Report (dated February 5, 2002).

The Authorized Nuclear Inservice Inspector's (ANII) services were provided by The Hartford Steam Boiler Inspection and Insurance Company of Connecticut. The ANII reviewed procedures, personnel qualifications, instrument and material certifications, and examination results.

All examinations were performed in accordance with the Dresden Station ISI Program, Dresden Station Technical Requirements Manual, and the ASME Boiler and Pressure Vessel Code, Section Xl, 1989 Edition.

A list of abbreviations used throughout this report can be found in Section IV of this report.

2

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules

1. Owner Exelon Generation Company (EGC, LLC), 200 Exelon Way, Kennett Square, PA, 19348 (Name and Address of Owner)
2. Plant Dresden Nuclear Power Station, 6500 N. Dresden Road, Morris, IL 60450 (Name and Address of Owner)
3. Plant Unit 2
4. Owner Certificate of Authorization (if required)

N/A

5. Commercial Service Date 06-09-70
6. National Board Number for Unit N-137
7. Components Inspected See Section 11 of this report (report is 38 total pages).

Component or Manufacturer Manufacturer State or National Appurtenance Or Installer or Installer Province No.

Board No.

Serial No.

Reactor Vessel Babcock & Wilcox, 610-0098-51-52 B0082800 N-137 Barberton, Ohio Class I & 2 Systems General Electric-APED N/A N/A N/A Morris, IL Note: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (I) size is 8/2 in. x I1 V2 in., (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

3

FORM NIS-1 (Back)

8. Examination Dates:

01/22/2002 to 10/31/2003

9. Inspection Period Identification:

3rd Period - From 10/1/1999 to 09/30/2003

10. Inspection Interval Identification:

3rd Interval - From 3/1/1992 to 09/30/2003*

  • Category B-A examinations were completed after the stated date in accordance with a scheduler exemption.
  • Category B-O examinations were completed after the stated date in accordance with a relief request.
11. Applicable Edition of Section XI 1989 Addenda N/A
12. Date/Revision of Inspection Plan:

04/01/2003 Revision 8

13. Abstract of Examination and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Attached Sections II and III.
14. Abstract of Results of Examinations and Tests. See Attached Sections II and 111.
15. Abstract of Corrective Measures. See Attached Sections II and III.

We certify that a) the statement made in this report are correct, b) the examinations and tests meet Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the ASME Code,Section XI.

Certificate of Authorization No. (if applicable)

N/A Expiration Date N/A Date 1-2 20 04 Signed Exelon Nuclear Dresden Nuclear Power Station.

By

Lg Dresden Station ISI Coordinator Owner CERTIFICATE OF INSERVICE INSPECTION I, the under signed, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois And employed by Hartford Steam Boiler of CT Have inspected the components described in the Owner's Report during the period 01/22/2002 To 10/31/2003

, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_____________________________ wCommissions NB7742NISB, IL932 Inspector's signature National Board, State, Province, and Endorsements Date 20 04 4

Exelon Generation Company (EGC, LLC)

October 2003 Inservice Inspection 200 Exelon Way, Kennett Square, PA, 19348 Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Section 11 Scope of Inspection Abstract of Is[ and Augmented Examinations ISI and Augmented Examinations Table A contains a list of components examined on-line prior to completion of the 3rd 0-Year Inservice Inspection Interval and Examination Category B-A and B-O examinations performed during the D2R18 refuel outage. These examinations are in accordance with the Dresden Station ISI Program, Dresden Station Technical Requirements Manual, and the ASME Boiler and Pressure Vessel Code, Section Xi, 1989 Edition. Those items which were examined and met the acceptance standards of ASME Section Xi are identified as "Acceptable" under the results column. Those items that required further evaluation are identified with "Section III" in the results column and are further discussed in Section III of this report.

Reactor Vessel Weld (Category B-A) Examinations The Unit 2 reactor vessel shell welds are examined as required by 1 OCFR50.55(a) and ASME Section Xl. These welds are addressed under Examination Category B-A, Item numbers B1.1 1, Circumferential Shell Welds; Item B1.12, Longitudinal Shell Welds; and Item B1.30, Head to Flange Weld. Two relief requests are associated with these inspections.

First, relief was requested, and subsequently granted, from requirements to examine welds under item B1.11. The technical basis for this request is established in BWRVIP-05.

Second, a schedule exemption was requested, and subsequently approved, to allow performance of these inspections over an additional refueling outage which was after the scheduled completion of the 3rd 10-year Inservice Inspection Interval. Otherwise, the entire inspection would have been required during D2R17, the last outage in the third inspection interval. The basis of this request is to allow the station to take advantage of a new inspection technology, the AIRIS 21 system, to achieve increased coverage without significantly impacting the outage.

Control Rod Housing Weld (Category B-O) Examinations The Unit 2 control rod housing welds are examined as required by ASME Section Xl. These welds are addressed under Examination Category B-O, Item number B4.10, Welds in CRD Housings. In accordance with an authorized relief request, these welds were nspected during D2R1 8 which was after the scheduled completion of the 3rd 1 0-year Inservice Inspection Interval.

5

Exelon Nuclear P.O. Box 805379, Chicago, IL 60680-5379 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 October 2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 6-9-72 Section 11 Scope of Inspection Abstract of ISI and Augmented Examinations Current Interval Status The percentages listed in the table below represent the status of inspections for the 3d inservice inspection interval. This report documents completion of the 3r 1 0-year Inservice Inspection Interval.

Examination Deferral is permissible in Inspected In accordance Category accordance with Table with Inspection Program B IWX-2500-1 B-A 100%/O 100%

B-D N/A 100%

B-E 100%

N/A B-G-1 100%

N/A B-G-2 100%'

100%

B-M-1 100%

N/A B-M-2 100%'

N/A B-N-1 N/A 100%

B-N-2 100%

N/A B-0 100%

N/A C-A N/A 100%

C-B N/A 100%

C-C N/A 100%

D-B N/A 100%

F-A N/A 100%

R-A NIA 100%

1. Percentage represents components subject to Inspection only when disassembled for maintenance, repair, or volumetric examination.

6

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 October2003 nservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Section 11 Scope of Inspection Abstract of ISI and Auamented Examinations ilateYrj4nttm

@ugmL~~ystenpone C~itix6Cedlt'

Results, B-A B1.12 N/A RPV RPV SHELL 2-SC1C-VERT LONG UT Xi Acceptable B-A B1.12 N/A RPV RPV SHELL 2-SC2A-VERT LONG UT Xl Acceptable B-A B1.12 N/A RPV RPV SHELL 2-SC2B-VERT LONG UT Xi Acceptable B-A B1.12 N/A RPV RPV SHELL 2-SC2C-VERT LONG UT Xi Acceptable B-A B1.12 N/A RPV RPV SHELL 2-SC3A-VERT LONG UT Xi Acceptable B-A B1.12 N/A RPV RPV SHELL 2-SC3B-VERT LONG UT Xi Acceptable B-G-1 B6.30 N/A RPV RPV UPP HD HD STUDS RMVD (92)

FLGBLT MT Xi Acceptable B-M-1 B12.40 N/A MS 3001B-6 ERV-2-203-3B VLVWLD RT Xl Acceptable B-O 614.10 N/A RPV RPV LWR HD B4-0615-2 P-P PT Xl Acceptable B-O B14.10 N/A RPV RPV LWR HD Hi-3003-2 P-P PT Xl Acceptable B-O B14.10 N/A RPV RPV LWR HD K15-3859-2 P-P PT Xl Acceptable B-O B14.10 N/A RPV RPV LWR HD M2-4607-2 P-P PT Xl Acceptable C-A C1.30 N/A LPCI HTEX 2B-1503 2-1503B-2 TBSHT-SHL MT Xi Acceptable C-B C2.31 N/A ECCS 1501-20 20-10 SDL-SHL MT Xi Acceptable C-B C2.31 N/A ECCS 1501-20 20-12 SDL-SHL MT Xl Acceptable C-B C2.33 N/A ECCS 1501-20 20-11 NOZ-SHL VT-2 Xi Acceptable C-B C2.33 N/A ECCS 1501-20 20-5 NOZ-SHL VT-2 Xi Acceptable C-B C2.33 N/A ECCS 1501-20 20-7 NOZ-SHL VT-2 Xi Acceptable C-B C2.33 N/A ECCS 1501-20 20-9 NOZ-SHL VT-2 Xi Acceptable C-B C2.33 N/A LPCI 1508-18 2-1503B-N3-1 NOZ-SHL VT-2 Xi Acceptable C-B C2.33 N/A LPCI 1509-18 2-1503B-N4-1 SHL-NOZ VT-2 Xl Acceptable C-C C3.1 0 C-C C3.10 C-C C3.10 C-C C3.10 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A LPCI HTEX 2A-1503 LPCI HTEX 2A-1503 LPCI HTEX 2B-1503 LPCI HTEX 2B-1503 CRD 031 8B-20 CS 1401-16 ECCS 1501-24 ECCS 1501-24 ECCS 1501-24 ECCS 1501-24 ECCS 1501-24 ECCS 1501-24 HPCI 2302-16 LPCI 1502-24 LPCI 1504-18 LPCI 1534-18 M-11 64D-577 M-1 164D-580 M-1 1 64D-578 M-1 1 64D-579 M-1152D-1 251 M-3203-05 M-3202-03 M-3202-04 M-3202-05 M-3202-06 M-3202-07 M-3202-08 M-3205-06 M-3203-06 M-321 3-02 M-321 4-42 IWA IWA IWA IWA IWA IWA IWA IWA IWA IWA IWA IWA IWA IWA IWA IWA MT AD MT AD L MT X BL MT Xi MT Xi MT Xi MT Xi MT Xl MT Xl MT Xl MT Xi MT Xl MT Xl MT Xl MT Xi MT Xi Acceptable See Section III See Section III Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable 7

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 October 2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Section 11 Scope of Inspection Abstract of ISI and Augmented Examinations v

ife~d jt em m-e,

C C-C C3.30 N/A LPCI PMP 2B-1502 M-1164D-572 IWA MT Xi Acceptable C-H C7.XX N/A CRD TEST BLOCK 2RC02 N/A VT-2 Xl Acceptable C-H C7.XX N/A CS TEST BLOCK 2CS01 N/A VT-2 Xl Acceptable C-H C7.XX N/A ECCS TEST BLOCK 2EC01 N/A VT-2 Xi Acceptable C-H C7.XX N/A ECCS TEST BLOCK 2EC02 N/A VT-2 Xi Acceptable C-H C7.XX N/A HPCI TEST BLOCK 2HP02 N/A VT-2 Xl Acceptable C-H C7.XX N/A LPCI TEST BLOCK 2LP01 N/A VT-2 Xl Acceptable C-H C7.XX N/A LPCI TEST BLOCK 2LP02 N/A VT-2 Xi Acceptable C-H C7.XX N/A LPCI TEST BLOCK 2LP03 N/A VT-2 Xi Acceptable C-H C7.XX N/A LPCI TEST BLOCK 2LP04 N1A VT-2 Xi Acceptable C-H C7.XX N/A SBLC TEST BLOCK 2SC02 N/A VT-2 Xl Acceptable D-B D2.IA N/A CCSW 1514-16 M-1164D-150 IWA VT-3 Xl Acceptable D-B D2.IA N/A ISCO 2-1302 M-1163D-553 IWA VT-3 Xl Acceptable D-B D2.IA N/A ISCO 2-1302 M-1163D-554 IWA VT-3 Xl Acceptable D-B D2.1A NIA ISCO 2-1302 M-1163D-555 IWA VT-3 Xi Acceptable D-B D2.XX N/A CCSW TEST BLOCK 2CC01 N/A VT-2 Xi See Section III D-B D2.XX N/A DGSW TEST BLOCK 2DG01 N/A VT-2 Xi Acceptable D-B D2.XX N/A DGSW TEST BLOCK 2DG03 N/A VT-2 Xi Acceptable D-B D2.XX N/A ISCO TEST BLOCK 21C02 N/A VT-2 Xi Acceptable F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.20 N/A F-A F1.30 N/A F-A F1.30 N/A F-A F1.30 N/A F-A F1.30 N/A F-A F1.30 N/A F-A F1.30 N/A F-A F1.30 N/A F-A F1.30 N/A CRD CRD CS CS ECCS ECCS HPCI HPCI HPCI HPCI HPCI LPCI LPCI CCSW CCSW CCSW CCSW CCSW CCSW CCSW CCSW 0385-8 04088-6 1402-16 1404-12 1501-20 1501-24 2302-16 2304-14 2304-14 2304-14 2304-14 1504-16 1521-16 1510-16 1510-16 1510-16 1512-24 1514-16 1514-16 1514-16 1514-16 M-1152D-1 034 M-1152D-1051 M-3204-03 (1/2)

M-3209-04 M-3230-02(X-303A)

M-3202-19 M-3205-10 M-1151 D-146 M-1 151 D-282 M-1151D-85 M-1151 D-86 M-3213-04 M-3214-13 M-1164D-287 M-1 164D-84 M-1 164D-87 M-1 164D-52 M-1164D-133 M-1164D-146 M-1 164D-265 M-1 164D-267 CL 2 SUP CL2SUP CL2SUP CL2SUP CL 2 SUP CL 2 SUP CL 2 SUP CL 2 SUP CL 2 SUP CL 2 SUP CL 2 SUP CL 2 SUP CL2SUP CL 3 SUP CL3SUP CL 3 SUP CL 3 SUP CL 3 SUP CL 3 SUP CL 3 SUP CL 3 SUP VT-3 Xl VT-3 Xi VT-3 Xl VT-3 Xl VT-3 Xl VT-3 Xl VT-3 Xl VT-3 Xl VT-3 Xl VT-3 Xl VT-3 Xl VT-3 Xi VT-3 Xi VT-3 Xl VT-3 XI VT-3 Xi VT-3 Xi VT-3 Xi VT-3 Xi VT-3 Xl VT-3 Xl Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable Acceptable See Section III Acceptable 8

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 October 2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Section 11 Scope of Inspection Abstract of ISI and Augmented Examinations W~augrientyl System pfle o ntd.

t.

F-A F1.30 N/A CCSW 1514C-10 M-1164D-62 CL3SUP VT-3 Xi Acceptable F-A F1.30 N/A DGSW 3930-8 M-1162D-113 CL3SUP VT-3 Xi Acceptable F-A F1.30 N/A DGSW 3930-8 M-11 62D-1 62 CL 3 SUP VT-3 Xi Acceptable F-A F1.40 N/A CCSW PMP 2A-1501-44 2A-1501-44 CL3 SUP VT-3 Xi Acceptable F-A F1.40 N/A DGSW PMP 2-3903B 2-3903B CL 3 SUP VT-3 Xl Acceptable F-A F1.40 N/A HPCI PMP 2-2302-1 2-2302-1 CL 2 SUP VT-3 Xi Acceptable F-A F1.40 N/A LPCI PMP 2B-1502 M-1 164D-572 CL2SUP VT-3 Xi Acceptable R-A R1.1 1 N/A HPCI 2306-24 24-17 P-EL UT-E Xl Acceptable R-A R1.20 N/A CS 1404-10 10-61 P-P UT-E Xi Acceptable R-A R1.20 N/A ECCS 1501-24 24-1 P-TEE UT-E Xl Acceptable R-A R1.20 N/A ECCS 1501-24 24-3 TEE-P UT-E XI Acceptable R-A R1.20 N/A ECCS 1501-24 24-44 P-P UT-E Xl Acceptable R-A R1.20 N/A ECCS 1501-24 24-46 P-P UT-E Xi Acceptable R-A R1.20 N/A ECCS 1501-24 24-49 P-P UT-E Xl Acceptable R-A R1.20 N/A ECCS 1501-24 24-50 P-P UT-E Xi Acceptable R-A R1.20 N/A LPCI 1502-24 24-3 P-EL UT-E Xi Acceptable R-A R1.20 N/A LPCI 1502A-14 14-2 P-EL UT-E Xl Acceptable R-A R1.20 N/A LPCI 1504-10 10-33 TEE-VLV UT-E Xl Acceptable R-A R1.20 N/A LPCI 15078-14 14-2 P-EL UT-E Xi Acceptable R-A R1.20 N/A LPCI 1509-10 10-37 TEE-P UT-E Xl Acceptable N/A N/A N/A CS 1404-12 12-32 P-EL UT SU Acceptable 9

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 October2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Section III Abstract of Corrective Measures The findings and subsequent measures taken to correct the findings demonstrate that all components examined are functional and in compliance with the Dresden Station ISI Program, Dresden Station Technical Requirements Manual, the ASME Boiler and Pressure Vessel Code, Section Xl, 1989 Edition.

The following is a summary of corrective measures taken as a result of examination findings.

10

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 October 2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Section III Abstract of Corrective Measures

'Cte'oyXltemi-ur-ren sw;me C-C C3.10 LPCI HTEX 2A-1 503 M-1 164D-580 IWA During MT examination of 2A LPCI heat exchanger IWA M-1164D-580, two linear Indications were discovered.

Condition Report 181014 was Initiated to document the as-found condition. Weld repairs were performed under Work Order 415749. Welds were examined after repairs were performed and found acceptable. Since all similar welded attachments associated with the 2A and 2B LPCI heat exchangers were examined, no additional expansion was performed.

C-C C3.10 LPCI HTEX 2B-1 503 M-1 164D-578 IWA During MT examination of 2B LPCI heat exchanger WA M-1 164D-578, two linear Indications were discovered.

Condition Report 176040 was Initiated to document the as-found condition. Weld repairs were performed under Work Order 415749. Welds were examined after repairs were performed and found acceptable. Since two welded attachments on the 2B LPCI heat exchanger were initially examined, two welded attachments associated with the 2A LPCI heat exchanger were expanded to.

D-B D2.XX CCSW TEST BLOCK 2CC01 NA During the system pressure test, leakage was discovered In a CCSW vault cooler standpipe and CCSW pump discharge elbow. Initiated condition reports 91463 and 94532, respectively, to document discrepancy. Repairs were made under work orders 400171 and 407488, respectively, reinspected and found acceptable.

F-A F1.30 CCSW 1514-16 M-1 164D-265 CL 3 SUP During VT-3 Inspection of support M-1 164D-265 a drawing discrepancy was discovered. Condition report 139424 was generated to address the discrepancy. The as-found condition was found acceptable and the drawing revised.

No futher action was required.

11

Exelon Generation Company (EGC, LLC)

October 2003 Inservice Inspection 200 Exelon Way, Kennett Square, PA, 19348 Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Section IV Abbreviations Augment GL88-01 Generic Letter 88-01 Exam, Weld Category Exam MT Magnetic Particle PT Liquid Penetrant RT Radiograph UT Ultrasonic UT-E Ultrasonic-Risk ISI Expanded Volume VT-1, 2, or 3 Visual Examination Exam Selection AD Additional Examination (expansion)

AG Augmented Requirement BL Baseline OTHR Other SU Successive Examination Xi ASME Section Xl Requirement System CCSW Containment Cooling Service Water CRD Control Rod Drive CS Core Spray DGSW Diesel Generator Service Water ECCS Emergency Core Cooling System Ring Header FW Feedwater HPCI High Pressure Coolant Injection ISCO Isolation Condenser LPCI Low Pressure Coolant Injection MS Main Steam RHS Reactor Head Spray RPV Reactor Pressure Vessel RR Reactor Recirculation RVBD Reactor Vessel Bottom Drain SBLC Standby Liquid Control SDC Shutdown Cooling 12

Exelon Generation Company (EGC, LLC)

October 2003 Inservice Inspection 200 Exelon Way, Kennett Square, PA, 19348 Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Section IV Abbreviations Type BELLOW Bellows BLTCONN Bolted Connection BPC Branch Pipe Connection BPCS Branch Pipe Connection Saddle CAP Pipe Cap CL Class COND Condenser CRO Cross EL Elbow ELS Elbow Longitudinal Seam F

Flued Head FLG Flange FLGBLT Flange Bolt FLS Fitting Longitudinal Seam GASKET Gasket HTEX Heat Exchanger IWA Integral Welded Attachment MBARR Moisture Barrier NIR Nozzle Inner Radius NOZ Nozzle P

Pipe PG Penetration Guide PLS Piping Longitudinal Seam PMP Pump PMPBLT Pump Bolting RED Reducer REDE Reducing Elbow RPV Reactor Pressure Vessel SDL Saddle SE Safe-end SEAL Seal SHL Shell SNB Snubber SUP Support SURF Containment Surface SWC Socket Welded Coupling SWCP Socket Welded Pipe Cap SWE Socket Welded Elbow SWF Socket Welded Flange SWP Sweep-O-Let, Weld-O-Let, Etc.

SWR Socket Welded Reducer SWT Socket Welded Tee SWV Socket Welded Valve TBSHT Tubesheet TEE Tee 13

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 October 2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Section IV Abbreviations VB Vacuum Breaker VLV VLVBLT VLVWLD Valve Valve Bolting Valve Weld 14

Exelon Generation Company (EGC, LLC)

October 2003 Inservice Inspection 200 Exelon Way, Kennett Square, PA, 19348 Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 Section V Repairs and Replacements Since the Preceding Summary Report Several ASME Section Xi repairs and replacements have taken place at Dresden Unit 2 since the previous summary report was issued. A review of the Dresden Station Section Xi Repair Program Log was conducted in order to identify the various repairs and replacements. Although not required per IWA-6210(c), Class 3 repairs and replacements are also included in this report.

Copies of the NIS-2 forms associated with all of the Section Xl repairs and replacements conducted since the previous summary report have been included in this section. The NIS-2 forms provide an abstract of the repairs and replacements and outline the examinations and tests performed in conjunction with them. Code Data Reports are not included in this report, but are available for review at Dresden Station.

A listing of NIS-2 forms is included in this section in order of repair/replacement plan number followed by the associated work request number.

15

Exelon Generation Company (EGC, LLC) 200 Exelon Way, Kennett Square, PA, 19348 Dresden Nuclear Power Station 6500 N. Dresden Road, Morris, IL 60450 October 2003 Inservice Inspection Unit No. 2; National Board No. N-137 Commercial Service Date: 06-09-72 Section V Repairs and Replacements Since the Preceding Summary Report gh_

rk~~~~~~~~~~~~~~,-

Reuest.-sel 2-01-067 2-02-004 2-02-006 2-02-014 2-02-016 2-02-018 2-02-019 2-02-022 2-02-023 2-02-024 2-02-025 2-03-011 3-02-021 3-02-022 3-02-066 3-02-079 3-02-080 3-02-081 00370865-01 00400171-02 00407488-01 00411655-01 00421878-05 00476711-07 00493780-01 00477343-01 00477343-05 00477344-01 00477344-02 Multiple-01 00408844-05 00408844-06 99213921-01 00442789-01 00443812-01 00433283-01 16

FORMS NIS-2 OWNER'S REPORT FOR REPAIR OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl

1. Owner: Exelon Cormoration. LLC.....................

\\.

wv}

P.O. Box 805379. Chicago IL. 60680-5379 (Address)

2. Plant: Dresden Nuclear Power Station (Name) 6500 North Dresden Road. Morris IL.. 60450 (Address)

Date:

2-4-2002 Sheet: 1 Of I Unit:

2 PLAN 2-01-067 WO 00370865-01

3. Work Performed By:

Same as Above Coma -

Ah ".-J (Name)

(Address)

Repair Organization P.O. No., Job No. etc.

sae O..

Hove~

4. Identification of System:

1500 (LPCI)

5. (a) Construction Code USAS B31.1.0 1967 Edition, NO Addenda, Code Cases NONE (b)

Edition of Section Xl used for Repair/Replacement 1989 Edition, NO Addenda, CodeCases NONE

6. Identification of Components Repaired or Replaced and Replacement Components Name of Name of Mfrs.

Nat Other Year

Repair, Code Component Manufacturer Serial No.

Brd ID Built Replaced or Stamped l_________________

No Replacement Yes/No Support M-3214-17 N/A N/A NA M-3214-14 N/A Replacement No Cat ID 1200164, UTC-2623398

7. Description of work: Installed shims between camn and shear lugs.
8. Test Conducted: Hydrostatic [

Pneumatic [ I Nominal Operating Pressure [

Not Applicable fi Test Pressure N/A psig Test Temperature N/A F

9. Remarks: Acceptable VT-3 examination was performed.

Certificate of Compliance We certify that the statements made In this report are correct and this REPAIR/REPLACEMENT Conforms to Section XI of the ASME Code.

Signed:

ISI COORDINATOR I.

.2002 Van';

-(071-or Owner's Designee)

(Tilue)

(Date)

Certificate of Inspection I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Pro nce of Illinois. employed by Hartford Steam Boiler of CT having inspected the REPAIR/REPLACEMENT described in this report on 4 j2:%,

20LAZ and state to the best of my knowledge and belief, this repair or replacement has been constructed In accordance with Section XI of the ASME Code. By signing this certificate neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the repair or replacement described In this report Furthermore, neither the inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Date:

A S7 Inspector Robert T. Rainey

- A9" 7 *WA Commissions:

1L932. NB7742NISB (State or Province, National Board)

FORM NIS-2 OWNER'S REPORT FOR REPAIR OR REPLACEMENTS As Required by the Provisions of ASNIE Code Section XI

1. Owner: Exelon Nuclear (Name)

P.O. Box 805379. Chicano IL. 60680-5379 (Address)

2. Plant: Dresden Nuclear Power Station (Name) 6500 North Dresden Road. Morris IL., 60450 (Address)

Date:

3-28-2002 Sheet: 1 Of 1 Unit:

3 (PLAN 2-02-004)

W/O 400171-02

3. Work Performed By:

Same as Above IKI-m-%

~

J'1111 OS Same as Above (Address)

Repair Organization P.O. No., Job No. etc.

4. Identification of System:

1500 (CCSW Vault Coolers)

5. (a) Construction Code USAS B31.1.0 (b) Edition of Section Xi used for Repair/Replacement 1967 Edition, NO Addenda, Code Cases N-416-1 1989 Edition, NO Addenda, Code Cases NONE
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Manufacturer Mfrs.

Serial No.

Nat Brd No Other ID Year Built

Repair, Replaced or Replacement Code Stamped Yes/No CCSW Room Cooler Aerofin N/A N/A EPN 2-5700-30A Unknown Replaced No Standpipe CCSW Room Cooler Aerofin Cat ID 9251 N/A EPN 2-5700-30A Unknown Replacement No Standpipe UTC 2002422 Flange Unknown Unknown N/A Une 2-15100B-2' Unknown Replaced No and 2-151 01 B-2' Flange Unknown Cat ID 40721 N/A Une 2-15100B-2" Unknown Replacement No UTC 2072548 and 2-15101 B-2' SMLS Pipe Unknown Unknown N/A Une 2-15100B-2" Unknown Replaced No and 2-15101 B-2' SMLS Pipe Unknown Cat ID 24507 N/A Une 2-151 00B-2' Unknown Replacement No UTC 2632630 and 2-15101 B-2' Elbow Unknown Unknown N/A

'Une 2-151 00B-2' Unknown Replaced No I

and 2-151 01 B-2' (t

ll11 Elbow Unknown Cat ID 7375 UTC 2018123 N/A Une 2-151 00B-2" and 2-151 01 B-2' Unknown Replacement No

7. Description of work: Replaced tube bundle stand pipes and associated supply and discharge piping.
8. Test Conducted: Hydrostatic [ ]

Pneumatic [)

Nominal Operating Pressure [ X]

Not Applicable []

Test Pressure 190 psig Test Temperature Ambient F

9. Remarks:

Certificate of Compliance C

We certify that the statements made In this report are correct and this REPAIRREPLACEMENT Confoms to Section XI of the ASME Code.

Signed:

ISI COORDINATOR t3

.20-P.v l

a eGw~7ei'or~wor's Designee)

(Title)

(Date)

Certificate of Inspection l

~~~~~~~~~~~~~Certificate of Inspection I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois, employed by The Hartford SteRn Boiler Inspection & Insurance Company of Connecticut having inspected the REPAIR/REPLACEM ENT described In this report on V

20_V7:end state to the best of my knowledge and belief, this repair or replacement has been constructed In accordance with Section Xl of the ASME Code. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the repair or replacement described In this report. Furthermore, neither the inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of akind rising frT or connected with this Inspection.

Date:

S GdInspector:

Commissions:

11-932. NB7742NISB Inspector:

(State or Province, National Board)

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Exelon Generation Company (EGC, LILC)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Date:

Sheet Unit 11-13-2003 1

of 1

2 Work Order 00407488-01 (R/R Plan 2-02-006)

3. Work Performed by Same as Above Same As Above Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp NIA Authorization No.

N/A Expiration Date N/A Address

4. Identification of System 1500, Containment Cooling Service Water, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, No Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1989
Edition, No
Addenda, N-416-1 Code Case
6. Identificatinn of Cnmnnnents ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes or No) 2C CCSW 8 300# Weld Neck Flange Unknown Unknown N/A N/A Unknown Corrected No

7. Description of work Through wall leak repaired by flaw removal and weld reair
8. Tests Conducted:

Hydrostatic I Pneumatic [

Nominal Operating Pressure [X Exempt [

Other [ ]

Pressure 200 psi Test Temp.

60 OF

9. Remarks Pressure test performed under WO 407488-03 after weld repair.

Applicable Manulacturers Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorizatign No.

NIA Expiration Date NIA Signed

K JSI Coordinator Date If-lb) owner or OOwners Deskcnee. Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois. and employed by The Hartford Steam and Boiler Insurance and Inspection Co. of Hartford. Connecticut have Inspected the components described in this Owner's Report during the period 02-11-2002 to 02-11-2002 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from gr connected with this inspection.

i 7

7

/

Commissions IL 932, NB7742NISB Insp~ec tor's signature National Board, State. Province and Endorsements Date

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, LLC)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Date:

Sheet Unit 12-07-2003 1

of 2

2 Work Order 00411655-01 (R/R Plan 2-02-014)

3. Work Performed by Same as Above Same As Above Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date N/A Address

4. Identification of System 1500/5700, CCSW Vault Room Cooler, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1989 Edition.

No

Addenda,
6. Identification of Components No Code Case N.416-1 Code Case ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~~~~~~~~~or No) _

EPN 2-5700-30D Supply Headers, Carbon Stl Buffalo Forge N/A N/A None Unknown Removed No Cat ID: 9251; Supply Headers, Carbon StI Aerofin NA N/A UTC: 2002422 Unknown Installed No Tee, Pipe, 2, A-1 05 Unknown N/A N/A None Unknown Removed No Heat Code:

Cat ID: 736 1; Tee, Pipe, 2, A-105 Unknown X1H N/A UTC 2602743 Unknown Installed No Flange, SW, 2, A-1 05 Unknown N/A N/A None Unknown Removed No Heat Code:

Cat ID: 38534; Flange, SW, 2', A-105 Unknown S1321 N/A UTC:2653803 Unknown Installed No

7. Description of work Replaced supply and return headers, various flanges and fittings. Capped damaged tube.
8. Tests Conducted:

Hydrostatic [

Pneumatic [ I Nominal Operating Pressure [X]

Exempt [

Other [ ]

Pressure 166 psi Test Temp.

Ambient OF

9. Remarks Applicable Manutacturers Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authon' tion No.

N/A Expiration Date N/A Signed

,ISI Coordinator Date

/2 2 O3

'A

~~~u Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois. and employed by The Hartford Steam and Boiler Insurance and InsDection Co. of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 01-13-2003 to 01-21-2003 and state that to the best of my knovedge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions IL 932, NB7742NISB National Board. State. Province, and Endorsements Date

_4____ __32

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Exelon Generation Company (EGC, LLC)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Date:

Sheet Unit 12-07-2003 2

Of 2

2/3 Work Order 00411655-01 (R/R Plan 2-02-014)

3. Work Performed by Same as Above Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp NIA Authorization No.

N/A Exiration Date N/A Same As Above Address

4. Identification of System 150015700, CCSW Vault Room Cooler, ASME Section Xl Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989
Edition, No
Addenda, No Code Case N-416-1 Code Case
6. Identification of Comnonents ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes or No) 2 Sch. 80 Pipe Unknown N/A NA N/A Unknown Removed No Heat Code:

Cat ID 24507; 2' Sch. 80 Pipe A-106 Gr. B Unknown 773164 N/A UTC 2632630 Unknown Installed No Elbow, pipe, 2', 90 deg, CS Unknown N/A NIA N/A Unknown Removed No Heat Code:

Cat ID: 7375; Elbow, pipe, 2', 90 deg, CS Unknown 75387 NIA UTC: 2656947 Unknown Installed No Flange, 2. Sch 80, SW, A-1O5, 300 lb Unknown N/A NA N/A Unknown Removed No Flange, 2. Sch 80. SW.

Heat Code:

Cat ID: 7480; A-105, 300 lb Unknown 4M38343 NIA U`TC 2656552 Unknown Installed No Cap, pipe, 1/8", 3000 psi, A-Cat ID: 553165; 105 Unknown N/A NIA UTC 2659746 Unknown Installed No

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, U-C)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Date:

12-2-2003 Sheet I

of I

Unit 2

Work Order 00421878.05 (R/R Plan 2-02-016)

3. Work Performed by' Same as Above Same As Above Repair/tRepacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date N/A Adoress

4. Identification of System 1500, Containment Cooling Service Water, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967 Edition.

No

Addenda, (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1989
Edition, No
Addenda,
6. Identification of Comoonents No Code Case N-416-1 Code Case ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes o r N o )

EPN 2-1501-44D Discharge Elbow Cat ID 7553; 1 W Outlet Fitting Unknown N/A N/A UTC 2001879 Unknown Installed No Heat Code:

A63145 L99-Cat ID 4625; 1 K4 Sch 80 Pipe Unknown 00599 N/A UTC 2063455 Unknown Installed No Heat Code:

AW4 B99-Cat ID 38433; 1 %- Pipe Cap Unknown 00641 N/A UTC 2067918 Unknown Installed No

7. Description of work Installed branch ine to repair through wall leak at discharge of 2-1501 44D Pump
8. Tests Conducted:

Hydrostatic [ ]

Pneumatic I Nominai Operating Pressure [ X Exempt [ I Other [ ]

Pressure 190 psi Test Temp.

OF

9. Remarks Apoticable Manutacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorz tion No.

N/A Expiration Date N/A Signed

,ISI Coordinator Date

/2-2. -

3 Owner or Owner's Desionee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam and Boiler Insurance and Insoection Co. of Hartford, Connecticut have Inspected the components described In this Owner's Report during the period 08-10-2002 to 08-12-2002 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner s report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

SCommissions IL 932, NB7742NiSB National Board. State, Province, and Endorsements Date Date

/,

-3 ' e0 5,

FORM NIS-2 OWNER'S REPORT FOR REPAIR OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl

1. Owner. Exelon Generation Company (EGC, LLC)

(Name) 200 Exelon Way, Kennett Square, PA, 19348 (Address)

2. Plant: Dresden Nuclear Power Station (Name) 6500 North Dresden Road. Morris IL.. 60450 (Address)

Date:

12-18-2002 Sheet: 1 Of 1 Unit:

2 PLAN 2-02-018 WO 00476711-07

3. Work Performed By: Same as Above (Name)

(Address)

Same as Above Repair Organization P.O. No., Job No. etc.

4. Identification of System:

3900 (Diesel Generator Cooling Water)

5. (a) Construction Code USAS B31.1.0 (b) Edition of Section XI used for Repair/Replacement 19 67 Edition, NO Addenda, Code Cases NONE 1989 Edition, NO Addenda, CodeCases NONE
6. Identification of Components Repaired or Replaced and Replacement Components Name of Name of Mfrs.

Nat Other Year

Repair, Code Component Manufacturer Serial No.

Brd ID Built Replaced or Stamped l_____________

No Replacement Yes/No 2-3903 Diesel Generator Crane Co. Chem-Unknown N/A 2/3-3903 N/A Replaced No Cooling Water Pump Pump Div.

2-3903 Diesel Generator Crane Co. Chem-19988-2B N/A Cat ID 15137 N/A Replacement No Cooling Water Pump Pump Div.

UTC 2643913 A

_ ~I _

I I_

I I

_ I __

_ I

7. Description of work:

Replaced existing pump with rebuilt spare.

8. Test Conducted: Hydrostatic ]

Pneumatic [l Nominal Operating Pressure [XI Not Applicable [l Test Pressure 83 psig Test Temperature Nominal F

9. Remarks:

Certificateof Compliance We certify that the statements made in this report are correct and this REPAIR/REPLACEMENT Conforms to Section Xl of the ASME Code.

Signed: 4, ISI COORDINATOR

/2

/8 Z

g (Oftror Ownes Designee)

(Title)

(Date)

Certificateof Inspection I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois, employed by The Hartford Steam and Boiler Insurance and Inspection Co. of Hartford, Connecticut having Inspected the REPAIR/REPLACEMENT described in this report on Z2 -/J 20_OZend state to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section Xl of the ASME Code. By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described In this report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personajnjury or property damage or a loss of any kind arising from or connected with this inspection.

Date: /

Inspector A '

1.9 Commissions

L932, NB7742NISB (State or Province, National Board)

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, LLC)

Narne 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address
3. Work Performed by Same as Above Same As Above Date:

09-11-2003 Sheet 1

of 1

Unit 2

Work Order 00493780-01 (R/R Plan 2-02-019)

Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

NA Expiration Date N/A Address

4. Identification of System 3900, Containment Cooling Service Water Supply to ECCS Room Coolers, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, No Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1989
Edition, Addenda, N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes o r N o)

Une 2-39211-4 Piping and Elbows Unknown N/A N/A NIA N/A Removed No Cat ID 36605 Line 2-3921 f-4' Piping Unknown Heat U41020 N/A UTC 2653062 Unknown Installed No Cat ID 47392 LIne 2-392114-Elbows Unknown NA N/A UTC 2653068 Unknown Installed No

7. Description of work Replaced piping section to repair leak.
8. Tests Conducted:

Hydrostatic [ ]

Pneumatic [

Nominal Operating Pressure [XI Exempt [ I Other [ J Pressure 190 psi Test Temp.

Ambient eF

9. Remarks None Applicable Manufacturers Data Reports to be attacied CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Wthorization No.

N/A Expiration Date N/A Signed ISI Coordinator Date t 0 9,..Arc Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam and Boiler Insurance and Inscoction Co. of Hartford. Connecticut have Inspected the components described In this Owners Report during the period 10-05-2002 to 10-06-2002 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

A______

Commissions IL 932, NB7742NISB Inspector's Snature National Board. State. Province, and Encorsernents Date - r ___ -

I

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, LLC)

Name Date:

11-3-2003 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Sheet 1

of 2

Unit 2

3. Work Performed by Same as Above Work Order 477343-01/05(R/R Plan 2-02-022/23)

Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date NIA Same As Above Address

4. Identification of System 1500, Containment Cooling Service Water, ASME Section Xi Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967 Edition.

No

Addenda, (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 1989 Edition.

No

Addenda, No Code Case N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes or No)

EPN 2-1501-44C Discharge 8' 300# Weld Neck Flange Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 25090; 8 300# Weld Neck Flange Unknown 2432ANF N/A UTC 2658937 Unknown Installed No 8' Sch. 40 1R 90 deg.

Elbow Unknown Unknown N/A N/A Unknown Removed No S' Sch. 40 LR 90 deg.

Heat Code:

Cat ID 36547; Elbow Unknown K80164 N/A UTC 2057015 Unknown Installed No Reducer, concentric, 10'x8',

Sch.40 Unknown Unknown N/A N/A Unknown Removed No Reducer, concentric, 10'x8',

Heat Code:

Cat ID 30930; Sch.40 Unknown 583UND-4 N/A UTC 2657796 Unknown Installed No

7. Description of work Replaced dischaMe elbow and associated piping, flanges and bolting at 2-1501-44C Pump
8. Tests Conducted:

Hydrostatic [

Pneumatic ( I Nominal Operating Pressure [X I Exempt [

Other [ ]

Pressure 180 psi TestTemp.

Ambient OF

9. Remarks Applicable Manutacturees Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorizatipn No.

N/A Expiration Date N/A Signed or

.11S Coordinator Date

/2--o3 r

~~~~~Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois. and employed by The Hartford Steam and Boiler Insurance and Inspection Co. of Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 01-13-2003 to 01-21-2003 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from r connected with this Inspection.

/

4 o f Commissions IL 932, NB7742NiSB Inspectors Signature National Board, State, Province, and Endorsements Date

-A

- 6

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Exelon Generation Company (EGC, LLC)

Name onnrY InwAI V-

.I...

rn 1-.

CLAJ rxVIUII wvY, Addrners sqae tlY Date:

11-3-2003 Sheet 2

of 2

Unit 2

Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Work Order 477343-0 15(R/R Plan 2-02-022/23)

AOreSSs HepairlKeptacement Organization P.O. No. Job NO. etc.

3. Work Performed by Same as Above Type Code Symbol Stamp N/A Authorization No.

N/A Same As Above Expiration Date N/A Address

4. Identification of System 1500, Containment Cooling Serice Water, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, No Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989 Edition.

No

Addenda, N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~~~~~~~~~~~~or No) 10 Sch. 40 Pipe Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24658; 10 Sch. 40 Pipe Unknown B68587 N/A UTC 2657795 Unknown Installed No 10- 300# Weld Neck Flange Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24466;

10. 300# Weld Neck Flange Unknown 2432ANF N/A UTC 2658938 Unknown Installed No 2-Socketweld Outlet fitting Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 27163; 2' Socketweld Outlet fitting Unknown T140 NIA UTC 2011820 Unknown Installed No 2 Sch. 80 Pipe Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24507; 2 Sch. 80 Pipe Unknown 773164 N/A UTC 2632630 Unknown Installed No 7/8-9 SA-193 Gr. B7 Studs Unknown Unknown N/A N/A Unknown Removed No 7/8-9 AISA-1 93 Gr. B7 Heat Code:

Cat ID 37096; Studs Unknown NWN N/A UTC 2045537 Unknown Installed No 7/8-9 SA-1 94 Gr. 2H Nuts Unknown Unknown N/A N/A Unknown Removed No Cat ID 7223; 718-9 SA-194 Gr. 2H Nuts Unknown Unknown N/A UTC 2639504 Unknown Installed No 1.-8 SA-193 Gr. B7 Studs Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 37098; 1.-8 ASA-1 93 Gr. B7 Studs Unknown A475 NA UTC 2639497 Unknown Installed No 1-8 SA-194 Gr. 2H Nuts Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 37034; 1--8 SA-194 Gr. 2H Nuts Unknown HDF N/A UTC 2029998 Unknown Installed No EPN 2-1501-1C

10. Discharge Check Valve Unknown Not Recorded N/A N/A Unknown Removed No 10- Discharge Check Valve Gulf 29206-1-1 N/A N/A Unknown Installed No

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Exelon Generation Company (EGC, U-C)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Date:

11-3-2003 Sheet 1

of 2

Unit 2

3. Work Performed by Same as Above Same As Above Work Order 477344-01/02 (RIR Plan 2-02-024125)

RepairtReolacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A

_ Expiration Date N/A Address

4. Identification of System 1500, Containment Cooling Service Water, ASME Section Xl Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989
Edition, No Addenda.

No Code Case N-416-1 Code Case

6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~~~~~~~~~~or No)

EPN 2-1501-44D Discharge 8-300# Weld Neck Fange Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 25090; 8 300# Weld Neck Flange Unknown 21022 N/A UTC 2638838 Unknown Installed No 8' Sch. 40 LR 90 deg.

Elbow Unknown Unknown N/A N/A Unknown Removed No B' Sch. 40 LR 90 deg.

Heat Code:

Cat ID 36547; Elbow Unknown K80164 N/A UTC 2057015 Unknown Installed No Reducer, concentric, 10 x8',

Sch.40 Unknown Unknown N/A NIA Unknown Removed No Reducer, concentric, 10'x8.

Heat Code:

Cat ID 30930; Sch.40 Unknown 583UND-5 N/A UTC 2657797 Unknown Installed No

7. Description of work Prefabricate spool piece and install Into CCSW system at discharge of 2-1501-44D Pump
8. Tests Conducted:

Hydrostatic [ ]

Pneumatic [ I Nominal Operating Pressure [XI Exempt [

Other [ ]

Pressure 186 psi TestTemp.

OF

9. Remarks Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Aq horizajon No.

N/A Expiration Date N/A Signed g

J

,ISI Coordinator Date

/Z-2 -o 3

o r;~

Owner or Owner's Desionee, Tle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission ssued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam and Boiler Insurance and Inspection Co. of Hartford, Connecticut have nspected the components described In this Owner's Report during the period 01-13-2003 to 01-21-2003 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report In accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising f m or connected with this nspection.

Commissions IL 932. NB7742NISB Inspector's Sionatuo National Board, State. Province, and Endorsements Date

/J -- -e

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, LLC)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morrs IL 60450 Address Date:

11-3-2003 Sheet 2

of 2

Unit 2

Work Order 477344-01/02 (R/R Plan 202-024/25)

Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date N/A

3. Work Performed by Same as Above Same As Above Address
4. Identification of System 1500, Containment Cooling Service Water, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989
Edition, No
Addenda, No Code Case N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes or No) 10- Sch. 40 Pipe Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24658; 10 Sch. 40 Pipe Unknown B68587 N/A UTC 2657795 Unknown Installed No 10- 300# Weld Neck Flanqe Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24466; 10 300# Weld Neck Fange Unknown 2432ANF N/A UTC 2658938 Unknown Installed No 7/8-9 SA-193 Gr. B7 Studs Unknown Unknown N/A N/A Unknown Removed No 7/8 -9 NSA-193 Gr. 57 Heat Code:

Cat ID 37096; Studs Unknown NWN N/A UTC 2045537 Unknown Installed No 7/8-9 SA-194 Gr. 2H Nuts Unknown Unknown N/A N/A Unknown Removed No Cat ID 7223; 7/8-9 SA-194 Gr. 2H Nuts Unknown Unknown N/A UTC 2639504 Unknown Installed No 1-8 SA-193 Gr. B7 Studs Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 37098; 1-8 AfSA-193 Gr. B7 Studs Unknown A475 N/A UTC 2639497 Unknown Instalted No 1-8 SA-194 Gr. 2H Nuts Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 37034; 1-8 SA-194 Gr. 2H Nuts Unknown HDF N/A UTC 2639509 Unknown Installed No EPN 2-1501-ID Discharge Check Valve Gulf 27823-1-3 N/A N/A Unknown Removed No Techno Model Cat ID 1234437; Discharge Check Valve 5053 13973-IA N/A UTC 2649966 Unknown Installed No

FORM NIS-2 OWNER'S REPORT FOR REPAIR OR REPLACEMENTS As Required by the Provisions of ASIE Code Section XI

1. Owner. Exelon Nuclear (Name)

P.O. Box 805379. Chicago IL, 60680-5379 (Address)

2. Plant: Dresden Nuclear Power Station (Name) 6500 North Dresden Road. Morris IL., 60450 (Address)

Date:

3-25-2003 Sheet: I Of I Unit:

2&3 WO Identified Below PLAN 2-03-011 Repair Organization P.O. No., Job No. etc.

3. Work Performed By:

Same as Above

,(Name)

  • (Address)

Same as Above

4. Identification of System:

2499 (CAM)

5. (a) Construction Code ASME Section III (b) Edition of Section XI used for Repair/Replacement 1974 Edition, Summer 1975 Addenda, Code Cases NONE 1998* Edition, NO Addenda, Code Cases NONE 1 998 Edition Implemented in accordance with Relief Request MCR-02
6. Identification of Components Repaired or Replaced and Replacement Components Name of Name of Mfrs.

Nat Other Year

Repair, Code Component Manufacturer Serial No.

Brd ID Built Replaced or Stamped No' Replacement Yes/No Valve Disk Target Rock Unknown N/A Model 76L-001 Unknown Replaced No EPN Work Order 2-2499-1 B 99269161 2-2499-2A 96034438 2-2499-2B 96034454 2-2499-3B 00344521 2-2499-4A 96034439 2-2499-4B 96034456 3-2499-2A 96081677 3-2499-2B 96081675 3-2499-4A 97028069 Valve Disk Target Rock I Unknown, N/A Cat ID 25595 1998.

Replacement Yes S/N 144,147, UTC 2003474,

2001,

/

149,157, 158, 2003475,2003476, 2002 162,155.159 2003477.2616027, 2616028, 2616029, 2638585,2638586

7. Description of work: Replace valve disk with silicone nbber seat as preventative maintenance.

8.TestConducted: Hydrostatic[ ]

Pneumatic ]

NominalOperatingPressure[ ]

NotApplicable[X]

Test Pressure psig Test Temperature OF

9. Remarks: Pneumatic test performed In accordance with 10 CFR 50 Appendix J.

[

Certificateof Compliance We certify hestatem nts made in this report are correct and this REPAIR/REPLACEMENT Conforms to Section Xl of the ASME Code.

Sign ISI COORDINATOR

.20O 3 (Owner or Owner's Designee)

(Title)

(Date)

Certificateof Inspection I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois, employed by The Hartford Steam and Boiler Insurgnrce and Inspection Co. of Hartford, Connecticut having inspected the REPAIRIREPLACEMENT described In this report on I

6

.20 and state to the best of my knowledge and belief, this repair or replacement has been constructed In accordance with Section Xl of the ASME Code. By signing this certificate neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the repair or replacement described In this report Furthermore, neither the inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Date: 5;21 Inspector.

v Commissions:

IL932, NB7742NISB (State or Province, National Board) i

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Exelon Generation Company (EGC, ULC)

Date:

11-3-2003 Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Pant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Sheet 1

of 2

Unit 3

Work Order 00408844-05 (R/R Plan 3-02-021)

3. Work Performed by Same as Above Same As Above Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date N/A Address

4. Identification of System 1500, Containment Cooling Service Water, ASME Section Xl Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, No Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1989 Edition.

No

Addenda, N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~~~~~~~~~~~~~~or No)

EPN 3-1501-44A Discharge 8-300# Weld Neck Flange Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 25090; 8 300# Weld Neck Flange Unknown PSA2 N/A UTC 2639069 Unknown Installed No 8" Sch. 40 SR 90 deg.

Elbow Unknown Unknown N/A N/A Unknown Removed No 8 Sch. 40 SR 90 deg.

Heat Code:

Cat ID 1234257 Elbow Unknown J337A-3 N/A UTC 2639090 Unknown Installed No Reducer, concentric, 10x8.

Sch. 40 Unknown Unknown N/A N/A Unknown Removed No Reducer, concentric, 10 x8, Heat Code:

Cat ID 30930; Sch. 40 Unknown 645UNA-2 N/A UTC 2639030 Unknown Installed No

7. Description of work Installation of new spool piece Into CCSW system at discharge of 3-1501-44A Pump
8. Tests Conducted:

Hydrostatic [ I Pneumatic [ I Nominal Operating Pressure [X Exempt [ ]

Other l Pressure 200 psi Test Temp.

Ambient OF

9. Remarks Applicable Manutacturees Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Auhoriztion P.

N/A Expiration Date N/A Signed

,ISI Coordinator Date

/-3-03

/~

Oer or Owner's Desimnee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois. and employed by The Hartford Steam and Boiler Insurance and InsDection Co. of Hartford. Connecticut have Inspected the components described in this Owner's Report during the period 01-07-2003 to 01-13-2003, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising fromgr connected with this Inspection.

Commissions IL 932, NB7742NISB Inspector's signature National Board. State. Province, and Endorsements Date

/-

"?t'K3 v

or-

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Exelon Generation Comoanv (EGC. ULC)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Date:

Sheet Unit 11-3-2003 2

of 2

3 Work Order 00408844-05 (RIR Plan 3-02-021)

Address HepalrHeplacemlent UrgarOzaton P.o. No. Job NO.

etc.

3. Work Performed by Same as Above Type Code Symbol Stamp N/A Authorization No.

N/A Same As Above Expiration Date N/A Address

4. Identification of System 1500, Containment Cooling Service Water, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, No Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1989 Edition.

No

Addenda, N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Nameof Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes or No) 10 Sch. 40 Pipe Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24658; 10 Sch. 40 Pipe Unknown B68587 N/A UTC 2639014 Unknown Installed No 10 300# Weld Neck Flange Unknown Unknown NA N/A Unknown Removed No Heat Code:

Cat ID 24466; 10 300# Weld Neck Flange Unknown GLMO N/A UTC 2639073 Unknown Installed No

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, LLC)

Name 200 Exelon Wav, Kennett Square, PA 19348 Date:

11-3-2003 Sheet 1

of 2

Unit 3

Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Work Order 00408844-06 (R/R Plan 3-02-022)

Address Repair/Replacement Orqanization P.O. No. Job No. etc.

3. Work Performed by Same as Above Type Code Symbol Stamp N/A Authorization No.

N/A Same As Above Expiration Date N/A Address

4. Identification of System 1500, Containment Cooling Service Water, ASME Section Xl Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, No Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 1989
Edition, No
Addenda, N-416-1 Code Case
6. Identification of Comnonents ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

_ _ _ _ _ _o r N o) _

EPN 3-1501-448 Discharge 8 300# Weld Neck Flanae Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 25090; 8 300# Weld Neck Flange Unknown 2432ANF NIA UTC 2658937 Unknown Installed No 8 Sch. 40 LR 90 deg.

Elbow Unknown Unknown NIA N/A Unknown Removed No 8 Sch. 40 LR 90 deg.

Heat Code:

Cat ID 36547; Elbow Unknown K80164 NIA UTC 2057015 Unknown Installed No Reducer, concentric, 10x8, Sch. 40 Unknown Unknown NIA NIA Unknown Removed No Reducer, concentric, 10 x8, Heat Code:

Cat ID 30930-Sch.40 Unknown 64SUNA-3 N/A UTC 2639031 Unknown Installed No

7. Description of work Installation of new spool piece Into CCSW system at discharge of 3-1501-44B Pump
8. Tests Conducted:

Hydrostatic [ ]

Pneumatic [ ]

Nominal Operating Pressure XI Exempt [

Other [ ]

Pressure 188 psi Test Temp, Ambient OF

9. Remarks Applicable Manutacturers Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of A oriation o.

N/A Expiration Date N/A SignedSI Coordinator Date

/

.'-2">3

~~

_crwn~~er Or Owner's Designee T]

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam and Boiler Insurance and InsDection Co. of Hartford. Connecticut have Inspected the components described in this Owner's Report during the period 01 2003 to 01 2003 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owners report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

/_____________________________ Commissions IL 932, NB7742NISB Inspectors SianatuVt National Board. State, Province, and Endorsements Date 1/ -Ye-*7

?

f

I I

FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, LLC)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant

_ Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Date:

11-3-2003 Sheet 2

of 2

Unit 3

Work Order 00408844-06 (R/R Plan 3-02-022)

Address Repair/Replacement Organization P.O. No. Job No. etc.

3. Work Performed by Same as Above Type Code Symbol Stamp N/A Authorization No.

N/A Same As Above Expiration Date N/A Address

4. Identification of System 1500, Containment Cooling Service Water, ASME Section Xl Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, No Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989
Edition, No
Addenda, N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes l______

_ l or No) 10 Sch. 40 Pipe Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24658; 10 Sch. 40 Pipe Unknown B68587 N/A UTC 2639014 Unknown Installed No 10 300# Weld Neck FRange Unknown Unknown N/A N/A Unknown Removed No Heat Code:

Cat ID 24466:

10 300# Weld Neck Range Unknown GLMO N/A UTC 2639073 Unknown Installed No 2-Socketweld Outlet fitting Unknown Unknown N/A NA Unknown Removed No Heat Code:

Cat ID 7554; 2 Socketweld Outlet fitting Unknown ORS NIA UTC 2001880 Unknown Installed No 2 Sch. 80 Pipe Unknown Unknown N/A NIA Unknown Removed No Heat Code:

Cat ID 24507; 2-Sch. 80 Pipe Unknown 773164 N/A UTC 2632630 Unknown Installed No EPN 3-1501-lB 10" Discharge Check Valve Gulf 29206-1-1 N/A N/A Unknown Removed No Cat ID 1234437; 10" Dischar e Check Valve Techo 13973-IA N/A UTC 2649966 Unknown Installed No

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner Exelon Generation Company (EGC, LLC)

Name 200 Exelon Way, Kennett Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Date:

11-11-2003 Sheet 1

of I

Unit 2/3 Work Order 99213921-01 (R/R Plan 3-02-066)

Repair/Replacement Orpanization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A

3. Work Performed by Same as Above Same As Above Address Expiration Date N/A
4. Identification of System 0200, Feed Water, ASME Section XI Class 1
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989
Edition, No
Addenda, No Code Case None Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~~~~ ~~~or N o)

Disc Assembly for 3.0220-EID Number.

58A Check Valve Crane Unknown N/A DOOZ02046 Unknown Corrected No Refurbished disc assembly by weld build up/machining and returned to storeroom under Cat ID

7. Description of work 1033169
8. Tests Conducted:

Hydrostatic [ ]

Pneumatic I I Nominal Operating Pressure [ l Exempt [I Other [

Pressure psi Test Temp.

OF

9. Remarks Apptlicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Auhoriztioo.

N/A Expiration Date N/A Signed 406 ISICoordinator Date CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam and Boiler Insurance and Inswection Co. of Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 09-12-2002 to 0401-2003. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from r ected With this Inspection.

SCommissions IL 932, NB7742NISB Inspectoes Ssgnature National Board. State, Province, and Endorsements Date

//

5>6

7

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner Exelon Generation Company (EGC, LLC)

Name 200 Exelon Way, Kenneft Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address
3. Work Performed by Same as Above Same As Above Date:

11-3-2003 Sheet 1

of I

Unit 2/3 Work Order 00442789-01 (R/R Plan 3-02-079)

Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp N/A Authortzaton No.

N/A Expiration Date N/A Address

4. Identification of System 3900, Service Water, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967 Edition.

No

Addenda, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989 Edition.

No

Addenda,
6. Identification of Comnnnents No Code Case N-416-1 Code Case ASME National Corrected.

Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes o r N o)

EPN 213-3999-334 Gate Valve, 3 Borg Wamer Unknown N/A N/A Unknown Removed No Gate Valve, 3. Class 300.

Sch. 40 Butt Weld ends, ASTM A-351 Gr. CF8M Cat ID 9502:

Stainless Steel Velan 02 N/A UTC 2656105 Unknown Installed No

7. Description of work Welded In new valve
8. Tests Conducted:

Hydrostatic

]

Pneumatic [ ]

Nominal Operating Pressure [X Exempt [

Other I ]

Pressure 193 psi TestTemp.

Ambient OF

9. Remarks Applicable Manufacturers Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Author n No.

Expiration Date N/A Signed B~ror~v~ner's~esiqneeTfle ISI Coordinator Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam and Boiler Insurance and Inspection Co. of Hartford Connecticut have Inspected the components described In this Owner's Report during the period 01-28-2003 to 01-30-2003 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions IL 932, NB7742NISB insperors sionature

~

National Board. State, Province and Endorsements Date at Id

-/

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, LLC)

Date:

11-3-2003 Name 200 Exelon Way, Kenneft Square, PA 19348 Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Sheet 1

of 1

Unit 213 Work Order 00443812-01 (R/R Plan 3-02-080)

3. Work Performed by Same as Above Same As Above Repair/Replacement Orqanization P.o. No. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date N/A

=

Address

4. Identification of System 3900, Service Water, ASME Section Xi Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 1989
Edition, No
Addenda, No Code Case N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~~~~~~~~~or No)

EPN 2/3-3999-332 Gate Valve, 3 Borq Wamer Unknown N/A N/A Unknown Removed No Gate Valve, 3-, Class 300, Sch. 40 Butt Weld ends, ASTM A-351 Gr. CF8M Cat ID 9502; Stainless Steel Velan 01 NIA UTC 2656104 Unknown Installed No

7. Description of work Replaced welded In valve
8. Tests Conducted:

Hydrostatic I Pneumatic [ I Nominal Operating Pressure I X I Exempt [

Other [ ]

Pressure 188 psi Test Temp.

Ambient OF

9. Remarks Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of A orition N/A Expiration Date N/A Signed C

,ISI Coordinator Date 6 -1 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam and Boiler Insurance and Insoection Co. of Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 01-28-2003 to 01-30-2003 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owners report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions IL 932, NB7742NISB Insictr' Siginature National Board. State. Province. end Endorsements Date

/_ _

I I

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Comoanv (EGC. LLC)

Date:

12-03-2003 Name 200 Exelon Way, Kennett Square, PA 19348

. Address

2. Plant Dresden Nuclear Power Station Name 6500 North Dresden Road, Morris IL 60450 Address Sheet 1.

of 2

Unit 2/3

3. Work Performed by Same as Above Work Order 00433283-01 (RJR Plan 3-02-081)

Repair/Replacement Organization P.O. No. Job No. etc.

Type Code Symbol Stamp NIA Authorization No.

N/A Expiration Date N/A Same As Above Address

4. Identification of System 3900, Service Water, ASME Section Xi Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No (b) Applicable Edition of Section XI Used for Repair/Replacement Activity
Addenda, No Code Case 1989
Edition, No
Addenda, N-416-1 Code Case
6. Identification of Components ASME National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~~~or N o)

EPN 2/3-3999-336 Gate Valve, 3, Class 300 Borg Wamer Not Recorded N/A N/A Unknown Removed No Gate Valve, 3', Class 300.

Sch. 40 Butt Weld ends.

ASTM A-351 Gr. CF8M Cat ID 1385276; Stainless Steel Velan Valve 03 N/A UTC 2656103 Unknown Installed No 3 Sch. 40 Pipe Unknown N/A N/A N/A Unknown Removed No Heat Code:

Cat ID 39115; 3 Sch. 40 Pipe A-106 Gr. B Unknown 426258 N/A UTC 2005854 Unknown Installed No Pipe Tee, 3 x 2-1/2. Sch.

40, ASTM A-234 Gr. WPB Unknown N/A N/A N/A Unknown Removed No Pipe Tee. 3-x 2-1/2. Sch.

Cat ID 445112; 40, ASTM A-234 Gr. WPB Unknown N/A N/A UTC 2657908 Unknown Installed No

7. Description of work Welded In new valve, pipe, and fitting
8. Tests Conducted:

Hydrostatic I ]

Pneumatic [ I Nominal Operating Pressure [Xl Exempt [

Other [ J Pressure 193 psi Test Temp.

Ambient OF

9. Remarks Applicable Manufacturer's Data Repofls to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authordzati nNo.

N/A Expiration Date N/A Signed

.ISI Coordinator Date

/Z-

- 2O3-%

or Ower's Desionee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois. and employed by The Hartford Steam and Boiler Insurance and Insoection Co. of Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 01-28-2003 to 01-30-2003. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described In this Owner's report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions IL 932, NB7742NISB National Board, State, Province. and Endorsements Date

/,2 "t/

e'3

FORM NIS.2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi

1. Owner Exelon Generation Company (EGC, UIC)

Name Date:

12-03-2003 200 Exelon Way, Kennett Square, PA 19348 Sheet 2

Of 2

Address Dresden Nuclear Power Station

2. Plant Name 6500 North Dresden Road, Morris IL 60450 Address Unit 2/3 Work Order00433283-01 (R/R Plan 3-02-081)
3. Work Performed by Same as Above Repair/Replacement OrCanization P.O. No. Jot No. etc.

Type Code Symbol Stamp NIA Authorization No.

N/A Expiration Date N/A Same As Above Address

4. Identification of System 3900, Service Water, ASME Section XI Class 3
5. (a) Applicable Construction Code USAS B31.1.0 1967
Edition, No
Addenda, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 1989
Edition, No
Addenda, No Code Case N-416-1 Code Case
6. Identification of Components

- ~ ~~AS M E National Corrected, Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No.

No.

Identification Built Installed (Yes

~~ ~~

~ ~~~o r N o )

2-1/2' Sch. 40 Pipe Unknown N/A N/A NIA Unknown Removed No 2-1/2 Sch. 40 Pipe A-106 Heat Code:

Cat ID 38487; Gr. B Unknown B69022 N/A UTC 2069655 Unknown Instalted No