I SOUTHERN CALIFORNIA LJ EDISON An EDISON INTERNATIONALV Company Dwight E. Nunn Vice President February 7, 2003 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Subject:
Reference:
Docket No. 50-362 Special Report: Inservice Inspection of Steam Generator Tubes, Cycle 12 San Onofre Nuclear Generating Station, Unit 3 Steam Generator Program Guidelines, Nuclear Energy Institute Document Number NEI 97-06, Revision 1 Gentlemen:
On January 26, 2003, Southern California Edison (SCE) completed the inservice inspection of steam generator tubes at San Onofre Nuclear Generating Station Unit 3. The attached report is submitted in accordance with Technical Specification (TS) 5.7.2.c reporting requirements:
Report the number of tubes plugged in each steam generator within 15 days of completing the inspection.
Report the complete results of steam generator tube inspections within 12 months of inspection completion.
The attachment to this letter, "Special Report - Inservice Inspection of Steam Generator Tubes,"
which was prepared in accordance with the referenced industry guidance, satisfies these reporting requirements. The report contains no new commitments.
If you require any additional information, please advise.
Sincei Attachments:
cc:
E. W. Merschoff, Regional Administrator, NRC Region IV B. M. Pham, NRC Project Manager, San Onofre Units 2 & 3 C. C. Osterholtz, NRC Senior Resident Inspector, San Onofre Units 2 & 3 Institute of Nuclear Power Operations (INPO)
- 1
-I P 0 Box 128 San Clemente, CA 92674-0128 949-368-1480 Fax 949-368-1490
Inservice Inspection of Steam Generator Tubes Special Report Attachment Page 1 of 12 SPECIAL REPORT - INSERVICE INSPECTION OF STEAM GENERATOR TUBES Regulatory Reporting Requirements Reporting Requirement 5.7.2.c of Appendix A, Technical Specification to Facility Operating License NPF-1 5, requires the number of tubes plugged and tubes sleeved in each steam generator to be reported to the Nuclear Regulatory Commission within 15 days following completion of the inspection.
Reporting Requirement 5.7.2.c of Appendix A, Technical Specification to Facility Operating License NPF-1 5, requires the complete results of steam generator tube inspections to be reported to the Nuclear Regulatory Commission within 12 months following completion of the inspection.
Planned Inspection Scope Table I summarizes the planned inspection program. Also, when indications by the bobbin probe were non-quantifiable or distorted, the inspection program included inspection with the Plus-Point Probe.
Table 3 provides the list of Nondestructive Examination (NDE) techniques utilized for each degradation mechanism.
Inspection Scope Expansion Table 2 summarizes the only significant inspection program scope expansion in response to inspection results. The expanded scope inspected the U-bend region of all Row 4 tubes in both steam generators.
All tubes were inspected with both mid-range and high-range frequency Plus-Point Probes.
Results This report satisfies the listed regulatory reporting requirements.
The contents of this report were prepared using the guidance contained in NEI 97-06, Rev. 1, "Steam Generator Program Guidelines." The NEI guidance is an initiative to unify the industry approach towards steam generator issues and strengthen, where necessary, the steam generator program.
Table 4 summarizes the number of tubes repaired, and active degradation mechanisms found. Each tube is only counted once in this listing, although it may also have an eddy current indication of a type below the point in the listing where it appears. The Appendices provide the complete results of the steam generator tubing inservice inspection.
Table 5 summarizes in-situ pressure and leak testing results. This particular testing demonstrated the structural and leakage (i.e., there was no leakage) integrity of the tested tubes consistent with EPRI guidelines and recent industry guidance.' Eddy current testing results and in-situ pressure and leak testing results (Condition Monitoring) provide assurance that performance criteria in the NEI guidance (structural integrity and accident-induced leakage) were met during operation prior to this inspection.
1 Letter from Lawrence F. Womack (Pacific Gas and Electric Company) to Steam Generator Management Program Utility Steering Committees, et. al, "Steam Generator Management Program (SGMP) Interim Guidelines on In Situ Pressure Testing of Steam Generator Tubes," dated October 13, 2000.
Inservice Inspection of Steam Generator Tubes Special Report Attachment Page 2 of 12 Repair of Tubes Table 4 lists the number of tubes repaired by plugging for each steam generator. The sleeving repair method has never been used at Unit 3.
Table 6 provides an itemized listing of the tubes plugged in steam generator E-088 along with the corresponding Table 4 category specifying the indication orientation/location.
Table 7 provides an itemized listing of tubes plugged in steam generator E-089 along with the corresponding Table 4 category specifying the indication orientation/location.
Repair Methods, Number of Tubes Repaired and Effective Plugging Percentage All tube plugging was performed using the design, materials, and installation methods of FRAMATOME-ANP (FANP). A "roll" method was used for all tube plugs. Nine tubes in Steam Generator E-088 and five tubes in Steam Generator E-089 were "stabilized" in the vicinity of the top of the tubesheet using the design, materials, and installation methods of FANP.
Seventy-two tubes were plugged in Steam Generator E-088 during the Cycle 12 refueling outage. A total of 658 tubes have been plugged. The design number of tubes is 9350 and no tubes have ever been sleeved in this steam generator. The effective plugging percentage for E-088 is 7.1%.
Sixty-seven tubes were plugged in Steam Generator E-089 during the Cycle 12 refueling outage. A total of 589 tubes have been plugged. The design number of tubes is 9350 and no tubes have ever been sleeved in this steam generator. The effective plugging percentage for E-089 is 6.3%.
Inservice Inspection of Steam Generator Tubes Attachment Description of Tables and Appendices Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Appendix 1 Appendix 2 Appendix 3 Appendix 4 -
Special Report Page 3 of 12 Summary of the Planned Inspection Program for the Unit 3 Cycle 12 (U3C12) Refueling Outage Summary of Significant Scope Expansions for the Unit 3 Cycle 12 (U3C12)
Refueling Outage List of Nondestructive Examination (NDE) Techniques Utilized for Each Degradation Mechanism for the U3C12 Refueling Outage Number of Tubes Repaired and Active Degradation Mechanisms Found During the U3C12 Refueling Outage Summary of Results of In-Situ Pressure and Leak Testing for the U3C1 2 Refueling Outage U3C12 Refueling Outage Tubes Plugged, Steam Generator E-088 U3C12 Refueling Outage Tubes Plugged, Steam Generator E-089 Steam Generator Reference Information Legend for Appendices 3 and 4 Inspection Summary, Steam Generator E-088 Inspection Summary, Steam Generator E-089
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 4 of 12 TABLE I - Summary of the Planned Inspection Program for the Unit 3 Cycle 12 (U3C12) Refueling Outage Number of TubeslPercentage of Tubes Steam Generator E-088 E-089 Full length of tube with the Bobbin Probe (excluding U-8764 /100%
8828 /100%
bends for Rows 1-3)
Hot leg expansion transition at the top-of-tubesheet with the 8764 / 100%
8828 / 100%
Plus-Point Probe Cold leg expansion transition at the top-of-tubesheet with 2697 / 30%
2638 / 29%
the Plus-Point Probe U-bend regions of Rows 1, 2, and 3 with mid-range 187 /100%
174 /100%
frequency Plus-Point Probes U-bend regions of Rows 1, 2, and 3 with high-range 187 /100%
174 /100%
frequency Plus-Point Probes Plus-Point Probe examinations of tube support 315/100%
353/100%
intersections with dents greater than, or equal to, 2 volts Plus-Point Probe dings greater than, or equal to, 4 volts 376 /100%
493 /100%
Plus-Point Probe examination of all tube support 948 / 100%
795 /100%
intersections with quantified wear indications by the bobbin probe I
I
_I TABLE 2 - Summary of Significant Scope Expansions for the Unit 3 Cycle 12 (U3C12) Refueling Outage Number of Tubes/Percentage of Tubes Steam Generator E-088 E-089 U-bend regions of Row 4 with mid-range frequency Plus-64 / 100%
64/100%
Point Probes U-bend regions of Row 4 with high-range frequency Plus-64 /100%
64 /100%
Point Probes
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 5 of 12 TABLE 3 - List of Nondestructive Examination (NDE) Techniques Utilized for Each Degradation Mechanism for the U3C12 Refueling Outage Indication OrientationlLocation Probe Type for Detection Characterization Axially oriented ID (initiated on the inside-diameter of Plus Point Plus Point the tubing wall) indications at U-bends Axially oriented OD (initiated on the outside-diameter of the tubing wall) indications not associated with a Bobbin Plus Point tube support (freespan)
Circumferentially oriented ID indications near or below the expansion transition at the top of the hot leg Plus Point Plus Point tubesheet Circumferentially oriented OD indications near the Plus Point Plus Point expansion transition at the top of the hot leg tubesheet Axially oriented ID indications near or below the Plus Point Plus Point expansion transition at the top of the hot leg tubesheet Axially oriented ID indications below the hot leg top-of-Bobbin Plus Point tubesheet Axially oriented OD indications in the sludge pile Plus Point Plus Point region near the top of the hot leg tubesheet Indications of wear at tube support locations Bobbin Plus Point Bobbin or Volumetric indications Plus Point Plus Point Bobbin or Miscellaneous preventative plugging Plus Point Plus Point
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 6 of 12 TABLE 4 - Number of Tubes Repaired and Active Degradation Mechanisms Found During the U3C12 Refueling Outage Indication OrientationlLocation Steam Generator E-088 E-089 Tubes with axially oriented ID (initiated on the inside-diameter of 0
the tubing wall) indications at U-bends (ID Axial @ U-bends) 2 Tubes with axially oriented OD indications not associated with a 4
1 tube support (freespan) (OD Axial @ Freespan)
Tubes with circumferentially oriented ID indications near the 3
expansion transition at the top of the hot leg tubesheet 6
2 (ID Circ @ TSH)
Tubes with circumferentially oriented OD indications near the 4
expansion transition at the top of the hot leg tubesheet 1
2 (OD Circ @ TSH)
Tubes with axially oriented OD indications in the sludge pile 5
region near the top of the hot leg tubesheet 0
1 (OD Axial @ Sludge Pile TSH) 6 Tubes with axially oriented ID indications below the inlet top-of-7 2
tubesheet (ID Axial below TSH)
Tubes with circumferentially oriented ID indications below the 2
1 inlet top-of-tubesheet (ID Circ below TSH) 8 Tubes with indications of wear at tube support locations 45 58 (Wear @ Support) 9 Tubes with volumetric indications (OD Vol @ Miscellaneous) 2 0
10 Miscellaneous preventative plugging (not an active degradation 4
0 mechanism) (Prevent @ Miscellaneous)
Total 72 67
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 7 of 12 TABLE 5 - Summary of Results of In-situ Pressure and Leak Testing for the U3C1 2 Refueling Outage Steam Generator E-088 TUBE AND EDDY CURRENT INFORMATION IN-SITU TEST RESULTS TUBE INFORMATION PLUS POINT DATA REGION Max PDA or COMMENTS GPM @
GPM @
GPM @ NODP PRESSURE ROW COL LOCATION LENGTH VOLTS Det Avg ORIENTATION NODP MSLB POST MSLB 3xNODP Depth Depth I
U-BEND 3
1 DBH + 8 69 089 1.12 75 585 IDAXIAL 0
0 0
4800 (AD)
Steam Generator E-089 TUBE AND EDDY CURRENT INFORMATION IN-SITU TEST RESULTS TUBE INFORMATION PLUS POINT DATA R NPDA or COMMENTS GPM @
GPM @
GPM @ NODP PRESSURE ROW COL LOCATION LENGTH VOLTS Max-Avg ORIENTATION NODP MSLB POST MSLB 3xNODP Depth De-
- ~~~
=
I iii 58 7%
TUBESHEET 31 123 TSH - 7 37 065 208 90%
587%
ID CIRC 0
0 0
4800 1(AD)
SUPPORT 54 90 DBC+1,89 407 303 68%
43.1%
ODVOL 0
0 0
4800 I
(AD) 1 1
- NOTES:
GPM = Gallons per Minute NODP = Normal Operation Differential Pressure MSLB = Main Steam Line Break Pressure Differential OD = Degradation initiated on the outside diameter of the tubing ID = Degradation initiated on the inside diameter of the tubing PDA = Percent degraded area
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 8 of 12 TABLE 6-SONGS U3C12 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 4) 3 1
ID Axial @ U-bend 31 5
Prevent @ Miscellaneous 1
9 Prevent @ Miscellaneous 68 18 ID Circ @ TSH 71 31 OD Axial @ Freespan 81 43 Wear @ Support 113 49 OD Vol @ Miscellaneous 34 54 OD Axial @ Freespan 118 54 Wear @ Support 103 55 OD Circ @ TSH 1
63 Prevent @ Miscellaneous 141 65 Wear @ Support 36 66 ID Axial below TSH 142 66 Wear @ Support 24 68 Wear @ Support 36 70 ID Axial below TSH 98 70 Wear @ Support 34 72 Wear @ Support 44 72 Wear @ Support 33 73 Wear @ Support 40 74 Wear @ Support 96 74 OD Axial @ Freespan 145 75 Wear @ Support 144 78 Wear @ Support 46 80 Wear @ Support 50 80 Wear @ Support 62 80 ID Circ @ TSH 102 80 Prevent @ Miscellaneous 49 81 Wear @ Support 59 83 Wear @ Support 59 85 Wear @ Support
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 9 of 12 TABLE 6 (CONT.) - SONGS U3C12 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 4) 50 88 Wear @ Support 84 88 Wear @ Support 61 89 Wear @ Support 65 89 Wear @ Support 54 90 Wear @ Support 62 90 Wear @ Support 146 90 Wear @ Support 51 91 Wear @ Support 59 91 Wear @ Support 61 91 Wear @ Support 54 92 Wear @ Support 56 92 Wear @ Support 55 93 Wear @ Support 61 93 Wear @ Support 54 94 Wear @ Support 147 95 Wear @ Support 53 97 ID Axial below TSH 146 98 Wear @ Support 48 100 Wear Q Support 41 101 Wear @ Support 33 103 Wear @ Support 37 103 Wear @ Support 39 103 Wear @ Support 103 103 OD Axial @ Freespan 144 104 Wear @ Support 22 108 Wear @ Support 37 109 ID Axial below TSH 49 109 ID Axial below TSH 32 110 ID Axial below TSH 126 110 Wear @ Support 37 111 ID Axial below TSH 49 113 ID Circ @ TSH
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 10 of 12 TABLE 6 (CONT.) - SONGS U3C12 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 4) 8 122 ID Circ below TSH 68 128 OD Vol @ Miscellaneous 11 129 ID Circ @ TSH 10 132 ID Circ @ TSH 10 136 ID Circ_ @ TSH 94 138 ID Circ below TSH 73 143 Wear @ Support 36 146 Wear @ Support 47 151 Wear @ Support
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 11 of 12 TABLE 7 -SONGS U3C12 Refueling Outage Tubes Plugged STEAM GENERATOR E-089 Row Column Reason for Plugging Tube (per Table 4) 50 22 Wear @ Support 41 31 Wear @ Support 31 41 ID Circ @ TSH 119 57 OD Axial @ Freespan 126 64 Wear @ Support 142 66 Wear @ Support 42 68 Wear @ Support 31 71 Wear @ Support 37 71 Wear @ Support 32 72 Wear @ Support 34 72 Wear @ Support 38 72 Wear @ Support 144 72 Wear @ Support 43 73 Wear @ Support 45 73 Wear @ Support 144 74 Wear @ Support 47 75 Wear @ Support 49 75 Wear @ Support 101 75 ID Circ @ TSH 53 77 Wear @ Support 46 78 Wear @ Support 126 78 Wear @ Support 146 78 Wear @ Support 79 81 Wear @ Support 52 82 Wear @ Support 146 82 Wear @ Support 53 83 Wear @ Support 59 85 Wear @ Support 54 88 Wear @ Support 54 90 Wear @ Support 56 90 Wear @ Support 97 91 Wear @ Support 54 92 Wear @ Support 79 93 Wear @ Support
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 12 of 12 TABLE 7 (CONT.) - SONGS U3C1 2 Refueling Outage Tubes Plugged STEAM GENERATOR E-089 Row Column Reason for Plugging Tube (per Table 4) 58 94 Wear @ Support 59 95 Wear @ Support 54 96 Wear @ Support 144 96 Wear @ Support 146 96 Wear @ Support 67 97 OD Axial @ Sludge Pile TSH 49 99 Wear @ Support 46 100 Wear @ Support 54 100 Wear @ Support 43 101 Wear @ Support 45 101 Wear @ Support 38 102 Wear @ Support 37 103 Wear @ Support 43 103 Wear @ Support 34 104 Wear @ Support 130 110 Wear @ Support 31 111 ID Axial below TSH 126 112 Wear @ Support 27 113 ID Axial below TSH 82 116 Wear @ Support 43 117 Wear @ Support 41 119 Wear @ Support 121 119 Wear @ Support 31 123 ID Circ below TSH 52 124 Wear @ Support 70 124 Wear @ Support 47 125 Wear @ Support 30 126 OD Circ @ TSH 34 128 OD Circ @ TSH 45 135 Wear @ Support 114 140 Wear @ Support 47 147 Wear @ Support 40 156 Wear @ Support
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 4 Appendix I Steam Generator Reference Information
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 2 of 4 Steam Generator CE Model 3410 Tube Support Drawing 1 OH 09H 08H 07H 06H 05H 04H 03H 02H 01H TSH TEl-
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 3 of 4 STEAM GENERATOR TUBE SUPPORT INTERSECTIONS ABOVE THE 7 TH (FULL) EGGCRATE SUPPORT
- Indicates those rows adjacent to scallop bars SUPPORT INTERSECTIONS ROW STRUCTURES 122-147 08H 09H 10H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 10C 09C 08C 120-121*
08H 09H 10H DBH VHI VH2 VH3 VSM VC3 VC2 VCI DBC 10C 09C 08C 115-119 08H 09H DBH VHI VH2 VH3 VSM VC3 VC2 VC1 DBC 09C 08C 86-114 08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 84-85*
08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 83 08H DBH VH2 VH3 VSM VC3 VC2 DBC 08C 51-82 08H DBH VH3 VSM VC3 DBC 08C 49-50*
08H DBH VSM DBC 08C 19-48 DBH VSM DBC 1-18 DBH DBC
6~ 00 0V0~000 00 O
OC0 0..
0.,00~C, 0
c
'000000 000 0000 0000 000000 00 O
O oG o
"l 9 oon 000 noo~'~
0000
.. 0
'O 000 oG 0VoQ0 co c<
O%%0 9
C0~0 000 000GOO 000 0
0e000G q) o0%%
0
~
%~
oo to
.00
.000 0 0Q00 Cu0!
0 0
1000 000~
o00
- 000, C0 Q0
__coo 0000000 0.0
'00 00, 0 C-r00
- 00~00 00 0
CL) 0000
-0o0000 0000 dc 00 oý 00ý 0
)000
)00'n 00 oO 3:..C '00 0
0100' c00 0
C 00,
" 600 601 00
- 00.
Go 00' 0
000 000 00to~OOO
~~o0
- ,0000 0000 0000 0000000 0000 0000 0000 0oo000 0000 00000 0000 00 0 000000 0 000 0
0 00000 0 00 0000%00 %Coo%
CP 0oC COOO 0000.0110 00 0
. 00 00C 0C 06C 00-60' 61 000 0
00 000000OO 0000 0009000 0000 0000 000
?OOCCOOC 000 C
0CO 00CC 00005I COO 000 0,0
.000. 090QC 0 k
100 0
0 o o o 0 0 0 0 0 00 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0,j 0 0 0
0 0-0 0 0 0 0 '
0
-3C.
30C,0
-~00 40
'000'000C 90 00:
O C
-0 lon
ý0O ooc4000 CO C
C OCC03C 0
00 00000' 000' G0 00.0 CC O C 0000 00000 0000o D00 0000000 000 0000000 00
>0000 00.00 VolC 000 Do0 000 000 G
0I 00000000.00 0C 00 "00>0 000 0G000 0O 30 0000.0.0 0000 "00CC 00 000-..
0000 000t I00.
a 00000CC
>C~
000 '000 0000- 0007 0000 0- 000 0000 000000000 0000Tý 0000 0000V 00 00 000f 000 00 00 00000CC0C 0C000
.%10-GOO Do 30..
00 00
'no.o4.*
G t 0 0~
94
~0-0 000 000 000 0000 000 00000~00 0
000 000 C00'00 00 0?
0 00 00 0300 C%%
C 0CCl 00C 1000 1%0T3.
<00 000300.0%O0%
00CC000aC0~0 Goo' I"
00 000 0000 000..09 C
loot 300CCo 000
- ~
~
(O aOC Go0 000 00 00 000 0C 0.00
'.00 COO 000C 00300.
33
.3v CCQ 00 CC00 0000 000 000 1.00000-1 00 0 00.00 4
.00
.'No LL
.0
.30 000 0C 000 0000 Z 000 0 000000000000 0000000 Door n
0.0 00 00 0000 0000 0000 0000 000C 0003 o000o 000) 000"p 0ýO or 0
9000 0
'Dcoo~0 7 o
00 0'
o p ?co no-,00
'~~I~
00,00C 0000 OO 00 0
.0 L..
0 U.
Wo:.
0C O
c0 oo oA ooo o
o o
o o
oo' 2
-~~~o 0Q QQQC 000ooW030 00 CCCCO' 00oCC o~0c00 Cl)%o o~o%
9oo oco o0-0 o
%3
%0 olO "Zc coo< Doooooo coo Q00000 Go0%
wo~ oo 0oocc 0o0 a'
00 o~~~
o in WU co
~
~
a
.ao..
Do.
coo,~ ()
00009f000 000 0
000 C,,ý 3Doo
?~%
~
o o
,%z~9%
oo 0003O 000 0000 00 o
0 oo 00000 0000'00'00 009too o..oo' oZo 3000o o00 o 0
0003. '000 000.0)003 Go0 003o0 in (o)
O< >o0 p30c 000' Co O
L 0003 z.
0000o o
OG 0
00 o
OO 000 0000 000 o
0C 00 0o0 Goo 00 c
0 o
I-~~~~Q 0000Q 000 000 00o o00 000 o00 I30 0
0 000 QOOC 0000 00' G0O 000 00 0000o 000CCP 00 000)00:
>U08 Go0 00o 000 0u.
o00 000 0000 jo 3l D
0 Door 00 c"'t300.
00CCo o
0 00
.303
- o0.'
00 0000 000 000 0000000 0000 00o 000000 0000 0o L33 000C o00 000 Go00 o%
003 300 00'000) 000 00C00 Co:' 0000 00 0
C 00 0
ooC 000)0 00 000000 ooC-q ooo
- o.
000 0000w~
OGG<
0000 00004 0030330't30no0 0004 0004 0403 Goo.+3.0 o04 0'-0 Do Goo c
rU),o6oo 000 000 00000 oo D
00 000 0
0 c
O:'
c c 000 00000 o-0 000
?o0000 CoiO 0Do03
~C 00.0C 040000 iow aQQ 00C33'0 0%0 o0 00 0'
0000oýco o.ý aý;_Z o
o Go 000 0'C 0000.000 000 00
(
a)~~30 30404 o
ý3000C 3000 cc....
Go
.?cc<>
0000000 0000o O o o
c o
c, c
G ICI G
I o
r 3
-0000o onoEN G)
Do oo 2
a a
9 a
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 2 Appendix 2 Legend for Appendices 3 and 4
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 2 of 2 List of Abbreviations and Format Used to Describe Indications from Rotating Probe Testing "I-Code" Abbreviations Explanation of the Abbreviations SC!
Single Circumferential Indication MCI Multiple Circumferential Indications SAI Single Axial Indication MAI Multiple Axial Indications MMI Mixed Mode Indications SVI Single Volumetric Indication (i.e. no special axial or circumferential aspect)
MVI Multiple Volumetric Indications (i e. no special axial or circumferential aspect)
Format In Appendices 3 and 4, a single line of data is associated with each individual rotating probe indication. Below is a descriptive example of the format.
- 1. All "I-Code" indications require a single line entry. The example above displays the form of a Resolution Report line The VOLTS field contains the Plus-Point P-to-P voltage of the largest, most representative response. The DEG field contains the corresponding phase angle The CHN field contains the reporting channel (i e. the appropriate 300kHz Plus-Point channel) The IND field contains the appropriate 3-letter code (see list above). The %TW field indicates the percent wall loss for wear indications The LOCATION field contains the abbreviation for the referenced landmark and the (FROM-TO) distance for the indication The EXT fields contain the landmarks of the beginning and end of the test extent. The UTIL 1 field contains the 300kHz pancake P-to-P voltage of the largest, most representative response. The UTIL 2 field was used to document the actual inspection distance below the hot leg top-of-tubesheet for applicable inspections. Exceptions to this general guidance are provided in paragraphs 2 through 4 below.
- 2.
For axial indications of extended length, the location should be ranged (FROM-TO) in the LOCATION field If the range of such an indication includes any part of a support structure, it should be references from that landmark
- 3.
For "I-Code" indications which have both axial and circumferential extent (i e. SVI, MVI, and MMI), the location should be ranged in the LOCATION field (as above) and the UTIL 2 field should contain the circumferential length.
- 4.
Some data lines contain a note abbreviation in the Util 1 column. These are the definitions of these abbreviations NEW. Result of re-analysis of the data LAR: Lead Analyst Reviewed LOCOK: Location Verification
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 46 Appendix 3 Inspection Summary Steam Generator E-088
0 10,
'0 0~
04 N
CD D-D-4D4-N ND-N4 4 D 0000 a, a, a, a, Ca Ca Ca Ca
%Dw I ID 00 I0 00
.I 00ý 00 I 00 to to I to to 00 iO0 IU.-2 0
II 0d II NII to 13 II-H 0
.-11:
0 II N
II 1 0
00 a, a, a, Ca Ca Ca N3 N',
0 0
Ca C) CD 00 to to o0 to to 0
U IO I 0 a
l0 10 IO I In Ca
'C:
HD 0a a,
0 to I CaW I HH E
I CaYa I> 00 I ++
LO ')
I 00 C.
I nIn 02
.4 0
a, to a,
+
- Ca 0~
co Hn c,4 u u E-E to I Ca Ca cN 100)
I CaW I HH I N H
-r*
0 Ca H
Ea Ca u
H 1o I0 I I l0 H
I0 I Hý 10 Ca N
0
+
E0 Ca H
0>
H HH i H HHH 0001 0000 Caa-I Caý~~
tot o I a, aaa Ca Ca Ca H H-H H H) N~ N I 000N Ca U) al M *)E)V CaaaI E-4H E HEa HHH 41
-HHHHi HH I HH I a, a, Ca I H a, a, In CI a
C 04Nt I
I 04I a,'
I D I
I o I
I n I
1-01
'E11I I
I; I Mn IN 04 a,
Ca 0
zD to4 Ný a,
Ca H
Ca HO I
I I
I 1.41 IOl 101 I 0 I
I to I I
I I
I I
I 101 I,-) I 101 101 I
I I
I I
I I 0 I
I to I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I 101
'Cal HI I
I WI HI I
I I
I I
I I
I I
I I
I I
I Ia, I
I H I
I
- I I H I
I I
I I
I I
I I
I I
Hz' IN I
I 0 I
Ca I I H I
iO I
'Cal H
I N D
IN I to I to I In I 0 I a, I N I H I H 0
I 0
I to I
- 0) w
,.4 E
0l In 0
Ca 00 I
toto I, O00 O00 I 00I I
C
- a IrHH I I
z I Cat I~
I H I
I I
I OIOI I
I I
I I
I I
I
,-r, I
I I I I
I I.
I.
00 1
to to I 01 0
I
.41 OIE OI I
Iý 0
3PI I
I 00 I
00D 00 I 001 a, a, I N001 0E' IN HH I4 N4 NI
- 1 o
Ho HLI Iý II 001 CC)co a, P, I H
I Ný NI 001 Ca1a 00C I 0D to to I to 00 I a 14.4 I.4 0010 H H4 IC0 to to I to HHW I H HH EI H
00 CI 0
00 I0 IN 004 04 4
0 1 10 0 a, to Co 100 I 00 I
00 I) tot I.L4-4 140W I In In
> >Q I n In)
I 4 00 I~ Cat.
I 00 P00 I
l EA M I Iý I 00a a, IH H I* Ca1a I 4 HH I1 N N I-NN I0 H IH In I N 00 u 0 C00 I 00) 00 I..
I)
E.4, I H am C4000 I HO IDH I I I 0"I 0 I
.4 11 0 H
11 a, Ra II Ca O
1N 0 II Ca II Cai dO H
In 0
- 0) ou 4.)
H ro D
"I zo u
0 H
0 (0 0 Ca U) 13 S
[.4 H
a CD C- 0 1
0000 1
0000I Sto to to I
0)0001 I u u--I.4
+
I I x I
II ICaC\\31')Ca" I
I A H
EHH I I
I N
I v CE) 1.2W I I
Il H H 00 N
Hq In9 0
CN In N~
C)00 Ca4 0
I 00C I 0
1 00D I w0 I to to I 0
00 U
U) U to o
o 00 w
00 0
I 00C
+
I++"t I 0 a, I-Ca Hq I0H 0o 10041 HI H I 0a 0 lI NN HH N 1 0N IC I I II I,
E-,El E-,El 0 00 00 I Ca*
C:a::a M~ Io CDW HH I HHE L)~
I C-) a r.. r..
r' *M N NCI Ca C
N N4 I1 N"
++
I ++
N N I n n NW N
)00 In Ca4 N1 N a,
N
Framatome ANP Inc.
01/26/2003 10:53:29 Am Customer Name: SONGS Unit 3 Component: S/G 88 Page 3 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 28 54 0.32 115 P 2 TWD 12 06H
+0.10 TEH TEC 26 COLD 600UL 28 122 0.42 92 P 2 TWD 16 01H
+0.90 TEH TEC 62 COLD 60OUL 28 172 0.61 101 P 2 TWD 18 01C
+0.10 TEH TEC 39 COLD 600UL 29 13 0.35 135 P 2 TWD 16 DBH
+0.75 TEC TEH NEW 80 HOT 600UL 29 107 0.43 148 P 2 TWD 16 DBH
-1.60 TEH TEC 48 COLD 600UL 0.43 148 P 2 TWD 16 DBH
-1.60 TEH TEC 48 COLD 600UL 30 126 0.39 41 P 2 TWD 17 02H
-1.24 TEH TEC 60 COLD 600UL 30 166 0.26 19 P 2 TWD 10 DBH
+1.83 TEH TEC 36 COLD 600UL 0.26 19 P 2 TWD 10 DBH
+1.83 TEH TEC 36 COLD 600UL 30 172 0.44 43 P 2 TWD 16 06H
+0.95 TEH TEC 38 COLD 60OUL 31 39 0.27 125 P 2 TWD 12 07H
+0.60 TEC TEH 93 HOT 600UL 0.27 125 P 2 TWD 10 07H
+0.60 TEC TEH 93 HOT 600UL 31 161 0.30 162 P 2 TWD 11 DBH
+1.75 TEH TEC 36 COLD 600UL 0.29 163 P 2 TWD 11 DBH
+1.75 TEH TEC 36 COLD 600UL 31 167 0.48 148 P 2 TWD 14 DBH
+0.90 TEH TEC NEW 39 COLD 600UL 32 42 0.27 74 P 2 TWD 11 07H
+0.72 TEC TEH 95 HOT 600UL 0.31 102 P 2 TWD 12 07H
+0.72 TEC TEH 95 HOT 600UL 32 106 0.35 142 P 2 TWD 13 04C
+0.90 TEH TEC 48 COLD 600UL 32 110 0.38 18 2
SAI TSH
-0.61 TSH TSH
.71 56 HOT 580PP 0.69 18 2
MAI TSH
-1.53 TSH TSH
.57 8.89 56 HOT 58OPP 32 124 0.56 136 P 2 TWD 18 VSM
-0.88 TEH TEC 44 COLD 600UL 0.56 137 P 2 TWD 18 VSM
-0 88 TEH TEC 44 COLD 600UL 33 43 0.20 107 P 2 TWD 8 07H
+0.72 TEC TEH 95 HOT 600UL 0.20 107 P 2 TWD 8 07H
+0.72 TEC TEH 95 HOT 600UL 33 73 1.12 105 P 2 TWD 31 DBC
-2.06 TEH TEC 22 COLD 600UL 1.40 99 P 6 TWD 50 DBC
-2.08 DBC DBC LAR 130 COLD 580FH 1.17 107 P 2 TWD 32 DBC
-2.06 TEH TEC 22 COLD 600UL 33 103 1.09 107 P 2 TWD 30 DBH
+1.84 TEH TEC 48 COLD 60OUL 0.45 129 P 2 TWD 16 DBC
+1.47 TEH TEC 48 COLD 600UL 0.47 138 P 2 TWD 17 DBC
+1.47 TEH TEC 48 COLD 60OUL 1.09 107 P 2 TWD 30 DBH
+1.84 TEH TEC 48 COLD 600UL 33 125 0.39 64 P 2 TWD 17 02H
-1.14 TEH TEC 60 COLD 600UL 34 54 0.11 101 2 SAI 02H
-2.31 02H 02H 0.35 129 HOT 580PP 34 72 0.79 87 P 2 TWD 25 DBH
-1.96 TEH TEC 22 COLD 600UL 0.78 86 P 2 TWD 26 DBH
-1.96 TEH TEC 22 COLD 600UL 34 108 0.27 121 P 2 TWD 11 07H
-0.12 TEH TEC 48 COLD 600UL 0.32 77 P 2 TWD 12 07H
-0.12 TEH TEC 48 COLD 60OUL 34 112 0.32 47 P 2 TWD 14 VSM
+0.81 TEH TEC 49 COLD 60OUL 0.31 47 P 2 TWD 14 VSM
+0.81 TEH TEC 49 COLD 600UL 34 128 0.28 130 P 2 TWD 12 VSM
+0.79 TEH TEC NEW 60 COLD 600UL 34 172 0.72 89 P 2 TWD 23 VSM
+0.76 TEH TEC 38 COLD 600UL 0.72 90 P 2 TWD 22 VSM
+0.76 TEH TEC 38 COLD 600UL 35 7
0.28 61 P 2 TWD 13 VSM
-1.11 TEC TEH 81 HOT 600UL 0.28 51 P 2 TWD 13 VSM
-1.11 TEC TEH 81 HOT 600UL 35 53 0.33 87 P 2 TWD 15 VSM
-0.70 TEH TEC NEW 27 COLD 600UL 35 107 0.28 152 P 2 TWD 13 VSM 0.35 143 P 2 TWD 15 VSM
+0.00 TEH TEC
-0.66 TEH TEC 49 COLD 600UL 49 COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:29 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 4 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.35 143 P 2 TWD 15 VSM
-0.66 TEH TEC 49 COLD 600UL 0.28 152 P 2 TWD 13 VSM
+0.00 TEH TEC 49 COLD 600UL 35 121 0.35 133 P 2 TWD 13 05H
+0.79 TEH TEC 46 COLD 60OUL 37 57 0.37 143 P 2 TWD 16 VSM
-0.02 TEH TEC 27 COLD 600UL 0.37 143 P 2 TWD 16 VSM
-0.02 TEH TEC 27 COLD 600UL 37 103 0.54 140 P 2 TWD 21 VSM
-0.84 TEH TEC 49 COLD 600UL 0.54 140 P 2 TWD 21 VSM
-0.84 TEH TEC 49 COLD 600UL 1.41 27 P 2 TWD 36 DBH
+1.72 TEH TEC NEW 49 COLD 600UL 37 105 0.31 71 P 2 TWD 12 DBH
+1.63 TEH TEC NEW 48 COLD 600UL 37 109 0.39 17 2
SAI TSH
-2.21 TSH TSH
.21 56 HOT 580PP 0.57 20 2
SAI TSH
-2.81 TSH TSH
.79 8.74 56 HOT 58OPP 37 111 0.85 24 2
MAI TSH
-5.04 TO-1.19 TSH TSH 1.32 8.87 57 HOT 580PP 37 127 0.52 102 P 2 TWD 17 VSM
-0.93 TEH TEC NEW 44 COLD 600UL 37 143 0.56 96 P 2 TWD 19 01H
+0.82 TEH TEC 33 COLD 600UL 37 147 0.32 116 P 2 TWD 16 VSM
+0.81 TEH TEC 32 COLD 60OUL 0.32 116 P 2 TWD 16 VSM
+0.81 TEH TEC 32 COLD 600UL 38 104 0.25 52 P 2 TWD 12 DBH
-1.73 TEH TEC NEW 49 COLD 600UL 35 125 0.31 158 P 2 TWD 11 VSM
-0.80 TEH TEC 44 uuCu ouuuL 0.51 128 P 2 TWD 17 VSM
+0.87 TEH TEC 44 COLD 600UL 0.34 161 P 2 TWD 12 VSM
-0.80 TEH TEC 44 COLD 60OUL 0.51 130 P 2 TWD 17 VSM
+0.87 TEH TEC 44 COLD 600UL 36 30 0.39 156 P 2 TWD 17 VSM
-0.70 TEC TEH 88 HOT 600UL 0.38 155 P 2 TWD 17 VSM
-0.70 TEC TEH 88 HOT 60OUL 36 46 0.35 121 P 2 TWD 14 VSM
+0.63 TEC TEH 95 HOT 60OUL 0.25 34 P 2 TWD 11 VSM
-0.58 TEC TEH 95 HOT 600UL 0.30 127 P 2 TWD 12 07H
-0.38 TEC TEH 95 HOT 600UL 0.36 122 P 2 TWO 14 VSM
+0.63 TEC TEH 95 HOT 600UL 0.26 36 P 2 TWD 10 VSM
-0.58 TEC TEH 95 HOT 600UL 0.30 127 P 2 TWD 12 07H
-0.38 TEC TEH 95 HOT 600UL 36 50 0.25 157 P 2 TWD 9 07H
+0.96 TEH TEC 26 COLD 600UL 0.43 42 P 2 TWD 15 07H
+0.43 TEH TEC 26 COLD 600UL 0.43 42 P 2 TWD 15 07H
+0.43 TEH TEC 26 COLD 60OUL 0.24 159 P 2 TWD 9 07H
+0.96 TEH TEC 26 COLD 600UL 36 52 0.30 44 P 2 TWD 13 06H
+0.43 TEH TEC 27 COLD 60OUL 36 66 0.62 16 2
MAI TSH
-5.08 TO-1.34 TSH TSH 0.74 8.24 102 HOT 580PP 0.79 113 P 2 TWD 24 VSM
-0.94 TEH TEC 24 COLD 600UL 0.79 116 P 2 TWD 25 VSM
-0.94 TEH TEC 24 COLD 600UL 36 70 0.37 16 2
SAI TSH
-2.91 TSH TSH 0.54 9.31 101 HOT 580PP 0.41 21 2
SAI TSH
-2.55 TSH TSH 0.46 101 HOT 580PP 36 108 0.46 123 P 2 TWD 19 VSM
-0.14 TEH TEC 49 COLD 600UL 0.52 107 P 2 TWD 21 VSM
-0.72 TEH TEC 49 COLD 600UL 0.52 107 P 2 TWO 20 VSM
-0.72 TEH TEC 49 COLD 600UL 0.42 113 P 2 TWD 17 VSM
-0.14 TEH TEC 49 COLD 600UL 36 112 0.76 143 P 2 TWD 24 VSM
+0.66 TEH TEC 48 COLD 600UL 0.28 135 P 2 TWD 11 VSM
-0.70 TEH TEC 48 COLD 600UL 0.28 126 P 2 TWD 11 VSM
-0.70 TEH TEC 48 COLD 600UL 0.76 143 P 2 TWD 24 VSM
+0.66 TEH TEC 48 COLD 600UL 36 146 1.28 123 P 2 TWD 35 VSM
+0.81 TEH TEC 32 COLD 600UL 1.26 130 P 2 TWD 34 VSM
+0.81 TEH TEC 32 COLD 600UL 37 43 0.55 67 P 2 TWD 20 VSM
+0.67 TEC TEH 95 HOT 600UL 0.55 72 P 2 TWD 19 VSM
+0.67 TEC TEH 95 HOT 600UL 37 51 0.44 58 P 2 TWO 19 07H
+0.43 TEH TEC 27 COLD 600UL 0.44 58 P 2 TWD 19 07H
+0.43 TEH TEC 27 COLD 60OUL
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 5 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 38 106 0.17 54 P 2 TWD 8 VSM
-0.07 TEH TEC 49 COLD 600UL 0.17 54 P 2 TWD 8 VSM
-0.07 TEH TEC 49 COLD 600UL 0.34 100 P 2 TWD 15 VSM
+0.94 TEH TEC 49 COLD 60OUL 0.36 98 P 2 TWO 15 VSM
+0.94 TEH TEC 49 COLD 600UL 38 170 0.27 89 P 2 TWD 11 01H
-0.09 TEH TEC 38 COLD 600UL 39 53 0.34 143 P 2 TWD 15 VSM
+0 67 TEH TEC NEW 27 COLD 600UL 39 65 0.35 128 P 2 TWD 14 VSM
+0.89 TEH TEC 25 COLD 600UL 0.35 133 P 2 TWD 14 VSM
+0.89 TEH TEC 25 COLD 60OUL 39 67 0.46 102 P 2 TWD 17 VSM
-0.64 TEH TEC 25 COLD 60OUL 0.43 107 P 2 TWD 16 VSM
+0.80 TEH TEC 25 COLD 60OUL 0.46 102 P 2 TWD 17 VSM
-0.64 TEH TEC 25 COLD 600UL 0.44 108 P 2 TWD 17 VSM
+0.80 TEH TEC 25 COLD 60OUL 39 103 0.80 88 P 2 TWD 25 DBH
+1.87 TEH TEC NEW 48 COLD 600UL 39 131 0.38 106 P 2 TWD 15 VSM
+0.27 TEH TEC 34 COLD 600UL 39 153 0.40 146 P 2 TWD 13 VSM
+1.08 TEH TEC 37 COLD 600UL 0.38 144 P 2 TWD 14 VSM
+1.08 TEH TEC 37 COLD 600UL 40 38 0.42 112 P 2 TWD 17 VSM
+0.73 TEC TEH 93 HOT 600UL 0.29 138 P 2 TWD 13 VSM
-0.82 TEC TEH 93 HOT 600UL 0.42 112 P 2 TWD 17 VSM
+0.73 TEC TEH 93 HOT 600UL 0.24 124 P 2 TWD 11 VSM
-0.82 TEC TEH 93 HOT 600UL 40 62 0.54 119 P 2 TWD 20 VSM
+0.71 TEH TEC 25 COLD 600UL 0.54 119 P 2 TWD 20 VSM
+0.71 TEH TEC 25 COLD 600UL 40 68 0.97 63 P 2 TWD 28 VSM
+0.75 TEH TEC 24 COLD 600UL 0.42 146 P 2 TWD 16 VSM
-0.81 TEH TEC 24 COLD 600UL 1.00 69 P 2 TWD 28 VSM
+0.75 TEH TEC 24 COLD 60OUL 0.42 143 P 2 TWD 16 VSM
-0.81 TEH TEC 24 COLD 600UL 40 74 0.86 96 P 2 TWD 28 DBC
+1.43 TEH TEC 23 COLD 600UL 0.36 121 P 2 TWD 16 VSM
+0.80 TEH TEC 23 COLD 600UL 0.36 124 P 2 TWD 16 VSM
+0.80 TEH TEC 23 COLD 600UL 0.86 96 P 2 TWD 28 DBC
+1.43 TEH TEC 23 COLD 600UL 40 104 0.56 156 P 2 TWD 19 VSM
+0.88 TEH TEC 48 COLD 600UL 0.56 158 P 2 TWD 19 VSM
+0.88 TEH TEC 48 COLD 60OUL 40 122 0.31 105 P 2 TWD 12 07H
-0.42 TEH TEC 62 COLD 600UL 0.31 105 P 2 TWD 12 07H
-0.42 TEH TEC 62 COLD 60OUL 41 73 0.39 115 P 2 TWD 16 DBH
-1.54 TEH TEC 23 COLD 600UL 0.39 124 P 2 TWD 16 DBH
-1.54 TEH TEC 23 COLD 600UL 41 101 0.68 77 P 2 TWD 24 DBH
-2.19 TEC TEH 90 HOT 600UL 0.71 77 P 2 TWD 25 DBH
-2.19 TEC TEH 90 HOT 600UL 41 129 0.59 21 P 2 TWD 22 DBH
+1.66 TEH TEC 60 COLD 60OUL 0.59 21 P 2 TWD 22 DBH
+1.66 TEH TEC 60 COLD 600UL 42 74 0.64 97 P 2 TWD 22 DBH
-1.76 TEH TEC 22 COLD 60OUL 0.63 96 P 2 TWD 22 DBH
-1.76 TEH TEC 22 COLD 600UL 42 124 0.31 93 P 2 TWD 12 01H
+0.78 TEH TEC 61 COLD 600UL 42 128 0.36 103 P 2 TWD 16 01H
+0.72 TEH TEC 60 COLD 600UL 43 5
0.59 109 P 2 TWD 23 04C
-0.13 TEC TEH 80 HOT 600UL 43 9
0.21 56 P 2 TWD 11 VSM
-0.88 TEC TEH 81 HOT 600UL 0.21 56 P 2 TWD 11 VSM
-0.88 TEC TEH 81 HOT 600UL 43 13 0.34 136 P 2 TWD 15 VSM
-0.83 TEC TEH 81 HOT 600UL 0.34 136 P 2 TWD 15 VSM
-0.83 TEC TEH 81 HOT 600UL 43 21 0.28 126 P 2 TWD 13 VSM
+0.80 TEC TEH 85 HOT 60OUL 0.28 126 P 2 TWD 13 VSM
+0.80 TEC TEH 85 HOT 600UL
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 6 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 43 53 0.24 149 P 2 TWD 11 VSM
+0.02 TEH TEC 27 COLD 600UL 0.54 138 P 2 TWD 21 VSM
+0.83 TEH TEC 27 COLD 600UL 0.54 138 P 2 TWO 21 VSM
+0.83 TEH TEC 27 COLD 600UL 0.24 149 P 2 TWD 12 VSM
+0.02 TEH TEC 27 COLD 60OUL 43 133 0.29 46 P 2 TWO 15 02H
-1.18 TEH TEC 32 COLD 600UL 43 149 0.61 70 P 2 TWD 24 VSM
+0.85 TEH TEC 32 COLD 600UL 0.61 70 P 2 TWD 24 VSM
+0.85 TEH TEC 32 COLD 600UL 44 72 1.03 101 P 2 TWD 30 VSM
-0 77 TEH TEC 22 COLD 600UL 1.03 101 P 2 TWD 30 VSM
-0.77 TEH TEC 22 COLD 600UL 44 74 0.30 44 P 2 TWD 13 DBH
-1.39 TEH TEC 23 COLD 600UL 0.20 128 P 2 TWD 10 DBC
+2.13 TEH TEC NEW 23 COLD 600UL 0.33 65 P 2 TWO 14 DBH
-1.39 TEH TEC 23 COLD 600UL 44 100 0.39 146 P 2 TWO 16 DBH
+1.62 TEC TEH 90 HOT 600UL 0.62 68 P 2 TWD 23 DBH
-1.71 TEC TEH 90 HOT 600UL 0.38 147 P 2 TWD 16 DBH
+1.62 TEC TEH 90 HOT 600UL 0.62 64 P 2 TWD 23 DBH
-1.71 TEC TEH 90 HOT 600UL 44 108 0.51 119 P 2 TWD 20 VSM
-0.21 TEH TEC 49 COLD 600UL 0.59 121 P 2 TWD 22 VSM
-0.83 TEH TEC 49 COLD 600UL 0.59 123 P 2 TWD 22 VSM
-0.83 TEH TEC 49 COLD 600UL 0.52 115 P 2 TWD 20 VSM
-0.21 TEH TEC 49 COLD 600UL 44 110 0.40 148 P 2 TWD 15 VSM
+0.82 TEH TEC 48 COLD 600UL 0.42 139 P 2 TWD 15 VSM
+0.82 TEH TEC 48 COLD 60OUL 44 130 0.46 67 P 2 TWD 16 02H
-1.16 TEH TEC 35 COLD 600UL 44 154 0.39 51 P 2 TWD 14 VSM
+0.70 TEH TEC 37 COLD 60OUL 0.39 51 P 2 TWO 14 VSM
+0.70 TEH TEC 37 COLD 600UL 45 65 0.37 147 P 2 TWD 14 02H
-1.18 TEH TEC 24 COLD 600UL 45 75 0.31 145 P 2 TWD 13 DBC
-2.11 TEH TEC 22 COLD 600UL 0.31 145 P 2 TWD 13 DBC
-2.11 TEH TEC 22 COLD 600UL 45 101 0.38 117 P 6 TWD 22 DBC
-1.75 DBC DBC LAR 130 COLD 580FH 0.37 175 P 2 TWD 16 DBH
+1.49 TEC TEH NEW 90 HOT 600UL 0.40 83 P 2 TWD 17 DBC
-1.75 TEC TEH NEW 90 HOT 600UL 46 78 0.22 100 P 2 TWD 10 DBH
-1.87 TEH TEC NEW 23 COLD 600UL 46 80 0.39 117 P 2 TWD 17 DBH
-1.84 TEH TEC NEW 23 COLD 60OUL 0.60 105 P 6 TWD 28 DBH
-1.72 TO+1.73 DBH DBH LAR 131 COLD 580FH 46 100 0.62 27 P 2 TWD 23 DBH
+1.70 TEC TEH NEW 90 HOT 600UL 46 118 0.21 109 P 2 TWD 9 07H
+0.28 TEH TEC 62 COLD 600UL 0.21 109 P 2 TWD 9 07H
+0.28 TEH TEC 62 COLD 600UL 47 73 0.48 111 P 2 TWD 18 DBC
-2.03 TEH TEC 22 COLD 600UL 0.47 109 P 2 TWD 18 DBC
-2.03 TEH TEC 22 COLD 600UL 47 77 0.33 126 P 2 TWD 14 DBC
-1.48 TEH TEC 23 COLD 600UL 0.36 123 P 2 TWD 16 DBC
-1.48 TEH TEC 23 COLD 600UL 47 101 0.46 108 P 6 TWO 23 DBH
-2.20 DBH DBH LAR 131 COLD 580FH 0.41 78 P 2 TWD 17 DBC
-1.59 TEC TEH 90 HOT 60OUL 0.36 99 P 2 TWD 15 DBH
-2.20 TEC TEH NEW 90 HOT 600UL 0.41 78 P 2 TWD 17 DBC
-1.59 TEC TEH 90 HOT 600UL 47 109 0.35 49 P 2 TWD 13 VSM
-0.14 TEH TEC 48 COLD 600UL 0.33 44 P 2 TWD 13 VSM
-0.14 TEH TEC 48 COLD 600UL 47 113 0.40 91 P 2 TWD 17 VSM
-0.84 TEH TEC 49 COLD 600UL 0.52 120 P 2 TWD 20 VSM
-0.04 TEH TEC 49 COLD 600UL 0.71 122 P 2 TWD 25 VSM
+0.78 TEH TEC 49 COLD 600UL 0.17 48 P 2 TWO 8 DBC
-1.69 TEH TEC NEW 49 COLD 600UL 0.39 73 P 2 TWD 16 VSM
-0.84 TEH TEC 49 COLD 600UL 0.68 122 P 2 TWD 24 VSM
+0.78 TEH TEC 49 COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 7 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.52 120 P 2 TWD 20 VSM
-0.04 TEH TEC 49 COLD 600UL 47 151 1.39 129 P 2 TWD 34 VSM
-0.69 TEH TEC 33 COLD 600UL 1.79 84 P 2 TWD 38 VSM
-0.04 TEH TEC 33 COLD 600UL 1.29 101 P 2 TWD 32 VSM
+0.81 TEH TEC 33 COLD 600UL 1.39 129 P 2 TWD 34 VSM
-0.69 TEH TEC 33 COLD 60OUL 1.79 84 P 2 TWD 38 VSM
-0.04 TEH TEC 33 COLD 600UL 1.29 101 P 2 TWD 32 VSM
+0.81 TEH TEC 33 COLD 60OUL 48 42 0.22 127 P 2 TWO 8 07H
-0.75 TEC TEH 95 HOT 600UL 0.22 127 P 2 TWD 9 07H
-0.75 TEC TEH 95 HOT 60OUL 48 68 0.26 72 P 2 TWD 10 VSM
+0.90 TEH TEC 24 COLD 600UL 0.26 72 P 2 TWD 10 VSM
+0.90 TEH TEC 24 COLD 600UL 48 80 0.50 85 P 2 TWD 19 DBH
-1.51 TEH TEC 22 COLD 600UL 0.49 76 P 2 TWD 18 DBH
-1.51 TEH TEC 22 COLD 600UL 0.20 47 P 2 TWD 8 DBC
-2.25 TEH TEC NEW 22 COLD 600UL 48 100 1.35 117 P 2 TWD 35 VSM
+0.77 TEC TEH 90 HOT 600UL 1.52 85 P 2 TWD 37 VSM
-0.04 TEC TEH 90 HOT 600UL 1.48 124 P 2 TWD 37 VSM
-0.69 TEC TEH 90 HOT 60OUL 0.51 175 P 2 TWD 20 DBH
+1.47 TEC TEH 90 HOT 60OUL 1.35 117 P 2 TWD 35 VSM
+0.77 TEC TEH 90 HOT 600UL 1.52 85 P 2 TWD 37 VSM
-0.04 TEC TEH 90 HOT 600UL 1.48 124 P 2 TWD 37 VSM
-0.69 TEC TEH 90 HOT 600UL 0.51 175 P 2 TWD 20 DBH
+1.47 TEC TEH 90 HOT 600UL 48 104 0 53 121 P 2 TWD 15 VSM
+0.86 TEH TEC 53 COLD 600UL 0.54 118 P 2 TWD 16 VSM
+0.86 TEH TEC 53 COLD 60OUL 48 106 0.58 90 P 2 TWD 16 VSM
+0.00 TEH TEC 53 COLD 600UL 0.57 121 P 2 TWD 16 VSM
+0.84 TEH TEC 53 COLD 600UL 0.41 119 P 2 TWD 12 VSM
-0.78 TEH TEC 53 COLD 60OUL 0.41 119 P 2 TWO 12 VSM
-0.78 TEH TEC 53 COLD 60OUL 0.43 97 P 2 TWD 13 VSM
+0.00 TEH TEC 53 COLD 60OUL 0.58 119 P 2 TWD 16 VSM
+0.84 TEH TEC 53 COLD 600UL 48 112 1.06 102 P 2 TWD 29 VSM
+0.82 TEH TEC 48 COLD 600UL 0.49 107 P 2 TWD 18 VSM
-0.02 TEH TEC 48 COLD 600UL 1.06 97 P 2 TWD 29 VSM
+0.82 TEH TEC 48 COLD 600UL 0.49 107 P 2 TWD 18 VSM
-0.02 TEH TEC 48 COLD 600UL 48 126 0.69 141 P 2 TWD 21 VSM
+1.00 TEH TEC 44 COLD 600UL 0.69 141 P 2 TWD 21 VSM
+1.00 TEH TEC 44 COLD 600UL 48 128 0.63 138 P 2 TWD 19 VSM
-0.72 TEH TEC 44 COLD 600UL 0.72 107 P 2 TWD 21 VSM
+0A20 TEH TEC 44 COLD 600UL 0.63 138 P 2 TWD 19 VSM
-0.72 TEH TEC 44 COLD 600UL 0.65 100 P 2 TWD 20 VSM
+0.20 TEH TEC 44 COLD 60OUL 48 152 0.68 105 P 2 TWD 25 VSM
-0.60 TEH TEC 32 COLD 600UL 0.70 104 P 2 TWD 26 VSM
-0.60 TEH TEC 32 COLD 600UL 48 154 0.42 117 P 2 TWD 15 VSM
+0.78 TEH TEC 37 COLD 600UL 0.42 117 P 2 TWD 15 VSM
+0.78 TEH TEC 37 COLD 600UL 49 7
0.26 133 P 2 TWD 12 06H
-1.11 TEC TEH 80 HOT 600UL 49 41 0.65 119 P 2 TWD 23 08H
+1.45 TEC TEH LOCOK 93 HOT 600UL 0.65 119 P 2 TWO 23 08H
+1.45 TEC TEH LOCOK 93 HOT 600UL 49 43 0.32 84 P 2 TWD 13 08H
+1.45 TEC TEH LOCOK 95 HOT 60OUL 0.47 116 P 2 TWD 17 08H
-1.39 TEC TEH LOCOK 95 HOT 600UL 0.32 84 P 2 TWD 12 08H
+1.45 TEC TEH LOCOK 95 HOT 600UL 0.47 115 P 2 TWD 17 08H
-1.39 TEC TEH LOCOK 95 HOT 60OUL 49 49 0.27 133 P 2 TWD 10 08H
-1.43 TEH TEC 29 COLD 600UL 0.43 122 P 2 TWD 16 08H
+1.67 TEH TEC 29 COLD 600UL 0.38 97 P 2 TWD 14 08C
-1.67 TEH TEC 29 COLD 600UL 0.43 123 P 2 TWD 16 08H
+1.67 TEH TEC LOCOK 29 COLD 600UL 0.27 135 P 2 TWD 10 08H
-1.43 TEH TEC LOCOK 29 COLD 60OUL 0.33 103 P 2 TWD 12 08C
-1.67 TEH TEC LOCOK 29 COLD 600UL S..................................................------------------------------------------...
22 COLD 600UL
-0.89 TEH TEC 49 77 0.36 86 P 2 TWD 14 06H
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 8 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY:
rpcicodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 49 81 0.92 91 P 2 TWD 28 DBC
+1.98 TEH TEC 22 COLD 60OUL 0.92 91 P 2 TWD 28 DBC
+1.98 TEH TEC 22 COLD 600UL 49 101 0.36 127 P 2 TWD 15 DBH
-2.03 TEC TEH 90 HOT 60OUL 0.36 128 P 2 TWD 15 DBH
-2.03 TEC TEH 90 HOT 600UL 49 109 0.56 18 2
SAI TSH
-0.33 TSH TSH
.71 9.45 56 HOT 580PP 49 113 0.43 15 2
SAI TSH
-1.50 TSH TSH
.44 56 HOT 580PP 0.49 15 2
SAI TSH
-2.30 TSH TSH
.66 56 HOT 580PP 0.41 15 2
SAI TSH
-3.34 TSH TSH
.35 8.93 56 HOT 580PP 0.36 15 P 1 SCI TSH
-0.07 TSH TSH
.00 56 HOT 580PP 49 119 0.46 113 P 2 TWD 17 08H
+0.04 TEH TEC 46 COLD 600UL 0.51 65 P 2 TWD 18 02H
-1.17 TEH TEC 46 COLD 600UL 0.46 113 P 2 TWD 17 08H
+0.04 TEH TEC 46 COLD 600UL 49 125 0.51 44 P 2 TWD 20 08H
+1.64 TEH TEC LOCOK 60 COLD 600UL 0.44 141 P 2 TWD 18 08H
-1.23 TEH TEC 60 COLD 600UL 0.45 141 P 2 TWD 18 08H
-1.23 TEH TEC 60 COLD 600UL 0.51 44 P 2 TWD 20 08H
+1.64 TEH TEC 60 COLD 60OUL 49 127 0.63 100 P 2 TWD 19 08H
-1.12 TEH TEC NEW 44 COLD 600UL 49 131 0.28 36 P 2 TWD 11 DBH
-0.69 TEH TEC 35 COLD 600UL 0.28 36 P 2 TWD 11 DBH
-0.69 TEH TEC 35 COLD 600UL 49 169 0.47 115 P 2 TWD 17 01C
-0.81 TEH TEC 38 COLD 600UL 50 80 0.34 69 P 2 TWD 14 DBC
-1.55 TEH TEC 23 COLD 600UL 1.31 98 P 2 TWD 35 DBH
-1.83 TEH TEC 23 COLD 600UL 0.34 70 P 2 TWD 15 DBC
-1.55 TEH TEC 23 COLD 600UL 1.31 98 P 2 TWD 35 DBH
-1.83 TEH TEC 23 COLD 600UL 50 88 0.33 59 P 2 TWD 14 DBH
-1.68 TEH TEC 23 COLD 600UL 0.41 141 P 2 TWD 17 08H
+1.43 TEH TEC 23 COLD 60OUL 0.78 88 P 2 TWD 27 DBC
-1.45 TEH TEC 23 COLD 600UL 0.33 59 P 2 TWD 14 DBH
-1.68 TEH TEC 23 COLD 600UL 0.79 82 P 2 TWD 27 DBC
-1.45 TEH TEC 23 COLD 600UL 0.41 143 P 2 TWD 17 08H
+1.43 TEH TEC LOCOK 23 COLD 600UL 50 100 0.56 75 P 2 TWD 21 DBH
-1.91 TEC TEH 90 HOT 600UL 0.56 75 P 2 TWD 21 DBH
-1.91 TEC TEH 90 HOT 600UL 51 83 0.43 78 P 2 TWD 18 DBC
-1.45 TEH TEC 23 COLD 600UL 0.44 78 P 2 TWD 18 DBC
-1.45 TEH TEC 23 COLD 600UL 51 91 1.09 33 P 2 TWD 32 DBH
+1.15 TEC TEH 87 HOT 60OUL 0.62 52 P 2 TWD 22 DBC
+1.92 TEC TEH 87 HOT 60OUL 1.10 33 P 2 TWD 32 DBH
+1.15 TEC TEH 87 HOT 60OUL 2.11 94 P 2 TWD 42 DBH
-1.21 TEC TEH 87 HOT 60OUL 0.62 52 P 2 TWD 22 DBC
+1.92 TEC TEH 87 HOT 600UL 2.11 94 P 2 TWD 42 DBH
-1.21 TEC TEH 87 HOT 600UL 51 99 0.26 129 P 4 TWD 18 DBH
+1.95 DBH DBH LAR 127 COLD 560FH 0.37 63 P 2 TWD 16 DBH
-1.80 TEC TEH 90 HOT 600UL 0.37 63 P 2 TWD 16 DBH
-1.80 TEC TEH 90 HOT 60OUL 51 127 0.35 83 P 2 TWD 16 01H
+0.90 TEH TEC 60 COLD 60OUL 51 151 0.42 66 P 2 TWD 16 03H
-1 18 TEH TEC 33 COLD 600UL 51 153 0.76 118 P 2 TWD 23 08H
+0.38 TEH TEC NEW 37 COLD 60OUL 51 167 0.39 125 P 2 TWD 12 VH3
+0.88 TEH TEC 39 COLD 600UL 0.38 119 P 2 TWD 11 VH3
+0.88 TEH TEC 39 COLD 600UL 52 82 0.43 126 P 2 TWD 17 DBH
-1.55 TEH TEC NEW 22 COLD 60OUL 52 98 0.51 62 P 2 TWD 20 DBH
+1.84 TEC TEH 90 HOT 600UL 0.42 123 P 2 TWD 17 DBH
-1.70 TEC TEH 90 HOT 600UL 0.53 53 P 2 TWD 21 DBH
+1.84 TEC TEH 90 HOT 600UL 0.42 123 P 2 TWD 17 DBH
-1.70 TEC TEH 90 HOT 600UL
44I 0
0 0000 0000 003CD00 to to to to 01 0000 C4 ii 0 000C E4 1 0000 0
II Ue u e u N ii X
U] WW 1 W
1I E
H, II W 11II E E 100 I 00 I.21*
I1 I
100 00 00!
00 a )I CD I
D ID I1 to to I to to 00 GoGo HH WW en e H H E-4 P 00 00 H H N4 N I
Ho o0 00 to o I
I I
I I
I I.-
I I 00 I 00 I 00 I 00 I 00 I 00 I to to I to to I
I I
I I
I I
I 03 I
to t 0000 0000 tototoo 00 I
00 I
00 w
00 I) 00 1 00C10010000100n 00 I 0 I1 00 I 00 I
o 0 00 a 00 to to I to to I to to I to to I to to w to I to to 000000101 000000 I 0 to to to to tot I to En En en En En en I en It
+Iittt
+
t ImWW 1W0 0
C n1:
Qi:
I to I
H HH IH 00 N 0N N I 0 W04 to 04 to I4 N
.~I OM 44-- I
-r M r
":C4 100 000 0
II I n I L N N N N tO tO tO tO 0000 en en en en 0000 H H4 H H
+
I+
0000 )
0000 0000!
C001 00D 00 I
to to I NN I 004 I
E-E I
00 en 0 r en 0 0 4J to 0
-0 04I 0ý I toI EH 0
-"rI 0 I 0
I 0 )
01 HI EI E.
HI (NI N, I I) I WI, C,
HI uUU I E I HH I LO L Iý to I HU Ia tot I 00 E
IN 00 mm IN N co Lo to to I tot HH L) L) too w (*
I I
00C oo NA N C4NO CC H o00 00 tO I N I -4 I en"
.-I to OW:ýr i :9 00 I 00
- 0) 0I H -
04N N I N NO INN 00
-4
-4 0
CIN
- 0)
C0 00 I.
N OW I 001
,Et I PoP HH HH 001 wW Po I EotE HH HHq[--
I I I
I OW I 00 E
I N N 00 LOr I en-I*
I' N en C,4l I 00 I
I E I00 H
N N I N> N ID 00
--W I L 0
I H IoNo en en I-NN N N I 0o 0 C0 I W W HH E I HH E
I 10 xU u
HH IP EHHE Ig I*
IU IU IM IM IB IB NM N IN NN to to I otot t t
t I
en en I E-, E.
0 001 toWIN HH I
00 I
N N I
4-4 I
I E,
I I
U'r) to to to to 0000 en 0 en 0)
- c.
0 o
-4 H
I I I 00 N CN UN
[4W N1 N E,-P to tO OD* r,.
M:} I, H
,4 I
I o00 0o O0 N N NO to t ent n~
I 0 - 4 rI I en IN tO Iton C
001I00,I001I00,I0000 1001 00 I00 I001I001 0000 I00 W Ll I 111 I
U UL I
- 1(1 I
rL)rr I
IW 10 1
01 0 U W
100001U U
I 1
I HD I
0 I
to H INI H H, 0000 0 0 HHO I HH I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I en en I I
I I H H I
I I I I I
I I
I I
I I
I I
I I WW I
I 00 I
I 00 I
I I
I I
I to N I
I H H I
I I
1001 100 I
I HH I I
I I N N I
I I
I NN I
I I
I I
I N H I
I N N I
I I
I I
I I
I 00 I
I en
I I
I 00 I
I I
I I
I I
10 I
10 I
I I
Ito I
4-)
u0 0 a
- 0 410 00 0D to 0D -4 0 00 r-4 4 1+1 I-N o N-to I Hn r
4-4 I WIOEO I H N1 H N4 I en He r-C IN LN N, N I- 0 to 0Ct en en 00 C
0 0
H 0-'
0) 0"I 0 II
ý Ie 0 en>
0P HI r4 0 H 0
kI)I M "H
11 H H H-H 0
II N N4 N N O 0l r4 N)1 0 II H
0O WH 0
I
!I U
H% 11-4 to
>4
ý4 N
0~
0 aIJ C
43 0
0
-4 0
'I 0
0 III Io 00 100W I EtoW I HH c
Io ene I3 en e H
H I) 00 I 00 I
t I H I 0 I0N*
I *N t E-P U L oto H H 00C toWC 000 I00 H en H en
-ý 4 1INC 0 N0o 4
NC W kWH kI I I 100 I0 I
I I
C I (
I HE-I E I
I PI I E 1 04 I
Iq L
10 I
I3 r I Lo I
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 10 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 56 30 0.34 74 P 2 TWD 15 03H
-1.25 TEC TEH 88 HOT 60OUL 56 38 0.40 74 P 2 TWD 16 VH3
-0.98 TEC TEH 93 HOT 600UL 0.41 73 P 2 TWD 16 VH3
-0.98 TEC TEH 93 HOT 600UL 56 44 0.40 36 P 2 TWO 15 08H
+0.87 TEC TEH 95 HOT 600UL 0.39 35 P 2 TWD 15 08H
+0.87 TEC TEH 95 HOT 600UL 56 46 0.63 99 P 2 TWD 22 08H
+0.62 TEC TEH 95 HOT 600UL 0.63 99 P 2 TWD 21 08H
+0.62 TEC TEH 95 HOT 600UL 56 68 0.35 132 P 2 TWD 13 08H
-0.94 TEH TEC 24 COLD 600UL 0.32 139 P 2 TWD 12 08H
-0.94 TEH TEC 24 COLD 600UL 56 82 0.38 139 P 2 TWD 15 DBH
-1.83 TEH TEC 22 COLD 60OUL 0.56 116 P 2 TWD 20 DBH
-1.83 TEH TEC 22 COLD 600UL 56 92 1.77 104 P 2 TWD 37 DBH
-1.89 TEH TEC 57 COLD 600UL 1.77 104 P 2 TWO 37 DBH
-1.89 TEH TEC 57 COLD 600UL 56 98 0.21 160 P 2 TWD 10 DBH
-2.12 TEC TEH NEW 90 HOT 60OUL 56 100 0.27 135 P 2 TWD 12 VSM
-0.71 TEC TEH 90 HOT 600UL 0.27 135 P 2 TWD 12 VSM
-0.71 TEC TEH 90 HOT 600UL 56 122 0.25 99 P 2 TWD 10 07H
+0.54 TEH TEC NEW 62 COLD 600UL 56 146 0.34 124 P 2 TWD 13 VH3
-0.94 TEH TEC 30 COLD 600UL 0.35 122 P 2 TWD 13 VH3
-0.94 TEH TEC 30 COLD 600UL 56 164 0.31 91 P 2 TWD 12 VH3
-0.70 TEH TEC 37 COLD 600UL 0.31 79 P 2 TWD 10 VH3
-0.70 TEH TEC 37 COLD 600UL 56 166 0.63 117 P 2 TWD 18 01C
-0.94 TEH TEC 39 COLD 60OUL 57 67 0.49 59 P 2 TWD 18 02H
-1.23 TEH TEC 24 COLD 600UL 57 79 0.33 32 P 2 TWD 14 DBC
-2.00 TEH TEC 22 COLD 600UL 0.33 32 P 2 TWO 14 DBC
-2.00 TEH TEC 22 COLD 600UL 57 83 0.18 42 P 2 TWO 8 DBC
+1.32 TEH TEC 23 COLD 600UL 0.22 57 P 2 TWO 10 DBC
-1.75 TEH TEC 23 COLD 600UL 0.41 13 P 2 TWD 17 DBC
+1.05 TEH TEC 23 COLD 600UL 0.23 62 P 2 TWO 11 DBC
-1.75 TEH TEC 23 COLD 600UL 0.23 50 P 2 TWO 10 DBC
+1.05 TEH TEC 23 COLD 600UL 0.19 34 P 2 TWO 10 DBC
+1.32 TEH TEC 23 COLD 600UL 57 85 0.27 43 P 2 TWO 13 DBH
+1.72 TEH TEC NEW 23 COLD 600UL 57 91 0.22 159 P 2 TWD 9 DBC
-1.92 TEC TEH 87 HOT 600UL 0.57 40 P 2 TWD 21 DBC
+2.21 TEC TEH 87 HOT 600UL 0.30 92 P 2 TWD 12 DBC
-1.92 TEC TEH 87 HOT 600UL 0.56 37 P 2 TWD 21 DBC
+2.21 TEC TEH 87 HOT 600UL 57 121 0.41 59 P 2 TWO 15 02H
-1.21 TEH TEC 46 COLD 600UL 57 143 0.51 73 P 2 TWD 18 05H
-0.23 TEH TEC 33 COLD 600UL 57 147 0.38 124 P 2 TWD 18 VH3
-0.69 TEH TEC 32 COLD 600UL 0.43 114 P 2 TWD 19 VH3
-0.69 TEH TEC 32 COLD 600UL 57 167 0.34 76 P 2 TWO 13 01H
+0.11 TEH TEC 38 COLD 600UL 58 44 0.29 133 P 2 TWO 13 08H
-0.48 TEC TEH 96 HOT 600UL 0.29 133 P 2 TWD 13 08H
-0.48 TEC TEH 96 HOT 600UL 58 84 0.52 92 P 2 TWD 20 DBH
+1.53 TEH TEC 23 COLD 60OUL 0.51 97 P 2 TWD 20 DBH
+1.53 TEH TEC 23 COLD 600UL 58 88 0.35 67 P 2 TWD 15 DBH
-0.87 TEH TEC 23 COLD 600UL 0.35 72 P 2 TWD 15 DBH
-0.87 TEH TEC 23 COLD 600UL 58 90 0.41 71 P 2 TWD 16 DBH
-1.40 TEC TEH 87 HOT 600UL 0.41 71 P 2 TWD 16 DBH
-1.40 TEC TEH 87 HOT 600UL
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 11 of 46
- MAI, MCI,
- MMI, NVI, SAI,
- SCI, SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 58 92 0.22 113 P 2 TWD 9 DBH
-1.73 TEC TEN NEW 87 HOT 600UL 58 98 0.26 46 P 2 TWD 12 DBH
-2.01 TEC TEE 90 HOT 600UL 0.27 52 P 2 TWD 12 DBE
-2.01 TEC TEE 90 HOT 600UL 58 122 0.44 41 P 2 TWD 16 02H
-1.24 TEE TEC 46 COLD 60OUL 59 11 0.29 132 P 2 TWD 14 VH3
-0.88 TEC TEE 81 HOT 600UL 0.29 132 P 2 TWD 14 VH3
-0.88 TEC TEE 81 HOT 60OUL 59 19 0.27 143 P 2 TWD 13 VH3
-0.90 TEC TEH 85 HOT 600UL 0.26 144 P 2 TWD 13 VH3
-0.90 TEC TEE 85 HOT 600UL 59 25 0.37 143 P 2 TWD 16 VH3
-0.85 TEC TEE 88 HOT 600UL 0.36 140 P 2 TWD 16 VH3
-0.85 TEC TEE 88 HOT 600UL 59 83 1.14 74 P 2 TWD 32 DEE
+1.76 TEH TEC 22 COLD 600UL 1.14 74 P 2 TWD 32 DEE
+1.76 TEH TEC 22 COLD 600UL 59 85 0.86 38 P 2 TWD 27 DEE
+2.00 TEE TEC 22 COLD 600UL 0.85 37 P 2 TWD 27 DEE
+2.00 TEE TEC 22 COLD 600UL 59 91 0.32 103 P 2 TWD 13 DBC
-1.57 TEC TEH 87 HOT 600UL 0.17 113 P 2 TWD 7 DEC
+1.80 TEC TEE NEW 87 HOT 60OUL 0.32 103 P 2 TWD 13 DEC
-1.57 TEC TEE 87 HOT 60OUL 0.81 106 P 6 TWD 34 DBC
-1.74 TO+1.82 DBC DEC LAR 131 COLD 580FH 59 93 0.39 73 P 2 TWD 16 DBH
-1.38 TEC TEH 87 HOT 600UL 0.39 73 P 2 TWD 16 DEE
-1.38 TEC TEH 87 HOT 60OUL 59 99 0.20 127 P 2 TWD 9 DEE
-1.96 TEC TEH NEW 90 HOT 60OUL 59 117 0.35 44 P 2 TWD 14 08H
-1.04 TEH TEC 62 COLD 600UL 0.43 63 P 2 TWD 16 01H
+0.85 TEE TEC 62 COLD 600UL 0.35 44 P 2 TWD 14 08H
-1.04 TEE TEC 62 COLD 600UL 60 22 0.49 68 P 2 TWD 18 VH3
-0.12 TEC TEE 84 HOT 60OUL 0.40 80 P 2 TWD 15 VH3
-0.12 TEC TEH 84 HOT 600UL 60 26 0.45 148 P 2 TWD 18 VH3
-0.89 TEC TEE 88 HOT 60OUL 0.44 148 P 2 TWD 19 VH3
-0.89 TEC TEE 88 HOT 60OUL 60 30 0.48 129 P 2 TWD 19 VH3
-0.97 TEC TEH 88 HOT 60OUL 0.46 125 P 2 TWD 19 VH3
-0.97 TEC TEE 88 HOT 600UL 60 32 0.32 71 P 2 TWD 14 VC3
+0.73 TEC TEH 88 HOT 60OUL 0.29 65 P 2 TWD 13 VSM
-0.81 TEC TEE NEW 88 HOT 60OUL 0.32 71 P 2 TWD 14 VC3
+0.73 TEC TEE 88 HOT 600UL 60 84 0.44 155 P 2 TWD 17 DBH
+1.41 TEE TEC 22 COLD 600UL 0.47 143 P 2 TWD 18 DEE
+1.41 TEE TEC 22 COLD 600UL 60 86 0.69 82 P 2 TWD 23 DBH
-1.80 TEE TEC 22 COLD 600UL 0.68 80 P 2 TWD 23 DEE
-1.80 TEH TEC 22 COLD 600UL 60 90 0.60 47 P 2 TWD 22 DEE
+1.97 TEC TEE 87 HOT 60OUL 0.60 47 P 2 TWD 22 DBH
+1.97 TEC TEH 87 HOT 600UL 60 92 0.34 15 P 2 TWD 14 DBH
+2.02 TEC TEH 87 HOT 600UL 0.34 15 P 2 TWD 14 DEE
+2.02 TEC TEH 87 HOT 600UL 60 98 0.31 10 P 2 TWD 14 DBH
+1.74 TEC TEE NEW 90 HOT 600UL 60 128 0.39 51 P 2 TWD 13 08H
+0.32 TEE TEC 44 COLD 600UL 0.40 46 P 2 TWD 14 08H
+0.32 TEH TEC 44 COLD 600UL 60 166 0.47 149 P 2 TWD 14 VH3
-0.82 TEE TEC 39 COLD 600UL 0.44 146 P 2 TWD 13 VH3
-0.82 TEH TEC 39 COLD 60OUL 61 29 0.40 44 P 2 TWD 17 VH3
-0.89 TEC TEH 88 HOT 600UL 0.41 46 P 2 TWD 17 VH3
-0.89 TEC TEE 88 HOT 60OUL 61 47 0.23 126 P 2 TWD 14 08H
+0.59 TEH TEC 28 COLD 60OUL 0.23 126 P 2 TWD 14 08H
+0.59 TEE TEC 28 COLD 600UL
0 ula
°.0 0'
0, U r')
4J
,4 S
En 00 noO H U) 0 D en..
N O)
(a 0 E. U 0 II 0 II 0 II O II P4 II O II 0 II I-)
II V
II I-)
II 111:
II 0 II N II 41 II H
II H II 0 II H II H II H II O II H II X II 0 II H II X II 0 II 00 1
ou I
00 U
04 1 EH I
XE I
+ 0 ElEl ene C1 Cui O, Cr) V)l oo I
N N I 001 14 01 u
I u
El N
01 011 01 4-1 0
0 0D 41 41 00)I CD00 00C 00 4141 co 00 I 4141 00 oow 0m0 00 00 00
+) U 4N 141 E'- E" en en CN CN 00 a
00 HM em ene 41414 00 00 O00 00 00C 00 N N Nm N 00 u u E.l E.'
HE-E N N H H
++
00 00 O
00 H
H NOH en e 414 Io0 Io0o I 00 I 00 I
I I
I i
00 I 00 I) 0 00
ý I 00 I 0o 00 I00 I0 P0P I P0P I P u
I E
I PPIP
+
I I
10 HH I H E-kX I kX I 0 10 10 E
141 10 LO 1 0 IV 10 10 H
IX' 10 00 00 00 I.D k O00 00 00 00 w w XE.E co 00 PSE 0404 0 0 P14P 00lcx H..
H..
H-1H 00 aI NP PI I P4PP4P Ioc)c I 0000LnLr I I0000I I
I)u n
E IA HE-HEE-I I SE-HHES I I HFHA H
I I n en) en en I0000I I00 00 I
I I
u U I EHHE I 0 Cl C4NN cODco I
++
I 00 c H
Ch C,
0:1I 1.41 I E-I HE 0
00 00 0, I -*
I X r,' r.'
- NN HE-E HE-E
+ +
(q.00 N (N N NA 00
- N W4P 41411 00 1
u u 00 I 4141w N N-I 0010 H-4I ES I
00 I
>H I X
I c>o co 00 I HHIN 00 ES I E-H OI CD 0
I 0
I
- 0) I 0
0)I I
01 I 014 HI Xo C1 Ho
- NI Xl 0
I 0
I 0
I HI El 0 I C00 00 00 00t
-441 00 00 00 00 01 0
1 01 014 NI CN I
+I C 01 00 00 1 00C 00 Io 00 01 0 1 01 Nl I 04 LOI 01 00 HI 01 No I i
I
-4 41 41414 I 00 I00 I 0 00C I 00 ID 0 00 I00 I0 w
I4 H
lI Il coI 00 I 0 00 1 00 1 0 00 Io N N N
H I
r I
I)
I I
I) 00 I 004 I
I LO
,00
-tD en en) I 0UI H E-I 00 I IO II Wq to,,
I 00 CD I 00 D0 00 O
SE-E UUL HE C 00 00 Nl N 00 I
I en en H>
C00 r'.s HE N
N
-14 LO VWV p00 i 00C I P4 0o 00 4l0141
ý4141 H-HE I HHP 00 0
00 000 u0 u
X!U
N Io N
IN en en) 0o en 0D I E)-H I P VE I) 00 I4 00 IN 00 kD HE-,
I N.,N I.-.4P I 0 I
N
-I-H I 0 I
V I 00 I '-
0 I
N o
do 0
0 U')
U H
H 0
en-0"I UO H I O I do.I 0 11 Em S.II 0
II
>1 4J do 0
u H
0
'A 04
'a (Di Io 00 I E-,
I 00 I HE I 00 I I I en en IH H4 1
00 a%
I N N".
I*
,P4, I n
442 0
en P4 O I tN I CD I W I 2-4I I
I E0000 E
4 2
0 0
0000 1 00 I 0 0000 I 00u I 0 0000 I 0 I
I Iz u
HHE-CH I CýI
>>>>I C) 1in I
I 000 I N H
I N 2a 2a 4C4 1
4 P
2 2 2n 2'
C 2
2-1 D r
2 Iý I
I1a
- 1 I3 I L I
I o
2n l Lr I ko 3k I 0 000a I 0000 2I0 UL) 0 20000 I
H Iý N N HN 100 I
I C1 04t "
2 0000 4
I 0 00 0
ODO 2NnN INOO 2 00 en I H 0
2 HH U
I 000 I
eOU 2 000 I 0O I
2 I
2 IgIl 201 2 0 2
2 0 2
I 0 2
2 I
2 I
I 2
HI 201 201 2
2 I
2 NI I 0 2
I I
2 I
2 2
I I
I 2
I I
2 I
2 I
2 2
2 2
132 WI 202 202 WI HI I
I 201 WI HI 2
I I
I I
I I
I 2
I 2
I 2
I 2 0 2 U)
I H I I 10 20 iO 2 0 I H 20 23 H
2 N 20 H
I en I
en 2 N I 0 2 H 2 0 I U) 2 0 rA3 0 4 en I
en 0 0 r.
00 NO 2
I I
I I
I I
2 00 2 00 2
00 2 00 2
00 I 00 I
00 2 00 I
2 2
2 I
I I
I I
00 200 I
I I
00 2002 00 2002 I
I I
I I
I 00 2 N N I
en en I en en I 2
I 2
2 2
2 I
2 I
I 2
I 2
2 2
2 2
2 I
2 I
2 2
2 2
2 00002 0 3
- 0) 00)0 2 0D I 0000 k
I 0o I 0000 1 0 N N N N I N 0
ID 0 0002 WWWW I W NODON 1 0 0 000 C2 0
I ++
2 2 2o 0 en n H
o H
H H H
H n2 gIl 02 02 0
I 0
2 I
I I
2 HI lOl 102 I
I I H I
I 0 2
I 2
I I
I I
I I
I 2
I I
I I
I 2
I 2
I I
2 2
201 202 HI I
2 102 2W2 HI I
I 2
I 2
2 I
2 I
I 2
I 2
I 2
2 I
I IN 2
H I
201 2 I I 2
I I
I I
I 2
I I
I 201 In I
2 0 I
I I
I I
I N 2 H 20 23 H
I N 20 2 0 In 2 H in IN 20 In H
2 0 2 0 00 Ww
.HH 00C 00 O
IC en en 00M H>)
H H
0 2
0 I
E-I 014 P4 WI 02 CI CI IN I N 204 ION 2
2 I
I 2 )i.)
I 0
0 0
I 0) 0 1 0 N
I e N
i 2
32 E 00 I
0 C2 00C 00 C2 00 1 00 00 200 I 00
ý E:I u U
I U
EElI E
IH H E
200100l I>
I I
00 r-N4 N4 I w w i
2:
0 I I
m 2 02 I NI 2 02 I en 2 0' 2>
2 0.
I H.
iO 23 H
IN IN H
H H
In In 20 in H
I 0 20 0
E-n rt 71 1 00 Il HH 00 o00o I
U0 I WW I EHHE I 0 IOH 00C 00 00C 00 k
0I I 02 101 I0 I
I )
I I
10 20a I
e 2
u0 I-,W IU C..*ý I OW 2 1 00 I I I"
en e I W 2>>
2N N INNlr 2 0 00 I
- 00. I 0o0 00 1
00 I 00 20 002ý 00O WW HH I
EA I 4 00
- 00)
I
.H ION I enI 120r 2 0 In 0
- 2 0 a20 0
2 0 020 N
I N) 14 w
I E-I E IHI m
N I p I k 00 00 00 I00 0
u u 2 00 P
00 I HH 200 N N Iý Iu 2r 00 I NN I H cn IDN I N 2 0o 202 1 02 I
Il 1 (N H/I 204 1204 IDI 1
I)
In I U)4 I H I EWWE I
2D I
200 O2 I C I
m In I O I0 2002 2 00 N
0 0
en) 4-)
H u0 0 en CD 00(1 0 0 (U
0ý 3
H F-t 0
H H
H.-
00I HII ow 0=
.HlI
,or P
II O II 4J IaI
- 0 C) 0 0
H 0
C)
V)
Q)
- 0 01 00 1 0002 00 1 0002 U )I I
E4P I P I
002Q 0001 ene IIe n en 1
I I)C 0 C H
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 14 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 69 15 0.39 132 P 2 TWD 15 VH3
-0.83 TEC TEH 84 HOT 60-UL 0.39 132 P 2 TWD 15 VH3
-0.83 TEC TEH 84 HOT 600UL 69 21 0.41 119 P 2 TWD 16 VH3
-0.71 TEC TEH 84 HOT 600UL 0.41 119 P 2 TWD 16 VH3
-0.71 TEC TEH 84 HOT 600UL 69 27 0.39 134 P 2 TWD 17 VH3
-0.77 TEC TEH 88 HOT 600UL 0.38 131 P 2 TWD 17 VH3
-0.77 TEC TEH 88 HOT 600UL 69 59 0.29 112 P 2 TWD 12 DBC
+2.00 TEH TEC NEW 24 COLD 600UL 69 89 0.51 82 P 2 TWD 20 DBC
-1.45 TEH TEC 23 COLD 600UL 0.54 83 P 2 TWD 21 DBC
-1.45 TEH TEC 23 COLD 600UL 69 91 0.67 60 P 2 TWD 24 DBH
+1.74 TEC TEH 87 HOT 600UL 0.68 61 P 2 TWD 24 DBH
+1.74 TEC TEH 87 HOT 600UL 69 163 0.29 117 P 2 TWD 11 VH3
-0.78 TEH TEC 37 COLD 600UL 0.25 106 P 2 TWD 9 VH3
-0.78 TEH TEC 37 COLD 600UL 70 50 0.24 115 P 2 TWD 11 08H
-0.98 TEH TEC 27 COLD 600UL 0.24 115 P 2 TWD 11 08H
-0.98 TEH TEC 27 COLD 600UL 70 114 0.32 120 P 2 TWO 14 07H
-0.79 TEH TEC 49 COLD 60OUL 0.32 120 P 2 TWD 14 07H
-0.79 TEH TEC 49 COLD 600UL 70 138 0.42 61 P 2 TWD 15 VC3
-0.86 TEH TEC 35 COLD 600UL 0.42 61 P 2 TWD 15 VC3
-0.86 TEH TEC 35 COLD 600UL 70 146 0.29 45 P 2 TWD 11 01H
+0.83 TEH TEC 35 COLD 600UL 70 158 0.27 150 P 2 TWD 10 VH3
-0.98 TEH TEC 37 COLD 600UL 0.26 150 P 2 TWD 9 VH3
-0.98 TEH TEC 37 COLD 60OUL 70 162 0.38 142 P 2 TWD 14 08H
+0.86 TEH TEC 36 COLD 600UL 0.38 139 P 2 TWD 14 08H
+0.86 TEH TEC 36 COLD 600UL 70 164 0.51 49 P 2 TWD 17 08H
+1.03 TEH TEC 36 COLD 600UL 0.55 41 P 2 TWD 18 08H
+1.03 TEH TEC 36 COLD 600UL 71 15 0.13 81 P 2 TWD 6 VH3
-1.04 TEC TEH 85 HOT 60OUL 0.14 61 P 2 TWD 7 VH3
-1.04 TEC TEH 85 HOT 600UL 71 31 0.17 114 2 SAI 02H
+3.96 02H 02H 0.38 127 HOT 580PP 72 14 0.42 144 P 2 TWD 18 DBC
-1.79 TEC TEH 80 HOT 600UL 0.42 143 P 2 TWD 18 DBC
-1.79 TEC TEH 80 HOT 600UL 72 34 0.56 106 P 2 TWD 22 VSM
-0.85 TEC TEH 88 HOT 600UL 0.56 110 P 2 TWD 22 VSM
-0.85 TEC TEH 88 HOT 600UL 72 42 0.42 124 P 2 TWD 16 VH3
+0.69 TEC TEH 95 HOT 600UL 0.49 139 P 2 TWD 18 VH3
+0.12 TEC TEH 95 HOT 600UL 0.42 136 P 2 TWD 15 VH3
-0.40 TEC TEH 95 HOT 600UL 0.42 126 P 2 TWD 16 VH3
+0.69 TEC TEH 95 HOT 60OUL 0.49 139 P 2 TWD 18 VH3
+0.12 TEC TEH 95 HOT 60OUL 0.42 136 P 2 TWD 16 VH3
-0.40 TEC TEH 95 HOT 600UL 72 44 0.49 126 P 2 TWD 18 DBC
+2.20 TEC TEH 95 HOT 600UL 0.49 126 P 2 TWD 18 DBC
+2.20 TEC TEH 95 HOT 600UL 72 58 0.44 68 P 2 TWD 15 08H
+0.71 TEH TEC 26 COLD 600UL 0.44 68 P 2 TWD 15 08H
+0.71 TEH TEC 26 COLD 600UL 72 148 0.19 123 P 2 TWD 6
VC3
+0.94 TEH TEC 34 COLD 600UL 0.20 123 P 2 TWD 8 VC3
+0.94 TEH TEC 34 COLD 600UL 73 31 0.36 97 P 2 TWD 16 VH3
+0.91 TEC TEH 88 HOT 600UL 0.35 93 P 2 TWD 16 VH3
+0.91 TEC TEH 88 HOT 60OUL 73 33 0.32 151 P 2 TWD 14 VH3
+0.73 TEC TEH 88 HOT 600UL 0.31 150 P 2 TWD 14 VH3
+0.73 TEC TEH 88 HOT 600UL 0.53 99 P 2 TWD 21 DBH
+1.76 TEC TEH 88 HOT 600UL 0.53 99 P 2 TWD 21 DBH
+1.76 TEC TEH 88 HOT 600UL
to 44 0
Ln H
.)
-C
'n to to L2 to 0 HO 0 0 4-)
04
- 0 1 00 0411
ý40 D0) 00C a00 to o 00C to o
.3
.0 to 0
11.0.0 0
E-00 0L 00
.4100
.411 L)L N
II.L
.141
.411E-EH UU Iý HE-HEE-HE-HE I HEHE-HE-HpE IH H to In H to In H I 00000000 C C C C I
4+1-4 v1-4+0r I~~~2 InI n0In 0
n I a' N' H HW ý H. 04 N IH H H-H) HD H-H H I HE-0HE-HE-HE-oo I 0404040 0404040 INN N
I E E-E I E I ý E I E I C; C
ýI C
I+
+
I I
1 1 -
Hmm1mm 1 mm'
ý I
I 4 1 L 100CD00100 I
I 4 I O I
I I
I I N N0I I E E-I I
I I E-I oo c cI c I mIm EA p 0I I1 034 Q.a N
I I C I
I I
I In I N-I
- 0)
LO 014 01 ml 0
0 to 0 0 0
L) w Eý E-t 04
-t 10 H
Ln m
I IN I
000000 000000 ID a4C)00.
I 0000 I 0 0
.4 0
o 0
to 00 00 to to 001) 0)0 I 000000 0000 I
0 1010U001 000 00 00 0
0UU I 0 00 00 In In In In In In I o w
tt HE-HPE-HE-HI H E-HE-E to 0 N N to 0 I+4 I +
N000 00 H-to Hi H Hi CO N (N N4 N N4 N 040PP40404040412 to to to to In N VO to
-T Vw VO N to V -v In 0 V
Ni to to V In I o to to to
+
+
I COU)042CN I4 totoI I N N N ND 104040404 I 0 000 01 El HI LO mi HI to N-U m
E-I 14 HI In 04 04
,-I, In H
0r 0
to
-to In
+4 w toto 00 00 m m HE 00 OD00 HE N
P40 I 000000 0
10000100 I 00 0
I 00000000 0000 00 00 N.N I In In I
I
>0 I mm ODE I N" Iq tot In 00 I )
I C I IOI oo4 00000000 10000 00000000O I 0)(D000 to to to to to to to to I to to to to 001 0I 00 L
I 0) I to to) I oI DII I
H I
H E-PI H I
I IN04 C
CQ I IQ to CN I N
I ýC4 I Iý In IO I
I I1 I1 C
04 0r 00 00 U
Lr) Ln H l 100 I4 to toD HE-I) 00 Iý 00D
.4' 0I 0
I 0
I to I Oh
.41 0I OI N
I I
I I
I I
I I
I I
I I
I I
I I
I I
I 101 ml I 01 I
I I
I 101 ml I HI I
I 101 ml HI I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I N I
NI I H I
1+1 I
I I
I I
I I
I I
I IOI ml 101 I
I I
I I In I I H I
I I
I0I 101 I HI I N I
104 I to I 0 I H I N I In I0 I N I to I V IN
- 0.
ID OOI 00 1
00 I N~ NI Q00 00 xot HE-c I
I I.4.4I I 00I I 00 I
I 00 I
I to to I
I I
I I
I I
1001 I.4.4I 1001 1001 I
I I
I I
I I
I I N N I
to to I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I 00 00 I
kD I
00 I
00 I to to I I I 0L)
C31 C1 0 n HE-Il
,"4 1" 00 I mmI C)
- EI 0 0)
H. H 00 C
0 0 H
-o 0
H 0
H2 H
OH H
>I 0 I 00 z-
- 3i r*
411.
H>
0 I H. IIN O
00 0 UI 0 II 0404 Opl 000 I
0O to 0O I El0 E E-4 I
1000 ID to I
I C
I0C I
0 I.W 0~
'0
ý4 o
0 0 o
r0
'C 0
I-4 o
$1 HE-I HE-IP E HE HE-E-I HE-I HE-E I,
I
+ +
U I)
I4 0
00 ID 00 I N0N II1+1 kI
Framatome ANP Inc.
01/26/2003 10:53:30 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 16 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 75 31 0.18 92 P 2 TWD 9 VH3
+0.84 TEC TEE 89 HOT 600UL 0.16 67 P 2 TWD 8 DBC
+1.56 TEC TEE NEW 89 HOT 600UL 0.18 92 P 2 TWD 9 VH3
+0.84 TEC TEE 89 HOT 600UL 75 33 0.25 105 P 2 TWD 12 VC3
+0.72 TEC TEE 89 HOT 600UL 0.36 33 P 2 TWD 16 DBC
-1.53 TEC TEN NEW 89 HOT 600UL 0.25 105 P 2 TWD 12 VC3
+0.72 TEC TEE 89 HOT 600UL 75 37 0.16 143 P 2 TWD 8 DBC
+2.20 TEC TEN NEW 93 HOT 600UL 75 45 0.39 143 P 2 TWD 16 VSM
+0.82 TEC TEH 96 HOT 600UL 0.28 158 P 2 TWD 13 VH3
+0.74 TEC TEH 96 HOT 600UL 0.29 82 P 2 TWD 13 VH3
-0.06 TEC TEH 96 HOT 60OUL 0.33 137 P 2 TWD 14 VSM
+0.82 TEC TEE 96 HOT 600UL 0.28 157 P 2 TWD 13 VH3
+0.74 TEC TEE 96 HOT 600UL 0.28 96 P 2 TWD 12 VH3
-0.06 TEC TEE 96 HOT 600UL 75 47 0.30 98 P 2 TWD 11 VH3
+0.12 TEN TEC 29 COLD 60OUL 0.28 67 P 2 TWD 10 VC3
+0.22 TEN TEC 29 COLD 60OUL 0.23 136 P 2 TWD 9 DBC
+1.73 TEE TEC 29 COLD 60OUL 0.30 98 P 2 TWD 11 VH3
+0.12 TEE TEC 29 COLD 600UL 0.23 136 P 2 TWD 9 DBC
+1.73 TEN TEC 29 COLD 600UL 0.27 68 P 2 TWD 10 VC3
+0.22 TEN TEC 29 COLD 600UL 75 57 0.14 154 P 2 TWD 6 VH3
+0.20 TEE TEC 27 COLD 60OUL 0.33 143 P 2 TWD 15 VH3
+0.80 TEN TEC 27 COLD 600UL 0.37 139 P 2 TWD 17 VSM
+0.82 TEN TEC 27 COLD 600UL 0.37 139 P 2 TWD 16 VSM
+0.82 TEN TEC 27 COLD 600UL 0.33 143 P 2 TWD 15 VH3
+0.80 TEN TEC 27 COLD 600UL 0.15 155 P 2 TWD 8 VH3
+0.20 TEN TEC 27 COLD 600UL 75 75 0.43 115 P 2 TWD 17 VSM
-0.78 TEN TEC 23 COLD 60OUL 0.37 136 P 2 TWD 16 VSM
+0.83 TEN TEC 23 COLD 600UL 0.43 117 P 2 TWD 18 VSM
-0.78 TEN TEC 23 COLD 60OUL 0.38 137 P 2 TWD 16 VSM
+0.83 TEE TEC 23 COLD 600UL 75 99 0.23 27 P 2 TWD 10 DBH
-1.40 TEC TEN NEW 90 HOT 60OUL 76 22 0.23 0
P 2 TWD 10 DBC
+1.94 TEC TEE 84 HOT 600UL 0.23 50 P 2 TWD 10 DBC
+1.94 TEC TEN 84 HOT 600UL 76 28 0.13 152 P 2 TWD 6 DBC
+1.47 TEC TEN 88 HOT 600UL 0.19 133 P 2 TWD 9 DBC
+1.47 TEC TEN 88 HOT 600UL S.........................................................................................................
76 32 0.60 54 P 2 TWD 23 DBH
+2.01 TEC TEN NEW 88 HOT 60OUL 76 34 0.58 82 P 2 TWD 22 VH3
+0.89 TEC TEE 88 HOT 600UL 0.43 156 P 2 TWD 18 DBC
+1.95 TEC TEE 88 HOT 600UL 0.23 156 P 2 TWD 11 DBC
+1.95 TEC TEN 88 HOT 600UL 0.58 85 P 2 TWD 22 VH3
+0.89 TEC TEN 88 HOT 60OUL 0.47 154 P 2 TWD 19 DBH
+2.14 TEC TEE NEW 88 HOT 600UL 76 36 0.43 129 P 2 TWD 17 VH3
-0.19 TEC TEN 93 HOT 600UL 0.58 107 P 2 TWD 21 VH3
-0.71 TEC TEN 93 HOT 600UL 0.32 122 P 2 TWD 14 DBC
+1.99 TEC TEE 93 HOT 600UL 0.32 126 P 2 TWD 12 DBC
+1.99 TEC TEN 93 HOT 600UL 0.43 129 P 2 TWD 16 VH3
-0.19 TEC TEN 93 HOT 60OUL 0.58 107 P 2 TWD 21 VH3
-0.71 TEC TEN 93 HOT 600UL 76 40 0.38 78 P 2 TWD 16 VH3
+0.69 TEC TEN 93 HOT 600UL 0.18 101 P 2 TWD 8 DBC
+1.88 TEC TEN NEW 93 HOT 600UL 0.38 78 P 2 TWD 16 VH3
+0.69 TEC TEN 93 HOT 600UL 76 48 0.54 113 P 2 TWD 25 VH3
-0.70 TEN TEC 28 COLD 600UL 0.42 141 P 2 TWD 21 VSM
-0.94 TEN TEC 28 COLD 60OUL 0.42 143 P 2 TWD 21 VSM
+0.88 TER TEC 28 COLD 600UL 0.37 62 P 2 TWD 19 VC3
+0.90 TEN TEC 28 COLD 600UL 0.17 133 P 2 TWD 11 VH3
+0.92 TEN TEC 28 COLD 600UL 0.52 110 P 2 TWD 24 VH3
-0.70 TEN TEC 28 COLD 600UL 0.17 133 P 2 TWD 11 VH3
+0.92 TEN TEC 28 COLD 600UL 0.42 141 P 2 TWD 21 VSM
-0.94 TEN TEC 28 COLD 600UL 0.42 143 P 2 TWD 21 VSM
+0.88 TEN TEC 28 COLD 600UL 0.37 62 P 2 TWD 19 VC3
+0.90 TEN TEC 28 COLD 600UL 76 62 0.31 123 P 2 TWD 13 04C
+0.91 TEN TEC 25 COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:31 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 17 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 76 68 0.58 63 P 2 TWD 20 07H
+0.94 TEH TEC 24 COLD 600UL 0.58 63 P 2 TWD 20 07H
+0.94 TEH TEC 24 COLD 600UL 76 72 0.40 58 P 2 TWD 16 VH3
-0.90 TEH TEC 22 COLD 600UL 0.40 51 P 2 TWD 16 VH3
-0.90 TEH TEC 22 COLD 600UL 76 90 0.38 62 P 2 TWD 15 08C
-0.17 TEC TEH 87 HOT 600UL 0.38 62 P 2 TWD 15 08C
-0.17 TEC TEH 87 HOT 600UL
- 76. 114. 0. 62....
106.....p 2
TWO.....21....VH3.....+0.53.......TEE.....TEC.....
48....
COLD..........0UL 76 114 0.62 106 P 2 TWD 21 VH3
+0.53 TEH TEC 48 COLD 60OUL 0.62 106 P 2 TWD 21 VH3
+0.53 TEH TEC 48 COLD 600UL 76 132 0.39 145 P 2 TWD 14 VH3
+0.78 TEH TEC 35 COLD 600UL 0.39 145 P 2 TWD 14 VH3
+0.78 TEH TEC 35 COLD 600UL S.........................................................................................................
76 136 0.51 120 P 2 TWD 19 VH3
+1.03 TEH TEC 34 COLD 600UL 0.52 134 P 2 TWD 19 VSM
-0.80 TEH TEC 34 COLD 600UL 0.51 120 P 2 TWD 19 VH3
+1.03 TEH TEC 34 COLD 600UL 0.52 134 P 2 TWD 19 VSM
-0.80 TEH TEC 34 COLD 60OUL 77 15 0.33 116 P 2 TWD 13 DBC
-1.25 TEC TEH 84 HOT 600UL 0.33 116 P 2 TWD 13 DBC
-1.25 TEC TEH 84 HOT 60OUL 77 17 0.19 64 P 2 TWD 8 DBC
+1.29 TEC TEH 84 HOT 600UL 0.17 3
P 2 TWD 8 DBC
+1.29 TEC TEH 84 HOT 600UL 77 19 0.17 56 P 2 TWD 7 DBC
+2.03 TEC TEH 84 HOT 60OUL 0.15 48 P 2 TWD 7 DBC
+2.03 TEC TEH 84 HOT 600UL 77 27 0.28 19 P 2 TWD 13 DBC
+1.53 TEC TEH 88 HOT 600UL 0.28 19 P 2 TWD 13 DBC
+1.53 TEC TEH 88 HOT 600UL 77 29 0.33 137 P 2 TWD 15 VC3
-0.75 TEC TEH 88 HOT 600UL 0.16 97 P 2 TWD 8 DBC
-1.60 TEC TEH 88 HOT 600UL 0.33 139 P 2 TWD 15 VC3
-0.75 TEC TEH 88 HOT 600UL 0.17 96 P 2 TWD 8 DBC
-1.60 TEC TEH 88 HOT 600UL 77 31 0.32 72 P 2 TWD 14 VC3
+0.81 TEC TEH 88 HOT 60OUL 0.67 132 P 2 TWD 24 VSM
+0.85 TEC TEH 88 HOT 600UL 0.42 121 P 2 TWD 18 DBH
+2.25 TEC TEH 88 HOT 600UL 0.32 67 P 2 TWD 15 VC3
+0.81 TEC TEH 88 HOT 600UL 0.65 130 P 2 TWD 24 VSM
+0.85 TEC TEH 88 HOT 600UL 0.46 145 P 2 TWD 19 DBH
+2.25 TEC TEH 88 HOT 600UL 77 57 0.40 26 P 2 TWD 14 VC3
+0.20 TEH TEC 26 COLD 600UL 0.67 82 P 2 TWD 21 VC3
+0.79 TEH TEC 26 COLD 60OUL 0.40 26 P 2 TWD 14 VC3
+0.20 TEH TEC 26 COLD 600UL 0.67 82 P 2 TWD 21 VC3
+0.79 TEH TEC 26 COLD 60OUL 77 113 0.32 113 P 2 TWD 12 VH3
+0.94 TEH TEC 48 COLD 60OUL 0.35 134 P 2 TWD 13 VH3
+0.94 TEH TEC 48 COLD 600UL 77 131 0.39 132 P 2 TWD 14 VH3
-0.84 TEH TEC 35 COLD 600UL 0.39 125 P 2 TWD 14 VH3
-0.84 TEH TEC 35 COLD 600UL 77 161 0.36 45 P 2 TWD 13 07C
-1.00 TEH TEC 37 COLD 600UL 0.28 146 P 2 TWD 11 08C
-1.04 TEH TEC 37 COLD 600UL 0.27 147 P 2 TWD 10 DBH
+1.82 TEH TEC NEW 37 COLD 600UL 0.31 145 P 2 TWD 10 08C
-1.04 TEH TEC 37 COLD 600UL 0.37 65 P 2 TWD 12 07C
-1.00 TEH TEC 37 COLD 600UL 78 20 0.32 100 P 2 TWD 15 DBH
+1.95 TEC TEH 85 HOT 600UL 0.32 100 P 2 TWD 15 DBH
+1.95 TEC TEH 85 HOT 600UL 78 26 0.84 66 P 2 TWD 28 VC3
+0.96 TEC TEH 89 HOT 600UL 0.35 88 P 2 TWD 16 VC3
-0.70 TEC TEH 89 HOT 600UL 0.84 65 P 2 TWD 28 VC3
+0.96 TEC TEH 89 HOT 60OUL 0.36 89 P 2 TWD 15 VC3
-0.70 TEC TEH 89 HOT 60OUL 78 30 0.68 114 P 2 TWD 25 VSM
+0.74 TEC TEH 89 HOT 60OUL 0.24 30 P 2 TWD 11 VSM
+0.04 TEC TEH 89 HOT 600UL 0.64 117 P 2 TWD 24 VSM
+0.74 TEC TEH 89 HOT 600UL 0.24 30 P 2 TWD 11 VSM
+0.04 TEC TEH 89 HOT 600UL
Framatome ANP Inc.
01/26/2003 10:53:31 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 18 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 78 38 0.25 41 P 2 TWD 12 DBH
+1.84 TEC TEH NEW 94 HOT 600UL 78 124 0.65 116 P 2 TWD 24 VC3
+0.90 TEH TEC 60 COLD 600UL 0.46 88 P 2 TWD 19 VC3
-0.78 TEH TEC 60 COLD 600UL 0.76 87 P 2 TWD 26 VH3
+0.88 TEH TEC 60 COLD 600UL 0.41 95 P 2 TWD 17 VH3
+0.00 TEH TEC 60 COLD 600UL 0.41 95 P 2 TWD 17 VH3
+0.00 TEH TEC 60 COLD 600UL 0.76 84 P 2 TWD 26 VH3
+0.88 TEH TEC 60 COLD 600UL 0.46 88 P 2 TWD 19 VC3
-0.78 TEH TEC 60 COLD 600UL 0.68 109 P 2 TWD 25 VC3
+0.90 TEH TEC 60 COLD 60OUL 79 17 0.34 129 P 2 TWD 14 VH3
-0.89 TEC TEH 84 HOT 600UL 0.34 129 P 2 TWD 14 VH3
-0.89 TEC TEH 84 HOT 600UL 79 21 0.22 121 P 2 TWD 11 DBC
+1.50 TEC TEH 85 HOT 600UL 0.48 135 P 2 TWD 21 DBH
+1.88 TEC TEH 85 HOT 60OUL 0.22 121 P 2 TWD 11 DBC
+1.50 TEC TEH 85 HOT 600UL 0.48 135 P 2 TWD 21 DBH
+1.88 TEC TEH 85 HOT 600UL 79 29 0.28 123 P 2 TWD 13 VC3
-0.98 TEC TEH 89 HOT 600UL 0.28 116 P 2 TWD 12 VC3
-0.98 TEC TEH 89 HOT 600UL 79 47 0.28 101 P 2 TWD 11 VC3
-0.89 TEH TEC 29 COLD 600UL 0.28 101 P 2 TWD 11 VC3
-0.89 TEH TEC 29 COLD 60OUL 79.. 55.
- 0. 17.....
166.....P...
2 TWO.....8.....EE....+1....74....TEE.....TEC.....
27....
COLD............UL 79 55 0.17 166 P 2 TWD 8 DBH
+1.74 TEH TEC 27 COLD 60OUL 0.17 166 P 2 TWD 8 DBH
+1.'74 TEH TEC 27 COLD 600UL 79 59 0.40 140 P 2 TWD 16 DBH
+2.10 TEH TEC NEW 25 COLD 60OUL 79 89 0.34 124 P 2 TWD 14 VH3
+0.97 TEH TEC 22 COLD 600UL 0.34 139 P 2 TWD 14 VH3
+0.97 TEH TEC 22 COLD 600UL 0.27 73 P 2 TWD 11 DBH
+1.93 TEH TEC NEW 22 COLD 600UL 79 115 0.42 81 P 2 TWD 17 VC3
-0.84 TEH TEC 49 COLD 600UL 0.25 165 P 2 TWD 12 VH3
+0 78 TEH TEC 49 COLD 600UL 0.42 81 P 2 TWD 17 VC3
-0.84 TEH TEC 49 COLD 600UL 0.24 163 P 2 TWD 11 VH3
+0.78 TEH TEC 49 COLD 600UL 79 117 0.70 143 P 2 TWD 23 VC3
+0.86 TEH TEC 62 COLD 600UL 0.75 119 P 2 TWD 24 VC3
-0.94 TEH TEC 62 COLD 600UL 0.34 142 P 2 TWD 13 07H
-0.79 TEH TEC 62 COLD 600UL 0.45 48 P 2 TWD 17 02H
-1.23 TEH TEC 62 COLD 600UL 0.34 142 P 2 TWD 13 07H
-0.79 TEH TEC 62 COLD 600UL 0.75 119 P 2 TWD 24 VC3
-0.94 TEH TEC 62 COLD 600UL 0.70 143 P 2 TWD 23 VC3
+0.86 TEH TEC 62 COLD 60OUL 79 125 0.29 132 P 2 TWD 10 VC3
-0.87 TEH TEC 44 COLD 600UL 0.43 101 P 2 TWD 14 VC3
+0.91 TEH TEC 44 COLD 600UL 0.30 134 P 2 TWD 10 VC3
-0.87 TEH TEC 44 COLD 600UL 0.43 106 P 2 TWD 14 VC3
+0.91 TEH TEC 44 COLD 600UL 79 131 0.34 86 P 2 TWD 13 VSM
-0.50 TEH TEC 34 COLD 600UL 0.35 121 P 2 TWD 13 VSM
-0.50 TEH TEC 34 COLD 600UL 79 161 0.53 72 P 2 TWD 18 DBH
+1.78 TEH TEC 36 COLD 60OUL 0.55 90 P 2 TWD 18 DBH
+1.78 TEH TEC 36 COLD 60OUL 80 22 0.25 0
P 2 TWD 10 DBH
+1.95 TEC TEH 84 HOT 60OUL 0.29 126 P 2 TWD 12 DBH
+1.95 TEC TEH 84 HOT 600UL 80 38 0.32 102 P 2 TWD 14 VC3
-0.87 TEC TEH 93 HOT 600UL 0.19 123 P 2 TWD 9 VC3
+0.66 TEC TEH 93 HOT 600UL 0.70 111 P 2 TWD 24 VSM
+0.71 TEC TEH 93 HOT 600UL 0.79 141 P 2 TWD 26 VH3
-0.83 TEC TEH 93 HOT 600UL 0.60 97 P 2 TWD 22 DBH
+1.76 TEC TEH 93 HOT 600UL 0.32 101 P 2 TWD 12 VC3
-0.87 TEC TEH 93 HOT 600UL 0.70 110 P 2 TWD 24 VSM
+0.71 TEC TEH 93 HOT 600UL 0.60 97 P 2 TWD 22 DBH
+1.76 TEC TEH 93 HOT 600UL 0.79 141 P 2 TWD 26 VH3
-0.83 TEC TEH 93 HOT 600UL 0.18 96 P 2 TWD 8 VC3
+0.66 TEC TEH 93 HOT 600UL 80 40 0.19 51 P 2 TWD 9 VC3
+0.67 TEC TEH 93 HOT 600UL 0.31 62 P 2 TWD 13 VC3
-0.04 TEC TEH 93 HOT 60OUL 0.25 153 P 2 TWD 11 VH3
+0.44 TEC TEH 93 HOT 600UL
Framatome ANP Inc.
Customer Name:
SONGS Unit 3 01/26/2003 10:53:31 AM Component: S/G 88 Page 19 of 46 MAI, MCI, MMI, MVI, SAI, SCI, SVI,. 0-100%TWD QUERY: rpc_icodes-and 0-100%twd.qry ROW LINE VOLTS 0.29 0.26 0.33 0.19 0.29 DEG 80 152 62 51 80 CHN P 2 P 2 P 2 P 2 P 2 IND TWD TWD TWD TWD TWD
%TW 13 10 13 9
13 LOCATION EXT VH3
+0.15 TEC VH3
+0.44 TEC VC3
-0.04 TEC VC3
+0.67 TEC VH3
+0.15 TEC EXT UTIL 1 UTIL 2
TEH TEH TEH TEH TEH 80 80 0.51 114 P 2 TWD 19 VSM
+0.90 TEE TEC 22 COLD 600UL 0.51 108 P 2 TWD 19 VSM
+0.90 TEH TEC 22 COLD 60OUL 80 102 0.72 95 P 2 TWD 19 VC3
-0.90 TEH TEC 53 COLD 600UL 0.72 95 P 2 TWD 19 VC3
-0.90 TEH TEC 53 COLD 600UL 80 140 0.50 115 P 2 TWD 17 VH3
-0.90 TEH TEC 35 COLD 600UL 0.43 145 P 2 TWD 16 VH3
+0.78 TEH TEC 35 COLD 60OUL 1.03 114 P 2 TWD 28 VC3
-0.92 TEH TEC 35 COLD 600UL 0.54 131 P 2 TWD 18 VC3
+0.80 TEH TEC 35 COLD 600UL 0.50 115 P 2 TWD 17 VH3
-0.90 TEH TEC 35 COLD 60OUL 0.43 145 P 2 TWD 16 VH3
+0.78 TEH TEC 35 COLD 60OUL 1.03 114 P 2 TWD 28 VC3
-0.92 TEH TEC 35 COLD 60OUL 0.54 131 P 2 TWD 18 VC3
+0.80 TEH TEC 35 COLD 600UL 80 142 0.66 137 P 2 TWD 21 VH3
-0.84 TEH TEC 35 COLD 60OUL 0.54 149 P 2 TWD 18 VSM
-0.76 TEH TEC 35 COLD 60OUL 0.57 143 P 2 TWD 19 VC3
-0.86 TEH TEC 35 COLD 600UL 0.84 122 P 2 TWD 25 VC3
+0.80 TEH TEC 35 COLD 600UL 0.60 133 P 2 TWD 20 VH3
+0.73 TEH TEC 35 COLD 600UL 0.28 79 P 2 TWD 11 VSM
+0.92 TEH TEC 35 COLD 600UL 0.66 137 P 2 TWD 21 VH3
-0.84 TEH TEC 35 COLD 600UL 0.60 133 P 2 TWD 20 VH3
+0.73 TEH TEC 35 COLD 600UL 0.54 149 P 2 TWD 18 VSM
-0.76 TEH TEC 35 COLD 60OUL 0.29 85 P 2 TWD 11 VSM
+0.92 TEH TEC 35 COLD 60OUL 0.57 143 P 2 TWD 19 VC3
-0.86 TEH TEC 35 COLD 600UL 0.84 122 P 2 TWD 25 VC3
+0.80 TEH TEC 35 COLD 600UL 81 33 0.43 134 P 2 TWD 18 VSM
-0.87 TEC TEH 88 HOT 600UL 0.77 130 P 2 TWD 27 VH3
+0.83 TEC TEH 88 HOT 60OUL 0.54 84 P 2 TWD 21 VH3
+0.06 TEC TEH 88 HOT 600UL 0.43 136 P 2 TWD 18 VSM
-0.87 TEC TEH 88 HOT 60OUL 0.54 85 P 2 TWD 21 VH3
+0.06 TEC TEH 88 HOT 60OUL 0.77 131 P 2 TWD 27 VH3
+0.83 TEC TEH 88 HOT 600UL 81 35 0.19 77 P 2 TWD 9 DBC
-1.95 TEC TEH NEW 93 HOT 60OUL 81 39 0.34 98 P 2 TWD 16 VC3
+0.86 TEC TEH 94 HOT 600UL 0.35 92 P 2 TWD 16 VC3
+0.86 TEC TEH 94 HOT 60OUL 81 41 0.50 77 P 2 TWD 19 VH3
+0.06 TEC TEH 93 HOT 600UL 0.29 69 P 2 TWD 13 VH3
+0.46 TEC TEH 93 HOT 600UL 0.25 142 P 2 TWD 11 VH3
-1.21 TEC TEH 93 HOT 600UL 0.29 68 P 2 TWD 11 VH3
+0.46 TEC TEH 93 HOT 600UL 0.27 142 P 2 TWD 11 VH3
-1.21 TEC TEH 93 HOT 600UL 0.50 77 P 2 TWD 19 VH3
+0.06 TEC TEH 93 HOT 600UL 81 43 0.31 74 P 2 TWD 13 DBC
+2.02 TEC TEH 95 HOT 600UL 0.35 123 P 2 TWD 14 VH3
+0.75 TEC TEH 95 HOT 600UL 0.83 121 P 2 TWD 26 VH3
-0.06 TEC TEH 95 HOT 600UL 1.07 114 P 2 TWD 30 VH3
-0.92 TEC TEH 95 HOT 60OUL 0.32 74 P 2 TWD 12 DBC
+2.02 TEC TEH 95 HOT 600UL 0.35 125 P 2 TWD 14 VH3
+0.75 TEC TEH 95 HOT 600UL 0.84 120 P 2 TWD 26 VH3
-0.06 TEC TEH 95 HOT 600UL 1.07 114 P 2 TWD 30 VH3
-0.92 TEC TEH 95 HOT 60OUL 81 57 0.40 47 P 2 TWD 14 07H
+0.93 TEH TEC 26 COLD 600UL 0.40 47 P 2 TWD 14 07H
+0.93 TEH TEC 26 COLD 600UL 81 59 0.88 138 P 2 TWD 26 VC3
-0.77 TEH TEC 24 COLD 600UL 0.64 102 P 2 TWD 22 VC3
-0.17 TEH TEC 24 COLD 600UL 0.45 77 P 2 TWO 16 DBH
+1.62 TEH TEC NEW 24 COLD 600UL 0.87 136 P 2 TWD 26 VC3
-0.77 TEH TEC 24 COLD 60OUL 0.67 99 P 2 TWD 22 VC3
-0.17 TEH TEC 24 COLD 60OUL 81 63 0.31 72 P 2 TWD 12 VSM
-0.86 TEH TEC 24 COLD 600UL 0.31 72 P 2 TWD 12 VSM
-0.86 TEH TEC 24 COLD 60OUL 81 65 0.73 140 P 2 TWD 23 VSM
+0.86 TEH TEC 24 COLD 600UL CAL # LEG 93 HOT 93 HOT 93 HOT 93 HOT 93 HOT PROBE 600UL 600UL 600UL 60OUL 600UL
Framatome ANP Inc.
01/26/2003 10:53"31 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 20 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY-rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.73 140 P 2 TWD 23 VSM
+0.86 TEH TEC 24 COLD 60OUL 81 69 0.24 117 P 2 TWD 9 DBH
+1.80 TEH TEC 24 COLD 60OUL 0.31 40 P 2 TWO 12 VSM
-0.64 TEH TEC 24 COLD 60OUL 0.23 136 P 2 TWD 9 VC3
-1.03 TEH TEC 24 COLD 60OUL 0.55 67 P 2 TWD 19 VC3
+0.88 TEH TEC 24 COLD 600UL 0.29 57 P 2 TWD 11 VSM
-0.64 TEH TEC 24 COLD 600UL 0.55 67 P 2 TWD 19 VC3
+0.88 TEH TEC 24 COLD 600UL 0.24 111 P 2 TWD 10 DEH
+1.80 TEH TEC 24 COLD 600UL 0.23 136 P 2 TWD 10 VC3
-1.03 TEH TEC 24 COLD 600UL 81 81 0.31 158 P 2 TWD 13 VH3
-0.75 TEE TEC 23 COLD 60OUL 0.47 148 P 2 TWD 19 VH3
+0.72 TEH TEC 23 COLD 600UL 0.35 126 P 2 TWD 15 VSM
+0.85 TEH TEC 23 COLD 60OUL 0.54 126 P 2 TWD 21 VC3
-0.87 TEH TEC 23 COLD 60OUL 0.51 69 P 2 TWD 20 VC3
+0.83 TEH TEC 23 COLD 600UL 0.61 71 P 2 TWD 23 VC3
-0.04 TEH TEC 23 COLD 600UL 0.47 148 P 2 TWD 19 VH3
+0.72 TEH TEC 23 COLD 600UL 0.51 71 P 2 TWD 20 VC3
+0.83 TEH TEC 23 COLD 600UL 0.34 129 P 2 TWD 15 VSM
+0.85 TEH TEC 23 COLD 600UL 0.54 128 P 2 TWD 21 VC3
-0.87 TEH TEC 23 COLD 600UL 0.31 158 P 2 TWD 13 VH3
-0.75 TEH TEC 23 COLD 600UL 0.34 65 P 2 TWD 15 VC3
-0.04 TEH TEC 23 COLD 60OUL 81 111 0.92 140 P 2 TWD 27 VC3
-0.87 TEH TEC 48 COLD 600UL 0.57 126 P 2 TWD 20 VC3
+0.72 TEH TEC 48 COLD 60OUL 0.34 157 P 2 TWD 13 VH3
+0.81 TEH TEC 48 COLD 60OUL 0.34 157 P 2 TWO 13 VH3
+0.81 TEH TEC 48 COLD 600UL 0.92 140 P 2 TWD 27 VC3
-0.87 TEH TEC 48 COLD 600UL 0.57 126 P 2 TWD 20 VC3
+0.72 TEH TEC 48 COLD 60OUL 81 113 0.64 96 P 2 TWD 21 08H
-0.38 TEH TEC 48 COLD 600UL 0.81 107 P 2 TWD 25 VSM
-0.56 TEH TEC 48 COLD 600UL 0.28 139 P 2 TWD 11 VC3
+0.64 TEH TEC 48 COLD 600UL 0.64 96 P 2 TWD 21 08H
-0.38 TEH TEC 48 COLD 60OUL 0.81 107 P 2 TWD 25 VSM
-0.56 TEH TEC 48 COLD 600UL 0.28 139 P 2 TWD 11 VC3
+0.64 TEH TEC 48 COLD 600UL 81 121 0.77 119 P 2 TWD 24 VH3
-0.85 TEH TEC 46 COLD 600UL 0.53 161 P 2 TWO 19 VH3
+0.78 TEH TEC 46 COLD 60OUL 0.77 119 P 2 TWD 24 VH3
-0.85 TEH TEC 46 COLD 60OUL 0.53 161 P 2 TWD 19 VH3
+0.78 TEH TEC 46 COLD 60OUL 81 129 0.87 124 P 2 TWD 24 VC3
+0.83 TEH TEC 44 COLD 600UL 0.39 81 P 2 TWD 13 VH3
+0.99 TEH TEC 44 COLD 600UL 0.88 124 P 2 TWD 25 VC3
+0.83 TEH TEC 44 COLD 600UL 0.39 84 P 2 TWD 13 VH3
+0.99 TEH TEC 44 COLD 600UL 81 141 0.45 162 P 2 TWD 16 VH3
-0.69 TEH TEC 35 COLD 600UL 0.44 145 P 2 TWD 16 VH3
+0.94 TEH TEC 35 COLD 60OUL 0.43 141 P 2 TWO 16 VH3
+0.94 TEH TEC 35 COLD 600UL 0.45 162 P 2 TWD 16 VH3
-0.69 TEH TEC 35 COLD 600UL 82 20 0.20 120 P 2 TWD 10 DBC
+2.04 TEC TEH NEW 85 HOT 60OUL 82 22 0.23 122 P 2 TWD 11 DBC
+1.55 TEC TEH 85 HOT 600UL 0.23 124 P 2 TWD 11 DBC
+1.55 TEC TEH 85 HOT 600UL 82 28 0.27 36 P 2 TWD 13 DBH
-2.01 TEC TEH NEW 89 HOT 600UL 82 62 0.42 35 P 2 TWO 16 VH3
+0.79 TEH TEC 24 COLD 600UL 0.43 34 P 2 TWD 16 VH3
+0.79 TEH TEC 24 COLD 600UL 82 68 0.33 138 P 2 TWD 13 VSM
-0.39 TEH TEC 25 COLD 60OUL 0.41 145 P 2 TWD 16 VH3
-0.71 TEH TEC 25 COLD 600UL 0.40 145 P 2 TWD 16 VH3
-0.71 TEH TEC 25 COLD 600UL 0.33 138 P 2 TWD 13 VSM
-0.39 TEH TEC 25 COLD 60OUL 82 74 0.58 31 P 2 TWD 21 DBH
+2.01 TEH TEC NEW 22 COLD 60OUL 82 100 0.41 35 P 2 TWD 17 VH3
+0.73 TEC TEH 90 HOT 60OUL 0.43 97 P 2 TWD 18 VH3
-0.69 TEC TEH 90 HOT 600UL 0.41 35 P 2 TWD 17 VH3
+0.73 TEC TEH 90 HOT 600UL 0.43 97 P 2 TWD 17 VH3
-0.69 TEC TEH 90 HOT 600UL
Framatome ANP Inc.
01/26/2003 10:53:31 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 21 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 82 110 0.37 59 P 2 TWD 16 VH3
+0.88 TEH TEC NEW 49 COLD 60OUL S.........................................................................................................
82 130 0.87 137 P 2 TWD 25 VH3
-0.86 TEH TEC 35 COLD 60OUL 0.38 131 P 2 TWD 14 VC3
-0.82 TEH TEC 35 COLD 600UL 0.87 137 P 2 TWD 25 VH3
-0.86 TEH TEC 35 COLD 600UL 0.38 131 P 2 TWD 14 VC3
-0.82 TEH TEC 35 COLD 600UL S.........................................................................................................
82 132 0.32 140 P 2 TWD 13 VH3
-0.80 TEH TEC 34 COLD 600UL 0.48 123 P 2 TWD 18 VH3
+0.82 TEH TEC 34 COLD 60OUL 0.32 140 P 2 TWD 13 VH3
-0.80 TEH TEC 34 COLD 60OUL 0.48 123 P 2 TWD 18 VH3
+0.82 TEH TEC 34 COLD 600UL S.........................................................................................................
82 152 0.41 149 P 2 TWD 15 08C
-0.21 TEH TEC 35 COLD 600UL 0.09 23 P 2 TWD 4 08C
+0.08 TEH TEC 35 COLD 600UL 0.41 148 P 2 TWD 15 08C
-0.21 TEH TEC 35 COLD 600UL 0.10 22 P 2 TWD 4 08C
+0.08 TEH TEC 35 COLD 600UL
- 83. 101. 0. 23.....
111.....P...
2 TWO.....10....07......-0.61.......TEC.....TEE.....
90........T U..
83 101 0.23 111 P 2 TWD 10 07H
-0.61 TEC TEH 90 HOT 60OUL 0.23 111 P 2 TWD 10 07H
-0.61 TEC TEH 90 HOT 600UL S.........................................................................................................
83 117 0.37 131 P 2 TWD 14 05C
+0.48 TEH TEC 62 COLD 60OUL 0.48 49 P 2 TWD 17 01H
+0.93 TEH TEC 62 COLD 600UL S.........................................................................................................
83 121 0.35 108 P 2 TWD 14 01H
+0.86 TEH TEC 62 COLD 600UL
- 83. 139. 0. 26....
157.....P 2
TWO 1...V......2...+0.92.......TEN....TEC.....
34... COLD..........OUL 83 139 0.26 157 P 2 TWD 11 VH2
+0.92 TEH TEC 34 COLD 600UL 0.26 157 P 2 TWD 13 VH2
+0.92 TEH TEC 34 COLD 60OUL S.........................................................................................................
83 153 0.36 104 P 2 TWD 13 VH2
+0.90 TEH TEC 34 COLD 60OUL 0.36 104 P 2 TWD 13 VH2
+0.90 TEH TEC 34 COLD 600UL 84.. 38.
- 0. 38.....
142.....P...
2 TWO.....16....V...2.....0.72......TEC.....TEN.....
93....
NOT...........UL 84 38 0.38 142 P 2 TWD 16 VH2
+0.72 TEC TEH 93 HOT 600UL 0.38 142 P 2 TWD 15 VH2
+0.72 TEC TEH 93 HOT 600UL S.........................................................................................................
84 58 0.32 151 P 2 TWD 11 09H
-1.24 TEH TEC 26 COLD 60OUL 0.73 44 P 2 TWD 22 09H
+1.75 TEH TEC LOCOK 26 COLD 600UL 0.32 151 P 2 TWD 11 09H
-1.24 TEH TEC 26 COLD 600UL 0.73 44 P 2 TWD 22 09H
+1.75 TEH TEC 26 COLD 600UL
- 84. 68.
- 0. 49....
161.....P 2
TWO.....18....09E.....-1.50.......TEE.....TEC.....
24....
COLD......
600UL....
84 68 0.49 161 P 2 TWD 18 09H
-1.50 TEH TEC 24 COLD 600UL 0.48 159 P 2 TWD 18 09H
-1.50 TEH TEC LOCOK 24 COLD 600UL S.........................................................................................................
84 70 0.28 109 P 2 TWD 27 09H
-1.35 TEH TEC 24 COLD 600UL 0.28 123 P 2 TWD 23 09H
-1.35 TEH TEC LOCOK 24 COLD 600UL S.........................................................................................................
84 88 0.84 144 P 2 TWD 27 DBH
+1.90 TEH TEC 22 COLD 600UL 0.65 113 P 2 TWD 23 DBH
-1.75 TEH TEC 22 COLD 600UL 0.83 134 P 2 TWD 27 DBH
+1.90 TEH TEC 22 COLD 600UL 0.68 113 P 2 TWD 23 DBH
-1.75 TEH TEC 22 COLD 600UL S.........................................................................................................
84 94 0.28 130 P 2 TWD 11 VH2
+0.88 TEC TEH NEW 87 HOT 600UL S.........................................................................................................
84 98 0.26 122 P 2 TWD 12 09H
-1.14 TEC TEH 90 HOT 600UL 0.26 122 P 2 TWD 16 09H
-1.14 TEC TEH 90 HOT 600UL S.........................................................................................................
84 100 0.66 129 P 2 TWD 24 09H
-1.41 TEC TEH 90 HOT 600UL 0.38 44 P 2 TWD 16 09H
+1.45 TEC TEH 90 HOT 600UL 0.36 59 P 2 TWD 16 09H
+1.45 TEC TEH LOCOK 90 HOT 600UL 0.66 132 P 2 TWD 24 09H
-1.41 TEC TEH LOCOK 90 HOT 600UL S.........................................................................................................
84 102 0.54 131 P 2 TWD 15 07H
-0.87 TEH TEC 53 COLD 600UL 0.35 48 P 2 TWD 10 09H
-1.44 TEH TEC 53 COLD 60OUL 0.39 146 P 2 TWO 11 09H
+1.42 TEH TEC 53 COLD 60OUL 0.54 131 P 2 TWD 15 07H
-0.87 TEH TEC 53 COLD 600UL 0.35 41 P 2 TWD 16 09H
-1.44 TEH TEC LOCOK 53 COLD 600UL 0.39 146 P 2 TWD 21 09H
+1.42 TEH TEC LOCOK 53 COLD 600UL S.........................................................................................................
84 106 0.56 137 P 2 TWD 16 09H
-1.42 TEH TEC 53 COLD 600UL 0.80 134 P 2 TWD 21 09H
+1.54 TEH TEC 53 COLD 600UL 0.56 138 P 2 TWD 16 09H
-1.42 TEH TEC LOCOK 53 COLD 600UL 0.81 133 P 2 TWD 21 09H
+1.54 TEH TEC LOCOK 53 COLD 600UL S.........................................................................................................
84 108 0.51 152 P 2 TWD 14 09H
-1.68 TEH TEC 53 COLD 600UL 0.45 132 P 2 TWD 13 09H
+1.50 TEH TEC 53 COLD 600UL 0.47 134 P 2 TWD 14 09H
+1.50 TEH TEC LOCOK 53 COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:31 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 22 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.51 150 P 2 TWD 15 09H
-1.68 TEH TEC LOCOK 53 COLD 600UL 84 110 0.46 49 P 2 TWD 17 08H
+0.02 TEH TEC 48 COLD 60OUL 0.77 144 P 2 TWD 24 09H
-1.35 TEH TEC LOCOK 48 COLD 60OUL 0.85 102 P 2 TWD 26 09H
+1.49 TEH TEC LOCOK 48 COLD 600UL 0.41 69 P 2 TWD 15 08H
+0.02 TEH TEC 48 COLD 600UL 0.77 145 P 2 TWD 24 09H
-1.35 TEH TEC LOCOK 48 COLD 600UL 0.85 102 P 2 TWD 26 09H
+1.49 TEH TEC LOCOK 48 COLD 600UL 84 114 0.54 146 P 2 TWD 19 09H
-1.29 TEH TEC LOCOK 48 COLD 600UL 0.47 125 P 2 TWD 17 09H
+1.84 TEH TEC LOCOK 48 COLD 600UL 0.47 125 P 2 TWD 17 09H
+1.84 TEH TEC LOCOK 48 COLD 600UL 0.54 146 P 2 TWD 19 09H
-1.29 TEH TEC LOCOK 48 COLD 600UL 84 116 0.49 122 P 2 TWD 18 09H
-1.36 TEH TEC LOCOK 48 COLD 600UL 0.37 113 P 2 TWD 14 09H
+1.66 TEH TEC LOCOK 48 COLD 600UL 0.49 122 P 2 TWD 18 09H
-1.36 TEH TEC LOCOK 48 COLD 600UL 0.37 125 P 2 TWD 14 09H
+1.66 TEH TEC LOCOK 48 COLD 600UL 84 118 0.45 139 P 2 TWD 16 09H
-1.20 TEH TEC 46 COLD 60OUL 0.45 139 P 2 TWD 16 09H
-1.20 TEH TEC 46 COLD 600UL 84 122 0.44 132 P 2 TWD 16 09H
-1.55 TEH TEC NEW LOCOK 62 COLD 600UL 84 130 0.38 88 P 2 TWD 15 VH2
+0.89 TEH TEC 34 COLD 600UL 0.38 88 P 2 TWD 15 VH2
+0.89 TEH TEC 34 COLD 600UL 85 57 1.03 120 P 2 TWD 28 08H
-0.79 TEH TEC 26 COLD 600UL 1.03 120 P 2 TWD 28 08H
-0.79 TEH TEC 26 COLD 600UL 85 61 0.58 121 P 2 TWD 20 08H
+0.52 TEH TEC 24 COLD 600UL 0.58 121 P 2 TWD 20 08H
+0.52 TEH TEC 24 COLD 600UL 85 83 0.25 141 P 2 TWD 11 06H
+0.85 TEH TEC 23 COLD 60OUL 85 97 0.27 71 P 2 TWD 12 09H
+1.24 TEC TEH 87 HOT 600UL 0.44 102 P 2 TWD 17 09H
-0.95 TEC TEH 87 HOT 600UL 0.24 68 P 2 TWD 10 09H
+1.24 TEC TEH 87 HOT 600UL 0.44 102 P 2 TWD 17 09H
-0.95 TEC TEH 87 HOT 60OUL 85 117 0.61 115 P 2 TWD 21 09H
-1.48 TEH TEC 46 COLD 60OUL 0.61 115 P 2 TWD 21 09H
-1.48 TEH TEC LOCOK 46 COLD 600UL 85 157 0.32 30 P 2 TWD 12 DBH
+1.73 TEH TEC 36 COLD 600UL 0.36 28 P 2 TWD 13 DBH
+1.73 TEH TEC 36 COLD 600UL 86 48 0.26 84 P 2 TWD 10 VH2
-0.88 TEH TEC 29 COLD 600UL 0.26 88 P 2 TWD 10 VH2
-0.88 TEH TEC 29 COLD 600UL 86 58 0.45 57 P 2 TWD 19 VH2
+0.62 TEH TEC 27 COLD 600UL 0.45 57 P 2 TWD 19 VH2
+0.62 TEH TEC 27 COLD 600UL 86 60 0.32 142 P 2 TWD 12 08H
-0.88 TEH TEC 24 COLD 600UL 0.41 159 P 2 TWD 15 09H
-0.85 TEH TEC 24 COLD 600UL 0.29 149 P 2 TWD 11 08H
-0.88 TEH TEC 24 COLD 60OUL 0.40 159 P 2 TWD 15 09H
-0.85 TEH TEC 24 COLD 600UL 86 98 0.26 35 P 2 TWD 12 06H
+0.78 TEC TEH 90 HOT 60OUL 86 102 0.30 164 P 2 TWD 14 09H
+0.58 TEH TEC 54 COLD 600UL 0.30 164 P 2 TWD 14 09H
+0.58 TEH TEC 54 COLD 600UL 86 108 0.49 47 P 2 TWD 20 VH2
-0.72 TEH TEC 54 COLD 600UL 0.49 47 P 2 TWD 20 VH2
-0.72 TEH TEC 54 COLD 600UL 86 112 0.36 47 P 2 TWD 16 08H
-0.14 TEH TEC NEW 49 COLD 600UL 86 114 0.34 70 P 2 TWD 15 VH2
-0.66 TEH TEC NEW 49 COLD 60OUL 86 116 0.39 112 P 2 TWD 17 VH2
-0.62 TEH TEC NEW 49 COLD 600UL 86 118 0.44 130 P 2 TWD 16 VH2
-0.58 TEH TEC 62 COLD 600UL 0.44 130 P 2 TWD 16 VH2
-0.58 TEH TEC 62 COLD 600UL 87 61 0.55 39 P 2 TWD 20 08H
+0.75 TEH TEC 25 COLD 600UL
Framatome ANP Inc.
Customer Name:
SONGS Unit 3 01/26/2003 10:53:31 AM Component: S/G 88 Page 23 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY:
rpcicodes and 0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT 0.55 39 P 2 TWD 20 08H
+0.75 TEH EXT UTIL 1 UTIL 2 CAL # LEG PROBE TEC 25 COLD 600UL 87 99 0.30 42 P 2 TWD 13 09H
+0.97 TEC TEH 90 HOT 600UL 0.24 80 P 2 TWD 11 08H
-0.45 TEC TEH 90 HOT 600UL 0.34 151 P 2 TWD 15 07H
+0.91 TEC TEH 90 HOT 60OUL 0.36 156 P 2 TWD 15 07H
+0.91 TEC TEH 90 HOT 60OUL 0.34 122 P 2 TWD 15 08H
-0.45 TEC TEH 90 HOT 60OUL 0.28 55 P 2 TWD 13 09H
+0.97 TEC TEH 90 HOT 600UL 87 101 0.35 132 P 2 TWD 15 07H
+0.23 TEC TEH 90 HOT 600UL 0.35 133 P 2 TWD 15 07H
+0.23 TEC TEH 90 HOT 60OUL 87 111 0.21 84 P 2 TWD 10 08H
-0.52 TEH TEC 49 COLD 60OUL 0.22 108 P 2 TWD 10 08H
-0.52 TEH TEC 49 COLD 600UL 87 117 0.40 117 P 2 TWO 15 09 0.40 117 P 2 TWD 15 09H
+0.32
+0.32 TEH TEC TEH TEC 62 COLD 600UL 62 COLD 600UL 88 36 0.39 150 P 2 TWO 16 VH2
-1.14 TEC TEE 93 HOT 6000L 0.38 148 P 2 TWD 16 VH2
-1.14 TEC TEH 93 HOT 60OUL 88 48 0.37 40 P 2 TWD 14 VH2
-0.68 TEH TEC 29 COLD 60OUL 0.36 43 P 2 TWD 14 VH2
-0.68 TEH TEC 29 COLD 60OUL 88 68 0.43 90 P 2 TWD 16 08H
-1.01 TEH TEC 24 COLD 60OUL 0.43 90 P 2 TWD 16 08H
-1.01 TEH TEC 24 COLD 600UL 88 124 0.50 107 P 2 TWD 16 VH2
-0.80 TEH TEC 44 COLD 600UL 0.50 107 P 2 TWD 16 VH2
-0.80 TEH TEC 44 COLD 600UL 88 126 0.46 105 P 2 TWD 15 VH2
-0.84 TEH TEC 44 COLD 60OUL 0.51 81 P 2 TWD 16 VH2
-0.84 TEH TEC 44 COLD 600UL 89 29 0.37 142 P 2 TWD 16 VH2
+0.93 TEC TEH 88 HOT 600UL 0.57 122 P 2 TWD 22 VH2
-0.02 TEC TEH 88 HOT 60OUL 0.37 129 P 2 TWD 16 VH2
-1.02 TEC TEH 88 HOT 600UL 0.38 143 P 2 TWD 16 VH2
+0.93 TEC TEH 88 HOT 600UL 0.57 120 P 2 TWD 22 VH2
-0.02 TEC TEH 88 HOT 600UL 0.38 132 P 2 TWD 16 VH2
-1.02 TEC TEH 88 HOT 600UL 89 57 0.45 39 P 2 TWD 15 09H
+0.51 TEH TEC 26 COLD 60OUL 0.45 39 P 2 TWD 15 09H
+0.51 TEH TEC 26 COLD 600UL 89 59 0.43 43 P 2 TWD 16 09H
+0.81 TEH TEC 24 COLD 600UL 0.29 23 P 2 TWD 11 01H
+0.78 TEH TEC 24 COLD 600UL 0.43 43 P 2 TWD 16 09H
+0.81 TEH TEC 24 COLD 600UL 89 61 0.64 113 P 2 TWD 22 09H
+0.69 TEH TEC 24 COLD 600UL 0.64 113 P 2 TWD 22 09H
+0.69 TEH TEC 24 COLD 600UL 89 79 0.57 125 P 2 TWD 21 09H
-0.15 TEH TEC 22 COLD 600UL 0.59 136 P 2 TWD 21 09H
-0.15 TEH TEC 22 COLD 600UL 89 101 0.44 144 P 2 TWD 18 07H
+1.03 TEC TEH 90 HOT 600UL 0.49 147 P 2 TWD 19 07H
+1.03 TEC TEH 90 HOT 600UL 89 113 0.47 129 P 2 TWD 17 09H
+0.52 TEH TEC 48 COLD 60OUL 0.47 129 P 2 TWD 17 09H
+0.52 TEH TEC 48 COLD 600UL 89 151 0.40 123 P 2 TWD 15 VC3
-0.78 TEH TEC 35 COLD 60OUL 0.40 123 P 2 TWD 15 VC3
-0.78 TEH TEC 35 COLD 60OUL 90 52 0.30 149 P 2 TWD 14 VH2
-0.58 TEH TEC 4
COLD 600UL 0.30 149 P 2 TWD 14 VH2
-0.58 TEH TEC 4
COLD 600UL 90 62 0.47 72 P 2 TWD 17 VH2
-0.70 TEH TEC 5
COLD 60OUL 0.47 72 P 2 TWD 17 VH2
-0.70 TEH TEC 5
COLD 600UL 90 72 0.32 95 P 2 TWD 15 08H
-0.30 TEH TEC 6
COLD 60OUL 0.32 95 P 2 TWD 15 08H
-0.30 TEH TEC 6
COLD 600UL 90 78 0.33 76 P 2 TWD 14 09H
-0.09 TEH TEC 8
COLD 600UL 0.24 53 P 2 TWD 11 09H
+0.67 TEH TEC 8
COLD 600UL 0.33 76 P 2 TWD 14 09H
-0.09 TEH TEC 8
COLD 600UL 0.24 53 P 2 TWD 12 09H
+0.67 TEH TEC 8
COLD 60OUL
Framatome ANP Inc.
01/26/2003 10:53:32 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 24 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 90 102 0.23 148 P 2 TWD 10 09H
+0.86 TEH TEC 15 COLD 60OUL 0.58 127 P 2 TWD 19 08H
+0.86 TEH TEC 15 COLD 600UL 0.58 127 P 2 TWD 19 08H
+0.86 TEH TEC 15 COLD 600UL 0.22 145 P 2 TWD 8 09H
+0.86 TEH TEC 15 COLD 600UL 91 21 0.44 83 P 2 TWD 18 VH2
-1.08 TEC TEH 73 HOT 600UL 0.44 83 P 2 TWD 18 VH2
-1.08 TEC TEH 73 HOT 600UL 91 25 0.25 137 P 2 TWD 11 VH2
+0.80 TEC TEH 73 HOT 600UL 0.26 137 P 2 TWD 12 VH2
+0.80 TEC TEH 73 HOT 600UL 91 37 0.32 102 P 2 TWD 14 VH2
+0.84 TSH TEC NEW 2
COLD 600UL 91 49 0.30 148 P 2 TWD 12 VH2
-0.60 TEH TEC 3
COLD 600UL 0.30 148 P 2 TWD 12 VH2
-0.60 TEH TEC 3
COLD 600UL 91 69 0.45 107 P 2 TWD 19 08H
+0.92 TEH TEC 6
COLD 600UL 0.45 132 P 2 TWD 19 09H
-0.06 TEH TEC 6
COLD 600UL 0.42 106 P 2 TWD 19 08H
+0.92 TEH TEC 6
COLD 60OUL 0.45 132 P 2 TWD 19 09H
-0.06 TEH TEC 6
COLD 600UL 91 73 0.75 140 P 2 TWD 26 09H
-0.32 TEH TEC 8
COLD 600UL 0.32 126 P 2 TWD 14 08H
+0.82 TEH TEC 8
COLD 600UL 0.32 126 P 2 TWD 14 08H
+0.82 TEH TEC 8
COLD 600UL 0.75 140 P 2 TWD 26 09H
-0.32 TEH TEC 8
COLD 600UL 91 79 0.37 128 P 2 TWD 16 09H
+0.48 TEH TEC 8
COLD 60OUL 0.27 92 P 2 TWD 12 07H
+0.32 TEH TEC 8
COLD 60OUL 0.40 75 P 2 TWD 17 09H
+0.48 TEH TEC 8
COLD 60OUL 0.27 92 P 2 TWD 12 07H
+0.32 TEH TEC LAR 8
COLD 60OUL 91 81 0.27 94 P 2 TWD 12 09H
-0.04 TEH TEC 8
COLD 600UL 0.27 93 P 2 TWD 12 09H
-0.04 TEH TEC 8
COLD 600UL 91 99 0.33 56 P 2 TWD 13 08H
+0.96 TEH TEC 13 COLD 600UL 0.31 24 P 2 TWD 12 08H
-0.92 TEH TEC 13 COLD 60OUL 0.22 146 P 2 TWD 9 09H
+0.00 TEH TEC 13 COLD 60OUL 0.32 30 P 2 TWD 13 08H
-0.92 TEH TEC 13 COLD 600UL 0.35 63 P 2 TWD 15 08H
+0.96 TEH TEC 13 COLD 60OUL 0.19 150 P 2 TWD 8 09H
+0.00 TEH TEC 13 COLD 60OUL 91 103 0.43 109 P 2 TWD 14 08H
+0.82 TEH TEC 15 COLD 600UL 0.43 109 P 2 TWD 14 08H
+0.82 TEH TEC 15 COLD 60OUL 91 105 0.43 76 P 2 TWD 14 09H
-0.15 TEH TEC 15 COLD 60OUL 0.43 75 P 2 TWD 16 09H
-0.15 TEH TEC 15 COLD 600UL 91 111 0.57 81 P 2 TWD 18 09H
-0.21 TEH TEC 15 COLD 600UL 0.57 75 P 2 TWD 18 09H
-0.21 TEH TEC 15 COLD 600UL 91 113 0.30 116 P 2 TWD 11 09H
-0.34 TEH TEC 15 COLD 60OUL 0.62 76 P 2 TWD 19 09H
+0.43 TEH TEC 15 COLD "600UL 0.30 116 P 2 TWD 11 09H
-0.34 TEH TEC 15 COLD 600UL 0.62 76 P 2 TWD 19 09H
+0.43 TEH TEC 15 COLD 600UL 91 115 0.36 128 P 2 TWD 12 09H
+0.30 TEH TEC 15 COLD 600UL 0.35 126 P 2 TWD 14 09H
+0.30 TEH TEC 15 COLD 600UL 92 66 0.35 142 P 2 TWD 13 09H
-0.13 TEH TEC 5
COLD 600UL 0.33 22 P 2 TWD 13 09H
+1.03 TEH TEC 5
COLD 60OUL 0.33 22 P 2 TWD 13 09H
+1.03 TEH TEC 5
COLD 600UL 0.35 141 P 2 TWD 13 09H
-0.13 TEH TEC 5
COLD 60OUL 92 68 0.88 125 P 2 TWD 27 09H
-0.19 TEH TEC 5
COLD 600UL 0.88 126 P 2 TWD 27 09H
-0.19 TEH TEC 5
COLD 600UL 92 72 0.26 36 P 2 TWD 10 09H
+0.62 TEH TEC 5
COLD 600UL 0.52 134 P 2 TWD 19 09H
-0.06 TEH TEC 5
COLD 600UL 0.36 117 P 2 TWD 14 05H
+0.81 TEH TEC 5
COLD 600UL 0.26 36 P 2 TWD 10 09H
+0.62 TEH TEC 5
COLD 600UL 0.52 134 P 2 TWD 19 09H
-0.06 TEH TEC 5
COLD 600UL S.........................................................................................................
92 74 0.55 113 P 2 TWD 20 07H
+0.86 TEH TEC 7
COLD 600UL 0.32 30 P 2 TWD 13 09H
+0 99 TEH TEC 7
COLD 60OUL
Framatome ANP Inc.
01/26/2003 10:53:32 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 25 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.56 114 P 2 TWD 20 07H
+0.86 TEH TEC 7
COLD 600UL 0.39 28 P 2 TWD 16 09H
+0.99 TEH TEC 7
COLD 600UL 92 76 0.35 73 P 2 TWD 14 09H
-0.24 TEH TEC 7
COLD 600UL 0.39 80 P 2 TWD 16 09H
-0.24 TEH TEC 7
COLD 60OUL 92 98 0.30 64 P 2 TWD 12 08H
-0.56 TEH TEC 13 COLD 60OUL 0.30 61 P 2 TWD 13 08H
-0.56 TEH TEC 13 COLD 600UL 92 102 0.81 105 P 2 TWD 25 09H
+0.88 TEH TEC 15 COLD 600UL 0.80 107 P 2 TWD 23 09H
+0.88 TEH TEC 15 COLD 60OUL 92 104 0.28 113 P 2 TWD 13 09H
-0.94 TEH TEC 16 COLD 600UL 0.36 129 P 2 TWD 16 09H
+0.06 TEH TEC 16 COLD 600UL 0.29 102 P 2 TWD 14 09H
-0.94 TEH TEC 16 COLD 600UL 0.37 126 P 2 TWD 17 09H
+0.06 TEH TEC 16 COLD 600UL 92 112 0.77 107 P 2 TWD 23 09H
+0.30 TEH TEC 15 COLD 600UL 0.34 89 P 2 TWD 12 09H
+0.83 TEH TEC 15 COLD 600UL 0.77 106 P 2 TWD 24 09H
+0.30 TEH TEC 15 COLD 600UL 0.34 77 P 2 TWD 12 09H
+0.83 TEH TEC 15 COLD 600UL 93 35 0.25 24 P 2 TWD 11 VH2
+0.72 TEC TEH 76 HOT 60OUL 0.25 24 P 2 TWD 11 VH2
+0.72 TEC TEH 76 HOT 600UL 93 61 0.82 118 P 2 TWD 26 09H
+0.77 TEH TEC 5
COLD 600UL 0.83 117 P 2 TWD 26 09H
+0.77 TEH TEC 5
COLD 600UL 93 63 0.30 57 P 2 TWD 12 09H
+1.03 TEH TEC 5
COLD 600UL 0.31 56 P 2 TWD 12 09H
+1.03 TEH TEC 5
COLD 600UL 93 69 0.37 145 P 2 TWD 14 09H
+0.77 TEH TEC 5
COLD 60OUL 0.37 145 P 2 TWD 14 09H
+0.77 TEH TEC 5
COLD 600UL 93 73 0.33 162 P 2 TWD 13 09H
+0.84 TEH TEC 7
COLD 600UL 0.33 162 P 2 TWD 13 09H
+0.84 TEH TEC 7
COLD 600UL 93 75 0.85 74 P 2 TWD 27 09H
-0.19 TEH TEC 7
COLD 600UL 0.85 73 P 2 TWD 27 09H
-0.19 TEH TEC 7
COLD 600UL 93 77 0.37 30 P 2 TWD 15 09H
-0.17 TEH TEC NEW 7
COLD 60OUL 93 79 0.31 61 P 2 TWD 12 09H
-0.15 TEH TEC 7
COLD 600UL 0.31 61 P 2 TWD 13 09H
-0.15 TEH TEC 7
COLD 600UL 93 97 0.53 125 P 2 TWD 21 09H
-0.19 TEH TEC 14 COLD 60OUL 0.20 127 P 2 TWD 10 09H
+0.86 TEH TEC 14 COLD 600UL 0.53 125 P 2 TWD 21 09H
-0.19 TEH TEC 14 COLD 600UL 0.20 127 P 2 TWD 10 09H
+0.86 TEH TEC 14 COLD 600UL 93 105 0.33 103 P 2 TWD 15 08H
-0.47 TEH TEC 16 COLD 600UL 0.33 102 P 2 TWD 16 08H
-0.47 TEH TEC 16 COLD 600UL 93 111 0.43 120 P 2 TWD 19 08H
+0.28 TEH TEC 16 COLD 600UL 0.43 116 P 2 TWD 19 08H
+0.28 TEH TEC 16 COLD 600UL 93 113 0.28 62 P 2 TWD 14 09H
+0.69 TEH TEC 16 COLD 600UL 0.30 49 P 2 TWD 15 09H
+0.69 TEH TEC 16 COLD 600UL 93 149 0.26 50 P 2 TWD 13 DBC
-1.70 TEH TEC NEW 21 COLD 600UL 94 28 0.49 92 P 2 TWD 19 VSM
-0.80 TEC TEH 73 HOT 600UL 0.38 60 P 2 TWD 16 VH3
+0.62 TEC TEH 73 HOT 600UL 0.49 92 P 2 TWD 19 VSM
-0.80 TEC TEH 73 HOT 600UL 0.39 66 P 2 TWD 16 VH3
+0.62 TEC TEH 73 HOT 600UL 94 38 0.24 151 P 2 TWD 11 VH2
+0.78 TEH TEC 2
COLD 600UL 0.23 148 P 2 TWD 11 VH2
+0.78 TEH TEC 2
COLD 600UL 94 40 0.85 129 P 2 TWD 25 VSM
+0.87 TEH TEC 1
COLD 600UL 0.85 129 P 2 TWD 25 VSM
+0.87 TEH TEC 1
COLD 600UL 94 50 0.34 102 P 2 TWD 14 08H
+0.47 TEH TEC NEW 3
COLD 60OUL 94 62 0.30 124 P 2 TWD 14 09H
+0 00 TEH TEC 6
COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:32 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 26 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY:
rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.30 125 P 2 TWO 14 09H
+0.00 TEH TEC 6
COLD 600UL 94 64 0.21 146 P 2 TWD 10 08H
-0.47 TEH TEC 6
COLD 600UL 0.32 69 P 2 TWD 15 09H
+0.28 TEH TEC 6
COLD 600UL 0.32 69 P 2 TWD 15 09H
+0.28 TEH TEC 6
COLD 600UL 0.22 150 P 2 TWD 11 08H
-0.47 TEH TEC 6
COLD 600UL 94 66 0.21 129 P 2 TWD 10 09H
+0.69 TEH TEC 6
COLD 60OUL 0.21 129 P 2 TWD 10 09H
+0.69 TEH TEC 6
COLD 600UL 94 68 0.33 151 P 2 TWO 15 VH2
+0.80 TEH TEC 6
COLD 600UL 0.31 141 P 2 TWO 14 VH2
+0.80 TEH TEC 6
COLD 600UL 94 72 0.26 144 P 2 TWD 12 07H
+0.39 TEH TEC 6
COLD 600UL 0.26 144 P 2 TWD 12 07H
+0.39 TEH TEC 6
COLD 600UL 94 74 0.33 61 P 2 TWD 14 09H
-0.37 TEH TEC 8
COLD 600UL 0.33 62 P 2 TWD 14 09H
-0.37 TEH TEC 8
COLD 600UL 94 78 0.37 136 P 2 TWD 16 09H
-0.11 TEH TEC 8
COLD 600UL 0.40 104 P 2 TWD 17 09H
+0.39 TEH TEC 8
COLD 600UL 0.40 104 P 2 TWD 17 09H
+0.39 TEH TEC 8
COLD 600UL 0.37 136 P 2 TWD 16 09H
-0.11 TEH TEC 8
COLD 600UL 94 82 0.52 125 P 2 TWD 21 09H
-0.19 TEH TEC 8
COLD 60OUL 0.52 125 P 2 TWO 21 09H
-0.19 TEH TEC 8
COLD 600UL 94 84 0.41 80 P 2 TWD 17 08H
-0.37 TEH TEC 8
COLD 600UL 0.41 80 P 2 TWD 17 08H
-0.37 TEH TEC 8
COLD 600UL 94 88 0.30 78 P 2 TWD 13 09H
-0.81 TEH TEC 13 COLD 600UL 0.27 68 P 2 TWD 11 09H
-0.81 TEH TEC 13 COLD 600UL 94 90 0.14 38 P 2 TWD 7 09H
+0.38 TEH TEC 14 COLD 60OUL 0.14 38 P 2 TWD 7 09H
+0.38 TEH TEC 14 COLD 600UL 94 94 0.25 130 P 2 TWD 12 07H
+0.98 TEH TEC 14 COLD 600UL 0.25 137 P 2 TWD 12 VH2
+0.92 TEH TEC 14 COLD 60OUL 0.25 130 P 2 TWD 12 07H
+0.98 TEH TEC 14 COLD 600UL 0.25 146 P 2 TWD 12 VH2
+0.92 TEH TEC 14 COLD 600UL 94 96 0.25 105 P 2 TWD 12 08H
-0.49 TEH TEC 14 COLD 60OUL 0.23 155 P 2 TWD 11 09H
+0.83 TEH TEC 14 COLD 600UL 0.23 155 P 2 TWD 11 09H
+0.83 TEH TEC 14 COLD 600UL 0.25 105 P 2 TWD 12 08H
-0.49 TEH TEC 14 COLD 600UL 94 102 0.35 112 P 2 TWD 16 09H
-0.43 TEH TEC 16 COLD 600UL 0.35 112 P 2 TWD 17 09H
-0.43 TEH TEC 16 COLD 600UL 94 104 0.31 100 P 2 TWD 11 DBH
+1.19 TEH TEC NEW 15 COLD 600UL 94 138 0.17 17 P 1 SCI TSH
-4.97 TSH TSH
.27 8.82 64 HOT 58OPP 94 146 0.27 157 P 2 TWD 13 VH2
-0.90 TEH TEC 21 COLD 600UL 0.38 106 P 2 TWO 17 VH2
+0.92 TEH TEC 21 COLD 600UL 0.71 112 P 2 TWO 26 VH3
-0.90 TEH TEC 21 COLD 60OUL 0.27 157 P 2 TWD 13 VH2
-0.90 TEH TEC 21 COLD 60OUL 0.38 106 P 2 TWD 17 VH2
+0.92 TEH TEC 21 COLD E0OUL 0.71 112 P 2 TWD 26 VH3
-0.90 TEH TEC 21 COLD 600UL 94 148 0.40 73 P 2 TWD 18 VC3
+0.85 TEH TEC 21 COLD 600UL 0.41 71 P 2 TWD 19 VC3
+0.85 TEH TEC 21 COLD 600UL 95 25 0.28 73 P 2 TWD 13 VH2
-0.70 TEC TEH 73 HOT 600UL 0.27 73 P 2 TWD 12 VH2
-0.70 TEC TEH 73 HOT 600UL 95 63 0.39 123 P 2 TWD 17 09H
+0.24 TEH TEC 6
COLD 60OUL 0.39 111 P 2 TWD 17 09H
+0.24 TEH TEC 6
COLD 600UL 95 65 0.32 96 P 2 TWD 15 08H
+0.33 TEH TEC 6
COLD 600UL 0.82 98 P 2 TWD 28 09H
-0.22 TEH TEC 6
COLD 600UL 0.18 150 P 2 TWD 9 09H
+0.87 TEH TEC 6
COLD 600UL 0.32 96 P 2 TWD 15 08H
+0.33 TEH TEC 6
COLD 600UL 0.81 98 P 2 TWD 28 09H
-0.22 TEH TEC 6
COLD 600UL 0.18 146 P 2 TWD 9 09H
+0.87 TEH TEC 6
COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:32 AM Customer Name:
SONGS Unit 3 Component:
S/G 88 Page 27 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 95 67 0.53 65 P 2 TWD 19 09H
+0.75 TEH TEC 5
COLD 600UL 0.41 118 P 2 TWD 15 09H
+0.75 TEH TEC 5
COLD 600UL 95 69 0.25 87 P 2 TWD 12 08H
+0.34 TEH TEC 6
COLD 600UL 0.25 87 P 2 TWD 12 08H
+0.34 TEH TEC 6
COLD 60OUL 95 71 0.26 136 P 2 TWD 10 07H
-0.87 TEH TEC 5
COLD 600UL 0.26 136 P 2 TWD 10 07H
-0.87 TEH TEC 5
COLD 60OUL 95 73 0.27 101 P 2 TWD 12 VH3
+0.80 TEH TEC 8
COLD 60OUL 0.68 82 P 2 TWD 25 09H
+0.60 TEH TEC 8
COLD 600UL 0.34 46 P 2 TWD 15 07H
+0.69 TEH TEC 8
COLD 60OUL 0.22 135 P 2 TWD 10 VSM
+0.91 TEH TEC 8
COLD 60OUL 0.10 16 P 2 TWO 5 07H
-0.93 TEH TEC 8
COLD 600UL 0.10 16 P 2 TWD 5 07H
-0.93 TEH TEC 8
COLD 600UL 0.34 46 P 2 TWD 15 07H
+0.69 TEH TEC 8
COLD 60OUL 0.68 82 P 2 TWD 25 09H
+0.60 TEH TEC 8
COLD 600UL 0.25 108 P 2 TWD 11 VH3
+0.80 TEH TEC 8
COLD 600UL 0.26 166 P 2 TWD 11 VSM
+0.91 TEH TEC 8
COLD 600UL 95 77 0.25 129 P 2 TWD 11 08H
+0.50 TEH TEC 8
COLD 600UL 0.25 129 P 2 TWD 11 08H
+0.50 TEH TEC 8
COLD 600UL 95 85 0.37 138 P 2 TWD 15 08H
+0.86 TEH TEC 7
COLD 60OUL 0.35 60 P 2 TWD 14 09H
+0.90 TEH TEC 7
COLD 600UL 0.37 138 P 2 TWD 15 08H
+0.86 TEH TEC 7
COLD 600UL 0.35 60 P 2 TWD 14 09H
+0.90 TEH TEC 7
COLD 600UL 95 89 0.34 111 P 2 TWO 13 09H
+0.60 TEH TEC 13 COLD 600UL 0.33 108 P 2 TWD 14 09H
+0.60 TEH TEC 13 COLD 600UL 95 97 0.28 84 P 2 TWD 12 09H
-0.21 TEH TEC 13 COLD 600UL 0.28 84 P 2 TWD 12 09H
-0.21 TEH TEC 13 COLD 600UL 95 101 0.68 89 P 2 TWD 25 09H
-0.26 TEH TEC 14 COLD 600UL 0.20 80 P 2 TWD 9 09H
+0.71 TEH TEC 14 COLD 600UL 0.68 89 P 2 TWD 25 09H
-0.26 TEH TEC 14 COLD 60OUL 0.20 80 P 2 TWD 9 09H
+0.71 TEH TEC 14 COLD 600UL 95 103 0.48 106 P 2 TWD 16 09H
+0.99 TEH TEC 15 COLD 600UL 0.48 106 P 2 TWD 16 09H
+0.99 TEH TEC 15 COLD 600UL 95 105 0.77 140 P 2 TWD 23 09H
+0.88 TEH TEC 15 COLD 600UL 0.29 47 P 2 TWD 10 DBH
+0.68 TEH TEC NEW 15 COLD 60OUL 0.77 140 P 2 TWD 23 09H
+0.88 TEH TEC 15 COLD 60OUL 95 109 0.35 97 P 2 TWD 12 09H
+0.94 TEH TEC 15 COLD 600UL 0.35 97 P 2 TWD 12 09H
+0 94 TEH TEC 15 COLD 60OUL 95 11 0.46 89 P 2 TWD 15 09H
+1.03 TEH TEC 15 COLD 600UL 0.46 89 P 2 TWD 15 09H
+1.03 TEH TEC 15 COLD 600UL 96 50 0.22 123 P 2 TWD 10 VH2
-0.56 TEH TEC 4
COLD 600UL 0.21 125 P 2 TWD 10 VH2
-0.56 TEH TEC 4
COLD 60OUL 96 60 0.34 58 P 2 TWD 15 09H
-0.23 TEH TEC NEW 6
COLD 600UL 96 66 0.39 50 P 2 TWD 15 07H
+0.79 TEH TEC NEW 5
COLD 60OUL 0.33 44 P 2 TWD 13 08H
-0.13 TEH TEC NEW 5
COLD 60OUL 96 68 0.33 103 P 2 TWD 13 09H
+0.77 TEH TEC 5
COLD 600UL 0.17 15 P 2 TWD 7 09H
-0.75 TEH TEC 5
COLD 600UL 0.33 101 P 2 TWD 13 09H
+0.77 TEH TEC 5
COLD 600UL 0.19 15 P 2 TWD 7 09H
-0.75 TEH TEC 5
COLD 600UL 0.25 11 P 2 TWD 10 DBH
+2.25 TEH TEC NEW 5
COLD 600UL 96 70 0.83 130 P 2 TWD 26 07H
+0.84 TEH TEC 5
COLD 600UL 0.84 129 P 2 TWD 26 07H
+0.84 TEH TEC 5
COLD 60OUL 0.19 147 P 2 TWD 7 09H
-0.13 TEH TEC NEW 5
COLD 600UL 96 72 0.33 56 P 2 TWD 13 09H
+0.21 TEH TEC 5
COLD 600UL 0.21 94 P 2 TWD 8 09H
-0.96 TEH TEC 5
COLD 600UL 0.33 56 P 2 TWD 13 09H
+0.21 TEH TEC 5
COLD 600UL 0.21 94 P 2 TWD 8 09H
-0.96 TEH TEC 5
COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:32 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 28 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 96 74 0.17 125 2 SAI 02H
+1.24 02H 02H 0.26 125 HOT 580PP 96 88 0.29 65 P 2 TWD 11 07H
+0.26 TEH TEC 13 COLD 600UL 0.30 43 P 2 TWD 13 07H
+0.26 TEH TEC 13 COLD 600UL 96 98 0.55 111 P 2 TWD 21 09H
+0.60 TEH TEC 13 COLD 600UL 0.56 115 P 2 TWD 21 09H
+0.60 TEH TEC 13 COLD 600UL 96 110 0.31 108 P 2 TWD 11 09H
+0.19 TEH TEC 15 COLD 600UL 0.31 108 P 2 TWO 11 09H
+0.19 TEH TEC 15 COLD 60OUL 96 132 0.36 58 P 2 TWD 15 VH2
-0.71 TEH TEC NEW 20 COLD 600UL 96 152 0.31 117 P 2 TWD 15 02C
+0 78 TEH TEC 21 COLD 600UL 97 23 0.31 101 P 2 TWD 14 VH2
-0.76 TEC TEH 73 HOT 60OUL 0.31 88 P 2 TWD 13 VH2
-0.76 TEC TEH 73 HOT 600UL 97 43 0.35 56 P 2 TWD 16 VH2
-0.57 TEH TEC 4
COLD 600UL 0.31 78 P 2 TWD 14 VH2
+0.54 TEH TEC 4
COLD 600UL 0.31 78 P 2 TWD 14 VH2
+0.54 TEH TEC 4
COLD 600UL 0.32 53 P 2 TWD 14 VH2
-0.57 TEH TEC 4
COLD 600UL 97 61 0.20 139 P 2 TWD 10 04C
-0.88 TEH TEC 6
COLD 600UL 97 65 0.35 125 P 2 TWO 13 09H
-0.69 TEH TEC NEW 5
COLD 600UL 97 69 0.22 37 P 2 TWD 9 07H
+0.90 TEH TEC 5
COLD 600UL 0.22 32 P 2 TWD 9 07H
+0.90 TEH TEC 5
COLD 600UL 97 73 0.43 113 P 2 TWD 17 08H
+0.73 TEH TEC 7
COLD 600UL 0.48 127 P 2 TWD 18 09H
+0.77 TEH TEC 7
COLD 600UL 0.21 120 P 2 TWD 9 08H
-0.58 TEH TEC 7
COLD 600UL 0.45 I11 P 2 TWD 17 08H
+0.73 TEH TEC 7
COLD 600UL 0.21 134 P 2 TWD 9 08H
-0.58 TEH TEC 7
COLD 600UL 0.50 129 P 2 TWD 19 09H
+0.77 TEH TEC 7
COLD 600UL 97 85 0.26 131 P 2 TWD 11 09H
-0.17 TEH TEC 8
COLD 600UL 0.26 131 P 2 TWD 11 09H
-0.17 TEH TEC 8
COLD 600UL 97 103 0.66 124 P 2 TWD 25 09H
+0.34 TEH TEC 16 COLD 600UL 0.66 124 P 2 TWO 25 09H
+0.34 TEH TEC 16 COLD 600UL S.........................................................................................................
97 107 0.82 100 P 2 TWD 24 09H
-0.67 TEH TEC 15 COLD 60OUL 0.58 57 P 2 TWD 18 09H
+0.06 TEH TEC 15 COLD 600UL 0.82 100 P 2 TWD 25 09H
-0.67 TEH TEC 15 COLD 600UL 0.57 62 P 2 TWD 20 09H
+0.06 TEH TEC 15 COLD 600UL 98 24 0.36 141 P 2 TWD 15 06C
+0.86 TEC TEH 73 HOT 600UL 0.22 68 P 2 TWD 11 06C
+0.06 TEC TEH 73 HOT 600UL 98 26 0.21 106 P 2 TWD 10 VC3
+0.78 TEC TEH 73 HOT 600UL 0.22 92 P 2 TWD 10 VC3
+0.78 TEC TEH 73 HOT 600UL 98 38 0.27 149 P 2 TWD 13 VH2
-0.83 TEH TEC 2
COLD 600UL 0.28 141 P 2 TWD 13 VH2
-0.83 TEH TEC 2
COLD 600UL 98 42 0.33 71 P 2 TWD 13 VH2
-0.82 TEH TEC NEW 3
COLD 600UL 98 48 0.28 137 P 2 TWD 13 VH2
-0.74 TEH TEC 4
COLD 60OUL 0.28 137 P 2 TWD 13 VH2
-0.74 TEH TEC 4
COLD 600UL 98 66 0.27 70 P 2 TWD 13 09H
+0.91 TEH TEC 6
COLD 600UL 0.28 69 P 2 TWD 13 09H
+0.91 TEH TEC 6
COLD 600UL 98 70 0.39 78 P 2 TWD 15 VH3
+0.99 TEH TEC 5
COLD 600UL 1.24 122 P 2 TWD 33 VSM
-0.84 TEH TEC 5
COLD 600UL 0.22 119 P 2 TWO 9 VC3
-0.96 TEH TEC 5
COLD 600UL 0.35 116 P 2 TWO 13 VC3
+1.01 TEH TEC 5
COLD 600UL 0.76 136 P 2 TWD 24 VH3
+0.99 TEH TEC 5
COLD 600UL 1.24 122 P 2 TWD 33 VSM
-0.84 TEH TEC 5
COLD 60OUL 0.22 119 P 2 TWD 9 VC3
-0.96 TEH TEC 5
COLD 600UL 0.30 120 P 2 TWD 12 VC3
+1.01 TEH TEC 5
COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:33 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 29 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 98 72 0.70 83 P 2 TWD 26 07H
+0.93 TEH TEC 6
COLD 600UL 0.70 83 P 2 TWD 27 07H
+0.93 TEH TEC 6
COLD 600UL 98 106 0.39 75 P 2 TWD 17 09H
-0.23 TEH TEC 16 COLD 600UL 0.43 142 P 2 TWD 19 09H
+0.88 TEH TEC 16 COLD 600UL 0.40 74 P 2 TWD 18 09H
-0.23 TEH TEC 16 COLD 600UL 0.44 142 P 2 TWD 19 09H
+0.88 TEH TEC 16 COLD 600UL 98 142 0.44 152 P 2 TWD 19 VH2
-0.83 TEH TEC 21 COLD 60OUL 0.44 152 P 2 TWD 19 VH2
-0.83 TEH TEC 21 COLD 60OUL 99 27 0.27 118 P 2 TWD 12 VH2
-0.70 TEC TEH 73 HOT 600UL 0.27 118 P 2 TWD 12 VH2
-0.70 TEC TEH 73 HOT 60OUL 99 29 0.29 104 P 2 TWD 12 DBH
+2.08 TEC TEH 73 HOT 600UL 0.29 104 P 2 TWD 13 DBH
+2.08 TEC TEH 73 HOT 600UL 99 65 0.37 107 P 2 TWD 17 08H
+0.61 TEH TEC 6
COLD 600UL 0.37 112 P 2 TWD 17 08H
+0.61 TEH TEC 6
COLD 600UL 99 79 0.28 83 P 2 TWD 12 07H
+0.91 TEH TEC 8
COLD 600UL 0.27 78 P 2 TWD 12 07H
+0.91 TEH TEC 8
COLD 600UL 99 81 0.52 150 P 2 TWD 21 09H
+0.67 TEH TEC 8
COLD 600UL 0.52 150 P 2 TWD 21 09H
+0.67 TEH TEC 8
COLD 60OUL 99 89 0.76 92 P 2 TWD 25 09H
+0.70 TEH TEC 13 COLD 600UL 0.75 91 P 2 TWD 25 09H
+0.70 TEH TEC 13 COLD 600UL 99 93 0.41 129 P 2 TWD 17 09H
+0.51 TEH TEC 14 COLD 60OUL 0.41 129 P 2 TWD 17 09H
+0.51 TEH TEC 14 COLD 600UL 99 99 0.55 74 P 2 TWD 21 09H
-0.15 TEH TEC 13 COLD 60OUL 0.55 74 P 2 TWD 21 09H
-0.15 TEH TEC 13 COLD 60OUL 99 101 0.27 91 P 2 TWD 13 08H
-0.24 TEH TEC 14 COLD 600UL 0.44 117 P 2 TWD 18 09H
+0.71 TEH TEC 14 COLD 600UL 0.25 48 P 2 TWD 12 DBH
+1.09 TEH TEC NEW 14 COLD 60OUL 0.29 90 P 2 TWD 13 08H
-0.24 TEH TEC 14 COLD 600UL 0.44 117 P 2 TWD 18 09H
+0.71 TEH TEC 14 COLD 60OUL 99 103 0.72 114 P 2 TWD 23 09H
+0.97 TEH TEC 15 COLD 600UL 0.12 130 P 2 TWD 6 09H
+0.22 TEC TEH 15 COLD 600UL 0.81 86 P 2 TWD 23 09H
+0.97 TEH TEC 15 COLD 600UL 0.18 144 P 2 TWD 6 09H
+0.22 TEH TEC 15 COLD 600UL 99 109 0.23 148 P 2 TWD 8 09H
+0.73 TEH TEC 15 COLD 600UL 0.24 147 P 2 TWD 10 09H
+0.73 TEH TEC 15 COLD 60OUL 100 38 0.29 145 P 2 TWD 13 VH2
-0.70 TEH TEC 2
COLD 600UL 0.29 145 P 2 TWD 13 VH2
-0.70 TEH TEC 2
COLD 600UL 100 46 0.29 47 P 2 TWD 13 VH2
-0.56 TEH TEC 4
COLD 600UL 0.29 46 P 2 TWD 13 VH2
-0.56 TEH TEC 4
COLD 600UL 100 60 0.63 97 P 2 TWD 24 VH2
-0.67 TEH TEC 6
COLD 60OUL 0.56 89 P 2 TWD 22 VH2
-0.67 TEH TEC 6
COLD 600UL 100 74 0.34 82 P 2 TWD 13 09H
-0.06 TEH TEC 7
COLD 600UL 0.13 48 P 2 TWD 5 09H
+1.01 TEH TEC 7
COLD 600UL 0.34 81 P 2 TWD 14 09H
-0.06 TEH TEC 7
COLD 600UL 0.24 160 P 2 TWD 10 09H
+1.01 TEH TEC 7
COLD 600UL 100 100 0.51 120 P 2 TWD 21 09H
+0.90 TEH TEC 14 COLD 600UL 0.51 120 P 2 TWD 21 09H
+0.90 TEH TEC 14 COLD 600UL 100 102 0.47 122 P 2 TWD 18 09H
-0.24 TEH TEC 15 COLD 600UL 0.49 120 P 2 TWD 16 09H
-0.24 TEH TEC 15 COLD 600UL 100 120 0.34 156 P 2 TWD 15 VH2
-0.86 TEH TEC 18 COLD 600UL 0.35 155 P 2 TWD 15 VH2
-0.86 TEH TEC 18 COLD 60OUL 100 134 0.18 146 P 2 TWD 8 DBC
+1.59 TEH TEC NEW 20 COLD 600UL 100 148 0.44 100 P 2 TWD 16 VH2
-0.85 TEH TEC 19 COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:33 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 30 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.46 122 P 2 TWD 17 VH2
-0.85 TEH TEC 19 COLD 600UL 101 27 0.37 141 P 2 TWO 15 VH2
-0.74 TEC TEH 73 HOT 600UL 0.37 141 P 2 TWO 16 VH2
-0.74 TEC TEH 73 HOT 600UL 101 67 0.48 61 P 2 TWD 20 09H
+0.97 TEH TEC 6
COLD 600UL 0.38 44 P 2 TWD 17 09H
+0.97 TEH TEC 6
COLD 600UL 101 71 0.23 91 P 2 TWO 11 DBH
-1.69 TEH TEC 6
COLD 600UL 0.23 91 P 2 TWO 11 DBH
-1.69 TEH TEC 6
COLD 600UL 101 77 0.26 133 P 2 TWO 11 09H
-0.69 TEH TEC 7
COLD 600UL 0.75 87 P 2 TWO 25 09H
+0.66 TEH TEC 7
COLD 600UL 0.74 87 P 2 TWD 25 09H
+0.66 TEH TEC 7
COLD 600UL 0.26 133 P 2 TWD 11 09H
-0.69 TEH TEC 7
COLD 600UL 101 79 0.30 75 P 2 TWD 12 09H
-1.05 TEH TEC 7
COLD 600UL 0.67 67 P 2 TWD 23 09H
+0.96 TEH TEC 7
COLD 600UL 0.30 59 P 2 TWD 12 09H
-1.05 TEH TEC 7
COLD 600UL 0.68 67 P 2 TWD 23 09H
+0.96 TEH TEC 7
COLD 600UL 101 81 0.66 138 P 2 TWO 23 09H
-0.77 TEH TEC 7
COLD 600UL 0.66 138 P 2 TWO 23 09H
-0.77 TEH TEC 7
COLD 600UL 101 83 0.69 136 P 2 TWD 23 09H
-0.47 TEH TEC 7
COLD 600UL 0.69 135 P 2 TWD 23 09H
-0.47 TEH TEC 7
COLD 600UL 101 85 0.43 102 P 2 TWD 18 09H
-0.47 TEH TEC 8
COLD 600UL 0.43 102 P 2 TWO 18 09H
-0.47 TEH TEC 8
COLD 600UL 101 95 0.34 37 P 2 TWO 15 09H
-0.19 TEH TEC 14 COLD 600UL 0.33 37 P 2 TWO 15 09H
+0.84 TEH TEC 14 COLD 600UL 0.33 34 P 2 TWD 15 09H
-0.19 TEH TEC 14 COLD 600UL 0.33 37 P 2 TWD 15 09H
+0.84 TEH TEC 14 COLD 600UL 101 97 0.70 114 P 2 TWD 25 09H
-0.99 TEH TEC 14 COLD 600UL 0.70 114 P 2 TWD 25 09H
-0.99 TEH TEC 14 COLD 600UL 101 101 0.27 22 P 2 TWD 10 09H
-0.24 TEH TEC 13 COLD 60OUL 0.28 23 P 2 TWO 12 09H
-0.24 TEH TEC 13 COLD 600UL 101 111 0.45 76 P 2 TWO 19 VH2
+0.98 TEH TEC 16 COLD 600UL 0.46 73 P 2 TWO 20 VH2
+0.98 TEH TEC 16 COLD 600UL S.........................................................................................................
102 28 0.26 75 P 2 TWO 11 VH2
+0.74 TEC TEH 73 HOT 60OUL 0.45 43 P 2 TWO 18 VH2
-0.78 TEC TEH 73 HOT 600UL 0.26 75 P 2 TWO 12 VH2
+0.74 TEC TEH 73 HOT 600UL 0.45 43 P 2 TWD 18 VH2
-0.78 TEC TEH 73 HOT 600UL 102 30 0.46 92 P 2 TWD 18 08C
-0.99 TEC TEH 73 HOT 60OUL 0.21 73 P 2 TWD 10 08C
+0.08 TEC TEH 73 HOT 600UL 0.46 92 P 2 TWD 18 08C
-0.99 TEC TEH 73 HOT 600UL 0.21 73 P 2 TWO 10 08C
+0.08 TEC TEH 73 HOT 60OUL 102 34 0.26 97 P 2 TWD 11 VH2
+0.68 TEC TEH 76 HOT 600UL 0.29 87 P 2 TWD 13 VH2
+0.68 TEC TEH 76 HOT 600UL 102 38 0.24 140 P 2 TWD 11 VH2
-0.73 TEH TEC 2
COLD 600UL 0.24 140 P 2 TWD 11 VH2
-0.73 TEH TEC 2
COLD 60OUL 102 48 0.38 79 P 2 TWO 16 VH2
-0.57 TEH TEC 4
COLD 600UL 0.41 68 P 2 TWO 17 VH2
-0.57 TEH TEC 4
COLD 600UL 102 66 0.26 124 P 2 TWO 13 09H
+0.89 TEH TEC 6
COLD 600UL 0.29 102 P 2 TWO 14 VH2
-0.82 TEH TEC 6
COLD 600UL 0.26 124 P 2 TWD 13 09H
+0.89 TEH TEC 6
COLD 60OUL 0.29 102 P 2 TWD 14 VH2
-0.82 TEH TEC 6
COLD 600UL 102 74 0.26 152 P 2 TWD 12 09H
+0.56 TEH TEC 8
COLD 600UL 0.23 155 P 2 TWD 10 09H
+0.56 TEH TEC 8
COLD 600UL 102 78 0.53 125 P 2 TWO 21 09H
+0.97 TEH TEC 8
COLD 600UL 0.53 125 P 2 TWO 21 09H
+0.97 TEH TEC 8
COLD 600UL 8
COLD 600UL
-0.13 TEH TEC 102 80 0.47 101 P 2 TWD 19 09H
Framatome ANP Inc.
Customer Name: SONGS Unit 3
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY:
rpcicodes and_0-100%twd.qry 01/26/2003 10:53:33 AM Component: S/G 88 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.25 137 P 2 TWD 11 09H
+0.82 TEH TEC 8
COLD 600UL 0.21 73 P 2 TWD 9 DBH
+2.08 TEH TEC NEW 8
COLD 600UL 0.46 108 P 2 TWD 19 09H
-0.13 TEH TEC 8
COLD 600UL 0.28 133 P 2 TWD 12 09H
+0.82 TEH TEC 8
COLD 600UL 0.30 98 P 2 TWD 12 DBH
+1.70 TEH TEC NEW 22 COLD 60OUL 102 82 0.26 109 P 2 TWD 11 09H
+0.69 TEH TEC 8
COLD 600UL 0.31 119 P 2 TWD 14 DBH
+2.16 TEH TEC 8
COLD 600UL 0.26 109 P 2 TWD 11 09H
+0.69 TEH TEC 8
COLD 60OUL 0.31 119 P 2 TWD 14 DBH
+2.16 TEH TEC 8
COLD 600UL 102 84 0.27 61 P 2 TWD 12 DBH
+1.46 TEH TEC 8
COLD 600UL 0.29 99 P 2 TWD 13 DBH
+1.46 TEH TEC 8
COLD 60OUL 102 92 0.20 61 P 2 TWD 9 DBH
+1.84 TEH TEC 13 COLD 600UL 0.20 61 P 2 TWD 9 DBH
+1.84 TEH TEC 13 COLD 600UL 102 108 0.45 118 P 2 TWD 20 VH2
-0.77 TEH TEC NEW 16 COLD 60OUL 103 33 0.40 112 P 2 TWD 17 VH2
+0.89 TEC TEH 76 HOT 600UL 0.41 107 P 2 TWD 17 VH2
+0.89 TEC TEH 76 HOT 600UL 103 41 0.18 151 P 2 TWD 7 VC2
-1.01 TEH TEC 1
COLD 600UL 0.18 151 P 2 TWD 7 VC2
-1.01 TEH TEC 1
COLD 60OUL 103 55 0.26 133 P 1 SCI TSH
+0.11 TSH TSH 0.00 9.26 11 HOT 580PP 103 71 0.42 122 P 2 TWD 16 09H
+0.96 TEH TEC 5
COLD 60OUL 0.42 122 P 2 TWD 16 09H
+0.96 TEH TEC 5
COLD 600UL 103 75 0.41 126 P 2 TWD 17 09H
-0 86 TEH TEC 8
COLD 600UL 0.26 108 P 2 TWD 11 09H
+0.47 TEH TEC 8
COLD 600UL 0.34 80 P 2 TWD 15 09H
+0.71 TEH TEC 8
COLD 600UL 0.34 82 P 2 TWD 15 09H
+1.01 TEH TEC 8
COLD 600UL 0.45 61 P 2 TWD 18 VH2
+0.71 TEH TEC 8
COLD 600UL 0.45 61 P 2 TWD 18 VH2
+0.71 TEH TEC 8
COLD 600UL 0.41 126 P 2 TWD 17 09H
-0.86 TEH TEC 8
COLD 60OUL 0.26 107 P 2 TWD 11 09H
+0.47 TEH TEC 8
COLD 600UL 0.34 82 P 2 TWD 15 09H
+0.71 TEH TEC 8
COLD 600UL 0.36 105 P 2 TWD 15 09H
+1.01 TEH TEC 8
COLD 600UL 103 79 0.25 155 P 2 TWD 11 09H
-0.93 TEH TEC 8
COLD 600UL 0.34 94 P 2 TWD 15 09H
+0.20 TEH TEC 8
COLD 600UL 0.38 132 P 2 TWD 16 09H
+0.67 TEH TEC 8
COLD 60OUL 0.34 94 P 2 TWD 15 09H
+0.20 TEH TEC 8
COLD 60OUL 0.25 155 P 2 TWD 11 09H
-0.93 TEH TEC 8
COLD 60OUL 0.39 131 P 2 TWD 16 09H
+0.67 TEH TEC 8
COLD 60OUL 103 81 0.55 100 P 2 TWD 21 09H
+0.86 TEH TEC 8
COLD 600UL 0.55 100 P 2 TWD 21 09H
+0.86 TEH TEC 8
COLD 600UL 103 85 0.36 96 P 2 TWD 14 09H
+0.21 TEH TEC 7
COLD 600UL 0.36 95 P 2 TWD 15 09H
+0.21 TEH TEC 7
COLD 600UL 103 87 0.40 129 P 2 TWD 17 09H
+0.00 TEH TEC 8
COLD 60OUL 0.44 118 P 2 TWD 18 09H
+0.00 TEH TEC 8
COLD 600UL 103 97 0.27 39 P 2 TWD 11 09H
+0.90 TEH TEC 13 COLD 600UL 0.31 113 P 2 TWD 13 09H
-0.92 TEH TEC 13 COLD 600UL 0.42 57 P 2 TWD 17 09H
+0.90 TEH TEC 13 COLD 60OUL 0.28 27 P 2 TWD 12 09H
-0.92 TEH TEC 13 COLD 600UL 103 103 0.17 11 2
SAI TSH
+3.16 TSH TSH
.29 10.16 65 HOT 580PP 104 32 0.26 79 P 2 TWD 11 VH2
-0.82 TEC TEH 73 HOT 60OUL 0.26 79 P 2 TWD 11 VH2
-0.82 TEC TEH 73 HOT 600UL 104 46 0.25 161 P 2 TWD 12 VH2
-0.93 TEH TEC 4
COLD 600UL 0.25 161 P 2 TWD 12 VH2
-0.93 TEH TEC 4
COLD 600UL 104 78 0.16 141 P 2 TWD 6 09H
+0.41 TEH TEC 7
COLD 60OUL 0.16 141 P 2 TWD 7 09H
+0.41 TEH TEC 7
COLD 600UL 104. 88.
- 0. 44.....
91....P...
2 TWO
- 17.
088...
0...51....TEN.....TEC...
13....
COLD.....
600UL...
104 88 0.44 91 P 2 TWD 17 08H
+0.51 TEH TEC 13 COLD 600UL 0.43 89 P 2 TWD 17 08H
+0.51 TEH TEC 13 COLD 600UL Page 31 of 46
(0
'4-4 0
04 (e)
.4.4 00C (0o 14 ).4 00 00 00=
(D0C)
.1.44-)4--)4 I
- 4.
0000 I
0000 (OOO0 I to (OOO
.1 0
o O
I 0
I C4 I LD W II 16 ii C'C 0E, NE I
.4
I Hw 10 1W C
I Ir I
0
+ +
I I
I-1 rI ý IM M 00 I H H-I 00 IW Il I I I 4
I P4 Iom r-r I
m I
I NCN 0 0 0
0 1 00q 1001 001 001 uu 001 OOI H
H-H H Iý N N NP w wWWW I
W WWW EHH Iý HýE E-HE-H en en I H H I
N N I
w w I
U W W I
W 0
ID I
I I
I 100I I
CI m
I I
1 I
Iý I
I II S-1 I00 I HH
.4 4144 I 4,41.4 4 43/44 I -PE HHH I.4 00 100100 100001 000W101 00 00C 00C 4--)
0 0
to 0
u W
I I
WI P
1(1) 1
+
- 10.
1W o
I0 I 0I H
14 I0 r,
-IH Iw
'0 1014 00 00 00C w0(0 00 00 I41
- 4.
00000 I:)DM=
000000 I
W W W WWW I
I HE-. E-HH I-E I H En 0, H 0 En I I
N C 0 N- 0 en I000000 I
I ++
I + +I 1 I N I N n N en NI I I > > >>>
I H-N% H-H- H-NI Cq NN Nq N N CN I-I04M 004-q04 I
H 4
H
-H 1
H H -H ICD Ne oe ID0 C) 01 0l to 01 en I WIZ WI WI
-H HI N N mWo I WWa HE-I HHE N4 N IN CN 040a410404 I (0(%D U, 0 I 00 U,)
t0 rI H H IOU I
H U I OW I1, E1 Iý HH IN N 0404 I >0 100 I4 0H I 0 IN 04 IN I H)
IH IU, U, co ko I 0 IO I-4 C-) -)
I 00 I0 w0(w I mo
-.4 3 00 00I 00C 00 w0(W 0t0 CD00 (10(0I
,.-1,.-3 00 w0(D 01 )
00 H4 H U
U 00 WW H H oco 1
) I0 I> 00 I
I I HH 1040N I 0
ý I
m 10 I H 10 I H4 C)0 001 I0 I00 I
I0 1I00 I IU Ulu o o W
I WWI 10E41 00. I2 I P I E E-I 101 00I I U I CI 4 I I I I
I I
I I
I I
c I
I I
I N I N
I I c D I 0I I
I I
I 101 00 I
I II I 00 I HHU WOW I E-4 i
I EQ E
ý,r, Il ene I00 I I N IIne 00 00 I I N>
00 H H N N4 to en N1 N
- 0) 0 H1 W W I
WW HHE I HE HEP I EHH 4
I 00 I 00I tot
- 0*0 001 00 to toI HD W 00 I 00 00 100 I:) I::
J H-H I -NN 00I 0 DOW W0( I (W W(W(W H-EI HE- & I HHE
((
MI (0
14 W HE-I H
I E-E en m I r-' r-n W WI H HI Oý 001 I 00 C
> 00 I 0 I ar I ýc U, IEH H I 0 IOWD I H I- (n~
I I.¢1' I 00 H
CD,,
I 0 I Ho 00100100 00100!
Z=
I 0-H H 0 I-HI H H I NOO N
I >
0 I HEH H H I N N NA N m104040404 I 00 H
H
ýIH I 0-00I 00I Nq N I
en0 I H
H-I 00 1
04 041 U, U,) I 0
N I4 H-H I
en UI 0I H4 I
U U UO L)1U HE-I HE-I, HE-E
- 4 x
OW I W I OWW E0 P0 E0P1P0H HE-H HE-en
- 41)
L)0 00a
- 04)
(a0 (a )
w0:
00)u I (00 (Y0 I 0000
+
I00+
I W W
CI HHHH IN N1 N N I
H-
-T IN en U, N Ir (N em NI I (
I0 I H-N H to 0
OH I
I I
I H2 Ia 004 I
w I I I m
rI I
ID I
I 00 0
I 1
0, 0
H H
0 U)
CIZ E
0 H
0 II 0 I H II Z
104I H
I O
I 0..I 13 1
..1 0- II 11:
(0 II 0 I C4 11 4 m 0
C) 0 (0
0 0
101 I0 C14 I>
H 1I0 1 :3 IN 104 I i-I I U, 1(0 I '-4
>1 w
rR 41 d0 0 C) 0 H "0
CD U) 8 "10 U
04 0
(0 04 0
WI WW W WW H-I H E-I HH E
I IO O 0 IWO IW WI (0(01(0 I S I
+ +
I In M
I I
LD..
I 4 I
I I
I-C nIJ I
0 0I I
Ir I
n n I I
Ir II I00 I 'A 1
N N 00 to toIw 00 I 00 N 4 N
INC I O 00 E
I H H
00I H-H 00 In 00 e) n ri H
In 0
10 H-H-
4-4 0
III 04 0
11 000 II 000 II ;000 IN It W r) UW.
(4 II H
H4 11EI HE
-3/40 00 1
00 I
00 I
00I I P IE 1
I I
I
+
I N 0 I
I Iq I
4 I
I I-E I
Iq I fl.
I~
I HH I
I In L
I MN I
1 1
I I
I I
I C)
I 1I I
0-C)3/4Ci0 0000 to to t.o to 001 00 1
to to I 00 00 1
00 k
I 0
0 D to o
0 9-i 0
0 w o I w D
I I
I4 0m 0
0 wo H
0 1
IS Nz w
H 0
CN H
H IN I HT I ýD I I
ID 1 14I 101 I tO I
I I -
I 101 I
I INI I -
I rII I
I 1011 I0 I
ID w I wi I 00101 I
I Hir I HI 00 0 00w1:1 I-E I
I1 I1 r
Iý Iý C
U U
I C I C N HH1 I-H MN I1 N HH I IN IN I 00 Im 00 I0 I) I I 00-1 01 L2 0'
0.
HI HHP H-4 00 E
IN4 0 C)
INI0 0
+
0 I
IN IN0 H I-EH IN IN IN 0; I 00 I 0o H
I H N
i I
1 1
I 1
1 1
00 10 0 0D I 0
w to I to to
.01) 94 2)12 00 100 MN INN11 H H I HE-4 H H I H H 0000 001001 u
I U
I m
I1 EI In In InI I
+
I I
1 00D to o 00
. -)- I to toI W
I p
I HE-E
- I I I
I I
I I
H Iq IIM m
I:
I H-H I
IX 00 I HH Iý I
I II I CD I -
I N N
,-iI 01 0p I 4 ii 0 u I NI k0 z
uI r-t NI HI OI In I NI 0I I I INI Q1 N
I HI 01 1 0 1 IN I 01 I I EHHE I EH lI EHH to tD 0U H H D1 w I
IN 0-00 IH H IH H cq cq r-t r-l
- 0)
I HH I INDI 100 I H I Iý 00 I 00 I 0 I N IN 00 I1 HH I 00 I HHE INN I HýC IH m
00 I
wto Io 00 H
HI Oý0 O0
- 00) 1 C) 0 k o I w o
I I
p 00 I00I UU I I
ý w
Io N
04 r-r 00 to to I HH I 001 POl w
w EI I
I I
I E-IE I
1 I
I Iq I
I Q
Ig Im I E-I I N N I4 OW I
I; IHH I
Iý NM I uNM HHw I HHw EH E-HHE 1
1 : I I
0 IJ C4 I
I-I-o N N I N NI 00 I-C 00 I I
Iý Cý I I;
In I
H I
I1 I
IN1 IN I NI I
I 00 00 toot C)
C 00 I
to to I
00 00 00 k p I w W I kow I
I 4 4
-I I1 00 1001001 00u I 00L I 0) 0 I
-i I C I 00 00 00 0
Ix=
0 00 to t H U NM HH I 0 11 P H Hq I4 04 I IN4 IN IN ININ IN I IIN IN I40 00 a
N N I0 H 0 00 I H rH Mw I
N-N I
CýOý 00 I
I
- m IH H 3:
E-00 100 (nOD
-04 I HH C
ID0 I 0l I 04 I 0 oH I H I
H r-I HH E=- E L) 0 IMN I EH I-NEN r-- r I 00 I 00 I I I
C--4 C-N I
0 IEH H I
04 I
00 I04H IHH I Hl In In NM HHE
ýr.e HHE In In r-t 00o I I CI 0
00 IO 00 I IN I
I 00 I In In IM 00 I 00 IN4 IN ICIN H
I H-00 I
0 N
0 0 0 o o H
H4 I N IN I ++
to to ID 00 00+ I 00 INN C
I NI In to I-NN H1 H Iq HH E-H I HE-E IN IN I II 0010 Hj H-I 00 00 I 00 0
0 IN 10 10 H
H C
H-H4 IO q IN 04I I H H H-H I IN6 C
I0 I H 00 r02U 0041
,a0 onL)
- N 0ý I
I
+4 PQP I
IQ c
Q I I>
0 I H N Iq NNC to to H H I 0 In COI In I
00 r0 1
00
) (In l I H 0
C IN 0ý H4 In 0
0 H
I0
-IW
+I
+
000 Cl
+'
In In 0ý I
I UU PE-4 I
WH H HH Iý to I 00 II I
>I
-I H-H I N IN CW ia4 I 00 I I H I00 1 -4
,E 0
o H
ý-Z H
H 02Z 0
Z2 H
()
11 C (,1 4 C..l 0
x Hp 11
,- H
-I H-IIF4H Z
1 IN IN IN Ow O, -I l OC-I 0 I dO II H H
10 i Oý 110 NIII0'I 0
IH 4J Op 0
0
'A
-0 LO)
H' w
I-I C
c 0
H, H--4
-t 00 NM HH 00w NM E
HHW I
44I 0
N i
4 (0
- )..9 0
4J HD 0 C,-O 00 CC 04 NHI El 0 I o
i N
I I
CC I NW IH-1 I ZNE I
E-,
I; 00 I00
,-,4 II I
INN I>>
I-H en I H H 100 I 3 IH-t
)00 wJ w 00C w o 00~
0D0 WD W O00 00 I
CCI 0 0 00 u u NJ C I
00C 00C 00 WoW I
00 1 0 I
I 0 0 I 0 I
I E-W- I pJ
+ +
I CDC I
I00 IC0A I 00 I 0H I
I I N NIc IN N, W
I I
I C
I C
I CD 1I I
I I 1 I
0000 k k I
0000
.4.U.4.4 0000 I
C14C4CC4 I E-HElE I HýE-HE I N 0 N- 0 I
0 W 0 I 0000 I n N1 en CN I. CCCC)
I n U-enT I HE-HE-E I0N N N N Iý 0H 0 en IN %.D en en I-N en ene en en en e I 41214 I HE 1 00 1
00 I CC I
Z=
en
- 4) m LD Z
O0 o 10 0 v 0 0.
Fý41 (a )
04u 00 I
NW I E-I ZN I
(-4 (4l NN I H
H
¢1 El
,E en-enl m 0 II 100 Iý 33 IOHD I N W-H N N)
NZ WN H-E C*4 ILN HE C-H IN 00 I 0 O01 I
0 I
0 I-W W-I I
I I
I
,I I
CI I
OI (
I, I
I..
I I
H-E
,-I H II I
I ZN 1 0 0
¢cli I00*
I H-0 I 33 04 IH-4 IO L I k 0I0 I 0 I
I 01 0 E 000 I
+
I I
l I
I.
I O I 0 I
I I ý I en I r I H I 0 0 0
0 C
I I
I I
I r-I I
o I
0O I -fl I00 IC-0 0
I 0 1 u
I E I 310 NI C,
m CI HI 0
0 0 NJ Ct 0
u IN a1 IC IN H
IN 00 00 w W HE-E 00 NJ W
- El NN HE-E I
I I
I I
I I
I I
I I
I I
001 00100 I 00 I 00 I 00 I 00 I 00 I 00 I W W I NJ W I
W NJ I
I I
I I
I I
I I
I I
I I
I 100100 100 I
I
-ll
I 100100100 ICC I
I I
I I
I I
I I
I I
I I
I en en I N N I H H I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I ICC I CC ICC I NW I NN I NW I HE-I HH I HE I
I I
I ZN I ZN I ZN I NW I NW I NW HE-! HE-HE I
I N
N1 Hý "Zý Ný I EnEn Im NN en1 en In HH 33n 133 00 100c 0 I H-0
-Ien 0c H n0 I
I 0I I
I N
4 IL I00I I
0 0 I I 001001 C)C)I CCuI en en)
H H
+4+
Eý1 E" NCC4 P400
-40 en en HE-0 3
E.
,-4 0
- 0)
H) 0ý I
I I
I I
I I
I I en en I I H H I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
ICC I
I NW I
I HE-I I
I I ZN I
INN I
I HE-I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I 00 I
I
I I
I H H I
1+41 I
I I
I I
I I
I I
I I
ZN I
1001 1001 I
I I
I I en en I I H H I
I I
I 001 133 I
I HE-I I
I I N N
I I
00' I
00 I
H H I
en en I
I 00 I N I 0 I H H
E.
I.
HI ca HE-E
- Z NW HE-,
CA00 0 0 I C IN N I en eni I 0 00C 00C W kN
,--1,I 00 00 NJO J 001O I
I
+
+
I I
o I
o CD Co 0 01 00 0
I00 u
I 0u 0
I 00 0 El I
- -t E en I n en WI NW0 0
I 00 H
IH H4 0D1
-1 0 N
n en CDl 0 -I 0
00 I UC 0
II OZ H I O>
C-II 0=I "3.I
- II N II C II C--1,-
00 I
O w I
001 O00 N
N i
,I NW.I E-HE IE-E-
I I0 I
I P
E I
(-14 C4 Iý I1 ID 00
,--1 Io HHO 1111ý I O 0I 0
Z 04 CI W
NI WI CI WIt HI NI NI HI4 4
H 0
0 Op o
0 CD to 0,
0
-4 Ul 00 r H4 H I HE IN N1 IN N1 MM PI 0 I"-
I I>>
100 S00 I
I e-e Ný N CN N1
0 U')
04'0 (N
L) o 44
-a C V 41!
rd V)
'-Cz WHO I-i 0 C C
(0 I-i'Ci 00 CD D 0
nI C C Zi 00 0
Ii-i i--i 1
w 1I 00 HIDI E-ill
!=
NO 11 H H 0
CD 010 C I C)
CIC E.0 I E.0 I U N-I N
Z4Ix 010 H4I Hý WIN NIO HIHC LO I U 1001 I (0(
I 100 1 00 I
H H I Nw I HH E
IN N I0 H
ICý Cý IC) UD IDN C) C)
Cý C ID0(D 0
11 IN C) C)
C C)
(0(w 00 Co C i-i' 00 C C C C (0(0 0 C 100CD1 001 00 I
C o
C w
I Co C I
C C
I I
I)
I -iD-I 1 001 I4 W
I I.
E Iw I
E I
I F
I 004 I.00 CIOUC I
ý a I
IO I
I I
I I
I I
I I
I I
100100100 I C C I C C I C C I C C I C C I C C I (0(0 I (0(0 I (0(0 I
I I
I I
I I
I I
I I
I I
I I
I 00 I 00 I 00 I i-i
I i-fl)
I i-i-i 1001 00100 1001 00100 I
I I
I I
I I
I I
I I
I I
I I
I en en I Cnlfl i li-I en I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I HHP I HHE I P H I PHH E-HE I EH EI HH 1 HH E
I NW I E-H INW IHH (0
w 0
0 H
H 00w NW E N4 N CI Q IN NW 00 OD OD I0 OD Uo OD 00 E (NW(
C Co I HH 00 1
0 ID I
-I I-i)
I 00 I0 C C I C C I C E,0 p. Ip.
NWW HH E
EN E CN CN 0 0 H H N (
00 I DI IDk I E IE u
I
+ +
I Iq I
INN I NW I
D I
I o
Io H 1
D I
o I
ý I
I 0
I
)
I D
)
C C) nC CD C) C C) C I
C C I
C0 C1 W00 I'0'0 I((
00 C C)
CD C 0-, CD 00 1
(0(
I
.- fli 00 C C O C (0(0 00 i 00 100100 100 100
-li-I iii)U I U-I.
C-i) I -i I-I 100 1 0 1 00 I -ii-I.- I u 1001 00 100 1
00 1 00100100 i
1001 00 00 00iu ! 00 I0 NW!u E-H C C c 00 (N C4 00 ZN HH (NA(
I I
I I
I I
I en en I
H H I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
100100 I NW I NW I HH I HH I
I I NW I NW INN INN I HH I HH I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I U) U) I (0(0 I N N I (0(0 I
-I I H H I H H
I
++
I
++
I I
I I
I I
I I
I I
I NW 100 I
00100 100100 I
I I
I I (0N I
I H H I
U) U)
I I
I 00 I 00 I ZN INN I HH I HH I
I I
(N N I (N (N I
I I 040410404 I
I I
I I N U)
I I U)
I N N
I I
I I
I I
I H Ifl I U) U)
I *
I H H
I C C I C 0
I I
I I
I I
H (N
U)
I
I I
1(0 IC H
(N H
H 00 0140 NWw (4W (N (N U) a)
C Cý I
I C, C H
H)
Co 140W I
EHHE I NW I
HH IrC CD I I Iý HH I00 I N cI H
I (
(
0 0 C C0 INN 00 HHE N Nq Cn C4 (N-W 0 0 NN a) (
I I
PI E IE-E I
In I ýC I
r I U) U)I ON(
I D
I I
I I
4 rI I enD IC'4 I I 10 100
'14 00 C4 04 C C I
CD C
U)
H 81 ii 0
I H 0E I zi-i II: H N Itci 1
0 II 00 H IIHo N4 II 0o LO 40
.No I-D 0'
04
>44 I4 04 I
E+ E IN C4 INN Io 00 SNN IHH (0
04 04 I0)
IN I U H4 I Cý C)
I I I
I H-H I00
4-4 0
Uo
%.0 e m oD -
.-4 U) en..
o4.
OC N 0)
C) 0 NO 4I en 4*J 0
00 CU)
"cci z
4-)E rd 0
ý4~
1-14 0
II
)I I Iz u-1I 4;1 ii 10,I I-4 W.4I H I H I 0
II 00 00 00 001 uu I
C I
I O0 I
u
-o I w. I 00 1 0 1
00L I 0 I
U) U-) I U) I IO
+ +
00T
,-0 00 I
E I
00 I 0 LOU IwU HE0 I
0 00 000 I 0 U) U) U) U) C) U) I U) 00000010 w
ý 00000010 CD U)C)
U) U) U) U) I
+
I PI
-PE IH I
4 1 I w 0
I D
10 00 01 IH))))))IU 00 C) C)
C) C)
C0 00 00 I
1 00 I00 I 00 I 00 E
100 P4-P4 I N N
-I E-U)
I HH mo I H IN N Cý I
-4 cm 100 I 00C
)00 I U) C) CD U) 0000 I uuuU U) U) I w- -41 m m Ec)
I)
HH I U) U) I C00 IT Um 00 04(3 mm NNI en en-I
.1 001 100 1 00 i 00 I.-3/4-I.-ThI) I 1000O01O00 100100100 00c U) 0 0 EU)
EI P HH ko 00 4 I I4 m m 00 NN 0
I 00 I
0 I 00u I CU) I U) U) I
+
+
U) I E) E) I P4 PI I
nID I
0I N
- 10)
I N N) I I 0 I
I I
I I
I
-I -. I I
I
- N mm 00I 1H 1
U)U 00 I4 I E-E N N
-4 I 00 N
N E'1 1-4 040 NN 0
-4 0
0
ýO 0
L)
CD I 0l CDI 0
I U) I 0I UI El E. i HI ml La U) 0 m
t-4 H
014 r-4 I 0 Io0 00 I 0000 00 I 0000 U) U) I U) U) U) w 00 I 000000 O00I 000000 U) U) I U) U.0 w) w) w w
0 1000000 001000000 001000000 Nr N
WWW'4 4-4 HH I HEIHE-4E-'
mm i mmmmm U)U)
WU)U)UU U) z 0
U H.
Cm en en I U) U) U) U)
BE-4 E El El 00 H
I N N U) U) 0 0 OtD C1-4 Il>N I
vI U) U) U) U) I 0000 0oC00 I HHHHP I H PE-HH II
+
I I 11 qI I iH 41 I A I
E I4C N
N4 N
NN I4 0U)U)U 1 C
'I1 4a 10 4P 1
I
-000 I 000 w1w+1+11111w I D Hw rI Hm I
H I
L I
I 4
1-4---
Iq- ---
00 SCU)
HE-'P
=mm W)U4 EHH LO U)
.- EI 00
- m 040 00
,U)
I N
H 0000 I u E
Iu Il H
H IP I E E mmmm I 0 U 0 C)
I 'A U)U)U I 0000 E E
I04 N -4 N I CC) en 00 en m--44 I0000 I om ICHH I
N N
,-41 00 E-I Em E IN N* 0N Uo I v-I v 0
I 00 r,
mm H
r N
I0N
-4 1 N U I N -409 4 -4 I 0 00000 C
IN 0
m H
H U)
C) 0 H0 0
-4 01
'U CI
'0 (0
00100100001 00!
00!
0000!
U) U) 0co0 00C U) U) 00 E-PI ECU HH mm N N
+4-00 00 00 U U D00
) U)
E.HH IE-El C.D Q, Ei ECU I HH IN ;N I 0 IH>
I"en U)
IN N Il i00 I 00 10 I v-N -VN N N4
-400-C 4 0 0 1 ++1I4++
mmmm 1 HHHHHH L
I Iý N -
N N
i N N
Framatome ANP Inc.
01/26/2003 10:53:35 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 37 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 122 114 0.30 118 P 2 TWD 14 VH1
+0.47 TEH TEC 16 COLD 600UL 0.30 118 P 2 TWD 14 VH1
+0.47 TEH TEC 16 COLD 60OUL 122 118 0.40 102 P 2 TWD 17 VH2
-0.88 TEH TEC NEW 18 COLD 600UL 123 41 0.25 103 P 2 TWD 12 06H
-1.14 TEH TEC 2
COLD 600UL 123 43 0.29 143 P 2 TWD 12 08C
+0.82 TEH TEC 3
COLD 600UL 0.28 127 P 2 TWD 12 08C
+0.82 TEH TEC 3
COLD 60OUL 123 49 0.28 91 P 2 TWD 11 VHI
-0.84 TEH TEC 3
COLD 60OUL 0.23 147 P 2 TWD 10 VHI
-0.84 TEH TEC 3
COLD 60OUL 123 59 0.26 124 P 2 TWD 12 VHI
+0.67 TEH TEC 6
COLD 60OUL 0.26 124 P 2 TWD 12 VH1
+0.67 TEH TEC 6
COLD 600UL 123 95 0.63 93 P 2 TWD 23 VHI
+0.90 TEH TEC 13 COLD 60OUL 0.60 71 P 2 TWD 22 VH1
+0.90 TEH TEC 13 COLD 600UL 123 97 0.31 10 P 2 TWD 13 DBH
+1.36 TEH TEC 13 COLD 600UL 0.31 10 P 2 TWD 13 DBH
+1.36 TEH TEC 13 COLD 600UL 124 42 0.19 104 P 2 TWD 9 04C
+0.85 TEH TEC 4
COLD 600UL 124 54 0.23 135 P 2 TWD 10 VHI
-0.86 TEH TEC 3
COLD 600UL 0.27 113 P 2 TWD 11 10H
+0.69 TEH TEC NEW 3
COLD 600UL 0.23 136 P 2 TWD 10 VHI
-0.86 TEH TEC 3
COLD 600UL 124 56 0.17 117 P 2 TWD 6 DBH
+1.69 TEH TEC NEW 5
COLD 600UL 124 64 0.32 51 P 2 TWD 12 VHI
+0.92 TSH TEC NEW 5
COLD 60OUL 124 76 0.38 147 P 2 TWD 16 VH2
-0.73 TEH TEC 8
COLD 60OUL 0.28 121 P 2 TWD 12 DBH
+1.72 TEH TEC NEW 8
COLD 60OUL 0.44 146 P 2 TWD 18 VH2
-0.73 TEH TEC 8
COLD 600UL 124 84 0.29 125 P 2 TWD 13 VH1
-0.78 TEH TEC 8
COLD 600UL 0.30 55 P 2 TWD 13 VH2
-0.93 TEH TEC 8
COLD 600UL 0.36 86 P 2 TWD 16 VH2
-0.93 TEH TEC 8
COLD 600UL 0.38 89 P 2 TWD 16 VH1
-0.78 TEH TEC 8
COLD 600UL 124 86 0.19 101 P 2 TWD 8 DBH
+1.39 TEH TEC NEW 7
COLD 600UL 0.37 14 P 2 TWD 15 DBH
-0.11 TEH TEC NEW 7
COLD 600UL 124 96 0.55 45 P 2 TWD 20 DBH
+1.77 TEH TEC 13 COLD 600UL 0.19 21 P 2 TWD 8 DBH
+0.47 TEH TEC 13 COLD 600UL 0.24 30 P 2 TWD 10 DBH
+0.53 TEH TEC 13 COLD 600UL 0.57 43 P 2 TWD 21 DBH
+1.77 TEH TEC 13 COLD 600UL 0.19 21 P 2 TWD 8 DBH
+0.47 TEH TEC 13 COLD 60OUL 0.19 71 P 2 TWD 10 DBH
+0.53 TEH TEC 13 COLD 600UL 124 110 0.77 116 P 2 TWD 23 VHI
-0.11 TEH TEC 15 COLD 600UL 0.76 124 P 2 TWD 24 VHI
-0.11 TEH TEC 15 COLD 60OUL 124 112 0.97 119 P 2 TWD 26 VHI
+0.60 TEH TEC 15 COLD 60OUL 0.81 106 P 2 TWD 25 VHI
+0.60 TEH TEC 15 COLD 60OUL 124 116 0.88 149 P 2 TWD 25 VHI
-0.60 TEH TEC 15 COLD 600UL 0.89 150 P 2 TWD 27 VHI
-0.60 TEH TEC 15 COLD 600UL 124 134 0.16 71 P 2 TWD 8 DBH
+1.93 TEH TEC NEW 20 COLD 600UL 125 49 0.30 114 P 2 TWD 14 08C
+0.79 TEH TEC 4
COLD 600UL 0.31 107 P 2 TWD 14 08C
+0.79 TEH TEC 4
COLD 600UL 125 67 0.36 56 P 2 TWD 14 VHI
+0.96 TEH TEC 5
COLD 600UL 0.37 55 P 2 TWD 14 VH1
+0.96 TEH TEC 5
COLD 60EUL 125 93 0.58 43 P 2 TWD 21 DBH
+1.80 TEH TEC 13 COLD 600UL 0.58 43 P 2 TWD 21 DBH
+1.80 TEH TEC 13 COLD 600UL 125 97 0.30 49 P 2 TWD 14 DBH
+1.72 TEH TEC NEW 14 COLD 60OUL 125 99 0.36 31 P 2 TWD 15 DBH
+0.72 TEH TEC 13 COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:35 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 38 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.39 40 P 2 TWD 16 DBH
+1.71 TEH TEC 13 COLD 600UL 0.36 31 P 2 TWD 15 DBH
+0.72 TEH TEC 13 COLD 600UL 0.40 42 P 2 TWO 16 DBH
+1.71 TEH TEC 13 COLD 600UL 125 115 0.39 134 P 2 TWD 17 VHl
+0.58 TEH TEC 16 COLD 600UL 0.40 131 P 2 TWD 18 VHI
+0.58 TEH TEC 16 COLD 600UL 125 131 0.17 158 P 2 TWD 8 DBH
+1.98 TEH TEC NEW 20 COLD 600UL 126 52 0.38 149 P 2 TWD 15 VH1
+0.84 TEH TEC 3
COLD 600UL 0.38 149 P 2 TWD 15 VHI
+0.84 TEH TEC 3
COLD 600UL 126 56 0.23 44 P 2 TWD 9 VHI
-0.81 TEH TEC 5
COLD 60OUL 0.24 44 P 2 TWD 9 VHI
-0.81 TEH TEC 5
COLD 600UL S.........................................................................................................
126 60 0.66 126 P 2 TWD 22 VHI
-0.96 TEH TEC 5
COLD 60OUL 0.66 126 P 2 TWD 22 VHI
-0.96 TEH TEC 5
COLD 600UL 126 62 0.21 137 P 2 TWD 10 VHI
+0.02 TEH TEC 6
COLD 60OUL 0.28 124 P 2 TWD 13 VH1
-0.80 TEH TEC 6
COLD 600UL 0.28 126 P 2 TWD 13 VHI
-0.80 TEH TEC 6
COLD 600UL 0.21 137 P 2 TWO 10 VHI
+0.02 TEH TEC 6
COLD 600UL 126 66 0.49 132 P 2 TWO 20 VHI
-0.41 TEH TEC 6
COLD 60OUL 0.25 141 P 2 TWO 12 VHI
+0.66 TEH TEC 6
COLD 600UL 0.44 108 P 2 TWO 19 VHi
-0.41 TEH TEC 6
COLD 600UL 0.25 141 P 2 TWD 12 VHI
+0.66 TEH TEC 6
COLD 600UL 126 80 0.35 119 P 2 TWD 15 VHI
-0.74 TEH TEC 8
COLD 60OUL 0.35 119 P 2 TWD 15 VHI
-0.74 TEH TEC 8
COLD 600UL 126 96 0.30 102 P 2 TWD 14 VH1
-0.67 TEH TEC 14 COLD 600UL 0.30 102 P 2 TWD 14 VH1
-0.67 TEH TEC 14 COLD 600UL 126 100 0.34 100 P 2 TWD 15 VHI
-0.71 TEH TEC 14 COLD 600UL 0.34 100 P 2 TWD 15 VHI
-0.71 TEH TEC 14 COLD 600UL 126 104 0.37 150 P 2 TWD 17 VHI
-0.56 TEH TEC 16 COLD 600UL 0.37 150 P 2 TWD 17 VHI
-0.56 TEH TEC 16 COLD 60OUL 126 106 0.53 131 P 2 TWD 21 VHI
-0.36 TEH TEC 16 COLD 600UL 0.53 131 P 2 TWD 22 VHI
-0.36 TEH TEC 16 COLD 600UL 126 108 0.46 141 P 2 TWD 20 VHI
-0.75 TEH TEC 16 COLD 600UL 0.25 125 P 2 TWD 12 VHI
+0.17 TEH TEC 16 COLD 60OUL 0.46 141 P 2 TWD 20 VHI
-0.75 TEH TEC 16 COLD 600UL 0.25 124 P 2 TWD 12 VHI
+0.17 TEH TEC 16 COLD 600UL 126 110 0.95 133 P 2 TWD 31 VH1
+0.58 TEH TEC 16 COLD 600UL 0.96 132 P 2 TWD 31 VH1
+0.58 TEH TEC 16 COLD 600UL 126 114 0.39 119 P 2 TWD 17 VH1
+0.71 TEH TEC 16 COLD 600UL 0.40 116 P 2 TWD 18 VHI
+0.71 TEH TEC 16 COLD 600UL 126 118 0.29 121 P 2 TWD 13 VHI
+0.75 TEH TEC 18 COLD 600UL 0.33 148 P 2 TWD 14 VHI
+0.75 TEH TEC 18 COLD 600UL 127 55 0.26 60 P 2 TWO 12 VHI
+0.71 TEH TEC 4
COLD 600UL 0.26 60 P 2 TWO 12 VHI
+0.71 TEH TEC 4
COLD 600UL 127 103 0.42 118 P 2 TWD 18 VHI
-0.54 TEH TEC 16 COLD 60OUL 0.74 98 P 2 TWD 27 VHI
+0.64 TEH TEC 16 COLD 600UL 0.43 116 P 2 TWD 19 VHI
-0.54 TEH TEC 16 COLD 60OUL 0.75 97 P 2 TWD 27 VH1
+0.64 TEH TEC 16 COLD 60OUL 127 111 0.44 146 P 2 TWD 15 VH1
-0.64 TEH TEC 15 COLD 600UL 0.44 144 P 2 TWD 17 VH1
-0.64 TEH TEC 15 COLD 600UL 127 115 0.44 100 P 2 TWD 15 VHI
+0.68 TEH TEC 15 COLD 600UL 0.43 94 P 2 TWO 17 VHI
+0.68 TEH TEC 15 COLD 600UL 127 123 0.30 148 P 2 TWD 11 VH2
-0.84 TEH TEC 17 COLD 60OUL 0.30 148 P 2 TWD 12 VH2
-0.84 TEH TEC 17 COLD 600UL 4
COLD 600UL 128 46 0.23 125 P 2 TWD 11 02C
+0.77 TEH TEC
Framatome ANP Inc.
01/26/2003 10:53:35 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 39 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 128 58 0.39 111 P 2 TWD 17 VH3
+0.90 TEH TEC 6
COLD 600UL 0.23 36 P 2 TWD 11 VH3
+0.26 TEH TEC 6
COLD 600UL 0.23 143 P 2 TWD 11 VH3
+0.90 TEH TEC 6
COLD 600UL 0.23 36 P 2 TWD 11 VH3
+0.26 TEH TEC 6
COLD 600UL 128 70 0.35 71 P 2 TWD 13 VH1
-0.62 TEH TEC NEW 5
COLD 600UL 128 76 0.30 122 P 2 TWD 13 10H
+0.88 TEH TEC 8
COLD 600UL 0.30 125 P 2 TWD 13 10H
+0.88 TEH TEC 8
COLD 600UL 128 78 0.47 122 P 2 TWD 18 VH1
-0.73 TEH TEC 7
COLD 600UL 0.51 134 P 2 TWD 19 VH1
-0.73 TEH TEC 7
COLD 600UL 128 80 0.30 125 P 2 TWD 12 VH1
-0.79 TEH TEC 7
COLD 600UL 0.33 141 P 2 TWD 14 VH1
-0.79 TEH TEC 7
COLD 600UL 128 82 0.32 111 P 2 TWD 13 VH1
-1.00 TEH TEC 7
COLD 60OUL 0.33 113 P 2 TWD 14 VH1
-1.00 TEH TEC 7
COLD 600UL 128 84 0.41 56 P 2 TWD 17 VHI
-0.86 TEH TEC 8
COLD 600UL 0.29 136 P 2 TWD 13 VH1
+0.82 TEH TEC 8
COLD 600UL 0.39 47 P 2 TWD 16 VHI
-0.86 TEH TEC 8
COLD 600UL 0.30 141 P 2 TWD 13 VHI
+0.82 TEH TEC 8
COLD 600UL 128 86 0.41 110 P 2 TWD 16 VHI
-0.88 TEH TEC 7
COLD 60OUL 0.42 113 P 2 TWD 16 VHI
-0.88 TEH TEC 7
COLD 600UL 128 100 0.46 122 P 2 TWD 18 VH1
-0.83 TEH TEC 13 COLD 600UL 0.46 133 P 2 TWD 18 VHI
-0.83 TEH TEC 13 COLD 600UL 128 106 0.47 153 P 2 TWD 16 VHI
-0.66 TEH TEC 15 COLD 600UL 0.49 152 P 2 TWD 18 VHI
-0.66 TEH TEC 15 COLD 600UL 128 130 0.22 95 P 2 TWD 8 08C
-0.95 TEH TEC 30 COLD 60OUL 0.22 95 P 2 TWD 8 08C
-0.95 TEH TEC 30 COLD 600UL 129 75 0.31 116 P 2 TWD 12 VHI
+0.68 TEH TEC 7
COLD 600UL 0.36 107 P 2 TWD 14 VHI
+0.68 TEH TEC 7
COLD 600UL 129 99 0.62 62 P 2 TWD 22 10H
-0.26 TEH TEC 13 COLD 600UL 0.62 62 P 2 TWD 22 10H
-0.26 TEH TEC 13 COLD 600UL 129 129 0.38 137 P 2 TWD 16 DBH
+2.02 TEH TEC NEW 18 COLD 600UL 130 54 0.30 117 P 2 TWD 12 DBH
-1.89 TEH TEC NEW 3
COLD 600UL 130 56 0.14 54 P 2 TWD 5 DBH
-2.25 TEH TEC NEW 5
COLD 600UL 130 72 0.27 136 P 2 TWD 10 VHI
-0.84 TEH TEC 5
COLD 600UL 0.27 136 P 2 TWD 10 VH1
-0.84 TEH TEC 5
COLD 600UL 130 74 0.46 105 P 2 TWD 17 VHI
-0.75 TEH TEC 7
COLD 600UL 0.48 106 P 2 TWD 18 VHI
-0.75 TEH TEC 7
COLD 60OUL 130 76 0.43 102 P 2 TWD 16 VHI
+0.60 TEH TEC 7
COLD 60OUL 0.43 102 P 2 TWD 17 VHI
+0.60 TEH TEC 7
COLD 60OUL 130 78 0.29 86 P 2 TWD 12 VHI
-0.81 TEH TEC 7
COLD 60OUL 0.32 118 P 2 TWD 13 VHI
-0.81 TEH TEC 7
COLD 600UL 130 84 0.49 63 P 2 TWD 18 VHI
-0.79 TEH TEC 7
COLD 600UL 0.49 63 P 2 TWD 18 VHi
-0.79 TEH TEC 7
COLD 600UL 130 88 0.31 96 P 2 TWD 14 VHI
+0.09 TEH TEC 14 COLD 600UL 0.15 160 P 2 TWD 7 VHI
+0.47 TEH TEC 14 COLD 600UL 0.15 160 P 2 TWD 7 VHi
+0.47 TEH TEC 14 COLD 600UL 0.31 96 P 2 TWD 14 VHI
+0.09 TEH TEC 14 COLD 600UL 130 106 0.44 140 P 2 TWD 19 VHI
-0.69 TEH TEC 16 COLD 600UL 0.31 108 P 2 TWD 14 VHI
-0.09 TEH TEC 16 COLD 600UL 0.45 139 P 2 TWD 20 VHI
-0.69 TEH TEC 16 COLD 600UL 0.31 107 P 2 TWD 15 VHi
-0.09 TEH TEC 16 COLD 600UL 131 51 0.11 48 P 2 TWD 3 VH2
+0.32 TEH TEC 9
COLD 60OUL
Framatome ANP Inc.
Customer Name:
SONGS Unit 3
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and 0-100%twd qry 01/26/2003 10:53:36 AM Component: S/G 88 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.55 127 P 2 TWD 19 VH2
+0.81 TEH TEC 9
COLD 600UL 0.66 96 P 2 TWD 22 DBC
+2.00 TEH TEC 9
COLD 600UL 0.55 127 P 2 TWD 19 VH2
+0.81 TEH TEC 9
COLD 600UL 0.64 101 P 2 TWD 21 DBC
+2.00 TEH TEC 9
COLD 600UL 0.11 48 P 2 TWD 3 VH2
+0.32 TEH TEC 9
COLD 600UL 131 57 0.25 120 P 2 TWD 9 DBH
+1.69 TEH TEC NEW 9
COLD 600UL 131 83 0.36 74 p 2 TWD 14 VHl
-0.77 TEN TEC 10 COLD 600UL 0.36 82 P 2 TWD 15 VHl
-0.77 TEH TEC 10 COLD 600UL 131 89 0.19 111 P 2 TWD 9 VHI
-1.00 TEH TEC 11 COLD 60OUL 0.19 111 P 2 TWD 9 VHI
-1.00 TEH TEC 11 COLD 600UL 131 97 0.30 93 P 2 TWD 13 VHN
+0.96 TEH TEC 11 COLD 600UL 0.39 142 P 2 TWD 16 10H
-1.09 TEH TEC 11 COLD 600UL 0.08 15 P 2 TWD 4 VHI
-0.98 TEH TEC 11 COLD 600UL 0.30 93 P 2 TWD 13 VHI
+0.96 TEH TEC 11 COLD 600UL 0.39 142 P 2 TWD 16 10H
-1.09 TEH TEC 11 COLD 600UL 0.08 9
P 2 TWD 4 VHI
-0.98 TEH TEC 11 COLD 60OUL 131 99 0.30 47 P 2 TWD 12 10H
-1.09 TEH TEC 11 COLD 600UL 0.35 129 P 2 TWD 15 10H
-1.09 TEH TEC 11 COLD 60OUL 131 103 0.93 54 P 2 TWD 29 VC3
-0.69 TEN TEC 11 COLD 600DL 0.93 54 P 2 TWD 29 VC3
-0.69 TEH TEC 11 COLD 600OUL 132 68 0.29 78 P 2 TWD 11 VN2
-0 77 TEH TEC 9
COLD 600UL 0.28 62 P 2 TWD 11 VH2
-0.77 TEH TEC 9
COLD 600UL 132 70 0.27 85 P 2 TWD 10 VHi
+0.19 TEH TEC 9
COLD 60OUL 0.70 85 P 2 TWD 23 VHN
+0.66 TEH TEC 9
COLD 600UL 0.71 87 P 2 TWD 23 VHI
+0.66 TEH TEC 9
COLD 600UL 0.25 87 P 2 TWD 10 VHI
+0.19 TEH TEC 9
COLD 600UL 132 76 0.30 104 P 2 TWD 13 VH2
-0.90 TEH TEC 10 COLD 600UL 0.26 97 P 2 TWD 11 VH2
-0.90 TEH TEC 10 COLD 600UL 132 78 0.33 78 P 2 TWD 13 VHI
-0.73 TEH TEC 10 COLD 600UL 0.28 121 P 2 TWD 12 VHl
-0.73 TEH TEC 10 COLD 600UL 132 82 0.33 67 P 2 TWD 14 VHI
-0.69 TEH TEC 10 COLD 600UL 0.29 138 P 2 TWD 12 VH2
-0.82 TEH TEC 10 COLD 600UL 0.30 55 P 2 TWD 12 VHN
-0.69 TEH TEC 10 COLD 600UL 0.28 137 P 2 TWD 12 VH2
-0.82 TEH TEC 10 COLD 60OUL 132 84 0.28 141 P 2 TWO 12 VHi
-0.70 TEN TEC 10 COLD 600UL 0.28 141 P 2 TWD 12 VHI
-0.70 TEH TEC 10 COLD 60OUL 132 92 0.24 61 P 2 TWD 11 VH2
-0.83 TEH TEC 10 COLD 60OUL 0.35 64 P 2 TWD 15 VHN
-0.88 TEH TEC 11 COLD 600UL 0.35 64 P 2 TWD 15 VHI
-0.88 TEH TEC 11 COLD 60OUL 0.25 74 P 2 TWD 11 VH2
-0.83 TEH TEC 11 COLD 600UL 132 96 0.40 67 P 2 TWD 16 VHI
-0.75 TEH TEC 11 COLD 600UL 0.15 88 P 2 TWD 7 VHI
+0.49 TEH TEC 11 COLD 60OUL 0.41 72 P 2 TWD 17 VHN
-0.75 TEH TEC 11 COLD 600UL 0.16 126 P 2 TWD 8 VHI
+0.49 TEH TEC 11 COLD 600UL 132 100 0.51 119 P 2 TWO 20 VN1
-0.86 TEN TEC 11 COLD 600UL 0.51 119 P 2 TWD 20 VHI
-0.86 TEH TEC 11 COLD 600UL 132 118 0.15 76 P 2 TWD 7 DBH
+1.94 TEH TEC NEW 11 COLD 60OUL 133 51 0.21 71 P 2 TWO 9 08C
+0.83 TEE TEC 10 COLD 600UL 0.21 71 P 2 TWD 9 08C
+0.83 TEH TEC 10 COLD 600UL 133 75 0.47 46 P 2 TWD 17 i0O
+0.79 TEH TEC 9
COLD 600UL 0.47 46 P 2 TWD 17 10H
+0.79 TEH TEC 9
COLD 600UL 133 87 0.93 118 P 2 TWD 28 VHI
-0.62 TEH TEC 10 COLD 600UL 0.93 118 P 2 TWD 28 VHI
-0.62 TEH TEC 10 COLD 600UL 133 91 0.23 94 P 2 TWD 11 VHI
-0.81 TEH TEC 12 COLD 600UL 0.22 52 P 2 TWD 10 VHI
-0.81 TEH TEC 12 COLD 600UL Page 40 of 46
44 0
(D 0
II C4 I1 0 I.
00 1
001 00 1
N N) I HHI El to E-9
-9 0
W0 NC4
-40 tDoUo I
I I
I1
+
N4 H H4 N4 I N0 0
N N IN in) 0 0 inI 0 000 IC0 co
+
rt E.
0
-4 H2 N~
0 I in in Io 00 I N N IW W0W0W0 00 I 00 1
00 1
to toI 0oCo o o 00 Wo to a )I n
I C)C D
I C 001I00100C00100 00W I 00W I 0000 I 00W 00001 tO nO no o I 0000i 00001 0000 1
1 U
'A 4 -
1 00 1
0 00 I 00 to to I to to 00 1 00)
I 0 000C C I
I H-H H H-I I EIE E
I I;0 0C I ý IIP4 I
Iý C
- 1 ID I
00 H4 H E-E r-r'-
00 torn HH E
El E 00 I EH HEI m m I NN 100 N in N N4 I
>m IN N1 II0 I HH E
Io 00 ID W
E-E 00
- tor, I
I N N N N 00 (
Nl N 00L N N 00 Nm N N 1 00 1
I uuI 100 100 00 00 O0 u0 00 I
I I
I I
I I
I I
I I
I H H I N N N N I N N I N N H H I H H H H I H H I H H I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
00 I 0000 100 I 00 toto I Ii)to I IOto I toto HE-' I HE-'HE-' I HE-' I HH I
I I
I 00I toto I totototo I toto I toN HH I HE-'E-'H I HE-' I HH
++
+
I
+
EH EH I H EH H EA mmI I>>>>>
N N N C, 4NN I i N t 00 10000r N-N1 I N N N*
00 1000 HHI I 00 I I I:1 C-D c I C; I 00 C
mm) 0 0 I
I 00 1
00 1
00o toto I C-) C)
W0W 00 I 00 00 I 00 001O00 10000100 100 IO0 IO01O00 0000 10000100 1001 00100100 10000 I 0000I 00 00 00 00 00 0000 I H-H- I N N1 I E E.
I H E I-In rIH H
I H H4 IN N1 I 00 C
I 0 I o to I n In Iý 00 I N N N4 H H 00w Et En HH E
) H I
'00 I
H w Hw I E. E I ++
N N N N 00 C
toDi
- 0) I to' 0.1 0I D00 to to 00 0 10 100 00 1 00 I 00 00u I 00u I 00u 0 1 -H H z I 0100
+o I
toI H
I H in I to to N
N to t
+11 0
(n LN I tft m Im I 00CD0 I 00 1 00C>0 I 00 II II II II I000 1 00 I U-)U9u I -3/4-)
I E IPH
ýE I E-E -
I E I to to to I to to I
I +
I
++
EAPE IHH I
I m m I ýC I c W
I i-D I 1 00 I 00 I C00
+
00 4 M Do 00 I 00 C)00 V
to I E I ot 00 H H I
II torn-I PtPtototo I torP I PoEo HHE I ElHHH H
H H
I HHE 0
I 0 0 Nl NI 0
I I~ I'- i r0,,
H-H I
HH I N No In9 4H Z
0 0
)
(00 oý 4n 1400
ý-4 rI 0
&o H
0 H
C')
U U) z 0
H Eý H
0 0
H dO 0
to H"
to 0
'-I 0
to
&P
'0 cO 0
0 H
01 0 I100 I.*
toto u HH E-, E-,
I HH E
IN N1 II I
I H H-m m I00 Io IN 00 H H 00 HHE rn HH 00 C
0121 I:
HH 100 100 I Dt I HH E
I E-E I HH C
I Nq N I
m I 00 I ICI I
Wm I H4 H I00 IW0 I mot
Framatome ANP Inc.
01/26/2003 10:53:36 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 42 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.47 41 P 2 TWD 18 VHI
-0.47 TEH TEC 10 COLD 600UL 0.50 99 P 2 TWD 18 VHl
+0.80 TEH TEC 10 COLD 60OUL 136 92 0.35 128 P 2 TWD 15 VHI
-0.77 TEH TEC 11 COLD 60OUL 0.38 140 P 2 TWD 16 VHI
-0.77 TEH TEC 11 COLD 60OUL 136 100 0.37 128 P 2 TWD 15 VH2
-0.92 TEH TEC 11 COLD 60OUL 0.37 128 P 2 TWD 15 VH2
-0.92 TEH TEC 11 COLD 60OUL 136 106 0.53 71 P 2 TWD 20 VH2
-1.20 TEH TEC 11 COLD 60OUL 0.55 23 P 2 TWD 21 VH2
-1.20 TEH TEC 11 COLD 600UL 136 108 0.50 104 P 2 TWD 19 VHl
-0.94 TEH TEC 11 COLD 600UL 0.27 69 P 2 TWD 12 VHI
+0.77 TEH TEC 11 COLD 600UL 0.50 104 P 2 TWD 19 VHI
-0.94 TEH TEC 11 COLD 60OUL 0.27 69 P 2 TWD 12 VHI
+0.77 TEH TEC 11 COLD 600UL 136 118 0.31 19 P 2 TWD 14 DBH
+1.96 TEH TEC NEW 12 COLD 600UL 137 59 0.48 134 P 2 TWD 18 DBC
+1.71 TEH TEC 10 COLD 600UL 0.47 129 P 2 TWD 18 DBC
+1.71 TEH TEC 10 COLD 60OUL 137 69 0.47 129 P 2 TWD 18 VHI
-0.94 TEH TEC 10 COLD 600UL 0.23 129 P 2 TWD 10 VHI
+1.00 TEH TEC 10 COLD 600UL 0.36 124 P 2 TWD 14 VHI
-0.94 TEH TEC 10 COLD 600UL 0.23 116 P 2 TWD 10 VHI
+1.00 TEH TEC 10 COLD 600UL 137 85 0.29 102 P 2 TWD 11 09H
+0.88 TEH TEC 9
COLD 600UL 0.11 151 P 2 TWD 3 09H
-1.05 TEH TEC 9
COLD 60OUL 0.30 107 P 2 TWD 12 09H
+0.88 TEH TEC 9
COLD 600UL 0.11 151 P 2 TWD 3 09H
-1.05 TEH TEC 9
COLD 600UL 137 89 0.38 125 P 2 TWD 16 VHI
+0.79 TEH TEC 12 COLD 600UL 0.20 128 P 2 TWD 9 VHI
-0.88 TEH TEC 12 COLD 600UL 0.23 110 P 2 TWD 10 VHI
-0.88 TEH TEC 12 COLD 600UL 0.38 125 P 2 TWD 16 VHI
+0.79 TEH TEC 12 COLD 600UL 137 93 0.34 84 P 2 TWD 14 VHI
-0.92 TEH TEC 12 COLD 600UL 0.34 84 P 2 TWD 14 VHI
-0.92 TEH TEC 12 COLD 600UL 137 103 0.58 39 P 2 TWD 21 VHI
-0.81 TEH TEC 11 COLD 600UL 0.58 40 P 2 TWD 21 VH1
-0.81 TEH TEC 11 COLD 600UL 138 64 0.25 141 P 2 TWD 11 VH2
-0.75 TEH TEC 10 COLD 600UL 0.25 138 P 2 TWD 10 VH2
-0.75 TEH TEC 10 COLD 600UL 138 68 0.12 50 P 2 TWD 5 DBH
+1.82 TEH TEC NEW 10 COLD 600UL 138 70 0.16 35 P 2 TWD 7 DBH
+1.86 TEH TEC NEW 10 COLD 60OUL 138 72 0.29 126 P 2 TWD 11 VH2
-0.83 TEH TEC 9
COLD 600UL 0.29 126 P 2 TWD 11 VH2
-0.83 TEH TEC 9
COLD 600UL 138 74 0.84 120 P 2 TWD 26 VHl
-0.88 TEH TEC 10 COLD 600UL 0.34 152 P 2 TWD 14 VH2
-0.86 TEH TEC 10 COLD 600UL 0.84 120 P 2 TWD 26 VHI
-0.88 TEH TEC 10 COLD 600UL 0.34 152 P 2 TWD 14 VH2
-0.86 TEH TEC 10 COLD 600UL 138 76 0.44 83 P 2 TWD 16 VHI
-0.26 TEH TEC 9
COLD 600UL 0.46 76 P 2 TWD 17 VH2
-0.83 TEH TEC 9
COLD 600UL 0.44 83 P 2 TWD 16 VHl
-0.26 TEH TEC 9
COLD 600UL 0.46 76 P 2 TWD 17 VH2
-0.83 TEH TEC 9
COLD 60OUL 138 86 0.44 92 P 2 TWD 16 VH2
-0.84 TEH TEC 9
COLD 600UL 0.44 92 P 2 TWD 16 VH2
-0.84 TEH TEC 9
COLD 60OUL 138 88 0.33 60 P 2 TWD 14 VHI
+0.70 TEH TEC 11 COLD 600UL 0.88 82 P 2 TWD 28 VHI
-0.73 TEH TEC 11 COLD 60OUL 0.88 82 P 2 TWD 28 VHI
-0.73 TEH TEC 11 COLD 600UL 0.33 60 P 2 TWD 14 VHl
+0.70 TEH TEC 11 COLD 600UL 138 92 0.32 123 P 2 TWD 14 VH2
-0.84 TEH TEC 12 COLD 600UL 0.26 135 P 2 TWD 12 VHI
-0.66 TEH TEC 12 COLD 600UL 0.31 128 P 2 TWD 14 VH2
-0.84 TEH TEC 12 COLD 600UL 0.26 135 P 2 TWD 12 VHI
-0.66 TEH TEC 12 COLD 60OUL
Framatome ANP Inc.
01/26/2003 10:53"37 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 43 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_icodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE S.........................................................................................................
138 94 0.30 31 P 2 TWD 13 VHI
+0.85 TEH TEC 11 COLD 600UL 0.20 67 P 2 TWD 9 VH2
+0.83 TEH TEC 11 COLD 60OUL 0.30 31 P 2 TWD 13 VHI
+0.85 TEH TEC 11 COLD 600UL 0.20 67 P 2 TWD 9 VH2
+0.83 TEH TEC 11 COLD 60OUL 139 69 0.24 130 P 2 TWD 9 VHI
+0.81 TEH TEC 9
COLD 600UL 0.98 73 P 2 TWD 28 VC1
-0.75 TEH TEC 9
COLD 60OUL 0.24 130 P 2 TWD 9 VHI
+0.81 TEH TEC 9
COLD 600UL 0.98 73 P 2 TWD 28 VC1
-0.75 TEH TEC 9
COLD 600UL 139 93 0.37 120 P 2 TWD 15 VC1
+0.90 TEH TEC 11 COLD 60OUL 0.37 120 P 2 TWD 15 VC1
+0.90 TEH TEC 11 COLD 600UL 139 111 0.36 138 P 2 TWD 15 DBH
+2.09 TEH TEC NEW 11 COLD 60OUL 140 72 0.36 20 P 2 TWD 15 DBH
+1.91 TEH TEC NEW 10 COLD 600UL 140 76 0.47 109 P 2 TWD 17 VHI
-0.86 TEH TEC 9
COLD 600UL 0.47 109 P 2 TWD 17 VHI
-0.86 TEH TEC 9
COLD 60OUL 140 78 0.24 146 P 2 TWD 10 VH1
-0.96 TEH TEC 10 COLD 600UL 0.25 151 P 2 TWD 10 VHI
-0.96 TEH TEC 10 COLD 600UL 0.29 149 P 2 TWD 12 VH2
-0.80 TEH TEC NEW 10 COLD 600UL 140 80 0.31 49 P 2 TWD 12 DBH
-1.72 TEH TEC 9
COLD 60OUL 0.77 77 P 2 TWD 24 VHI
-0.79 TEH TEC 9
COLD 600UL 0.31 49 P 2 TWD 12 DBH
-1.72 TEH TEC 9
COLD 600UL 0.77 81 P 2 TWD 25 VHI
-0.79 TEH TEC 9
COLD 600UL 140 82 0.22 127 P 2 TWD 10 VH2
-0.83 TEH TEC 10 COLD 600UL 0.21 138 P 2 TWD 9 VHI
-0.68 TEH TEC 10 COLD 600UL 0.24 136 P 2 TWD 10 VHI
-0.68 TEH TEC 10 COLD 600UL 0.25 134 P 2 TWD 10 VH2
-0.83 TEH TEC 10 COLD 600UL 140 84 0.36 150 P 2 TWD 15 VH2
-0.92 TEH TEC 10 COLD 600UL 0.36 150 P 2 TWD 15 VH2
-0.92 TEH TEC 10 COLD 600UL 140 88 0.36 125 P 2 TWD 15 VH2
-0.83 TEH TEC 12 COLD 600UL 0.35 125 P 2 TWD 15 VH2
-0.83 TEH TEC 12 COLD 600UL 140 92 0.22 59 P 2 TWD 10 VH2
-0.81 TEH TEC 11 COLD 600UL 0.28 145 P 2 TWD 12 VHI
-0.71 TEH TEC 11 COLD 600UL 0.28 115 P 2 TWD 12 VHI
-0.71 TEH TEC 11 COLD 60OUL 0.24 83 P 2 TWD 11 VH2
-0.81 TEH TEC 11 COLD 60OUL 140 106 0.31 64 P 2 TWD 14 DBH
+1.90 TEH TEC NEW 12 COLD 600UL 141 63 0.36 86 P 2 TWD 15 DBH
-1.35 TEH TEC 10 COLD 60OUL 0.27 127 P 2 TWD 11 08H
+0.71 TEH TEC 10 COLD 60OUL 0.36 85 P 2 TWD 14 DBH
-1.35 TEH TEC 10 COLD 600UL 0.27 129 P 2 TWD 11 08H
+0.71 TEH TEC 10 COLD 600UL 141 65 0.52 118 P 2 TWD 19 09H
+0.66 TEH TEC 10 COLD 600UL 0.34 147 P 2 TWD 14 VHI
+1.18 TEH TEC 10 COLD 600UL 1.01 99 P 2 TWD 29 DBC
+1.59 TEH TEC 10 COLD 600UL 0.35 112 P 2 TWD 14 07H
-0.64 TEH TEC 10 COLD 600UL 0.35 116 P 2 TWD 14 07H
-0.64 TEH TEC 10 COLD 600UL 1.00 91 P 2 TWD 29 DBC
+1.59 TEH TEC 10 COLD 60OUL 0.51 138 P 2 TWD 19 09H
+0.66 TEH TEC 10 COLD 600UL 0.34 147 P 2 TWD 14 VHI
+1.18 TEH TEC 10 COLD 600UL 141 67 0.22 57 P 2 TWD 10 DBH
+1.87 TEH TEC 10 COLD 600UL 0.21 53 P 2 TWD 10 DBH
+1.87 TEH TEC 10 COLD 60OUL 141 69 0.20 63 P 2 TWD 9 DBH
+1.95 TEH TEC NEW 10 COLD 600UL 0.21 47 P 2 TWD 9 DBC
+1.75 TEH TEC NEW 10 COLD 600UL 141 71 0.24 22 P 2 TWD 9 DBH
+2.25 TEH TEC NEW 9
COLD 600UL 141 83 0.65 85 P 2 TWD 22 VC1
+1.01 TEH TEC 9
COLD 60OUL 0.65 85 P 2 TWD 22 VC1
+1.01 TEH TEC 9
COLD 600UL 141. 93.
- 0. 31....
143.....p 2
TWO.....13....VC1.....+0.86.......TEE.....TEC.....
12....
COLD......
600.....
141 93 0.31 143 P 2 TWD 13 VC1
+0.86 TEH TEC 12 COLD 600UL 0.31 143 P 2 TWD 13 VCI
+0.86 TEH TEC 12 COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:37 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 44 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY:
rpcicodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 141 97 0.30 100 P 2 TWD 14 VH2
+0.96 TEN TEC 12 COLD 600UL 0.33 115 P 2 TWD 14 VH2
+0.96 TEN TEC 12 COLD 600UL 141 109 0.31 79 P 2 TWD 14 VH2
-0.77 TEN TEC 12 COLD 60OUL 0.34 78 P 2 TWD 15 VH2
-0.77 TEN TEC 12 COLD 600UL 141 113 0.36 155 P 2 TWD 15 09C
+0.74 TEN TEC 12 COLD 600UL 0.36 155 P 2 TWD 15 09C
+0.74 TEN TEC 12 COLD 600UL 142 66 0.84 118 P 2 TWD 26 DBH
+2.00 TEN TEC 10 COLD 600UL 0.33 110 P 2 TWD 13 VC3
-0.84 TEN TEC 10 COLD 600UL 0.33 136 P 2 TWD 14 01H
+0.44 TEN TEC 10 COLD 600UL 0.43 99 P 2 TWD 17 VHI
+0.80 TEN TEC 10 COLD 600UL 0.83 109 P 2 TWD 26 DBC
+1.61 TEN TEC 10 COLD 600UL 0.42 64 P 2 TWD 16 VH1
+0.80 TEN TEC 10 COLD 600UL 0.33 110 P 2 TWD 13 VC3
-0.84 TEE TEC 10 COLD 600UL 0.83 108 P 2 TWD 26 DBC
+1.61 TEE TEC 10 COLD 600UL 0.87 96 P 2 TWD 27 DBH
+2.00 TEN TEC 10 COLD 60OUL 142 72 0.32 92 P 2 TWD 12 VH1
+1.01 TEN TEC 9
COLD 600UL 0.35 54 P 2 TWD 13 DBH
+1.69 TEN TEC NEW 9
COLD 600UL 0.31 103 P 2 TWD 12 VHI
+1.01 TEN TEC 9
COLD 60OUL 142 74 0.32 52 P 2 TWD 12 DBH
+2.01 TEN TEC NEW 9
COLD 60OUL 142. 78.
- 0. 80.....
101.....P...
2 TWO.....25....V.......-0.90.......TEN.....TEC.....
9...
COLD..........OUL..
142 78 0.80 101 P 2 TWD 25 VHI
-0.90 TEN TEC 9
COLD 600UL 0.80 101 P 2 TWD 25 VHI
-0.90 TEN TEC 9
COLD 600UL 142 80 0.38 157 P 2 TWD 15 VH2
-0.88 TEN TEC 10 COLD 600UL 0.38 154 P 2 TWD 15 VH2
-0.88 TEN TEC 90 COLD 600UL S.........................................................................................................
142 82 0.71 84 P 2 TWD 23 VH2
-0.90 TEN TEC 9
COLD 600UL 0.71 84 P 2 TWD 23 VH2
-0.90 TEN TEC 9
COLD 60OUL S.........................................................................................................
142 90 0.31 145 P 2 TWD 14 VH2
-0.83 TEN TEC 12 COLD 60OUL 0.31 145 P 2 TWD 14 VH2
-0.83 TEN TEC 12 COLD 60OUL 142 92 0.37 153 P 2 TWD 16 VHI
-0.85 TEN TEC 12 COLD 600UL 0.28 50 P 2 TWD 12 VH2
-0.77 TEN TEC 12 COLD 60OUL 0.37 153 P 2 TWD 16 VH2
-0.85 TEN TEC 12 COLD 60OUL 0.28 50 P 2 TWD 12 VH2
-0.77 TEE TEC 12 COLD 600UL S.........................................................................................................
142 94 0.26 146 P 2 TWD 12 VH2
-0.86 TEE TEC 12 COLD 600UL 0.20 109 P 2 TWD 10 VHI
-0.79 TEE TEC 12 COLD 600UL 0.17 34 P 2 TWD 9 VH1
+0.81 TEE TEC 12 COLD 600UL 0.21 101 P 2 TWD 10 VHN
-0.79 TEE TEC 12 COLD 600UL 0.18 32 P 2 TWD 9 VHI
+0.81 TEE TEC 12 COLD 600UL 0.24 148 P 2 TWD 12 VH2
-0.86 TEE TEC 12 COLD 600UL S.........................................................................................................
142 98 0.40 115 P 2 TWD 16 VHD
+0.66 TEE TEC 12 COLD 600UL 0.38 121 P 2 TWD 16 VHB
+0.66 TEE TEC 12 COLD 600UL 142 104 0.32 133 P 2 TWD 14 DBH
+2.20 TEE TEC 12 COLD 600UL 0.32 133 P 2 TWD 14 DBH
+2.20 TEE TEC 12 COLD 600UL S.........................................................................................................
142 108 0.29 128 P 2 TWD 13 VHI
-0.82 TEE TEC 12 COLD 600UL 0.27 156 P 2 TWD 13 VH2
-0.82 TEE TEC 12 COLD 600UL 0.31 127 P 2 TWD 14 VH3
+0.86 TEN TEC 12 COLD 600UL 0.31 127 P 2 TWD 14 VH3
+0.86 TEN TEC 12 COLD 600UL 0.29 122 P 2 TWD 14 VHD
-0.82 TEN TEC 12 COLD 600UL 0129 154 P 2 TWD 13 VH2
-0.82 TEN TEC 12 COLD 600UL S.........................................................................................................
142 110 0.22 46 P 2 TWD 10 DBH
+2.13 TEE TEC NEW 12 COLD 600UL S.........................................................................................................
143 71 0.37 41 P 2 TWD 15 DBH
-1.68 TEN TEC 10 COLD 600UL 0.41 143 P 2 TWD 16 DBH
+2.15 TEN TEC 10 COLD 60OUL 0.36 39 P 2 TWD 14 DBH
-1.68 TEE TEC 10 COLD 60OUL 0.38 150 P 2 TWD 15 DBH
+2.15 TEH TEC 10 COLD 600UL S.........................................................................................................
143 75 0.35 86 P 2 TWD 14 DBH
+2.10 TEE TEC 10 COLD 60OUL 0.35 86 P 2 TWD 14 DBH
+2.10 TEH TEC 10 COLD 600UL 143 79 0.58 94 P 2 TWD 20 DBH
+2.05 TEN TEC 9
COLD 600UL 0.58 94 P 2 TWD 20 DBH
+2.05 TEN TEC 9
COLD 600UL
Framatome ANP Inc.
01/26/2003 10:53:38 AM Customer Name: SONGS Unit 3 Component: S/G 88 Page 45 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc_lcodes and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 144 92 0.34 78 P 2 TWD 15 10C
-1.02 TEH TEC 11 COLD 600UL 0.37 67 P 2 TWD 15 10C
-1.02 TEH TEC 11 COLD 600UL S.........................................................................................................
144 96 0.39 79 P 2 TWD 16 DBH
+1.83 TEH TEC 11 COLD 60OUL 0.82 65 P 2 TWD 27 VHI
+0.97 TEH TEC 11 COLD 600UL 0.29 24 P 2 TWD 13 VHI
+0.21 TEH TEC 11 COLD 60OUL 0.39 79 P 2 TWD 16 DBH
+1.83 TEH TEC 11 COLD 600UL 0.29 24 P 2 TWD 13 VHI
+0.21 TEH TEC 11 COLD 600UL 0.83 69 P 2 TWD 27 VHI
+0.97 TEH TEC 11 COLD 600UL 144 102 0.26 51 P 2 TWD 12 DBH
+1.65 TEH TEC 12 COLD 60OUL 0.45 77 P 2 TWD 18 VC3
+0.92 TEH TEC 12 COLD 600UL 0.26 51 P 2 TWD 12 DBH
+1.65 TEH TEC 12 COLD 600UL 0.40 83 P 2 TWD 17 VC3
+0.92 TEH TEC 12 COLD 60OUL 144 104 0.81 118 P 2 TWD 27 DBC
+1.69 TEH TEC 12 COLD 600UL 0.41 17 P 2 TWD 17 DBH
+1.79 TEH TEC 12 COLD 60OUL 0.43 23 P 2 TWD 17 DBH
+1.79 TEH TEC 12 COLD 600UL 0.81 118 P 2 TWD 27 DBC
+1.69 TEH TEC 12 COLD 600UL 145. 75.
- 0. 83... 94.. P.2..
TWO..
26.. DEE...
+1. 91.......TEE........
TEC.........9....COLD.............
D........L 145 75 0.83 94 P 2 TWD 26 DBH
+1.91 TEH TEC 9
COLD 600UL 0.86 96 P 2 TWD 26 DBH
+1.91 TEH TEC 9
COLD 600UL S.........................................................................................................
145 91 0.49 85 P 2 TWD 19 VC1
-0.84 TEH TEC 12 COLD 600UL 0.49 85 P 2 TWD 19 VCI
-0.84 TEH TEC 12 COLD 600UL S.........................................................................................................
145 93 0.26 53 P 2 TWD 11 VC1
-0.73 TEH TEC 12 COLD 600UL 0.49 139 P 2 TWD 19 DBC
+1.36 TEH TEC 12 COLD 60OUL 0.49 139 P 2 TWD 19 DBC
+1.36 TEH TEC 12 COLD 600UL 0.24 48 P 2 TWD 12 VC1
-0.73 TEH TEC 12 COLD 600UL S.........................................................................................................
145 95 0.16 37 P 2 TWD 8 DBC
-1.41 TEH TEC NEW 12 COLD 600UL S.........................................................................................................
145 99 0.31 143 P 2 TWD 14 08H
+0.77 TEH TEC 12 COLD 600UL 0.50 136 P 2 TWD 20 VH2
+0.83 TEH TEC 12 COLD 600UL 0.28 67 P 2 TWD 13 VH3
+0.28 TEH TEC 12 COLD 600UL 0.82 138 P 2 TWD 27 VH3
+0.86 TEH TEC 12 COLD 600UL 0.50 136 P 2 TWD 20 VH2
+0.83 TEH TEC 12 COLD 600UL 0.82 138 P 2 TWD 27 VH3
+0.86 TEH TEC 12 COLD 600UL 0.30 142 P 2 TWD 14 08H
+0.77 TEH TEC 12 COLD 600UL 0.28 67 P 2 TWD 12 VH3
+0.28 TEH TEC 12 COLD 600UL 143 83 0.17 25 P 2 TWD 8 DBC
+1.78 TEH TEC NEW 10 COLD 600UL 143. 89.
- 0. 26.....
49....P...
2 TWO 12....08C.....+0.80.......TEE.....TEC.....
11....
COLD......
60....UL 143 89 0.26 49 P 2 TWD 12 08C
+0.80 TEH TEC 11 COLD 600UL 0.26 49 P 2 TWD 12 08C
+0.80 TEH TEC 11 COLD 600UL 143. 99.
- 0. 17....
45....P..2 TWO 8..DEC.....+1.75......TEE....TEC NEW..........
COLD..... 6000......
143 91 0.44 27 P 2 TWD 18 VC1
-0.84 TEH TEC 11 COLD 600UL 0.44 27 P 2 TWD 18 VC1
-0.84 TEH TEC 11 COLD 600UL S.........................................................................................................
143 99 0.17 45 P 2 TWD 8 DBC
+1.75 TEH TEC NEW 11 COLD 60OUL S.........................................................................................................
143 101 0.27 55 P 2 TWD 12 VCD
-0.84 TEH TEC 12 COLD 600UL 0.27 55 P 2 TWD 12 VCl
-0.84 TEH TEC 12 COLD 600UL S.........................................................................................................
143 105 0.35 56 P 2 TWD 15 DBH
-1.87 TEH TEC 12 COLD 600UL 0.29 17 P 2 TWD 13 DBH
+1.96 TEH TEC 12 COLD 600UL 0.48 122 P 2 TWD 19 DBC
+1.72 TEH TEC 12 COLD 600UL 0.35 56 P 2 TWD 15 DBH
-1.87 TEH TEC 12 COLD 600UL 0.48 122 P 2 TWD 19 DBC
+1.72 TEH TEC 12 COLD 600UL 0.29 17 P 2 TWD 13 DBH
+1.96 TEH TEC 12 COLD 600UL S.........................................................................................................
144 78 1.26 45 P 2 TWD 33 DBH
+2.06 TEH TEC 9
COLD 600UL 1.26 45 P 2 TWD 33 DBH
+2.06 TEH TEC 9
COLD 600UL S.........................................................................................................
144 80 0.39 136 P 2 TWD 14 DBC
+2.24 TEH TEC 9
COLD 600UL 0.39 136 P 2 TWD 14 DBC
+2.24 TEH TEC 9
COLD 600UL S.........................................................................................................
144 82 0.24 95 P 2 TWD 9 DBH
+2.25 TEH TEC 9
COLD 600UL 0.29 138 P 2 TWD 11 DBC
+1.90 TEH TEC NEW 9
COLD 600UL 0.25 96 P 2 TWD 10 DBH
+2.25 TEH TEC 9
COLD 600UL 144. 84.
- 0. 39... 132..
P..
- 2. TWO...16..V..
2 0............
95.TEE.T 144 84 0.39 132 P 2 TWD 16 VH2
-0.95 TEH TEC 10 COLD 600UL 0.33 146 P 2 TWD 14 VH2
-0.95 TEH TEC 10 COLD 600UL S.........................................................................................................
Framatome ANP Inc.
01/26/2003 10:53-36 AM Customer Name:
SONGS Unit 3 Component: S/G 88 Page 46 of 46
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%TWD QUERY: rpc icodes and 0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EZT EXT UTIL I-UTIL 2 CAL # LEG PROBE 146 84 0.45 113 P 2 TWD 16 VH2
-1.07 TEH TEC 9
COLD 600UL 0.45 113 P 2 TWD 16 VH2
-1.07 TEH TEC 9
COLD 60OUL 146 90 0.32 120 P 2 TWD 14 VH2
-1.09 TEH TEC 12 COLD 600UL 0.74 84 P 2 TWD 26 DBC
+1.41 TEH TEC 12 COLD 60OUL 0.74 84 P 2 TWD 26 DBC
+1.41 TEH TEC 12 COLD 600UL 0.28 133 P 2 TWD 13 VH2
-1.09 TEH TEC 12 COLD 60OUL 146 92 0.41 122 P 2 TWD 17 10C
+0.71 TEH TEC 12 COLD 60OUL 0.28 48 P 2 TWD 13 VC1
+0.90 TEH TEC 12 COLD 60OUL 0.33 49 P 2-TWD 15 DBC
+1.26 TEH TEC 12 COLD 600UL 0.33 77 P 2 TWD 14 VC1
+0.90 TEH TEC 12 COLD 6o01!L 0.41 122 P 2 TWD 17 10C
+0.71 TEH TEC 12 COLD 60CUL 0.34 50 P 2 TWD 15 DBC
+1.26 TEH TEC 12 COLD 600UL 146 96 0.36 107 P 6 TWD 20 DBC
-+1.79 DBC DBC LAR 131 COLD 580FH 146..
98..
- 1. 42..
137.. P. 2..TW O.. 36
. DEC..
+ 1. 44......
TEN....
TEC...
12..
...COLD..
600U..
146 98 1 42 137 P 2 TWD 36 DBC
+1.44 TEH TEC 12 COLD 600UL 1.42 137 P 2 TWD 36 DBC
+1.44 TEH TEC 12 COLD 600UL 146 100 0.26 101 P 2 TWD 12 VC2
-0.83 TEH TEC 12 COLD 600UL 0.50 109 P 2 TWD 20 10C
+0.68 TEH TEC 12 COLD 600UL 0.30 81 P 2 TWD 13 08C
-0.28 TEH TEC 12 COLD 600UL 0.32 73 P 2 TWD 14 10C
+0.00 TEH TEC 12 COLD 600UL 0.28 85 P 2 TWD 12 08C
-0.28 TEH TEC 12 COLD 600UL 0.19 83 P 2 TWD 10 VC2
-0.83 TEH TEC 12 COLD 60OUL 0.50 111 P 2 TWD 20 10C
+0.68 TEH TEC 12 COLD 600UL 0.32 73 P-2 TWD 14 10C
+0.00 TEH TEC 12 COLD 60OUL 147 91 0.38 105 P 2 TWD 16 VC1
-0.90 TEH TEC 12 COLD 600UL 0.62 117 P 2 TWD 23 VC1
+0.69 TEH TEC 12 COLD 600UL 0.38 105 P 2 TWD 16 VC1
-0.90 TEH TEC 12 COLD 600UL 0.62 117 P 2 TWD 23 VC1
+0.69 TEH TEC 12 COLD 600UL 147 93 0.66 135 P 2 TWD 24 VH2
-0.65 TEH TEC 12 COLD 60OUL 0.66 135 P 2 TWD 24 VH2
-0.65 TEH TEC 12 COLD 600UL 147 95 0.78 99 P 6 TWD 33 DBC
+1.45 DBC DBC LAR 131 COLD 580FH Total Tubes
- 970 Total Records: 2370
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 37 Appendix 4 Inspection Summary Steam Generator E-089
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 2 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 3
117 0.44 122 P 2 TWD 17 02H
+0.84 07H TEH LAR 30 HOT 600UL 3
131 0.29 107 P 2 TWD 12 03H
+0.79 07H TEH LAR 30 HOT 60OUL 5
25 0.41 89 P 2 TWD 17 03H
+0.79 TEH TEC 44 COLD 600UL 5
159 0.62 52 P 2 TWD 24 02H
-0.88 TEC TEH 21 HOT 600UL 6
160 0.47 152 P 2 TWD 19 02H
-0.83 TEC TEH 21 HOT 600UL 8
154 0.54 122 P 2 TWD 21 02H
-0.88 TEC TEH 21 HOT 600UL 14 110 0.22 42 P 2 TWD 11 DBH
-1.54 TEH TEC NEW 52 COLD 600UL 16 60 0.53 103 P 2 TWD 22 01H
+0.57 TEC TEH 23 HOT 600UL S.........................................................................................................
16 128 0.19 148 P 2 TWD 9 DBH
-1.09 TEH TEC 51 COLD 600UL 0.21 144 P 2 TWD 10 DBH
-1.09 TEH TEC 51 COLD 60OUL 18 8
0.27 73 P 2 TWD 12 02H
-0.83 TEH TEC 42 COLD 600UL 19 165 0.23 128 P 2 TWD 12 01H
-1.03 TEC TEH 18 HOT 600UL 19 171 0.36 152 P 2 TWD 17 DBC
+1.50 TEC TEH NEW 20 HOT 600UL 20 138 0.32 76 P 2 TWD 13 DBH
+1.61 TEC TEH NEW 7
HOT 600UL 20 166 0.30 92 P 2 TWD 13 02H
+0.89 TEC TEH 17 HOT 600UL 21 67 0.59 73 P 2 TWD 21 VSM
-0.87 TEH TEC 7
COLD 600UL 0.59 73 P 2 TWD 21 VSM
-0.87 TEH TEC 7
COLD 600UL 22 32 0.44 51 P 2 TWD 16 02H
-1.20 TEH TEC 34 COLD 600UL 22 164 0.36 80 P 2 TWD 17 DBC
+1.62 TEC TEH 18 HOT 60OUL 0.36 85 P 2 TWD 17 DBC
+1.62 TEC TEH 18 HOT 600UL 22 170 0.31 37 P 2 TWD 13 01C
+0.87 TEC TEH 19 HOT 600UL 24 20 0.38 102 P 2 TWD 19 07H
+0.87 TEH TEC NEW 39 COLD 600UL 24 22 0.30 103 P 2 TWD 13 VSM
-0.68 TEH TEC 38 COLD 600UL 0.30 103 P 2 TWD 13 VSM
-0.68 TEH TEC 38 COLD 600UL 24 68 0.36 52 P 2 TWD 15 DBH
+1.70 TEH TEC NEW 8
COLD 600UL 25 65 0.26 133 P 2 TWD 11 VSM
+0.92 TEH TEC NEW 9
COLD 600UL 25 67 0.37 132 P 2 TWD 15 VSM
-0.84 TEH TEC 7
COLD 600UL 0.37 135 P 2 TWD 15 VSM
-0.84 TEH TEC 7
COLD 60OUL 25 115 0.48 67 P 2 TWD 21 VSM
+1.00 TEH TEC 19 COLD 600UL 0.48 69 P 2 TWD 21 VSM
+1.00 TEH TEC 19 COLD 60OUL 26 38 0.30 101 P 2 TWD 13 03H
-0.18 TEH TEC 32 COLD 600UL 26 48 0.44 27 P 2 TWD 22 VSM
-0.93 TEC TEH 24 HOT 600UL 0.44 27 P 2 TWD 22 VSM
-0.93 TEC TEH 24 HOT 600UL 26 162 0.34 157 P 2 TWD 16 DBC
+1.51 TEC TEH 18 HOT 600UL 0.34 157 P 2 TWD 16 DBC
+1.51 TEC TEH 18 HOT 600UL 27 113 0.25 16 2
SAI TSH
-1.28 TSH TSH 0.0 9.45 108 HOT 580PP 27 167 0.17 170 P 2 TWD 6 DBH
+0.85 TEC TEH NEW 20 HOT 600UL 29 35 0.40 82 P 2 TWD 15 02H
-1.18 TEH TEC 34 COLD 600UL 29 107 0.17 157 P 2 TWD 8 DBC
-1.70 TEH TEC NEW 26 COLD 600UL 30 44 0.28 74 P 2 TWD 14 07H
+0.91 TEH TEC NEW 31 COLD 600UL 30 122 0.27 68 P 2 TWD 13 05H
+0.51 TEH TEC 19 COLD 60OUL 30 126 0.17 101 P 1 SCI TSH
+0.05 TSH TSH
.71 9.14 100 HOT 58OPP
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 3 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 31 41 0.31 17 P 1 SCI TSH
-0.12 TSH TSH 0.20 11.92 97 HOT 580PP 31 51 0.38 136 P 2 TWD 17 06H
+0.77 TEC TEH 23 HOT 600UL 31 71 1.36 107 P 2 TWD 36 DBH
+0.00 TEH TEC 8
COLD 600UL 1.35 107 P 2 TWD 36 DBH
+0.00 TEH TEC 8
COLD 60OUL 0.23 128 P 2 TWD 10 DBC
+2.04 TEH TEC NEW 8
COLD 60OUL 1.62 90 P 2 TWD 40 DBH
+0.00 TEH TEC 51 COLD 600UL 31 107 0.50 59 P 2 TWD 20 DBH
-1.87 TEH TEC 25 COLD 600UL 0.49 62 P 2 TWD 20 DBH
-1.87 TEH TEC 25 COLD 60OUL 31 111 0.29 20 2
SAI TSH
-3.78 TSH TSH 0.0 10.19 107 HOT 58OPP 31 123 2.08 32 P 1 MCI TSH
-7.37 TSH TSH 3.02 8.73 100 HOT 58OPP 32 72 1.35 93 P 2 TWD 35 DBH
-1.71 TEH TEC 8
COLD 600UL 1.34 94 P 2 TWD 35 DBH
-1.71 TEH TEC 8
COLD 600UL 1.54 94 P 2 TWD 36 DBH
-1.71 TEH TEC 47 COLD 600UL 32 118 0.41 124 P 2 TWD 19 VSM
-0.73 TEH TEC 19 COLD 600UL 0.42 119 P 2 TWD 19 VSM
-0.73 TEH TEC 19 COLD 600UL 33 55 0.94 58 P 2 TWD 29 VSM
+0.94 TEH TEC 9
COLD 600UL 0.27 147 P 2 TWD 11 VSM
-0.95 TEH TEC 9
COLD 60OUL 0.31 22 P 2 TWD 12 VSM
-0.95 TEH TEC 9
COLD 600UL 0.94 59 P 2 TWD 29 VSM
+0.94 TEH TEC 9
COLD 600UL 33 71 0.57 117 P 2 TWD 21 DBC
+1.82 TEH TEC 7
COLD 600UL 0.57 117 P 2 TWD 21 DBC
+1.82 TEH TEC 7
COLD 600UL 33 171 0.36 134 P 2 TWD 15 O1C
-0.02 TEC TEH 19 HOT 60OUL 34 28 0.40 148 P 2 TWD 14 VSM
+0.46 TEH TEC 34 COLD 600UL 0.40 148 P 2 TWD 14 VSM
+0.46 TEH TEC 34 COLD 600UL 34 72 0.75 143 P 2 TWD 25 DBC
-2.15 TEH TEC 7
COLD 60OUL 0.75 143 P 2 TWD 25 DBC
-2.15 TEH TEC 7
COLD 600UL 0.24 54 P 2 TWO 10 DBH
-1.69 TEH TEC NEW 7
COLD 600UL 34 104 0.72 116 P 2 TWD 27 DBC
+2.18 TEH TEC 26 COLD 600UL 1.04 133 P 2 TWD 33 DBC
+2.18 TEH TEC 26 COLD 600UL 34 128 0.11 89 P 1 SCI TSH
+0.09 TSH TSH 0
8.96 100 HOT 58OPP 34 148 0.38 66 P 2 TWD 18 VSM
-0.72 TEC TEH 12 HOT 600UL 0.37 66 P 2 TWD 17 VSM
-0.72 TEC TEH 12 HOT 600UL 35 45 0.33 87 P 2 TWD 16 VSM
+0.59 TEH TEC NEW 31 COLD 600UL 35 71 0.72 102 P 2 TWD 25 VSM
-0.62 TEH TEC 8
COLD 600UL 0.27 142 P 2 TWD 11 VSM
+0.13 TEH TEC 8
COLD 60OUL 0.72 102 P 2 TWO 25 VSM
-0.62 TEH TEC 8
COLD 60OUL 0.27 142 P 2 TWD 11 VSM
+0.13 TEH TEC 8
COLD 600UL 35 113 0.46 116 P 2 TWD 14 VSM
-0.56 TEH TEC 26 COLD 600UL 0.34 Ill P 2 TWD 16 VSM
-0.10 TEH TEC 26 COLD 600UL 0.47 122 P 2 TWD 20 VSM
-0.56 TEH TEC 26 COLD 600UL 0.36 121 P 2 TWD 17 VSM
-0.10 TEH TEC 26 COLD 600UL 36 24 0.36 95 P 2 TWD 19 DBC
+1.95 TEH TEC NEW 39 COLD 600UL 36 30 0.56 123 P 2 TWD 19 VSM
+1.01 TEH TEC 34 COLD 600UL 0.50 89 P 2 TWD 17 VSM
+1.01 TEH TEC 34 COLD 600UL 36 72 0.27 43 P 2 TWD 12 DBH
-1.75 TEH TEC 8
COLD 60OUL 0.28 39 P 2 TWD 12 DBH
-1.75 TEH TEC 8
COLD 600UL 36 104 0.33 159 P 2 TWD 15 DBH
+1.79 TEH TEC NEW 25 COLD 600UL 36 144 0.37 122 P 2 TWO 14 VSM
-0.73 TEC TEH NEW 7
HOT 600UL 36 146 0.28 53 P 2 TWD 11 VSM
+0.94 TEC TEH 7
HOT 600UL 0.28 57 P 2 TWD 11 VSM
+0.94 TEC TEH 7
HOT 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component:
S/G 89 Page 4 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 37 53 0.62 38 P 2 TWD 21 VSM
-0.02 TEH TEC NEW 11 COLD 600UL 37 71 1.05 127 P 2 TWD 31 VSM
-0.66 TEH TEC 7
COLD 600UL 0.68 134 P 2 TWD 24 VSM
+0.87 TEH TEC 7
COLD 600UL 0.46 70 P 2 TWD 18 VSM
-0.02 TEH TEC 7
COLD 600UL 1.05 127 P 2 TWD 31 VSM
-0.66 TEH TEC 7
COLD 600UL 0.46 70 P 2 TWD 18 VSM
+0.02 TEH TEC 7
COLD 600UL 0.68 134 P 2 TWD 24 VSM
+0.86 TEH TEC 7
COLD 600UL 0.66 105 P 2 TWD 22 VSM
+0.87 TEH TEC 47 COLD 600UL 0.50 90 P 2 TWD 18 VSM
-0.02 TEH TEC 47 COLD 600UL 1.03 107 P 2 TWD 29 VSM
-0.66 TEH TEC 47 COLD 600UL 37 103 0.98 116 P 2 TWD 32 DBC
+1.84 TEH TEC 26 COLD 600UL 0.71 112 P 2 TWD 26 DBH
+1.94 TEH TEC 26 COLD 600UL 0.93 85 P 2 TWD 31 DBC
+1.84 TEH TEC 51 COLD 600UL 0.63 80 P 2 TWD 25 DBH
+1.94 TEH TEC 51 COLD 600UL 0.70 113 P 2 TWD 27 DBH
+1.94 TEH TEC 26 COLD 600UL 0.98 116 P 2 TWD 32 DBC
+1.84 TEH TEC 26 COLD 600UL 37 107 0.58 114 P 2 TWD 24 VSM
-0.89 TEH TEC 26 COLD 600UL 0.55 105 P 2 TWD 23 VSM
+0.66 TEH TEC 26 COLD 600UL 0.23 43 P 2 TWD 11 VSM
-0.10 TEH TEC 26 COLD 60OUL 0.58 114 P 2 TWD 24 VSM
-0.89 TEH TEC 26 COLD 6000L 0.60 32 P 2 TWD 24 VSM
+0.66 TEH TEC 26 COLD 600UL 0.23 43 P 2 TWD 11 VSM
-0.10 TEH TEC 26 COLD 600UL 37 145 0.61 119 P 2 TWD 21 VSM
+0.82 TEC TEH 7
HOT 60OUL 0.61 119 P 2 TWD 21 VSM
+0.82 TEC TEH 7
HOT 600UL 37 157 0.27 53 P 2 TWD 11 VSM
+0.77 TEC TEH 17 HOT 600UL 0.27 53 P 2 TWD 12 VSM
+0.77 TEC TEH 17 HOT 600UL 37 159 0.28 52 P 2 TWD 12 VSM
+0.83 TEC TEH 17 HOT 600UL 0.28 51 P 2 TWD 13 VSM
+0.83 TEC TEH 17 HOT 600UL 37 165 0.29 58 P 2 TWD 12 VSM
+0.80 TEC TEH 17 HOT 600UL 0.29 59 P 2 TWD 13 VSM
+0.80 TEC TEH 17 HOT 600UL 37 171 0.62 72 P 2 TWD 23 VSM
-1.01 TEC TEH 19 HOT 600UL 0.71 115 P 2 TWD 25 VSM
-1.01 TEC TEH 19 HOT 600UL 38 28 0.45 33 P 2 TWD 16 VSM
+0.82 TEH TEC 34 COLD 600UL 0.23 41 P 2 TWD 9 VSM
-0.79 TEH TEC 34 COLD 600UL 0.25 55 P 2 TWD 9 VSM
-0.79 TEH TEC 34 COLD 60OUL 0.33 16 P 2 TWD 12 VSM
+0.82 TEH TEC 34 COLD 600UL 38 38 0.56 132 P 2 TWD 21 VSM
+0.00 TEH TEC 32 COLD 600UL 0.56 132 P 2 TWD 21 VSM
+0.00 TEH TEC 32 COLD 600UL 38 40 0.77 43 P 2 TWD 27 VSM
-0.83 TEH TEC 32 COLD 600UL 0.28 161 P 2 TWD 12 VSM
-0.23 TEH TEC 32 COLD 600UL 0.77 43 P 2 TWD 27 VSM
-0.83 TEH TEC 32 COLD 600UL 0.26 163 P 2 TWD 11 VSM
-0.23 TEH TEC 32 COLD 600UL 38 56 0.22 137 P 2 TWD 9 06H
+0.50 TEH TEC 9
COLD 600UL 38 72 0.98 73 P 2 TWD 30 DBH
-1.78 TEH TEC 7
COLD 60OUL 0.94 90 P 2 TWD 28 DBH
-1.78 TEH TEC 47 COLD 600UL 0.98 73 P 2 TWD 30 DBH
-1.78 TEH TEC 7
COLD 600UL 38 102 1.00 121 P 2 TWD 31 DBH
-2.13 TEH TEC 25 COLD 600UL 0.31 99 P 2 TWD 14 DBC
-1.70 TEH TEC 25 COLD 600UL 0.93 106 P 2 TWD 31 DBH
-2.13 TEH TEC 51 COLD 600UL 0.23 61 P 2 TWD 11 DBC
-1.70 TEH TEC 51 COLD 600UL 1.00 121 P 2 TWD 31 DBH
-2.13 TEH TEC 25 COLD 600UL 0.29 106 P 2 TWD 13 DBC
-1.70 TEH TEC 25 COLD 600UL 38 128 0.27 118 P 2 TWD 13 VSM
+1.06 TEH TEC NEW 18 COLD 60OUL 38 162 0.36 33 P 2 TWD 17 VSM
-0.84 TEC TEH 18 HOT 60OUL 0.23 92 P 2 TWD 12 VSM
-0.02 TEC TEH 18 HOT 600UL 0.36 33 P 2 TWD 17 VSM
-0.84 TEC TEH 18 HOT 600UL 0.21 91 P 2 TWD 11 VSM
-0.02 TEC TEH 18 HOT 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 5 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 39 41 0.50 80 P 2 TWD 21 DBH
-1.51 TEH TEC NEW 31 COLD 600UL 39 43 0.38 40 P 2 TWD 16 VSM
+0.91 TEH TEC 32 COLD 60OUL 0.38 40 P 2 TWD 16 VSM
+0.91 TEH TEC 32 COLD 600UL 39 69 0.30 134 P 2 TWD 13 VSM
+0.69 TEH TEC NEW 8
COLD 600UL 39 71 0.26 155 P 2 TWD 12 VSM
+0.64 TEH TEC NEW 8
COLD 60OUL 39 73 0.53 54 P 2 TWD 20 DBH
+1.99 TEH TEC 8
COLD 60OUL 0.53 53 P 2 TWD 20 DBH
+1.99 TEH TEC 8
COLD 600UL 39 101 0.30 16 P 2 TWD 15 DBH
-1.58 TEH TEC 27 COLD 600UL 0.30 16 P 2 TWD 13 DBH
-1.58 TEH TEC 27 COLD 600UL 39 147 0.48 146 P 2 TWD 18 VSM
+0.78 TEC TEH 7
HOT 600UL 0.48 146 P 2 TWD 18 VSM
+0.78 TEC TEH 7
HOT 600UL 40 68 0.46 36 P 2 TWD 18 VSM
-0.86 TEH TEC NEW 8
COLD 600UL 40 110 0.84 124 P 2 TWD 28 VSM
-0.68 TEH TEC 25 COLD 600UL 0.31 111 P 2 TWD 14 VSM
-0.14 TEH TEC 25 COLD 600UL 0.31 111 P 2 TWD 14 VSM
-0.14 TEH TEC 25 COLD 600UL 0.84 124 P 2 TWD 28 VSM
-0.68 TEH TEC 25 COLD 600UL 0.28 97 P 2 TWD 13 DBC
+1.93 TEH TEC NEW 25 COLD 600UL 40 112 0.57 152 P 2 TWD 23 DBH
-2.02 TEH TEC NEW 26 COLD 600UL 40 146 0.51 70 P 2 TWD 19 VSM
+0.90 TEC TEH 7
HOT 600UL 0.51 70 P 2 TWD 18 VSM
+0.90 TEC TEH 7
HOT 600UL 40 156 1.16 113 P 2 TWD 32 VSM
+0.87 TEC TEH 17 HOT 600UL 0.96 115 P 2 TWD 31 VSM
+0.87 TEC TEH 17 HOT 600UL 0.90 122 P 2 TWD 28 VSM
+0.87 TEH TEC 49 COLD 600UL 40 162 0.43 94 P 2 TWD 15 VSM
-0.80 TEC TEH 17 HOT 600UL 0.24 28 P 2 TWD 10 VSM
-0.09 TEC TEH 17 HOT 600UL 0.31 63 P 2 TWD 14 VSM
-0.09 TEC TEH 17 HOT 600UL 0.39 109 P 2 TWD 17 VSM
-0.80 TEC TEH 17 HOT 600UL 40 168 0.66 32 P 2 TWD 24 VSM
+0.86 TEC TEH 19 HOT 600UL 0.31 25 P 2 TWD 14 VSM
-0.23 TEC TEH 19 HOT 600UL 0.17 153 P 2 TWD 8 VSM
-0.65 TEC TEH 19 HOT 600UL 0.66 32 P 2 TWD 24 VSM
+0.86 TEC TEH 19 HOT 600UL 0.26 145 P 2 TWD 12 VSM
-0.23 TEC TEH 19 HOT 600UL 0.20 155 P 2 TWD 10 VSM
-0.65 TEC TEH 19 HOT 60OUL 40 170 0.54 124 P 2 TWD 21 01C
+0.94 TEC TEH 20 HOT 600UL 41 5
0.24 50 P 2 TWD 11 DBC
+1.98 TEH TEC NEW 42 COLD 600UL 41 7
0.43 68 P 2 TWD 18 VSM
+0.69 TEH TEC 42 COLD 600UL 0.30 95 P 2 TWD 13 VSM
-0.65 TEH TEC 42 COLD 60OUL 0.30 95 P 2 TWD 13 VSM
-0.65 TEH TEC 42 COLD 60OUL 0.43 67 P 2 TWD 18 VSM
+0.69 TEH TEC 42 COLD 600UL 41 31 1.21 121 P 2 TWD 32 VSM
+0.84 TEH TEC 34 COLD 600UL 1.21 121 P 2 TWD 32 VSM
+0.84 TEH TEC 34 COLD 60OUL 1.13 114 P 2 TWD 31 VSM
+0.84 TEH TEC 47 COLD 60OUL 41 39 0.31 92 P 2 TWD 13 DBC
+1.37 TEH TEC NEW 32 COLD 60OUL 41 47 0.40 147 P 2 TWD 18 VSM
+0.83 TEC TEH 23 HOT 60OUL 0.37 142 P 2 TWD 17 VSM
+0.00 TEC TEH 23 HOT 600UL 0.37 142 P 2 TWD 17 VSM
+0.00 TEC TEH 23 HOT 600UL 0.40 147 P 2 TWD 18 VSM
+0.83 TEC TEH 23 HOT 600UL 41 59 0.46 119 P 2 TWD 19 VSM
-0.85 TEH TEC 10 COLD 600UL 0.41 146 P 2 TWD 17 VSM
+0.00 TEH TEC 10 COLD 600UL 0.46 119 P 2 TWD 19 VSM
-0.85 TEH TEC 10 COLD 600UL 0.41 146 P 2 TWD 17 VSM
+0.00 TEH TEC 10 COLD 60OUL 41 63 0.45 89 P 2 TWD 17 VSM
-0.85 TEH TEC 9
COLD 600UL 0.46 59 P 2 TWD 17 VSM
+0.11 TEH TEC 9
COLD 600UL 0.50 63 P 2 TWD 19 VSM
+0.11 TEH TEC 9
COLD 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 6 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.45 88 P 2 TWD 17 VSM
-0.85 TEH TEC 9
COLD 600UL 41 69 0.59 114 P 2 TWD 21 VSM
+0.87 TEH TEC 7
COLD 600UL 0.59 117 P 2 TWD 21 VSM
+0.87 TEH TEC 7
COLD 600UL 41 103 0.49 124 P 2 TWD 21 DBC
+1.84 TEH TEC 26 COLD 600UL 0.49 124 P 2 TWD 21 DBC
+1.84 TEH TEC 26 COLD 600UL 41 107 0.24 61 P 2 TWD 12 VSM
+0.99 TEH TEC NEW 26 COLD 600UL 0.13 12 P 2 TWD 6 VSM
-0.75 TEH TEC 26 COLD 60OUL 41 113 0.52 135 P 2 TWD 21 VSM
-0.76 TEH TEC 25 COLD 600UL 0.21 128 P 2 TWD 10 VSM
-0.14 TEH TEC 25 COLD 600UL 0.21 128 P 2 TWD 10 VSM
-0.14 TEH TEC 25 COLD 600UL 0.52 133 P 2 TWD 21 VSM
-0.76 TEH TEC 25 COLD 600UL 41 119 1.27 79 P 2 TWD 37 VSM
-1.08 TEH TEC 19 COLD 600UL 0.68 49 P 2 TWD 27 VSM
+0.04 TEH TEC 19 COLD 600UL 1.28 78 P 2 TWD 37 VSM
-1.08 TEH TEC 19 COLD 600UL 0.72 53 P 2 TWD 28 VSM
+0.04 TEH TEC 19 COLD 600UL 41 123 0.60 60 P 2 TWD 23 VSM
+0.90 TEH TEC 17 COLD 60OUL 0.60 60 P 2 TWD 23 VSM
+0.90 TEH TEC 17 COLD 600UL 41 131 0.59 97 P 2 TWD 23 VSM
-0.77 TEC TEH 28 HOT 600UL 0.47 116 P 2 TWD 20 VSM
+0.74 TEC TEH 28 HOT 600UL 0.61 82 P 2 TWD 23 VSM
+0.74 TEC TEH 28 HOT 60OUL 0.59 97 P 2 TWD 23 VSM
-0.77 TEC TEH 28 HOT 600UL 41 157 0.66 131 P 2 TWD 22 VSM
+0.73 TEC TEH 17 NOT 600UL 0.58 133 P 2 TWD 23 VSM
+0.73 TEC TEH 17 HOT 600UL 42 62 0.43 113 P 2 TWD 17 VSM
+0.20 TEH TEC NEW 9
COLD 60OUL 42 68 1.59 118 P 2 TWD 37 VSM
-0.61 TEH TEC 7
COLD 600UL 1.13 107 P 2 TWD 32 VSM
+0.37 TEH TEC 7
COLD 600UL 1.59 118 P 2 TWD 37 VSM
-0.61 TEH TEC 7
COLD 600UL 1.13 107 P 2 TWD 32 VSM
+0.37 TEH TEC 7
COLD 600UL 0.62 84 P 2 TWD 21 VSM
+0.37 TEH TEC 47 COLD 600UL 1.58 125 P 2 TWD 37 VSM
-0.61 TEH TEC 47 COLD 600UL 42 144 0.47 95 P 2 TWD 20 VSM
+0.74 TEC TEH 8
HOT 600UL 0.47 95 P 2 TWD 20 VSM
+0.74 TEC TEH 8
HOT 600UL 42 148 0.47 132 P 2 TWD 20 VSM
+0.30 TEC TEH 12 HOT 60OUL 0.33 134 P 2 TWD 15 VSM
+0.82 TEC TEH 12 HOT 60OUL 0.33 134 P 2 TWD 15 VSM
+0.82 TEC TEH 12 HOT 600UL 0.44 84 P 2 TWD 19 VSM
+0.30 TEC TEH 12 HOT 600UL 42 162 0.30 33 P 2 TWD 14 02H
-0.93 TEC TEH 18 HOT 600UL 42 166 0.29 50 P 2 TWD 14 02H
-0.86 TEC TEH 18 HOT 600UL 43 41 0.38 71 P 2 TWD 18 07H
+0.77 TEH TEC NEW 31 COLD 600UL 43 45 0.35 24 P 2 TWD 17 DBH
+1.89 TEH TEC 31 COLD 60OUL 0.35 24 P 2 TWD 17 DBH
+1.89 TEH TEC 31 COLD 600UL 43 51 0.37 132 P 2 TWD 17 02H
+0.79 TEH TEC 12 COLD 600UL 43 73 1.03 81 P 2 TWD 31 DBH
+1.72 TEH TEC 8
COLD 600UL 0.51 48 P 2 TWD 20 VSM
+0.24 TEH TEC 8
COLD 600UL 1.03 88 P 2 TWD 31 DBH
+1.72 TEH TEC 8
COLD 60OUL 0.51 48 P 2 TWD 20 VSM
+0.24 TEH TEC 8
COLD 60OUL 0.63 66 P 2 TWD 22 VSM
+0.24 TEH TEC 47 COLD 60OUL 1.09 100 P 2 TWD 31 DBH
+1.72 TEH TEC 47 COLD 600UL 0.32 67 P 2 TWD 13 VSM
+0.86 TEH TEC NEW 47 COLD 600UL 43 101 1.31 83 P 2 TWD 37 DBC
+1.85 TEH TEC 27 COLD 600UL 1.36 91 P 2 TWD 34 DBC
+1.85 TEH TEC 47 COLD 600UL 1.31 84 P 2 TWD 37 DBC
+1.85 TEH TEC 27 COLD 60OUL 0.20 67 P 2 TWD 9 DBH
+2.48 TEH TEC NEW LAR 27 COLD 600UL 43 103 1.14 173 P 2 TWD 33 DBC
+1.75 TEH TEC 25 COLD 600UL 1.36 159 P 2 TWD 38 DBC
+1.75 TEH TEC 51 COLD E0OUL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 7 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 1.11 173 P 2 TWD 33 DBC
+1.75 TEH TEC 25 COLD 600UL 43 107 0.48 74 P 2 TWD 20 VSM
+0.61 TEH TEC 25 COLD 600UL 0.32 44 P 2 TWD 15 VSM
+0.29 TEH TEC 25 COLD 60OUL 0.46 73 P 2 TWD 19 VSM
+0.61 TEH TEC 25 COLD 600UL 0.33 33 P 2 TWD 15 VSM
+0.29 TEH TEC 25 COLD 600UL 0.30 77 P 2 TWD 14 DBC
+1.76 TEH TEC NEW 25 COLD 600UL 43 117 0.59 62 P 2 TWD 23 VSM
-0.80 TEH TEC 25 COLD 600UL 1.17 112 P 2 TWD 34 VSM
+0.85 TEH TEC 25 COLD 600UL 0.32 43 P 2 TWD 15 VSM
+0.00 TEH TEC 25 COLD 600UL 0.59 62 P 2 TWD 23 VSM
-0.80 TEH TEC 25 COLD 600UL 1.17 112 P 2 TWD 34 VSM
+0.85 TEH TEC 25 COLD 60OUL 0.31 47 P 2 TWD 15 VSM
+0.00 TEH TEC 25 COLD 600UL 0.34 57 P 2 TWO 16 VSM
+0.00 TEH TEC 51 COLD 600UL 0.56 55 P 2 TWD 23 VSM
-0.80 TEH TEC 51 COLD 600UL 1.08 108 P 2 TWD 34 VSM
+0.85 TEH TEC 51 COLD 600UL 43 131 0.65 102 P 2 TWD 25 VSM
+0.84 TEC TEH 27 HOT 600UL 0.65 99 P 2 TWD 25 VSM
+0.84 TEC TEH 27 HOT 60OUL 43 145 0.45 100 P 2 TWD 20 VSM
-0.85 TEC TEH 8
HOT 600UL 0.83 112 P 2 TWD 29 VSM
+0.83 TEC TEH 8
HOT 600UL 0.45 100 P 2 TWD 20 VSM
-0.85 TEC TEH 8
HOT 60OUL 0.83 112 P 2 TWD 29 VSM
+0.83 TEC TEH 8
HOT 600UL 43 153 0.35 142 P 2 TWD 16 DBC
+1.53 TEC TEH NEW 12 HOT 60OUL 43 159 0.45 18 P 2 TWD 20 02H
-0.68 TEC TEH 18 HOT 600UL 44 66 0.28 72 P 6 TWD 16 DBC
+2.14 DBC DBC LAR 198 HOT 560FH 44 72 0.34 150 P 2 TWD 14 DBC
+1.55 TEH TEC NEW 8
COLD 600UL 44 74 0.23 79 P 2 TWD 10 DBH
-1.72 TEH TEC NEW 8
COLD 600UL 44 100 0.45 78 P 2 TWD 19 DBH
-1.78 TEH TEC NEW 27 COLD 60OUL 44 112 0.29 48 P 2 TWD 14 VSM
-0.93 TEH TEC 26 COLD 600UL 0.16 105 P 2 TWD 8 VSM
+0.17 TEH TEC 26 COLD 600UL 0.29 48 P 2 TWD 14 VSM
-0.93 TEH TEC 26 COLD 600UL 0.24 124 P 2 TWD 12 VSM
+0.17 TEH TEC 26 COLD 600UL 44 114 0.48 97 P 2 TWD 20 VSM
-0.76 TEH TEC 25 COLD 600UL 0.50 125 P 2 TWD 20 VSM
+0.98 TEH TEC 25 COLD 60OUL 0.48 97 P 2 TWD 20 VSM
-0.76 TEH TEC 25 COLD 60OUL 0.50 125 P 2 TWD 20 VSM
+0.98 TEH TEC 25 COLD 600UL 44 128 0.42 160 P 2 TWD 17 VSM
-0.89 TEH TEC 17 COLD 600UL 0.52 149 P 2 TWD 20 VSM
+0.96 TEH TEC 17 COLD 600UL 0.42 160 P 2 TWD 17 VSM
-0.89 TEH TEC 17 COLD 600UL 0.52 149 P 2 TWD 20 VSM
+0.96 TEH TEC 17 COLD 600UL 44 134 0.31 115 P 2 TWD 12 VSM
-0.69 TEC TEH 7
HOT 600UL 0.31 115 P 2 TWD 12 VSM
-0.69 TEC TEH 7
HOT 600UL 44 158 0.53 140 P 2 TWD 19 VSM
+0.85 TEC TEH 17 HOT 600UL 0.39 98 P 2 TWD 14 VSM
-0.74 TEC TEH 17 HOT 600UL 0.22 136 P 2 TWD 9 VSM
-0.11 TEC TEH 17 HOT 600UL 0.41 145 P 2 TWD 17 VSM
+0.85 TEC TEH 17 HOT 60OUL 0.36 115 P 2 TWD 16 VSM
-0.74 TEC TEH 17 HOT 60OUL 0.21 137 P 2 TWD 9 VSM
-0.11 TEC TEH 17 HOT 600UL 45 39 0.38 97 P 2 TWD 16 02H
-1.20 TEH TEC 32 COLD 600UL 45 73 0.76 91 P 2 TWD 25 DBH
+1.49 TEH TEC 7
COLD 60OUL 0.76 91 P 2 TWD 25 DBH
+1.49 TEH TEC 7
COLD 600UL 45 101 0.75 101 P 2 TWD 28 DBC
+1.85 TEH TEC 27 COLD 600UL 0.75 113 P 2 TWD 27 DBC
+1.85 TEH TEC 27 COLD 600UL 45 119 0.43 81 P 2 TWD 19 VSM
-1.02 TEH TEC 19 COLD 60OUL 0.27 32 P 2 TWD 13 VSM
+0.79 TEH TEC 19 COLD 60OUL 0.16 168 P 2 TWD 8 VSM
+0.17 TEH TEC 19 COLD 60OUL 0.43 74 P 2 TWD 20 VSM
-1.02 TEH TEC 19 COLD 60OUL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 8 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.17 168 P 2 TWD 8 VSM
+0.17 TEH TEC 19 COLD 600UL 0.23 35 P 2 TWD 12 VSM
+0.79 TEH TEC 19 COLD 600UL 45 131 0.73 94 P 2 TWD 26 VSM
+0.78 TEC TEH 28 HOT 600UL 0.42 134 P 2 TWD 18 VSM
-0.87 TEC TEH 28 HOT 600UL 0.73 94 P 2 TWO 26 VSM
+0.78 TEC TEH 28 HOT 60OUL 0.42 134 P 2 TWO 18 VSM
-0.87 TEC TEH 28 HOT 600UL 45 133 0.18 31 P 2 TWO 9 DBC
-1.30 TEC TEH NEW 26 HOT 600UL 45 135 0.50 137 P 2 TWD 18 VSM
+0.76 TEC TEH 7
HOT 600UL 1.16 125 P 2 TWO 32 VSM
-0.85 TEC TEH 7
HOT 600UL 0.50 137 P 2 TWO 18 VSM
+0.76 TEC TEH 7
HOT 600UL 1.16 125 P 2 TWD 32 VSM
-0.85 TEC TEH 7
HOT 600UL 0.42 128 P 2 TWD 19 VSM
+0.76 TEH TEC 51 COLD 600UL 0.87 108 P 2 TWD 30 VSM
-0.85 TEH TEC 51 COLD 600UL 45 145 0.40 65 P 2 TWD 15 VSM
-0.83 TEC TEH NEW 7
HOT 600UL 45 167 0.27 156 P 2 TWD 12 VSM
+0.93 TEC TEH 19 HOT 600UL 0.27 156 P 2 TWO 13 VSM
+0.93 TEC TEH 19 HOT 600UL 45 169 0.38 91 P 2 TWO 16 01C
+0.95 TEC TEH 19 HOT 600UL 46 36 0.93 87 P 2 TWD 27 VSM
-0.85 TEH TEC 34 COLD 600UL 0.34 40 P 2 TWD 12 VSM
+0.27 TEH TEC 34 COLD 600UL 0.58 93 P 2 TWD 19 VSM
+0.93 TEH TEC 34 COLD 600UL 0.93 87 P 2 TWO 27 VSM
-0.85 TEH TEC 34 COLD 600UL 0.34 40 P 2 TWD 12 VSM
+0.27 TEH TEC 34 COLD 600UL 0.60 95 P 2 TWD 20 VSM
+0.93 TEH TEC 34 COLD 600UL 46 54 0.24 135 P 2 TWO 11 DBH
+1.63 TEH TEC NEW 10 COLD 600UL 46 72 0.42 98 P 2 TWD 17 VSM
+0.80 TEH TEC NEW 7
COLD 60OUL 46 78 1.07 126 P 2 TWD 31 DBH
+1.80 TEH TEC 14 COLD 600UL 0.14 38 P 2 TWO 6 DBH
-1.54 TEH TEC 14 COLD 600UL 0.29 178 P 2 TWO 13 DBC
+2.25 TEH TEC 14 COLD 600UL 0.17 89 P 2 TWO 7 DBH
-1.54 TEH TEC 47 COLD 60OUL 0.62 9
P 2 TWO 21 DBC
+2.25 TEH TEC 47 COLD 600UL 0.85 125 P 2 TWD 26 DBH
+1.80 TEH TEC 47 COLD 600UL 0.14 38 P 2 TWO 7 DBH
-1.54 TEH TEC 14 COLD 600UL 1.07 126 P 2 TWD 31 DBH
+1.80 TEH TEC 14 COLD 600UL 0.29 178 P 2 TWD 13 DBC
+2.25 TEH TEC 14 COLD 600UL 46 100 0.30 22 P 2 TWD 13 DBH
-1.80 TEH TEC NEW 27 COLD 600UL 0.74 129 P 2 TWO 27 DBH
+1.66 TEH TEC NEW 27 COLD 600UL 46 104 0.53 93 P 2 TWD 22 VSM
-0.86 TEH TEC 26 COLD 600UL 0.53 93 P 2 TWD 22 VSM
-0.86 TEH TEC 26 COLD 600UL 46 118 0.21 145 P 2 TWO 10 VSM
-1.03 TEH TEC 26 COLD 600UL 0.16 86 P 2 TWO 8 VSM
-1.03 TEH TEC 26 COLD 600UL 46 138 0.48 125 P 2 TWO 20 04C
-0.14 TEC TEH 2
HOT 600UL 46 146 0.70 89 P 2 TWD 26 VSM
-0.75 TEC TEH 8
HOT 600UL 0.62 116 P 2 TWD 24 VSM
+0.73 TEC TEH 8
HOT 600UL 0.62 116 P 2 TWD 24 VSM
+0.73 TEC TEH 8
HOT 600UL 0.70 89 P 2 TWD 26 VSM
-0.75 TEC TEH 8
HOT 600UL 46 158 0.21 140 P 2 TWD 11 02H
-0.85 TEC TEH 18 HOT 60OUL 46 164 0.41 136 P 2 TWD 18 VSM
-0.83 TEC TEH 18 HOT 600UL 0.18 20 P 2 TWD 10 VSM
-0.11 TEC TEH 18 HOT 600UL 0.41 136 P 2 TWO 18 VSM
-0.83 TEC TEH 18 HOT 60OUL 0.23 34 P 2 TWO 12 VSM
-0.11 TEC TEH 18 HOT 60OUL 46 170 0.31 52 P 2 TWD 13 05C
+0.93 TEC TEH 19 HOT 600UL 47 45 0.45 67 P 2 TWD 20 02H
-1.23 TEH TEC 31 COLD 600UL 47 73 0.67 65 P 2 TWD 24 DBH
+1.65 TEH TEC 8
COLD 600UL 0.68 61 P 2 TWD 24 DBH
+1.65 TEH TEC 8
COLD 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 9 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY:
QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 47 75 0.36 74 P 6 TWD 19 DBC
+1.76 DBC DBC LAR 198 HOT 560FH 0.53 89 P 6 TWD 26 DBC
-2.04 DBC DBC LAR 198 HOT 560FH 0.30 58 P 2 TWD 15 DBC
-2.10 TEH TEC NEW 6
COLD 60OUL 47 101 0.47 16 P 2 TWD 20 DBC
+1.77 TEH TEC 27 COLD 60OUL 0.58 16 P 2 TWD 23 DBC
+1.77 TEH TEC 27 COLD 600UL 47 103 0.34 31 P 2 TWD 15 DBC
+1.75 TEH TEC 25 COLD 600UL 0.29 89 P 6 TWD 17 DBH
+1.88 DBH DBH LAR 198 HOT 560FH 0.34 31 P 2 TWD 16 DBC
+1.75 TEH TEC 25 COLD 600UL 0.31 23 P 2 TWD 15 DBH
-1.55 TEH TEC NEW 25 COLD 600UL 47 111 0.75 85 P 2 TWD 28 VSM
+0.92 TEH TEC 26 COLD 60OUL 0.39 107 P 2 TWD 18 VSM
+0.27 TEH TEC 26 COLD 60OUL 0.39 107 P 2 TWD 18 VSM
+0.27 TEH TEC 26 COLD 600UL 0.75 85 P 2 TWD 28 VSM
+0.92 TEH TEC 26 COLD 600UL 47 119 0.39 58 P 2 TWD 15 VSM
-0.67 TEH TEC NEW 20 COLD 60OUL 47 125 0.43 39 P 2 TWD 18 VSM
-0.62 TEH TEC 17 COLD 60OUL 1.55 76 P 2 TWD 39 VSM
+0.95 TEH TEC 17 COLD 60OUL 1.56 79 P 2 TWD 39 VSM
+0.95 TEH TEC 17 COLD 60OUL 0.48 45 P 2 TWD 20 VSM
-0.62 TEH TEC 17 COLD 600UL 0.20 83 P 2 TWD 10 DBC
+1.75 TEH TEC NEW 17 COLD 600UL 0.48 119 P 2 TWD 21 VSM
-0.62 TEH TEC 51 COLD 600UL 1.15 117 P 2 TWD 35 VSM
+0.95 TEH TEC 51 COLD 600UL 47 133 0.56 105 P 2 TWD 20 VSM
+0.78 TEC TEH 25 HOT 600UL 0.71 104 P 2 TWD 24 VSM
-0.81 TEC TEH 25 HOT 600UL 0.68 147 P 2 TWD 23 VSM
+0.02 TEC TEH 25 HOT 600UL 0.49 104 P 2 TWD 18 VSM
+0.78 TEC TEH 25 HOT 600UL 0.68 147 P 2 TWD 23 VSM
+0.02 TEC TEH 25 HOT 600UL 0.63 91 P 2 TWD 21 VSM
-0.81 TEC TEH 25 HOT 600UL 47 147 0.85 83 P 2 TWD 26 VSM
+0.80 TEC TEH 7
HOT 600UL 1.12 107 P 2 TWD 31 VSM
-0.85 TEC TEH 7
HOT 600UL 0.85 84 P 2 TWD 26 VSM
+0.80 TEC TEH 7
HOT 600UL 1.12 107 P 2 TWD 31 VSM
-0.85 TEC TEH 7
HOT 60OUL 0.86 87 P 2 TWD 30 VSM
-0.85 TEH TEC 51 COLD 60OUL 0.70 79 P 2 TWD 26 VSM
+0.80 TEH TEC 51 COLD 60OUL 48 30 0.54 156 P 2 TWD 19 07H
+0.91 TEH TEC 36 COLD 600UL 0.57 158 P 2 TWD 20 07H
+0.91 TEH TEC 36 COLD 600UL 48 120 0.39 147 P 2 TWD 18 VSM
+0.96 TEH TEC 19 COLD 600UL 0.33 56 P 2 TWD 16 VSM
-0.87 TEH TEC 19 COLD 600UL 0.41 141 P 2 TWD 19 VSM
+0.96 TEH TEC 19 COLD 600UL 0.33 56 P 2 TWD 16 VSM
-0.87 TEH TEC 19 COLD 600UL 48 162 0.26 59 P 2 TWD 11 VSM
+0.87 TEC TEH 17 HOT 600UL 0.26 59 P 2 TWD 12 VSM
+0.87 TEC TEH 17 HOT 600UL 49 49 0.50 156 P 2 TWD 18 08H
+1.61 TEH TEC LOCOK 11 COLD 600UL 0.51 156 P 2 TWD 18 08H
+1.61 TEH TEC LOCOK 11 COLD 600UL 49 75 1.42 105 P 2 TWD 35 VSM
-0.74 TEH TEC 5
COLD 600UL 1.47 120 P 2 TWD 36 VSM
+0.02 TEH TEC 5
COLD 600UL 1.12 124 P 2 TWD 31 VSM
+0.78 TEH TEC 5
COLD 600UL 1.23 100 P 2 TWD 33 VSM
-0.74 TEH TEC 47 COLD 60OUL 0.97 130 P 2 TWD 29 VSM
+0.78 TEH TEC 47 COLD 60OUL 1.32 111 P 2 TWD 34 VSM
+0.02 TEH TEC 47 COLD 600UL 0.26 129 P 2 TWD 11 DBC
-1.83 TEH TEC NEW 47 COLD 60OUL 1.42 105 P 2 TWD 35 VSM
-0.74 TEH TEC 5
COLD 60OUL 1.47 120 P 2 TWD 36 VSM
+0.02 TEH TEC 5
COLD 60OUL 1.12 124 P 2 TWD 31 VSM
+0.78 TEH TEC 5
COLD 600UL 0.32 156 P 2 TWD 13 DBC
-2.12 TEH TEC NEW 5
COLD 600UL 1.24 112 P 2 TWD 36 VSM
+0.02 TEH TEC 6
COLD 600UL 1.14 106 P 2 TWD 35 VSM
-0.74 TEH TEC 6
COLD 600UL 0.86 131 P 2 TWD 30 VSM
+0.78 TEH TEC 6
COLD 600UL 49 77 0.61 150 P 2 TWD 21 DBH
-1.67 TEH TEC 5
COLD 600UL 0.22 13 P 2 TWD 10 DBH
+1.76 TEH TEC 5
COLD 600UL 0.62 154 P 2 TWD 21 DBH
-1.67 TEH TEC 5
COLD 600UL 0.23 19 P 2 TWD 10 DBH
+1.76 TEH TEC 5
COLD 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 10 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 49 97 0.47 58 P 2 TWD 18 DBH
+1.46 TEH TEC NEW 13 COLD 60OUL 49 99 0.99 61 P 2 TWD 30 DBH
-1.59 TEN TEC 13 COLD 600UL 0.99 61 P 2 TWD 30 DBH
-1.59 TEN TEC 13 COLD 600UL 0.84 116 P 2 TWO 29 DBH
-1.59 TEN TEC 27 COLD 60OUL 49 101 0.38 94 P 2 TWO 18 DBH
-1.70 TEN TEC 27 COLD 600UL 0.37 96 P 2 TWO 16 DBH
-1.70 TEN TEC 27 COLD 600UL 49 123 0.57 112 P 2 TWO 22 08H
+1.64 TEN TEC LOCOK 17 COLD 600UL 0.50 123 P 2 TWD 20 08H
+1.25 TEN TEC 17 COLD 60OUL 49 129 0.64 91 P 2 TWD 25 08H
-1.50 TEN TEC LOCOK 51 COLD 600UL 0.64 91 P 2 TWD 25 08H
-1.50 TEN TEC LAR 51 COLD 600UL 50 18 0.56 70 P 2 TWD 20 VSM
-0.89 TEN TEC 40 COLD 600UL 0.26 146 P 2 TWD 10 VSM
+0.77 TEN TEC 40 COLD 60OUL 0.52 70 P 2 TWD 20 VSM
-0.89 TEN TEC 40 COLD 60OUL 0.26 146 P 2 TWD 11 VSM
+0.77 TEN TEC 40 COLD 600UL 50 20 0.63 118 P 2 TWD 22 VSM
+0.21 TEN TEC 38 COLD 60OUL 0.55 138 P 2 TWD 20 VSM
+0.66 TEN TEC 38 COLD 60OUL 0.63 118 P 2 TWD 22 VSM
+0.21 TEN TEC 38 COLD 60OUL 0.55 138 P 2 TWD 20 VSM
+0.66 TEN TEC 38 COLD 60OUL 50 22 0.88 139 P 2 TWD 31 VSM
-0.71 TEN TEC 39 COLD 600UL 0.65 124 P 2 TWD 26 VSM
+0.99 TEN TEC 39 COLD 600UL 0.65 127 P 2 TWO 27 VSM
+0.99 TEN TEC 39 COLD 600UL 0.84 147 P 2 TWD 31 VSM
-0.71 TEN TEC 39 COLD 600UL 0.49 108 P 2 TWD 32 VSM
+0.99 TEE TEC 47 COLD 600UL 0.61 117 P 2 TWD 21 VSM
-0.71 TEN TEC 47 COLD 600UL 50 62 0.61 88 P 2 TWD 22 08H
-1.25 TEN TEC NEW 9
COLD 600UL 50 66 0.51 56 P 2 TWD 20 08H
+1.25 TEN TEC NEW 8
COLD 600UL 50 78 0.37 118 P 2 TWD 15 DBH
-1.32 TEN TEC 14 COLD 600UL 0.37 119 P 2 TWD 15 DBH
-1.32 TEN TEC 14 COLD 60OUL 50 98 0.53 127 P 2 TWD 20 DBH
-1.92 TEN TEC 14 COLD 600UL 0.54 127 P 2 TWD 20 DBH
-1.92 TEN TEC 14 COLD 600UL 0.52 69 P 2 TWD 20 DBC
-1.54 TEN TEC NEW 14 COLD 600UL 50 114 0.78 87 P 2 TWD 28 VSM
-0.78 TEN TEC 26 COLD 600UL 0.80 119 P 2 TWD 29 VSM
+0.84 TEN TEC 26 COLD 600UL 0.80 119 P 2 TWD 29 VSM
+0.84 TEN TEC 26 COLD 600UL 0.78 87 P 2 TWD 28 VSM
-0.78 TEN TEC 26 COLD 60OUL 50 118 0.35 137 P 2 TWO 14 08H
+1.00 TEN TEC 20 COLD 60OUL 0.32 157 P 2 TWD 13 08H
+1.00 TEE TEC 20 COLD 600UL 50 120 0.54 93 P 2 TWD 20 08H
+1.25 TEE TEC 20 COLD 600UL 0.60 114 P 2 TWD 22 08H
+1.25 TEN TEC 20 COLD 600UL 51 45 0.18 164 P 2 TWD 10 DBH
-1.12 TEN TEC NEW 31 COLD 600UL 51 93 0.66 19 P 2 TWD 23 DBH
+1.75 TEN TEC 14 COLD 600UL 0.66 19 P 2 TWD 23 DBH
+1.75 TEN TEC 14 COLD 600UL 51 99 0.41 81 P 2 TWD 17 DBH
-1.98 TEN TEC 14 COLD 600UL 0.41 84 P 2 TWD 17 DBH
-1.98 TEN TEC 14 COLD 600UL 51 101 0.38 143 P 2 TWD 18 DBH
-1.95 TEN TEC 27 COLD 600UL 0.54 70 P 2 TWD 22 DBH
-1.95 TEN TEC 27 COLD 600UL 51 109 0.54 87 P 2 TWD 22 08H
+0.98 TEN TEC 25 COLD 600UL 0.54 87 P 2 TWO 22 08H
+0.98 TEN TEC 25 COLD 600UL 51 117 0.44 155 P 2 TWD 20 DBC
+1.90 TEN TEC NEW 26 COLD 600UL 51 129 0.34 100 P 2 TWD 15 08H
+0.75 TEN TEC 15 COLD 60OUL 0.34 100 P 2 TWD 15 08H
+0.75 TEN TEC 15 COLD 60OUL 52 76 0.28 81 P 2 TWD 14 DBC 0.28 82 P 2 TWD 14 DBC
-1.72 TEN TEC
-1.72 TEN TEC 6
COLD 60OUL 6
COLD 600UL
Framatome ANP Inc.
Customer Name: SONGS Unit 3 01/26/03 10:20 Component:
S/G
- 55 89 Page 11 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 52 78 0.32 17 P 2 TWD 13 DBH
+1.42 TEH TEC NEW 13 COLD 600UL 52 80 0.57 132 P 2 TWD 21 DBH
-1.90 TEH TEC 14 COLD 600UL 0.56 132 P 2 TWD 21 DBH
-1.90 TEH TEC 14 COLD 600UL 0.24 147 P 2 TWD 11 DBC
-1.63 TEH TEC NEW 14 COLD 60OUL 52 82 0.96 48 P 2 TWD 29 DBH
-1.69 TEH TEC 13 COLD 600OUL 0.94 49 P 2 TWD 29 DBH
-1.69 TEH TEC 13 COLD 600UL 0.78 16 P 2 TWD 25 DBC
+2.25 TEH TEC NEW 13 COLD 600UL 52 94 0.48 19 P 2 TWD 18 DBH
+1.72 TEH TEC 13 COLD 600UL 0.48 19 P 2 TWD 18 DBH
+1.72 TEH TEC 13 COLD 600UL 0.30 116 P 2 TWD 12 DBC
-1.27 TEH TEC NEW 13 COLD 600UL 52 100 0.42 37 P 2 TWD 19 DBC
-1.85 TEH TEC 27 COLD 600UL 0.42 37 P 2 TWD 18 DBC
-1.85 TEH TEC 27 COLD 600UL 52 122 0.37 150 P 2 TWD 15 VC3
-0.87 TEH TEC NEW 20 COLD 600UL 52 124 0.46 114 P 2 TWD 19 07H
+0.29 TEH TEC 17 COLD 600OUL 0.94 112 P 2 TWD 31 08H
+0.83 TEH TEC 17 COLD 600UL 0.47 115 P 2 TWD 19 07H
+0.29 TEH TEC 17 COLD 600UL 0.94 114 P 2 TWD 30 08H
+0.83 TEH TEC 17 COLD 6000L 0.45 102 P 2 TWD 20 07H
+0.29 TEH TEC 51 COLD 6000L 0.65 92 P 2 TWD 25 08H
+0.83 TEH TEC 51 COLD 6000L 53 43 0.29 67 P 2 TWD 14 DBC
+1.75 TEH TEC NEW 31 COLD 60OUL 53 47 0.24 62 P 2 TWD 10 03C
+0.89 TEH TEC 11 COLD 600UL 53 73 0.23 130 P 2 TWD 10 DBC
+2.02 TEH TEC NEW 7
COLD 60OUL 53 77 0.74 121 P 2 TWD 27 DBH
-1.70 TEH TEC 6
COLD 600UL 0.80 129 P 2 TWD 29 DBH
-1.70 TEH TEC 6
COLD 600UL 53 81 0.59 85 P 2 TWD 21 DBC
-1 42 TEH TEC 13 COLD 600UL 0.59 85 P 2 TWD 21 DBC
-1.42 TEH TEC 13 COLD 600UL 53 83 0.92 103 P 2 TWD 28 DBH
-1.46 TEH TEC 13 COLD 600UL 0.89 110 P 2 TWD 28 DBH
-1.46 TEH TEC 13 COLD 600UL 53 91 0.25 168 P 2 TWD 10 DBH
-2.25 TEH TEC NEW 13 COLD 60OUL 0.31 107 P 2 TWD 13 DBH
+1.75 TEH TEC NEW 13 COLD 600UL 53 93 0.50 58 P 2 TWD 19 DBH
-1.70 TEH TEC 13 COLD 600UL 0.50 58 P 2 TWD 19 DBH
-1.70 TEH TEC 13 COLD 600UL 53 95 0.54 98 P 2 TWD 20 DBC
-1.70 TEH TEC 13 COLD 600UL 0.54 98 P 2 TWD 20 DBC
-1.70 TEH TEC 13 COLD 600UL 0.23 144 P 2 TWD 9 DBH
+1.82 TEH TEC NEW 13 COLD 60OUL 53 97 0.45 43 P 2 TWD 17 DBH
-1.76 TEH TEC 13 COLD 600UL 0.23 151 P 2 TWD 9
DBH
-1.76 TEH TEC 13 COLD 600UL 53 101 0.27 146 P 2 TWD 14 DBH
-1.65 TEH TEC 27 COLD 600UL 0.27 146 P 2 TWD 14 DBH
-1.65 TEH TEC 27 COLD 60OUL 54 8
0.36 90 P 2 TWD 15 02C
-0.93 TEH TEC 42 COLD 600UL 54 42 0.48 63 P 2 TWD 19 02H
-1.10 TEH TEC 32 COLD 600UL 54 78 0.45 40 P 2 TWD 18 DBH
-1.26 TEH TEC NEW 14 COLD 600UL 54 88 1.54 1.08 0.25 1.12 0.25 1.54 0.35 1.04 1.36 83 45 19 44 19 83 25 41 88 P
P P
P P
P P
P P
2 2
2 2
2 2
2 2
2 TWD TWD TWD TWD TWD TWD TWD TWD TWD 37 31 10 32 10 37 14 30 34 DBH DBC DBH DBC DBH DBH DBH DBC DBH
-1.54
-1.86
+1.75
-1.86
+1.75
-1.54
+1.75
-1.86
-1.54 TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC 13 13 13 13 13 13 47 47 47 COLD COLD COLD COLD COLD COLD COLD COLD COLD 600UL 600UL 600UL 600UL 600UL 60OUL 600OUL 600UL 600UL 54 90 4.42 55 P 2 TWD 71 DBC
+1.89 TEH TEC 57 COLD 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 12 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.70 84 P 2 TWD 24 DBH
-1.50 TEH TEC 14 COLD 600UL 0.25 41 P 2 TWO 11 DBC
-1.91 TEH TEC 14 COLD 60OUL 0.70 84 P 2 TWD 24 DBH
-1.50 TEH TEC 14 COLD 600UL 0.27 38 P 2 TWD 12 DBC
-1.91 TEH TEC 14 COLD 600UL 4.20 50 P 2 TWD 52 DBC
+1.89 TEH TEC 14 COLD 600UL 4.42 55 P 2 TWD 72 DBC
+1.89 TEH TEC 57 COLD 600UL 0.78 85 P 2 TWD 28 DBH
-1.50 TEH TEC 57 COLD 600UL 0.34 89 P 2 TWD 14 DBC
-1.91 TEH TEC 57 COLD 600UL 54 92 1.88 91 P 2 TWD 41 DBH
-1.46 TEH TEC 13 COLD 60OUL 0.14 31 P 2 TWD 6 DBH
+2.25 TEH TEC LAR 13 COLD 600UL 1.84 87 P 2 TWD 40 DBH
-1.46 TEH TEC 13 COLD 600UL 0.19 12 P 2 TWD 8 DBH
+2.25 TEH TEC 13 COLD 600UL 1.52 107 P 2 TWD 39 DBH
-1.46 TEH TEC 27 COLD 600UL 0.15 35 P 2 TWD 6 DBH
+2.25 TEH TEC 27 COLD 600UL
- 54. 96.
- 1. 18....
151.....P 2
TWO.....33....DEC.....+1.86.......TEN.....TEC.....
14....
COLD............UL 54 96 1.12 151 P 2 TWD 33 DBC
+1.86 TEH TEC 14 COLD 600UL 1.24 150 P 2 TWD 34 DBC
+1.86 TEH TEC 14 COLD 60OUL 1.12 170 P 2 TWD 34 DBC
+1.86 TEH TEC 27 COLD 600UL 54 100 0.73 18 P 2 TWD 27 DBH
+1.99 TEH TEC NEW 27 COLD 600UL 54 102 0.45 142 P 2 TWD 20 DBC
+1.86 TEH TEC 26 COLD 600UL 0.32 128 P 2 TWD 15 DBC
-1.70 TEH TEC 26 COLD 600UL 0.45 142 P 2 TWD 20 DBC
+1.86 TEH TEC 26 COLD 600UL 0.29 149 P 2 TWD 14 DBC
-1.70 TEH TEC 26 COLD 60OUL 54 158 0.31 116 P 2 TWD 15 VSM
+0.73 TEC TEH 18 HOT 60OUL 0.31 116 P 2 TWD 15 VSM
+0.73 TEC TEH 18 HOT 600UL 55 9
0.31 105 P 2 TWD 14 02C
+0.14 TEH TEC 42 COLD 600UL 55 85 0.63 32 P 2 TWD 23 DBH
+1.78 TEH TEC 14 COLD 600UL 0.69 33 P 2 TWD 24 DBH
+1.78 TEH TEC 14 COLD 60OUL 55 87 0.35 13 P 2 TWD 15 DBH
+1.65 TEH TEC NEW 14 COLD 60OUL 55 89 0.41 128 P 2 TWD 17 DBH
-1.97 TEH TEC 14 COLD 600UL 0.41 128 P 2 TWD 17 DBH
-1.97 TEH TEC 14 COLD 600UL 55 95 0.34 101 P 2 TWD 14 DBH
-1.86 TEH TEC 14 COLD 600UL 0.32 124 P 2 TWD 14 DBH
-1.86 TEH TEC 14 COLD 600UL 55 99 0.42 69 P 2 TWD 17 DBH
-1.47 TEH TEC 14 COLD 600UL 0.42 39 P 2 TWD 17 DBH
-1.47 TEH TEC 14 COLD 600UL 55 107 0.35 119 P 2 TWD 16 DBH
-1.52 TEH TEC 26 COLD 600UL 0.32 120 P 2 TWD 15 DBH
-1.52 TEH TEC 26 COLD 600UL 55 145 0.38 135 P 2 TWD 15 VH3
-0.90 TEC TEH NEW 7
HOT 600UL 56 76 0.60 99 P 2 TWD 24 VSM
+0.62 TEH TEC 6
COLD 600UL 0.60 114 P 2 TWD 24 VSM
+0.62 TEH TEC 6
COLD 600UL 56 80 0.66 135 P 2 TWD 23 DBH
-1.94 TEH TEC 14 COLD 600UL 0.66 135 P 2 TWD 23 DBH
-1.94 TEH TEC 14 COLD 60OUL 56 82 0.69 133 P 2 TWD 24 DBH
-1.86 TEH TEC 14 COLD 600UL 0.69 133 P 2 TWD 24 DBH
-1.86 TEH TEC 14 COLD 600UL 56 90 0.94 11 P 2 TWD 25 DBC
+2.14 TEH TEC NEW 13 COLD 600UL 56 96 0.27 76 P 2 TWD 11 DBH
-1.80 TEH TEC NEW 13 COLD 600UL 0.48 53 P 2 TWD 18 DBC
+2.25 TEH TEC NEW 13 COLD 60OUL 56 136 0.49 124 P 2 TWD 19 VSM
-0.79 TEC TEH 1
HOT 600UL 0.32 133 P 2 TWD 14 VSM
+0.79 TEC TEH 1
HOT 60OUL 0.32 131 P 2 TWD 14 VSM
+0.79 TEC TEH 1
HOT 600UL 0.49 124 P 2 TWD 20 VSM
-0.79 TEC TEH 1
HOT 600UL 56 146 0.43 43 P 2 TWD 16 VH3
-0.90 TEC TEH NEW 7
HOT 600UL 57 47 0.36 126 P 2 TWD 14 08H
+0.51 TEH TEC 11 COLD 600UL 0.36 126 P 2 TWD 14 08H
+0.51 TEH TEC 11 COLD 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 13 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 57 51 0.35 135 P 2 TWD 13 08H
+0.95 TEH TEC NEW 11 COLD 60OUL 0.25 129 P 2 TWD 10 08H
+0.32 TEH TEC NEW 11 COLD 600UL 57 79 0.39 39 P 2 TWD 15 DBH
+1.57 TEH TEC NEW 13 COLD 60OUL 57 83 0.55 36 P 2 TWD 20 DBH
-1.70 TEH TEC 13 COLD 60OUL 0.42 33 P 2 TWD 16 DBH
-1.70 TEH TEC 13 COLD 600UL 0.27 19 P 2 TWD 11 DBH
+1.61 TEH TEC NEW 13 COLD 60OUL 57 87 0.55 90 P 2 TWD 20 DBC
-2.06 TEH TEC 13 COLD 600UL 0.53 104 P 2 TWD 20 DBC
-2.06 TEH TEC 13 COLD 600UL 57 89 0.22 114 P 2 TWD 9 DBH
-2.01 TEH TEC NEW 13 COLD 60OUL 57 123 0.69 65 P 2 TWD 25 VH3
-0.75 TEH TEC 17 COLD 600UL 0.70 69 P 2 TWD 25 VH3
-0.75 TEH TEC 17 COLD 600UL 57 129 0.28 143 P 2 TWD 13 DBH
+0.00 TEH TEC 51 COLD 600UL 0.28 143 P 2 TWD 13 DBH
+0.00 TEH TEC 51 COLD 600UL 57 143 0.52 78 P 2 TWO 20 VH3
+0.99 TEC TEH 1
HOT 600UL 0.52 78 P 2 TWD 21 VH3
+0.99 TEC TEH 1
HOT 600UL 57 157 0.22 45 P 2 TWD 9 VSM
-0.85 TEC TEH 17 HOT 600UL 0.22 45 P 2 TWD 10 VSM
-0.85 TEC TEH 17 HOT 600UL 58 86 0.54 93 P 2 TWD 20 DBH
-1.89 TEH TEC 14 COLD 600UL 0.54 93 P 2 TWD 20 DBH
-1.89 TEH TEC 14 COLD 600UL 58 90 0.30 144 P 2 TWD 13 DBC
+1.22 TEH TEC 14 COLD 600UL 0.32 140 P 2 TWD 14 DBC
+1.22 TEH TEC 14 COLD 60OUL 0.15 93 P 2 TWD 7 DBH
-1.35 TEH TEC NEW 14 COLD 60OUL 58 94 0.74 126 P 2 TWD 25 DBC
-1.71 TEH TEC 14 COLD 600UL 0.75 126 P 2 TWD 25 DBC
-1.71 TEH TEC 14 COLD 600UL 58 126 0.30 138 P 2 TWD 13 VSM
-0.78 TEH TEC NEW 18 COLD 600UL 58 148 0.53 60 P 2 TWD 22 VSM
+0.77 TEC TEH 8
HOT 60OUL 0.52 133 P 2 TWD 22 VC3
-0.81 TEC TEH 8
HOT 600UL 0.52 133 P 2 TWD 22 VC3
-0.81 TEC TEH 8
HOT 600UL 0.53 60 P 2 TWD 22 VSM
+0.77 TEC TEH 8
HOT 600UL 58 162 0.27 42 P 2 TWD 14 VH3
-0.80 TEC TEH 18 HOT 600UL 0.33 22 P 2 TWD 16 VH3
-0 80 TEC TEH 18 HOT 600UL 58 166 0.37 45 P 2 TWD 17 VH3
-0.68 TEC TEH 18 HOT 600UL 0.38 27 P 2 TWD 18 VH3
-0.68 TEC TEH 18 HOT 600UL 59 33 0.36 150 P 2 TWD 14 VH3
-0.83 TEH TEC NEW 36 COLD 600UL 59 81 0.53 35 P 2 TWD 20 DBH
+1.80 TEH TEC 14 COLD 600UL 0.53 35 P 2 TWD 20 DBH
+1.80 TEH TEC 14 COLD 60OUL 59 85 0.80 112 P 2 TWD 27 DBC
-1.74 TEH TEC 14 COLD 60OUL 0.83 99 P 2 TWD 27 DBC
-1.74 TEH TEC 14 COLD 600UL 59 95 0.59 87 P 6 TWD 28 DBC
+1.71 DBC DBC LAR 198 HOT 560FH 59 97 0.16 165 P 2 TWD 8 DBC
-2.01 TEH TEC NEW 14 COLD 600UL 60 48 0.50 120 P 2 TWD 21 08H
-0.88 TEH TEC 12 COLD 60OUL 0.50 119 P 2 TWD 20 08H
-0.88 TEH TEC 12 COLD 600UL 60 50 0.42 61 P 2 TWD 15 08H
-0.40 TEH TEC 11 COLD 600UL 0.40 58 P 2 TWD 15 08H
-0.40 TEH TEC 11 COLD 600UL 60 54 0.32 120 P 2 TWD 13 08H
+0.93 TEH TEC NEW 9
COLD 600UL 60 88 0.57 46 P 2 TWD 21 DBH
-1.28 TEH TEC 14 COLD 600UL 0.58 46 P 2 TWD 21 DBH
-1.28 TEH TEC 14 COLD 600UL 60 92 0.53 142 P 2 TWD 19 DBH
-1.49 TEH TEC 13 COLD 600UL 0.56 128 P 2 TWD 20 DBH
-1.49 TEH TEC 13 COLD 60OUL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 14 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 60 94 0.47 21 P 2 TWD 18 DBH
+1.76 TEH TEC NEW 13 COLD 60OUL 60 164 0.23 149 P 2 TWD 12 VH3
-1.09 TEC TEH 18 HOT 600UL 0.29 138 P 2 TWD 14 08C
+0.82 TEC TEH 18 HOT 60OUL 0.26 38 P 2 TWD 13 DBC
+1.56 TEC TEH 18 HOT 60OUL 0.26 38 P 2 TWD 13 DBC
+1.56 TEC TEH 18 HOT 600UL 0.33 131 P 2 TWD 16 VH3
-1.09 TEC TEH 18 HOT 600UL 0.29 138 P 2 TWD 14 08C
+0.82 TEC TEH 18 HOT 600UL 61 25 0.40 105 P 2 TWD 17 VH3
-0.83 TEH TEC 36 COLD 600UL 0.36 53 P 2 TWD 14 VH3
-0.83 TEH TEC 36 COLD 600UL 61 79 0.36 26 P 2 TWD 14 DBH
+1.59 TEH TEC NEW 13 COLD 60OUL 61 85 0.65 68 P 2 TWD 23 DBC
-1.93 TEH TEC 13 COLD 600UL 0.62 52 P 2 TWD 22 DBC
-1.93 TEH TEC 13 COLD 600UL 61 153 0.38 129 P 2 TWD 14 VC3
-1.15 TEC TEH 11 HOT 600UL 0.36 130 P 2 TWD 14 VC3
-1.15 TEC TEH 11 HOT 600UL 61 155 0.26 111 P 2 TWD 11 VH3
-1.11 TEC TEH 17 HOT 600UL 0.26 111 P 2 TWO 12 VH3
-1.11 TEC TEH 17 HOT 60OUL 61 157 0.23 117 P 2 TWD 10 02H
-1.04 TEC TEH 17 HOT 600UL 62 50 0.64 82 P 2 TWD 24 08H
-0.15 TEH TEC 12 COLD 600UL 0.62 81 P 2 TWD 24 08H
-0.15 TEH TEC 12 COLD 600UL 62 78 0.33 25 P 2 TWD 14 DBH
+1.84 TEH TEC NEW 14 COLD 600UL 62 88 0.64 50 P 2 TWD 22 DBH
-1.42 TEH TEC 13 COLD 600UL 0.53 105 P 2 TWD 19 DBH
-1.42 TEH TEC 13 COLD 600UL 62 92 0.30 101 P 2 TWD 13 02H
-1.25 TEH TEC 14 COLD 600UL 62 96 0.36 150 P 2 TWD 15 DBH
+2.15 TEH TEC 14 COLD 600UL 0.36 150 P 2 TWD 15 DBH
+2.15 TEH TEC 14 COLD 600UL 62 154 0.40 134 P 2 TWD 18 VH3
-0.88 TEC TEH 12 HOT 600UL 0.35 139 P 2 TWD 16 VH3
-0.88 TEC TEH 12 HOT 600UL 62 160 0.21 11 P 2 TWD 9 DBH
-1.85 TEC TEH 17 HOT 600UL 0.21 11 P 2 TWD 10 DBH
-1.85 TEC TEH 17 HOT 60OUL 62 162 0.23 80 P 2 TWD 12 VH3
-1.01 TEC TEH 18 HOT 60OUL 0.28 122 P 2 TWD 14 VH3
-1.01 TEC TEH 18 HOT 600UL 62 166 0.24 157 P 2 TWD 12 VH3
-1.07 TEC TEH 18 HOT 600UL 0.32 132 P 2 TWD 15 02H
-0.31 TEC TEH 18 HOT 600UL 0.39 101 P 2 TWD 18 02H
-0.86 TEC TEH 18 HOT 600UL 0.25 145 P 2 TWD 13 VH3
-1.07 TEC TEH 18 HOT 60OUL 63 53 0.50 120 P 2 TWD 20 08H
+0.41 TEH TEC 12 COLD 600UL 0.52 118 P 2 TWD 21 08H
+0.41 TEH TEC 12 COLD 600UL 63 81 0.24 21 P 2 TWD 11 DBH
+1.78 TEH TEC NEW 14 COLD 600UL 63 83 0.66 66 P 2 TWD 23 DBC
+1.52 TEH TEC 14 COLD 600UL 0.69 85 P 2 TWD 24 DBC
+1.52 TEH TEC 14 COLD 600UL 63 85 0.46 94 P 2 TWD 18 DBH
+1.76 TEH TEC NEW 14 COLD 600UL 64 42 0.40 129 P 2 TWD 18 VH3
-0.79 TEH TEC NEW 31 COLD 600UL 64 82 0.31 147 P 2 TWD 13 DBH
-1.54 TEH TEC 14 COLD 600UL 0.32 144 P 2 TWD 14 DBH
-1.54 TEH TEC 14 COLD 600UL 64 96 0.42 11 P 2 TWD 16 DBC
+2.00 TEH TEC NEW 13 COLD 60OUL 64 158 0.27 103 P 2 TWD 11 VH3
-0.93 TEC TEH 17 HOT 600UL 0.32 111 P 2 TWD 14 VH3
-0.93 TEC TEH 17 HOT 600UL 64 166 0.33 25 P 2 TWD 14 07H
+0.63 TEC TEH 17 HOT 600UL 0.33 24 P 2 TWD 15 07H
+0.63 TEC TEH 17 HOT 600UL
Framatome ANP Inc.
01/26/03 10:20:55 Customer Name: SONGS Unit 3 Component: S/G 89 Page 15 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 65 27 0.52 44 P 2 TWD 21 VC3
-0.87 TEH TEC 36 COLD 600UL 0.86 130 P 2 TWD 26 VSM
-0.85 TEH TEC 36 COLD 600UL 0.86 130 P 2 TWD 26 VSM
-0.85 TEH TEC 36 COLD 600UL 0.50 38 P 2 TWD 18 VC3
-0.87 TEH TEC 36 COLD 600UL 65 49 0.45 155 P 2 TWD 16 VH3
-0.76 TEH TEC 11 COLD 60OUL 0.26 113 P 2 TWD 10 VH3
+0.85 TEH TEC 11 COLD 600UL 0.45 155 P 2 TWD 16 VH3
-0.76 TEH TEC 11 COLD 600UL 0.26 113 P 2 TWD 10 VH3
+0.85 TEH TEC 11 COLD 600UL 65 53 0.29 92 P 2 TWD 11 08H
-0.56 TEH TEC 11 COLD 600UL 0.29 92 P 2 TWD 11 08H
-0.56 TEH TEC 11 COLD 600UL 65 59 0.73 128 P 2 TWD 26 VSM
-0.77 TEH TEC 10 COLD 600UL 0.39 147 P 2 TWD 17 VSM
+0.84 TEH TEC 10 COLD 600UL 0.39 149 P 2 TWD 17 VSM
+0.84 TEH TEC 10 COLD 600UL 0.73 128 P 2 TWD 26 VSM
-0.77 TEH TEC 10 COLD 600UL 65 87 0.40 54 P 2 TWD 15 DBH
+1.72 TEH TEC 13 COLD 600UL 0.33 34 P 2 TWD 13 DBH
+1.72 TEH TEC 13 COLD 600UL 65 91 0.62 23 P 2 TWD 22 DBH
+1.99 TEH TEC 13 COLD 60OUL 0.71 23 P 2 TWD 24 DBH
+1.99 TEH TEC 13 COLD 600UL 65 97 0.20 57 P 2 TWD 8 DBC
-1.89 TEH TEC NEW 13 COLD 600UL 65 131 0.56 36 P 2 TWD 22 02H
-1.25 TEC TEH 2
HOT 600UL 65 143 0.38 91 P 2 TWD 16 VH3
-0.81 TEC TEH NEW 1
HOT 600UL 65 151 0.51 124 P 2 TWD 18 VSM
+0.86 TEC TEH 11 HOT 600UL 0.25 58 P 2 TWD 11 VSM
+0.15 TEC TEH 11 HOT 600UL 0.35 15 P 2 TWD 14 VSM
-0.94 TEC TEH 11 HOT 600UL 0.51 124 P 2 TWD 18 VSM
+0.86 TEC TEH 11 HOT 60OUL 0.43 26 P 2 TWD 15 VSM
-0.94 TEC TEH 11 HOT 60OUL 0.25 55 P 2 TWD 9 VSM
+0.15 TEC TEH 11 HOT 60OUL 66 28 0.42 144 P 2 TWD 18 VH3
-0.95 TEH TEC 36 COLD 600UL 0.38 100 P 2 TWD 15 VH3
-0.95 TEH TEC 36 COLD 600UL 66 60 0.80 143 P 2 TWD 26 VSM
+0.85 TEH TEC 9
COLD 60OUL 0.44 114 P 2 TWD 17 VSM
-0.68 TEH TEC 9
COLD 60OUL 0.59 36 P 2 TWD 21 01H
+0.87 TEH TEC 9
COLD 600UL 0.44 114 P 2 TWD 17 VSM
-0.68 TEH TEC 9
COLD 600UL 0.80 143 P 2 TWD 26 VSM
+0.85 TEH TEC 9
COLD 60OUL 66 82 0.29 79 P 2 TWD 12 DBH
-1.63 TEH TEC 13 COLD 600UL 0.36 120 P 2 TWD 14 VH3
+0.87 TEH TEC 13 COLD 60OUL 0.19 40 P 2 TWD 8 DBH
-1.63 TEH TEC 13 COLD 600UL 0.30 145 P 2 TWD 12 VH3
+0.87 TEH TEC 13 COLD 600UL 66 164 0.47 125 P 2 TWD 20 VH3
-0.85 TEC TEH 17 HOT 600UL 0.47 125 P 2 TWD 20 VH3
-0.85 TEC TEH 17 HOT 600UL 67 33 0.51 151 P 2 TWD 18 VC3
+0.96 TEH TEC NEW 36 COLD 60OUL 67 39 0.20 24 P 2 TWD 11 DBC
-1.75 TEH TEC NEW 31 COLD 600UL 67 55 0.31 132 P 2 TWD 14 08H
+0.78 TEH TEC 10 COLD 600UL 0.31 132 P 2 TWD 14 08H
+0.78 TEH TEC 10 COLD 600UL 67 87 0.24 109 P 2 TWD 11 DBC
-1.91 TEH TEC 14 COLD 600UL 0.27 39 P 2 TWD 12 DBC
-1.91 TEH TEC 14 COLD 600UL 0.36 95 P 2 TWD 15 DBH
+1.76 TEH TEC NEW 14 COLD 600UL 67 97 0.25 122 2 SAI TSH
+1.17 TSH TSH 0.0 8.40 71 HOT 580PP 0.15 24 P 2 TWD 7 DBC
-2.03 TEH TEC NEW 14 COLD 60OUL 67 145 0.64 135 P 2 TWD 22 VC3
+1.14 TEC TEH NEW 7
HOT 600UL 67 155 0.33 117 P 2 TWD 16 VSM
+0.79 TEC TEH 18 HOT 600UL 0.33 117 P 2 TWD 16 VSM
+0.79 TEC TEH 18 HOT 600UL 67 159 0.21 133 P 2 TWD 11 VH3 0.21 133 P 2 TWD 11 VH3
-0.81 TEC TEH 18 HOT 600UL
-0.81 TEC TEH 18 HOT 600UL
02 H-00 00 00001 0000 I
00 0o I co 00 00a 0202 0
0 02 0D 00 ooW 00 0 0 0D W2 E4 N
CQ 0
0ý 14 A
E 14 Ig 0
I 0l
,4 t*
1 0 El ICN I Hý IN
'o 10 11:2 Ho 0
I 0 u
I 0 u
u H El E2 El0 H I 02 I N 1:2 INc 0D I H 0.I 02 0, I0
+11 "0.10010 00 00 0
00 0
L) )
U L
)
- ==
=
001 00 I O00 Hý H I
I HE-4 Iý N1 NI I4 I I en4 enI mX (1) oo H>
I 022o OZ)I 01 0- I 02 I HliI 014 Hý I Ci H
H H
H 00 mN 00 r-W T ON en en a) a):
00 c
H H
00 a)In I-HH I NN I EH tOD I 0 0N N
I 0202ý 00 ID 00 0 )
I0 00w 00
)00 00 C)00 CD00 00 020 C) 0 0
- 0) 02 0
0 0o i-o2 00o000000000 000000000000 00 00 2o2 00o 0202 en H
- 0)
N*
0 H
I N Ioa 0000 00co00 I0 H-H- H H I NN N I HH H I I+1
>00 00001 N
I N1 02i HN I~
000 0
+400 rnO Oe Il OD H
CD000 I
0000 I
000 ImImc 00001 000 I)U I
Ig 0
OI 00 0
I 00I 00 00 I HHý:
0D I u
0 en I U
EI NI 0I 01 NI NI HIl WI 02 oI I
CN CN H
Hý CA00 H
H 00 I I H>
020
{N N c00 00*
HH%
N N 040 020 Iý Ene I H H I
EE I 00 SNN I HH I4 00 I 00 P
I 00 Iý HH I
00 I 0 E-E 00 NN HH CDq CD 0 0 O00 N N 00 r--i 0202 00 H
H H 00 HE 00
+ +
00 a')
In Hu 00 mNm H,-4,"
00 aO aO 02('
02 H
INz u
10 IE
+
ca 1 0 IN I 4 0
OD 10 I
0 10 13 HHH HHE-H I HH HHHH E E I EHH I E-HE 00 100 00 i0 0 iO0 i000000000000 oo00 0
0 10oI 0 I 00 I 00000000 00 1001 00) I) 0 I u
0I 0 I0 0000 0000 IZ IN H
00mCD00 I+l+
m f
N en 02 too Iý I I OC en 02 0(
w 0
,--0 O 0
0 0) 4-)
{-I 0
z L)0 0 a (a0 0)4.
L.
00 I
I N- 02 0 NA 001 0-I F-i -4 E
-4E,..i N1 N1 I1 NN al 04 I P4 04 020 I 02 en H- 0 IHD H.4,,.
H
.I H-H-1004 I HH I 00 C
I H>
A 04 E.l E a", rW I HH I N ND I n a)
I 4N ko r00 No I
I
+
+
co I
I I
I I
I I
I001 I 40 I N I H 10 IN T3 4J Op CD 0
H H
H
-4 U)
F--1 H
In In)
N N D) a)
0) 0 It OH 00I HI OW 0
0 I
.1.
0 II H
OZ 0I0 0
I H: II 0
II en 0
C4 01 H H
ý H H H H H H E004 0000000 r-C)(N00 -000
[0 N; 0 N ND 0 N 0 0 N 0D N I n en en en en en en en en en en en
=I=0000=000000004 0 I )
0 4
H 020 H- 02 N H 00 In LN I en en N H en N4 H en en Nq N H I 2 l-:
000000000 000 INNNNN N Nq N CN Nq N4 N I
~~
0.10040 I N N1 N-In Nq N-a) N1 N H H4 02 I H H Ný Nl H-N- N H H Hi 02 N 02 Hý N 02 H N 02022000 0 H 00 C H a000 H
H- 0 0
44 0
r-0 w
- m.
4 4D U
N
".1
,-1 E
H I00 II C) Ca 1I 00 u u w 00 EI HP 11 E E II 0
- I Ca-Ca IIH 00 00 00 000000 000000 to t Ca Ca Ca Ca CD Ca cc]
ýO1.
00 10 00 I 0 00 I 0 00 I 0 uuI L
0010 0010 N N I CNI El I"D
ý HH I CC m H
IH 00 IW 01 V) Ca I3 00 I0 m3 I
t.
0 0) 00000000 Ca0 Ca tot Ca Ca Ca Ca 00000000 3333333W H
H H P H H H
Hý 33333333 wwwwwwww H-en NO H H HnO OOOOOOOO H LA LA ND OD N LA NLN N H N H N N 00000000 33333333 HHHHHHHH N
0000444 I
+
114H u
e 0 n H Hen HLA e
Cen 00CaNen 0 LAenenenLAenLAe 00000000 0 0 I El 0l I Ca H-I H
I r.al H
- 1 N :
NI 041 N
0 I 00 00 00 00 WW1 NW Ca Ca I I H
H tD00 (N N' 0 Ca H Ca Ca 04 3
Ea 3
3 Ca H
0 N
Hi I4 en1 en en en ene I WNW WN4
-I WW
-4W O N I c H H Ca4 H CA H)
Iý Ca 04 Ný Ca N 0 II + + I + +
I > >O> > >O I
N04H I. H HHHHHE Iq N N N N N~ N CaIC C)
C4 VL I H4 en H H Nj Ca I 0) LA n
r, en mLA I LA LA Ný LA Ný W I Ca )C I NUU lenMM g-3/4 00 00
- 0) m H
H 040 0404 Ca H 00 Ca Ca w 00 000000 00 uu I.
4UUUUUUI UI )
Ca Ca Ca IDýO O I) 00 I 00 I 0 g
g 0
p-C) 0 t0 0
Ca D00 00 00 CagC EH H 0-0 E
raW HH 33 N N mm mm
-4,--.I H H 00 Ca 04
- .CI 0
H.'.
04 0 0 0 0 4-)0 a4 0
r40 40 a m0) 00L) i; O
co en 0
en 3l H-C) 50 3
N 3
0 N
Ca en 0
+
en 3
H*
LA I I I
I n C4I 1001 I-00-I I 00 ICa4 CA 100 0
gg mm I
100 I HH INW I
HH I N I C-C Hý H I
CN I I
I "IN m CY 00o I, en enW LA4 Ca Hr N N CD 0 LA 4
L) co U)
L)
H en En uHu Wr33 0)0 Ca Ca 0M I
I
" NN I CU 04 I100 I Ca4 00 1 00 1
=3x I =3= I 001 C) Ca 00 00u 050' 0 1 0 0 I 0 L)
I Ca Ca I en En I H Ca4 1W 010 WIN C,
[--I 0
en 0ý 000 100 en:
en e I Ca to Hl H H-E-ene m3 0
100m C; Ca a I C; N HH0H I HH>
014 NCa 4 IF 040 N N1 CN I 04C H3 H H) I H H 000 1C)00 333'3 mH IH N
NI OH H E I
.4 11 >:
UIIH 0 11 0 H
- H 3 II (511 en 0II4 Ca4I Ig
- 0D0 I 00 0 0 I 00C Ca Ca I Ca Ca noon 00 100 Ca Ca I )
CaC NW I4NNw HH E
I HH 3W 133
(
CA0) m 00 Iý I I I I C
m m MM I I I >
00 1Q00 N N IN N
04 N40404 I ý 04 IC I en Ca ILA e H I H H I H
- H 1 0 Ca I Ca en I00 I100 IN IN I -
I Uuu I N N I En en I Caý I HH PI H
I e e I en en-en O4 0)
ICa4 Ca4 I 33 L I ND N C1 0D I 0o I 0 1 0l uI CNI W
u 3'
,.0 ElI
+
HI mWI en I
+1ý 10 1 0-4 Oh 00 CN N u0 NW EHH E..E Ca Ca 04 00 NA N 00
(
N N 0404 N NN
.4 1 0 1 00 0
I0
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 18 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 74 140 0.26 142 P 2 TWD 13 VC3
+0.81 TEC TEH 2
HOT 600UL 0.26 142 P 2 TWD 13 VC3
+0.81 TEC TEH 2
HOT 600UL 75 19 0.38 145 P 2 TWD 16 VH3
-0.97 TEH TEC 36 COLD 600UL 0.25 88 P 2 TWD 11 VSM
-0.54 TEH TEC 36 COLD 60OUL 0.84 151 P 2 TWD 28 VC3
+0.85 TEH TEC 36 COLD 60OUL 0.35 118 P 2 TWO 14 VH3
-0.97 TEH TEC 36 COLD 60OUL 0.22 106 P 2 TWO 9 VSM
-0.54 TEH TEC 36 COLD 600UL 0.82 145 P 2 TWD 26 VC3
+0.85 TEH TEC 36 COLD 600UL 75 43 0.62 41 P 2 TWD 23 VC3
+0.77 TEH TEC 32 COLD 600UL 0.62 41 P 2 TWD 23 VC3
+0.77 TEH TEC 32 COLD 600UL 75 45 0.41 138 P 2 TWD 19 VH3
-0.80 TEH TEC NEW 31 COLD 600UL 75 79 0.76 144 P 2 TWD 26 VSM
+0.94 TEH TEC 14 COLD 600UL 0.22 164 P 2 TWD 10 VSM
-0.90 TEH TEC 14 COLD 600UL 0.76 144 P 2 TWD 26 VSM
+0.94 TEH TEC 14 COLD 600UL 0.22 148 P 2 TWD 10 VSM
-0.90 TEH TEC 14 COLD 600UL 75 95 0.81 75 P 2 TWD 27 VC3
-0.90 TEH TEC 14 COLD 60OUL 0.81 75 P 2 TWD 27 VC3
-0.90 TEH TEC 14 COLD 60OUL 75 147 0.74 102 P 2 TWD 24 VC3
+0.65 TEC TEH 7
HOT 60OUL 0.74 I01 P 2 TWD 24 VC3
+0.65 TEC TEH 7
HOT 600UL 75 159 0.29 63 P 2 TWO 14 VH3
-0.85 TEC TEH 18 HOT 600UL 0.29 63 P 2 TWD 14 VH3
-0.85 TEC TEH 18 HOT 600UL 76 16 0.44 120 P 2 TWD 17 08C
-0.06 TEH TEC 35 COLD 600UL 0.44 120 P 2 TWD 18 08C
-0.06 TEH TEC 35 COLD 600UL 76 54 0.24 95 P 2 TWD 10 DBH
+0.95 TEH TEC 11 COLD 600UL 0.24 95 P 2 TWD 10 DBH
+0.95 TEH TEC 11 COLD 600UL 76 132 0.40 146 P 2 TWD 16 VH3
-0.73 TEC TEH 1
HOT 600UL 0.39 145 P 2 TWD 17 VH3
-0.73 TEC TEH 1
HOT 60OUL 76 134 0.33 157 P 2 TWD 14 DBC
-1.99 TEC TEH NEW 1
HOT 600UL 76 146 0.53 29 P 2 TWD 19 VH3
+0.67 TEC TEH 7
HOT 600UL 0.62 132 P 2 TWD 22 VH3
-0.78 TEC TEH 7
HOT 600UL 0.54 31 P 2 TWD 19 VH3
+0.67 TEC TEH 7
HOT 600UL 0.63 132 P 2 TWD 21 VH3
-0.78 TEC TEH 7
HOT 600UL 76 152 0.29 55 P 2 TWD 10 VC3
-0 63 TEC TEH 11 HOT 600UL 0.29 55 P 2 TWD 10 VC3
-0.63 TEC TEH 11 HOT 600UL 76 154 0.50 135 P 2 TWD 17 VH3
-0.78 TEC TEH 11 HOT 600UL 0.50 135 P 2 TWD 17 VH3
-0.78 TEC TEH 11 HOT 600UL 76 156 0.31 146 P 2 TWD 13 VH3
-0.86 TEC TEH 17 HOT 60OUL 0.31 147 P 2 TWD 14 VH3
-0.86 TEC TEH 17 HOT 60OUL 76 160 0.35 155 P 2 TWD 16 VH3
-0.91 TEC TEH 18 HOT 60OUL 0.35 155 P 2 TWD 17 VH3
-0.91 TEC TEH 18 HOT 600UL 76 162 0.41 82 P 2 TWD 15 08H
+0.75 TEC TEH 17 HOT 600UL 0.38 76 P 2 TWD 17 08H
+0.75 TEC TEH 17 HOT 600UL 77 15 0.44 122 P 2 TWD 18 VH3
-0.93 TEH TEC 36 COLD 600UL 0.37 45 P 2 TWD 14 VH3
-0.93 TEH TEC 36 COLD 600UL 77 29 0.51 140 P 2 TWD 19 VC3
+0.71 TEH TEC 35 COLD 600UL 0.51 140 P 2 TWD 19 VC3
+0.71 TEH TEC 35 COLD 600UL 77 39 0.31 67 P 2 TWD 13 VC3
+0.91 TEH TEC 32 COLD 600UL 0.30 70 P 2 TWD 13 VC3
+0.91 TEH TEC 32 COLD 600UL 77 61 0.66 154 P 2 TWO 23 VSM
+0.72 TEH TEC 9
COLD 600UL 0.60 119 P 2 TWO 21 VH3
-0.85 TEH TEC 9
COLD 60OUL 0.60 119 P 2 TWD 21 VH3
-0.85 TEH TEC 9
COLD 600UL 0.66 154 P 2 TWD 23 VSM
+0.72 TEH TEC 9
COLD 60OUL 77 75 0.42 58 P 2 TWD 16 VH3
-0.98 TEH TEC 5
COLD 600UL
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name: SONGS Unit 3 Component: S/G 89 Page 19 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY:
QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.42 58 P 2 TWD 16 VH3
-0.98 TEH TEC 5
COLD 60OUL 0.21 101 P 2 TWD 9 DEC
+1.85 TEH TEC NEW 5
COLD 60OUL 77 155 0.82 139 P 2 TWD 29 VH3
+0.80 TEC TEH 18 HOT 600UL 0.39 53 P 2 TWD 18 VH3
-0.98 TEC TEH 18 HOT 60OUL 0.82 139 P 2 TWO 29 VH3
+0.80 TEC TEH 18 HOT 600UL 0.44 140 P 2 TWO 19 VH3
-0.98 TEC TEH 18 HOT 60OUL 78 20 0.58 136 P 2 TWD 22 VH3
-0.93 TEH TEC 36 COLD 600UL 0.52 100 P 2 TWD 19 VH3
-0.93 TEH TEC 36 COLD 60OUL 78 24 0.52 109 P 2 TWD 21 VC3
-0.85 TEH TEC 36 COLD 600UL 0.49 72 P 2 TWD 18 VC3
-0.85 TEH TEC 36 COLD 600UL 78 40 0.17 122 P 2 TWD 7 DBC
-1.63 TEH TEC NEW 32 COLD 60OUL 78.. 62.
- 0. 50.....
134.....P...
2 TWO.....19......C.....-0.68.......TEE.....TEC.....
9...
COLD..........OUL..
78 62 0.50 134 P 2 TWD 19 VC3
-0.68 TEH TEC 9
COLD 60OUL 0.49 137 P 2 TWD 18 VC3
-0.68 TEH TEC 9
COLD 600UL 78 116 0.26 151 P 2 TWD 11 DBH
+2.20 TEH TEC NEW 22 COLD 600UL 78 158 0.50 113 P 2 TWD 21 VH3
-0.85 TEC TEH 18 HOT 600UL 0.51 116 P 2 TWD 22 VH3
-0.85 TEC TEH 18 HOT 600UL 78 160 0.86 105 P 2 TWO 27 VH3
-0.81 TEC TEH 17 HOT 60OUL 0.74 109 P 2 TWD 26 VH3
-0.81 TEC TEH 17 HOT 600UL 79 19 0.29 8
P 2 TWD 12 DBH
+1.82 TEH TEC NEW 36 COLD 600UL 79 25 0.36 51 P 2 TWD 14 08C
-1.00 TEH TEC 35 COLD 600UL 0.42 29 P 2 TWD 17 08C
-1.00 TEH TEC 35 COLD 600UL 79 29 0.44 47 P 2 TWD 17 VC3
+0.93 TEH TEC 36 COLD 600UL 0.44 50 P 2 TWD 17 VC3
+0.93 TEH TEC 36 COLD 600UL 0.29 34 P 2 TWD 12 VSM
-0.83 TEH TEC NEW 36 COLD 60OUL 79 39 0.49 98 P 2 TWD 21 DEC
+1.95 TEH TEC 31 COLD 600UL 0.51 95 P 2 TWD 22 DEC
+1.95 TEH TEC 31 COLD 600UL 79 81 1.85 130 P 2 TWD 40 VSM
+0.90 TEH TEC 14 COLD 600UL 0.49 145 P 2 TWD 19 VSM
-0.62 TEH TEC 14 COLD 600UL 0.46 140 P 2 TWD 19 VSM
-0.62 TEH TEC 27 COLD 60OUL 1.58 127 P 2 TWD 40 VSM
+0.90 TEH TEC 27 COLD 60OUL 1.87 130 P 2 TWO 41 VSM
+0.90 TEH TEC 14 COLD 60OUL 0.49 145 P 2 TWD 19 VSM
-0.62 TEH TEC 14 COLD 60OUL 79 93 0.50 97 P 4 TWD 26 DEC
+2.14 DEC DEC LAR 174 HOT 560FH 0.58 88 P 2 TWD 21 VH3
-0.49 TEH TEC 14 COLD 600UL 1.02 120 P 2 TWD 31 VC3
-1.01 TEH TEC 14 COLD 600UL 0.84 86 P 2 TWD 27 VC3
+0.88 TEH TEC 14 COLD 60OUL 0.78 113 P 2 TWD 26 VH3
+0.90 TEH TEC 14 COLD 600UL 0.58 87 P 2 TWD 22 VH3
-0.49 TEH TEC 14 COLD 600UL 0.88 108 P 2 TWD 28 VH3
+0.90 TEH TEC 14 COLD 60OUL 0.85 86 P 2 TWD 27 VC3
+0.88 TEH TEC 14 COLD 600UL 1.03 119 P 2 TWD 31 VC3
-1.01 TEH TEC 14 COLD 600UL 0.87 133 P 2 TWD 30 VC3
-1.01 TEH TEC 27 COLD 600UL 0.59 83 P 2 TWD 23 VH3
-0.49 TEH TEC 27 COLD 600UL 0.74 132 P 2 TWD 27 VH3
+0.90 TEH TEC 27 COLD 600UL 0.82 62 P 2 TWD 29 VC3
+0.88 TEH TEC 27 COLD 60OUL 79 95 0.30 85 P 4 TWD 19 DEC
+1.78 DEC DEC LAR 174 HOT 560FH 79 125 0.32 155 P 2 TWD 14 VH3
+0.78 TEH TEC 18 COLD 600UL 0.72 129 P 2 TWD 26 VSM
+0.76 TEH TEC 18 COLD 600UL 0.32 154 P 2 TWO 14 VH3
+0.78 TEH TEC 18 COLD 600UL 0.72 127 P 2 TWD 26 VSM
+0.76 TEH TEC 18 COLD 60OUL 79 129 0.39 120 P 2 TWD 16 VSM
-0.87 TEH TEC 15 COLD 600UL 0.48 157 P 2 TWD 19 VSM
+0.83 TEH TEC 15 COLD 600UL 0.79 139 P 2 TWD 26 VH3
+0.95 TEH TEC 15 COLD 600UL 0.78 142 P 2 TWD 26 VH3
+0.95 TEH TEC 15 COLD 60OUL 0.39 120 P 2 TWD 16 VSM
-0.87 TEH TEC 15 COLD 60OUL 0.48 157 P 2 TWD 19 VSM
+0.83 TEH TEC 15 COLD 60OUL 79 161 0.25 20 P 2 TWD 11 VH3
-0.85 TEC TEH 17 HOT 60OUL
0 0
04 a)
(a 04 00C to to w
co 0
04 0
C4 0
El N
i-C H
H 01 E
0 1
0- I toI I
0I 31 oi 31 WI 0 10 0
I 0D 0
I 0 to I to I e I N WIWc HIH In 0
0I N N I H toto to t I
I I
I I
I I
I I 00 I
I 00 I
I 00 I
I to to I I
I I
I 0 0 00 to to to to to en) toooo IDI oow I
-C:
0D 00000 0000o 00000 00 000 00 '000 1100 00 133333x U0u
-C)
El 0
Eý 0
0 to H
Cý 0
3 I o H-
-C) 00 N N w
H E33E H00 WW HO m
u') LnI (n
W W NN Eýle E 0o r, r,'
Q
°l H H 04 04 a00 en en H H; ene co o0 I 0) to 10 10 10z u
I N 04
+
U CQ Eý
,-i I co 0%
10 N* N I Nl N CN N 0I NN a40a4I 040a4 I 00 r-- r' u-O u-)
toc N-N en en) 00 C OD I N 00 CN 0 I 00000 I cHHcc en ID141 00000 I4 04040140404 I Hý Hý 0 H I 0000 N N N N N I if0I EH H-H- H H
I ene 00 I
0I 00
- 0) I 00 0- I 00 E
Hi H'I N' N N4 N M0I (N NI CN N H1 00 to o toto I0 I 00 I -C U I -Cu en) en en en en 00000 U
0H 0- H- 0E Cc 0 en 0 en en) 0 en) 0 HHHE- ýE-4i N1 N N N N 0COH HOr N I 0 Cl' en N
Nc H1 CcH N
C;Ne 10 1W H)
I13 0 000 00000 00000 0
U0 I 0 UUUU 0uuuuu U
0 CD C) 0 00001 0000 0 0 I
0 4
E-, E-, E, En (3) En (7, o.-
N N
-C'41 Ln °D ° 0 0000 C) to
.01 000 00 I 000 0 0 I 000) C to to I to to to iCl 04 0
I 0
0-0l OI 0I H
N 0
en H
r r-q 4n 3l 0;
I0 0 c to to H H
,+
1*33 t N' H H 00 33 HH to 0 en cc "w
0 04 4 0 0
.)
u0 00(1 (ai0 r44 C) 0 00 000 0 I001 000 0
00 04 1
L) iC 00 HH E
H H 04 El E
- 33 N N 00 33 H0) 0 00 0 cca 0 cc NH c
1N Hw 000004 r ý 333O33L HHHHHL C4 N; N; Ný N N 0400440 NI0 HOnD Nt I.N N I
00
+ +
1 00 LO I-c c I1 00 I00 I 3 enl enl N N O
0 0
ý4 0
00 WW HH 00 I
I to N H H 00 (NN I 00 C
Ico I P I
l W W I4 WW I WW WM I H H P EHHHHO1:
4 C
H 0
H U) en H
0g en z
ii 0II HO H I UO
.4 0 I1 0, II H
or*
ow I 0 I O I H
I 3 I 3OI W
W 33 10 I cc CDc WW o3 0 H N-N- N (N N N t4 0
0 0
4 U0U0 cc o wcc
+
+
000 N4 0 H Nl N N N N' (N 0 e toCD t 0
0 H
0 r-r N N
+4+
00 I I
4-4 0
cu 11 0 II0 E*
Uý 1 E II 04 II P IIN 0010 D oo 00 I
00 U
u I E-E Cl Cl N N 100 I N0 C,H I.-
N 00L "L
r 00 N U
-LD u0
ý41 0 a) 1001 41)
I I
I I
I I
.- 4I 01 0
I 101 I 0 I
I I
I I
I I
I I
I I
101 I.-4I 101 101 I
I I
I I
I I
I IClI I N I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
131 WI NI I
I I
I 101 NI HI I
I WI NI HI I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I 101 101 I
- I H
I I I I I
I I
I I
I I
I I
I I N I
WI 1>1 I
I I
I I N I
NI I
I 101 131 HI I
I I N I
NI I Cl I I 0 I
I H
I I 0 I 0 I H H
I cc 01 0
I 0-I D I 014 E-4 N
[o.
CI NI 0
I-1-4.4 I
001 00 I) 00 ID noo 00 U
u H
I Iý 0404
-NW
- NW HH1 00 H H CDI
.41 01 Ol 0
I CI El r01 0-I H
I
-I I
N-I HI E.
u 01 04 I
H m
.4.4 I 00 I
00 I
00 I
00 I
HH I
001 I NW I
I I
I I
I I
I I
I I
I H H I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I NW I
I NW I
I HH I
I I
1001 I NW I
I HH I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I 00 I
I H H I
I H H I
I I
I I
I I
I I
I I
I I
I I
I N N I
I NW I
I >>
I I
I I
I I
cc 0 I
I H H I
I I
I 00 I
I 3W I I HH I
I I
I N N I
I I
I NN I
I I
I I
I 00 I
I
I I
I I
I I
I I '
I I
'
I I 00 I
I I
I I
10 I
H I
I I
I I
10 I
CD I I
0 I00 I 0 0 I 00 I 0) 1 I
El I I-E-E N
DN ID 0
+
+
I 1
-1 M
I I
I In I
I
)
31 1-4 Wr 0i IN0 0 I) 00 I 0 0 I 00 I 00L m
00 O00 U
L IEH H W100
-i N I HH
-I N-W I N 04104 InHH I H Io m
I00 I 0 0
0 0
-41 0
C, 0
N4 Hý NC 00 00 I
U U 0014 ll -IB NN 00 H
H NW NW p N N a43 a I H I 00C I)0 U.)m IC0 C) C) 00 00
ý 00 C I 0) I 00 1 0 1
L)u I I
51I 00101 r r I I1 a
I Iý P
I I
I m I Io 001 00!
00 I
00 I 001 LI LI I 0U 00 NW N N cccc cIN N I 00 I cc 00 I 0 00 I 0 00u I 0
00I 0 00 E
I 0 IN WN I Ný HH I+
N' N IN Lr U.)
ID0 00 I) 0
+D I
00 I 0 001 Hý H I
N4 NI 0 0I I
I 00 I
0 0 I
00 1 00 I
L)U I u I
N ID 00I 00q1 001 N N I N N0I I7 I
ZN I~ N 1
HH I H H MW I NW HH I H
+110 N N IND
-41 01 0
I 0
I 01 01 i-4I 01 01 F 0 I
NI I
I I
I I
I I
I I
I I
I 131 WI NI I
I 101 NI HI I
I NI I NI HI I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I NI I 0 I
I 0 I
I II I
I I
I I
I I
I I
I NI NI I>'
I I
I I
I Cl I I
H I
I I
101 131 HI I
I IN I
I I
NI I
I 101 IClI H
I I
I I
I I
I I H I
I Cl I
I 0 I
I I
I I
IN' I N I H 10 I 0 U) 4-)
0 0
I 0
H LI H
H 4
LI 01 0I 0
I 01 01 cc
,.-)
N ko 01 WI HI E-4 0
E-
- 0. I
,--1 01 Q H
01 N I E.
I NI 04 Ho I co CN 0
0 I
c 0
1 01 0- I 0
I 04I HI 04 NI NI 001 00 00 00 OO0 000)
NW z
0 H
0 H
0 0
N 0
0ý Cl N
H I-I a)
C 0
N N
0 0
u 3
to N
oC4C
+
N I0 MMNNNN NW NNNNW 00:I00000 ND I
00 I 0000 I 00 0 0 C 0
I 00000 I 00000U I 4 H
-H 4 -g IgC C C CgC
44 0
N
- 0)
- 0.
(
03 tool
- 0° 4N z
.. U 0
H
ý44 o -0 too H.o ro0) en L. u
-9 to C9 to r3I 0
0 ID 0 1I 0000 C
IC 0ý 11 0000 N, II to to to to 1I 0 00 0
(9 II -9 i-u 9
4 L) II 0000i 14c HE 00 EH 4
-4 11EII E
0 4 0 I to I co OD H;I E-4I L0 N;I Zi 01 NI M
I 04 04 HI1 03,4 04 0
4 0 4 to I
04 NI HI 0ý I
en 0a4 000 1 0 4 0 00040!
0 to to I
0000 0000 0 0 C)
C000D 000D k 04
- 0)
I z
u a.l to
-9 04 04
- N eIr op P &I El en en en 0o00 0 0 0 N OUN:
0W00W 0l 0l a to to 0 4 -4 000 CC)
S0)
E El 0 4 N
,N IH xli C14 N4 0
03 4 0 co uv N I N 0oC40 T4w N ION
-44 1-4 0
u to 00 L
I CD 0M
- 0.
0 001 a4 0 00Q0 14 F 4 4 19-4-9 00 1 0000 N N I N N N N E-HH
ý HHHH 00 1 0000 00 Q
QI r 0 00 CA 0000v enen I N-N1r 00 4
000 N Nm N N1 N1 N C
I Ný C;C; 03W o0t 3
03 N'
N N N m
l 0 4 0 1 0 I to 4o II)
I N 04 M
I C40 0
M I
10 I
co 140 I 0 Ito C40 40 10 04 C0 4 00
)uu I to to;
[--i C1 4 00 Ifn en o W I NO rI HH 4'x 00 I NN IoH 000 000 4
CN N0N I
I 4 4-94-9 I 4 00 4
4 00 4
4 00 4
I to to I
I I
I I
I I
I I
4 00 4
4 4-94-9 4 4 00 4
4 00 4
I I
I I
I I
I I
4 001 4 4 44 I
I I
I I
I I
I I
I I
I I
I I
I I
I 4
4 I
I I
I I
I I
I 4004 I ON I
I HH I
I I
4 00 4
000 Eý Eý Eý E4 E00 E
I I +
to tN to N N en to to N r- (:D *-I c3c) c 0
0 0
I 0I Lo to I
oI Q a 040 4 NN 040D 04100 I
NO I HH E
N I kD w Co C; 00 toN 0D CD C) :D i D 4
00 C4 00 00 E4 00 I
00 4 004 U
LI E E-I E
IE 0404 C~
4 004 cl 4 00 4 E E-I P
I NN4 Il a)-1-4--4 -4 ID I
N M
I o I OD C) CD 00 0 ID to to 00 NC1O
, HH I
I.
4 N N 04 00 4N 00 1 00 1 0 H p
4 l94 104 p04 p04 Ito I I
I I
I HI 404 404 I
I I
I I
I I
I 4-44 I
I I
I I
I I
I I
I I
I I
I 4
4 I
I I
I 404 404 404 I
I I
I 404 IN' HI I
I 404 404 H I I
I I
I 4
4 I
I I 0 4 404
.4 404 I
I I
I I
I I N I 404 I>
I I
I I
I I 0 I 4-44 4
4 404 404 HI IN I
I I
IN I
I I
I I
IN I
I 03 4 I
I I
I Ito I
I en I
I 404 I
I I
I NI 4 -44 I
I 404 4 0 4
04 0ý 4 to I
HI 04 04
-4 0M 4.)
H H
0" H
4 04 0 040 D
40 N
I en 040I E040E 040o 040C 0; 1 03 0
<D 00 04100 0400 0
No tr4t 04 00 0400
+
OO N I N) 0 a4 00 4 4 ++i IL L0 400 N I r-en,e 9-
-I-4 0'4 001,
N I No en N N en II00Ma,00 II0000C 110000 N
II 00r00 II 0000 C
IIHH CC) NN z 0 0
H 6p 0
0 O
-9 H
H (D
0 0
0 I 0 000 0 I 000012 0
10000 u-U U L) U o'
1000 0
0 0
0- 1 000 0
+
I
+00 t.9 4 C14 C4 EN I E03P3E303 04 0000 14N 0ý I Ný in, N N I n w CA toM M3 CD-4-In 0
C4300 0 M4 0
0 HIN-
-44 M'
ne 0D 1 000 en 0
N N
N cN 0D to, 0
-4 a) 0D H-I 04 CD HI NDI
-ý4 0
en N
04 a) to 0)
) (D N..N w0
.4 0)1 O 0 coul 00 en
'I-)
v r4 (30 4 :U)
C U) to to C-)
0 to 40 0
I 01 P2 ii 04 4 N I
E-11I EH.I HEl 0
I HEI 4-I to to to to to I
00000 1
E-4 E4 H H H I
0'Cl tom'3)0)r 0lC C
+0+0I0+
N en en N) M 000 N'
I 000 1
0O U) U) 00 I
H ý H
HH I
0000 00 I
0 0
1 00 1
-3/4-) I 00 00o HoHo 00' 00 1
00D 00 1
00 to t toto 0t0 001 00 H
H) Ien n
Io I~n tow H H H
)U
-I EI E I E++E I- 00C N
0 I0 H
H P HEH NI N I* N0N to to I
ID 00P I
00 IN O NU en: T to H.'
,-4,-H 0o 10t -
I ID I t I
I L
I I
14)1w I
0ý I 0ý E-H I
Cý I I,
I
- )
w Itoý H
C14 Ito H
.+.
I-O
,-0 10 IN 00o 00o 00 I
14 to UU I
U0 00 1
00 HE'E I HE' 0000 0000 to to to to HHHH 0000 U
I I
I-E I
) U m a)
I D I
I l I1 Iw V
I I;
00 C i 0 i 0) 0 00 0
I 01 UU01 0U HE' E 00I 00x 0000 10000 I oN to N I to 0 to 0 100 Oo -
noo I0000 I Hý H; H H
I 000 enI 01 HIc
.4.C) I C3/4) 00100 00 I00 toi to Im tot 001 00 N
N I
N) N HE' I HE' t w I 00 OI 0
004 I
00 C N1 N I
0 I
I I I
I 001 NN 00Oý171 04 0014 04 0
00 I
N 1 3 H+ I 0 N
I 00C 0 0 t
to 00 00 U
L 00 N
N H E' HE' en en N1 N i-.,-4 00 00 N N 0404 U) U)
I 00 IN Ito z0 HE-'
U0 tww
+ 0 INN E 0 I
00 ko INN I n0 c n 001 00I kD ko I
HE H0E-P 001 00I
'0 0~
H U)
H U)
HO 04 O
0 0
E-4 H
H u
W 04 co
.-I 0
0 I--,
0 H
0 S>
H to 0
C)
- g. g 0
I0 toI to
,1 O
I 010 w
It "to I 0
0ý I 0ý OI~
01 10 N
IN N I to I U 00 I
Ir I
00 I
00 001 N N H-H 00 C 00 0)0 E" E" E00 I
Iý tot I
00 I
++
I mm N CA I
00 oCC) to w HE' 00 00
+ +
00 PI tok I N N N
N LO r
a)
>1, H
0)
N1 N I I 0"0o 0404 ru00 en e co 4 00L 0-01 HE' to to I
I en N H
Hn 00 404 N
N C' 0U)
I Ig C.) C>
C)
I ko o 100 O 0 00 x
uu IU I
H' El I P00 c0 00 to to OO 00 UL) x 0
LO O 100 I
0
-I tot I HE I H 00001 to to to to 00001 wotwtw wi en o en to
+
I I
I >I IU') N U') N D 0000 0
ao
44 o
In 0
o n O CO O'D
.0) w0
.Z 00 9
to 0 0
(.)
(a0 Fi4.4 H 0:
C-4L 0
I 00 0.4 Ito0t PD 1I HD H w
II 00 E-,
H 11U
.-1 I H
1 331 H
I0t) x 11 00 0
11 H Hl I-i-4.
I 00 C
I 00 E
1 00 IOW I 00 I In I to H
,.q 0
x LO 0
3 0
3 3
t) w 04 Ný
-41 p 0D I ko I 101 I to I
1 I4 1
I II I 0 I
I4 ioi 1WE' C13
+
04 1O 1W 0
H 10 H
IN H
H o+
oW 10
-4.C) I 00 I
I I
I HHu I 1 3W I
I P
I I
I I
I I
00 I
I co m I I
I)
I 0 IEl 00 I HH I
00 00 I N a,4 a, 00 L
00 040
- 00)
In)I
- 0) I 0) I a)
I 0) I El q
0 I
1 0 I 0 SI I
- 0) I I
co I r 0I N
I
- 10o 0l I >
HIH10 0
I 01 I a 0
I 0
I 0ý I to 00 It)
I 0ý 13 E-i It) 10 H
I,l 10 I
0 04 0
04 NY 0
0:
N-1014 I 0I I 0 I to o
It)ý I
(13 N
oo 10 It) 10
'H 1-i o0 H
10 1 01 I to I I u I
w I
I I
I.
CC) u I,.I IDI
'Ell I
I CN 0
,-4 0
0 0
to 0
4 0
0 0
13z co 10 C10 H
1r 4
104 H
I"0 IC)
- 0)
I 0
1 0
o (1) n DI IDa 0)0 I 00 I 0 00 I 00- I 0l p00 I 00 I 0 1I C
I I
1 l I E4p I E
I I
u u I
I W
I4 1
IW I El E-2 I E-'Hý I H I C I
c)o I
>I I
>>Io I I I
.I ID I'
I cI Io 1110 O
IO to I
I I 0 0
I I
I0I I -cc-I (D.-
0 I 00 1001 I 00 I1 0
I00 I 00I I to to Ito o I
I I uu I
I 4 IWW I ElH IE-E I
I I 00 C
I C I.Th4 I1 HH I
00100 I
>0>
I o Io 0)
I E
I E I
00 I
00 00 00 C
to to 3
0 3
W 0
H
- 0.
E-a, a,
H
- 0) 0, 0
H N,
04 H
00'1 3W.ý'
I 0
C.) I 00 1
00 I
to to) I 00 In In I
HE-I 001 00I 00 IgI N N HH I 00 I
H H en en 00 to
- 0 I In In I I m m I
I I
I UuI
+
+
MI 00 Q 0 cN 0 i
H Ii HH 10 I HH I --
I.
I '
I' 1I41I I
I r-I I
P' I 0 IO0 I 0 I +
00 0u tu 00 ID 00C en In 00 00 00 E'4(E, 04 0W CNN 00n 00 0
0 0
LO t0 3
In w
0-I n 2.- ID I
I c0 I 0 I
I 00C I 0) I I 00 I 0 I
I L) tO I t I
I I L
) I I
IN I El.E-I HE I 1O 10 I
E I E I
I, I 00H 0 I I
I I
04 0
I 4 I4 P I n I
I H I
I I
Il I
I) C I
CI I )
I r
I I
CD 0
0 0
k001 to to I 00 I
WW I tOtO to rI 4 I I
4 m 11+c 1
I I
" -II II I
"22 4J U) 0 02 Hn 0
0I:::
0- I O
01 P31 014 C14 CD f.,q 1-1 HI 00 1
00 I
to to 00 I 00I 00,I 00O In n to I HI
-i3 0
13 0
0 E
Co4 H
10 Lo 0
00 I
to to I Ut) 0"0 I
00n Cý -ý 00 I I N N CNH 00
- 040 HNN H-, H, I 0
-I n In 00L I U0 P
wHH I wHH WW I p W E00E I E00E HHO HH 3
0 0
H 4
0 0
'.9 U) 3 H
U) 0 3
-C.) I 00 I
u uI 00 I
I u u I 00 I
w w-I 00 I
I>
W,3 I,
N N 00 IL C> 0 No NW mW In HD H 00 33DI In 3
>9 I-04 0O N
en to 0
H4 C) 0 I
+ +I HD H I
040C4I 00I H
Hf H I
00 I enCnD N N PIIP NH H H, tDll 00 N N to t N
0 U')
a)
L2 CC) ou 0
w
- 0.
-4 0 o U) 4.J~
U 0 o U)
'-I 00(L CC)21 C.
C00Z 00 k
C) 0ý 0
14 II 0 C
II0000 II0000 E-E E-HH 11 0000 E E I
E-4 I00 W w' I E-EH CD0C 00 k 00I noI 140W E-E- I 1 C14 I1 IUco ) I I
Iý C
I 0000 I0 0000 I0 I H 000010L En En En En I E'I ODUu)0c)
CD O
C ;
I Cs) 0w C14 C1 Co (I
C CN N Nl NI Nq N1 1 N I N no4 i4 040 P
H3 C\\ Ch I)1 ko cr 0 N-I uO r- 00 u.) i 0000 C C
I C; N
IN o
10
- 1.
Iq4 to I E-I 0I LO C
I Hý I CD E1-1 C00 C00 ID kD 0o 0
u 0
00 0
00 H-EI E-'
0 00 H I r-ko I HI 0I E-4 04 1 0I I0 1 C')I C; I 01 H I 00 I 00I IDw t 0)C)000 0
00 0
wC w o wat 00 i00 i0 i0 UU )
U U1u1 U
en (Y) 00 N N1 Ut-)
co E-H C0 C) 0 E-)
m E-'
C-)
0
-4 C00C 00 to t HE-E 00 HE-E C) C m
C00 m m E-HE LI) ý
-4 H m (1n Cl C
-o z
I co r-1 E.4 Cr)
'-4' MO I
I I
I I
I w w) kD HE-E CN C14 to Cu Hl 4
00 00 00C wD to 0000a C 0000 (
C ko o oL ppI HPHHd 00 I0000 zz Ix===
Lfl Li) LO u)
M n M (n
e EH E-H EH "d
m "~ m
+
1+
'- C4
('-4 c,4 N N N (Ni it) (NJ U) CN c,4 to el Wo C')
0 o a 00 00 UL) L CD C'J (N00 0Cs) 00
-4 H -4 0
0 z
- 0) m 00 D I; I Y
Y H4 H~ I* N (N 04J I CN Cq m HO IH Hi Lo) LI) 00 c) c)
I cD (
c)Ic co OD 1N N
.Hi H N 0 0404 0
0 m flU Inm LO I dý dý Oý Cý I 0000 ICA N N N' Iý E-'EP4EH I N (N Nl "N 1 040C C'J 0
1 0C)000D
-IN H
1lz IC)
I 0)
I0 0 0 I 00 00 I00 I 00 Cs)
C; Cr) 0 I 0; Im co00 NczqL 00 00 HC) rIs-I C
- I x
I I
IA N
N I)
I Iq 00 I
I; I
I Cs)
U4 E-i H
00 C14 E-'
Cý 0
00 I0000 Iuu
=I
'.ý I 'C W kC W I H.4 -.-4 I d 0 I s' EHP I HE-E I PHE IPPE-E I
I I
E:I U
u I
I00 I
E.
E-I E-E I HEl PE-4 C-)
u' 0l 0
o eN m ID cq dq 0q CN C; Cr)
H HH 000 SnC)N'
-4 z" ii 10)I H 11 U I4 oII4 1-4 a) 0 ca 0
4-4 0
U) 0 U'
'4 m
0 OU 0 -)
0 0 E U)
ND 00 (a0 (dU)
- 0:3 r00 w
0 U.)
C4 4
A
'CI 04 N
A Hý H-ko o 00 1100 1100 II E I H 00I1 ko "o I I 0000 I 0000 k 10000 I LA LA LA LA I HHHH E E Ia) cc) U) U)
I 0000 c c 1+
+
I000 I1 N U N U)
IH Ho H-- H IN N I U)
C;C I e Fq AA 1 00 I 00c I 00 I HHF 100 w100 I00 I HH 100 IN N I 00 o
I 0 A
0 0
0 U) 0 0
E-,
In 13P N
0:
CAAC 00 00w AAAAA C C 00000 00000 k k A) 0 U) 0
'C 0l N
C H
I 00001 U) U) U) U)
U) c) U) CA
+00 I U) Nq N U)
U): U) U) U)I m -W
.4 CD 0I C)I 01 C;I 041 U) I DD
ýo o O00 00 U U H E-'
00
+ +
00 o00 co HE HE-E U-)
C14 PP4+
00 U) U 00 I 0 I 0ý E)
-1 I Vý I n 10-I.CA k
IOU' I 00 E
00 I HH E
+ +
-I 0 0'
,1 CN C1 I HE IV) U) LO I 00 I cI IN cxl C14 1-4 IH,'
I n N2 I E*
I 04 1
I ) 1')
I U) H OO 0
Il0 I N VV I
C') C') I 00 I 00 EE-EH I E-H 00100 LA)
Lo LA u-)
e e H
Iý HHýHH IN -4 U) W ILA LA LA)
LA I H;CýC HH I HHHHH 00 100000 H
H
'U u a) U U3)
U) c:{ O3 0404 I
I N N 040P oa-v CNN
'.4O 00 HH N N I HH I I 0 I
00 IW V V VIV VW I e e e e e W (4W
)
Iý NýHHF I
0:uu I HHHHHý C C ID 0 U 0 U) >
I C)U
) U) N IN 0404000r I U)4 N1 U)N 0*
C IO 0000>cl In 0
m I
ý N NN I 00000D C C IC4 00 coo 000 k,-W 000 LA)
Lo LA H-,E.,E.
- 0) im I +I I N
N
,1-1 cl ý C4 N
'NN HH 0
C) 0 U
1'4 E.
u' 0'
A C
- 0
- 0 4
U U) 0 I
o H
H H
0000 u)
U) U) 00C) o00 U) U) U) U) 0000 U) U) V) m) en H 0 ND N NN A)AC I 001 00 I U) U) I UA I
00 I NC I NN I
- 1 00 Il ci I 4
N N4 00
I 00 k
U) E) I U) 11 00 100 I01 100 D
VEV H H E
'CU)- INNm HHC C
I HH C
I I M a 0
IN N1 I 00i I 1 a I c o
I00 In NN I00 I 00 0
I O
0I" U 11 CN N4 0
- 11.
0 I)
I dP
-4H 0 II 0 H II H Hl 0 11IxI N II, 00 U) 11 E.
0 11 i-i i
H II 00 O
II 0 H II In A. II H 0o
'I04
$4 01 Ol 0
,2 0
I 0000 Ol I 0000 0
I0000 EH I H-H H H
OI EN I ENN-ENE HýI HHHH C c
+o I 000 N
1 I
N ECU N* IC0 0 0A 0 01 I N1 N1 N4 N N ILA )
r-Go o i o
0000r ri r, oo HI HHHHý ND ID ND N NI NNN HH E
I HHp I HHp Lo LA IC) (n
'IT H4 H I 0 00m ene If In I V; C')
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 27 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 114 120 0.25 148 P 2 TWD 15 VH2
-0.91 TEC TEH 16 HOT 600UL 0.24 156 P 2 TWD 15 VH2
-0.91 TEC TEH 16 HOT 600UL 114 130 0.40 101 P 2 TWD 16 09H
-0.89 TEC TEH 34 HOT 600UL 0.40 101 P 2 TWD 16 09H
-0.89 TEC TEH 34 HOT 600UL 114 132 0.84 143 P 2 TWD 29 07H
+0.74 TEC TEH 35 HOT 600UL 0.84 142 P 2 TWD 29 07H
+0.74 TEC TEH 35 HOT 600UL 114 140 0.93 112 P 2 TWD 30 VH2
-0.85 TEC TEH 34 HOT 60OUL 0.93 112 P 2 TWD 30 VH2
-0.85 TEC TEH 34 HOT 60OUL 0.87 112 P 2 TWD 27 VH2
-0.85 TEH TEC 49 COLD 60OUL 115 45 0.66 130 P 2 TWD 24 VHI
-0.99 TEH TEC 30 COLD 60OUL 0.66 130 P 2 TWD 24 VH1
-0.99 TEH TEC 30 COLD 600UL 115. 127.
- 0. 39.....
141.....P...
2 TWO.....15....09......+0.64.......TEC.....TEN.....
15....
NOT.............
115 127 0.39 141 P 2 TWD 15 09H
+0.64 TEC TEH 15 HOT 600UL 0.37 144 P 2 TWD 15 09H
+0.64 TEC TEH 15 HOT 600UL 115 129 0.30 140 P 2 TWD 12 09H
-0.89 TEC TEH 15 HOT 600UL 0.30 145 P 2 TWD 12 09H
-0.89 TEC TEH 15 HOT 600UL 115 133 0.43 51 P 2 TWD 17 VH2
+0.69 TEC TEH NEW 34 HOT 600UL 116 88 0.46 168 P 2 TWD 18 VHI
-1.23 TEC TEH NEW 3
HOT 600UL 116 110 0.59 105 P 2 TWD 22 VH1
-1.25 TEC TEH NEW 9
HOT 600UL 116 124 0.39 115 P 2 TWD 14 09H
+0.68 TEC TEH 15 HOT 600UL 0.42 79 P 2 TWD 16 08H
+0.83 TEC TEH 15 HOT 600UL 0.29 159 P 2 TWD 12 08H
+0.38 TEC TEH 15 HOT 600UL 0.42 79 P 2 TWD 16 08H
+0.83 TEC TEH 15 HOT 600UL 0.21 152 P 2 TWD 8 08H
+0.38 TEC TEH 15 HOT 60OUL 0.39 115 P 2 TWD 14 09H
+0.68 TEC TEH 15 HOT 60OUL 116 126 0.29 29 P 2 TWD 17 VH2
-1.10 TEC TEH 16 HOT 600UL 0.23 151 P 2 TWD 15 08H
+0.93 TEC TEH 16 HOT 600UL 0.30 36 P 2 TWD 18 VH2
-1.10 TEC TEH 16 HOT 600UL 0.23 152 P 2 TWD 14 08H
+0.93 TEC TEH 16 HOT 600UL 116 128 0.38 121 P 2 TWD 21 09H
+0.76 TEC TEH 16 HOT 600UL 0.31 112 P 2 TWD 18 08H
+0.92 TEC TEH 16 HOT 600UL 0.22 39 P 2 TWD 14 09H
-1.18 TEC TEH 16 HOT 600UL 0.39 113 P 2 TWD 21 09H
+0.76 TEC TEH 16 HOT 600UL 0.21 26 P 2 TWD 13 09H
-1.18 TEC TEH 16 HOT 600UL 0.31 114 P 2 TWD 18 08H
+0.92 TEC TEH 16 HOT 600UL 117 55 0.42 70 P 2 TWD 16 VC1
+0.74 TEH TEC NEW 5
COLD 600UL 117 123 0.67 104 P 2 TWD 22 08H
+0.85 TEC TEH 15 HOT 600UL 0.66 108 P 2 TWD 22 08H
+0.85 TEC TEH 15 HOT 600UL 117 129 0.26 113 P 2 TWD 16 08H
+0.97 TEC TEH 16 HOT 600UL 0.26 113 P 2 TWD 16 08H
+0.97 TEC TEH 16 HOT 600UL 118 46 0.41 97 P 2 TWD 17 VH1
-0.89 TEH TEC 29 COLD 600UL 0.20 142 P 2 TWD 10 VH1
+0.85 TEH TEC 29 COLD 600UL 0.40 95 P 2 TWD 17 VH1
-0.89 TEH TEC 29 COLD 600UL 0.21 132 P 2 TWD 10 VH1
+0.85 TEH TEC 29 COLD 600UL 118 54 0.29 137 P 2 TWD 13 VH2
-0.91 TEC TEH 23 HOT 60OUL 0.27 141 P 2 TWD 13 VH2
-0.91 TEC TEH 23 HOT 60OUL 0.62 29 P 2 TWD 24 VH1
-0.83 TEC TEH NEW 23 HOT 60OUL 118 58 0.45 30 P 2 TWD 18 VH2
+0.89 TEH TEC NEW 3
COLD 60OUL 118 60 0.45 46 P 2 TWD 18 VH1
-0.90 TEH TEC 3
COLD 600UL 0.34 68 P 2 TWD 14 VH2
-0.83 TEH TEC 3
COLD 600UL 0.40 59 P 2 TWD 16 VH1
-0.90 TEH TEC 3
COLD 60OUL 0.29 67 P 2 TWD 12 VH2
-0.83 TEH TEC 3
COLD 600UL 118 100 0.58 92 P 2 TWD 28 VH1
-0.72 TEC TEH 6
HOT 600UL 0.58 92 P 2 TWD 28 VH1
-0.72 TEC TEH 6
HOT 600UL 119 57 0.30 87 2
SAI TSH
+6.16 TSH TSH 0.0 8.59 57 HOT 580PP
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name: SONGS Unit 3 Component: S/G 89 Page 28 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 119 123 0.57 99 P 2 TWD 27 09H
+0.76 TEC TEH 16 HOT 60OUL 0.57 99 P 2 TWD 27 09H
+0.76 TEC TEH 16 HOT 600UL 119 125 0.26 127 P 2 TWD 10 09H
+0.06 TEC TEH 15 HOT 60OUL 0.35 157 P 2 TWD 14 09H
-0.98 TEC TEH 15 HOT 60OUL 0.39 150 P 2 TWD 15 09H
-0.98 TEC TEH 15 HOT 60OUL 0.25 112 P 2 TWD 11 09H
+0.06 TEC TEH 15 HOT 600UL 119 139 0.62 134 P 2 TWD 24 10C
-1.25 TEC TEH 35 HOT 60OUL 0.62 134 P 2 TWD 24 10C
-1.25 TEC TEH LOCOK 35 HOT 600UL 120 76 0.38 142 P 2 TWO 18 VH1
-0.79 TEH TEC NEW 6
COLD 600UL 0.35 122 P 2 TWO 17 VH2
-0.84 TEH TEC NEW 6
COLD 600UL 120 80 0.26 42 P 2 TWD 11 DBH
+1.37 TEC TEH 3
HOT 600UL 0.26 42 P 2 TWD 11 DBH
+1.37 TEC TEH 3
HOT 600UL 120 92 0.71 153 P 2 TWD 23 VH1
-0.86 TEC TEH 5
HOT 600UL 0.42 116 P 2 TWD 14 VH1
+0.80 TEC TEH 5
HOT 600UL 0.90 134 P 2 TWD 28 VH1
-0.86 TEC TEH 5
HOT 600UL 0.42 117 P 2 TWD 16 VH1
+0.80 TEC TEH 5
HOT 600UL 120 112 0.28 143 P 2 TWD 13 10H
+1.27 TEC TEH LOCOK 9
HOT 600UL 0.28 143 P 2 TWD 13 10H
+1.24 TEC TEH 9
HOT 600UL 120 134 0.33 127 P 2 TWD 14 VH1
-1.00 TEC TEH NEW 34 HOT 60OUL 121 113 0.33 121 P 2 TWD 21 VH1
-1.02 TEC TEH 10 HOT 600UL 0.33 121 P 2 TWD 21 VHI
-1.02 TEC TEH 10 HOT 60OUL 121 119 0.44 96 P 2 TWD 23 10H
+0.02 TEC TEH 16 HOT 60OUL 0.31 158 P 2 TWD 18 09H
-0.69 TEC TEH 16 HOT 60OUL 0.39 138 P 2 TWO 21 08H
+0.80 TEC TEH 16 HOT 60OUL 0.77 115 P 2 TWD 32 08H
+0.30 TEC TEH 16 HOT 600UL 0.87 101 P 2 TWD 27 08H
+0.30 TEH TEC 49 COLD 60OUL 0.55 108 P 2 TWD 19 08H
+0.80 TEH TEC 49 COLD 600UL 0.34 99 P 2 TWD 13 09H
-0.69 TEH TEC 49 COLD 60OUL 0.58 85 P 2 TWD 20 10H
+0.02 TEH TEC 49 COLD 60OUL 0.57 64 P 2 TWD 27 10H
+0.02 TEC TEH 16 HOT 600UL 0.31 156 P 2 TWD 18 09H
-0.69 TEC TEH 16 HOT 600UL 0.39 138 P 2 TWD 21 08H
+0.80 TEC TEH 16 HOT 600UL 0.77 115 P 2 TWD 32 08H
+0.30 TEC TEH 16 HOT 600UL 121 121 0.40 51 P 2 TWD 22 09H
+0.43 TEC TEH 16 HOT 600UL 0.42 130 P 2 TWD 22 10H
-0 19 TEC TEH 16 HOT 600UL 0.43 125 P 2 TWD 23 10H
-0.19 TEC TEH 16 HOT 600UL 0.41 50 P 2 TWD 22 09H
+0.43 TEC TEH 16 HOT 600UL 122 50 0.27 104 P 2 TWD 13 08C
+0.93 TEC TEH NEW 23 HOT 600UL 122 72 0.36 149 P 2 TWD 16 VH1
-1.03 TEH TEC 1
COLD 60OUL 0.37 149 P 2 TWD 16 VH1
-1.03 TEN TEC 1
COLD 600UL 122 78 0.33 143 P 2 TWD 18 VHI
-0.83 TEC TEH 4
HOT 600UL 0.33 143 P 2 TWD 18 VH1
-0.83 TEC TEH 4
HOT 600UL 122 86 0.18 121 P 2 TWO 11 DBH
+0.17 TEC TEH 4
HOT 600UL 0.18 122 P 2 TWD 10 DBH
+0.17 TEC TEH 4
HOT 600UL 122 112 0.44 103 P 2 TWD 25 10H
+0.50 TEC TEH 10 HOT 600UL 0.44 103 P 2 TWD 23 10H
+0.50 TEC TEH 10 HOT 600UL 122 120 0.36 140 P 2 TWD 14 08H
-0.84 TEC TEH 15 HOT 600UL 0.34 49 P 2 TWD 14 08H
+0.45 TEC TEH 15 HOT 60OUL 0.36 145 P 2 TWD 14 08H
-0.84 TEC TEH 15 HOT 600UL 0.35 48 P 2 TWD 14 08H
+0.45 TEC TEH 15 HOT 600UL 122 122 0.48 124 P 2 TWD 17 10C
+0.85 TEC TEH 15 HOT 60OUL 0.48 124 P 2 TWD 18 10C
+0.85 TEC TEH 15 HOT 600UL 122 124 0.29 159 P 2 TWD 17 VH2
-0.76 TEC TEH 16 HOT 600UL 0.28 160 P 2 TWD 17 VH2
-0.76 TEC TEH 16 HOT 60OUL 123 115 0.29 58 P 2 TWD II 09H
+0.42 TEC TEH 15 HOT 600UL
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name: SONGS Unit 3 Component: S/G 89 Page 29 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.29 58 P 2 TWO 12 09H
+0.42 TEC TEE 15 HOT 600UL 123 117 0.53 125 P 2 TWO 19 09H
-0.62 TEC TEH 15 HOT 600UL 0.55 123 P 2 TWD 19 09H
-0.62 TEC TEH 15 HOT 600UL 123 119 0.53 88 P 2 TWD 19 09H
+0.49 TEC TEH 15 HOT 60OUL 0.18 37 P 2 TWO 6 09H
-0.13 TEC TEH 15 HOT 600UL 0.53 88 P 2 TWO 19 09H
+0.49 TEC TEH 15 HOT 600UL 0.21 42 P 2 TWO 8 09H
-0.13 TEC TEH 15 HOT 60OUL 123 131 0.34 131 P 2 TWD 14 VH2
-1.13 TEC TEH NEW 34 HOT 600UL 124 58 0.42 117 P 2 TWD 16 VH1
-0.85 TEH TEC 3
COLD 60OUL 0.38 95 P 2 TWD 15 VH1
+0.79 TEH TEC 3
COLD 60OUL 0.40 91 P 2 TWD 16 VHI
-0.85 TEH TEC 3
COLD 600UL 0.38 49 P 2 TWD 16 VH1
+0.79 TEH TEC 3
COLD 600UL 0.38 62 P 2 TWD 16 VH2
-0.81 TEH TEC NEW 3
COLD 600UL 124 78 0.34 153 P 2 TWD 15 VHI
-1.08 TEC TEH 3
HOT 600UL 0.34 154 P 2 TWD 14 VHI
-1.08 TEC TEH 3
HOT 600UL 124 114 0.25 161 P 2 TWD 11 05H
+0.76 TEC TEH 9
HOT 60OUL 124 116 0.35 98 P 2 TWO 14 09H
+0.11 TEC TEH 15 HOT 600UL 0.35 94 P 2 TWO 14 09H
+0.11 TEC TEH 15 HOT 600UL 0.30 31 P 2 TWO 11 10H
-1.23 TEC TEH 15 HOT 600UL 0.53 97 P 2 TWO 19 08H
+0.85 TEC TEH 15 HOT 600UL 0.53 97 P 2 TWD 19 08H
+0.85 TEC TEH 15 HOT 60OUL 0.30 31 P 2 TWO 11 10H
-1.23 TEC TEH 15 HOT 600UL S.........................................................................................................
124 126 0.27 98 P 2 TWD 11 VH2
-0.98 TEC TEH 15 HOT 60OUL 0.33 115 P 2 TWD 13 VH1
-1.04 TEC TEH 15 HOT 60OUL 0.45 130 P 2 TWD 17 VH1
-1.04 TEC TEH 15 HOT 60OUL 0.44 96 P 2 TWD 16 VH2
-0.98 TEC TEH 15 HOT 600UL 125 57 0.46 126 P 2 TWO 20 VHI
+0.72 TEC TEH 23 HOT 600UL 0.69 118 P 2 TWO 26 VHI
-0.91 TEC TEH 23 HOT 60OUL 0.69 118 P 2 TWO 26 VHI
-0.91 TEC TEH 23 HOT 600UL 0.45 129 P 2 TWO 20 VHI
+0.72 TEC TEH 23 HOT 60OUL 125 65 0.37 155 P 2 TWD 16 VHI
+0.73 TEH TEC NEW 2
COLD 600UL 125 117 0.29 153 P 2 TWD 17 08H
+0.76 TEC TEH 16 HOT 600UL 0.31 154 P 2 TWD 18 08H
+0.76 TEC TEH 16 HOT 600UL 1 2 6. 5 6.
- 0. 3 0..
1 3 5.....
P 2
TW O.
- 14.
VH 1.
+1.0 8.
TE C.
TE E.
- 23....
H O T..............
126 56 0.30 135 P 2 TWD 14 VHI
+1.08 TEC TEH 23 HOT 600UL 0.30 135 P 2 TWD 14 VHI
+1.08 TEC TEH 23 HOT 600UL 126 62 0.41 39 P 2 TWD 18 VHI
-0.75 TEH TEC 1
COLD 600UL 0.40 45 P 2 TWD 17 VHI
-0.75 TEH TEC 1
COLD 600UL 126 64 0.93 117 P 2 TWD 31 VHI
-1.04 TEH TEC 1
COLD 600UL 0.96 115 P 2 TWD 31 VHI
-1.04 TEC TEH 23 HOT 600UL 0.93 119 P 2 TWD 31 VHI
-1.04 TEH TEC 1
COLD 600UL 126 78 0.37 139 P 2 TWO 19 VHl
-0.82 TEC TEH 4
HOT 600UL 0.89 57 P 2 TWO 34 VHI
+0.99 TEC TEH 4
HOT 600UL 0.43 122 P 2 TWD 16 VHI
-0.82 TEH TEC 47 COLD 600UL 1.00 41 P 2 TWD 29 VHI
+0.99 TEH TEC 47 COLD 600UL 126 84 0.29 70 P 2 TWD 17 VH2
-0.96 TEC TEH 4
HOT 60OUL 0.28 153 P 2 TWO 16 VHI
+0.86 TEC TEH 4
HOT 60OUL 0.28 152 P 2 TWO 16 VHI
+0.86 TEC TEH 4
HOT 60OUL 0.29 70 P 2 TWO 16 VH2
-0.96 TEC TEH 4
HOT 600UL 7
126 86 0.33 143 P 2 TWO 18 VHI
-1.00 TEC TEH 4
HOT 600UL 0.30 120 P 2 TWO 17 VHI
+0.98 TEC TEH 4
HOT 600UL 0.30 122 P 2 TWD 17 VHI
+0.98 TEC TEH 4
HOT 600UL 0.33 143 P 2 TWD 18 VHI
-1.00 TEC TEH 4
HOT 600UL 126 96 0.35 80 P 2 TWD 20 VH2
-1.05 TEC TEH 6
HOT 60OUL 0.27 26 P 2 TWD 17 VH2
-1.05 TEC TEH 6
HOT 600UL 126 98 0.55 128 P 2 TWO 27 VHI
-1.19 TEC TEH 6
HOT 600UL 6
HOT 600UL 0.45 125 P 2 TWO 24 VH2
-1.13 TEC TEH
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 30 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.47 123 P 2 TWD 25 VH2
-1.13 TEC TEH 6
HOT 600UL 0.55 129 P 2 TWD 27 VH1
-1.19 TEC TEH 6
HOT 600UL S.........................................................................................................
126 104 0.38 65 P 2 TWD 23 VH2
-0.96 TEC TEH 10 HOT 600UL 0.51 62 P 2 TWD 28 VH2
-0.96 TEC TEH 10 HOT 600UL S.........................................................................................................
126 108 0.33 145 P 2 TWD 21 VH2
-1.00 TEC TEH 10 HOT 600UL 0.53 92 P 2 TWD 28 10H
+0.02 TEC TEH 10 HOT 60OUL 0.42 138 P 2 TWD 25 VH1
-1.24 TEC TEH 10 HOT 600UL 0.27 47 P 2 TWD 18 VH2
-1.00 TEC TEH 10 HOT 600UL 0.53 92 P 2 TWD 28 10H
+0.02 TEC TEH 10 HOT 600UL 0.46 146 P 2 TWD 24 VH1
-1.24 TEC TEH 10 HOT 60OUL S.........................................................................................................
126 112 0.65 138 P 2 TWD 32 10H
+0.98 TEC TEH 10 HOT 60OUL 0.27 144 P 2 TWD 18 09H
-0.39 TEC TEH 10 HOT 60OUL 0.32 42 P 2 TWD 21 08H
-0.59 TEC TEH 10 HOT 60OUL 0.27 144 P 2 TWD 18 09H
-0.39 TEC TEH 10 HOT 600UL 0.32 42 P 2 TWD 21 08H
-0.59 TEC TEH 10 HOT 60OUL 0.78 136 P 2 TWD 32 10H
+0.98 TEC TEH 10 HOT 600UL 0.32 33 P 2 TWD 12 08H
-0.59 TEH TEC 49 COLD 60OUL 0.30 124 P 2 TWD 11 09H
-0.39 TEH TEC 49 COLD 600UL 0.84 105 P 2 TWD 26 10H
+0.98 TEN TEC 49 COLD 60OUL S.........................................................................................................
126 114 0.34 125 P 2 TWD 19 08H
+0.89 TEC TEH 10 HOT 60OUL 0.34 141 P 2 TWD 19 08H
+0.89 TEC TEH 10 HOT 60OUL S.........................................................................................................
126 122 0.24 81 P 2 TWD 15 VH2
-1.02 TEC TEH 16 HOT 600UL 0.41 112 P 2 TWD 22 VH1
-0.93 TEC TEH 16 HOT 600UL 0.30 33 P 2 TWD 18 VH2
-1.02 TEC TEH 16 HOT 600UL 0.40 112 P 2 TWD 22 VHI
-0.93 TEC TEH 16 HOT 600UL S.........................................................................................................
126 124 0.16 78 P 2 TWD 11 VH2
-1.17 TEC TEH 16 HOT 600UL 0.25 61 P 2 TWD 15 VH1
-1.22 TEC TEH 16 HOT 600UL 0.16 61 P 2 TWD 11 VH2
-1.17 TEC TEH 16 HOT 600UL 0.23 45 P 2 TWD 15 VH1
-1.22 TEC TEH 16 HOT 600UL 126. 132..
35.. 45.p.2. TWO. 16. VN2.-0.......
92.......TEC........
TEN.........35......NOT.....................
126 132 0.35 45 P 2 TWD 16 VH2
-0.92 TEC TEH 35 HOT 600UL 0.35 45 P 2 TWD 15 VH2
-0.92 TEC TEH 35 HOT 600UL S.........................................................................................................
127 51 0.35 28 P 2 TWD 16 DBH
-1.40 TEC TEH NEW 23 HOT 600UL S.........................................................................................................
127 61 0.38 110 P 2 TWD 17 10H
+0.43 TEH TEC 1
COLD 600UL 0.47 114 P 2 TWD 19 10H
+0.43 TEH TEC 1
COLD 600UL S.........................................................................................................
127 63 0.40 115 P 2 TWD 17 VHI
+1.02 TEH TEC I
COLD 600UL 0 28 101 P 2 TWD 13 VH1
-0.68 TEH TEC 1
COLD 600UL 0.28 106 P 2 TWD 12 VH1
-0.68 TEH TEC 1
COLD 600UL 0.41 118 P 2 TWD 17 VH1
+1.02 TEH TEC 1
COLD 600UL S.........................................................................................................
127 65 0.52 143 P 2 TWD 21 VH1
+0.77 TEH TEC NEW 1
COLD 600UL S.........................................................................................................
127 67 0.33 118 P 2 TWD 15 VH1
+0.11 TEH TEC 1
COLD 600UL 0.38 113 P 2 TWD 16 VH1
+0.11 TEH TEC 1
COLD 600UL S.........................................................................................................
127 69 0.40 105 P 2 TWD 17 VHI
-0.92 TEH TEC 1
COLD 600UL 0.35 126 P 2 TWD 15 VHl
-0.92 TEH TEC 1
COLD 600UL S.........................................................................................................
127 79 0.76 129 P 2 TWD 26 VHI
+0.88 TEC TEH 3
HOT 600UL 0.76 132 P 2 TWD 26 VHI
+0.88 TEC TEH 3
HOT 600UL 127. 85.
- 0. 69.. 151.p.2. TWO..
24.V.1.-0.....
85.......TEC.........TEN.........3.....NOT......................
127 85 0.69 151 P 2 TWD 24 VH1
-0.85 TEC TEH 3
HOT 60OUL 0.69 151 P 2 TWD 24 VHI
-0.85 TEC TEH 3
HOT 600UL S.........................................................................................................
127 101 0.29 161 P 2 TWD 12 VHI
-0.76 TEC TEH 5
HOT 60OUL 0.37 157 P 2 TWD 15 VHI
-0.76 TEC TEH 5
HOT 60OUL S.........................................................................................................
127 111 0.52 101 P 2 TWD 21 10H
+0.21 TEC TEH 9
HOT 600UL 0.53 103 P 2 TWD 21 09H
-0.23 TEC TEH 9
HOT 600UL 0.52 101 P 2 TWD 21 10H
+0.21 TEC TEH 9
HOT 60OUL 0.53 103 P 2 TWD 21 09H
-0.23 TEC TEH 9
HOT 600UL S.........................................................................................................
127 113 0.37 91 P 2 TWD 15 08H
+0.83 TEC TEH 9
HOT 600UL 0.31 147 P 2 TWD 13 09H
-0.87 TEC TEH 9
HOT 600UL 0.44 118 P 2 TWD 18 09H
-0.87 TEC TEH 9
HOT 60OUL 0.36 79 P 2 TWD 15 08H
+0.83 TEC TEH 9
HOT 600UL
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name: SONGS Unit 3 Component: S/G 89 Page 31 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 127 115 0.36 154 P 2 TWD 14 08H
+0.70 TEC TEH 15 HOT 600UL 0.37 80 P 2 TWD 15 08H
-0.56 TEC TEH 15 HOT 600UL 0.37 80 P 2 TWO 14 08H
-0.56 TEC TEH 15 HOT 600UL 0.35 158 P 2 TWO 13 08H
+0.70 TEC TEH 15 HOT 600UL 128 62 0.41 133 P 2 TWO 18 VN2
-0.86 TEN TEC 2
COLD 600UL 0.41 133 P 2 TWO 18 VH2
-0.86 TEH TEC 2
COLD 600UL 128 72 0.55 71 P 2 TWO 22 VH2
-0.86 TEH TEC 2
COLD 600UL 0.55 66 P 2 TWO 22 VH2
-0.86 TEH TEC 2
COLD 600UL 0.52 78 P 2 TWO 21 VHI
-0.82 TEH TEC NEW 2
COLD 600UL 128 76 0.44 143 P 2 TWO 19 VHI
+0.81 TEN TEC 6
COLO 600UL 0.44 146 P 2 TWO 20 VHI
+0.81 TEH TEC 6
COLD 600UL 128 80 0.93 136 P 2 TWO 29 VHI
-0.83 TEC TEH 3
HOT 600UL 0.58 94 P 2 TWO 21 VH1
+0.87 TEC TEH 3
HOT 600UL 0.58 94 P 2 TWO 21 VHI
+0.87 TEC TEH 3
HOT 60OUL 0.95 135 P 2 TWO 29 VH1
-0.83 TEC TEH 3
HOT 60OUL 128 88 0.61 150 P 2 TWO 22 VH1
-0.90 TEC TEH NEW 3
HOT 600UL 128 90 0.68 129 P 2 TWO 24 VN1
-0.96 TEC TEN 3
NOT 600UL 0.69 134 P 2 TWO 24 VH1
-0.96 TEC TEH 3
HOT 60OUL 128 110 0.33 124 P 2 TWO 14 10H
+0.64 TEC TEH 9
HOT 600UL 0.36 106 P 2 TWD 16 VH2
-0.89 TEC TEH 9
HOT 600UL 0.26 152 P 2 TWO 12 10H
-0.73 TEC TEH 9
HOT 600UL 0.39 117 P 2 TWO 17 VH2
-0.89 TEC TEH 9
HOT 600UL 0.33 120 P 2 TWO 14 10H
+0.64 TEC TEH 9
HOT 600UL 0.26 152 P 2 TWO 12 10H
-0.73 TEC TEH 9
HOT 600UL 128 116 0.37 134 P 2 TWD 14 09C
+0.95 TEC TEH 15 HOT 600UL 0.38 130 P 2 TWO 15 VHI
+0.74 TEC TEH 15 HOT 600UL 0.36 144 P 2 TWD 14 09C
+0.95 TEC TEH 15 HOT 600UL 0.38 139 P 2 TWD 15 VHI
+0.74 TEC TEH 15 HOT 600UL 129 61 0.25 66 P 2 TWO 12 VN1
-0.65 TEN TEC 2
COLD 6000L 0.25 66 P 2 TWD 12 VHI
-0.65 TEH TEC 2
COLD 600UL 129 63 0.50 81 P 2 TWO 20 VH1
+0.92 TEH TEC 2
COLD 600UL 0.37 125 P 2 TWO 16 10H
+0.43 TEH TEC 2
COLD 600UL 0.50 81 P 2 TWO 20 VH1
+0.92 TEH TEC 2
COLD 600UL 0.37 125 P 2 TWO 16 10H
+0.43 TEH TEC 2
COLD 60OUL 129 79 0.27 160 P 2 TWO 15 VN1
+0.73 TEC TEN 4
NOT 600UL 0.27 160 P 2 TWO 15 VH1
+0.73 TEC TEH 4
HOT 600UL 129 105 0.50 150 P 2 TWO 27 VH1
+0.74 TEC TEH 10 HOT 600UL 0.50 150 P 2 TWO 25 VH1
+0.74 TEC TEH 10 HOT 600UL 129 111 0.35 145 P 2 TWO 19 09H
-0.80 TEC TEH 10 HOT 60OUL 0.28 136 P 2 TWO 16 09H
+0.48 TEC TEH 10 HOT 60OUL 0.27 129 P 2 TWO 18 09H
+0.48 TEC TEH 10 HOT 60OUL 0.31 156 P 2 TWO 20 09H
-0.80 TEC TEH 10 HOT 600UL 130 54 0.18 16 P 2 TWO 9 DBH
+1.11 TEC TEH NEW 23 HOT 600UL 130 56 0.33 147 P 2 TWO 15 VH1
-0.74 TEC TEH NEW 23 HOT 600UL 130 60 0.41 126 P 2 TWO 18 VH2
+0.63 TEC TEH NEW 23 HOT 600UL 130 62 0.70 110 P 2 TWO 26 VH1
+0.89 TEH TEC 1
COLD 600UL 0.69 118 P 2 TWO 25 VH1
+0.89 TEH TEC 1
COLD 600UL 130 66 0.32 77 P 2 TWO 14 08C
+0.87 TEH TEC NEW 1
COLD 600UL 0.48 86 P 2 TWO 19 VHI
+0.75 TEH TEC NEW 1
COLD 600UL 130 68 0.54 112 P 2 TWD 22 VHI
+0.75 TEH TEC 1
COLD 600UL 0.55 113 P 2 TWO 22 VH1
+0.75 TEH TEC 1
COLD 600UL 0.22 134 P 2 TWD 9 DBH
-0.04 TEH TEC NEW 1
COLD 600UL 130 72 0.49 98 P 2 TWO 20 VHI 0.48 98 P 2 TWD 20 VHI
+0.90 TEH TEC
+0.90 TEH TEC 1
COLD 60OUL I
COLD 600UL
N 0
00 I
kD 00O 00 (D C)
)00 00 00 I,
I, OO im i)
I I4 HH I4 H1 I-P 0000 1001 00 00 I) 0)
I)
=
I u
Eý N
E.
x4 0
N 00.I 0 0-0-
I NN IN IE HH*] I H
I-IB I 4-4-4 E
100000 I HHHHI I
>0>0>
I0) -4)0 -4 rI 0000 1
I 0 N 00 I000 Im33 I
HH ko o 0o0 00 I H>
I N1 N I
004 I
00 00 NO 0
I N,
.4 4 4 4-.
0000 0000 0 0 00 0000 w 00 C
00o C0 00 00 I
0
ýD en en ID 000D k I 0D EH H
H E I H 0000 0
(4 NoC1 NN I No HHHH C C I Hý I
I++
N 01 N Nl 0 ci0 NC N N0 C
04 P I ++
Iý I I4 No 0 ND N-W
,-41NN*-4 4
1 N I N a0 -0 0
I
-44D IC' N
40 000 I 0D 0001 0
oom r
1-4 I en) 133 HHE-H IH 00 I Cl 0004 c I -4 I+
0001 0
00 I0 (M0 N N
+
+)
W.3 '
001¢ oN
-00 NN CN N
)00
++)
r N N I4 W HH CD C 00 0 0 00 a 00 ko rII 0
H>
10 00 I 0010 xm*
= IV U
00 00 LD L 00 00 000 000 0
- 0) 0) 000 t~
0 0 C) C) 0000 0000 0000C C 0000 ý k
kD tD 0
I 0
I
+
ena i31 04 0',
00C:
00 00
%oDW 00 HH 00 w E° 00 H H CNN I I 4
)00 0: o N N4 00 E
00C 00
-14 E.3 E4l I En en ION I I H
CC)00 I NN 0-4 C-.
IL 00 I 'N N I
0 I I I
,4 en en enm N I II 0001 NNN I1 HHH I4P 000 ID NNN In I
H 0000 E E en en en en 0000W NNNNF E HHHH mOZ V04 V~
040 00 c H00 I0 VT 0V I) a 4 1000
'333 ImHH rINNNN I
I I
I I
I
.4.4 I.4.41 00 1001 00 I 00 I'
00 I 00 I'
00 I 00 I'
I I
I I
I I
I I
I I
HH I HH I
00 I 001 00 I 00 I
I I
I I
I I
I I
N N I N N I
en en I en en I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I 00 I
IN N Ienl enl I 00 I NN I CA I NN cI HHc I 00 LO I
IP P4 04 I 00 CD I 4 I
H Io I 40 00 C)00 00 00 N1 N 4
en n NN I ENNr H H I-HH I
I I ++
0N N
N I -4
> >I>
00 IO en NA N N I N N NI N NA In I n 0 N I) N c *1 1
0104 00 1001C)00 00 I
I 00 I 00w 00 00 IO0 00 100 IO0 00C CDCD
ýo I' 00*
oD 0o I
I I
0 C
I l EH I HH I HH I HH I -4 00100 00 10010
=0 1
0
=0
10=
010I N N IN N en en mene HH I
HH P4 N-a-4-43 Ný rI --
I4 014 en4 1 H -
HHE i EHHH i HHHHp i HHp 00:000:0000:00!
-1 E
..l I CO c4 I>
N I 00 4 00 I00 I I NN I* P w100 100 a)
I 1-4 r
I 00 oo>
10o IoI 100 I
m 0I I4 I1 I-4 Iý I
Il 0I In I
I1 I
CD CD CDI C)I I N N rIN N I EN P
H UI 00
+W+
gC)C ool E ci 00 INN I00 00 m
00 o
"N 0
0 eoU 4-J u0 (40 4-4 (a0 ro )
00)ý:
u0 41 0
0 0
H H
H 0
En)
En uI z
0" H
I 0
I E-1 0
I 4I H
II UO 10,I
>i I
H 0:
0I)
C 0
3 N
0 0
N H
E-4 N
0 I
-14 0
El 3
I 0
Cý 0
N 04 n
I0 I0
Framatome ANP Inc.
01/26/03 10:20:56 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 33 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 132 104 0.46 94 P 2 TWD 17 VHI
-0.91 TEH TEC 49 COLD 60OUL 0.47 83 P 2 TWD 17 VHI
-0.91 TEH TEC 49 COLD 600UL 132 106 0.56 132 P 2 TWD 20 VH2
-0.64 TEH TEC 49 COLD 600UL 0.56 132 P 2 TWD 20 VH2
-0.64 TEH TEC 49 COLD 600UL 132 108 0.57 110 P 2 TWD 20 VHI
-0.79 TEH TEC NEW 49 COLD 600UL 132 110 0.46 128 P 2 TWD 17 VH2
-0.80 TEH TEC 49 COLD 600UL 0 34 67 P 2 TWD 13 08H
+0.82 TEH TEC 49 COLD 600UL 0.46 108 P 2 TWD 17 VHI
-0.77 TEH TEC 49 COLD 600UL 0.34 67 P 2 TWD 13 08H
+0.82 TEH TEC 49 COLD 600UL 0.46 108 P 2 TWD 17 VHI
-0.77 TEH TEC 49 COLD 600UL 0.46 128 P 2 TWD 17 VH2
-0.80 TEH TEC' 49 COLD 60OUL S.........................................................................................................
132 112 0.31 150 P 2 TWD 12 VHI
-0.79 TEH TEC NEW 49 COLD 600UL 0.49 88 P 2 TWD 18 VH2
+0.00 TEH TEC NEW 49 COLD 600UL 132 116 0.50 143 P 2 TWD 18 DBC
+2.08 TEH TEC 49 COLD 600UL 0.50 143 P 2 TWD 18 DBC
+2.08 TEH TEC 49 COLD 600UL 133 53 0.49 118 P 2 TWD 23 DBH
+1.77 TEC TEH 37 HOT 60OUL 0.48 134 P 2 TWD 23 DBH
+1.77 TEC TEH 37 HOT 60OUL 133 65 0.21 52 P 2 TWD 11 DBH
+1.20 TEC TEH NEW 37 HOT 600UL 133 89 0.33 150 P 2 TWD 17 VH2
-0.86 TEC TEH 33 HOT 600UL 0.28 161 P 2 TWD 15 VH2
-0.86 TEC TEH 33 HOT 600UL 133 93 0.18 89 P 2 TWD 8 VHI
-0.98 TEC TEH 32 HOT 600UL 0.22 122 P 2 TWD 9 VHI
-0.98 TEC TEH 32 HOT 600UL 133 95 0.37 157 P 2 TWD 15 VHI
+0.82 TEC TEH 32 HOT 600UL 0.37 148 P 2 TWD 14 VHI
+0.82 TEC TEH 32 HOT 60OUL 133 101 0.28 165 P 2 TWD 16 VHl
+0.76 TEC TEH 33 HOT 60OUL 0.18 170 P 2 TWD 10 VHt
+0.76 TEC TEH 33 HOT 600UL 133 103 0.53 117 P 2 TWD 19 08H
+0.86 TEH TEC 49 COLD 600UL 0.36 132 P 2 TWD 14 VHI
-0.80 TEH TEC 49 COLD 60OUL 0.53 117 P 2 TWD 19 08H
+0.86 TEH TEC 49 COLD 60OUL 0.36 132 P 2 TWD 14 VHI
-0.80 TEH TEC 49 COLD 60OUL 133 107 0.32 123 P 2 TWD 15 09H
+0.85 TEH TEC 50 COLD 600UL 0.18 151 P 2 TWD 9 09H
-0.83 TEH TEC 50 COLD 600UL 0.18 151 P 2 TWD 9 09H
-0.83 TEH TEC 50 COLD 600UL 0.32 123 P 2 TWD 15 09H
+0.85 TEH TEC 50 COLD 600UL 134 56 0.35 155 P 2 TWD 18 DBC
+0.93 TEC TEH NEW 37 HOT 600UL 134 68 0.34 153 P 2 TWD 17 VHI
-0.82 TEC TEH 37 HOT 600UL 0.45 132 P 2 TWD 22 10H
-0.84 TEC TEH 37 HOT 600UL 0.45 132 P 2 TWD 22 10H
-0.84 TEC TEH 37 HOT 600UL 0.36 122 P 2 TWD 19 VHI
-0.82 TEC TEH 37 HOT 600UL 134 74 0.44 107 P 2 TWD 21 VH2
-0.90 TEC TEH 37 HOT 600UL 0.59 40 P 2 TWD 26 VH1
-0.82 TEC TEH 37 HOT 600UL 0.41 101 P 2 TWD 20 VH2
-0.90 TEC TEH 37 HOT 600UL 0.31 35 P 2 TWD 17 VHI
-0.82 TEC TEH 37 HOT 600UL 134 80 0.20 156 P 2 TWD 12 VHI
+0.72 TEC TEH 33 HOT 600UL 0.40 154 P 2 TWD 20 VHI
-0.78 TEC TEH 33 HOT 60OUL 0.17 153 P 2 TWD 10 VHI
+0.72 TEC TEH 33 HOT 600UL 0.32 162 P 2 TWD 17 VHI
-0.78 TEC TEH 33 HOT 600UL 134 84 0.34 149 P 2 TWD 18 VHI
-0.95 TEC TEH 33 HOT 600UL 0.34 149 P 2 TWD 18 VHI
-0.95 TEC TEH 33 HOT 600UL 134 88 0.33 85 P 2 TWD 17 10H
+0.02 TEC TEH 33 HOT 600UL 0.33 84 P 2 TWD 17 10H
+0.02 TEC TEH 33 HOT 600UL 134 90 0.34 154 P 2 TWD 18 VHI
-1.01 TEC TEH 33 HOT 600UL 0.32 151 P 2 TWD 17 VH2
-0.90 TEC TEH 33 HOT 600UL 0.26 160 P 2 TWD 14 VH2
-0.90 TEC TEH 33 HOT 600UL
Framatome ANP Inc.
Customer Name: SONGS Unit 3
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 01/26/03 10:20:56 Component: S/G 89 Page 34 of 37 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL #
0.29 109 P 2 TWD 16 VHI
-1.01 TEC TEE 33 LEG PROBE HOT 60OUL 134 96 0.60 142 P 2 TWO 26 VHI
-0.90 TEC TEN 33 HOT 600UL 0.48 151 P 2 TWD 22 VHI
-0.90 TEC TEN 33 HOT 600UL 134 102 0.47 111 P 2 TWD 19 VHI
-0.78 TEH TEC NEW 48 COLD 60OUL 0.42 122 P 2 TWD 17 VH2
-0.84 TEH TEC NEW 48 COLD 60OUL 134 104 0.32 147 P 2 TWD 15 VHI
-0.67 TEH TEC NEW 50 COLD 600UL 0.26 131 P 2 TWD 12 VH2
-0.84 TEE TEC NEW 50 COLD 600UL 134 108 0.28 41 P 2 TWD 14 10H
+0.96 TEE TEC 50 COLD 600UL 0.28 41 P 2 TWD 14 10H
+0.96 TEN TEC 50 COLD 60OUL 134 110 0.30 128 P 2 TWD 14 VH2
-0.79 TEH TEC 50 COLD 600UL 0.30 128 P 2 TWD 14 VH2
-0.79 TEE TEC 50 COLD 600UL 134 112 0.41 145 P 2 TWD 18 VHE
-0 67 TEE TEC 50 COLD 600UL 0.41 145 P 2 TWD 18 VH1
-0.67 TEN TEC 50 COLD 600UL 135 57 0.31 142 P 2 TWD 16 10H
+1.24 TEC TEE NEW 37 HOT 600UL 135 77 0.38 79 P 2 TWD 19 VHl
+0.82 TEC TEN 37 HOT 600UL 0.38 79 P 2 TWD 19 VHI
+0.82 TEC TEN 37 HOT 600UL 135 89 0.51 102 P 2 TWD 19 VH3
-0.92 TEC TEN 32 HOT 600UL 0.49 84 P 2 TWD 18 VH3
-0.92 TEC TEE 32 HOT 60OUL 135 95 0.45 143 P 2 TWD 17 VHI
-1.02 TEC TEE 32 HOT 600UL 0.46 141 P 2 TWD 17 VH1
-1.02 TEC TEE 32 HOT 600UL 135 117 0.35 29 P 2 TWD 16 08H
+0.34 TEE TEC 50 COLD 60OUL 0.35 29 P 2 TWD 16 08H
+0.34 TEE TEC 50 COLD 60OUL 0.33 159 P 2 TWD 15 DBC
+0.23 TEN TEC 50 COLD 600UL 0.33 159 P 2 TWD 15 DBC
+0.23 TEE TEC 50 COLD 600UL 136 58 0.19 161 P 2 TWD 9 DBH
+1.89 TEC TEE NEW 36 HOT 600UL 0.27 23 P 2 TWD 12 DBH
-1.86 TEC TEE NEW 36 HOT 600UL 136 68 0.35 110 P 2 TWD 15 VHI
-0.95 TEC TEE 36 HOT 600UL 0.35 110 P 2 TWD 15 VHI
-0.95 TEC TEE 36 HOT 600UL 136 74 0.43 78 P 2 TWD 18 VHl
+0.94 TEC TEH 36 HOT 600UL 0.43 78 P 2 TWD 18 VHI
+0.94 TEC TEH 36 HOT 600UL 136. 86.
- 0. 49.. 45.P.. 2. TWO. 18.. VE2.-1.....
04.......TEC........
TEE.........32......HOT.....................
136 86 0.49 45 P 2 TWD 18 VH2
-1.04 TEC TEE 32 HOT 600UL 0.47 44 P 2 TWD 17 VH2
-1.04 TEC TER 32 HOT 600UL 136 90 0.63 65 P 2 TWD 22 VHl
+0.70 TEC TEN 32 HOT 600UL 0.45 74 P 2 TWD 17 VH2
+0.82 TEC TEE 32 HOT 600UL 0.43 53 P 2 TWD 16 VH2
+0.82 TEC TEE 32 HOT 600UL 0.61 46 P 2 TWD 21 VHI
+0.70 TEC TEE 32 HOT 600UL 136 92 0.50 141 P 2 TWD 18 VHE
-1.13 TEC TEE 32 HOT 600UL 0.50 141 P 2 TWD 18 VHI
-1.13 TEC TEE 32 HOT 600UL 136 94 0.36 73 P 2 TWD 19 VHl
-0.98 TEC TEE 33 HOT 600UL 0.34 55 P 2 TWD 18 VHI
-0.98 TEC TEE 33 HOT 60OUL 136 114 0.49 45 P 2 TWD 18 DBC
+1.18 TEE TEC 49 COLD 600UL 0.49 45 P 2 TWD 18 DBC
+1.18 TEE TEC 49 COLD 600UL 137 59 0.10 11 P 2 TWD 5 DBC
+1.65 TEC TEE 37 HOT 600UL 0.40 149 P 2 TWD 20 DBC
+1.65 TEC TEH 37 HOT 600UL 137 79 0.32 125 P 2 TWD 17 09H
-0.91 TEC TEE 33 HOT 600UL 0.32 126 P 2 TWD 17 09H
-0.91 TEC TEE 33 HOT 600UL 137 81 0.35 42 P 2 TWD 18 08H
+0.89 TEC TEE 33 HOT 600UL 0.35 42 P 2 TWD 18 08H
+0.89 TEC TEE 33 HOT 60OUL 137 83 0.41 52 P 2 TWD 20 09H
+0.76 TEC TEE 33 HOT 60OUL 0.55 60 P 2 TWD 25 09H
+0.76 TEC TEE 33 HOT 60OUL 137 91 0.32 164 P 2 TWD 17 VHI
+0.80 TEC TEE 33 HOT 60OUL
Framatome ANP Inc.
01/26/03 10:20:57 Customer Name:
SONGS Unit 3 Component: S/G 89 Page 35 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.55 108 P 2 TWD 25 09H
+0.80 TEC TEH 33 HOT 60OUL 0.32 164 P 2 TWD 17 VHI
+0.80 TEC TEH 33 HOT 600UL 0.52 114 P 2 TWD 24 09H
+0.80 TEC TEH 33 HOT 60OUL 137 115 0.35 52 P 2 TWD 16 VH2
-0.86 TEH TEC 50 COLD 60OUL 0.35 52 P 2 TWD 16 VH2
-0.86 TEH TEC 50 COLD 60OUL 138 76 0.33 139 P 2 TWO 17 10H
+0.65 TEC TEH 37 HOT 600UL 0.33 139 P 2 TWD 17 10H
+0.65 TEC TEH 37 HOT 600UL 138 84 0.21 115 P 2 TWD 12 VH2
-0.93 TEC TEH 33 HOT 60OUL 0.23 150 P 2 TWD 13 VH1
-0.91 TEC TEH 33 HOT 600UL 0.20 152 P 2 TWD 11 VH2
-0.93 TEC TEH 33 HOT 60OUL 0.19 142 P 2 TWD 11 VHI
-0.91 TEC TEH 33 HOT 600UL 138 88 0.37 135 P 2 TWD 19 VHI
-0.86 TEC TEH 33 HOT 600UL 0.27 152 P 2 TWD 15 VHI
-0.86 TEC TEH 33 HOT 60OUL 138 100 0.34 133 P 2 TWD 18 VHI
-0.90 TEC TEH 33 HOT 60OUL 0.28 82 P 2 TWD 15 VH1
-0.90 TEC TEH 33 HOT 60OUL 138 102 0.41 85 P 2 TWD 17 VHI
-0.84 TEH TEC NEW 48 COLD 600UL 0.37 146 P 2 TWD 16 VH2
-0.88 TEH TEC NEW 48 COLD 600UL 138 104 0.37 153 P 2 TWD 17 VH2
-0.80 TEH TEC 50 COLD 600UL 0.45 119 P 2 TWD 19 VH1
-0.73 TEH TEC 50 COLD 60OUL 0.22 102 P 2 TWD 11 VHl
-0.19 TEH TEC 50 COLD 600UL 0.45 119 P 2 TWD 19 VH1
-0.73 TEH TEC 50 COLD 60OUL 0.22 102 P 2 TWD 11 VH1
-0.19 TEH TEC 50 COLD 60OUL 0.37 153 P 2 TWO 17 VH2
-0.80 TEH TEC 50 COLD 600UL 138. 108..
24....
151.....P 2
TWO.....12....V...2...-0.84.......TEN.....TEC.....
50....
COLD......
600UL...
138 108 0.24 151 P 2 TWO 12 VH2
-0.84 TEH TEC 50 COLD 600UL 0.24 150 P 2 TWO 12 VH2
-0.84 TEH TEC 50 COLD 600UL 138 110 0.35 88 P 2 TWD 16 VH2
-0.82 TEH TEC NEW 50 COLD 600UL 139 85 0.36 126 P 2 TWD 15 VH3
+0.94 TEC TEH 32 HOT 600UL 0.34 82 P 2 TWD 13 VH3
+0.94 TEC TEH 32 HOT 600UL 139 89 0.32 141 P 2 TWD 13 09H
+0.74 TEC TEH 32 HOT 600UL 0.19 51 P 2 TWD 8 09H
-0.90 TEC TEH 32 HOT 600UL 0.32 134 P 2 TWD 12 09H
+0.74 TEC TEH 32 HOT 600UL 0.19 51 P 2 TWD 8 09H
-0.90 TEC TEH 32 HOT 600UL 139 95 0.28 54 P 2 TWD 12 VHI
-1.03 TEC TEH 32 HOT 60OUL 0.28 65 P 2 TWD 11 VH1
-1.03 TEC TEH 32 HOT 60OUL 139 99 0.37 145 P 2 TWD 15 VH2
-0.84 TEC TEH 32 HOT 60OUL 0.36 116 P 2 TWD 14 VH2
-0.84 TEC TEH 32 HOT 600UL 140 64 0.44 70 P 2 TWD 21 DBH
-1.95 TEC TEH 37 HOT 60OUL 0.44 70 P 2 TWD 21 DBH
-1.95 TEC TEH 37 HOT 60OUL 140 86 0.48 141 P 2 TWD 18 VH2
-0.88 TEC TEH 32 HOT 600UL 0.48 123 P 2 TWD 18 VH2
-0.88 TEC TEH 32 HOT 60OUL 140 88 0.44 157 P 2 TWO 17 VH1
-0.90 TEC TEH 32 HOT 60OUL 0.48 139 P 2 TWD 18 VH1
-0.90 TEC TEH 32 HOT 60OUL 140 90 0.40 152 P 2 TWD 16 VH2
-0.82 TEC TEH 32 HOT 600UL 0.49 158 P 2 TWD 18 VHI
-0.86 TEC TEH 32 HOT 600UL 0.39 140 P 2 TWD 15 VH2
-0.82 TEC TEH 32 HOT 60OUL 0.61 132 P 2 TWD 21 VH1
-0 86 TEC TEH 32 HOT 600UL 140 94 0.46 130 P 2 TWD 22 VH1
-0.88 TEC TEH 33 HOT 600UL 0.40 145 P 2 TWD 20 VHI
-0.88 TEC TEH 33 HOT 600UL 140 102 0.38 94 P 2 TWD 16 VH2
-0.88 TEH TEC NEW 48 COLD 600UL 140 112 0.48 60 P 2 TWD 20 DBC
-1.84 TEH TEC 50 COLD 600UL 0.39 95 P 2 TWD 17 VHI
-0.80 TEH TEC 50 COLD 600UL 0.31 120 P 2 TWD 15 04H
+0.82 TEH TEC 50 COLD 60OUL 0.34 33 P 2 TWO 16 DBC
+1.97 TEH TEC 50 COLD 60OUL 0.39 95 P 2 TWD 17 VH1
-0.80 TEH TEC 50 COLD 60OUL 0.42 26 P 2 TWD 18 DBC
+1.97 TEH TEC 50 COLD 60OUL
Framatome ANP Inc.
01/26/03 10:20:57 Customer Name: SONGS Unit 3 Component: S/G 89 Page 36 of 37
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100% twd QUERY: QueryM3 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.48 60 P 2 TWD 20 DBC
-1.84 TEH TEC 50 COLD 60OUL 0.34 113 P 2 TWD 16 VH2
-0.75 TEH TEC NEW 50 COLD 60OUL S.........................................................................................................
141 67 0.27 152 P 2 TWD 14 VHI
-0.85 TEC TEH 37 HOT 600UL 0.18 44 P 2 TWD 10 DBC
-1.85 TEC TEH NEW 37 HOT 60OUL 0.30 65 P 2 TWD 16 VHI
-0.85 TEC TEH 37 HOT 600UL 141 99 0.27 45 P 2 TWD 15 DBH
+1.39 TEC TEH 33 HOT 600UL 0.24 100 P 2 TWD 13 VH1
+0.80 TEC TEH 33 HOT 600UL 0.24 119 P 2 TWD 13 VH1
+0.80 TEC TEH 33 HOT 600UL 0.27 48 P 2 TWD 15 DBH
+1.39 TEC TEH 33 HOT 600UL S.........................................................................................................
142 66 1.30 63 P 2 TWD 39 DBH
+1.96 TEC TEH 37 HOT 600UL 0.73 62 P 2 TWD 29 DBH
-1 66 TEC TEH 37 HOT 600UL 0.39 115 P 2 TWD 20 DBC
+1.76 TEC TEH NEW 37 HOT 600UL 1.54 56 P 2 TWD 36 DBH
+1.96 TEH TEC 47 COLD 600UL 0.72 71 P 2 TWD 24 DBH
-1.66 TEH TEC 47 COLD 600UL 0.27 62 P 2 TWD 11 DBC
+1.47 TEH TEC NEW 47 COLD 600UL 0.72 53 P 2 TWD 29 DBH
-1.66 TEC TEH 37 HOT 600UL 1.29 54 P 2 TWD 39 DBH
+1.96 TEC TEH 37 HOT 600UL S.........................................................................................................
142 78 0.42 150 P 2 TWD 21 VH2
-0.93 TEC TEH 33 HOT 600UL 0.37 105 P 2 TWD 19 VH1
-0.81 TEC TEH 33 HOT 600UL 0.40 150 P 2 TWD 20 VH2
-0.93 TEC TEH 33 HOT 600UL 0.30 151 P 2 TWD 16 VH1
-0.81 TEC TEH 33 HOT 600UL 142 84 0.29 111 P 2 TWD 15 VH2
-0.87 TEC TEH 33 HOT 60OUL 0.22 154 P 2 TWD 13 VH2
-0.87 TEC TEH 33 HOT 600UL 142. 88.
- 0. 38.....
144.....p...
2 TWO.....19....VH2.....-0.84.......TEC.....TEN.....
33....
NOT..............
142 88 0.38 144 P 2 TWD 19 VH2
-0.84 TEC TEH 33 HOT 60OUL 0.38 145 P 2 TWD 19 VH2
-0.84 TEC TEH 33 HOT 600UL 142. 100. 0. 55.....
123.....P...
2 TWO.....25....V...2...-0.82.......TEC.....TEN.....
33....
NOT.............
142 100 0.55 123 P 2 TWD 25 VH2
-0.82 TEC TEH 33 HOT 600UL 0.53 128 P 2 TWD 24 VH2
-0.82 TEC TEH 33 HOT 600UL 142 102 0.64 131 P 2 TWD 23 VH2
-0.82 TEH TEC 48 COLD 600UL 0.41 106 P 2 TWD 17 VH1
-0.86 TEH TEC 48 COLD 600UL 0.47 113 P 2 TWD 19 VH1
-0.86 TEH TEC 48 COLD 600UL 0.64 131 P 2 TWD 23 VH2
-0.82 TEH TEC 48 COLD 600UL 143 95 0.32 26 P 2 TWD 13 DBH
-1.32 TEC TEH NEW 32 HOT 600UL 143 103 0.52 78 P 2 TWD 19 VH1
-0.74 TEH TEC 49 COLD 600UL 0.52 78 P 2 TWD 19 VH1
-0.74 TEH TEC 49 COLD 600UL 144. 70.
- 0. 46... 87.. P.2..
TWO.. 22.. VC1...
+0. 44.......TEC........
TEN.........37......NOT.................UL..
144 70 0.46 87 P 2 TWD 22 VCI
+0.44 TEC TEH 37 HOT 600UL 0.46 58 P 2 TWD 22 VC1
+0.44 TEC TEH 37 HOT 60OUL S.........................................................................................................
144 72 0.37 57 P 2 TWD 19 DBH
+2.06 TEC TEH NEW 37 HOT 600UL 0.58 51 P 2 TWD 26 DBC
-1.75 TEC TEH 37 HOT 60OUL 0.55 56 P 2 TWD 25 DBC
-1.75 TEC TEH 37 HOT 600UL S.........................................................................................................
144 74 0.48 84 P 2 TWD 23 VH1
-0.93 TEC TEH 37 HOT 60OUL 0.53 56 P 2 TWD 24 DBH
+0.67 TEC TEH 37 HOT 60OUL 0.43 148 P 2 TWD 21 VH1
-0.93 TEC TEH 37 HOT 60OUL 0.49 60 P 2 TWD 23 DBH
+0.67 TEC TEH 37 HOT 600UL S.........................................................................................................
144 76 0.19 110 P 2 TWD 9 DBH
-1.98 TEC TEH NEW 36 HOT 600UL 144. 78.
- 0. 51.....
119.....P...
2 TWO.....19....DON.....-2.15.......TEC.....TEN.....
32....
NOT..............
144 78 0.51 119 P 2 TWD 19 DBH
-2.15 TEC TEH 32 HOT 600UL 0.52 117 P 2 TWD 19 DBH
-2.15 TEC TEH 32 HOT 60OUL S.........................................................................................................
144 80 0.35 134 P 2 TWD 14 VH1
-0.84 TEC TEH 32 HOT 60OUL 0.34 106 P 2 TWD 13 VH1
-0.84 TEC TEH 32 HOT 600UL 0.18 175 P 2 TWD 7 DBH
+1.52 TEC TEH NEW 32 HOT 600UL 144. 82.
- 0. 40.....
112.....P...
2 TWO.....15....VN2.....-0.88.......TEC.....TEN.....
32....
NOT..............
144 82 0.40 112 P 2 TWD 15 VH2
-0.88 TEC TEH 32 HOT 600UL 0.40 112 P 2 TWD 15 VH2
-0.88 TEC TEH 32 HOT 600UL S.........................................................................................................
144 84 0.51 66 P 2 TWD 24 VH3
+0.73 TEC TEH 33 HOT 600UL 0.44 106 P 2 TWD 21 VH3
+0.73 TEC TEH 33 HOT 600UL 144. 90.
- 0. 52.....
153.....p...
2 TWO.....19....VN2.....-0.86.......TEC.....TEN.....
32....
NOT...........UL 144 90 0.52 153 P 2 TWD 19 VH2
-0.86 TEC TEH 32 HOT 60OUL 0.52 145 P 2 TWD 19 VH2
-0.86 TEC TEH 32 HOT 600UL S.........................................................................................................
Framatome ANP Inc.
Customer Name: SONGS Unit 3 01/26/03 10:20:57 Component: S/G 89
- MAI, MCI,
- MMI, MVI, QUERY: QueryM3
- SAI, SCI,
- SVI, 0-100% twd ROW LINE VOLTS 144 94 0.40 0.33 0.18 DEG 136 156 51 CHN P 2 P 2 P 2 IND TWD TWD TWD
%TW 20 17 10 LOCATION VH2
-0.90 VH2
-0.90 DBH
+1.43 EXT TEC TEC TEC EXT TEH TEH TEH UTIL 1 UTIL 2 CAL #
33 33 NEW 33 LEG PROBE HOT 600UL HOT 600UL HOT 60OUL 144 96 0.68 139 P 2 TWD 28 VH2
-0.83 TEC TEH 33 HOT 60OUL 0.66 104 P 2 TWD 28 DBC
+1.58 TEC TEH 33 HOT 600UL 0.28 90 P 2 TWD 15 VH2
+0.91 TEC TEH 33 HOT 600UL 0.67 104 P 2 TWD 28 DBC
+1.58 TEC TEH 33 HOT 600UL 0.28 90 P 2 TWD 15 VH2
+0.91 TEC TEH 33 HOT 600UL 0.66 134 P 2 TWD 28 VH2
-0.83 TEC TEH 33 HOT 600UL 144 102 0.36 51 P 2 TWD 16 VH2
-0.91 TEH TEC 48 COLD 600UL 0.39 56 P 2 TWD 17 VH2
-0.91 TEH TEC 48 COLD 60OUL 144 106 0.53 84 P 2 TWD 22 DBH
-1.83 TEH TEC 50 COLD 600UL 0.22 103 P 2 TWD 11 DBC
-1.51 TEH TEC 50 COLD 60OUL 0.53 84 P 2 TWD 22 DBH
-1.83 TEH TEC 50 COLD 600UL 0.22 103 P 2 TWD 11 DBC
-1.51 TEH TEC 50 COLD 60OUL 145 73 0.26 58 P 2 TWD 14 DBH
+1.49 TEC TEH NEW 37 HOT 60OUL 145 79 0.18 95 P 2 TWO 10 DBH
-1.49 TEC TEN NEW 33 HOT 600UL 145 91 0.22 145 P 2 TWD 13 DBH
-1.40 TEC TEH NEW 33 HOT 60OUL 145 101 0.29 20 P 2 TWD 16 DBC
+2.03 TEC TEH NEW 33 HOT 60OUL 146 78 0.29 149 P 2 TWD 16 08H
+0.70 TEC TEH 33 HOT 600UL 0.52 89 P 6 TWD 25 DBH
+1.55 DBH DBH LAR 198 HOT 560FH 0.19 132 P 2 TWD 11 DBH
-1.71 TEC TEH NEW 33 HOT 600UL 0.29 149 P 2 TWD 16 08H
+0.70 TEC TEH 33 HOT 600UL 0.25 62 P 2 TWD 14 DBH
+1.53 TEC TEH NEW 33 HOT 600UL 146 82 0.68 100 P 2 TWO 28 DBH
+1.65 TEC TEN LOCOK 33 NOT 6000L 0.68 100 P 2 TWD 28 DBH
+1.65 TEC TEH 33 HOT 600UL 146 90 0.37 115 P 2 TWO 19 OBC
+1.44 TEC TEN 33 NOT 600UL 0.41 116 P 2 TWD 20 DBC
+1.44 TEC TEH 33 HOT 60OUL 146 92 0.27 73 P 2 TWD 15 DBH
+1.91 TEC TEH 33 HOT 600UL 0.39 126 P 2 TWD 20 VH2
-1.17 TEC TEH 33 HOT 600UL 0.39 128 P 2 TWO 20 VH2
-1.17 TEC TEN 33 HOT 600UL 0.30 66 P 2 TWD 16 DBH
+1.91 TEC TEH 33 HOT 600UL 146 94 0.48 30 P 2 TWD 23 DBC
+1.99 TEC TEH NEW 33 HOT 600UL 146 96 1.07 57 P 2 TWD 36 DBC
+1.19 TEC TEH 33 HOT 600UL 0.80 24 P 2 TWD 28 DBC
+1.19 TEH TEC 52 COLD 600UL 1.01 71 P 2 TWD 35 DBC
+1.19 TEC TEH 33 HOT 600UL Total Tubes
- 806 Total Records: 1869 Page 37 of 37