Susquehanna Learning Center

-'00 769 Salem Boulevard m,

Berwick, PA 18603-0467 570-542-3353 November 21, 2002 Mr. Alan Blarney USNRC Chief Examiner USNRC Region 1 475 Allendale Road King of Prussia, PA 19406-1415 Susquehanna Learning Center Examination Materials/References PLA 005562 File A14-13D

Dear Alan:

Enclosed are the Examination Materials for the Susquehanna Steam Electric Station Operator Examination scheduled for December 11, 2002. This information is being provided in accordance with NUREG 1021 Operating Examination Standards for Power Reactors, Rev 8, Supplement 1.

"* JPMs as per ES-301-2 Control Room Systems and Facility Walkthrough Test Outline

"* Applicable Procedure references which facilitate execution of the JPMs Susquehanna Steam Electric Station requests that the enclosed materials be withheld from public disclosure until after the December 2002 examination process is complete.

If you have any questions, please feel free to contact me at 570-542-3553.

Sincerely, Richard E. Chin Examination Coordinator

Response

No Enclosures cc:

W.W. Hunt J. M. Helsel Ops Letter File Nuc Records-Site Rcnrcexamoutlineletter5 REC/vah

PENNSYLVANIA POWER & LIGHT COMPANY JOB PERFORMANCE MEASURE APPROVAL AND ADMINISTRATIVE DATA SHEET 64.OP.004.103 JPM Number 0

Rev No.

11/18/02 Date 202002 A2.05 NUREG 1123 Sys. No.

Task

Title:

Reset Recirculation Pump Limiter #2 Runback lAW ON-164-002 Completed By:

Rich Chin Writer 11/18702 Date Reviews:

n4sructor/Writer Date AppRroval Requesting Supv.IC.A. Head Dae 2

Date Date Date of Performance:

20 Min Allowed Time (Min)

Time Taken (Min)

JPM Performed By:

First Employee #/S.S. #

Performance Evaluation:

) Satisfactory

) Unsatisfactory Evaluator Name:

Signature Comments:

STCP-QA-125A Rev. 2, (9/93)

Page 1 of 1 Typed or Printed File No. A14-5B S/RO Appl To 3.8/4.0 K/A Last M.I.

REQUIRED TASK INFORMATION JOB PERFORMANCE MEASURE S/RO 64.OP.004.103 SAFETY CONSIDERATIONS A.

All Operations personnel are responsible for maintaining their radiation exposure As Low As Reasonably Achievable in accordance with OP-AD-002, Standards for Shift Operations.

B.

All applicable safety precautions shall be taken in accordance with established PPL safety policies and the Safety Rule Book, for example:

1. Whenever any electrical panel is opened for inspection during JPM performance.
2. Whenever entering any plant area where specific safety equipment; such as hearing or eye protection, safety shoes, hardhats, etc; is required and/or posted as being necessary.

C.

If in the judgement of the evaluator any safety issue occurs during the performance of a JPM, the JPM will be terminated until the issue is resolved Il. REFERENCES ON-164-002, Loss Of Reactor Recirculation Flow II1.

REACTIVITY MANIPULATIONS This JPM satisfies the requirements of Reactivity Manipulation(s):

36 Reset recirc pump runback IV.

TASK CONDITIONS A.

The plant is in Mode 1.

B.

Rods 18-23, 18-39, 42-23, and 42-39, are fully inserted to support HCU maintenance on Rod 18-23 B.

A trip of CWP 1 D has caused a Reactor Recirculation runback to occur.

C.

NO Operator actions have been taken.

V.

INITIATING CUE Reset recirculation pump runback in accordance with appropriate Off Normal procedure.

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 64.OP.004.103 Student Name:

Step Action Standard Eval Comments Evaluator:

"* The FAULTED step in this JPM is preceded by a fault statement in BOLD TYPE WITH ALL CAPITAL LETTERS.

"* This JPM must be performed in the simulator.

"* Select IC 18 (100 percent).

"* FULLY INSERT THE FOLLOWING RODS:

Rods 18-23, 18-39, 42-23, and 42-39

"* Allow plant to stabilize

"* Insert the following preference file:

RESTOREPREF YPP.JPM95-3 DEPRESS PB-I TRG El RRE.1S12BRST PB-2 TRG El = IMF CN03:SYB31 1 R621 B 100

"* When ready, place simulator in RUN.

"* Trip (electrical fault) 1 D circ water pump.

IMF CW142002D

"* Ensure Reactor Recirc Pump B Limiter #2 runback has occurred prior to start of the JPM,

"* Silence all alarms and allow plant to stabilize.

(DO NOT PERFORM ANY OPERATOR ACTIONS)

  • Critical Step STCP-QA-1 25B Rev. 2 (9/93)

Page 1 of 1

  1. Critical Sequence Page 3 of 9

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 64.OP.004.103

  • Critical Step STCP-QA-1 25B Rev. 2 (9/93)

Page 1 of 1 Student Name:

  1. Critical Sequence Step Action Standard Eval Comments 1

Obtain a controlled copy of ON-164-002, Loss Of Controlled copy obtained.

Reactor Recirculation Flow 2

Selects the correct section to perform Selects section 3.4 3

Plot position on Power/Flow Map, Form NDAP-QA-Plots Power to flow and determines 0338-10.

NOT to be in Region 1 or 2 4

Perform appropriate action specified on Determines NO action required for Power/Flow Map.

current region 5

Determine which limiter initiated runback:

Verifies:

RX RECIRC LIMITER 1 RUNBK RESET HS-B31-1S15A(B) pushbutton Green light NOT LIT Limiter (#2) LOSS OF FW PP RUNBK RESET HS-B31-1S12A(B) pushbutton Green lights LIT Page 4 of 9

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 64.OP.004.103

  • Critical Step STCP-QA-1 25B Rev. 2 (9/93)

Page 1 of 1 Student Name:______________

  1. Critical Sequence Step Action Standard Eval Comments 6

Ensure both pumps have run back to value Verifies:

associated with controlling limiter.

Reactor Recirc Pump A SY-B31 -1 R621A controller AND Reactor Recirc Pump B SY-B31 -1 R621 B controller approximately 45%

7 Monitor neutron instrumentation for indication of Checks:

core instability.

Neutron instrumentation and IF required, Perform ON-178-002, Core Flux determines they are stable and Oscillations.

ON-178-002 is NOT required 8

On 1C600, Monitor the following:

Checks:

Main Steam Line Radiation Monitor, RR-D12-Main Steam Line Radiation 1 R603.

Monitor, RR-D12-1 R603.

Offgas Pretreatment Log Radiation Monitor, RR-AND D12-1R601.

Offgas Pretreatment Log Radiation Monitor, RR-D12-1 R601.

Evaluator:

It may be necessary to inform student that these trends are Normal since the recorder will not display a history trend for the JPM setup.

j Page 5 of 9

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 64.OP.004.103 Student Name:

Step I

Action Standard

[Eval 1 Comments 9

Determines

  • Critical Step STCP-QA-1 25B Rev. 2 (9/93)

Page 1 of 1

  1. Critical Sequence IF Main Steam Line Radiation Monitor or Offgas Pretreatment Log Radiation Monitor increases, Direct Chemistry to sample per CH-ON-003.

Observe following plant parameters WITHIN LIMITS corresponding to new power level:

a. Power to flow limits
b. Condenser vacuum
c. Feedwater flow/steam flow
d. RPV water level Determine signal that initiated runback Evaluator:

CWP 1 D trip was given in initial conditions Ensure REACTOR RECIRC PUMP A(B) SPEEDS SY-B31-1R621A(B) IN MANUAL.

10 11 12 Radiation Monitor, RR-D1 2-1 R603.

AND Offgas Pretreatment Log Radiation Monitor, RR-D1 2-1 R601.

NORMAL for this power level.

Checks:

Power to flow limits Condenser vacuum Feedwater flow/steam flow RPV water level And determines WITHIN LIMITS for the new power level Determines:

Limiter #2 (45%) runback initiated by Circulating Water Pump 1 D protective trip Checks:

the amber M (manual) lights on both of the following are LIT Reactor Recirc Pump A SY-B31-1 R621A Reactor Recirc Pump B SY-B31-1 R621 B Page 6 of 9

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 64.OP.004.103 Student Name:_____________

Step Action Standard Eval Comments Evaluator:

If necessary provide student with INITIAL recirc pump RPM: (available from monitored parameters)

A: 756 RPM + 2 RPM B: 756 RPM + 2 RPM Ensure GEN 1A(1B) DEMAND adjusted such that GEN 1A(1 B) SPEED decreases when controller DEMAND is decreased.

Evaluator:

If necessary provide student with recirc pump RPM: (available from monitored parameters)

A: 750 RPM and slowly dropping B: 750 RPM and slowly dropping Student may observe loop flow to confirm control Depress RECIRC A LOSS OF FW PP RUNBK RESET HS-B31-1S12A pushbutton.

Monitor GEN 1A SPEED SI-14032A.

Observe Green light above RECIRC A LOSS OF FW PP RUNBK RESET HS-B31-1S12A pushbutton EXTINGUISHED.

Depresses the DEC pushbuttons on Reactor Recirc Pump A(B)

SY-B31-1 R621A(B) controller until Gen 1A(B) Demand XI-14032A(B) and Gen 1A(B) Speed SI 14032A(B) start to decrease.

Depresses the Recirc A Loss of FW PP Runback Reset HS-B31-1 $1 2A pushbutton.

Checks Gen 1A Speed SI-14032A. and determines speed is stable Verifies:

RECIRC A LOSS OF FW PP RUNBK RESET HS-B31-1S12A Pushbutton green light NOT LIT L ______________________

  • Critical Step STCP-QA-1 25B Rev. 2 (9/93)

Page 1 of 1

  1. Critical Sequence
  • 13
  • 14 15 16 Page 7 of 9

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 64.OP.004.103 Student Name:

Step Action Standard Eval Comments Evaluator If minor speed oscillations occur, acknowledge student concerns and direct student to continue with FW PP Runback Resets. Speed oscillations will be addressed subsequent to the reset.

FAULT STATEMENT: RRP B WILL EXPERIENCE AN UNCONTROLLED SPEED INCREASE AFTER THE STUDENT HAS RESET THE RUNBACK.

  • 17 Depress RECIRC B LOSS OF FW PP RUNBK Depresses the Recirc B Loss of RESET HS-B31-1S12B pushbutton.

FW PP Runback Reset HS-B31-1S12B pushbutton.

18 Monitor GEN 1B SPEED SI-14032B.

Checks Gen 1B Speed S1-14032B and Determines RRP B speed is increasing.

  • 19 Trip scoop tube on affected generator by Depresses the SCOOP TUBE B depressing SCOOP TUBE B LOCK OR RESET LOCK OR RESET HS-B31-1S03B HS-B31-1S03B TRIP pushbutton.

Trip pushbutton.

20 Observe Green light above RECIRC B LOSS OF Verifies:

FW PP RUNBK RESET HS-B31-1S12B RECIRC B LOSS OF FW PP pushbutton EXTINGUISHED.

RUNBK RESET HS-B31-1iS12B Pushbutton green light NOT LIT

  • Critical Step STCP-QA-1 25B Rev. 2 (9/93)

Page 1 of 1

  1. Critical Sequence Page 8 of 9

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 64.OP.004.103

  • Critical Step STCP-QA-1 25B Rev. 2 (9/93)

Page 1 of 1 Student Name:

  1. Critical Sequence Step Action Standard Eval Comments 21 Check RECIRC A(B) FLOW LIMIT RUNBACK Verifies:

annunciator CLEARED.

RECIRC A(B) FLOW LIMIT RUNBACK annunciator SLOW FLASHES 22 Notify Reactor Engineering.

States requirement to Notify Reactor Engineering Evaluator:

Acknowledge notification Page 9 of 9

TASK CONDITIONS:

A.

The plant is in Mode 1.

B.

Rods 18-23, 18-39, 42-23, and 42-39, are fully inserted to support HCU maintenance on Rod 18-23 C.

A trip of CWP 1 D has caused a Reactor Recirculation runback to occur.

D.

NO Operator actions have been taken.

INITIATING CUE:

Reset recirculation pump runback in accordance with appropriate Off Normal procedure.

Page 1 of 2

TASK CONDITIONS:

A.

The plant is in Mode 1.

B.

Rods 18-23, 18-39, 42-23, and 42-39, are fully inserted to support HCU maintenance on Rod 18-23 C.

A trip of CWP 1 D has caused a Reactor Recirculation runback to occur.

D.

NO Operator actions have been taken.

INITIATING CUE:

Reset recirculation pump runback in accordance with appropriate Off Normal procedure.

Page 2 of 2

PROCEDURE COVER SHEET PPL SUSQUEHANNA, LLC NUCLEAR DEPARTMENT PROCEDURE LOSS OF REACTOR RECIRCULATION FLOW 7/10/2002 ON-164-002 Revision 20 Page 1 of 10 QUALITY CLASSIFICATION:

APPROVAL CLASSIFICATION:

(X)

QA Program

(

)

Non-QA Program (X)

Plant

(

)

Non-Plant

)

Instruction EFFECTIVE DATE:

PERIODIC REVIEW FREQUENCY:

N/A PERIODIC REVIEW DUE DATE:

N/A RECOMMENDED REVIEWS:

Procedure Owner:

Shift Technical Advisor-A Shift Responsible Supervisor:

Shift Manager-A Shift Responsible FUM:

Manager-Nuclear Operations Responsible Approver:

Manager-Nuclear Operations FORM NDAP-QA-0002-1, Rev. 3, Page 1 of 1 I

ON-164-002 Revision 20 Page 2 of 10

1.

SYMPTOMS AND OBSERVATIONS 1.1 Reactor power begins to decrease immediately.

1.2 Reactor vessel water level increases.

1.3 Any following indication on Standby Information Panel 1C652:

1.3.1 Recirculation loop flow(s) decreases in affected loop(s).

1.3.2 Jet pump flow(s) for affected loop(s) and total jet pump flow decreases.

1.4 Any following annunciator on Operating Unit Benchboard 1C651:

1.4.1 RECIRC M-G GEN A(B) LOCKOUT TRIP.

1.4.2 RECIRC M-G A(B) DRIVE MTR TRIP.

1.4.3 RECIRC PUMP A(B) HI PRESS/LO LEVEL TRIP.

1.4.4 RPT SYS LOOP A(B) TRIP.

1.4.5 RECIRC A(B) FLOW LIMIT RUNBACK.

2.

AUTOMATIC ACTIONS 2.1 Possible main turbine trip and reactor scram because of RPV level swell caused by the trip of both Reactor Recirculation Pumps, depending on plant operating conditions.

2.2 Reduction in Reactor power, core flow, steam flow, feedwater flow, and generator output corresponding to recirc runback flow decrease.

3.

OPERATOR ACTIONS M

3.1 Record Date and Time of event.

Shift Supervision Date Time M

3.2 IF both Recirculation Pumps trip, Immediately Scram reactor.

ON-1 64-002 Revision 20 Page 3 of 10 3.3 IF one Reactor Recirculation Pump trips:

IF operating recirculation pump speed is <75% rated speed (1260 rpm), Determine actual core flow by (else N/A):

a.

Display Core Pressure Drop via PICSY computer point NJP51 - Core PL Press OR if PICSY unavailable via XR-B21-1R613, Blue Pen: Core Plate DP.

b.

Determine actual core flow using Form GO-1 00-009-2 "Core Flow vs. Core Pressure Drop" curve.

Plot position on Power/Flow Map, Form NDAP-QA-0338-10.

Perform appropriate action as specified on Power/Flow Map.

IF Power/Flow Map indicates operation in Region 1 OR Core Flow is < the Natural Recirculation Line or operations in any region not bounded by Power/Flow map, Place MODE SWITCH to SHUTDOWN.

Ensure thermal power REDUCED to < 70% rod line.

Reduce operating pump speed to 80% rated pump speed (80% = 1344 rpm) in accordance with OP-164-001.

Comply with COLR Section 8.0 Limits in TRM.

Comply with Tech Spec LCOs 3.4.1.

For stopped pump, Place RECIRC A(B) MOV OL BYPS HV-143-FO31A(B)/F032A(B) key switch to TEST position.

NOTE:

WHEN operating recirculation pump speed is <75% rated speed (1260 rpm), Core Pressure Drop (i.e., Core Plate DP) is used to determine actual core flow due to inaccuracies associated with indicated core flow.

3.3.1 17 F1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 17 CAUTION Thermal binding and/or pressure locking of recirculation isolation valves might occur if closed for more than approximately 5 minutes.

3.3.9

ON-1 64-002 Revision 20 Page 4 of 10 El 3.3.10 Ensure RECIRC PUMP A(B) DSCH BYPS HV-143-F032A(B)

OPEN.

El 3.3.11 Close RECIRC PUMP A(B) DSCH HV-143-F031A(B).

El 3.3.12 Within 5 minutes, Open RECIRC PUMP A(B) DSCH HV-143-FO31A(B).

El 3.3.13 AFTER 2 minutes, Place RECIRC A(B) MOV OL BYPS HV-143-FO31A(B)/F032A(B) key switch to NORM position.

El 3.3.14 Prior to restart of pump, Notify Duty Reactor Engineer to perform an evaluation of core thermal limits and preconditioning.

CAUTION Do not attempt to restart recirc pump if operating above 70% rod line or if any flux oscillations are observed.

El 3.3.15 WHEN cause of trip corrected, Restart Reactor Recirculation Pump in accordance with OP-164-001 Reactor Recirculation System.

El 3.3.16 IF pump will be out of service > 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, Comply with GO-1 00-009 Single Recirculation Loop Operation.

3.4 In the event of Reactor Recirculation Pump runback:

El 3.4.1 Plot position on Power/Flow Map, Form NDAP-QA-0338-10.

El 3.4.2 Perform appropriate action specified on Power/Flow Map.

El 3.4.3 IF Power/Flow Map indicates operation in Region 1 or Core Flow is < the Natural Recirculation Line OR operation in any region not bounded by Power/Flow map, Place MODE SWITCH to SHUTDOWN.

3.4.4 Determine which limiter initiated runback:

El

a.

Limiter #1 (30%) limiting by Green light ILLUMINATED above RX RECIRC LIMITER 1 RUNBK RESET HS-B31-1S15A(B) pushbutton.

ON-164-002 Revision 20 Page 5 of 10 El

b.

Limiter #2 (45%) limiting by Green light ILLUMINATED above LOSS OF FW PP RUNBK RESET HS-B31-1S12A(B) pushbutton.

3.4.5 Ensure both pumps run back to value associated with controlling limiter.

CAUTION As core flow decreases, core flux instabilities are more likely to occur.

3.4.6 Monitor neutron instrumentation for indication of core instability.

El

a.

IF required, Perform ON-178-002, Core Flux Oscillations.

CAUTION Power reduction will further reduce amount of feedwater heating which will cause reactor power to increase.

O

b.

Continue Monitoring position on Power/Flow map.

3.4.7 On 1C600, Monitor the following:

El

a.

Main Stream Line Radiation Monitor, RR-D12-1R603.

17

b.

Offgas Pretreatment Log Radiation Monitor, RR-D12-1 R601.

El 3.4.8 IF Main Steam Line Radiation Monitor or Offgas Pretreatment Log Radiation Monitor increases, Direct Chemistry to sample per CH-ON-003.

3.4.9 Observe following plant parameters WITHIN LIMITS corresponding to new power level:

El

a.

Power to flow limits El

b.

Condenser vacuum El

c.

Feedwater flow/steam flow El

d.

RPV water level

ON-164-002 Revision 20 Page 6 of 10 3.4.10 Determine signal that initiated runback from following:

a.

Limiter #1 (30%) runback initiated by any following condition:

1-(1)

Total feedwater flow

  • 20% for > 15 seconds.

El (2)

RECIRC PUMP A(B) DSCH HV-143-FO31A(B) not fully open.

El (3)

RPV water level < level 3.

b.

Limiter #2 (45%) runback initiated by:

17 (1)

Any Circulating Water Pump protective trip.

(2)

RPV low water level (+ 30") and any of following:

El (a)

Feedwater flow A, B, or C decrease to

< 20%.

17 (b)

Any Condensate Pump discharge pressure

< 100 psig.

El (c)

Auto isolation of Feedwater Heaters String A, B or C due to high level in Feedwater Heaters 1 or 2.

El 3.4.11 Ensure REACTOR RECIRC PUMP A(B) SPEEDS SY-B31-1R621A(B) IN MANUAL.

El 3.4.12 For Limiter #1 runback Perform following for one or both pumps as required:

CAUTION (1)

When establishing control with the recirc pump speed controllers, minimize lowering core flow to avoid inadvertent entry into Regions I or II of the power/flow map.

ON-164-002 Revision 20 Page 7 of 10 CAUTION (2)

When establishing control with the recirc pump speed controllers, pump speed should be maintained at appx. 500 rpm. Speed oscillations are possible when the pump is operated between 460 and 485 rpm.

Ol

a.

To prevent pump speed from changing when Limiter #1 reset, Ensure GEN 1A(1B) DEMAND adjusted such that GEN 1A(1B) SPEED decreases when controller DEMAND is decreased.

EO

b.

Depress RX RECIRC LIMITER 1 RUNBK RESET HS-B31-1S15A(B) pushbutton.

El

c.

Monitor GEN 1A(1B) SPEED SI-14032A(B).

E]

d.

IF speed increases rapidly, Trip scoop tube on affected generator by depressing SCOOP TUBE A(B) LOCK OR RESET HS-B31-1S03A(B) TRIP pushbutton.

El

e.

IF previously illuminated, Observe Green light above RX RECIRC LIMITER 1 RUNBK RESET HS-B31-1S15A(B) pushbutton EXTINGUISHED.

3.4.13 For Limiter #2 runback Perform following for one or both pumps as required:

CAUTION When establishing control with the recirc pump speed controllers, minimize lowering core flow to avoid inadvertent entry into Regions I or II of the powerlflow map.

El

a.

To prevent pump speed from changing when Limiter #2 reset, Ensure GEN IA(1 B) DEMAND adjusted such that GEN IA(1 B) SPEED decreases when controller DEMAND is decreased.

El

b.

Depress RECIRC A(B) LOSS OF FW PP RUNBK RESET HS-B31-1S12A(B) pushbutton.

c.

Monitor GEN 1A(1B) SPEED SI-14032A(B).

ON-164-002 Revision 20 Page 8 of 10 17

d.

IF speed increases rapidly, Trip scoop tube on affected generator by depressing SCOOP TUBE A(B) LOCK OR RESET HS-B31-1S03A(B) TRIP pushbutton.

El

e.

Observe Green light above RECIRC A(B) LOSS OF FW PP RUNBK RESET HS-B31-1S12A(B) pushbutton EXTINGUISHED.

El 3.4.14 Check RECIRC A(B) FLOW LIMIT RUNBACK annunciator CLEARED.

El 3.4.15 Notify Reactor Engineering.

3.5 Forward completed copy of this procedure to following for review and retention:

3.5.1 Shift Manager Signature Date 3.5.2 Assistant Operations Mgr.-Shift Operations Signature Date 3.5.3 Manager-Nuclear Operations Signature Date 3.5.4 DCS Supervisor

4.

REFERENCES 4.1 FSAR Section 5.4.1 Reactor Recirculation Pumps 4.2 FSAR Section 15.3 Decrease in Reactor Coolant Flowrate 4.3 GE SIL No. 380 4.4 M-143 Reactor Recirculation 4.5 Memo PLI-42281, S.A. Somma to A.M. Price, "Indicated Core Flow Anomaly,"

October 1, 1985 4.6 NRC Bulletin 88-07 Supplement 1 4.7 OP-164-001, Reactor Recirculation System

ON-164-002 Revision 20 Page 9 of 10

5.

DISCUSSION Loss of Reactor recirculation flow can be caused by the unexpected tripping of one or both Reactor Recirculation Pumps. Tripping of both pumps has the greatest impact on plant operation. At high power levels, the Main Turbine may trip automatically because of RPV water level swell and result in a Reactor scram. If the Reactor does not scram automatically following trip of both Reactor Recirculation Pumps, the reactor is immediately scrammed manually to avoid potential for core flux oscillations.

The Reactor may be operated at reduced power with one Reactor Recirculation Pump out of service and the other driving half of the jet pumps. The idle Reactor Recirculation Pump is kept hot by reverse flow through the loop and is not started unless the idle loop temperature is within 50°F of the operating loop temperature, and the Reactor is operating below the 70% rod line.

Loss of one Reactor Recirculation Pump during Reactor operation does not initiate any Reactor Protection System or safeguards systems actuation because fuel thermal margins are maintained. Flow in the idle jet pumps reverses in approximately 6 seconds, and flow in the operating jet pumps increases to about 143% of its normal flow if the operating pump is at 84% pump speed.

In single loop operation, core flow indication is not accurate when recirculation pump speeds are less than 75% of rated pump speed (1260 rpm). There are two reasons for this inaccuracy:

1. When core flow is below about 38 MIb/hr, forward flow takes place through both loops of jet pumps, in single loop operation, however, the Reverse Flow Summer instrumentation will subtract off the measured flow in the idle loop.
2. When the flow through a jet pump loop is too low to accurately measure the flow i.e.,

below about 8 Mlb/hr), the individual jet pump low flow cut-off instrumentation provides a zero reading. The low forward or reverse flow through the jet pumps in the idle loop will not be accounted for.

When the recirculation pump speed is 75% of rated or higher, the indicated core flow can be accurately determined from control room instrumentation or PICSY. If recirculation pump speed is less than 75% of rated, core flow should be determined by using the Core Flow vs. Core Pressure Drop Curve provided.

If total core flow decreases into Region I of Power/Flow Map, the Reactor is manually scrammed to avoid potential for core flux oscillations. The operator reduces flow in the operating loop to single pump flow criteria. Single pump flow criteria is based on reducing the operating pump speed to less than 80% rated pump speed (80% = 1344 rpm), in accordance with OP-164-001.

ON-164-002 Revision 20 Page 10 of 10 Automatic trips of Reactor Recirculation Pumps can come from EOC-RPT trip (CV fast closure, >_ 500 psig; SV closure, _< 5.5% closed) or ATWS (RPV low level 2, Reactor high pressure). The ATWS and EOC RPT trips open the RPT breakers which in turn cause the MG set drive motor to trip. A LPCI Initiation signal with low Reactor pressure

(< 236 psig) trips the Reactor Recirculation Pumps by closing the discharge and discharge bypass valves.

Two speed limiters limit recirc flow by limiting generator speed on the Reactor Recirc MG sets. Limiter #1 limits speed to 30% and provides NPSH protection for the recirc pumps. Limiter #2 limits speed to 45% and prevents spurious scrams due to transients on the Condensate/Feedwater System and Circulating Water System.

PENNSYLVANIA POWER LIGHT COMPANY JOB PERFORMANCE MEASURE APPROVAL AND ADMINISTRATIVE DATA SHEET 52.OP.010.151 JPM Number 0

Rev No.

11/15/02 206000 A2.17 Date NUREG 1123 Sys. No.

Task

Title:

Override An Inadvertent Start Of The HPCI System In Accordance With OP-152-001 Completed By:

Richard E. Chin Writer 11/15/02 Date Approval:

Requesting Supv./C.A. Head Reviews:

In tructor/Writer Date Date

//- / i-ate Date Date of Performance:

15 Min Allowed Time (Min)

Time Taken (Min)

JPM Performed By:

First Employee #/S.S. #

Performance Evaluation:

) Satisfactory

) Unsatisfactory Evaluator Name:

Signature Typed or Printed Comments:

STCP-QA-1 25A Rev. 2, (9/93)

Page 1 of 1 File No. A14-5B S/RO Appl To 3.9/4.3 K/A Last M.I.

REQUIRED TASK INFORMATION JOB PERFORMANCE MEASURE S/RO 52.OP.01 0.151 SAFETY CONSIDERATIONS A.

All Operations personnel are responsible for maintaining their radiation exposure As Low As Reasonably Achievable in accordance with OP-AD-002, Standards for Shift Operations.

B.

All applicable safety precautions shall be taken in accordance with established PPL safety policies and the Safety Rule Book, for example:

1. Whenever any electrical panel is opened for inspection during JPM performance.
2. Whenever entering any plant area where specific safety equipment; such as hearing or eye protection, safety shoes, hardhats, etc; is required and/or posted as being necessary.

C.

If in the judgement of the evaluator any safety issue occurs during the performance of a JPM, the JPM will be terminated until the issue is resolved

11. REFERENCES OP-152-001, High Pressure Coolant Injection (HPCI) System Ill.

REACTIVITY MANIPULATIONS This JPM satisfies the requirements of Reactivity Manipulation(s):

None IV.

TASK CONDITIONS A.

The plant is in Mode 1 at approximately 90 percent reactor power.

B.

You are the PCOP.

C.

An event will occur on panel 1C601.

V.

INITIATING CUE Respond to the event as required.

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 52.OP.010.151 Student Name:_____________

Step Action Standard Eval Comments Note

"* The IC is to be set up at 90% power.

"* Override the HPCI Flow Controller to prevent manual override of HPCI injection, requiring the operator to isolate HPCI.

IMF CN02:FCE411R600 100 0 100 IMF CN03:FCE411R600 100 0 100

"* Give the Task Conditions/Initiating Cue Sheet to the student.

"* When the student indicates that he/she is prepared to respond to the plant conditions, the simulator should be placed in RUN.

"* Insert HPCI Inadvertent Initiation IMF HP 152004 Evaluator

  • The FAULTED step in this JPM is preceded by a fault statement in BOLD TYPE WITH ALL CAPITAL LETTERS.
  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 3 of 7

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 52.OP.010.151 Student Name:_____________

Step Action Standard Eval Comments 1

Respond to Alarm HPCI Flow -Low Acknowledges alarm HPCI Flow (AR1 14 window E02)

Low (AR1 14 window E02) and Informs SRO of the Alarm Evaluator Student may immediately Place HPCI TURBINE Determines HPCI flow initiation is FLOW CONTROL FC-E41-1R600 in MANUAL inadvertent.

AND Reduce demand to zero (0). This is acceptable.

Evaluator If necessary Role play the SRO and Acknowledge receipt of the alarm, and direct overriding HPCI injection.

2.

Obtains correct hard card for overriding HPCI Obtains hard card for overriding HPCI Evaluator Student may refer to OP-1 52-001 section 2.15 to address the alarm. This is acceptable.

3.

(HC) Place or Check Placed HPCI Aux Oil Pump Places the control switch for HPCI 1 P213 to START Aux Oil Pump 1 P213 in the START position.

Evaluator:

The Auxiliary Oil Pump will not start until HPCI speed decreases to less than 2,200 rpm.

  • Critical Step STCP-QA-1 25B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 4 of 7

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 52.OP.010.151 Student Name:

Step Action Standard

[ Eval Comments FAULT STATEMENT HPCI INJECTION FLOW WILL NOT DECREASE TO ZERO WHEN PRESSURE IS REDUCED TO LESS THAN REACTOR PRESSURE.

(HC) Place HPCI Flow Controller to Manual (HC) Adjusts Controller to reduce HPCI discharge pressure to less than Reactor pressure.

(HC) Ensure that HPCI minimum flow valve HV 155-F012 opens when conditions are met.

(HC) Ensure injection has been stopped.

Evaluator If SRO is informed that the flow indication has NOT decreased to zero, instruct the student to continue performing the procedure.

Places the Manual/Auto switch on HPCI Turbine Flow Control FC-E41-1R600 in the M position.

Depresses the Close pushbutton on HPCI Turbine Flow Control FC E41-1R600.

Checks that HPCI flow does NOT decrease to zero.

Notes that the Min Flow valve HV 155-F012 remains closed.

Notes Injection to vessel continues

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence
4.
5.
6.

7.

Page 5 of 7

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 52.OP.010.151 Student Name:_____________

Step I

Action

[

Standard I Eval I Comments 8.

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence
9.
10.

11.

(HC) Attempt to reset the HPCI initiation signal.

Evaluator:

The initiation signal will not reset. The green indicator lamp above the HPCI Int Sig Reset HS-E41-1S17.

(HC) Reduce HPCI turbine speed to stop flow.

Evaluator This may have been done initially.

(HC) Ensure injection has been stopped.

Evaluator If SRO is informed that the flow indication has NOT decreased to zero, instruct the student to continue performing the procedure.

Notes no oscillations and requirement to isolate HPCI Evaluator Student should determine that HPCI isolation should be attempted through steam supply line isolation in the subsequent steps.

Depresses the HPCI Int Sig Reset HS-E41-1 S17 Reset pushbutton.

Notes that the initiation signal will NOT reset by observing that the green indicator lamp above the HPCI Sig Reset HS-E41-1S17 Reset pushbutton remains LIT.

Depresses the decrease pushbutton on HPCI Turbine Flow Control FC-E41-1 R600.

Checks that HPCI flow indication does NOT decrease to zero.

Checks HPCI speed and determines that it is stable Page 6 of 7

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 52.OP.010.151 Student Name:_____________

Step Action Standard Eval Comments

  • 12.

(HC) Isolate HPCI.

Depresses the HPCI Steam Supply Manual Isolation HS-E41 -1S32 pushbutton.

13.

(HC) Ensure Stm Supply OB Iso valve CLOSES.

Checks HPCI Steam Supply OB Iso HV-1 55-F003 amber light LIT

14.

(HC) Ensure Pump Suction from Supp Pool Checks HPCI Pump Suction from CLOSES Supp Pool HV-155-F042 amber light LIT

15.

(HC) Ensure Injection valve CLOSES Checks HPCI Injection HV-155 F006 amber light LIT

16.

(HC) Ensures Auxiliary Oil Pump STARTS Checks HPCI Auxiliary Oil Pump 1P213 red light LIT

17.

(HC) Places IB Stm supply valve to close Places the HPCI Steam Supply IB Iso HV-155-F002 Keylock Switch in the CLOSE position

18.

(HC) Places OB Stm supply valve to close Places the HPCI Steam Supply OB Iso HV-155-F003 Keylock Switch in the CLOSE position.

Evaluator:

Instruct the student to stop.

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 7 of 7

TASK CONDITIONS A.

The plant is in Mode 1 at approximately 90 percent reactor power.

B.

You are the PCOP.

C.

An event will occur on panel 1C601.

INITIATING CUE Respond to the event as required.

Page 1 of 2

TASK CONDITIONS A.

The plant is in Mode 1 at approximately 90 percent reactor power.

B.

You are the PCOP.

C.

An event will occur on panel 1C601.

INITIATING CUE Respond to the event as required.

Page 1 of 2

Attachment C OP-152-001 Revision 28 Page 66 of 67 OVERRIDING HPCI INJECTION (Ref. Section 2.15)

[] 1.

To prevent auto injection if HPCI not initiated.

El

a.

Place HPCI TURBINE FLOW CONTROL FC-E41-1R600 in MANUAL AND Reduce demand to zero (0).

El

b.

IF HPCI turbine auto starts shutdown HPCI in accordance with step 3.

MJ 2.

To stop injection place HPCI pump on minimum flow as follows:

l

a.

Place or CHECK PLACED HPCI AUXILIARY OIL PUMP 1P213 switch to START.

l

b.

Place HPCI TURBINE FLOW CONTROL FC-E41-1R600 in MANUAL.

l

c.

Adjust HPCI TURBINE FLOW CONTROL FC-E41-1R600 to reduce HPCI discharge pressure less than Reactor pressure.

El

d.

Ensure HPCI MIN FLOW TO SUPP POOL HV-155-F012 opens when HPCI flow

< 500 gpm and discharge pressure > 125 psig.

E]

e.

IF HPCI flow indication does not decrease to zero gpm with HPCI pump discharge pressure less than reactor pressure, Shut Down HPCI per following step.

El 3.

To stop injection/shutdown HPCI:

El

a.

Ensure HPCI AUXILIARY PUMP 1P213 switch placed to START.

El

b.

Depress HPCI INT SIG RESET HS-E41-1S17 RESET pushbutton.

E]

c.

IF HPCI initiation resets, Shut Down HPCI in accordance with section 2.9 of OP-152-001.

El

d.

IF HPCI initiation does not reset, stop injection/shut down using following sections (1) preferred, or (2):

E]

(1)

Reduce HPCI turbine speed to stop injection:

El (a)

Place HPCI TURBINE FLOW CONTROL FC-E41-1R600 in MANUAL.

El (b)

Reduce demand to stop HPCI flow.

El (c)

Ensure HPCI Auxiliary Oil Pump 1P213 does not cycle on and off.

El (d)

Monitor frequently HPCI speed for oscillations.

El (e)

IF turbine speed oscillations occur Increase HPCI turbine speed.

El (f)

IF HPCI flow indication does not decrease to zero gpm with HPCI pump discharge pressure < Reactor pressure or turbine speed oscillations continue, Isolate HPCI in accordance with following section:

El (2)

To isolate HPCI:

El (a)

Depress HPCI STM SUPPLY MAN ISO HS-E41-1S32 pushbutton.

El (b)

Ensure HPCI STM SUPPLY OB ISO HV-155-F003 CLOSES.

E]

(c)

Ensure HPCI PUMP SUCT FROM SUPP POOL HV-155-F042 CLOSES.

E]

(d)

Ensure HPCI INJECTION HV-155-F006 CLOSES.

E]

(e)

Ensure HPCI AUX OIL PUMP 1 P213 starts as HPCI turbine coasts down.

El (f)

Close HPCI STM SUPPLY IB ISO HV-155-F002.

El (g)

Place HPCI STM SUPPLY OB ISO HV-155-F003 KEYSWITCH to CLOSE.

FORM OP-152-001-3, Rev. 1, Page 1 of I

PENNSYLVANIA POWER LIGHT COMPANY JOB PERFORMANCE MEASURE APPROVAL AND ADMINISTRATIVE DATA SHEET 00.ON.015.105 JPM Number 3

Rev No.

11/15/02 Date 295016 AA 1.06 NUREG 1123 Sys. No.

Immediate Operator Action For Control Room Evacuation Completed By:

R. E. Chin Writer 11/15/02 Date Reviews:

nstructor/[Writer Approval:

e tSup v./.A.Head

//-Y.7-

-22 Date N lI Eý-training Supv.

//-//

-CZ._.

Date Date of Performance:

10 Min Allowed Time (Min)

Time Taken (Min)

JPM Performed By:

First Employee #/S.S. #

Performance Evaluation:

) Satisfactory

) Unsatisfactory Evaluator Name:

Signature Comments:

STCP-QA-1 25A Rev. 2, (9/93)

Page 1 of 1 Typed or Printed File No. A14-5B S/RO Appt To Task

Title:

4.0/4.1 KiA

/5..

Date Last M.I.

REQUIRED TASK INFORMATION JOB PERFORMANCE MEASURE SIRO 00.ON.015.105 SAFETY CONSIDERATIONS A.

All Operations personnel are responsible for maintaining their radiation exposure As Low As Reasonably Achievable in accordance with OP-AD-002, Standards for Shift Operations.

B.

All applicable safety precautions shall be taken in accordance with established PPL safety policies and the Safety Rule Book, for example:

1. Whenever any electrical panel is opened for inspection during JPM performance.
2. Whenever entering any plant area where specific safety equipment; such as hearing or eye protection, safety shoes, hardhats, etc; is required and/or posted as being necessary.

C.

If in the judgement of the evaluator any safety issue occurs during the performance of a JPM, the JPM will be terminated until the issue is resolved Il. REFERENCES ON-100-009, Control Room Evacuation III.

REACTIVITY MANIPULATIONS This JPM satisfies the requirements of Reactivity Manipulation(s):

02 Plant Shutdown Outside the Control Room in Conjunction with JPM 00.ON.015.101 IV.

TASK CONDITIONS A.

A condition has occurred requiring abandonment of the Control Room.

B.

You are the Unit Supervisor in the Control Room.

C.

The Control Room will be non-inhabitable in five to eight minutes.

V.

INITIATING CUE Perform the Immediate Operator Actions of Control Room evacuation.

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 00.ON.015.105 Student Name:

Step Action Standard Eval Comments Evaluator:

If performed in the simulator, any power level IC may be selected. IC-18 preferred.

The student is allowed to reference ON-1 00-009.

1.

Announce twice over PA system "Control Room Pick up PA and announce evacuation in progress."

that the Control Room is being evacuated.

  • 2.

Place the reactor MODE SWITCH to SHUTDOWN.

Place HS-C72A-1S01 to SHUTDOWN.

3.

ENSURE all control rods INSERTED.

Check any of the following:

a.

Full Core Display

b.

RSCS

c.

OD-7

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 3 of 5

Appl. To/JPM No.: S/RO 00.ON.015.105 PERFORMANCE CHECKLIST Student Name:

Page 4 of 5 Step Action Standard Eval Comments

4.

INSERT SRMs and IRMs.

Select IRMs and SRMs.

Drive power on.

Depress DRIVE IN.

  • 5.

Close the MSIVs and MSL Drains.

Takes HS for F022A-D to close.

Takes HS for F028A-D to close.

Takes HS for F016 and F019 to close.

  • 6.

Close RFP A, B, and C discharge valves.

Takes HS for HV-10603 A, B, and C to close.

  • 7.

Trip RFPT A, B, and C.

Depresses TRIP pushbutton for all three RFPTs.

  • 8.

Place FW Low Load Valve in AUTO.

Places LIC-C32-1 R602 in AUTO.

  • 9.

Opens HPCI Test Line isolation valve F011.

Places the HV-155-FOl1 to OPEN.

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 00.ON.015.105 Student Name:

Step Action Standard Eval Comments

10.

Take two (2) security controlled keys from Shift States requirement to get keys Supervisor key cabinet to gain entrance into from Shift Supervisor.

Reactor Building. (Unit Supervisor only)

11.

Take PICSY laptop computer.

Obtains laptop computer from (Unit Supervisor only)

Shift Supervisor's Office.

Evaluator:

Inform student that the keys and the laptop have been obtained.

"*12.

Leaves the Control Room to go to Evacuate the Control Room.

the RSDP.

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 5 of 5

TASK CONDITIONS:

A. A condition has occurred requiring abandonment of the Control Room.

B. You are the Unit Supervisor in the Control Room.

C. The Control Room will be non-inhabitable in five to eight minutes.

INITIATING CUE:

Perform the Immediate Operator Actions of Control Room Evacuation.

Page 1 of 2

TASK CONDITIONS:

A. A condition has occurred requiring abandonment of the Control Room.

B. You are the Unit Supervisor in the Control Room.

C. The Control Room will be non-inhabitable in five to eight minutes.

INITIATING CUE:

Perform the Immediate Operator Actions of Control Room Evacuation.

Page 2 of 2

PROCEDURE COVER SHEET PPL SUSQUEHANNA, LLC NUCLEAR DEPARTMENT PROCEDURE 8-13-02 CONTROL ROOM EVACUATION ON-100-009 Revision 6 Page 1 of 31 QUALITY CLASSIFICATION:

APPROVAL CLASSIFICATION:

(X)

QA Program

( )

Non-QA Program (X)

Plant

( )

Non-Plant

( )

Instruction EFFECTIVE DATE:

PERIODIC REVIEW FREQUENCY:

N/A PERIODIC REVIEW DUE DATE:

N/A RECOMMENDED REVIEWS:

Procedure Owner:

Shift Technical Advisor-B Shift Responsible Supervisor:

Shift Manager-B Shift Responsible FUM:

Manager-Nuclear Operations Responsible Approver:

Manager-Nuclear Operations FORM NDAP-QA-0002-1, Rev. 3, Page 1 of 1

ON-1 00-009 Revision 6 Page 2 of 31

1.

SYMPTOMS AND OBSERVATIONS Conditions exist which require Control Room EVACUATION:

1.1 Dense SMOKE 1.2 Extreme HEAT 1.3 Hazardous GAS which induces difficulty in breathing 1.4 Direction from Shift Supervision

2.

AUTOMATIC ACTIONS None

3.

IMMEDIATE OPERATOR ACTIONS 3.1 Record date and time of event.

Shift Supervision Date Time NOTE:

If Control Room evacuation is anticipated, Notify Security to provide access to BOTH Units' Remote Shutdown Panels.

3.2 As time 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 permits, Perform following prior to Control Room evacuation:

Announce twice over Plant PA System "Control Room evacuation in progress."

Place MODE SWITCH HS-C72A-1S01 to SHUTDOWN.(5 )

Ensure all Control Rods INSERTED.

Insert SRM's and IRM's.

Close MSIV's and MSL drains HV-141-F022A,B,C,& D, HV-141-F028A,B,C & D, HV-141-F016 and HV-141-F019.(5)

Close RFP A,B & C DSCH ISO HV-0603A,B & C.(5)

Trip RFPT A,B & C, RFPT A, B & C TRIP RESET HS-12745A, B & C.(5)

Place FW LOW LOAD DEMAND LIC-C32-1 R602 in AUTO.

El El El El 17-

ON-100-009 Revision 6 Page 3 of 31 Open HPCI TEST LINE TO CST ISO HV-1 55-FOl1.

Take two (2) sets of security keys from Shift Supervisor key cabinet to gain entrance into Reactor Building. (Unit Supervisor only)

Take PICSY laptop computer from under the Shift Supervisor's desk. (Unit Supervisor only)

El 3.3 Evacuate Main Control Room.

4.

SUBSEQUENT OPERATOR ACTIONS I NOTE:

All indications and controls are from 1C201 unless otherwise indicated.

4.1 IF required to establish communication between Remote Shutdown Panel and locations in the plant, Refer to Attachment C for sound powered phone location.

NOTE:

Unit Two Remote Shutdown Panel Room phone extension is 3823.

4.2 IF Control Room evacuated prior to completing immediate operator actions, Perform locally:

Open the following breakers to Scram Reactor and isolate Inboard and Outboard MSIV's and Main Steam Line Drains:(5)

NOTE:

A screwdriver has been stored in JP1203 Sound Powered Phone Headset Storage Box (by A RPS Panel) if needed to open RPS panels.

a.

1Y201A Bkr CB2A in RPS power distribution panel (27-749')

b.

2Y201 B Bkr CB8B in RPS power distribution panel (27-749')

Manually Close following valves (11-729'):

a.

HV-10603A RFP A Dsch Iso

b.

HV-10603B RFP B Dsch Iso

c.

HV-10603C RFP C Dsch Iso 3.2.9 3.2.10 Ml 3.2.11 El 4.2.1 4.2.2 El

[]

PENNSYLVANIA POWER & LIGHT COMPANY JOB PERFORMANCE MEASURE APPROVAL AND ADMINISTRATIVE DATA SHEET 55.OP.007.001 JPM Number 1

Rev No.

11/14/02 Date 201001 A2.07 NUREG 1123 Sys. No.

Shift The CRD Flow Stations From A To B In Accordance With OP-1 55-001 Completed By:

Richard Chin Writer Reviews:

11/14/02 Date Instructor/Writer Date Approval:

1eq e s fi.nýi p7. A. Hea Date Nuo( ekTraining Supv.

Date Date of Performance:

20 Allowed Time (Min)

Time Taken (Min)

JPM Performed By:

First Employee #/S.S. #

Performance Evaluation:

) Satisfactory

) Unsatisfactory Evaluator Name:

Signature Typed or Printed Comments:

STCP-QA-1 25A Rev. 1, (9/93)

Page 1 of 1 File No. A14-5B S/RO Appi To Task

Title:

3.2/3.1 K/A Last M.I.

REQUIRED TASK INFORMATION JOB PERFORMANCE MEASURE SIRO 55.OP.007.001 SAFETY CONSIDERATIONS A.

All Operations personnel are responsible for maintaining their radiation exposure As Low As Reasonably Achievable in accordance with OP-AD-002, Standards for Shift Operations.

B.

All applicable safety precautions shall be taken in accordance with established PP&L safety policies and the Safety Rule Book, for example:

1. Whenever any electrical panel is opened for inspection during JPM performance.
2. Whenever entering any plant area where specific safety equipment; such as hearing or eye protection, safety shoes, hardhats, etc; is required and/or posted as being necessary.

C.

If in the judgement of the evaluator any safety issue occurs during the performance of a JPM, the JPM will be terminated until the issue is resolved 1I. REFERENCES OP-155-001, Control Rod Drive Hydraulic System III.

REACTIVITY MANIPULATIONS This JPM satisfies the following reactivity manipulations:

None IV.

TASK CONDITIONS A.

Unit 1 is at 80 percent reactor power.

B.

While adjusting Control Rods per Reactor Engineering Instructions, it is noted that the "A" CRD Flow Control station is not responding properly.

C.

The "B" CRD Flow Control Station needs to be placed in service so that I&C can investigate.

V.

INITIATING CUE Change CRD flow control stations from FV-1 F002A to FV-1 F002B.

PERFORMANCE CRITERIA Appl. To/JPM No.:S/RO 55.OP.007.001 Student Name:_________________

Step Action Standard Eval Comments Evaluator With the A flow control station in service the following conditions exist:

"* M/A-1 D009A is in auto.

"* Closed and Open position indicator lights for FCV are illuminated.

"* M/A-1D009B is in MAN.

"* FCV B closed light is ILLUMINATED and the open light is EXTINGUISHED.

1 Obtain a controlled copy of OP-155-001.

Controlled copy obtained.

2.

Select the correct section to perform.

Selects Section 3.4.

3.

Review the prerequisites.

Ensures that all prerequisites have been met.

Evaluator Inform the student that all prerequisites have been met.

4.

Review the precautions.

Follows all precautions as applicable.

  • Critical Step STCP-QA-1 25B Rev. 1 (9/93)

Page 1 of 1

  1. Critical Sequence Page 3 of 8

PERFORMANCE CRITERIA Appl. To/JPM No.:S/RO 55.OP.007.001 Student Name:

Step Action Standard Eval Comments

5.

Ensure that the master CRD flow controller is in Calls the Control Room and automatic.

confirms that CRD Flow Controller FIC-C12-1R600 is in automatic.

Evaluator FIC-C12-1R600 is located on Panel 1C601 in the Control Room. Inform the student that the controller is in automatic.

6.

Ensure that the FCV B controller is in manual at Ensures that the following minimum.

conditions exist for M/A-1 D009B Man/Auto Station Control Valve B controller:

  • Man/Auto control switch is in the MAN position.
  • The red pen is at 0.
  • Amber light is ILLUMINATED and the red light is EXTINGUISHED
7.

Check that the inlet isolation valve for flow control Checks that the Flow Control Valve valve B is open.

B Iso 146F046B is open.

Evaluator Inform the student that the valve is open.

  • Critical Step STCP-QA-125B Rev. 1 (9/93)

Page 1 of 1

  1. Critical Sequence Page 4 of 8

PERFORMANCE CRITERIA Appl. To/JPM No.:S/RO 55.OP.007.001 Student Name:

Step Action Standard Eval Comments

  • 8.

Open the outlet isolation valve for FCV B.

Very slowly cracks open Flow Control Valve B Iso 146F047B.

Evaluator

"* Flow will change dramatically (20-25 gpm)

Waits for flow to stabilize as if this valve is more than cracked open indicated by any of the following:

initially.

  • Audible sound change has

" For training, ensure that the student understands stopped.

the necessity for waiting for the flow to stabilize.

e M/A-1 D009A Man/Auto Station Control Valve A Black pen STABLE.

9 Flow Control Station Total Water Flow FI-1 R019 - 63 gpm.

Completes opening Flow Control Valve B Iso 146F047B.

  • 9.

Open Flow Control Valve FV-1 F002B.

Slowly rotates the manual adjust knob on M/A-1 D009B Man/Auto Evaluator Station Control Valve B until the

"* The red Open light will illuminate as the valve red and black pens are matched.

opens.

"* Both the Closed and Open lights will remain illuminated.

"* Flow Control Valve A will go in the closed direction as Flow Control Valve B is opened.

  • Critical Step STCP-QA-125B Rev. 1 (9/93)

Page 1 of 1

  1. Critical Sequence Page 5 of 8

PERFORMANCE CRITERIA Appl. To/JPM No.:S/RO 55.OP.007.001 Student Name:

Step Action Standard Eval Comments

10.

Wait for flow to stabilize.

Waits for flow to stabilize as indicated by any of the following:

"* Audible sound change has stopped.

Evaluator e M/A-1 D009A Man/Auto Station If necessary, inform student that the Audible sound Control Valve A Black pen change has stopped.

DECREASES and STABILIZES.

"* Flow Control Station Total Water Flow on FI-1 R01 9-63 gpm.

11.

Adjust the inservice flow control station manual Slowly rotates the manual adjust position indication.

knob on M/A-1 D009A Man/Auto Station Control Valve A until the Evaluator red and black pens are matched.

Nothing will occur when this is performed. The student should match these needles as closely as possible. The closer the match the smaller the change when the controller is placed in manual later.

12.

Check total water flow.

Notes that Flow Control Station Total Water Flow FI-1 R019 indicates approximately 63 gpm.

  • Critical Step STCP-QA-125B Rev. 1 (9/93)

Page 1 of 1

  1. Critical Sequence Page 6 of 8

PERFORMANCE CRITERIA Appl. To/JPM No.:S/RO 55.OP.007.001

  • Critical Step STCP-QA-125B Rev. 1 (9/93)

Page 1 of 1 Student Name:_________________

  1. Critical Sequence Step Action Standard Eval Comments
13.

Place Flow Control Station A in manual.

Places the Man/Auto switch on M/A-1 D009A Man/Auto Station Control Valve A in the MAN position.

14.

Place Flow Control Station B in automatic.

Rotates the Man/Auto control switch on M/A-1 D009B Man/Auto Station Control Valve B to the AUTO position.

"*15.

Close Flow Control Valve A.

Slowly rotates the manual adjust knob on M/A-1 D009A Man/Auto Evaluator Station Control Valve A in the

"* FCV FV-1 F002A will go closed and valve counterwise direction until the red FV-1 F002B will open farther to compensate.

pen indicates 0.

"* The open indicator for FV-1 F002A will extinguish.

16.

Check total water flow.

Notes that Flow Control Station Total Water Flow FI-1 R019 indicates approximately 63 gpm.

Page 7 of 8

PERFORMANCE CRITERIA Appl. To/JPM No.:S/RO 55.OP.007.001

  • Critical Step STCP-QA-125B Rev. 1 (9/93)

Page 1 of 1 Student Name:_________________

  1. Critical Sequence Step Action Standard Eval Comments
17.

Close Flow Control Valve A Iso 146F047A.

Slowly closes Flow Control Valve A Iso 146F047A.

18.

Check CRD System parameters.

Notes the following parameters:

"* Flow Control Station Total Water Flow FI-1 R019 - 63 gpm.

"* Downstream P-C/Rea Differential Pressure PDI-1R005

< 50 psid.

"* Upstream P-C/Rea Differential Pressure PDI-1 R009 is - 250 psig.

Page 8 of 8

TASK CONDITIONS:

A. Unit 1 is at 80 percent reactor power.

B. While adjusting Control Rods per Reactor Engineering Instructions, it is noted that the "A" CRD Flow Control station is not responding properly.

C. The "B" CRD Flow Control Station needs to be placed in service so that I&C can investigate.

INITIATING CUE:

Change CRD flow control stations from FV-1 F002A to FV-1 F002B.

Page 1 of 2

TASK CONDITIONS:

A. Unit 1 is at 80 percent reactor power.

B. While adjusting Control Rods per Reactor Engineering Instructions, it is noted that the "A" CRD Flow Control station is not responding properly.

C. The "B" CRD Flow Control Station needs to be placed in service so that I&C can investigate.

INITIATING CUE:

Change CRD flow control stations from FV-1 F002A to FV-1 F002B.

Page 2 of 2

OP-155-001 Revision 31 Page 21 of 76 3.4 SWAPPING FLOW CONTROL STATIONS 3.4.1 Prerequisites CRD Hydraulic System operation in accordance with section 3.1 of this procedure.

3.4.2 Precautions None NOTE:

Following steps describe changing from Flow Control Valve FV-1 F002A to FV-1 F002B. To change from valve B to A, use valves in parentheses.

3.4.3 ENSURE CRD FLOW CONTROLLER FC-C12-1R600 in AUTO.

3.4.4 ENSURE M/A-1D009B(A) Man/Auto Station Control Valve B(A) in MAN with Red pen indicating 0. Red pen displays MANUAL demand on the local controller.

3.4.5 ENSURE Position Indicator Flow Control Valve B(A) Amber light ILLUMINATED and Red light EXTINGUISHED indicating FV-1 F002B(A) CLOSED.

3.4.6 CHECK OPEN Flow Control Valve B(A) Iso 146F046B(A).

NOTE:

To prevent large (20 to 25 gpm) flow changes, following step should be performed very slowly.

3.4.7 SLOWLY CRACK OPEN Flow Control Valve B(A)

Iso 146F047B(A).

OP-155-001 Revision 31 Page 22 of 76 3.4.8 OBSERVE following indicating flow stabilized:

a.

Audible sound change STOPPED.

b.

M/A-1 D009A(B) Man/Auto Station Control Valve A(B)

Black pen STABLE. The black pen displays control room demand.

c.

Flow Control Station Total Water Flow FI-1 R019 9 63 gpm.

3.4.9 When stable flow indicated, FULLY OPEN Flow Control Valve B(A) Iso 146F047B(A).

3.4.10 SLOWLY ROTATE manual adjust knob on M/A-1D009B(A)

Man/Auto Station Control Valve until Black and Red pens closely matched as possible.

3.4.11 OBSERVE following indicating flow stabilized:

a.

Audible sound change STOPPED.

b.

M/A-1 D009A(B) Man/Auto Station Control Valve A(B)

Black pen DECREASES and STABILIZES.

c.

Flow Control Station Total Water Flow Fi-i R019 - 63 gpm.

3.4.12 SLOWLY ROTATE manual adjust knob on M/A-ID009A(B)

Man/Auto Station Control Valve until Black and Red pens closely matched as possible.

3.4.13 ENSURE Flow Control Station Total Water Flow FI-IR019

- 63 gpm and stable.

3.4.14 PLACE M/A-1 D009A(B) Man/Auto Station Control Valve A(B) control switch to MAN.

3.4.15 PLACE M/A-ID009B(A) Man/Auto Station Control Valve B(A) control switch to AUTO.

3.4.16 SLOWLY ROTATE manual adjust knob on M/A-1D009A(B)

Man/Auto Station Flow Control Valve A(B) until Red pen indicates 0.

3.4.17 ENSURE Flow Control Station Total Water Flow FI-1 R01 9

- 63 gpm and stable.

OP-155-001 Revision 31 Page 23 of 76 NOTE:

To prevent large (20 to 25 gpm) flow changes, following step should be performed very slowly.

3.4.18 SLOWLY CLOSE Flow Control Valve A(B) Iso 146F047A(B).

3.4.19 CHECK following for normal CRD System parameters:

a.

Flow Control Station Total Water Flow FI-I R019 - 63 gpm.

b.

Downstream P-C/Rea Differential Pressure PDI-1R005

< 50 psid.

c.

Upstream P-C/Rea Differential Pressure PDI-1R009

- 250 psid.

PENNSYLVANIA POWER & LIGHT COMPANY JOB PERFORMANCE MEASURE APPROVAL AND ADMINISTRATIVE DATA SHEET S/RO Appl. To Task

Title:

24.OP.001.007 JPM Number 0

Rev. No.

11/14/02 Date 264000 A2.09 NUREG 1123 Sys. No.

3.7/4.1 K/A Transfer of DG "E" for DG "C" Completed By:

Richard Chin Writer Requesting Supv./C.A.

Head 11/14/02 Date 16"g-ruct-or/W nfer Date Reviews:

rt/.L Date

/I/-r T.- 2 r

&k Tr'ng. Supv.

Date Date of Performance:

20 Allowed Time (Min.)

Time Taken (Min.)

JPM Performed By:

Student Name:

Last Performance Evaluation:

First

(

)

Satisfactory M.I.

Employee #/S.S. #

(

)

Unsatisfactory Evaluator Name:

Signature Typed or Printed Comments:

Form STCP-QA-125A Rev. 4, (05/00)

Page 1 of 1 File No. A14-5B

REQUIRED TASK INFORMATION JOB PERFORMANCE MEASURE S/RO 24.OP.001.007 SAFETY CONSIDERATIONS A.

All Operations personnel are responsible for maintaining their radiation exposure As Low As Reasonably Achievable in accordance with OP-AD-002, Standards for Shift Operations.

B.

All applicable safety precautions shall be taken in accordance with established PPL safety policies and the Safety Rule Book, for example:

1. Whenever any electrical panel is opened for inspection during JPM performance.
2. Whenever entering any plant area where specific safety equipment; such as hearing or eye protection, safety shoes, hardhats, etc; is required and/or posted as being necessary.

C.

If in the judgement of the evaluator any safety issue occurs during the performance of a JPM, the JPM will be terminated until the issue is resolved I1.

REFERENCES A.

OP-024-004, TRANSFER AND TEST MODE OPERATIONS OF DIESEL GENERATOR E Attachment C (Revision 23 ) [Steps 1 and 2 signed as being completed]

II1.

REACTIVITY MANIPULATIONS This JPM satisfies the requirements of Reactivity Manipulation(s):

None IV.

TASK CONDITIONS A.

Both Units were at 100% Steady State Power B.

A Station Blackout occurred C.

The "A" Diesel generator was started LOCALLY D.

The control room crew is performing Unit 1(2) Response to Station Blackout EO-100(200)-030, E.

To facilitate two diesels in same division operating, the control room is attempting to energize the "C" bus using the "E" DIESEL GENERATOR.

F.

Another operator is at the "E" DG and has already performed steps 1 and 2 of OP-024-004, TRANSFER AND TEST MODE OPERATIONS OF DIESEL GENERATOR E Attachment C (Revision 23)

V.

INITIATING CUE Prepare the "C" DG for Transfer by performing steps 3 through 11 of OP-024-004, TRANSFER AND TEST MODE OPERATIONS OF DIESEL GENERATOR E Attachment C (Revision 23)

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 024.OP.001.007 Student Name:

Step Action Standard Eval Comments Obtain a controlled copy of OP-024-004, TRANSFER Controlled copy obtained from AND TEST MODE OPERATIONS OF DIESEL evaluator.

GENERATOR E Attachment C (Revision 23)

  • 1.
3.

At 0C521 C Diesel Generator C Engine Control PLACES DG C Control Mode Panel, PLACE DG C Control Mode Select Switch Select Switch 43CM to LOCAL 43CM to LOCAL.

2.
4.

OBSERVE following:

4.1 Control Switches Not Proper for Remote Verifies:

Auto Oper. ALARM.

"Control Switches Not Proper for Remote Auto Oper" ALARM (Window E08) LIT 4.2 Remote white light EXTINGUISHES.

Verifies:

REMOTE white light NOT LIT 4.3 Local white light ILLUMINATED.

Verifies:

LOCAL white light LIT 4.4 DG C Available for Emergency white light Verifies:

EXTINGUISHES.

DG C Available for Emergency white light NOT LIT

3.
5.

ENSURE Control Room received DG Panel Calls the Control Room to verify ALARM.

DG Panel ALARM has been received.

Evaluator Role play the control room and inform the candidate that DG Panel ALARM has been received

  • Critical Step STCP-QA-1 25B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 3 of 7

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 024.OP.001.007 Student Name:

Step Action Standard Eval Comments

  • 4.
6.

At 0C521C CLOSE ESW Loop A Valves for DG C PLACES ESW Supply/Return by momentarily placing switch to CLOSE for ESW HV-01 112C/HV-01 122C switch to Supply/Return HV-01 112C/HV-01 122C.

CLOSE

  • 5.
7.

At 0C521 C CLOSE ESW Loop B Valves for DG C PLACES ESW Supply/Return by momentarily placing switch to CLOSE for ESW HV-0111 OC/HV-01 120C switch to Supply/Return HV-01 110C/HV-01 120C.

CLOSE NOTE:

Switching protective equipment required at switchgear.

Evaluator This JPM will not proceed to the point of racking the breakers, therefore Switching protective equipment will not be required.

6.
8.

At 0C512C DG E for DG C Transfer Panel PLACE PLACES DG C Bldg Ventil Supply DG C Bldg Ventil Supply Fan 0V512C to STOP.

Fan 0V512C switch to STOP

  • 7.
9.

At 0C512C PLACE HS-00057C, DG C Auto Start PLACES HS-00057C, DG C Auto Control, to DISABLE to prevent inadvertent start Start Control switch to DISABLE while transferring logic.

8.
10.

At 0C512C OBSERVE DG C Aligned white light Verifies DG C Aligned white light EXTINGUISHED.

NOT LIT

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 4 of 7

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 024.OP.001.007 Student Name:

Step Action Standard Eval Comments

    1. 9.
11.

At 0C512C SEQUENTIALLY PLACE following switches to D/G E position:

11.1 HS-00058C Generator Metering &

PLACES HS-00058C Generator Computer Monitoring Metering & Computer Monitoring switch to D/G E position 11.2 HS-00059C Generator Field Current PLACES HS-00059C Generator Computer Monitoring Field Current Computer Monitoring switch to D/G E position 11.3 HS-00060C Diesel Alarms to Control Room PLACES HS-00060C Diesel Annunciator Alarms to Control Room Annunciator switch to D/G E position 11.4 HS-00061C ESW Temp Monitoring &

PLACES HS-00061 C ESW Temp HVAC Alarms Monitoring & HVAC Alarms switch to D/G E position 11.5 HS-00062C ESW Loop A Supply Valve PLACES HS-00062C ESW Loop Control & Indication A Supply Valve Control &

Indication switch to D/G E position 11.6 HS-00063C ESW Loop A Return Valve PLACES HS-00063C ESW Loop Control & Indication A Return Valve Control &

Indication switch to D/G E position 11.7 HS-00064C ESW Loop B Supply Valve PLACES HS-00064C ESW Loop Control & Indication B Supply Valve Control &

Indication switch to D/G E position

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence Page 5 of 7

PERFORMANCE CHECKLIST Appi. To/JPM No.: S/RO 024.OP.001.007 Student Name:

Step I

Action I

Standard I Eval I Comments 11.14 HS-00071C DG Ctl, Indication, Metering &

Breaker Trip Interlock 11.15 HS-00072C Generator Relaying & Breaker Trip Interlock 11.8 HS-00065C DG Bypass Indication Unit 1 11.9 HS-00066C DG Bypass Indication Unit 2 11.10 HS-00067C Alignment Alarm & Indication Only 11.11 HS-00068C ESW Loop B Return Valve Control & Indication 11.12 HS-00069C ESW Bypass Indication and Auto Loop Transfer 11.13 HS-00070C Ventilation Supply Fans Control

_______~~~~~

a Ij I__ _

  • Critical Step STCP-QA-125B Rev. 2, (9/93)

Page 1 of 1

  1. Critical Sequence PLACES HS-00065C DG Bypass Indication Unit 1 switch to D/G E position PLACES HS-00066C DG Bypass Indication Unit 2 switch to D/G E position PLACES HS-00067C Alignment Alarm & Indication Only switch to D/G E position PLACES HS-00068C ESW Loop B Return Valve Control &

Indication switch to D/G E position PLACES HS-00069C ESW Bypass Indication and Auto Loop Transfer switch to D/G E position PLACES HS-00070C Ventilation Supply Fans Control switch to D/G E position PLACES HS-00071C DG Ctl, Indication, Metering & Breaker Trip Interlock switch to D/G E position PLACES HS-00072C Generator Relaying & Breaker Trip Interlock switch to D/G E position Page 6 of 7

PERFORMANCE CHECKLIST Appl. To/JPM No.: S/RO 024.OP.001.007 Student Name:

At-i~n 11.16 HS-00073C Generator Metering & Breaker Trip Interlock 11.17 HS-00074C Engine Control & Indication 11.18 HS-00075C Engine, Generator & ESW Pump Control 11.19 HS-00076C Generator Breaker Control I

  • Critical Step STCP-QA-1 25B Rev. 2, (9/93)

Page 1 of 1 Stndr LI uomei PLACES HS-00073C Generator Metering & Breaker Trip Interlock switch to D/G E position PLACES HS-00074C Engine Control & Indication switch to D/G E position PLACES HS-00075C Engine, Generator & ESW Pump Control switch to D/G E position PLACES HS-00076C Generator Breaker Control switch to D/G E position

  1. Critical Sequence Ste I Itn Page 7 of 7 C~omments Standard Eval

£f*.n

TASK CONDITIONS A. Both Units were at 100% Steady State Power B. A Station Blackout Occurred C. The "A" Diesel generator was started LOCALLY D. The control room crew is performing Unit 1(2) Response to Station Blackout EO-100(200)-030, E. To facilitate two diesels in same division operating, the control room is attempting to energize the "C" bus using the "E" Diesel generator.

F. Another operator is at the "E" DG and has already performed steps 1 and 2 of OP-024-004, TRANSFER AND TEST MODE OPERATIONS OF DIESEL GENERATOR E Attachment C (Revision 23)

INITIATING CUE Prepare the "C" DG for Transfer by performing steps 3 through 11 of OP-024-004, TRANSFER AND TEST MODE OPERATIONS OF DIESEL GENERATOR E Attachment C (Revision 23)

Page 1 of 2

TASK CONDITIONS A. Both Units were at 100% Steady State Power B. A Station Blackout Occurred C. The "A" Diesel generator was started LOCALLY D. The control room crew is performing Unit 1(2) Response to Station Blackout EO-1 00(200)-030, E. To facilitate two diesels in same division operating, the control room is attempting to energize the "C" bus using the "E" Diesel generator.

F. Another operator is at the "E" DG and has already performed steps 1 and 2 of OP-024-004, TRANSFER AND TEST MODE OPERATIONS OF DIESEL GENERATOR E Attachment C (Revision 23)

INITIATING CUE Prepare the "C" DG for Transfer by performing steps 3 through 11 of OP-024-004, TRANSFER AND TEST MODE OPERATIONS OF DIESEL GENERATOR E Attachment C (Revision 23 )

Page 2 of 2

Attachment C OP-024-004 TRANSFER OF DG E FOR DG C Revision 23 Page 41 of 77 DATE:

CONFIRM VERIFY

1.

CHECK DG E available for substitution determined by following at 0C521E Diesel Generator E Engine Control Panel:

1.1 Master Trip Ckt Reset light ILLUMINATED.

1.2 DC Power Avail Circuit #1 & #2 lights ILLUMINATED.

1.3 All annunciators clear or evaluated as not affecting DG E operability.

2.

LOG transfer start time in PCO log.

NOTE:

Next step produces Control Room & Local Alarm.

3.

At 0C521C Diesel Generator C Engine Control Panel, PLACE DG C Control Mode Select Switch 43CM to LOCAL.

4.

OBSERVE following:

4.1 Control Switches Not Proper for Remote Auto Oper.

ALARM.

4.2 Remote white light EXTINGUISHES.

4.3 Local white light ILLUMINATED.

4.4 DG C Available for Emergency white light EXTINGUISHES.

5.

ENSURE Control Room received DG Panel ALARM.

6.

At 0C521 C CLOSE ESW Loop A Valves for DG C by momentarily placing switch to CLOSE for ESW Supply/Return HV-01 1 12C/HV-01 122C.

7.

At 0C521C CLOSE ESW Loop B Valves for DG C by momentarily placing switch to CLOSE for ESW Supply/Return HV-0 111 C/HV-01 120C.

Form to be forwarded to DCS by Ops Clerk.

FORM OP-024-004-3, Rev. 5, Page 0 of 6 (File R5-17)

Attachment C OP-024-004 TRANSFER OF DG E FOR DG C Revision 23 Page 42 of 77 CONFIRM VERIFY NOTE:

Switching protective equipment required at switchgear.

8.

At 0C512C DG E for DG C Transfer Panel PLACE DG C Bldg Ventil Supply Fan 0V512C to STOP.

9.

At 0C512C PLACE HS-00057C, DG C Auto Start Control, to DISABLE to prevent inadvertent start while transferring logic.

10.

At 0C512C OBSERVE DG C Aligned white light EXTINGUISHED.

11.

At 0C512C SEQUENTIALLY PLACE following switches to D/G E position:

11.1 HS-00058C Generator Metering & Computer Monitoring 11.2 HS-00059C Generator Field Current Computer Monitoring 11.3 HS-00060C Diesel Alarms to Control Room Annunciator 11.4 HS-00061 C ESW Temp Monitoring & HVAC Alarms 11.5 HS-00062C ESW Loop A Supply Valve Control &

Indication 11.6 HS-00063C ESW Loop A Return Valve Control &

Indication 11.7 HS-00064C ESW Loop B Supply Valve Control &

Indication 11.8 HS-00065C DG Bypass Indication Unit 1 11.9 HS-00066C DG Bypass Indication Unit 2 11.10 HS-00067C Alignment Alarm & Indication Only 11.11 HS-00068C ESW Loop B Return Valve Control &

Indication 11.12 HS-00069C ESW Bypass Indication and Auto Loop Transfer 11.13 HS-00070C Ventilation Supply Fans Control FORM OP-024-004-3, Rev. 5, Page 1 of 6 (File R5-17)

TRANSFER OF DG E FOR DG C Attachment C OP-024-004 Revision 23 Page 43 of 77 CONFIRM 11.14 HS-00071C DG Ctl, Indication, Metering & Breaker Trip Interlock 11.15 HS-00072C Generator Relaying & Breaker Trip Interlock 11.16 HS-00073C Generator Metering & Breaker Trip Interlock 11.17 HS-00074C Engine Control & Indication 11.18 HS-00075C Engine, Generator & ESW Pump Control 11.19 HS-00076C Generator Breaker Control

12.

At DG C-C 4.16KV Swgr, OPEN Diesel Gen. Bkr OA51OC01.

13.

OPEN Transfer Breaker OA51OC01 Control & Trip DC Power Knife Switch.

14.

RACK OUT OA510CO1.

15.

REMOVE transfer breaker from 0A51 OC01 and PLACE in 0A510C02 DG E - C 4.16KV Swgr, Diesel Gen. Bkr Alternate Pos.

16.

RACK IN 0A510C02.

17.

CLOSE Transfer Breaker 0A510C02 Control & Trip DC Power Knife Switch.

18.

CLOSE 0A510C02.

19.

At 0C512C PLACE DG C Bldg Ventil Supply Fan 0V512C to AUTO.

20.

At 0C512C OBSERVE DG E Aligned white light ILLUMINATED.

NOTE:

Breaker will not close in following step.

21.

At 0A510, Diesel Generator E 4.16KV Switchgear:

21.1 PLACE Feeder Breaker to MCC 0B565 0A51005 control switch to CLOSE position and RELEASE to reset breaker logic for automatic closure on undervoltage at 0B565.

FORM OP-024-004-3, Rev. 5, Page 2 of 6 (File R5-17)

VERIFY

TRANSFER OF DG E FOR DG C Attachment C OP-024-004 Revision 23 Page 44 of 77 CONFIRM 21.2 CONFIRM Bkr OA51005 Aligned for Auto white light ILLUMINATED.

22.

At 0C512E-C DG E for DG C Transfer Panel CHECK DG C Auto Start Control HS-00057E-C in DISABLE.

23.

At 0C512E-C SEQUENTIALLY PLACE following switches to D/G E position:

23.1 HS-00076E-C Generator Breaker Control 23.2 HS-00075E-C Engine, Generator & ESW Pump Control 23.3 HS-00074E-C Engine, Control & Indication 23.4 HS-00073E-C Generator Metering & Breaker Trip Interlock 23.5 HS-00072E-C Generator Relaying & Breaker Trip Interlock 23.6 HS-00071E-C DG Ctl, Indication, Metering & Breaker Trip Interlock 23.7 HS-00070E-C Ventilation Supply Fans Control 23.8 HS-00069E-C ESW Bypass Indication & Auto Loop Transfer 23.9 HS-00068E-C ESW Loop B Return Valve Control &

Indication 23.10 HS-00067E-C Alignment Alarm & Indication Only 23.11 HS-00066E-C DG Bypass Indication Unit 2 23.12 HS-00065E-C DG Bypass Indication Unit 1 23.13 HS-00064E-C ESW Loop B Supply Valve Control &

Indication 23.14 HS-00063E-C ESW Loop A Return Valve Control &

Indication 23.15 HS-00062E-C ESW Loop A Supply Valve Control &

Indication FORM OP-024-004-3, Rev. 5, Page 3 of 6 (File R5-17)

VERIFY

Attachment C OP-024-004 TRANSFER OF DG E FOR DG C Revision 23 Page 45 of 77 CONFIRM VERIFY 23.16 HS-00061E-C ESW Temp Monitoring & HVAC Alarms 23.17 HS-00060E-C Diesel Alarms to Control Room Annunciator 23.18 HS-00059E-C Generator Field Current Computer Monitoring 23.19 HS-00058E-C Generator Metering & Computer Monitoring NOTE:

Following steps refer to one transfer breaker used in five different locations. Normally it is located at 0A510, DG E 4.16KV Switchgear, Feeder Breaker to Test Facility Xfmr 0A51006. There is an associated label "Transfer Breaker Location" that is moved with the transfer breaker to each of the five locations.

(3)

24.

At 0A510, PERFORM following:

24.1 REMOVE transfer breaker 0A51006, and 24.2 PLACE in DG E for DG C Breaker 0A51003 in accordance with OP-000-001, Racking Breakers, and 24.3 PLACE "Transfer Breaker Location" label on the DG E for DG C Breaker cubicle door.

25.

RACK IN 0A51003 in accordance with OP-000-001.

26.

CLOSE Transfer Breaker 0A51003 Control & Trip DC Power Knife Switch.

27.

CLOSE 0A51003.

28.

At 0C512E-C PLACE DG C Auto Start Control HS-00057E-C to ENABLE position.

29.

At 0C512E-C OBSERVE DG E Aligned white light ILLUMINATED.

FORM OP-024-004-3, Rev. 5, Page 4 of 6 (File R5-17)

Attachment C OP-024-004 TRANSFER OF DG E FOR DG C Revision 23 Page 46 of 77 CONFIRM VERIFY NOTE:

Flow should not be directed through the "E" diesel while ESW supply and return valves (HV-01 11 OE/HV-01 120E/

HV-01 112E/HV-01 122E) are being stroked.

30.

At 0C577E DG E Bldg Auxiliary Systems Control Panel, OPEN ESW Loop A Valves for DG E by placing handswitch to OPEN for ESW Loop A Supply/Return HV-01 11 2E/HV-01 122E.

31.

At 0C577E OPEN ESW Loop B Valves for DG E by placing handswitch to OPEN for ESW Loop B Supply/Return HV-01 11 GE/HV-01 120E.

32.

At 0C521 E PLACE Control Mode Select Switch to REMOTE.

33.

ENSURE Control Room DG Panel Alarm EXTINGUISHED.

34.

At 0C521 E OBSERVE:

34.1 Control Switches Not Proper for Remote Auto Oper.

Alarm EXTINGUISHED.

34.2 DG Bypassed or Inoperable alarm EXTINGUISHED.

34.3 Local white light EXTINGUISHED.

34.4 Remote white light ILLUMINATED.

34.5 DG Available for Emerg white light ILLUMINATED.

35.

ALIGN Diesel Generator E for Standby Automatic operation in accordance with OP-024-001.

36.

NOTIFY Control Room DG E has been substituted for DG C.

37.

AFFIX E DG placards on C Diesel Controls on Panel 0C653.

38.

LOG time of transfer completion in PCO Log.

39.

PERFORM SO-024-001 to maintain DG E operability. System Test Verification is performed in lieu of Independent Verification.

FORM OP-024-004-3, Rev. 5, Page 5 of 6 (File R5-17)