ML023470135

From kanterella
Jump to navigation Jump to search

Tech Spec Pages for Amendments 232 and 232 Surveillance Frequency for the Containment Spray and Recirculation Spray Nozzles
ML023470135
Person / Time
Site: Surry  Dominion icon.png
Issue date: 12/10/2002
From:
NRC/NRR/DLPM
To:
References
TAC MB5114, TAC MB5115
Download: ML023470135 (3)


Text

TS 4.5-1 4.5 SPRAY SYSTEMS TESTS Applicability Applies to the testing of the Spray Systems.

Objective To verify that the Spray Systems will respond promptly and perform their design function, if required.

Specification A. Each containment spray subsystem shall be demonstrated OPERABLE:

1. By verifying, that on recirculation flow, each containment spray pump performs satisfactorily when tested in accordance with Specification 4.0.5.
2. By verifying that each motor-operated valve in the containment spray flow path performs satisfactorily when tested in accordance with Specification 4.0.5.
3. By verifying each spray nozzle is unobstructed following maintenance which could cause nozzle blockage.
4. Coincident with the containment spray pump test described in Specification 4.5.A.1, by verifying that no particulate material clogs the test spray nozzles in the refueling water storage tank.

B. Each recirculation spray subsystem shall be demonstrated OPERABLE:

1. By verifying each recirculation spray pump performs satisfactorily when tested in accordance with Specification 4.0.5.

AmendmentNos. 232 and 232

TS 4.5-2

2. By verifying that each motor-operated valve in the recirculation spray flow paths performs satisfactorily when tested in accordance with Specification 4.0.5.
3. By verifying each spray nozzle is unobstructed following maintenance which could cause nozzle blockage.

C. Each weight-loaded check valve in the containment spray and outside containment recirculation spray subsystems shall be demonstrated OPERABLE once per 18 months by cycling the valve one complete cycle of full travel and verifying that each valve opens when the discharge line of the pump is pressurized with air and seats when a vacuum is applied.

D. A visual inspection of the containment sump and the inside containment recirculation spray pump wells and the engineered safeguards suction inlets shall be performed once per 18 months and/or after major maintenance activities in the containment. The inspection should verify that the containment sump and pump wells are free of debris that could degrade system operation and that the sump components (i.e., trash racks, screens) are properly installed and show no sign of structural distress or excessive corrosion.

AmendmentNos. 232 and 232

TS 4.5-4 The recirculation spray pumps outside the containment have the capability of being dry-run and flow tested. The test of an outside recirculation spray pump is performed by closing the containment sump suction line valve and the isolation valve between the pump discharge and the containment penetration. This allows the pump casing to be filled with water and the pump to recirculate water through a test line from the pump discharge to the pump casing.

With a system flush conducted to remove particulate matter prior to the installation of spray nozzles and with corrosion resistant nozzles and piping, it is not considered credible that a significant number of nozzles would plug during the life of the unit to reduce the effectiveness of the subsystems. Therefore, an inspection or air or smoke test of the nozzles following maintenance which could cause nozzle blockage is sufficient to indicate that plugging of the nozzles has not occurred.

The spray nozzles in the refueling water storage tank provide means to ensure that there is no particulate matter in the refueling water storage tank and the containment spray subsystems which could plug or cause deterioration of the spray nozzles. The nozzles in the tank are identical to those used on the containment spray headers. The flow test of the containment spray pumps and recirculation to the refueling water storage will indicate any plugging of the nozzles by a reduction of flow through the nozzles.

Performing the containment sump and pump well inspections will reduce the potential for system degradation due to sump debris associated with refueling activities or major maintenance activities as well as reduce wear on the inside containment recirculation spray pumps during dry testing. Ensuring proper installation and structural integrity of the trash racks and sump screens will prevent ingress of debris generated during the DBA and will allow long term containment cooling and recirculation mode cooling of the core.

References FSAR Section 6.3.1, Containment Spray Pumps FSAR Section 6.3.1, Recirculation Spray Pumps AmendmentNos. 232 and 232