September 24, 2002 MEMORANDUM TO: Richard J. Laufer, Chief, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation FROM:
Daniel S. Collins, Project Manager, Section 1
/RA/
Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation
SUBJECT:
BEAVER VALLEY POWER STATION, UNIT NO 2 - DRAFT REQUEST FOR ADDITIONAL INFORMATION (RAI), REGARDING AMENDMENT REQUEST TO INCREASE ENRICHMENT LIMITS FOR NEW FUEL STORAGE RACKS (TAC MB5301)
The attached draft RAI was transmitted by facsimile on September 12, 2002, to Mr. Ron Fedin of FirstEnergy Nuclear Operating Company in preparation for an upcoming conference call. Review of the RAI would allow the licensee to identify areas where clarification may be needed, as well as determine and agree upon a schedule for responding to the RAI. This memorandum and its attachment do not convey a formal request for information or represent a Nuclear Regulatory Commission position.
Docket No. 50-412
Attachment:
As stated CONTACT: D. Collins, NRR 301-415-1427
September 24, 2002 MEMORANDUM TO: Richard J. Laufer, Chief, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation FROM:
Daniel S. Collins, Project Manager, Section 1
/RA/
Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation
SUBJECT:
BEAVER VALLEY POWER STATION, UNIT NO 2 - DRAFT REQUEST FOR ADDITIONAL INFORMATION (RAI), REGARDING AMENDMENT REQUEST TO INCREASE ENRICHMENT LIMITS FOR NEW FUEL STORAGE RACKS (TAC MB5301)
The attached draft RAI was transmitted by facsimile on September 12, 2002, to Mr. Ron Fedin of FirstEnergy Nuclear Operating Company in preparation for an upcoming conference call. Review of the RAI would allow the licensee to identify areas where clarification may be needed, as well as determine and agree upon a schedule for responding to the RAI. This memorandum and its attachment do not convey a formal request for information or represent a Nuclear Regulatory Commission position.
Docket No. 50-412
Attachment:
As stated CONTACT: D. Collins, NRR 301-415-1427 DISTRIBUTION PUBLIC PDI-1 R/F D. Collins M. OBrien Accession No: ML022670140 Office PDI-2/LA PDI-1/PM PDI-1/SC Name MOBrien DCollins RLaufer Date 9/20/02 9/20/02 9/20/02 OFFICIAL RECORD COPY
DRAFT DRAFT BEAVER VALLEY POWER STATION, UNIT NO. 2 DOCKET NO. 50-412 The U.S. Nuclear Regulatory Commission (NRC) staff is reviewing FirstEnergy Nuclear Operating Companys (FENOC) May 31, 2002, application (L-02-070), and supplement dated September 11, 2002 (L-02-093), for an amendment to Facility Operating License No. NPF-73 for the Beaver Valley Power Station, Unit No 2 (BVPS2), which would allow new fuel with an enrichment of 5.00 weight percent (w/o) U-235 to be placed into and stored in the BVPS2 new fuel storage racks.
The NRC staff has determined that additional clarification of FENOCs response to the staffs second question addressed in the September 11, 2002, supplement is needed in order to complete the NRC review of the amendment request. The following is a revision of the staffs previous question #2, and refers to the May 31, 2002, applications Attachment C, Criticality Analysis of the Beaver Valley Unit 2 Fresh Fuel Racks, April 2002:
1.
The benchmarking of topical report WCAP-14416 used critical experiments only up to 4.31 w/o U-235 enriched fuel. However the requested amendment is for 5.05 w/o (including the tolerance). Demonstrate whether the bias and uncertainty from the topical report is appropriate by showing how keff would change at this higher enrichment and what if any impact that has on meeting the keff acceptance criteria of 10 CFR 50.68.