VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 March 27, 2002 United States Nuclear Regulatory Commission Serial No.02-179 Attention: Document Control Desk SS&LIBAG RO Washington, D. C. 20555-0001 Docket No.
50-280 50-281 License No. DPR-32 DPR-37 Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 REVISIONS TO EMERGENCY PLAN IMPLEMENTING PROCEDURES Pursuant to 10 CFR 50.54(q), enclosed are revisions to two Surry Power Station Emergency Plan Implementing Procedures. The revisions do not implement actions that decrease the effectiveness of our Emergency Plan.
The Emergency Plan and Implementing Procedures continue to meet the standards of 10 CFR 50.47(b). Please update your manual by performing the actions described in the enclosed tabulation of changes.
Very truly yours, Rich d H Blount, Site ice President Surry Power Station Enclosure Commitments contained in this letter: None.
cc:
U. S. Nuclear Regulatory Commission, Region II (2 copies)
Sam Nunn Atlanta Federal Center 61 Forsyth Street S.W., Suite 23 T85 Atlanta, Georgia 30303-8931 Mr. R. A. Musser NRC Senior Resident Inspector Surry Power Station
Serial No.02-179 Surry EPIP Revisions VIRGINIA ELECTRIC AND POWER COMPANY REVISION TO SURRY POWER STATION EMERGENCY PLAN IMPLEMENTING PROCEDURE Enclosed are revisions to Surry Power Station Emergency Plan Implementing Procedures. Please take the following actions in order to keep your manual updated with the most recent revisions.
REMOVE AND EFFECTIVE INSERT:
EFFECTIVE DESTROY:
DATE:
DATE:
EPIP-1.01, Rev. 42 10/06/00 EPIP-1.01, Rev. 43 03/14/02 EPIP-4.30, Rev. 08 01/25/01 EPIP-4.30, Rev. 09 03/21/02 Emerc,-icy Plan Privacy and Proprietary Material have been removed.
Reference Generic Letter No. 81-27
PURPOSE To initially assess a potential emergency condition and initiate corrective actions.
ENTRY CONDITIONS Any one of the following:
- 1.
Another station procedure directs initiation of this procedure.
- 2.
A potential emergency condition is reported to the Shift Supervisor.
Approvals on File Effective Date ©
ACTION/EXPECTED RESPONSE I -1 RESPONSE NOT OBTAINED I
CAUTION:
Declaration of the highest emergency class for which an Emergency Action Level is exceeded shall be made.
NOTE:
The ERFCS is potentially unreliable in the event of Therefore, ERFCS parameters should be evaluated for an earthquake occur.
1 EVALUATE EMERGENCY ACTION LEVELS:
a) Determine event category using. Emergency Action Level Table Index b)
Review EAL Tab associated with event category c)
Use Control Room monitors,
- ERFCS, and outside reports to get indications of emergency conditions listed in the EAL Table d) Verify EAL -
CURRENTLY EXCEEDED an earthquake.
accuracy should d)
IF basis for EAL no longer exists when discovered AND no other reasons exist for an emergency declaration, THEN do the following:
- RETURN TO procedure in effect.
e GO TO VPAP-2802, NOTIFICATIONS AND REPORTS, to make one-hour, non-emergency reports for classification without declaration.
IF EAL was NOT exceeded, THEN RETURN TO procedure in effect.
(STEP 1 CONTINUED ON NEXT PAGE)
NUMBER PROCEDURE TITLE REVISION EPIP-1.01 EMERGENCY MANAGER CONTROLLING PROCEDURE 43 PAGE 2 of 7
,,I
ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 1
EVALUATE EMERGENCY ACTION LEVELS: (Continued) e) Record procedure initiation:
By:
Date:
Time:
f) Initiate a chronological log of events g) Declare position of Station Emergency Manager NOTE:
Assembly, accountability and/or initiation of facility staffing may not be desired during certaig situations (e.g., security event, severe weather, anticipated grid disturbance) or may have already been completed.
These activities should be implemented as quickly as achievable given the specific situation.
2 CHECK - CONDITIONS ALLOW FOR NORMAL IMPLEMENTATION OF EMERGENCY RESPONSE ACTIONS IF deviation from normal emergency response actions warranted, THEN do the following:
a)
Refer to Attachment 2, Considerations for Operations Response Under Abnormal Conditions.
b) Consider applicability of 50.54(x).
c)
IF classification/assembly announcement deferred.
THEN GO TO Step 4.
NUMBER PROCEDURE TITLE REVISION EPIP-I.01 EMERGENCY MANAGER CONTROLLING PROCEDURE 43 PAGE 3 of 7 I ---
-1 ýSTEP
ACTION/EXPECTED RESPONSE
-4I 3 NOTIFY PLANT STAFF OF ALERT OR HIGHER CLASSIFICATION:
a)
Check classification - Alert OR HIGHER b) Check if emergency assembly and accountability -
PREVIOUSLY CONDUCTED RESPONSE NOT OBTAINED a)
GO TO Step 4.
b)
Do the following:
- 1) Sound emergency alarm and make announcement on station Gai-Tronics system as follows:
"(Emergency classification) has been declared due to "All emergency response personnel report to your assigned stations.
All other personnel report to your Emergency Assembly Area".
- 2) Repeat RNO Step 3.b.1.
- 3)
GO TO Step 4.
c)
Sound emergency alarm and make announcement on station Gai-Tronics system as follows:
"(Emergency classification) has been declared due to d)
Repeat Step 3.c NUMBER PROCEDURE TITLE REVISION EPIP-1.01 EMERGENCY MANAGER CONTROLLING PROCEDURE 43 PAGE 4 of 7 H-I
-LFJ-t ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION:
All further instructions should directed to hold.
be continued through unless otherwise 4
INITIATE SUPPORTING PROCEDURES:
a)
Direct Emergency Communicators to initiate the following:
- 1) EPIP-2.01, NOTIFICATION OF STATE AND LOCAL GOVERNMENTS
- 2) EPIP-2.02, NOTIFICATION OF NRC b)
Check if classification announcement made using Gai-Tronics system b) Notify the following to initiate controlling procedures:
"* HP Shift Supervisor:
EPIP-4.01, RADIOLOGICAL ASSESSMENT DIRECTOR CONTROLLING PROCEDURE
"* Security Shift Supervisor:
EPIP-5.09, SECURITY TEAM LEADER CONTROLLING PROCEDURE NUMBER PROCEDURE TITLE REVISION EPIP-1.01 EMERGENCY MANAGER CONTROLLING PROCEDURE 43 PAGE 5 of 7 I-A I
-LKJ-t ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 5
CHECK TSC - ACTIVATED IF TSC NOT activated, THEN do the following:
a) Have STA report to the Control Room.
b) Notify Operations Manager-On-Call (OMOC) or Superintendent Operations.
c) Evaluate initiation of Operations Department directive for augmenting staff resources during Emergency Plan activation.
d) Evaluate having Radiological Assessment Director report to the Control Room.
6 INITIATE EPIP FOR EMERGENCY CLASSIFICATION IN EFFECT:
"* Notification of Unusual Event EPIP-I.02, RESPONSE TO NOTIFICATION OF UNUSUAL EVENT
"* Alert EPIP-1.03, RESPONSE TO ALERT
"* Site Area Emergency EPIP-1.04, RESPONSE TO SITE AREA EMERGENCY
"* General Emergency EPIP-1.05, RESPONSE TO GENERAL EMERGENCY NUMBER PROCEDURE TITLE REVISION EPIP-1.01 EMERGENCY MANAGER CONTROLLING PROCEDURE 43 PAGE 6 of 7
---4 I
I
ACTION/EXPECTED RESPONSE 7 NOTIFY OFFSITE AUTHORITIES OF EMERGENCY TERMINATION:
a) State and local governments (made by LEOF or CEOF when activated) b)
NRC 8
NOTIFY STATION PERSONNEL ABOUT THE FOLLOWING:
"* Emergency termination
"* Facility de-activation
"* Selective release of personnel
"* Completion and collection of procedures
"* Recovery 9
TERMINATE EPIP-1.01:
- Give completed EPIPs, forms and other applicable records to the Emergency Procedures Coordinator in the TSC
o Completed By:
Date:
Time:
- END -
NUMBER PROCEDURE TITLE REVISION EPIP-1.01 EMERGENCY MANAGER CONTROLLING PROCEDURE 43 PAGE 7 of 7 F-RESPONSE NOT OBTAINED F-l l
I STEPED4
CAUTION:
- Declaration of the highest emergency class for which an EAL is exceeded shall be made.
- Emergency Action Levels shall be conservatively classified based on actual or anticipated plant conditions.
GO TO IF EVENT CATEGORY IS:
TAB
- 1.
Safety, Shutdown, or Assessment System Event......................
A
- 2.
Reactor Coolant System Event......................................
B
- 3.
Fuel Failure or Fuel Handling Accident............................
C
- 4.
Containment Event.................................................
D
- 5.
Radioactivity Event...............................................
E
- 6.
DELETED
- 7.
Loss of Secondary Coolant.........................................
G
- 8.
Electrical Failure................................................
H
- 9.
Fire..............................................................
I
- 10.
Security Event....................................................
J
- 11.
Hazard to Station Operation.......................................
K
- 12.
Natural Events....................................................
L
- 13.
Miscellaneous Abnormal Events.....................................
M NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT PAGE INDEX 1
1 of 38
CONDITION/APPLICABILITY
- 1.
Inability to reach required unit operating condition within T.S. time limits ABOVE CSD CONDITION INDICATION Intentional reduction in power, load, or temperature IAW T.S. Action Statement - HAS COMMENCED CLASSIFICATION NOTIFICATION OF UNUSUAL EVENT AND T.S. Action Statement time limit for condition change CANNOT BE MET
- 2.
Loss of Function needed for unit HSD condition ABOVE CSD CONDITION a) Inability to attain the minimum required heat sink as indicated by loss of the following:
"* Main Feedwater System AND
"* Auxiliary Feedwater AND
- Auxiliary Feedwater Crosstie OR b) Loss of High Head flowpath as indicated by loss of the following:
"* Normal Charging System AND
"* High Head SI System NUMBER ATTACHMENT TITLE REVISION EPIP-l.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB A)
PAGE SYSTEM SHUTDOWN, OR ASSESSMENT 1
SYSTEM SHUTDOWN 2 of 38 SITE AREA EMERGENCY
CONDITION/APPLICABILITY
- 3.
Loss of cooling function needed for Cold Shutdown and Refueling Condition CSD & RSD INDICATION
"* Secondary System cooling capability -
UNAVAILABLE AND
"* Loss of any of the following systems:
"* Component Cooling
"* Residual Heat Removal AND
"* RCS temperature GREATER THAN 1400 F
- 4.
Failure of a safety or relief valve to close after pressure reduction ALL CONDITIONS
ENABLED AND NOTIFICATION OF UNUSUAL EVENT
- Any indication after lift or actuation that Pressurizer Safety or PORV -
REMAINS OPEN AND
- Flow -
NON-ISOLABLE
- MAIN STEAM Excessive flow through Steam Generator Safety or PORV as indicated by rapid RCS cooldown rate -
GREATER THAN 500 F per hour NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB A)
PAGE SYSTEM SHUTDOWN, OR ASSESSMENT 1
SYSTEM EVENT 3 of 38 CLASSIFICATION ALERT
CONDITION/APPLICABILITY
- 5.
Failure of the reactor to trip (ATWT)
POWER OPS & HSD INDICATION
"* Reactor trip setpoint and coincidences -
EXCEEDED AND
"* Automatic reactor trip from RPS - FAILED AND
"* Manual reactor trip from Control Room - FAILED CLASSIFICATION SITE AREA EMERGENCY
- 6.
Trip following ATWT that takes the reactor subcritical POWER OPS & HSD
"* Reactor trip setpoint and coincidences -
EXCEEDED AND
"* Automatic reactor trip from RPS -
FAILED AND
"* Manual reactor trip REQUIRED AND
"* Manual reactor trip from Control Room -
SUCCESSFUL NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB A)
PAGE SYSTEM SHUTDOWN, OR ASSESSMENT 1
SYSTEM EVENT 4 of 38 ALERT
CONDITION/APPLICABILITY
- 7.
Loss of plant communications capability INDICATION
- Station PBX phone system FAILED CLASSIFICATION NOTIFICATION OF UNUSUAL EVENT ALL CONDITIONS AND
"* Station Gai-Tronics system FAILED AND
"* Station UHF radio system FAILED
- 8.
Inability to monitor a significant transient in progress ABOVE CSD CONDITION
- Most (>75%)
or all visual annunciator alarms on panels "A" to "K" -
NOT AVAILABLE AND
"* All computer monitoring capability (e.g., plant
- computer, ERFCS)
NOT AVAILABLE AND
"* Significant transient IN PROGRESS (e.g., reactor trip, SI, turbine runback >25%
thermal reactor power, thermal power oscillations >10%)
AND
- Inability to directly monitor any one of the following using Control Room indications:
"* Subcriticality
"* Core Cooling
"* Heat Sink
"* Vessel Integrity
"* Containment Integrity NUMBER ATTACHMENT TITLE REVISION EPIP-I.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB A)
PAGE SYSTEM SHUTDOWN, OR ASSESSMENT 1
SYSTEM EVENT 5 of 38 SITE AREA EMERGENCY
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 9.
Unplanned loss of safety system annunciators with compensatory indicators unavailable or a transient in progress ABOVE CSD CONDITION
- Unplanned loss of most
(>75%)
or all visual annunciator alarms on panels "A" to "K" for GREATER THAN 15 minutes AND ALERT
- All computer monitoring capability (e.g.. plant
- computer, ERFCS)
NOT AVAILABLE OR Significant transient -
INITIATED OR IN PROGRESS (e.g., reactor trip, SI, turbine runback >25%
thermal reactor power, thermal power oscillations >10%)
- 10. Unplanned loss of most or all safety system annunciators for greater than 15 minutes Unplanned loss of most
(>75%)
or all visual annunciator alarms on panels "A" to "K" for GREATER THAN 15 minutes NOTIFICATION OF UNUSUAL EVENT ABOVE CSD CONDITION
- 11.
Evacuation of Main Evacuation of the Control SITE AREA Control Room with Room with stable shutdown EMERGENCY control NOT established control NOT established within 15 minutes within 15 minutes ALL CONDITIONS
- 12. Evacuation of Main Control Room required ALL CONDITIONS Evacuation of the Control Room with stable shutdown control established within 15 minutes NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB A)
PAGE SYSTEM SHUTDOWN, OR ASSESSMENT 1
SYSTEM EVENT 6 of 38 ALERT
CONDITION/APPLICABILITY
- 1.
RCS leak rate exceeds makeup capacity INDICATION
- Primary system leak (LOCA)
IN PROGRESS CLASSIFICATION SITE AREA EMERGENCY ABOVE CSD CONDITION AND
"* Safety Injection REQUIRED AND
"* RCS subcooling based on Core Exit Thermocouples LESS THAN 300 F
OR RCS inventory cannot be maintained based on pressurizer level or RVLIS indication
- 2.
RCS leak rate limit -
Primary system leak ALERT EXCEEDED determined to be GREATER THAN 50 gpm ABOVE CSD CONDITION AND Pressurizer level can be RESTORED AND MAINTAINED
- 3.
Leak rate requiring IAW T.S.
or leakage plant shutdown ABOVE CSD CONDITION Intentional reduction in power, load, or temperature IAW T.S. 3.1.C leakage limit Action Statement -
HAS COMMENCED NOTIFICATION OF UNUSUAL EVENT NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB B)
PAGE REACTOR COOLANT SYSTEM EVENT 1
7 of 38 I
CONDITION/APPLICABILITY
- 4. Steam generator tube rupture with loss of offsite power ABOVE CSD CONDITION INDICATION
- Steam generator tube rupture -
IN PROGRESS CLASSIFICATION SITE AREA EMERGENCY AND
"* Offsite power to unit specific Transfer Buses (Unit 1: D & F; Unit 2: E & F)
NOT AVAILABLE AND
"* Atmospheric steam release from ruptured Steam Generator OCCURRING OR REQUIRED
- 5.
Excessive Primary to Secondary leakage with loss of offsite power ABOVE CSD CONDITION
- Intentional reduction in power, load, or temperature IAW T.S.
3.1.C.6 leakage limit Action Statement -. HAS COMMENCED AND
- Offsite power to unit specific Transfer Buses (Unit 1: D & F; Unit 2:
NOT AVAILABLE
- 6. Gross Primary to
- Steam Generator tube
- 6.
Gross Primary to Secondary leakage ABOVE CSD CONDITION
- Steam Generator tube rupture -
IN PROGRESS AND
- Safety Injection -
REQUIRED NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB B)
PAGE REACTOR COOLANT SYSTEM EVENT 1
8 of 38 ALERT E & F)
ALERT
CONDITION/APPLICABILITY
- 7.
Loss of 2 of 3 fission product barriers with potential loss of 3rd barrier ALL CONDITIONS INDICATION CLASSIFICATION Any two of a),
b) or c) exist and the third is imminent:
GENERAL EMERGENCY a) Fuel clad integrity failure as indicated by any of the following:
- RCS specific activity GREATER THAN OR EQUAL TO 300 jtCi/gm dose equivalent 1-131 OR 5 or more core exit thermocouples GREATER THAN 12000 F OR CHRRMS (Inside) Containment High Range Radiation Monitor:
RM-RMS-127 or -227, RM-RMS-128 or -228:
GREATER THAN 2 x 103 R/hr OR Outside Containment High Range Radiation Monitor:
RM-RMS-161 or -261, GREATER ]HAN 6.3 x 10 mR/hr b)
Loss of RCS integrity as indicated by any of the following:
- PORV failed open OR Loss of reactor coolant c) Loss of containment integrity as indicated by any of the following:
- Containment pressure GREATER THAN 60 psia and NOT decreasing OR Release path to environment EXISTS NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB B)
PAGE REACTOR COOLANT SYSTEM EVENT 1
9 of 38
CONDITION/APPLICABILITY
- 8.
Fuel failure with steam generator tube rupture ALL CONDITIONS INDICATION Any two of a),
b) or c) exists and the third is imminent:
CLASSIFICATION GENERAL EMERGENCY a)
Fuel clad integrity failure as indicated by any of the following:
- RCS specific activity GREATER THAN OR EQUAL TO 300 ý+/-Ci/gm dose equivalent 1-131 OR 5 or more core exit thermocou ples GREATER THAN 12000 F OR High Range Letdown Radiation Monitor:
1-CH-RM-118, 2-CH-RM-218:
GREATER THAN 7.0x10 6 cpm b)
S/G tube rupture as indicated by both of the following:
e Safety Injection REQUIRED AND
- Steam generator tube rupture IN PROGRESS c)
Loss of Secondary integrity associated with ruptured S/G pathway as indicated by:
- Steam discharge to atmosphere OR Loss of secondary coolant outside containment -
IN PROGRESS NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB B)
PAGE REACTOR COOLANT SYSTEM EVENT 1
10 of 38
CONDITION/APPLICABILITY
- 1.
Core damage with possible loss of coolable geometry INDICATION a) Fuel clad failure as indicated by any of the following:
CLASSIFICATION SITE AREA EMERGENCY ABOVE CSD CONDITION
° RCS Specific activity GREATER THAN 60 pCi/gm dose equivalent 1-131 OR High Range Letdown Radiation Monitor:
1-CH-RM-118, 2-CH-RM-218:
GREATER THAN 1.4x10 6 cpm AND b) Loss of cooling as indicated by any of the following:
5 confirmed core exit thermocouples GREATER THAN 12000 F OR Core delta T -
ZERO OR Core delta T - RAPIDLY DIVERGING NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB C)
PAGE FUEL FAILURE OR FUEL HANDLING ACCIDENT 1
11 of 38
CONDITION/APPLICABILITY
- 2.
Severe Fuel Clad Damage ABOVE CSD CONDITION INDICATION
- RCS specific activity GREATER THAN 300 jiCi/gm dose equivalent 1-131 OR CLASSIFICATION ALERT High Range Letdown Radiation Monitor:
Either of the following indications occur within 30 minutes and remain for at least 15 minutes:
- 3.
Fuel clad damage indication ABOVE CSD CONDITION
- Intentional reduction in power, load, or temperature IAW T.S. 3.1.D reactor coolant activity limit Action Statement HAS COMMENCED NOTIFICATION OF UNUSUAL EVENT OR High Range Letdown Radiation Monitor:
Either of the following indications occur within 30 minutes and remain for at least 15 minutes:
1-CH-RM-118, 2-CH-RM-218:
GREATER THAN 5.8 x 103 cpm NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB C)
PAGE FUEL FAILURE OR FUEL HANDLING ACCIDENT 1
12 of 38 1-CH-RM-118, 2-CH-RM-218:
GREATER THAN 5.8 x 104 cpm
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 4.
Probable large radioactivity release initiated by LOCA with ECCS failure leading to core degradation ABOVE CSD CONDITION
"* Loss of reactor or secondary coolant IN PROGRESS AND RCS specific activity GREATER THAN 300 1iCi/gm dose equivalent 1-131 OR CHRRMS (Inside) Containment High Range Radiation Monitor:
RM-RMS-127 or -227, RM-RMS--128 or -228:
GREATER THAN 2 x 103 R/hr AND High or Low Head ECCS flow -
NOT being delivered to the core (if expected by plant conditions)
- 5.
Probable large radioactivity release initiated by loss of heat sink leading to core degradation ABOVE CSD CONDITION
"* Loss of Main Feedwater System and Condensate System AND
"* Loss of Auxiliary Feedwater System AND
- RHR System -
NOT OPERABLE NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB C)
PAGE FUEL FAILURE OR FUEL HANDLING ACCIDENT 1
13 of 38 GENERAL EMERGENCY GENERAL EMERGENCY
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 6.
Probable large radioactivity release initiated by failure of protection system to bring reactor subcritical and causing core degradation ABOVE CSD CONDITION
- Reactor nuclear power after trip remains GREATER THAN 5%
AND
- RCS pressure GREATER THAN 2485 psig and NOT decreasing OR Containment pressure and temperature RAPIDLY INCREASING
- 7.
Probable large radioactivity release initiated by loss of AC and all feedwater ABOVE CSD CONDITION
- Loss of all onsite and offsite AC power AND
- Turbine Driven Auxiliary Feedwater Pump NOT OPERABLE AND
- Restoration of either of the above NOT LIKELY within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB C)
PAGE FUEL FAILURE OR FUEL HANDLING ACCIDENT 1
14 of 38 GENERAL EMERGENCY GENERAL EMERGENCY
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 8.
Probable large radioactivity release initiated by LOCA with loss of ECCS and containment cooling ABOVE CSD CONDITION
- Loss of reactor or secondary coolant IN PROGRESS AND
"* High or Low Head ECCS flow NOT being delivered to the core (if expected by plant conditions)
AND
"* Containment RS sump temperature GREATER THAN 1900 F and NOT decreasing OR All Containment Spray and Recirculation Spray Systems -
NOT OPERABLE
- 9.
Major fuel damage accident with radioactive release to containment or fuel buildings ALL CONDITIONS
- Water level in reactor vessel during refueling BELOW TOP OF CORE OR Water level in Spent Fuel Pit verified BELOW TOP OF SPENT FUEL AND
- Verified damage to irradiated fuel resulting in readings on Ventilation Vent Kaman Monitor:
RM-VG-131 GREATER THAN 4.2 x 107 pCi/sec NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB C)
PAGE FUEL FAILURE OR FUEL HANDLING ACCIDENT 1
15 of 38 GENERAL EMERGENCY SITE AREA EMERGENCY
CONDITION/APPLICABILITY
- 10.
Fuel damage accident with release of radioactivity to containment or fuel buildings ALL CONDITIONS INDICATION CLASSIFICATION
"* Verified accident involving damage to irradiated fuel AND
"* HP confirms fission product release from fuel OR Readings on Ventilation Vent Kaman Monitor:
RM-VG-131 GREATER THAN 2.8 x 10 5 jiCi/sec
- 11.
Loss of cask/fuel
- Verified loss of all cask/
ALERT containment barriers or fuel containment barriers accidental criticality AND ALL CONDITIONS
- HP confirms fission product release
- 12.
Spent Fuel Storage Facility accident ALL CONDITIONS
- Verified Spent Fuel Storage Cask seal leakage NOTIFICATION OF UNUSUAL EVENT OR Spent Fuel Storage Cask dropped or mishandled NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB C)
PAGE FUEL FAILURE OR FUEL HANDLING ACCIDENT 1
16 of 38 ALERT
CONDITION/APPLICABILITY
- 1.
Extremely high Containment radiation, pressure and temperature ABOVE CSD CONDITION INDICATION Outside Containment High Range Radiation Monitor:
RM-RMS-161 or -261, GREATER IHAN 3.0 X 10i mR/hr OR CLASSIFICATION GENERAL EMERGENCY CHRRMS (Inside) Containment High Range Radiation Monitor:
RM-RMS-127 or -227.
RM-RMS-128 or -228:
GREATER THAN 9 x 103 R/hr AND Containment pressure GREATER THAN 45 psia and is NOT DECREASING OR Containment temperature GREATER THAN 2800 F
- 2.
High Containment radiation, pressure and temperature ABOVE CSD CONDITION
- Outside Containment High Range Radiation Monitor:
RM-RMS-161 or -261, GREATER IHAN 6.3 x 10 mR/hr OR CHRRMS (Inside) Containment High Range Radiation Monitor:
RM-RMS-127 or -227, RM-RMS-128 or -228:
GREATER THAN 2 x 103 R/hr AND
- Containment pressure -
GREATER THAN 23 psia and NOT decreasing OR Containment temperature GREATER THAN 2000 F NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB D)
PAGE ATTACHMENT CONTAINMENT EVENT 1
17 of 38 SITE AREA EMERGENCY
CONDITION/APPLICABILITY
- 3.
High Containment radiation, pressure and temperature ABOVE CSD CONDITION INDICATION
- Outside Containment High Range Radiation Monitor:
RM-RMS-161 or -261 GREATER THAN 24 mR/hr CLASSIFICATION ALERT OR CHRMMS (Inside) Containment High Range Radiation Monitor:
RM-RMS-127 or -227, RM-RMS-128 or -228:
GREATER THAN 1.54 R/hr AND
- Containment pressure GREATER THAN 17.7 psia OR Containment temperature GREATER THAN 1500 F NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB D)
PAGE CONTAINMENT EVENT 1
18 of 38
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 1.
Release imminent or in progress and site boundary doses projected to exceed 1.0 Rem TEDE or 5.0 Rem Thyroid CDE ALL CONDITIONS HP assessment indicates actual or projected doses at or beyond Site Boundary -
GREATER THAN 1.0 Rem TEDE or 5.0 Rem Thyroid CDE
- 2.
Release imminent or in progress and site boundary doses projected to exceed 100 mrem TEDE or 500 mrem Thyroid CDE HP assessment indicates actual or projected doses at or beyond Site Boundary GREATER THAN 100 mrem TEDE or 500 mrem Thyroid CDE ALL CONDITIONS NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB E)
PAGE RADIOACTIVITY EVENT 1
19 of 38 GENERAL EMERGENCY SITE AREA EMERGENCY
CONDITION/APPLICABILITY
- 3.
High radiation or airborne contamination levels indicate a severe degradation in control of radioactive material ALL CONDITIONS INDICATION a) Valid unexpected readings on any of the following monitors have increased by a factor of 1000:
- Control Room RM-R Area CLASSIFICATION ALERT MS-157I
"* Auxiliary Building Control Area
"* Auxiliary Building Drumming Area
"* Decontamination Building Area
"* Fuel Pit Bridge Area
"* New Fuel Storage Area
"* Laboratory Area
"* Sample Room Area RM-RMS-154 RM-RMS-155 RM-RMS-151 iRM-RMS-153 IRM-RMS-152 RM-RMS-158 RM-RMS-156f OR b) Surry Radwaste Facility reports valid unexpected readings on any of the following monitors have increased by a factor of 1000:
.Control Room
! RRM-121
"* Chemistry Laboratory
"* Local Control Panel
"* Bitumen Control Room RRM-122 RRM-129 RRM -130 NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB E)
PAGE ATTACHMENT RADIOACTIVITY EVENT 1
20 of 38
CONDITION/APPLICABILITY
- 4.
Effluent release GREATER THAN 10 times ODCM allowable limit ALL CONDITIONS INDICATION CLASSIFICATION a)
Any of the following monitors ALERT indicate valid readings above specified value for GREATER THAN 15 minutes:
- Vent Vent Kaman RM-VG-131 GREATER THAN 2.84 x 105 ACi/sec
"* Process Vent Kaman RM-GW-130 GREATER THAN 4.59 x 107 PCi/sec
"* Discharge Tunnel RM-SW-120 or
-220 GREATER THAN 3.3 x 105 cpm OR b)
HP assessment (sample results or dose projections) indicates GREATER THAN 10 times ODCM allowable limit OR c)
Surry Radwaste Facility Monitor GREATER THAN 10 times ODCM allowable limit as determined by HP:
- RRM-101: Ventilation Stack Noble Gas monitor OR RRM-131: Liquid Effluent Monitor NUMBER ATTACHMENT TITLE EPIP-1.01 EMERGENCY ACTION LEVEL TABLE ATTACHMENT (TAB E)
RADIOACTIVITY EVENT 1
CONDITION/APPLICABILITY
- 5.
Effluent release GREATER THAN ODCM allowable limit ALL CONDITIONS INDICATION a)
Any of the following monitors indicate valid readings above specified value for GREATER THAN one hour:
"* Vent Vent Kaman RM-VG-131 GREATER THAN 2.84 x 104 liCi/sec
"* Process Vent Kaman RM-GW-130 GREATER THAN 4.59 x 106 pCi/sec
"* Discharge Tunnel RM-SW-120 or
-220 GREATER THAN 3.3 x 104 cpm CLASSIFICATION NOTIFICATION OF UNUSUAL EVENT OR b)
HP assessment (sample results or dose projections) indicate GREATER THAN 100% ODCM allowable limit OR c)
Surry Radwaste Facility Monitor GREATER THAN 100% ODCM allowable limit as determined by HP:
- RRM-101: Ventilation Stack Noble Gas monitor OR RRM-131: Liquid Effluent Monitor NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB E)
PAGE RADIOACTIVITY EVENT 1
22 of 38
CONDITION/APPLICABILITY
- 1. Major Secondary line break with Primary to Secondary leakage GREATER THAN 50 gpm and fuel damage indicated ABOVE CSD CONDITION INDICATION Uncontrolled loss of secondary coolant -
IN PROGRESS AND CLASSIFICATION SITE AREA EMERGENCY RCS specific activity
> 300 1iCi/gm D.E.
1-131 OR High Range Letdown Radiation Monitor on affected pathway 1-CH-RM-118, 2-CH-RM-219:
> 7.0 x 10 cpm AND Condenser Air Ejector Radiation Monitor on affected pathway 1-SV-RM-111, 2-SV-RM-211:
> 1 x 107 cpm OR Vent Vent Kaman Monitor RM-VG-131 > 1.1 x 107 liCi/sec OR Steam Generator Blowdown Radiation Monitor on affected pathway 1-SS-RM-112 or -113, 2-SS-RM-212 or -213:
GREATER THAN 1 x 107 cpm OR Main Steam Line High Range Radiation Monitor on affected pathway RM-RI-MS-124 or
-224 RM-RI-MS-125 or
-225 RM-RI-MS-126 or
-226 GREATER THAN 1.94 mR/hr NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB G)
PAGE LOSS OF SECONDARY COOLANT 1
23 of 38
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 2.
Major Secondary line break with Primary to Secondary leakage GREATER THAN 10 gpm ABOVE CSD CONDITION a) Uncontrolled loss of secondary coolant IN PROGRESS AND ALERT b) Condenser Air Ejector Monitor 1-SV-RM-111, 2-SV-RM-211:
GREATER THAN 1 x 107 cpm OR Vent Vent Kaman Monitor RM-VG-131 GREATER THAN 2.84 x 105 pCi/sec OR Steam Generator Blowdown Radiation Monitor on affected pathway 1-SS-RM-112 or -113, 2-SS-RM-212 or -213:
GREATER THAN 1 x 107 cpm Secondary line Uncontrolled loss of secondary coolant -
IN PROGRESS NOTIFICATION OF UNUSUAL EVENT ABOVE CSD CONDITION NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB G)
PAGE LOSS OF SECONDARY COOLANT 1
24 of 38
- 3.
Major break
CONDITION/APPLICABILITY INDICATION CLASSIFICATION CAUTION:
EAL A.2 is duplicated EAL H.1:
Loss of Function needed for unit HSD condition ABOVE CSD CONDITION below for cross-reference/comparison to a)
Inability to attain the minimum required heat sink as indicated by loss of the following:
"* Main Feedwater System AND
"* Auxiliary Feedwater AND
"* Auxiliary Feedwater Crosstie OR b) Loss of High Head flowpath as indicated by loss of the following:
"* Normal Charging System AND
"* High Head SI System.
- 1. Loss of offsite and onsite AC power for more than 15 minutes ALL CONDITIONS The following conditions exist for GREATER THAN 15 minutes:
"* Offsite power to unit specific Transfer Buses (Unit 1: C & F; Unit 2: E & F)
NOT AVAILABLE AND
"* Station Service Buses A, B, & C -
DE-ENERGIZED AND
"* Emergency Buses H & J DE-ENERGIZED NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB H)
PAGE ATTACHMENT ELECTRICAL FAILURE 1
25 of 38 SITE AREA EMERGENCY SITE AREA EMERGENCY M
ýý
CONDITION/APPLICABILITY INDICATION CLASSIFICATION CAUTION:
EAL A.2 is duplicated EAL H.2:
Loss of Function needed for unit HSD condition ABOVE CSD CONDITION below for cross-reference/comparison to a) Inability to attain the minimum required heat sink as indicated by loss of the following:
"* Main Feedwater System AND
"* Auxiliary Feedwater AND
"* Auxiliary Feedwater Crosstie OR b) Loss of High Head flowpath as indicated by loss of the following:
"* Normal Charging System AND
"* High Head SI System
- 2.
Loss of all offsite and onsite AC power ALL CONDITIONS
- Offsite power to unit specific Transfer Buses (Unit 1: D & F; Unit 2: E & F)
NOT AVAILABLE AND
"* Station Service Buses A, B, & C -
DE-ENERGIZED AND
"* Emergency Buses H & J DE-ENERGIZED NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB H)
PAGE ELECTRICAL FAILURE 1
26 of 38 SITE AREA EMERGENCY ALERT
CONDITION/APPLICABILITY
- 3.
Loss of offsite power or onsite AC power capability ALL CONDITIONS INDICATION o Offsite power to unit specific Transfer Buses (Unit 1: D & F; Unit 2: E & F)
NOT AVAILABLE CLASSIFICATION NOTIFICATION OF UNUSUAL EVENT OR Unit Main Generator and both Emergency Diesel Generators OUT OF SERVICE
- 4.
Loss of all onsite DC power for GREATER THAN 15 minutes ALL CONDITIONS
- 5.
Loss of all onsite DC power ALL CONDITIONS The following conditions exist for GREATER THAN 15 minutes:
"* All Station Battery voltmeters -
ZERO (0)
VOLTS AND No light indication available to Reserve Station Service Breakers
- 15D1, 15E1 and 15F1
- All Station Battery
- All Station Battery voltmeters ZERO (0)
VOLTS AND
- No light indication available to Reserve Station Service Breakers 15D1,
- 15E1, and 15F1 NUMBER ATTACHMENT TITLE REVISION EPIP-l.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB H)
PAGE ELECTRICAL FAILURE 1
27 of 38 SITE AREA EMERGENCY ALERT
CONDITION/APPLICABILITY
- 1. Fire resulting in degradation of safety systems ABOVE CSD CONDITION INDICATION
- Fire which causes major degradation of a safety system function required for protection of the public CLASSIFICATION SITE AREA EMERGENCY AND
- Affected systems are caused NOT to be operable as defined by T.S. 1.0.D and T.S. 3.0.2
- 2.
Fire potentially Fire which has potential ALERT affecting station for causing a safety system safety systems NOT to be operable as defined by T.S. 1.0.D and ABOVE CSD CONDITION and T.S. 3.0.2
- 3.
Fire lasting GREATER THAN 10 minutes ALL CONDITIONS Fire in the Protected Area or Switchyard which is not under control within 10 minutes after Fire Brigade DISPATCHED NOTIFICATION OF UNUSUAL EVENT NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB I)
PAGE FIRE 1
28 of 38
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 1.
Loss of Station physical control ALL CONDITIONS
- Shift Supervisor has been informed that the Security force has been neutralized by attack, resulting in loss of physical control of station OR Shift Supervisor has been informed of intrusion into one or more Vital Areas which are occupied or controlled by an aggressor
- 2.
Imminent loss of Supervisor Security Shift SITE AREA physical Station control has notified the Shift EMERGENCY Supervisor of imminent ALL CONDITIONS intrusion into a Vital Area
- 3.
Ongoing Security Supervisor Security Shift ALERT compromise or bomb has notified the Shift potentially affecting Supervisor of a confirmed station safety systems un-neutralized intrusion into the Protected Area ALL CONDITIONS or ISFSI OR Shift Supervisor notified of a verified bomb discovered on or near a safety related system NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB J)
PAGE SECURITY EVENT 1
29 of 38 GENERAL EMERGENCY I
CONDITION/APPLICABILITY
- 4.
Security threat, unauthorized attempted entry, or attempted sabotage ALL CONDITIONS INDICATION Any of the following when determined to have potential for degrading the level of safety of the plant or ISFSI
"* Receipt of a credible site-specific threat from
- Security, NRC or FBI
"* Confirmed hostage situation
"* Civil disturbance
"* Discovery of a bomb device (other-than on or near a safety-related system which represents an on-going security compromise)
"* Confirmed attempted intrusion (Protected Area or ISFSI)
- Attempted sabotage NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB J)
PAGE ATTACHMENT SECURITY EVENT 1
30 of 38 CLASSIFICATION NOTIFICATION OF UNUSUAL EVENT
CONDITION/APPLICABILITY
- 1.
Aircraft damage to vital plant systems ABOVE CSD CONDITION INDICATION Aircraft crash adversely affects vital structures by impact or fire CLASSIFICATION SITE AREA EMERGENCY
- 2.
Aircraft crash on
- Aircraft crash within ALERT the facility the Protected Area or Switchyard ALL CONDITIONS
- 3.
Aircraft crash or, unusual aircraft activity
- Confirmed notification of aircraft crash within the site boundary NOTIFICATION OF UNUSUAL EVENT ALL CONDITIONS OR Unusual aircraft activity in the vicinity of the site as determined by the Shift Supervisor or Supervisor Security Shift
- 4.
Severe explosive damage Explosion which results SITE AREA in severe degradation of EMERGENCY any systems required for ABOVE CSD CONDITION safe shutdown
- 5.
Explosion damage to Unplanned explosion ALERT facility resulting in damage to plant structure ALL CONDITIONS or equipment that affects plant operations
- 6.
Onsite explosion ALL CONDITIONS Confirmed report of unplanned explosion within Protected Area or Switchyard NOTIFICATION OF UNUSUAL EVENT NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB K)
PAGE HAZARD TO STATION OPERATION 1
31 of 38
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 7.
Entry of toxic or flammable gases or liquids into plant vital areas other than the Control Room ABOVE CSD CONDITION
- Uncontrolled release of toxic or flammable agents into Vital Areas AND
- Evacuation of Vital Area other than Control Room -
REQUIRED OR Loss of a safety system function required for protection of the public
- 8.
Entry of toxic or flammable gases or liquids into plant facility ALL CONDITIONS Uncontrolled release of toxic or flammable agent which causes:
"* Evacuation of personnel from plant areas AND
"* Safety related equipment to be rendered inoperable
- 9.
Onsite or nearsite release of toxic or flammable liquids or gases ALL CONDITIONS Unplanned release of toxic or flammable agents which may affect safety of station personnel or equipment NOTIFICATION OF UNUSUAL EVENT NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB K)
PAGE HAZARD TO STATION OPERATION 1
32 of 38 SITE AREA EMERGENCY ALERT
CONDITION/APPLICABILITY
- 10. Severe missile damage to safety systems ABOVE CSD CONDITION INDICATION Missile impact causing severe degradation of safety systems required for unit shutdown CLASSIFICATION SITE AREA EMERGENCY
- 11. Missile damage to Notification of missile ALERT safety related impact causing damage equipment or structures to safety related equipment or structures ABOVE CSD CONDITION
- 12. Turbine failure with Failure of turbine/
ALERT penetration generator rotating equipment resulting POWER in casing penetration
- 13. Turbine rotating component failure with no casing penetration Failure of turbine/
generator rotating component resulting in unit trip NOTIFICATION OF UNUSUAL EVENT POWER & STARTUP NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB K)
PAGE Al-IACIMEIT HAZARD TO STATION OPERATION 1
33 of 38
CONDITION/APPLICABILITY
- 1.
Earthquake GREATER THAN DBE levels ABOVE CSD CONDITION INDICATION
- Earthquake which activates the Event Indicator on the Strong Motion Accelerograph CLASSIFICATION SITE AREA EMERGENCY AND
- Safety related systems are significantly degraded by earthquake OR AP-37.00, SEISMIC EVENT, calculations indicate horizontal motion of 0.15g or GREATER
- 2.
Earthquake GREATER THAN OBE levels ALL CONDITIONS
- Confirmed earthquake which activates Event Indicator on the Strong Motion Accelerograph AND
- Safety related equipment is rendered inoperable by earthquake OR AP-37.00.
SEISMIC EVENT, calculations indicate horizontal motion of O.07g or GREATER
- 3.
Earthquake detected ALL CONDITIONS Confirmed earthquake which activates the Event Indicator on the Strong Motion Accelerograph NOTIFICATION OF UNUSUAL EVENT NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB L)
PAGE ATTACHMENT NATURAL EVENTS 1
34 of 38 ALERT I
CONDITIONS/APPLICABILITY
- 4.
Tornado striking facility ALL CONDITIONS INDICATION Tornado visually detected striking structures within the Protected Area or Switchyard CLASSIFICATION ALERT
- 5.
Tornado within Protected Area or Switchyard ALL CONDITIONS Tornado visually detected within Protected Area or Switchyard NOTIFICATION OF UNUSUAL EVENT
- 6.
Sustained winds in excess Sustained winds 150 mph SITE AREA of design levels OR GREATER experienced EMERGENCY experienced or projected or projected ABOVE CSD CONDITION
- 7.
Hurricane winds near Hurricane winds 120 mph ALERT design basis level OR GREATER experienced experienced or projected or projected ALL CONDITIONS
- 8.
Hurricane force winds projected onsite within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
"* "Inland High Wind Warning for Hurricane Force Winds" in effect for Surry County NOTIFICATION OF UNUSUAL EVENT ALL CONDITIONS OR Sustained hurricane force winds (GREATER THAN 73 mph) projected onsite within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> NUMBER ATTACHMENT TITLE REVISION EPIP-l.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB L)
PAGE NATURAL EVENTS 1
35 of 38
CONDITION/APPLICABILITY
- 9.
Flood or low water level above design levels ALL CONDITIONS INDICATION
- Flood in the James River -
GREATER THAN
+27 feet MSL (station operating level)
CLASSIFICATION SITE AREA EMERGENCY OR Water level in the James River -
LESS THAN
-9 feet MSL as indicated by loss of Emergency SW Pump suction
- 10.
Flood or low water level near design levels ALL CONDITIONS
- Flood in the James ALERT River GREATER THAN
+21 feet MSL (Emergency Service Water Pump House entrance is at +21 1/6 feet) but LESS THAN +27 feet MSL (Site Area Emergency criteria)
OR Water level in Surry Power Station Intake Canal -
LESS THAN
+23 1/2 feet and decreasing
- 11.
Flood or low water level ALL CONDITIONS
- Flood in the James River -
GREATER THAN
+12 feet MSL (CW pump motors and entrance to the CW pump pits are at
+12 1/2 feet MSL) but LESS THAN +21 feet MSL (Alert criteria)
NOTIFICATION OF UNUSUAL EVENT OR Water level in Surry Power Station Intake Canal (CW-LI-101,
-201)
LESS THAN +23 1/2 feet and NOT increasing NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB L)
PAGE ATTACHMENT NATURAL EVENTS 1
36 of 38
CONDITION/APPLICABILITY INDICATION CLASSIFICATION
- 1.
Any major internal or external event which singly or in combination cause massive damage to station facilities or may warrant evacuation of the public Shift Supervisor/
Station Emergency Manager judgement GENERAL EMERGENCY ALL CONDITIONS
- 2.
Station conditions which Shift Supervisor/
SITE AREA may warrant noti'ication Station Emergency EMERGENCY of the public near the Manager judgement site ALL CONDITIONS
- 3.
Station conditions which have the potential to degrade or are actually degrading the level of safety of the station Shift Supervisor/
Station Emergency Manager judgement ALL CONDITIONS NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB M)
PAGE MISCELLANEOUS ABNORMAL EVENTS 1
37 of 38 ALERT
CONDITION/APPLICABILITY
- 4.
Station conditions which warrant increased awareness of state and/
or local authorities ALL CONDITIONS INDICATION Shift supervisor judgment that any of the following exist:
CLASSIFICATION NOTIFICATION OF UNUSUAL EVENT
- Unit shutdown is other than a controlled shutdown OR Unit is in an uncontrolled condition during operation OR A condition exists which has the potential for escalation and, therefore, warrants notification NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 EMERGENCY ACTION LEVEL TABLE 43 ATTACHMENT (TAB M)
PAGE MISCELLANEOUS ABNORMAL EVENTS 1
38 of 38
This attachment provides procedural guidance for controlling selected emergency response actions when their implementation would have adverse results.
Station Emergency Manager (SEM) approval is required before any required action is postponed, suspended or modified.
The guidance below is not all-inclusive.
UNANTICIPATED HAZARD EXISTS (e.g., security event, tornado or toxic release):
IF implementation of emergency response actions could compromise Security Plan response strategies, THEN consider postponing or suspending emergency response actions until threat has been resolved, e.g., on-site announcement directing assembly and emergency response facility activation, pager activation and call out per EPIP-3.05, AUGMENTATION OF EMERGENCY RESPONSE ORGANIZATION, dispatch of Security Team members to the LEOF per EPIP-3.04, ACTIVATION OF LOCAL EMERGENCY OPERATIONS FACILITY, and staging of road blocks per EPIP-5.04, ACCESS CONTROL.
IF assembling on-site personnel for accountability or activation of emergency response facilities could endanger plant personnel, THEN consider postponing emergency assembly until hazardous conditions are resolved.
(Consider having Corporate Security notify corporate emergency response organization only using CPIP-3.4, INNSBROOK SECURITY SUPPORT, and notifying personnel in unaffected areas on-site selectively.)
IF notifying augmentation could create a safety hazard for personnel coming to the station, THEN consider postponing augmentation notification.
(Consider having Corporate Security notify corporate emergency response organization only using CPIP-3.4, INNSBROOK SECURITY SUPPORT, or defering notifications until hazardous conditions are resolved.)
ANTICIPATED SITUATION (e.g., forecasted severe weather or grid disturbance):
IF all or part of the ERO has been staged in anticipation of a predicted
- event, THEN notify Security to omit performance of augmentation notification (as described in EPIP-3.05, AUGMENTATION OF EMERGENCY RESPONSE ORGANIZATION).
IF adequate controls have been established to continually account for personnel staged in anticipation of a predicted event, THEN notify Security to omit performance of initial accountability (as described in EPIP-5.03, PERSONNEL ACCOUNTABILITY).
IF a decision has been made to staff the Central EOF in lieu of the LEOF, THEN notify Security that performance of EPIP-3.04, ACTIVATION OF LOCAL EMERGENCY OPERATIONS FACILITY, is not required.
IF environmental conditions are hazardous, THEN consult with Security Team Leader about suspending procedural requirements for staging road blocks (IAW EPIP-5.04, ACCESS CONTROL).
NUMBER ATTACHMENT TITLE REVISION EPIP-1.01 CONSIDERATIONS FOR OPERATIONS
RESPONSE
43 ATTACHMENT UNDER ABNORMAL CONDITIONS PAGE 2
1 of 1
PURPOSE To provide instructions for execution of the MIDAS Class A Model.
ENTRY CONDITIONS Any one of the following:
- 1.
Entry from EPIP-4.01, RADIOLOGICAL ASSESSMENT DIRECTOR CONTROLLING PROCEDURE.
- 2.
Entry from EPIP-4.03, DOSE ASSESSMENT TEAM CONTROLLING PROCEDURE.
- 3. Direction by the Radiological Assessment Director or Radiological Assessment Coordinator.
Approvals on File Effective Date O VZ
I N CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE I-I RESPONSE NOT OBTAINED NOTE:
e Dose assessments should be performed within 15 minutes after a radiological release. MIDAS may underestimate the effects of a release which begins or ends during the current 15-minute period.
e An abnormal run is one in which a red bar containing messages that meteorological or radiation monitor data is missing appears on the screen.
o Pressing the DIALOG key causes tte terminal to display three lines of text and allows the operator to read system messages during a run.
- Attachment 2, Design Basis Accident assumptions and default values used 1 INITIATE PROCEDURE:
a)
By:
Date:
Time:
b)
Press START/STOP button (the top button near the lower right front of terminal) c) Ensure STOP/START button stays in the engaged position d) Press LOCK key on the keyboard e) Verify LOCK and TEK indicating lights - ON f) Verify MIDAS in one of the following locations being used:
"* Surry HP Office
"* Surry TSC
"* Surry LEOF Technical Overview, provides in the MIDAS code and EPIPs.
e)
Do the following:
- 1) Notify RAD/RAC MIDAS terminal malfunctioning.
- 2) Initiate Attachment 1.
f)
IF in
- CEOF, THEN ensure "Black Box" ABC switch positioned to "B" for Surry.
g) Verify -
INITIAL MIDAS RUN g)
GO TO Step 5.
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 2 of 23 H-l l
-GEH
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT-exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSEill-'
RESPONSE NOT OBTAINED 2 DO INITIAL ASSESSMENT:
a) Press RETURN b) Verify USERNAME displayed b) IF "Local>" appears, THEN type C SMIDAS and RETURN TO Step 2.a.
IF message "Local-715 or Local-013" appears, THEN do the following:
- 1) Press CTRL K keys.
- 2)
WHEN "Local>" appears, type C NMIDAS.
THEN
- 3) Wait for USERNAME to appear.
- 4)
IF USERNAME appears, THEN do the following:
a)
GO TO Step 2.c.
b) Continue using manually entered monitor and met data.
IF USERNAME does NOT appear, THEN do dose assessment using manual EPIPs.
c) Type MIDAS d) Press RETURN e) Verify MIDAS in one of the following locations being used:
"* Surry HP Office
"* Surry TSC
"* Surry LEOF (STEP 2 CONTINUED ON NEXT PAGE) e) lF in CEOF, THEN do the following:
- 1) Type SU (Surry Site ID).
- 2) Press RETURN.
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 3 of 23 H-L
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image), which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
-F-
ýTE ACTION/EXPECTED RESPONSE K-H RESPONSE NOT OBTAINED 2
DO INITIAL ASSESSMENT: (Continued) f)
WHEN the following prompt appears ENTER: [51]
[S2]
[R1]
[R2]
[EX]
SURRY SURRY SURRY SURRY EXIT 1
2 1 TREND 2 TREND THEN type appropriate unit (S1 or S2) g) Press RETURN h)
WHEN the appears
[XX]
[XXX]
[FM]
[CTRL-Z]
following prompt FUNCTION OR TASK CODE FUNCTION AND TASK CODE FUNCTION MENU EXIT THEN type TS (touch screen) i)
Press RETURN j)
Verify MIDAS connected to Surry VAX k) Check if quick assessment desired
- 1) Touch REAL TIME QUICK DOSE PROJECTIONS on the ACCIDENT RUN MENU SELECTION screen j)
IF MIDAS is connected to North Anna VAX (i.e., connection made using C NMIDAS),
THEN GO TO Step 7.
k)
GO TO Step 5.
m) Touch CONFIRM NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 4 of 23 H-I I
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image), which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
7 LFJ-E1ý
ý ACTION/EXPECTED RESPONSE F-]
RESPONSE NOT OBTAINED NOTE:
e Meteorological (MET) parameters with good values are backlit in gray with their value under the parameter name.
e Rate of rainfall (inches per 15 minutes) may be obtained from the Weather Center (Innsbrook, 8-730-3025).
Zero (0) may be entered if data is not available.
However, using zero during periods of rainfall may yield unrepresentative results.
e The Stability Class letter designator (A-G) should be used in lieu of a Delta T numerical value.
This is preferred because numerical values must be entered in OF, but station monitoring systems display the parameter in °C.
- EPIP-4.10, Determination of X/0, meteorological information, e.g.
measurements unavailable.
3 ENTER METEOROLOGICAL DATA:
a)
Check gray boxes APPEAR b)
Touch RAIN box c) Put in rate of rainfall (inches per 15 minutes) d) Touch CONFIRM e)
GO TO Step 3.j f)
Do one of the following:
"* Use LAST MET and touch each box to activate parameter OR
"* Touch box for each MET parameter to be entered and put in value using the NUM pad g) Verify the entered value appears under the parameter name contains instructions for getting inches rainfall, when on-site a)
GO TO Step 3.f.
g) Enter parameter value again.
(STEP 3 CONTINUED ON NEXT PAGE)
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 5 of 23 l
l
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment-and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes.
Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
-LIiEJ-E ACTION/EXPECTED RESPONSE
-H RESPONSE NOT OBTAINED 3
ENTER METEOROLOGICAL DATA: (Continued) h)
Ensure values for each of the following parameters are entered (touch the appropriate box and enter the value using the NUM pad as needed):
- Delta temperature [enter letter of Stability Class (A-G) in Delta T field]:
"* Upper and lower wind speed (mph)
"* Lower wind direction (degrees)
"* Ambient temperature (OF)
"* Rain (inches per 15 minutes) i) Touch CONFIRM after all MET parameters are correctly entered (STEP 3 CONTINUED ON NEXT PACE)
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 6 of 23 DELTA T (°C)
SIGMA THETA (0)
STABILITY CLASS
_< -0.67
>_ 22.5 A (most unstable)
-0.66 to -0.60 22.4 to 17.5 B
-0.59 to -0.53 17.4 to 12.5 C
-0.52 to -0.18 12.4 to 7.5 D
-0.17 to +0.53 7.4 to 3.8 E
+0.54 to +1.41 3.7 to 2.1 F
> +1.41
< 2.1 G (most stable)
I
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1. TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2. SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
-ThJ-z ACTION/EXPECTED RESPONSE
-I RESPONSE NOT OBTAINED 3
ENTER METEOROLOGICAL DATA: (Continued) j)
Verify run proceeds into calculation mode j)
IF Red Warning message appears (i.e., rad monitor data invalid),
THEN do the following:
- 1) Touch EXIT.
- 2)
RETURN TO Step 2.j.
4 GET REPORTS:
a)
Check if SPECIAL REPORT appears following calculation routine a)
IF DATA RESULT SCREEN appears, THEN touch CONTINUE multiple times to step through data results and calculation routine until the SPECIAL REPORT appears.
b)
Make a print of SPECIAL REPORT (touch "D COPY/S COPY")
c)
Touch CONTINUE d)
WHEN page 1 of the RADIOLOGICAL STATUS REPORT appears, THEN press "D COPY/S COPY" e) Touch CONTINUE f)
WHEN page 2 of the RADIOLOGICAL STATUS REPORT appears, THEN press "D COPY/S COPY" g)
Touch MORE REPORTS h) Wait for MORE REPORTS SELECTION screen to appear i) Touch box for MET,
- RAD, X/Q, DOSE
SUMMARY
report (STEP 4 CONTINUED ON NEXT PAGE)
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 7 of 23 1-I
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE: e MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT) 0 Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
-Ei-E ACTION/EXPECTED RESPONSE 1-LI RESPONSE NOT OBTAINED I
4 GET REPORTS: (Continued) j)
Touch CONFIRM 0
CAUTION:
The Quick Dose option uses available valid automatic inputs to calculate a dose projection without identifying invalid inputs to the user.
Therefore, if current radiation monitor or flow readings for the release pathway are recognized as invalid, the Quick Dose result will exclude these parameters and may yield an invalid (nonconservative) estimate.
k) Check current radiation monitor and flow readings appear for expected release paths k)
IF MET,
- RAD, X/Q.
DOSE
SUMMARY
report indicates Quick Dose results are suspect, e.g.,
release path excluded from dose calculation, THEN do the following:
- 1)
Record note on RADIOLOGICAL STATUS REPORT indicating it appears to be based on incomplete inputs and is not to be used.
- 2)
Do one of the following:
"* IF MIDAS dose projections to be continued using operator input, THEN GO TO Step 6.
"* IF hand-calculations to be used for evaluation of release consequences, THEN initiate EPIP-4.08, INITIAL OFFSITE RELEASE ASSESSMENT.
- 1) Touch CONTINUE (STEP 4 CONTINUED ON NEXT PAGE)
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 8 of 23 B
q I
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE: ° MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE 4
GET REPORTS: (Continued) m) Touch EXIT TO MORE REPORTS n)
Touch REPORTS o)
Check with RAD/RAC about need for the following specific reports (to support State assessments):
"* DOSE/DOSE RATE PLOTS
"* Additional SPECIAL REPORT
"* Additional RADIOLOGICAL STATUS REPORT p) Touch box for desired report q) Touch CONFIRM r) Check if REPORT PARAMETER SELECTION screen appears s) Set projection time on REPORT PARAMETER SELECTION SCREEN:
- 1) Touch PROJ.
TIME box to scroll to duration specified by RAD/RAC (Use 2-hour default duration if no duration specified)
- 2) Touch CONFIRM RESPONSE NOT OBTAINED o)
WHEN NO additional reports are
- needed, THEN do the following:
- 1)
Touch EXIT twice to return to the ACCIDENT RUN MENU SELECTION SCREEN.
- 2)
GO TO Step 16.
r)
GO TO Step 15.
t)
GO TO Step 15 NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 9 of 23 m
I
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to
.,previous screen.
CONFIRM is selected to continue model processing whtin all, information on screen is correct.
EXIT exits the modeling process.- Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
- Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes.
Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE
[-
RESPONSE NOT OBTAINED NOTE:
CHRRMS (Unit 1:
RMS-127/128, Unit 2:
RMS-227/228) readings may be used to select MIDAS LOCA accident type.
5 DO ENHANCED DOSE ASSESSMENT WITH DEFAULT DATA:
a) Verify MIDAS system default data to be used (i.e., real time meteorological and radiation monitor data, and default accident isotope mix) b) Touch REAL TIME ENHANCED DOSE PROJECTIONS c) Touch CONFIRM a)
GO TO Step 7.
(STEP 5 CONTINUED ON NEXT PAGE)
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 10 of 23 H-HOURS CONTAINMENT HIGH RANGE RADIATION AFTER LOCA MONITOR READING (R/hr) 0
Ž1.3E+4
Ž4.5E+2
Ž1.54 1
Ž5.OE+3
ý1.8E+2
Ž1.3 2
Ž3.7E+3 1.4E+2
Ž1.2 4
- 2.8E+3
Ž8.6E+1
Ž1.0 MIDAS ACCIDENT LOCA LOCA LOCA TYPE SELECTION MELT GAP PC I
-- ýSTEP
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 5
DO ENHANCED DOSE ASSESSMENT WITH DEFAULT DATA: (Continued) d)
WHEN DBA ACCIDENT TYPE SELECTION screen appears, THEN touch the selection box for the accident type as specified by RAD/RAC:
"* MSLB (Main Steam Line Break)
"* SGTR (Steam Generator Tube Rupture)
"* FUEL HANDLING (in Fuel Building only)
"* WGTR (Waste Gas Decay Tank Rupture)
"* LOCA -
PC (PRI COOL)
"* LOCA -
GAP
"* LOCKED ROTOR e) Touch CONFIRM f)
RETURN TO Step 3 6 RETURN TO ACCIDENT RUN MENU SELECTION SCREEN:
a)
Touch CONTINUE b)
Touch EXIT TO MORE REPORTS c) Touch MORE REPORTS d)
Touch EXIT twice to return to the ACCIDENT RUN MENU SELECTION screen NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 11 of 23
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
- Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point I is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes.
Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE I
RESPONSE NOT OBTAINED CAUTION:
Only use monitor values from 1-RM-VG-110 or 1-RM-GW-102 if 1-RM-VG-131-1 or 1-RM-GW-130-1 are unavailable.
Values for 1-RM-VG-110 and 1-RM-GW-102 must be corrected due to vacuum in the detector chamber by the following equation:
Corrected CPM = Indicated CPM X [30 + (30
- inches Hg)]
NOTE:
- Each input screen will appear with preselected values backlit in white.
Changes are made by pressing the appropriate box and using the touch screen keypad in the upper right quadrant on the screen.
Keypad entries are entered by touching EN on the keypad.
Times between midnight and 0100 must be entered as 2400 through 2459 using the previous date.
- Use of bad radiation monitor or source term data (equal to zero) during a previous run will require selection of a new (different) release option.
7 USE REAL TIME ALL SCREEN DOSE PROJECTIONS TO DO ENHANCED DOSE ASSESSMENT WITH OPTIONAL OPERATOR INPUT DATA:
a) Verify user input is desired for Release Date/Time, Release Option, Monitor Data or Sample Data b) Touch REAL TIME ALL SCREEN DOSE PROJECTIONS c)
Touch CONFIRM d)
WHEN MISCELLANEOUS PARAMETERS screen appears, THEN verify default choices are to be used a)
RETURN TO Step 5.
d) Adjust choices on the MISCELLANEOUS PARAMETERS screen per RAD/RAC instructions OR Touch MANUAL if manual input of weather data is desired.
e) Touch CONFIRM NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A-MODEL 9
PAGE 12 of 23 I-I i
_IH14
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
- RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:
o Run type is preset to PROJECTED (FORECAST)
DOSE.
o PROJECTION TIME (HOURS) is preset to 1, 2, 4 and 8.
__8 INPUT DATE AND TIME INFORMATION:
a)
WHEN RUN MODE AND INTEGRATION TIME SELECTION screen appears, THEN verify current date/time to be used a) IF current date/time NOT to be used, THEN do the following:
- 1) Touch START DATE OF INTEGRATION and then use the touch screen NUM pad to enter date in the format:
MO/DY/YR HR:MN.
(MIDAS will provide "/" marks between the pairs of digits for month, day and year, and a colon between the pairs of digits for hours and minutes.)
- 2) Touch EN when entry is complete.
b)
Touch CONFIRM NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 13 of 23 I
I I
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image), which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
-~-
ýTE ACTION/EXPECTED RESPONSE I-]
RESPONSE NOT OBTAINED NOTE:
If rad data was bad or the source term data was equal to zero in a previous run, a new release option must be selected different from the one previously selected.
9 SELECT RELEASE (SOURCE TERM)
OPTION:
a) Use RELEASE OPTION SELECTION screen b) Select one of the following release options:
RELEASE OPTIONS SELECTION AND TRANSITION STEPS Radiation monitor data is available
- 1)
Touch MANUAL ENTRY OF EACH for manual entry and/or predictive MONITOR READING dose assessment is desired based on
- 2)
Touch CONFIRM a potential release
- 3)
GO TO Step 10
- 1) Touch MONITOR DATA FROM Radiation monitor data is available V & F FILE from file
- 2)
Touch CONFIRM
- 3)
GO TO Step 12 Isotopic release rates are available
- 1)
Touch MANUAL ENTRY OF for manual entry and/or predictive ISOTOPE RELEASE RATE dose assessment is desired based on
- 2)
Touch CONFIRM a potential release
- 3)
GO TO Step 11 Isotopic concentrations and flow
- 1)
Touch MANUAL ENTRY OF rates of each release path are known, ISOTOPE CONCENTRATION and/or predictive dose assessment is
- 2)
Touch CONFIRM desired based on a potential release
- 3)
GO TO Step 11
- 1)
Touch DEFAULT DBA ACCIDENT Design Basis Assident Default (DBA)
- 2)
Touch CONFIRM
- 3)
GO TO Step 12 NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 14 of 23 l
l
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
- Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1. TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes.
Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE F-I RESPONSE NOT OBTAINED CAUTION:
- Double counting will occur if more than one monitor in each release pathway is entered.
- Default flow rates will automatically be used if flow rates are not entered and may result in overconservative dose projections.
NOTE:
& Monitor readings may be obtained from ERFCS Group Review screens if RMS data is not available to MIDAS.
- Monitor readings from RM-VG-123 (Vent Vent High Range) or RM-GW-122 (Process Vent High Range) may be obtained from Operations if Kaman monitors (RM-VG-131 or RM-GW-130) or Victoreen monitors (RM-VG-11O or RM-GW-102) are offscale or out of service.
e CHRRMS (Unit 1:
RMS-127/128, Unit 2:
RMS-227/228) readings may be used to select MIDAS LOCA accident type.
HOURS CONTAINMENT HIGH RANGE RADIATION AFTER LOCA MONITOR READING (R/hr) 0
Ž1.3E+4
Ž4.5E+2
Ž1.54 1
Ž5.OE+3
Ž1.8E+2
Ž1.3 2
Ž3.7E+3
Ž1.4E+2 21.2 4
Ž2.8E+3
Ž8.6E+I
Ž1.0 MIDAS ACCIDENT LOCA LOCA LOCA TYPE SELECTION MELT GAP PC 10 ENTER MONITOR DATA MANUALLY:
(STEP 10 CONTINUED ON NEXT PAGE)
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 15 of 23 H-I
-- ýSTEP
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 10 ENTER MONITOR DATA MANUALLY:
(Continued) a)
WHEN DBA ACCIDENT TYPE SELECTION screen appears, THEN touch the selection box for the accident type as specified by RAD/RAC:
"* MSLB (Main Steam Line Break)
"* SGTR (Steam Generator Tube Rupture)
"* FUEL HANDLING (in Fuel Building only)
"* WGTR (Waste Gas Decay Tank Rupture)
"* LOCA -
GAP
"* LOCA -
"* LOCKED ROTOR b)
Touch CONFIRM c)
WHEN RADIATION MONITOR READINGS screen appears, THEN do the following:
- 1) Touch the box for each monitor to be entered (one at a time)
- 2) Enter radiation and flow values for each monitor using EN on the NUM pad (Enter monitor and flow rate values by making two entries on the NUM pad separated by a comma; e.g., 1E6,25000 for cpmflow rate)
- 3)
WHEN entry for one monitor is
- complete, THEN repeat Step 1O.c.1 through 1O.c.2 until all monitor data is entered (STEP 10 CONTINUED ON NEXT PAGE)
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 16 of 23
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1. TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
-LI J-TE ACTION/EXPECTED RESPONSE H-RESPONSE NOT OBTAINED 10 ENTER MONITOR DATA MANUALLY: (Continued) d)
WHEN all entries have been
- made, THEN touch CONFIRM e) GO TO Step 13 NOTE:
o An input is required for each active release point.
o Zero is an acceptable input for radiation level or flow.
11 ENTER STATION INVENTORY OR SAMPLE DATA:
a)
Check if isotopic release RATE is to be used b) Select each isotope AND Enter release rates (for each selection) using the NUM pad c) Touch CONFIRM after all data has been correctly entered a)
IF isotopic CONCENTRATION is to be entered, THEN do the following:
- 1) Select each isotope.
- 2) Enter concentration using the NUM pad.
- 3) Enter flow rate in bottom box of center column.
- 4)
GO TO Step 11.c c)
IF a data entry error was made, THEN re-enter the correct data using the NUM pad and touch CONFIRM when complete.
d) GO TO Step 13 NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 17 of 23 1-
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1. TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:
e The UNKNOWN MIX option may not appear on all DBA ACCIDENT TYPE SELECTION screens.
e CHRRMS (Unit 1:
RMS-127/128, Unit 2:
RMS-227/228) readings may be used to select MIDAS LOCA accident type.
HOURS CONTAINMENT HIGH RANGE RADIATION AFTER LOCA MONITOR READING (R/hr) 0
Ž1.3E+4
Ž4.5E+2
Ž1.54 1
Ž5.OE+3
ý1.8E+2
Ž1.3 2
3.7E+3
Ž1.4E+2
Ž1.2 4
Ž2.8E+3
Ž8.6E+1
Ž1.0 MIDAS ACCIDENT LOCA LOCA LOCA TYPE SELECTION MELT GAP PC 12 ENTER ACCIDENT TYPE:
a) Verify DBA ACCIDENT TYPE SELECTION screen appears b) Select accident type as specified by RAD/RAC:
"* MSLB (Main Steam Line Break)
"* SGTR (Steam Generator Tube Rupture)
"* FUEL HANDLING (in Fuel Building only)
"* WGTR (Waste Gas Decay Tank Rupture) 0 0
0 S
a)
IF accident type screen does NOT appear, THEN GO TO Step 13.
LOCA GAP LOCA MELT LOCKED ROTOR c) Touch CONFIRM NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 18 of 23 I
I 7'
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal.
THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image), which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
-LIii-t ACTION/EXPECTED RESPONSE F-I RESPONSE NOT OBTAINED 13 ENTER RELEASE TIMING SELECTION:
a) Verify NO "abnormal run" occurred b)
Check if trip occurred GREATER THAN 15 minutes ago a)
IF recovering from an "abnormal run",
THEN GO TO Step 14.e.
b) IF time of trip within the past THEN GO TO Step is unknown or 15 minutes, 13.d.
c) Touch TRIP DATE box on the RELEASE TIMING SELECTION screen and enter date and time of trip using the NUM pad d)
Check if time of start of release since trip is known e) Touch RELEASE START MINS SINCE TRIP box f) Enter number of minutes using the NUM pad g)
Check if 120 minute release duration is to be used h) Touch DURATION box and enter 120 minutes using the NUM pad i) Touch CONFIRM j)
Verify run is proceeding into calculation mode and data result screen appears d) GO TO Step 13.g.
g)
IF release duration is
- known, THEN do the following:
- 1) Touch DURATION box.
- 2) Enter number of minutes using the NUM pad.
- 3)
GO TO Step 13.i.
j)
ILF meteorological data is not available and the manual entry screen appears, THEN RETURN TO Step 3.
IF error warning messages
- appear, THEN touch EXIT and RETURN TO Step 2.j.
k) RETURN TO Step 4 NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 19 of 23 I-I
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT) 0 Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes.
Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE 14 RESTART PROCEDURE FOR ABNORMAL RUN:
a) Touch REAL TIME ALL SCREENS DOSE PROJECTIONS box on ACCIDENT RUN MENU SELECTION screen b) Touch CONFIRM c)
WHEN the next screen requesting run type and time selection information appears, THEN touch CONFIRM without making any changes d) Refer to Step 9 to select a new release option e) Wait for RELEASE TIMING SELECTION screen to appear f)
Touch CONFIRM without making any changes g) Verify that the run proceeds into the calculation mode g)
IF meteorological data NOT available and the manual entry WEATHER SELECTION screen appears, THEN RETURN TO Step 3.
h) RETURN TO Step 4 NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 20 of 23 i-RESPONSE NOT OBTAINED H-m i
I
-- ýSTEP
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes.
Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
+LFJ-H ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE:
- Displays may be graphic or tabular, depending on what was selected in the MORE REPORTS menu.
Map features allow the user to put on or take off map overlays using function keys.
"* Instructions at the bottom of all graphic and tabular plume menus provide directions on how to move within them.
"* Graphic displays of plumes should not be used to determine emergency classifications. Instead, use the printed Special Report information.
"* Point of Interest allows the user to select specific points to determine X/Q, dose or dose rate values through the location of the terminal cursor. The cursor is moved using the "joy disk" to any location and then the space bar is toggled to display values.
15 EVALUATE DISPLAYS:
a) Set map scale:
- 1) Do one of the following:
"* Use default distance (miles)
"* Touch MAP SCALE box and enter miles of interest using NUM pad
- 2) Touch CONFIRM b) Check use of MAP FEATURES DESIRED:
- 1) Touch MAP FEATURES
- 2) Select (highlight) desired options on screen menu
- 3)
Touch CONFIRM (STEP 15 CONTINUED ON NEXT PAGE) b)
IF use of map features is NOT desired, THEN GO TO Step 15.c.
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 21 of 23
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
- MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE H-15 EVALUATE DISPLAYS: (Continued) c)
Check enlargement of selected area of display - DESIRED:
- 1) Touch SELECT AREA
- 2) Touch screen at two points bounding the desired area
- 3)
Touch RESTORE when use of this function is complete d)
Check use of POINT OF INTEREST feature - DESIRED:
- 1) Touch POINT OF INTEREST, move cursor to desired location using "joy disk",
and toggle the space bar (Place mouse cross-hairs at desired point and click)
- 2)
WHEN POINT OF INTEREST function complete, THEN move cursor to bottom right-hand corner of the plot and press the space bar (Place mouse cross-hairs at bottom right corner of plot and click) e) Touch CONTINUE f)
Touch MORE REPORTS g)
RETURN TO Step 4.h 16 CHECK IF MIDAS OPERATIONS CAN BE TERMINATED:
RESPONSE NOT OBTAINED c)
IF use of SELECT AREA feature is NOT desired, THEN GO TO Step 15.d.
d)
IF POINT OF INTEREST feature is NOT desired, THEN GO TO Step 15.e.
RETURN TO Step 5.
o Event -
TERMINATED
- RAD/RAC directs termination of MIDAS operation NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 22 of 23 F-I a
CONTINUOUS ACTION PAGE FOR EPIP-4.30 NOTE:
MIDAS screen selection boxes include:
- RESET, CONFIRM and EXIT.
RESET clears data entered before initiating a run or returns to previous screen.
CONFIRM is selected to continue model processing when all information on screen is correct.
EXIT exits the modeling process.
Selection touch screens are as follows:
"* ACCIDENT RUN MENU SELECTION (CONFIRM,
- EXIT, RESET)
"* MISCELLANEOUS PARAMETERS (CONFIRM, RESET)
"* RUN TYPE AND TIME SELECTION (CONFIRM, RESET)
"* RELEASE OPTION SELECTION (CONFIRM, RESET)
"* DBA ACCIDENT TYPE SELECTION (CONFIRM, RESET)
"* RELEASE TIMING SELECTION (CONFIRM, RESET)
"* WEATHER SELECTION (CONFIRM, RESET)
"* MORE REPORTS SELECTION (CONFIRM, EXIT)
Surry release points are assigned as follows:
"* Release Point 1:
Containment and Vent Vent (The expressed flow (EX VEL) for Release Point 1 is "O.OOE+O0" based on no containment release.)
"* Release Point 2:
Process Vent
"* Release Point 3:
Main Steam Safety Valves and AFWPT
- 1.
TERMINAL INTERFACE CRITERIA IF touch screen feature activated, THEN use touch screen to make entries.
IF a "mouse" is connected to the terminal, THEN do the following when instructed to touch the screen during performance of this procedure:
a)
Do not touch the screen when prompted to do so by the procedure.
b)
Use the "mouse" to position cross-hairs at desired location on screen.
c)
Click the "mouse" after cross-hairs are properly positioned.
NOTE: Copying may take over two minutes. Using the CONTROL key with D COPY/S COPY key will produce light text on black background (reverse image),
which may improve resolution of maps/isopleths.
- 2.
SCREEN PRINT CRITERIA WHEN individual screen print desired, THEN press "D COPY/S COPY" key while screen is displayed.
- 3.
TERMINAL MALFUNCTION RESPONSE CRITERIA IF terminal malfunctions, THEN have dose projections made from another terminal.
- 4.
TERMINAL LOCK-UP RESPONSE CRITERIA IF terminal lock-up occurs, THEN refer to Attachment 1 for response actions.
ACTION/EXPECTED RESPONSE 17 DISENGAGE SYSTEM:
a) Touch EXIT twice on the ACCIDENT RUN MENU SELECTION screen b) Press "CTRL" and "Z" keys simultaneously c)
WHEN "Local>" appears, THEN type LO d)
Press RETURN e)
Ensure "LOGGED OFF" message appears on screen f)
Press START/STOP button (the top button near the lower right front of terminal) g)
Ensure START/STOP button DISENGAGED 18 TERMINATE EPIP-4.30:
"* Give completed EPIP-4.30, forms and other applicable records to the Radiological Assessment Di rector/Coordinator
"* By:
Date:
Time:
- END -
NUMBER PROCEDURE TITLE REVISION EPIP-4.30 USE OF MIDAS CLASS A MODEL 9
PAGE 23 of 23 I-RESPONSE NOT OBTAINED H-G STEPEld
Perform the following actions, in sequence, to recover from terminal or system lock-up.
The user may return to the procedure upon recovery (i.e., it is not necessary to complete the entire sequence if operation is restored).
- 1. Enter the letter "E" AND press RETURN.
IF system accepts commands, THEN RETURN TO procedure.
- 2.
Enter "CTRL Y".
IF system accepts commands, THEN RETURN TO procedure.
- 3.
Press "RESET" on terminal.
IF system accepts commands, THEN RETURN TO procedure.
- 4. Enter "CTRL Y".
IF system accepts commands, THEN RETURN TO procedure.
- 5. Turn terminal power OFF and back ON again.
IF system accepts commands, THEN RETURN TO procedure.
- 6.
Enter "CTRL Y".
IF system accepts commands, THEN RETURN TO procedure.
NOTE: The HP and CEOF terminals are normally connected to Server "A".
TSC and LEOF terminals are normally connected to Server "B".
- 7.
Reset the MIDAS terminal servers as follows:
a)
Have all users exit MIDAS.
b)
Have the power cord for the affected terminal unplugged from the MIDAS terminal server (located in TSC Computer Room MIDAS Cabinet).
c)
Plug the power cord back in to the MIDAS terminal server.
d)
Wait for approximately 2 minutes while the server loads files from MIDAS and restarts operation.
MIDAS will be out of service on at least two terminals during this time.
e)
IF system accepts commands, THEN RETURN TO procedure.
- 8. Connect to backup (alternate) MIDAS system:
a)
Reset terminal by turning terminal power OFF and then back ON again.
b)
Press CTRL K keys.
c)
WHEN the "Local>" prompt appears, THEN type "C NMIDAS".
Make sure to put a space between "C" and "NMIDAS".
d)
Return to procedure Step 2 and continue procedure using manually entered monitor and meteorological data.
- 9.
Notify the MIDAS System Manager or Code Administrator, and the RAD or RAC.
NUMBER ATTACHMENT TITLE REVISION EPIP-4.30 9
ATTACHMENT RESPONSE TO TERMINAL LOCK-UP PAGE 1
1 of 1
- 1.
MAIN STEAM LINE BREAK:
- Release duration: 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, with all activity released in first 1/2 hour.
- Release from faulted line: 2.15E+5 lb-mass/hr.
"* Release from unaffected steam lines: 0 2
hours = 38,924 lb-mass/hr per line; 2
8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> = 41,296 lb-mass/hr per line.
"* Primary and secondary side activity:
Technical Specification limits at onset of event.
"* Primary to secondary leak rate: Technical Specification limit, 500 gpd in affected generator, and 1440 gpd (1 gpm) total for all 3 steam generators.
"* Iodine partition factors: Faulted S/G = 1; Intact S/Gs = 0.10.
- Condenser is assumed unavailable and the following release points apply:
Broken steam line, intact steam line relief valves, and AFWPT.
Activity released from broken steam line is distributed among the other 3 remaining release paths: 2 intact reliefs and AFWPT.
- Concurrent Iodine spike is 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> in duration.
- 10% of total activity is released via AFWPT.
Steam flow to AFWPT:
40.5 lbs/hr per horsepower.
Rated power = 710 horsepower.
AFWPT total steam flow = 28,755 lbs/hr.
- 2.
STEAM GENERATOR TUBE RUPTURE:
- Release duration: 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
Tubes in the affected steam generator are uncovered at 5 minutes from event initiation, and remain uncovered for 10 minutes.
Iodine Partition Factor: 1.0 in affected steam generator; 0.01 in unaffected generators.
- The affected steam generator is assumed isolated within 30 minutes.
- Primary and secondary side activity:
Technical Specification limits at onset of event.
"* Primary to secondary leak rate:
Technical Specification limit, 500 gpd in affected generator, and 1440 gpd (1 gpm) total for all 3 steam generators.
"* Primary coolant release to affected steam generator:
108,381 lbs (0
- 30 minutes).
"* Steam release from affected steam generator: 107,395 lbs from 0 30 minutes, or 2.15E+5 lb-mass/hr.
"* Steam release from intact steam generators: 0 -
2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> = 38,924 lb-mass/hr per generator; 2 - 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> = 41,296 lb-mass/hr per generator.
"* Condenser is assumed unavailable and the following release points apply:
faulted generator relief valves, intact steam line relief valves, AFWPT.
If condenser is available, release points are as follows:
steam line relief valves (3),
- AFWPT, Vent Vent 1, and Air Ejector.
The Unit 1 Air Ejector vents through Vent Vent 1.
The Unit 2 Air Ejector vents via an independent stack.
"* All activity released is distributed among the 3 main steam reliefs and AFWPT.
"* Concurrent Iodine spike is 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> in duration.
- 10% of total activity is released via AFWPT.
Steam flow to AFWPT:
40.5 lbs/hr per horsepower.
Rated power
= 710 horsepower.
AFWPT total steam flow = 28,755 lbs/hr.
NUMBER ATTACHMENT TITLE REVISION EPIP-4.30 DESIGN BASIS ACCIDENT TECHNICAL OVERVIEW 9
ATTACHMENT PAGE 2
1 of 3
- 3.
FUEL HANDLING ACCIDENT (in Fuel Building):
- Release duration assumed for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
- Fuel Pool effective Iodine partition factor of 100.
- Release is through the charcoal filtration system.
The filters through which the fuel building is exhausted are assumed to be 95% efficient for all species of Iodine.
- Fuel is not moved until 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> post shutdown (= decay time).
- 4.
WASTE GAS DECAY TANK RUPTURE:
- Release duration assumed for 15 minutes.
- Entire contents of tank released (25,000 Ci D.E.
Xe-133).
1/2 of release occurs via Process Vent.
1/2 of release occurs via Vent Vent.
- 5.
LOSS OF COOLANT ACCIDENT -
MELT:
Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
- Release paths:
Containment (Containment leakage) and Vent Vent 2 (ECCS leakage).
Containment airborne source term: 100% core Noble Gases, 25% core lodines.
- Spray removal: 10 hr-1 for elemental Iodine.
- Containment leak rate: 0.1% per day, 0 to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> (1.3 cfm).
- ECCS leakage: 0 gpm, 0 to 5 min.;
964 cc/hour 5 min. to 20 min.;
4800 cc/hr 20 min to 30 days.
- Filter efficiency for safeguards exhaust: 90% elemental Iodine.
- 6.
LOSS OF COOLANT ACCIDENT -
PC:
RCS concentration assumed at Technical Specification limits.
- Safeguards filter efficiency: 90% Elemental Iodine.
- Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
- 7.
LOSS OF COOLANT ACCIDENT -
GAP:
- 3% core Noble Gases and 2% core Iodines assumed in gap.
- Safeguards filter efficiency: 90% Elemental Iodine.
- Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
- 8.
LOCKED ROTOR:
- Fuel cladding failure is assumed at 5%.
- Total release duration: 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
Iodine Partition Factor of 100 is assumed for the condenser.
- Steam flow to AFWPT = 40.5 lbs/hr per horsepower.
Rated power = 710 horsepower.
AFWPT steam flow = 28,755 lbs/hr.
- Release duration: 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
NUMBER ATTACHMENT TITLE REVISION EPIP-4.30 DESIGN BASIS ACCIDENT TECHNICAL OVERVIEW 9
ATTACHMENT PAGE 2
2 of 3
- 9.
MISCELLANEOUS GENERAL ASSUMPTIONS:
- Vent Vent:
Auxiliary Building, Air Ejector(s). Safeguards (filtered),
Fuel Building (filtered), Containment Purge (filtered), Waste Gas Decay Tank area.
- Process Vent: Waste Gas Decay Tanks, Containment Vacuum.
- Containment leakage:
MIDAS uses the higher of the two CHRRMS monitors to calculate the release.
- Air Ejector Monitors:
MIDAS adds the Air Ejector release to the associated vent vent release.
"* Main Steam and AFWPT: MIDAS adds the flows from each "open" and "status unknown" valve to calculate the total flow for a particular steam line.
MIDAS sums the releases from all three steam lines and AFWPT to calculate the total release.
"* For Vent Vents and Process Vents, MIDAS uses the highest radiation monitor indication on the affected pathway to calculate dose projections.
"* For "Quick Dose" defaults:
Unidentified mix, ground level, all release points active, and noble gas and iodine.
"* SPS MIDAS FLOW RATES:
NUMBER ATTACHMENT TITLE REVISION EPIP-4.30 DESIGN BASIS ACCIDENT TECHNICAL OVERVIEW 9
ATTACHMENT PAGE 2
3 of 3 PATHWAY FLOW RATES VENT VENT STACK 2:
Flow as indicated by FT-VS-116 (for VG-110, VG-131)
ERFCS unknown/bad data: 0 scfm MIDAS default: 1.72 E+5 scfm PROCESS VENT:
Flow indicated by FT-GW-100 (for GW-130, GW-102)
ERFCS unknown/bad data: 0 scfm MIDAS default flow: 300 scfm AIR EJECTOR:
TV-SV-103 (-203) open:
25 scfm TV-SV-103 (-203) closed:
0 scfm TV-SV-103 (-203)
ERFCS unknown/bad data:
25 scfm MIDAS default: 25 scfm CONTAINMENT:
Containment pressure < 14.7 psia: 0 scfm Containment pressure > 14.7 psia: 1.3 scfm ERFCS unknown/bad data: 0 scfm MIDAS default: 1.30 scfm MAIN STEAM:
The flow for all valves associated with a specific line are summed to determine the release rate associated with the radiation monitor for that pathway.
SAFETY VALVES:
Valve open or ERFCS unknown/bad data: 838,739 lb-mass/hr Valve closed: 0 ATMOSPHERIC RELIEFS: Valve open or ERFCS unknown/bad data: 370.618 lb-mass/hr Valve closed: 0 MIDAS DEFAULT TOTAL: 3.73 E+6 lbs-mass/hr per steam line AFWPT:
Flow indicated by FT-MS-100 (-200)
ERFCS unknown/bad data: 0 MIDAS default: 3.7 E+5 lb-mass/hr