March 5, 2002 Mr. Harold B. Ray Executive Vice President Southern California Edison Company San Onofre Nuclear Generating Station P.O. Box 128 San Clemente, CA 92674-0128
SUBJECT:
SAN ONOFRE NUCLEAR GENERATING STATION, UNITS 2 AND 3 -
ISSUANCE OF AMENDMENTS RE: TECHNICAL SPECIFICATION FOR DIESEL FUEL OIL (TAC NOS. MB3601 AND MB3602)
Dear Mr. Ray:
The Commission has issued the enclosed Amendment No. 183 to Facility Operating License No. NPF-10 and Amendment No. 174 to Facility Operating License No. NPF-15 for San Onofre Nuclear Generating Station, Units 2 and 3, respectively. The amendments are in response to your application dated December 11, 2001, and revise Technical Specification 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air, to support the use of California Diesel fuel rather than the existing Environmental Protection Agency Clear diesel fuel, and reflect a change in the diesel generator load profile in Modes 1 through 4.
A copy of our related Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commission's next biweekly Federal Register notice.
Sincerely,
/RA/
L. Raghavan, Senior Project Manager, Section 2 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-361 and 50-362
Enclosures:
- 1. Amendment No. 183 to NPF-10
- 2. Amendment No. 174 to NPF-15
- 3. Safety Evaluation cc w/encls:
See next page
March 5, 2002 Mr. Harold B. Ray Executive Vice President Southern California Edison Company San Onofre Nuclear Generating Station P.O. Box 128 San Clemente, CA 92674-0128
SUBJECT:
SAN ONOFRE NUCLEAR GENERATING STATION, UNITS 2 AND 3 -
ISSUANCE OF AMENDMENTS RE: TECHNICAL SPECIFICATION FOR DIESEL FUEL OIL (TAC NOS. MB3601 AND MB3602)
Dear Mr. Ray:
The Commission has issued the enclosed Amendment No. 183 to Facility Operating License No. NPF-10 and Amendment No. 174 to Facility Operating License No. NPF-15 for San Onofre Nuclear Generating Station, Units 2 and 3, respectively. The amendments are in response to your application dated December 11, 2001, and revise Technical Specification 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air, to support the use of California Diesel fuel rather than the existing Environmental Protection Agency Clear diesel fuel, and reflect a change in the diesel generator load profile in Modes 1 through 4.
A copy of our related Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commission's next biweekly Federal Register notice.
Sincerely,
/RA/
L. Raghavan, Senior Project Manager, Section 2 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-361 and 50-362
Enclosures:
- 1. Amendment No. 183 to NPF-10
- 2. Amendment No. 174 to NPF-15
- 3. Safety Evaluation DISTRIBUTION PUBLIC RidsNrrDripRtsb (R. Dennig)
MRubin PDIV-2 r/f RidsAcrsAcnwMailCenter G. Hill (4)
RidsOgcRp RidsNrrDlpmLpdiv (S. Richards)
RidsRgn4MailCenter (K. Kennedy, L. Hurley, D. Bujol)
RidsNrrPMLRaghavan RidsNrrLAMMcAllister PACKAGE: ML020780070 TS PAGES: ML020640446 ACCESSION NO: ML020780080 ML020770391 OFFICE PDIV-2/PM PDIV-I/LA EMCB OGC PDIV-2/SC NAME LRaghavan McAllister WBateman SUttal SDembek DATE 2/7/02 2/5/02 2/7/02 2/11/02 2/20/02 OFFICIAL RECORD COPY
SOUTHERN CALIFORNIA EDISON COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY THE CITY OF RIVERSIDE, CALIFORNIA THE CITY OF ANAHEIM, CALIFORNIA DOCKET NO. 50-361 SAN ONOFRE NUCLEAR GENERATING STATION, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 183 License No. NPF-10 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Southern California Edison Company, et al.,
(SCE or the licensee), dated December 11, 2001, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. NPF-10 is hereby amended to read as follows:
(2)
Technical Specifications The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised through Amendment No. 183, are hereby incorporated in the license. Southern California Edison Company shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendment is effective as of the date of its issuance and shall be implemented within 30 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION
/RA/
Stephen Dembek, Chief, Section 2 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of Issuance: March 5, 2002
ATTACHMENT TO LICENSE AMENDMENT NO. 183 FACILITY OPERATING LICENSE NO. NPF-10 DOCKET NO. 50-361 Replace the following pages of the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.
REMOVE INSERT 3.8-20 3.8-20 3.8-21 3.8-21
SOUTHERN CALIFORNIA EDISON COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY THE CITY OF RIVERSIDE, CALIFORNIA THE CITY OF ANAHEIM, CALIFORNIA DOCKET NO. 50-362 SAN ONOFRE NUCLEAR GENERATING STATION, UNIT 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.174 License No. NPF-15 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Southern California Edison Company, et al.,
(SCE or the licensee) dated December 11, 2001, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. NPF-15 is hereby amended to read as follows:
(2)
Technical Specifications The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised through Amendment No. 174, are hereby incorporated in the license. Southern California Edison Company shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendment is effective as of the date of its issuance and shall be implemented within 30 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION
/RA/
Stephen Dembek, Chief, Section 2 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of Issuance: March 5, 2002
ATTACHMENT TO LICENSE AMENDMENT NO. 174 FACILITY OPERATING LICENSE NO. NPF-15 DOCKET NO. 50-362 Replace the following pages of the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.
REMOVE INSERT 3.8-20 3.8-20 3.8-21 3.8-21
Enclosure SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 183 TO FACILITY OPERATING LICENSE NO. NPF-10 AND AMENDMENT NO. 174 TO FACILITY OPERATING LICENSE NO. NPF-15 SOUTHERN CALIFORNIA EDISON COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY THE CITY OF RIVERSIDE, CALIFORNIA THE CITY OF ANAHEIM, CALIFORNIA SAN ONOFRE NUCLEAR GENERATING STATION, UNITS 2 AND 3 DOCKET NOS. 50-361 AND 50-362
1.0 INTRODUCTION
By application dated December 11, 2001, Southern California Edison Company, et al., (SCE or the licensee), requested changes to the Technical Specifications (TS) for San Onofre Nuclear Generating Station (SONGS), Units 2 and 3. The proposed changes would revise TS 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air, to change the minimum required amount of stored diesel fuel. The licensee indicated that the proposed changes are required to support the use of California Diesel fuel rather than the existing Environmental Protection Agency (EPA) Clear diesel fuel, and reflect a change in the diesel generator load profile in Modes 1 through 4.
The licensee proposed to revise TS 3.8.3, Conditions A and C, and surveillance requirement (SR) 3.8.3.1, to express the 7-day and 6-day fuel volume requirements in gallons rather than percent tank level.
Specifically, the licensee proposed to revise:
(1)
TS 3.8.3, Condition A, to specify that during Modes 1 through 4, if one or more diesel generators (DGs) has a fuel volume in the storage tank less than 45,662 gallons (instead of 89 percent level) and greater than 39,468 gallons (instead of greater than or equal to 76 percent level), then fuel oil level must be restored to within limits within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.
(2)
TS 3.8.3, Condition C, to specify that during Modes 5 and 6, if one DG has a fuel volume in the storage tank less than 41,691 gallons (instead of 72 percent level) and greater than 35,735 gallons (instead of greater than or equal to 63 percent level), then fuel oil level must be restored to within limits within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.
The volumes specified above do not include allowances for instrument uncertainty.
(3)
SR 3.8.3.1 to verify the above specified fuel volume every 31 days instead of levels.
(4)
TS 3.8.3 Conditions A and C to change the "greater than or equal to" sign to a "greater than" sign for consistency with the rest of the specification.
(5)
TS Bases 3.8.3 to reflect the above proposed TS changes.
The new requirements will continue to ensure that sufficient fuel is available to supply loads for the necessary time periods (7-day, and 6-day supply).
2.0 REGULATORY ANALYSIS
Appendix A to 10 CFR Part 50, General Design Criterion, Criterion 17, Electric power systems, requires :
An onsite electric power system and an offsite electric power system shall be provided to permit functioning of structures, systems, and components important to safety. The safety function for each system (assuming the other system is not functioning) shall be to provide sufficient capacity and capability to assure that (1) specified acceptable fuel design limits and design conditions of the reactor coolant pressure boundary are not exceeded as a result of anticipated operational occurrences and (2) the core is cooled and containment integrity and other vital functions are maintained in the event of postulated accidents.
American National Standards Institute (ANSI) standard ANSI 195/ANS 59.51, "Fuel Oil Systems for Standby Diesel Generators," requires that the onsite fuel oil storage shall be sufficient to operate the minimum number of DGs following the limiting design-basis accident for either seven (7) days, or the time required to replenish the oil from the sources outside the plant site following any limiting design-basis event without interrupting the operation of the diesel, whichever is longer.
3.0 EVALUATION SONGS, Units 2 and 3 design includes an onsite power system consisting of one DG for each safety-related load group (two per unit) complete with accessories, fuel storage, and transfer systems. Each DG is provided with sufficient stored diesel fuel oil to operate the DG for a period of 7 days, while the DG is supplying maximum post-loss-of-coolant accident (LOCA) load demand.
Presently, SONGS uses EPA Clear diesel fuel. SONGS is required by California State regulation as implemented by the San Diego Air Pollution Control District to discontinue use of the current EPA Clear diesel fuel and replace it with California Diesel fuel for emissions purposes. The California Diesel fuel has slightly lower heating value (LHV) per gallon basis compared to the existing EPA Clear diesel fuel. As a result, a larger quantity of diesel fuel will be required to ensure a 7-day or 6-day supply of fuel is available for each DG.
In addition, the licensee has revised fuel volume calculations to reflect a change to the diesel generator load profile in Modes 1 through 4 in accordance with the provisions of 10 CFR 50.59.
The existing fuel volume calculations assumed operation of the third-of-a-kind High Pressure Safety Injection (HPSI) pump under post-accident conditions. Operation of the third-of-a-kind HPSI is no longer required under these conditions. Removal of this load from the post-accident load profile has decreased the overall required volumes of fuel in the tank for Modes 1 through 4, even when use of the new fuel is taken into account. The NRC staff did not review the DG load profile changes which were made in accordance with 10 CFR 50.59.
Using the methods described in ANSI 195/ANS 59.51, and based on the LHV of California Diesel fuel, and the revised post-accident load profile, the licensee has re-calculated the minimum required volume of fuel necessary to ensure a 7-day or 6-day supply of fuel is available for each DG. Based on the revised calculations, the licensee has determined that the amount of stored fuel required to ensure a sufficient supply of fuel in Modes 1 through 4 will be decreased from 49,724 gallons to 45,662 gallons (7-day supply of fuel), and from 42,960 gallons to 39,468 gallons (6-day supply of fuel). The minimum amount of fuel in Modes 5 and 6 will be increased from 40,472 gallons to 41,691 gallons (7-day supply of fuel) and from 34,690 gallons to 35,735 gallons (6-day supply of fuel).
Because the revised volume of stored diesel fuel oil is sufficient to operate the DG for a required period of 7 or 6 days, as applicable, while the DG is supplying maximum post-LOCA load demand, the proposed changes are acceptable. The change of units for the minimum required diesel fuel from tank level (percent) to volume (gallons), and the "greater than or equal to" sign to greater than in TS 3.8.3, are administrative in nature and have no impact on the safe operation of the DGs. Therefore, these changes are acceptable.
Because the new values are expressed in gallons, these values need not include allowances for instrument uncertainty. However, the licensee indicated that instrument uncertainty will continue be included in calculations to determine corresponding tank levels for use in control room alarm setpoints and surveillance procedures.
Following implementation of these proposed changes, there will be no change in the ability of the diesel fuel oil storage and transfer system to supply the diesel generators over the required 7-day and 6-day periods and, therefore, the NRC staff finds the proposed changes to be acceptable.
4.0 STATE CONSULTATION
In accordance with the Commission's regulations, the California State official was notified of the proposed issuance of the amendments. The State official had no comments.
5.0 ENVIRONMENTAL CONSIDERATION
The amendments change a requirement with respect to the installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20 and changes a surveillance requirement. The NRC staff has determined that the amendments involve no significant increase in the amounts and no significant change in the types of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendments involve no significant hazards consideration, and there has been no public comment on such finding (67 FR 932 dated January 8, 2002). Accordingly, the amendments meet the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendments.
6.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the
December 17, 2001 Commission's regulations, and (3) the issuance of the amendments will not be inimical to the common defense and security or to the health and safety of the public.
Principal Contributor: L. Raghavan Date: March 5, 2002 San Onofre Nuclear Generating Station, Units 2 and 3 cc:
Mr. R. W. Krieger, Vice President Southern California Edison Company San Onofre Nuclear Generating Station P. O. Box 128 San Clemente, CA 92674-0128 Mr. Douglas K. Porter Southern California Edison Company 2244 Walnut Grove Avenue Rosemead, CA 91770 Mr. David Spath, Chief Division of Drinking Water and Environmental Management P. O. Box 942732 Sacramento, CA 94234-7320 Chairman, Board of Supervisors County of San Diego 1600 Pacific Highway, Room 335 San Diego, CA 92101 Eileen M. Teichert, Esq.
Supervising Deputy City Attorney City of Riverside 3900 Main Street Riverside, CA 92522 Mr. Gary L. Nolff Power Projects/Contracts Manager Riverside Public Utilities 2911 Adams Street Riverside, CA 92504 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-8064 Mr. Michael Olson San Onofre Liaison San Diego Gas & Electric Company P.O. Box 1831 San Diego, CA 92112-4150 Mr. Steve Hsu Radiologic Health Branch State Department of Health Services Post Office Box 942732 Sacramento, CA 94327-7320 Mr. Ed Bailey, Radiation Program Director Radiologic Health Branch State Department of Health Services Post Office Box 942732 (MS 178)
Sacramento, CA 94327-7320 Resident Inspector/San Onofre NPS c/o U.S. Nuclear Regulatory Commission Post Office Box 4329 San Clemente, CA 92674 Mayor City of San Clemente 100 Avenida Presidio San Clemente, CA 92672 Mr. Dwight E. Nunn, Vice President Southern California Edison Company San Onofre Nuclear Generating Station P.O. Box 128 San Clemente, CA 92674-0128 Mr. Robert A. Laurie, Commissioner California Energy Commission 1516 Ninth Street (MS 31)