ML020640446
| ML020640446 | |
| Person / Time | |
|---|---|
| Site: | San Onofre (NPF-010, NPF-015) |
| Issue date: | 03/05/2002 |
| From: | NRC/NRR/DLPM |
| To: | |
| References | |
| TAC MB3601, TAC MB3602 | |
| Download: ML020640446 (2) | |
Text
Diesel Fuel Oil, Lube Oil, and Starting Air 3.8.3 3.8 ELECTRICAL POWER SYSTEMS 3.8.3 Diesel Fuel Oil, Lube Oil, and Starting Air LCO
3.8.3 APPLICABILITY
The stored diesel fuel oil, lube oil, and starting air subsystem shall be within limits for each required diesel generator (DG).
When associated DG is required to be OPERABLE.
ACTIONS
-NOTE-Separate Condition entry is allowed for each DG.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more DGs with A.1 Restore fuel oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> fuel volume < 45,662 level to within gallons and > 39,468 limits.
gallons in storage tank during MODE 1,2,3 or 4.
B.
One or more DGs with B.1 Restore lube oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> lube oil inventory inventory to within
< TS min and ; TS limits.
inop.
C.
One required DG with C.1 Restore fuel oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> fuel volume in the level to within storage tank < 41,691 limits.
gallons and > 35,735 gallons during MODE 5 or 6.
D. One or more DGs with D.1 Restore fuel oil 7 days stored fuel oil total total particulates to particulates not within limits.
within limits.
(continued)
Amendment No.
183 SAN ONOFRE--UNIT 2 3.8-20
Diesel Fuel Oil, Lube Oil, and Starting Air 3.8.3 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME E.
One or more DGs with E.1 Restore stored fuel 30 days new fuel oil oil properties to properties not within within limits.
limits.
F.
One or more DGs with F.1 Restore starting air 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> starting air receiver receiver pressure to pressure < 175 psig
Ž 175 psig.
and Ž 136 psig.
G.
Required Action and G.1 Declare associated DG Immediately associated Completion inoperable.
Time of Condition A, B, C, D, E or F not met.
OR One or more DGs with diesel fuel oil, lube oil, or starting air subsystem not within limits for reasons other than Condition A, B, C, D, E, or F.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.3.1 Verify each fuel oil storage tank contains 31 days 2 45,662 gallons in MODE 1,2,3 or 4 and 41,691 gallons in MODE 5 or 6.
(continued)
Amendment No.
183 SAN ONOFRE--UNIT 2 3.8-21