&MAW"IH Nuclear Operating Company South Te.s Pir-oect Electric GenerabtnS Station PO. Box 289 Wadsworth, Texas 77483 January 22, 2002 NOC-AE-02001254 10CFR50.55a U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555-0001 South Texas Project Unit 1 Docket No. STN 50-498 Special Report - 1RE10 Refueling Outage Inservice Inspection Results for Steam Generator Tubing Enclosed are four copies of the summary report describing the complete results of the steam generator tube inservice inspection performed during refueling outage IRE10. This Special Report satisfies the reporting requirements of ASME Section XI, Article IWA-6230, and Section 4.4.5.5.b. of the South Texas Project Technical Specifications.
If there are any questions regarding this report, please contact Jim Haning at (361) 972-8983 or me at (361) 972-7902.
Manager, Engineering jtc
Enclosure:
1RE10 Inservice Inspection Summary Report for Steam Generator Tubing of the South Texas Project Electric Generating Station - Unit 1 STI:31398127
NOC-AE-02001254 Page 2 of 2 cc: w/o enclosure Ellis W. Merschoff Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, Texas 76011-8064 Mohan C. Thadani Project Manager U. S. Nuclear Regulatory Commission 1 White Flint North, Mail Stop: O-7D1 11555 Rockville Place Rockville, MD 20852-2738 Cornelius F. O'Keefe U. S. Nuclear Regulatory Commission P. O. Box 289, Mail Code MN116 Wadsworth, TX 77483 A. H. Gutterman, Esquire Morgan, Lewis & Bockius 1111 Pennsylvania Avenue Washington, DC 20004 M. T. Hardt/W. C. Gunst City Public Service P. 0. Box 1771 San Antonio, TX 78296 A. Ramirez/C. M. Canady City of Austin Electric Utility Department 721 Barton Springs Road Austin, TX 78704 Jon C. Wood Matthews & Branscomb 112 East Pecan, Suite I100 San Antonio, Texas 78205-3692 Institute of Nuclear Power Operations - Records Center 700 Galleria Parkway Atlanta, GA 30339-5957 Richard A. Ratliff Bureau of Radiation Control Texas Department of Health 1100 West 49th Street Austin, TX 78756-3189 R. L. Balcom/D. G. Tees Reliant Energy, Inc.
P. 0. Box 1700 Houston, TX 77251 C. A. Johnson/A. C. Bakken, III AEP - Central Power and Light Company P. 0. Box 289, Mail Code: N5022 Wadsworth, TX 77483 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555-0001
1RE10 INSERVICE INSPECTION
SUMMARY
REPORT FOR STEAM GENERATOR TUBING of the SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION UNIT 1 P.O. BOX 289 WADSWORTH, TEXAS 77483 Owner: South Texas Project Nuclear Operating Company Commercial August 25, 1988 Operation:
Issue Date:
October 19, 2001 IREIO INSERVICE INSPECTION
SUMMARY
REPORT
1RE10 INSERVICE INSPECTION
SUMMARY
REPORT FOR STEAM GENERATOR TUBING of the SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION UNIT 1 USNRC DOCKET NO.: 50-498 OPERATING LICENSE NO.:
NPF-76 COMMERCIAL OPERATION DATE: August 25, 1988 Prepared By:
Approved By:
ISI gineer - Steam Gennar Tubing M. E. Kanavos Steam Generator Manufacturing Project Manager Z ?=- - 7Z,0,dZ Date
/- 2-.L - 0 2 Date
TABLE OF CONTENTS Page No.
I 1.0 Introduction 2.0 Scope of Examinations 3.0 Personnel, Procedures and Equipment 3.1 Personnel Qualifications 3.2 Examinations and Analysis Procedures 3.3 Equipment 3.4 Calibration Standards 4.0 Summary of Examinations 5.0 Examination Results 5.1 Steam Generator A 5.2 Steam Generator B 5.3 Steam Generator C 5.4 Steam Generator D 6.0 Certification of Inspections Appendix A Appendix B Appendix C Appendix D Appendix E Appendix F List of Examination and Data Analysis Personnel Tubes Examined by RPC Dings and Dents Tubes with Other Anomalous Signals Tubes Removed from Service Prior to and during IRE10 Owner's Report for In-service Inspections - NIS - I Form iii 2
3 3
3 4
5 6
7 8
8 8
8 9
STEAM GENERATOR TUBE EXAMINATIONS 1.0 Introduction This Summary Report describes the South Texas Project Nuclear Operating Company's (STPNOC's)
Inservice Inspection (ISI) of the steam generator (S/G) tubing at the South Texas Project Electric Generating Station, Unit I during thei RE1O refueling outage.
The steam generator tube ISI is required by Sections 3/4.4.5 and 4.0.5 of the Technical Specifications to be performed in accordance with the edition and addenda of the American Society of Mechanical Engineers (ASME)Section XI Code "Inservice Inspection of Nuclear Power Plant Components" prescribed by Title 10 of the Code of Federal Regulations, Part 50, Section 50.55a(g). Therefore, the ISI is required to meet the 1989 Edition of the ASME Code Section XI. The ISI summarized herein constitutes the first IS1 performed on the Delta 94 replacement steam generators since they were installed during I RE9.
The STPEGS-1 plant design contains four (4) Westinghouse recirculating design steam generators designated as model Delta 94 (D94). Each model D94 steam generator was designed and fabricated by Westinghouse Electric Company of Pensacola, Florida. Each steam generator contains 7885 tubes. The tubing material is thermally treated Inconel Alloy 690 having a nominal outer diameter (OD) of 0.688 inch and nominal wall thickness of 0.040 inch. The nominal thickness of the tubesheet is 25.43 inches.
The examination agency for the IRE1O outage was Westinghouse Electric Company, LLC.
I
2.0 Scope of Examinations The ISI plan (ISI Outage Plan) entitled, "2001 Outage Plan for the In-service Inspection of Steam Generator Tubing at the South Texas Project Electric Generating Station Unit 1 ", including Change Number 001, was prepared by Westinghouse and approved by STPNOC. The ISI Outage Plan identified the steam generator tube areas to be examined by eddy current testing (ET) and the ET procedures expected to be used during the ISI.
A Degradation Assessment (DA) was written prior to the outage. This document identified necessary examination techniques. An evaluation of these techniques was performed to ensure their qualification.
Finally, a site-appropriateness review was conducted to satisfy that each technique could be used in STPNOC Unit 1 Steam Generators. All techniques were reviewed for use by the Westinghouse Level III QDA, the STP ISI engineer, and the STP QDA.
The initial scope consisted of the following planned examinations:
"* Bobbin coil ET of all in-service tubing over its full length in each steam generator.
"* Plus Point testing of all I-codes detected by bobbin.
"* Signals of interest - with STPNOC approval (ie: PLP's).
2
3.0 Personnel, Procedures, and Equipment 3.1 Personnel Qualifications The personnel who performed the ET acquisition and analysis during the 1RE10 outage were employed by Westinghouse, NDE Technology, Core Star International and Framatome Technology (FTI). They were certified in accordance with the requirements of IWA-2300 of ASME Code Section XI and the certification practices of their respective employers. One hundred (100) percent of the ET analysts were certified as Qualified Data Analysts (QDA's) for the steam generator work performed. A QDA is a Level IIA or III who has passed rigorous testing of his ability to analyze a random selection of expertly-judged indications, from the Electric Power Research Institute's "PWR Steam Generator Examination Guidelines", Appendix G Performance Demonstration Database, for various steam generator designs and all types of known defects.
Before an ET data analyst could perform any analysis during IRE10, they were required to successfully complete a STPEGS Site Specific Performance Demonstration (SSPD) steam generator ET data analysis training program. The analyst-training program consisted of (1) ET data analysis course and (2) site specific practical training. The ET data analysis course consisted of Computer Based Training (CBT) on CD-ROM and the analysis procedures. The CBT course addressed the specific STPEGS steam generator design, operating history, previous ET results, the data acquisition procedure, and analysis procedures to be used for the STPEGS Unit 2 ET examinations. The site specific practical training included hands-on review of flaw indications for the damage mechanisms that have been identified at STPEGS. Successful completion of the SSPD required the passing of a written and a practical test, which could be limited to either bobbin coil, MRPC or both, depending on staffing assignments.
3.2 Examination and Analysis Procedures All ET inspections were performed in accordance with the WNSD procedure MRS 2.4.2 GEN-35, Revision 10 entitled, "Eddy Current Inspection of Preservice and Inservice Heat Exchanger Tubing",
with Field Change Request Number 1 and 2. This procedure, with the change authorization, is STPEGS document no. 0120RSG--00048-AW2. In addition, the Westinghouse document no. SGO-01-057, Revision 0 entitled "South Texas 1RE10 Data Quality Guidelines" was used. The data quality guideline is STPEGS document no. 0120RSG--00049-AW2.
The bobbin coil examination technique was performed using inspection frequencies of 630, 300, 150 and 35 kHz in both the differential and absolute modes for each tube. A nominal pull speed of 40 inches per second with a digital signal-sampling rate of 1450 samples per second or greater was used during the 1RElO ET examination. MRS 2.4.2 GEN-35 prescribes that the applicable Acquisition Technique Sheets (ACTS) will define the data sample rate and probe rotation and pull speeds. ACTS TGX-01-101, Rev. 1 listed these and other essential variables required for bobbin probe testing. Additionally, a slower test speed was used as needed to reduce probe snap in u-bend areas. This slower nominal pull speed of 24 inches per second used a digital signal sample rate of 850 samples per second or greater, and is listed on ACTS TGX-03-101, Rev. 1.
The 3C+Pt and the 1C+Pt u-bend probe was utilized for further diagnostic testing of signals of interest identified by bobbin. The three-coil +Pt RPC ET examination technique was performed using the examination frequencies of 300, 200, 100, and 10 kHz. Also, the high frequency pancake coil on the 3-3
coil probe head was operated at 600 kHz, in addition to 300 kHz. The single coil +Pt u-bend examination technique was performed using the examination frequencies of 400, 300, 150 and 20 kHz. The 3-coil and single coil +Pt test specifications are defined on ACTS TGX-02-101 and TGX-06-101, respectively.
The ET data analysts performed the analysis per Westinghouse procedure MRS-SSP-1209-TGX Rev. 0, titled, "Steam Generator Eddy Current Data Analysis Guidelines for Inservice Inspections at South Texas Unit 1 ", STPEGS document number 0120RSG--00046-AW2. All bobbin coil and RPC ET data for each steam generator tube or tube area examined were subjected to two (2) separate independent analyses in accordance with the analysis procedure.
FTI and it's subcontractors performed the secondary analysis in accordance with the FTI procedure 54 ISI-400-11 entitled "Multi-frequency Eddy Current Examination of Tubing" including Safety Document Change Notice numbers 30-5011160-00 and 30-5014571-00. This FTI Procedure is STPEGS document no. ST401280-0023 1-C2U.
The ET primary and secondary data analysis was performed in separate facilities. The primary analysis was performed by Westinghouse (at Waltz Mill, Pa.) utilizing ANSER Automated Data Screening (ADS), while the secondary analysis was performed by Framatome (at Lynchburg, Va.) utilizing ANSER manually. Resolutions was performed at STP and consisted of personnel representing both Framatome and Westinghouse.
Results of all of the eddy current examinations were recorded on a digital, rewritable optical disk and the final resolution data sheets, which are stored as records. Each disk contains the raw ET data, primary, secondary, and resolution results for each calibration group. The optical disks also contain the system calibration and calibration verification with the dates and times for each calibration and verification. The unique number of the digital rewritable optical disk and the calibration group number have been recorded on the data sheets and optical disks. Therefore, the system calibration and calibration verification of the raw signals for each tube examined can be easily recalled.
3.3 Equipment All examinations were performed using ANSER ROSA software and the TECHRAD TC-6700 test instrument. The acquisition test instrument and software store and process the ET data in a digital format and have a significantly improved dynamic range and signal-to-noise ratio as compared to analog systems. The test system is capable of being operated at locations remote from the steam generators (e.g.,
in low radiation areas). All analysis was performed using Westinghouse ANSER software.
The bobbin program was performed using the Westinghouse Replaceable Probe Head (RPH) design, WA-560-RPH and WA-540-RPH. Diagnostic testing/special interest (RPC) was performed using the Zetec 1C+PtRPC (single +Pt coil) and the 3C+PtRPC (three coil) probe. The lC+Pt RPC was used in the u-bend area and the 3C+Pt was used in the straight sections. The 3C+PtRPC probe consists of one (1) plus-point coil (interwoven axially and circumferentially oriented coils that are differentially connected),
one (1) 0.115 inch diameter pancake coil and one (1) shielded high frequency 0.080 inch diameter pancake coil. These inspections took place from either leg, depending on the location requiring inspection.
4
3.4 Calibration Standards The calibration standard design used for bobbin coil inspections was a combination in-line standard. It contained ASME Code Section XI flaws, drill holes for measuring probe wear, simulated AVB wear flaws, a small 3 mil radial dent and both a 1.12" tri-foil and donut stainless steel support rings. The calibration standard utilized for all of the 3-coil and Plus point MRPC inspections was a EP5 guide tube design containing several ID and OD, axially and circumferentially oriented, electro-discharge machined (EDM) notches in sufficient quantities to permit the sizing of indications if necessary.
5
4.0 Summary of Examinations Bobbin coil ET techniques were performed on one hundred (100) percent of all in-service tubes in each of Steam Generators A, B, C, and D. All of these tubes were examined over their full length (FL), from tube end to tube end.
The following table summarizes the quantities of tubes that were examined:
S/G Bobbin Coil Bobbin Coil H/L RPC C/L RPC H/L Program C/L Program SI Program SI Program A
7552 689 10 4
B 7545 690 17 7
C 7559 689 4
8 D
7576 692 22 9
The following table identifies a breakdown of the special interest programs:
Steam DNI's NQI's MBI's PLP's DNG's PLP Generator "Box In" A
3 7
5 0
0 0
B 4
8 11 0
1 0
C 2
6 5
0 0
0 D
4 11 11 1
0 6
Totals 13 32 32 1
1 6
6
5.0 Examination Results The location of the indications were recorded relative to the adjacent tube support, baffle plate and/or anti-vibration bar. The tube support plates and baffle plates were numbered consecutively from 01H to support plate. The anti-vibration bars were numbered AV I through AV 16 from the hot leg to the cold leg side, respectively. Indications in the tubesheet area were recorded relative to TEH or TSH (hot leg) or TEC or TSC (cold leg) depending on whether the indications were at the tube end (E) or secondary face (S). In addition, the vertical distances from these landmarks to flaws were recorded, with positive being upward from the reporting structure. This convention was used through out the tube bundle, except at support structures, where a plus/minus 2-inch window was used when reporting indications that were at, or near the support structure.
The three letter code reflects the suspected nature of the discontinuity. Some of the codes used during IRE1O are as follows:
DNG - ding, located in freespan only DNI - ding or dent containing a possible indication DNT - dent, located at TSP' s only NQI - non-quantifiable indication MMB - multiple manufacturing buff mark MBM - manufacturing buff mark PVN - permeability variation BLG -bulge PLP - possible loose part NQI - non-quantifiable indication MBS - manufacturing buff mark signal DNS - ding signal NQS - non-quantifiable signal The reporting requirements during IREI0 were as follows: MBMs indications greater than or equal to one (1.00) volt on 150 kHz absolute, that were found to be in the baseline bobbin data results, and having not changed, were re-identified as Manufacturing Buff Marks (MBM' s). If change has occurred, the code was changed to MBI and subjected to RPC testing (+PT). MBM's less than one volt were also compared to the PSI database for change. If change has occurred, or the MBM is not in the baseline data results, the raw baseline data was reviewed for comparison. Those that could not be traced to baseline were then reported as MBI and subjected to a RPC inspection. All NQI signals reported were also compared to the baseline data. NQI signals that either changed or did not exist in the baseline data were subjected to RPC testing. DNG's and DNT's greater than 0.75 volts on the 630/150 kHz mix, were monitored for distortion and change. DNG's and DNT's that exhibited change were reported as DNI and subjected to RPC testing. MBS, NQS and DNS are bobbin three letter codes that indicates that the signal was dispositioned from an I-code by either diagnostic testing (RPC) or by historical review of the raw baseline data.
There were no axial or circumferential crack-like indication reported in any of the four steam generators.
No wear of any kind was reported in any of the four steam generators There was one ding-like signal reported in S/G-B that measured a voltage of 58.55 volts. RPC testing revealed that no degradation was present.
7
A PLP was reported by bobbin on tube R43 C79 in S/G-D at 6H - 1.74. This tube and surrounding tubes were tested with RPC. No degradation or additional signals of possible loose parts were detected.
The following table summarizes the final results for the IREIO inspection:
TGX-A TGX-B TGX-C TGX-D MBM's / Tubes 191/181 159/147 163/149 209/187 MBS's/Tubes 6/5 11/11 5/5 11/10 MMB's / Tubes 0/0 1/1 0/0 0/0 DNG's / Tubes 13/13 22/19 9/8 7/6 DNT's / Tubes 416/ 173 6/4 218/167 125/98 DNS's / Tubes 3/3 4 /3 2/2 5/4 NQS's / Tubes 69/63 39/37 51/47 47/33 BLG's / Tubes 0/0 1/1 0/0 0/0 PVN's / Tubes 0/0 0/0 0/0 5/4 PLP's / Tubes 0/0 0/0 0/0 1/1 The total numbers of degraded and defective tubes detected during the bobbin coil ET and MRPC ET are as follows:
5.1 Steam Generator A There were no tubes considered degraded and defective. There were no tubes removed from service.
5.2 Steam Generator B There were no tubes considered degraded and defective. There were no tubes removed from service.
5.3 Steam Generator C There were no tubes considered degraded and defective. There were no tubes removed from service.
5.4 Steam Generator D There were no tubes considered degraded and defective. There were no tubes removed from service.
8
6.0 Certification of Inspections A Section XI NIS-I form "Owner's Report for In-Service Inspections", has been prepared to certify the STPEGS Unit 1 ISI examinations described in this Summary Report. The STPEGS Unit 1 ISI examinations have been certified by our ANII, Factory Mutual Insurance Company, on the NIS-1 form included in Appendix F.
9
APPENDIX A LISTING OF CERTIFIED PERSONNEL
Appendix A Listing of Certified Personnel NAME EC LEVEL COMPANY Site Analysis Crew Brown, M E Case, J M Nelson, D L Neyman, R L Obazenu, D J Pocratsky, R J Richards, T A Siegel, R A Spence W J Stokke, T F Thompson, V A Wheeler, C K III III Ill Ill
'II Ill III III Ill Ill III III Primary Analysis Crew - REDAC Akerlind, B E III Beiers, T S III Ingraham, R H III Jerina, F J III Lewis, C L IIA Popovich, R A III Richmond, M A III Taylor, S H III Secondary Analysis Crew - Lynchburg Anderson, D A IIA Blankinship, M B IIA Causby, G W IIA Janet, J M IIA Kovalesky, T L IIA Lee, R E IIA Martin, A P IIA Newman, E P IIA Schwenn, J S IIA Shelden, J T III Stach, G J IIA Thulien, T A IIA Turner, D G IIA Visconti, C G IIA Washburn, T G IIA NDE NDE NDE FTI Anetec WNSD FTI NDE WNSD NDE NDE NDE NDE NDE NDE NDE NDE WNSD NDE WNSD NDE FTI Corestar FTI FTI FTI Corestar FTI FTI NDE Corestar Corestar Corestar Corestar FTI REP - FUNCTION W - Reso FTI - Reso W - Data Cop FTI - Reso Ind. QDA W -Senior FTI - Reso W - Data Cop W - Reso W - Reso FTI - Reso W - Reso W - Pri W - Pri W - Pri W - Pri W - Pri W - Pri W-Pri W - Pri F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec F - Sec A-1
Listing of Certified Personnel NAME EC LEVEL COMPANY REP - FUNCTION Acquisition Crew AtIman, T R I
WNSD W - Acq Bradley, D G II WNSD W - Acq Dvorak, D J I
Spec ATS W - Acq Evering, D P II WNSD W - Acq Groh, T A II WNSD W - Acq Kessler, J D I
Spec ATS W - Acq Mains, P J II WNSD W - Acq Mardell, D M II WNSD W - Acq Parris, J R II WNSD W - Acq Rondeau, E A I-T Spec ATS W - Acq Scott, A W II WNSD W -Acq Smith, AO II WNSD W -Acq Tedrick, J E I
WNSD W -Acq Tucker, R L II WNSD W - Acq Appendix A A-2
APPENDIX B TUBES EXAMINED BY RPC
Appendix B Tubes Examined by RPC SG-A ROW COLUMN BEGIN TEST END TEST PROBE 33 29 04H 05H
.560 ZPSNM 50 30 06H 07H
.560 ZPSNM 69 35 08H 08H
.560 ZPSNM 91 35 01H 02H
.560 ZPSNM 42 44 06H 07H
.560 ZPSNM 115 55 08H 09H
.560 ZPSNM 91 73 01H 02H
.560 ZPSNM 11 77 08H 09H
.560 ZPSNM 111 77 07C 07C
.560 ZPSNM 115 79 02C 03C
.560 ZPSNM 116 86 05H 06H
.560 ZPSNM 43 115 FBC o1C
.560 ZPSNM 57 125 FBH FBH
.560 ZPSNM 89 129 09C 09C
.560 ZPSNM B-1
Tubes Examined by RPC SG-B ROW COLUMN BEGIN TEST END TEST PROBE 19 21 08H 09H
.560 ZPSNM 19 21 08C 09C
.560 ZPSNM 46 30 06C 07C
.560 ZPSNM 44 32 06H 07H
.560 ZPSNM 3
33 09H 09H
.520 ZRUNM 61 35 TSC TSC
.560 ZPSNM 12 38 07H 08H
.560 ZPSNM 14 38 07H 08H
.560 ZPSNM 16 38 07H 08H
.560 ZPSNM 104 38 09H 09H
.520 ZRUNM 98 40 08H 09H
.560 ZPSNM 3
43 09H 09H
.520 ZRUNM 127 79 TSC TSC
.520 ZPUMB 19 85 06H 07H
.560 ZPSNM 25 93 03H 04H
.560 ZPSNM 122 98 TSC FBC
.560 ZPSNM 3
99 09H 09H
.520 ZRUNM 109 99 07H 08H
.560 ZPSNM 90 102 02C 03C
.560 ZPSNM 102 110 02H 03H
.560 ZPSNM 76 114 08H 09H
.560 ZPSNM 103 115 08H 09H
.560 ZPSNM 80 122 06H 07H
.560 ZPSNM 88 122 TSC FBC
.560 ZPSNM B-I Appendix B
Tubes Examined by RPC SG-C ROW COLUMN BEGIN TEST END TEST PROBE 99 31 09H 09H
.560 ZPSNM 38 50 06H 07H
.560 ZPSNM 77 51 02C 03C
.560 ZPSNM 116 56 07C 07C
.560 ZPSNM 22 92 TSC 01C
.560 ZPSNM 79 99 08H 09H
.560 ZPSNM 65 101 01C 01C
.560 ZPSNM 65 101 01C 01C
.560 ZPSNM 10 122 08C 09C
.560 ZPSNM 38 126 01C 02C
.560 ZPSNM 33 127 05H 06H
.560 ZPSNM 40 128 05C 06C
.560 ZPSNM 42 128 060 07C
.560 ZPSNM B-1 Appendix B
Tubes Examined by RPC SG-D ROW COLUMN BEGIN TEST END TEST PROBE 2
14 09C 09H
.520 ZPUMB 17 31 07C 07C
.560 ZPSNM 17 31 07C 08C
.560 ZPSNM 96 44 02C 03C
.560 ZPSNM 81 49 08H 09H
.560 ZPSMB 98 50 Al 08H
.520 ZPUMB 118 56 08H 08H
.560 ZPSMB 23 63 TSC 01C
.560 ZPSNM 84 66 02H 02H
.560 ZPSMB 119 67 07C 07C
.560 ZPSNM 122 68 07C 07C
.560 ZPSNM 80 70 05H 06H
.560 ZPSMB 116 70 06C 07C
.560 ZPSNM 42 78 06H 06H
.560 ZPSMB 44 78 06H 06H
.560 ZPSMB 41 79 06H 06H
.560 ZPSMB 43 79 06H 06H
.560 ZPSMB 45 79 06H 06H
.560 ZPSMB 42 80 06H 06H
.560 ZPSMB 44 80 06H 06H
.560 ZPSMB 54 92 08H 08H
.560 ZPSMB 54 92 04H 05H
.560 ZPSMB 54 92 06H 07H
.560 ZPSMB 39 105 01C 02C
.560 ZPSNM 57 107 TSC FBC
.560 ZPSNM 106 114 08H 09H
.560 ZPSMB 46 116 05H 06H
.560 ZPSMB 89 121 06H 07H
.560 ZPSMB 86 122 07H 08H
.560 ZPSMB 26 126 06H 07H
.560 ZPSMB 28 126 06H 06H
.560 ZPSMB B-1 Appendix B
APPENDIX C DENTS AND DINGS
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 26 6
DNG A16 2.72 7
43 13 DNG 03H 17.72 1
86 22 DNG A12 18.62 19 93 31 DNG 05H 10.97 27 91 35 DNS 01H 13.03 37 45 43 DNG 08H 30..60 41 6
44 DNT A16
.00 129 6
46 DNT Al
.00 137 13 47 DNG 05C 12.30 83 6
50 DNT A16
.00 129 122 56 DNT 09C
-.32 81 123 61 DNT 09C
-.37 79 122 62 DNT 09H
-.52 81 124 62 DNT 09C
-.31 81 125 63 DNT 09C
-.37 81 124 64 DNT 09C
-.40 75 86 66 DNT 04H
.64 51 23 67 DNG A3
.88 89 47 67 DNG 05H 8.48 53 108 68 DNT 08C
.06 53 111 77 DNS 07C 2.69 69 127 85 DNT 09C
.65 75 68 86 DNG 08H 36.31 73 127 87 DNT 09C
.65 77 126 88 DNT 09C
.70 75 126 88 DNT 09H
.56 75 126 88 DNT 09H
-.58 75 123 89 DNT 09H
.53 75 123 89 DNT 09H
-.53 75 126 90 DNT 09C
.69 77 126 90 DNT 09H
-.50 77 126 90 DNT 09H
.58 77 123 91 DNT 09H
-.39 75 123 91 DNT 09H
.64 75 125 91 DNT 09C
-.34 77 125 91 DNT 09C
.69 77 125 91 DNT 09H
-.41 77 125 91 DNT 09H
.64 77 122 92 DNT 09C
-.43 75 122 92 DNT 09H
.50 75 122 92 DNT 09H
-.39 75 124 92 DNT 09C
.67 75 124 92 DNT 09C
-.37 75 124 92 DNT 09H
-.36 75 124 92 DNT 09H
.64 75 C-1
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 121 93 DNT 09H
.55 77 121 93 DNT 09H
-.53 77 123 93 DNT 09C
.70 77 123 93 DNT 09C
-.37 77 123 93 DNT 09H
.58 77 123 93 DNT 09H
-.50 77 125 93 DNT 09C
.65 77 125 93 DNT 09C
-.31 77 125 93 DNT 09H
-.50 77 125 93 DNT 09H
.61 77 120 94 DNT 09H
-.53 75 122 94 DNT 09C
-.40 75 122 94 DNT 09H
-.45 75 122 94 DNT 09H
.61 75 124 94 DNT 09C
-.37 77 124 94 DNT 09C
.62 77 124 94 DNT 09H
-.52 77 124 94 DNT 09H
.58 77 121 95 DNT 09C
-.34 75 121 95 DNT 09C
.66 75 121 95 DNT 09H
-.53 75 121 95 DNT 09H
.56 75 123 95 DNT 09C
.69 75 123 95 DNT 09C
-.31 75 123 95 DNT 09H
-.53 75 123 95 DNT 09H
.58 75 120 96 DNT 09H
-.53 75 122 96 DNT 09C
.69 77 122 96 DNT 09C
-.37 77 122 96 DNT 09H
.55 77 122 96 DNT 09H
-.52 77 124 96 DNT 09C
-.37 77 124 96 DNT 09C
.68 77 124 96 DNT 09H
-.47 77 124 96 DNT 09H
.64 77 121 97 DNT 09C
.60 77 121 97 DNT 09H
-.53 77 121 97 DNT 09H
.53 77 123 97 DNT 09C
.66 77 123 97 DNT 09C
-.37 77 123 97 DNT 09H
.66 77 123 97 DNT 09H
-.41 77 120 98 DNT 09H
-.52 77 120 98 DNT 09H
.55 77 122 98 DNT 09C
-.37 77 C-2
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 122 98 DNT 09C
.68 77 122 98 DNT 09H
-.52 77 122 98 DNT 09H
.55 77 119 99 DNT 09C
.61 153 119 99 DNT 09H
.55 153 121 99 DNT 09C
.66 153 121 99 DNT 09C
-.35 153 121 99 DNT 09H
.58 153 121 99 DNT 09H
-.58 153 120 100 DNT 09C
.60 153 122 100 DNT 09C
.69 153 122 100 DNT 09C
-.40 153 122 100 DNT 09H
-.52 153 122 100 DNT 09H
.58 153 119 101 DNT 09C
.63 155 119 101 DNT 09C
-.46 155 119 101 DNT 09H
-.52 155 119 101 DNT 09H
.52 155 121 101 DNT 09C
-.40 153 121 101 DNT 09C
.69 153 121 101 DNT 09H
.55 153 121 101 DNT 09H
-.58 153 118 102 DNT 09H
.55 153 120 102 DNT 09C
.66 155 120 102 DNT 09C
-.40 155 120 102 DNT 09H
-.55 155 120 102 DNT 09H
.55 155 119 103 DNT 09C
.69 155 119 103 DNT 09C
-.40 155 119 103 DNT 09H
-.55 155 119 103 DNT 09H
.52 155 116 104 DNT 09H
.49 153 118 104 DNT 09H
.55 153 118 104 DNT 09H
-.57 153 120 104 DNT 09C
-.32 153 120 104 DNT 09C
.69 153 120 104 DNT 09H
.55 153 117 105 DNT 09C
.64 153 117 105 DNT 09H
.55 153 119 105 DNT 09C
-.35 153 119 105 DNT 09C
.55 153 119 105 DNT 09H
.58 153 116 106 DNT 09C
.62 155 116 106 DNT 09H
.55 155 118 106 DNT 09C
.64 155 C-3
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 118 106 DNT 09C
-.44 155 118 106 DNT 09H
.52 155 115 107 DNT 09H
.52 155 117 107 DNT 09C
.70 155 117 107 DNT 09H
.55 155 16 108 DNG 09H 4.05 199 64 108 DNG 03H 27.57 157 116 108 DNT 09C
.61 153 116 108 DNT 09C
-.44 153 116 108 DNT 09H
.52 153 116 108 DNT 09H
-.55 153 113 109 DNT 09C
.61 153 113 109 DNT 09H
.61 153 115 109 DNT 09C
-.43 153 115 109 DNT 09C
.66 153 115 109 DNT 09H
-.44 153 115 109 DNT 09H
.61 153 112 110 DNT 09C
.69 155 112 110 DNT 09H
.52 155 114 110 DNT 09C
-.45 155 114 110 DNT 09C
.66 155 114 110 DNT 09H
.57 155 114 110 DNT 09H
-.55 155 116 110 DNT 09C
-.38 153 116 110 DNT 09C
.61 153 116 110 DNT 09H
-.52 153 116 110 DNT 09H
.55 153 111 111 DNT 09C
.69 155 111 111 DNT 09H
.58 155 113 111 DNT 09C
-.34 155 113 111 DNT 09C
.69 155 113 111 DNT 09H
.55 155 113 111 DNT 09H
-.52 155 115 111 DNT 09C
-.37 153 115 111 DNT 09C
.63 153 115 111 DNT 09H
.58 153 115 111 DNT 09H
-.47 153 46 112 DNG 08H 9.47 157 110 112 DNT 09C
.62 153 110 112 DNT 09H
.58 153 112 112 DNT 09C
.69 153 112 112 DNT 09C
-.40 153 112 112 DNT 09H
-.55 153 112 112 DNT 09H
.60 153 114 112 DNT 09C
-.43 155 C-4
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 114 112 DNT 09C
.67 155 114 112 DNT 09H
-.52 155 114 112 DNT 09H
.60 155 109 113 DNT 09C
.59 153 109 113 DNT 09H
.55 153 111 113 DNT 09C
-.41 153 111 113 DNT 09C
.64 153 111 113 DNT 09C
-.47 153 111 113 DNT 09H
-.39 153 111 113 DNT 09H
-.44 153 111 113 DNT 09H
.63 153 113 113 DNT 09C
.69 155 113 113 DNT 09C
-.40 155 113 113 DNT 09H
-.49 155 113 113 DNT 09H
.58 155 108 114 DNT 09C
.60 155 108 114 DNT 09H
.55 155 110 114 DNT 09C
.68 155 110 114 DNT 09C
-.43 155 110 114 DNT 09H
-.52 155 110 114 DNT 09H
.55 155 112 114 DNT 09C
.69 155 112 114 DNT 09C
-.40 155 112 114 DNT 09H
.55 155 112 114 DNT 09H
-.52 155 109 115 DNT 09C
.65 155 109 115 DNT 09C
-.43 155 109 115 DNT 09H
-.52 155 109 115 DNT 09H
.55 155 111 115 DNT 09C
-.40 155 111 115 DNT 09C
.65 155 111 115 DNT 09H
.55 155 111 115 DNT 09H
-.52 155 106 116 DNT 09C
.69 161 108 116 DNT 09C
.66 161 108 116 DNT 09C
-.35 161 108 116 DNT 09H
-.55 161 108 116 DNT 09H
.58 161 110 116 DNT 09C
.69 161 110 116 DNT 09C
-.37 161 110 116 DNT 09H
-.55 161 110 116 DNT 09H
.58 161 105 117 DNT 09C
.66 163 107 117 DNT 09C
.67 161 107 117 DNT 09C
-.43 161 C-5
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 107 117 DNT 09H
.55 161 107 117 DNT 09H
-.52 161 109 117 DNT 09C
.69 161 109 117 DNT 09C
-.34 161 109 117 DNT 09H
.55 161 109 117 DNT 09H
-.52 161 106 118 DNT 09C
.64 161 106 118 DNT 09C
-.44 161 106 118 DNT 09H
-.55 161 106 118 DNT 09H
.58 161 108 118 DNT 09C
.68 163 108 118 DNT 09C
-.40 163 108 118 DNT 09H
.66 163 108 118 DNT 09H
-.47 163 105 119 DNT 09C
.69 161 105 119 DNT 09H
.55 161 107 119 DNT 09C
.69 161 107 119 DNT 09C
-.34 161 107 119 DNT 09H
.63 161 107 119 DNT 09H
-.39 161 104 120 DNT 09H
.61 161 106 120 DNT 09C
.69 161 106 120 DNT 09C
-.34 161 106 120 DNT 09H
.55 161 106 120 DNT 09H
-.52 161 103 121 DNT 09C
.67 163 103 121 DNT 09H
.57 163 105 121 DNT 09C
-.46 163 105 121 DNT 09C
.61 163 105 121 DNT 09H
.55 163 105 121 DNT 09H
-.55 163 102 122 DNT 09C
.64 163 102 122 DNT 09H
.69 163 104 122 DNT 09C
.61 163 104 122 DNT 09H
.58 163 99 123 DNT 09H
.55 161 101 123 DNT 09C
.67 161 101 123 DNT 09H
.55 161 100 124 DNT 09C
.69 161 100 124 DNT 09H
.58 161 97 125 DNT 09C
.61 163 97 125 DNT 09H
.55 163 99 125 DNT 09C
.58 163 99 125 DNT 09H
.55 163 96 126 DNT 09C
.62 163 C-6
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 98 126 DNT 09C
.67 163 98 126 DNT 09H
.58 163 93 127 DNT 09C
.62 163 93 127 DNT 09H
.52 163 95 127 DNT 09C
.64 161 95 127 DNT 09H
.58 161 97 127 DNT 09C
.61 161 97 127 DNT 09H
.64 161 6
128 DNG 04H 32.17 203 90 128 DNT 09C
.64 179 92 128 DNT 09C
.64 161 92 128 DNT 09H
.55 161 94 128 DNT 09C
.67 161 94 128 DNT 09H
.55 161 96 128 DNT 09C
-.35 161 96 128 DNT 09C
.66 161 96 128 DNT 09H
.58 161 89 129 DNS 09C
-.39 177 89 129 DNT 09H
.69 177 91 129 DNT 09C
.68 161 91 129 DNT 09H
.55 161 93 129 DNT 09C
.62 163 93 129 DNT 09H
.60 163 84 130 DNT 09H
.63 179 86 130 DNT 09C
.56 161 86 130 DNT 09H
.55 161 88 130 DNT 09C
.67 161 88 130 DNT 09H
.55 161 90 130 DNT 09C
.61 163 90 130 DNT 09H
.58 163 92 130 DNT 09C
.61 163 92 130 DNT 09C
-.35 163 92 130 DNT 09H
.61 163 92 130 DNT 09H
-.52 163 83 131 DNT 09H
.50 181 85 131 DNT 09C
.65 161 85 131 DNT 09H
.55 161 87 131 DNT 09C
.68 161 87 131 DNT 09H
.61 161 89 131 DNT 09C
-.41 163 89 131 DNT 09C
.68 163 89 131 DNT 09H
.60 163 89 131 DNT 09H
-.52 163 91 131 DNT 09C
.69 163 91 131 DNT 09C
-.36 163 C-7
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 91 131 DNT 09H
-.52 163 91 131 DNT 09H
.60 163 84 132 DNT 09C
.62 163 84 132 DNT 09H
.60 163 86 132 DNT 09C
-.47 163 86 132 DNT 09C
.62 163 86 132 DNT 09H
.60 163 86 132 DNT 09H
-.55 163 88 132 DNT 09C
-.35 161 88 132 DNT 09C
.61 161 88 132 DNT 09H
-.44 161 88 132 DNT 09H
.63 161 81 133 DNT 09H
.44 181 83 133 DNT 09C
.65 163 83 133 DNT 09H
.63 163 85 133 DNT 09C
-.39 163 85 133 DNT 09C
.69 163 85 133 DNT 09H
.60 163 87 133 DNT 09C
-.35 161 87 133 DNT 09C
.67 161 87 133 DNT 09H
-.41 161 87 133 DNT 09H
.64 161 80 134 DNT 09C
.65 161 80 134 DNT 09H
.52 161 82 134 DNT 09C
.68 161 82 134 DNT 09H
.61 161 84 134 DNT 09C
-.35 161 84 134 DNT 09C
.67 161 84 134 DNT 09H
-.52 161 84 134 DNT 09H
.55 161 86 134 DNT 09C
-.41 163 86 134 DNT 09C
.68 163 86 134 DNT 09H
-.49 163 86 134 DNT 09H
.63 163 81 135 DNT 09C
.62 161 81 135 DNT 09H
.55 161 83 135 DNT 09C
.61 161 83 135 DNT 09C
-.32 161 83 135 DNT 09H
-.52 161 83 135 DNT 09H
.55 161 78 136 DNT 09C
.65 163 78 136 DNT 09H
.60 163 80 136 DNT 09C
.65 163 80 136 DNT 09H
.58 163 82 136 DNT 09C
.69 163 C-8
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 82 136 DNT 09C
-.35 163 82 136 DNT 09H
-.52 163 82 136 DNT 09H
.60 163 75 137 DNT 09C
.67 161 77 137 DNT 09C
.61 161 77 137 DNT 09H
.61 161 79 137 DNT 09C
.67 163 79 137 DNT 09H
.60 163 72 138 DNT 09C
.66 187 74 138 DNT 09C
.61 161 74 138 DNT 09H
.58 161 76 138 DNT 09C
.68 163 76 138 DNT 09H
.54 163 78 138 DNT 09C
.59 163 78 138 DNT 09H
-.52 163 78 138 DNT 09H
.60 163 71 139 DNT 09C
.66 161 73 139 DNT 09C
.69 163 73 139 DNT 09H
.69 163 75 139 DNT 09C
.65 163 75 139 DNT 09C
-.42 163 75 139 DNT 09H
.60 163 70 140 DNT 09C
.66 161 72 140 DNT 09C
.68 163 72 140 DNT 09H
.57 163 65 141 DNT 09C
.61 189 67 141 DNT 09C
.64 189 67 141 DNT 09H
.64 189 69 141 DNT 09C
.59 163 69 141 DNT 09H
.63 163 71 141 DNT 09C
.68 163 71 141 DNT 09H
.58 163 64 142 DNT 09C
.64 189 64 142 DNT 09H
.67 189 66 142 DNT 09C
.61 189 66 142 DNT 09H
.64 189 68 142 DNT 09C
.61 163 68 142 DNT 09H
.60 163 59 143 DNT 09C
.67 191 61 143 DNT 09C
.67 191 61 143 DNT 09H
.66 191 63 143 DNT 09C
.64 189 63 143 DNT 09H
.53 189 65 143 DNT 09C
.66 189 65 143 DNT 09H
.70 189 C-9
Appendix C Dents and Dings SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 54 144 DNT 09C
.67 189 56 144 DNT 09C
.65 191 58 144 DNT 09C
.64 191 58 144 DNT 09H
.64 191 60 144 DNT 09C
.61 189 60 144 DNT 09H
.67 189 62 144 DNT 09C
.63 189 62 144 DNT 09H
.67 189 55 145 DNT 09H
.69 191 57 145 DNT 09C
.69 189 57 145 DNT 09H
.67 189 59 145 DNT 09C
.60 189 59 145 DNT 09H
.67 189 52 146 DNT 09C
.63 189 52 146 DNT 09H
.67 189 54 146 DNT 09C
.63 189 54 146 DNT 09H
.64 189 56 146 DNT 09C
.66 189 56 146 DNT 09H
.66 189 49 147 DNT 09C
.61 191 51 147 DNT 09C
.66 189 53 147 DNT 09C
.63 189 53 147 DNT 09H
.66 189 48 148 DNT 09C
.63 189 50 148 DNT 09C
.65 189 43 149 DNT 09C
.62 189 42 150 DNT 09C
.59 189 C-I0
Appendix C Dents and Dings SG-B C-1 ROW COLUMN INDICATION LOCATION CAL NUMBER 19 21 DNG 08C 15.57 23 19 21 DNS 08C 11.78 23 19 21 DNG 08C 19.75 23 19 21 DNS 08H 23.26 23 19 21 DNG 08H 22.26 23 12 22 DNG 09H 3.68 25 16 22 DNG 09H 3.80 23 16 24 DNG 09H 3.66 23 12 26 DNG 09H 3.71 23 16 26 DNG 09H 3.68 35 12 30 DNG 09H 2.82 23 14 30 DNG 09H 3.15 35 16 30 DNG 09H 3.31 31 12 32 DNG 09H 3.33 31 13 33 DNG 09H 3.40 35 15 33 DNG 09H 3.64 35 17 33 DNG 09H 3.50 31 61 35 DNS TSC
.82 25 98 40 DNS 08H 9.48 37 119 51 DNT 09C
.56 73 95 53 DNT 09C
.56 61 95 53 DNT 09H
.58 61 16 62 DNG A16 6.00 99 16 62 DNG A16 6.30 97 59 63 DNG 04H 14.81 69 127 79 DNG TSC 3.21 181 14 86 DNG TSC 12.85 171 119 105 DNT 09C
.64 139 119 105 DNT A6
.00 139 1
123 DNG 09C
-.83 14 78 138 DNT 09H
.55 165 53 147 DNG A2 12.36 171
Appendix C Dents and Dings SG-C ROW COLUMN INDICATION LOCATION CAL NUMBER 16 4
DNG 09H 4.12 11 48 8
DNT 09C
.67 5
50 8
DNT 09C
.70 5
47 9
DNT 09C
.67 5
49 9
DNT 09C
.67 5
51 9
DNT 09C
.69 5
53 9
DNT 09C
.67 5
52 10 DNT 09C
.62 7
54 10 DNT 09C
.45 7
56 10 DNT 09C
.66 7
53 11 DNT 09C
.39 7
55 11 DNT 09C
.56 7
57 11 DNT 09C
.66 11 59 11 DNT 09C
.60 11 16 12 DNG 09H 3.59 11 52 12 DNT 09C
.57 11 54 12 DNT 09C
.69 11 56 12 DNT 09C
.67 9
58 12 DNT 09C
.58 9
60 12 DNT 09C
.57 11 62 12 DNT 09C
.60 11 55 13 DNT 09C
.57 11 57 13 DNT 09C
.64 9
59 13 DNT 09C
.61 9
61 13 DNT 09C
.57 11 63 13 DNT 09C
.66 11 65 13 DNT 09C
.66 9
58 14 DNT 09C
.66 9
60 14 DNT 09C
.65 9
62 14 DNT 09C
.66 11 64 14 DNT 09C
.60 11 66 14 DNT 09C
.60 11 68 14 DNT 09C
.60 11 65 15 DNT 09C
.65 9
67 15 DNT 09C
.63 9
69 15 DNT 09C
.52 11 71 15 DNT 09C
.65 11 68 16 DNT 09C
.67 11 70 16 DNT 09C
.66 11 73 17 DNT 09C
.66 13 76 18 DNT 09C
.69 13 78 18 DNT 09C
.67 15 79 19 DNT 09C
.70 5
81 21 DNT 09C
.61 15 83 21 DNT 09C
.69 15 84 22 DNT 09C
.69 19 86 22 DNT 09C
.69 19 C-I
Appendix C Dents and Dings SG-C ROW COLUMN INDICATION LOCATION CAL NUMBER 83 23 DNT 09C
.62 19 85 23 DNT 09C
.66 5
87 23 DNT 09C
.68 5
87 23 DNT 09C
-.39 5
16 24 DNG 09H 3.25 25 86 24 DNT 09C
.66 5
88 24 DNT 09C
.61 15 88 24 DNT 09C
-.50 15 87 25 DNT 09C
.69 1
89 25 DNT 09C
.68 1
91 25 DNT 09C
-.44 15 91 25 DNT 09C
.61 15 90 26 DNT 09C
.66 97 92 26 DNT 09C
.61 15 89 27 DNT 09C
.61 21 91 27 DNT 09C
.60 19 91 27 DNT 09C
.67 97 93 27 DNT 09C
.61 19 90 28 DNT 09C
.64 95 94 28 DNT 09C
.60 19 96 28 DNT 09C
.63 19 97 29 DNT 09C
.57 19 96 30 DNT 09C
.61 25 98 30 DNT 09C
.67 25 99 31 DNT 09C
.67 33 99 31 DNS 09H
-.62 33 99 31 DNT 09H
.51 33 100 32 DNT 09C
.66 31 101 33 DNT 09C
.62 33 104 34 DNT 09H
.50 33 103 35 DNT 09C
.59 33 107 37 DNT 09C
.62 37 108 38 DNT 09C
.69 37 112 42 DNT 09C
.59 43 113 43 DNT 09C
.58 43 114 44 DNT 09C
.67 43 116 48 DNT 07C
.22 47 113 49 DNT 07C
.42 45 117 49 DNT 07C
.22 47 116 50 DNT 07C
.40 51 118 50 DNT 07C
.31 51 115 51 DNT 07C
.28 51 117 51 DNT 07C
.34 51 119 51 DNT 07C
.20 51 119 51 DNT 09C
.65 51 116 52 DNT 07C
.36 55 118 52 DNT 07C
.34 55 C-2
Appendix C Dents and Dings SG-C ROW COLUMN INDICATION LOCATION CAL NUMBER 120 52 DNT 07C
.22 55 117 53 DNT 07C
.25 55 119 53 DNT 07C
.25 55 116 54 DNT 07C
.28 55 118 54 DNT 07C
.26 57 120 54 DNT 07C
.26 57 117 55 DNT 07C
.37 55 119 55 DNT 07C
.29 57 121 55 DNT 07C
-.69 57 121 55 DNT 07C
.26 57 121 55 DNT 08C
.23 57 121 55 DNT 09C
.58 57 116 56 DNS 07C
-.64 59 118 56 DNT 07C
.41 59 120 56 DNT 07C
.34 57 122 56 DNT 07C
.23 57 122 56 DNT 08C
.29 57 122 56 DNT 09C
.70 57 117 57 DNT 07C
.30 59 119 57 DNT 07C
.28 59 121 57 DNT 07C
.26 57 121 57 DNT 08C
.29 57 118 58 DNT 07C
.41 57 122 58 DNT 07C
.31 95 122 58 DNT 08C
.20 95 122 58 DNT 09C
-.43 95 122 58 DNT 09C
.57 95 115 59 DNT 07C
.29 95 119 59 DNT 07C
.28 59 121 59 DNT 07C
.37 95 121 59 DNT 08C
.37 95 123 59 DNT 07C
.23 95 123 59 DNT 08C
.20 95 120 60 DNT 07C
.26 95 120 60 DNT 08C
.20 95 122 60 DNT 07C
.26 95 122 60 DNT 08C
.29 95 124 60 DNT 07C
.31 95 124 60 DNT 08C
.32 95 117 61 DNT 07C
.28 63 119 61 DNT 07C
.25 63 121 61 DNT 07C
.25 63 121 61 DNT 08C
.23 63 123 61 DNT 07C
.34 63 123 61 DNT 08C
.22 63 120 62 DNT 07C
.25 63 122 62 DNT 07C
.39 63 C-3
Appendix C Dents and Dings SG-C ROW COLUMN INDICATION LOCATION CAL NUMBER 122 62 DNT 08C
.22 63 124 62 DNT 07C
.22 63 124 62 DNT 08C
.28 63 119 63 DNT 07C
.29 65 121 63 DNT 07C
.26 65 121 63 DNT 08C
.32 65 123 63 DNT 07C
.34 65 123 63 DNT 08C
.23 65 125 63 DNT 07C
.31 65 125 63 DNT 08C
.17 65 125 63 DNT 09C
.69 65 120 64 DNT 07C
.26 65 122 64 DNT 07C
.25 63 122 64 DNT 08C
.28 63 124 64 DNT 07C
.34 63 124 64 DNT 08C
.20 63 119 65 DNT 07C
.25 63 121 65 DNT 07C
.25 63 123 65 DNT 07C
.25 63 123 65 DNT 08C
.23 63 125 65 DNT 07C
.31 63 125 65 DNT 08C
.17 63 120 66 DNT 07C
.34 63 122 66 DNT 07C
.25 63 124 66 DNT 07C
.23 63 124 66 DNT 08C
.31 63 126 66 DNT 07C
.22 63 126 66 DNT 08C
.28 63 123 67 DNT 07C
.25 69 123 67 DNT 08C
.31 69 125 67 DNT 07C
.23 69 125 67 DNT 08C
.17 69 122 68 DNT 07C
.35 67 124 68 DNT 07C
.35 67 124 68 DNT 08C
.29 67 126 68 DNT 07C
.25 69 126 68 DNT 08C
.17 69 126 68 DNT 09C
-.45 69 126 68 DNT 09C
.59 69 121 69 DNT 07C
.29 67 123 69 DNT 07C
.41 67 125 69 DNT 07C
.35 67 125 69 DNT 08C
.29 67 127 69 DNT 07C
.20 69 127 69 DNT 09C
.62 69 124 70 DNT 07C
.25 69 126 70 DNT 07C
.22 69 C-4
Dents and Dings SG-C ROW COLUMN INDICATION LOCATION CAL NUMBER 126 70 DNT 08C
.17 69 126 70 DNT 09C
.69 69 125 71 DNT 07C
.25 69 125 71 DNT 08C
.26 69 127 71 DNT 07C
.23 69 127 71 DNT 09C
.56 69 124 72 DNT 07C
.37 79 126 72 DNT 07C
.26 79 126 72 DNT 08C
.29 79 55 73 DNG 07C 24.83 77 125 73 DNT 07C
.26 79 127 73 DNT 07C
.26 79 127 73 DNT 08C
.17 79 126 74 DNT 07C
.34 81 126 74 DNT 08C
.20 81 125 75 DNT 07C
.25 81 127 75 DNT 07C
.31 81 72 76 DNG 01H 33.51 77 126 76 DNT 08C
.29 79 127 81 DNT 09C
-.43 87 127 81 DNT 09C
.57 87 125 85 DNT 09C
.66 87 127 85 DNT 09C
.57 87 125 87 DNT 09C
.56 89 127 87 DNT 09C
-.39 89 127 87 DNT 09C
.62 89 124 88 DNT 09C
.66 87 126 88 DNT 09C
.57 87 125 89 DNT 09C
.57 91 124 90 DNT 09C
.60 89 126 90 DNT 09C
.63 89 123 91 DNT 09C
.56 93 82 94 DNG 06H
-.92 89 16 96 DNG 09H 4.34 165 124 96 DNT 09C
.69 111 113 97 DNT 09H
.23 111 123 97 DNT 09C
.67 111 119 105 DNT 09C
-.23 115 98 126 DNT 09C
.61 117 62 144 DNG TSH 2.13 123 62 144 DNG TSH 1.02 123 C-5 Appendix C
Appendix C Dents and Dings SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 16 6
DNG 09H 3.65 21 61 21 DNG 08H 35.25 5
61 21 DNG 08H 34.13 5
100 32 DNT 07C
-.63 15 102 34 DNT 07C
-.59 13 102 34 DNT 08C
-.63 13 104 34 DNT 07C
-.58 13 104 34 DNT 08C
-.69 13 101 35 DNT 08C
-.60 13 105 35 DNT 07C
-.61 13 102 36 DNT 08C
-.63 15 104 36 DNT 08C
-.66 13 106 36 DNT 07C
-.61 13 105 37 DNT 08C
-.66 15 107 37 DNT 07C
-.56 13 106 38 DNT 08C
-.60 13 108 38 DNT 07C
-.56 13 108 38 DNT 08C
-.65 13 107 39 DNT 08C
-.66 13 109 39 DNT 07C
-.61 13 109 39 DNT 08C
-.62 13 16 40 DNG 09H 3.68 25 108 40 DNT 08C
-.63 13 110 40 DNT 07C
-.56 13 110 40 DNT 08C
-.63 13 107 41 DNT 08C
-.66 19 109 41 DNT 08C
-.67 17 111 41 DNT 07C
-.68 17 111 41 DNT 08C
-.64 17 110 42 DNT 08C
-.68 17 112 42 DNT 07C
-.67 17 112 42 DNT 08C
-.68 17 111 43 DNT 08C
-.69 17 113 43 DNT 08C
-.65 17 112 44 DNT 08C
-.67 17 114 44 DNT 08C
-.64 17 113 45 DNT 08C
-.68 17 112 46 DNT 08C
-.65 17 114 46 DNT 08C
-.69 17 116 46 DNT 08C
-.65 53 116 48 DNT 08C
-.69 55 117 49 DNT 08C
-.65 53 118 50 DNT 08C
-.60 53 118 56 DNS 08H
-.89 41 8
62 DNG A16 1.10 91 23 63 DNS TSC 33.92 85 23 63 DNS TSC 33.77 51 C-1
Appendix C Dents and Dings SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 125 65 DNT 07C
.38 57 124 66 DNT 07C
.41 57 126 66 DNT 07C
.37 59 126 66 DNT 07C
.36 79 119 67 DNS 07C
-.65 59 125 67 DNT 07C
.37 59 122 68 DNS 07C
-.60 57 124 68 DNT 07C
.38 57 126 68 DNT 07C
.33 57 127 69 DNT 07C
.35 57 126 70 DNT 07C
.37 59 127 71 DNT 07C
.35 57 127 73 DNT 07C
.38 61 127 75 DNT 08C
.33 61 126 78 DNT 08C
.37 65 127 79 DNT 07C
.37 67 127 81 DNT 07C
.36 65 126 82 DNT 07C
.35 71 127 83 DNT 07C
.37 71 124 84 DNT 07C
.50 69 126 84 DNT 04C
.28 69 126 84 DNT 07C
.52 69 123 85 DNT 07C
.47 69 125 85 DNT 07C
.50 69 127 85 DNT 04C
.55 69 127 85 DNT 07C
.47 69 127 85 DNT 08C
.37 69 122 86 DNT 07C
.42 79 124 86 DNT 07C
.36 79 126 86 DNT 04C
.41 79 126 86 DNT 07C
-.60 79 126 86 DNT 07C
.36 79 121 87 DNT 07C
.38 79 123 87 DNT 07C
.38 79 125 87 DNT 04C
.43 79 125 87 DNT 07C
.36 79 127 87 DNT 04C
.41 79 127 87 DNT 07C
.33 79 122 88 DNT 07C
.40 83 124 88 DNT 07C
.37 83 126 88 DNT 04C
.45 83 126 88 DNT 07C
.37 83 123 89 DNT 07C
.37 83 125 89 DNT 07C
.37 83 120 90 DNT 07C
.39 85 124 90 DNT 04C
.44 81 124 90 DNT 07C
.36 81 C-2
Appendix C Dents and Dings SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 126 90 DNT 04C
.41 81 126 90 DNT 07C
.33 81 117 91 DNT 07C
.39 81 123 91 DNT 07C
.36 81 125 91 DNT 04C
.41 81 125 91 DNT 07C
.33 81 124 94 DNT 04C
.41 105 124 94 DNT 07C
.34 105 124 94 DNT 08C
.38 105 123 95 DNT 07C
.33 105 124 96 DNT 07C
.33 105 119 97 DNT 07C
.37 111 123 97 DNT 07C
.32 111 118 98 DNT 07C
.36 105 117 101 DNT 07C
.35 111 112 114 DNT 08C
-.70 113 13 117 DNT Al
.00 153 98 126 DNT 07C
-.59 127 78 138 DNT 07C
-.64 131 67 139 DNT 07C
-.69 133 67 139 DNT 08C
-.69 133 73 139 DNT 07C
-.69 133 73 139 DNT 08C
-.69 133 75 139 DNG 07C
-.78 131 70 140 DNT 07C
-.61 141 72 140 DNT 07C
-.53 141 67 141 DNT 07C
-.54 141 69 141 DNT 07C
-.57 141 71 141 DNT 07C
-.50 141 64 142 DNT 07C
-.59 137 66 142 DNT 07C
-.54 137 66 142 DNT 07C
-.66 157 68 142 DNT 07C
-.54 137 61 143 DNT 07C
-.45 137 61 143 DNT 08C
-.66 137 63 143 DNT 07C
-.62 137 65 143 DNT 07C
.30 157 65 143 DNT 07C
-. 69 157 65 143 DNT 07C
-.67 137 60 144 DNT 07C
-.64 141 62 144 DNT 07C
-.64 141 59 145 DNT 07C
-.57 141 42 146 DNG A3
-1.86 137 C-3
APPENDIX D TUBES WITH OTHER ANOMALOUS SIGNALS
Appendix D Tubes with Other Anomalous Signals SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 36 6
MBM 01C 3.72 7
31 7
MBM 01C 2.68 7
10 8
MBM 07C 33.68 105 20 8
MBM 06C 25.82 7
34 8
NQS A15 -1.70 7
13 9
MBM 07C 37.15 79 15 9
PVN 08C 37.08 81 6
10 MBM 04H 27.36 107 32 10 MBM 07H 21.11 1
40 10 MBM 02C 15.25 1
15 11 MBM 03H 11.64 81 53 11 MBM 08H 19.69 1
59 11 NQS A16 5.29 1
12 12 MBM 03H 16.34 79 23 13 MBM 05H 12.20 1
8 14 MBM 01C 35.20 8
64 16 MBM 08C 27.18 7
68 16 MBM 07H 21.34 7
57 17 MBM 02H 5.41 99 9
19 MBM 04H 31.79 105 57 19 MBM 06C 17.09 101 20 20 MBM 07H 2.18 15 12 22 MBM 07C 37.63 83 14 22 MBM FBH 6.73 103 78 22 MBM 08C 20.21 17 11 23 MBM 03C 12.30 83 34 24 NQS 06H 3.40 103 48 24 MBM 08C 38.27 103 15 25 PVN 08C 37.22 87 17 25 PVN 08C 37.26 87 6
26 MBM 06C 23.87 12 20 26 MBM 03H 29.32 103 20 26 MBM 04H 4.50 103 70 26 MBM 01H
-1.49 29 70 26 NQS 01H 3.77 29 9
27 MBM 03H 36.48 105 83 27 MBM 08H 37.02 29 33 29 MBS 04H 24.33 29 6
30 MBM 03C 30.76 12 16 30 PVN FBC 15.24 87 50 30 MBS 06H 22.97 29 58 30 NQS 05H 9.30 29 58 30 MBM 05H 11.78 29 92 30 MBM 01H 3.81 103 D-1
Tubes with Other Anomalous Signals SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 34 32 MBM A14
-1.19 29 13 33 MBM 07C 33.81 83 57 33 NQS 04C 16.80 29 26 34 MBM 07H 31.93 29 26 34 MBM 06H 22.87 29 26 34 NQS 08H
-1.52 29 53 35 NQS A16
.71 31 61 35 MBM All 1.70 31 69 35 MBS 07H 37.62 31 69 35 MBS 07H 37.49 101 89 35 MBM 07H 18.13 37 22 36 NQS 03C 15.44 31 28 36 MBM 03H 22.82 33 62 36 MBM A16 13.71 31 45 37 MBM 04H 30.02 31 87 37 MBM A16 12.61 33 10 38 NQS 06C 7.60 83 40 38 MBM FBC 14.04 31 40 38 MBM 07H 36.68 31 46 38 MBM TSC 8.95 31 70 38 MBM 02H 16.72 31 37 39 MBM A4 1.58 31 83 39 NQS 01C 13.05 31 104 40 MBM FBH 12.40 35 104 40 MBM 08H
-1.47 35 95 41 MBM A15
-.58 35 66 42 NQS 07H
-1.86 97 70 42 MBM 03C 38.01 41 84 42 MBM 03C
-1.01 39 88 42 MBM 02C 11.01 41 31 43 MBM 05H 24.04 39 69 43 NQS 05C 24.16 41 99 43 NQS 07H 17.90 39 103 43 MBM 07C 34.12 41 109 43 NQS 08H 23.82 37 42 44 MBS 06H 26.00 99 73 45 MBM 05H 13.32 43 20 46 MBM 08C 24.46 43 96 46 PVN 06H 16.86 45 116 46 MBM 07H 12.14 79 15 47 NQS 08H 18.72 87 57 47 MBM TSH 12.94 43 57 47 MBM 07H 12.96 43 109 47 NQS 05H 18.03 45 D-2 Appendix D
Appendix D Tubes with Other Anomalous Signals SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 18 48 MBM 02H 4.85 87 94 48 MBM A6 9.48 43 115 49 NQS 02H 20.04 45 22 50 MBM FBC 1.41 43 32 50 MBM 07H 12.94 43 75 51 MBM 03H 30.18 45 81 51 MBM 01H 32.48 43 87 51 NQS 07H 37.83 43 118 52 MBM 02C 16.40 81 35 53 MBM 01H 37.07 97 56 54 MBM 01H 7.50 47 66 54 MBM A2 5.67 47 70 54 NQS 07C 4.15 49 63 55 MBM A16 1.25 47 81 55 MBM A15
-1.18 47 115 55 NQS 08H 20.59 49 115 55 NQS 08H 19.43 49 24 56 MBM 04C 2.37 47 24 56 MBM 04C 6.01 47 74 56 MBM TSH 1.91 47 23 57 MBM FBC 1.55 47 116 58 NQS 03H 33.70 49 81 59 MBM 08C 14.80 47 101 59 MBM 08H 12.46 49 6
60 MBM 07H 20.28 129 68 62 MBM 06C 1.93 51 124 62 MBM 01C 26.42 81 94 64 MBM 02H 14.07 51 77 65 NQS 08H 30.21 53 104 66 MBM 02H 32.09 51 41 67 NQS 04H 17.77 51 38 68 MBM 08H 30.27 55 27 69 MBM 01C 2.79 95 41 69 MBM 07H 5.90 55 65 69 MBM 02H 17.85 55 73 69 MBM 08C 18.69 55 103 69 MBM A10 2.52 57 8
70 MBM 07C 35.03 24 3
71 MBM 02C 23.49 26 3
71 MBM 06H 28.42 133 2
72 MBM 07C 15.22 24 24 72 MBM 01H 10.03 93 26 72 MBM A2 6.37 93 86 72 MBM 08C 17.38 63 D-3
Tubes with Other Anomalous Signals SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 27 73 MBM 07C 20.17 95 91 73 NQS 01H 34.25 63 127 73 NQS A10 3.42 77 33 75 MBM 06C 36.50 63 39 75 MBM 04C 7.85 65 57 75 MBM 08H 25.05 63 65 75 MBM 08H 11.23 63 65 75 NQS 06C 21.91 63 99 75 NQS TSC 4.59 63 6
76 MBM 06C 18.11 26 34 76 MBM 01C 15.25 69 52 76 NQS 02H 28.80 67 54 76 MBM 05C 16.95 67 68 76 MBM 08H 10.80 67 94 76 NQS TSC 13.35 97 120 76 MBM 01H 17.23 75 7
77 MBM 06C 10.64 22 11 77 MBS 08H 18.53 93 55 77 NQS 07C 5.21 69 67 77 MBM 07C 20.98 67 75 77 MBM 05H 7.16 67 81 77 MBM A2 4.63 67 108 78 MBM 08C 24.17 69 51 79 MBM 07H 33.18 71 61 79 MBM 02C 15.43 73 115 79 NQS 02C 32.12 75 60 80 PVN 02H 30.80 73 47 81 NQS 03H 6.91 73 47 81 NQS 01H 15.07 73 47 81 NQS 04H 37.27 73 47 81 NQS 03H 5.06 73 30 82 MBM 03H 25.86 223 117 83 MBM 08C 24.04 77 12 84 MBM A16 6.98 221 90 84 MBM 03H 15.26 73 90 84 MBM 03H 11.43 73 25 85 NQS 06H 8.23 221 39 85 NQS FBH 10.45 151 123 85 MBM 04C 34.18 75 116 86 NQS 05H 31.68 77 16 88 MBM 01C 25.17 221 18 88 NQS 04H 36.16 221 38 88 MBM 03C 5.98 151 13 89 MBM TSC 26.69 221 D-4 Appendix D
Tubes with Other Anomalous Signals SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 23 89 NQS 04H 29.07 221 101 89 MBM 04H 21.95 75 10 90 MBM TSH 17.05 221 40 90 MBM 08C 26.23 149 68 90 MBM 08C 9.96 77 110 90 NQS 04C 14.53 77 29 91 NQS 07H 21.33 221 10 92 MBM 05C 26.65 221 120 92 MBM 07H 29.85 75 45 93 MBM 04H 29.86 151 63 93 MBM 04H 30.78 153 77 93 MBM A2 7.61 77 65 95 MBM A10 11.29 75 115 95 MBM A2 24.75 75 64 96 MBM 04H 23.30 153 98 96 NQS A8 3.35 1
31 97 MBM 01C 31.33 149 61 97 MBM TSC 8.90 151 75 97 MBM 08C 19.03 155 91 97 MBM 05H 37.94 155 4
98 MBM 04C 20.60 16 72 98 NQS TSH 13.41 151 122 98 NQS 07H 28.35 77 23 99 MBM 08H 36.25 197 50 100 NQS 08H 28.78 151 64 100 MBM 02C 32.92 153 66 100 MBM A2 11.33 151 98 100 MBM A2
.83 155 43 101 NQS 08H 32.84 149 10 102 MBM FBC
-.95 201 7
103 MBM 05H 20.69 203 23 103 NQS 02H 34.00 1
18 104 MBM FBH 3.91 199 18 104 MBM FBH
-1.81 199 76 104 NQS 08H 2.04 153 67 105 MBM 07H 29.60 153 3
107 MBM TSC 7.21 20 35 109 MBM 05C 29.98 159 4
110 MBM 02C 11.03 20 66 110 MBM 07H 23.60 159 68 110 MBM 07H 27.16 159 90 110 NQS 04H
-1.82 159 17 111 NQS 08H 5.90 159 69 111 MBM 06H 16.02 157 D-5 Appendix D
Tubes with Other Anomalous Signals SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 68 112 MBM 02C 7.43 157 19 113 MBM 03H 34.10 159 107 113 NQS A8 8.52 1
80 114 NQS A12 6.93 1
43 115 NQS FBC 8.65 163 109 115 MBM 01C 9.40 155 109 115 MBM 01C 8.62 155 32 116 MBM A2 7.12 163 74 116 MBM 04C 27.25 161 82 116 MBM 04H
-1.76 161 21 117 MBM 06H 20.10 161 64 118 MBM 07H 37.58 161 2
120 MBM 03C 27.98 18 21 121 NQS 05H 33.54 171 35 121 MBM 04H 37.48 171 79 121 MBM 03H 8.14 169 38 122 MBM 06C 38.33 201 58 122 MBM 06C 19.89 175 84 122 MBM 04C 33.36 175 33 123 MBM 08H 14.28 177 78 124 MBM 05H 2.10 179 88 124 MBM 01H 14.41 179 21 125 NQS 07H 18.22 177 31 125 MBM 02H 12.46 179 57 125 NQS TSH 16.85 179 38 126 MBM 01H 18.44 179 25 127 NQS 02H 9.24 1
25 127 NQS 07H 19.25 1
25 127 NQS 07H 14.08 1
23 129 MBM 02H 9.95 179 61 129 NQS 08C 2.84 179 69 129 MBM 01C 35.64 179 75 129 NQS A16 11.31 179 25 131 MBM 06H 6.56 177 4
132 MBM 05H 2.51 209 79 133 NQS 01C 13.00 181 40 134 MBM 05C 19.30 183 24 136 NQS 08H 24.16 1
60 136 NQS A4 4.00 1
2 138 MBM 05H 7.56 207 56 138 NQS 06H 2.17 187 16 140 MBM 07C 6.74 209 42 142 MBM 06C 7.37 193 3
143 MBM 08C 18.06 20 D-6 Appendix D
Tubes with Other Anomalous Signals SG-A ROW COLUMN INDICATION LOCATION CAL NUMBER 16 144 M BM 07C 9.40 193 19 147 M BM 07C 15.97 193 6
150 NQS 07H 20.55 203 21 151 MBM 07C 16.40 189 27 151 MBM 06H 33.89 189 20 152 MBM 07H 37.00 191 7
153 M BM 08C 10.29 18 13 153 MBM 01H 28.87 191 D-7 Appendix D
Tubes with Other Anomalous Signals SG-B ROW COLUMN INDICATION LOCATION CAL NUMBER 3
3 MBM 05C 9.20 6
21 3
NQS TSH 1.85 15 30 6
MBM 05C 26.70 103 22 8
MBM 04H 9.20 19 22 12 MBM 09H
-1.22 15 28 12 MBM 03H 26.20 19 54 12 MBM A16 10.94 37 22 14 MBM 05H 3.93 15 54 14 MBM 08H 3.88 15 62 14 MBM A6 6.68 101 9
15 MBM TSH 12.22 105 9
15 MBM TSH 12.36 107 32 16 MBM 03C 10.98 11 54 16 MBM 04H 21.71 11 63 17 MBM 06C 26.40 9
38 18 MBM 06C 25.78 11 54 18 MBM 02C 3.60 11 51 19 MBM 03C 34.41 9
69 19 MBM 08H 17.17 9
69 19 MBM 08H 13.61 9
80 22 MBM 07H 17.25 9
81 23 MBM 01H 10.30 11 54 26 MBM TSC 16.13 31 9
27 MBM 04C 36.16 12 47 27 MBM 07C 11.85 103 47 27 MBM 07C 10.24 31 60 28 MBM 06H 15.72 31 92 28 NQS TSC 3.12 7
46 30 MBS 06C 19.70 35 2
32 MBM 03C 7.68 12 2
32 MBM 03C 6.54 12 44 32 MBS 06H 20.82.
31 3
33 NQS 09H 2.76 121 84 34 MBM 03C 11.43 7
100 34 MBM A12 16.62 7
27 35 MBM 01C 29.20 23 101 37 MBM 08H 15.10 99 12 38 MBS 07H 35.87 35 14 38 MBS 07H 34.61 35 16 38 MBS 07H 34.59 31 64 38 MBM Al5
-1.96 33 104 38 MBS 09H 4.59 33 92 40 MBM A15
-1.91 39 51 41 NQS 02H 9.59 39 D-1 Appendix D
Tubes with Other Anomalous Signals SG-B ROW COLUMN INDICATION LOCATION CAL NUMBER 97 41 MBM 08H 29.29 39 42 42 MBM 08C 4.32 37 50 42 MBM 06H 4.55 37 72 42 MBM 08C 32.27 37 3
43 NQS 09H 2.09 117 44 44 MBM 08H 33.43 41 80 44 MBM 08H 30.51 43 65 45 MBM 06H 14.95 41 87 45 MBM 01C 28.15 43 111 45 MBM A2 8.13 41 111 45 MBM 04H 8.21 41 65 47 MBM 04H 24.89 99 65 47 MBM 04H 24.76 41 67 47 MBM 08H 6.81 43 91 47 MBM 09H 14.82 43 62 48 MBM 08H 35.41 47 62 48 MBM 06C 19.16 47 90 48 MBM 04C 1.99 45 35 49 MBM 07C 15.13 49 57 49 MBM 02H 38.01 47 12 50 MBM 02C 13.57 47 61 51 MBM 06C 11.12 47 59 53 MBM 08C 7.72 59 40 56 NQS 06H 6.52 59 9
57 MBM 08C 4.40 10 59 57 MBM 07C 8.93 65 79 57 MBM 02H 26.35 63 10 58 NQS 02C 3.69 97 16 58 MBM 07C 8.64 97 36 58 MBM TSH 5.53 65 80 60 NQS 01C 4.85 65 95 61 NQS 07C 10.43 65 97 61 MBM 04H 25.31 65 22 62 MBM TSC 29.45 69 110 62 MBM A12 18.26 69 11 63 MBM 04C 4.77 69 11 63 MBM 04C 6.66 69 23 63 MBM 07C 18.60 71 95 63 MBM 07C 21.33 71 107 63 MBM 05H 3.77 69 90 64 MBM A10 3.29 71 92 64 MBM 05C 35.68 69 92 64 MBM 06C 4.82 69 30 66 NQS 08H 30.77 71 D-2 Appendix D
Appendix D Tubes with Other Anomalous Signals SG-B ROW COLUMN INDICATION LOCATION CAL NUMBER 82 66 MBM 02C 36.56 69 92 66 MBM 05H 34.62 69 92 68 MBM 05C 18.21 71 97 69 MBM 02H 21.87 73 127 69 MBM 07C 18.29 97 116 70 MBM 03H 12.12 75 7
71 MBM 02C 35.33 20 29 71 MBM 06H 29.46 89 51 71 NQS 06C 38.33 73 119 71 NQS 02C 13.63 77 20 72 NQS 07C 21.73 91 46 72 MBM 03C 16.05 75 125 73 MBM 07C 34.03 79 86 74 NQS 08C 33.58 77 114 74 MBM 01H 35.47 79 29 75 MBM 06H 18.70 89 49 75 MBM 08C 1.92 77 97 75 MBM 06C 25.94 77 119 75 MBM 02C 7.22 97 127 77 MBM 07C 21.17 77 66 78 MBM 07H 28.82 81 68 78 MBM 07H 27.54 81 96 78 MBM 05C 24.66 77 40 80 MBM 08H 20.03 81 48 80 MBM FBC 5.29 81 19 81 NQS 01C 32.90 171 55 81 NQS A2 11.90 85 63 81 MBM 06H 16.73 85 10 82 NQS 01C 7.49 171 28 82 MBM 01H 10.77 89 85 83 MBM A8 2.07 87 115 83 MBM 03C 23.81 99 115 83 MBM A16 6.50 99 13 85 MBM 09C
-1.52 171 19 85 MBS 06H 13.27 171 10 86 MBM 03H 38.45 171 48 86 MBM 03H 18.47 89 68 86 MBM 07H 24.06 85 122 86 MBM 07C 35.81 97 101 87 MBM 07C 29.48 87 73 89 MBM 05H 37.10 95 120 90 MBM 07C 34.76 99 21 91 MBM 07H 17.27 171 25 91 MBM 06H
-1.58 169 D-3
Appendix D Tubes with Other Anomalous Signals SG-B ROW COLUMN INDICATION LOCATION CAL NUMBER 57 91 MBM 08H 7.59 93 48 92 MBM 04H 17.43 93 17 93 MBM 01H 22.70 171 25 93 MBS 03H 35.25 171 55 93 NQS 06C 32.66 93 112 96 MBM 08C 17.82 93 97 97 MBM A12 20.67 143 123 97 MBM 06C 31.86 141 122 98 NQS TSC 4.68 143 3
99 NQS 09H 2.74 121 109 99 MBS 07H 13.19 139 8
102 MBM 08H 20.30 119 90 102 NQS 02C 35.49 143 27 103 NQS FBH 15.21 151 85 103 MBM 06C 4.59 139 16 104 MBM 07H 24.37 149 42 104 MBM 04C 9.66 153 45 105 NQS 03H 31.93 147 81 105 NQS TSC 11.19 147 83 105 MBM 06C 19.83 147 6
106 MBM 05H 37.84 123 36 106 MBM 04C 28.55 155 109 107 MBM 07C 30.27 139 93 109 M BM 06C 17.85 177 32 110 MBM 03H 7.03 177 32 110 MBM 01H 32.44 177 102 110 NQS 02H 12.29 147 103 113 NQS 02C 32.65 147 111 113 MBM A6 6.67 147 12 114 MBM 07H 22.41 155 32 114 MBM 08C 29.42 155 76 114 MBS 08H 34.17 147 29 115 MMB 07C 26.58 155 63 115 MBM 07C 4.68 145 103 115 NQS 08H 5.17 145 2
116 MBM 05C 4.54 14 29 117 MBM 04H 35.99 153 35 117 MBM 02C 4.86 153 65 119 MBM 04C 26.26 149 38 122 MBM 06C 11.41 155 38 122 MBM 07C 6.90 155 76 122 MBM 06C 29.63 151 80 122 MBS 06H 26.52 151 88 122 NQS TSC 14.47 151 D-4
Appendix D Tubes with Other Anomalous Signals SG-B ROW COLUMN INDICATION LOCATION CAL NUMBER 9
123 MBM FBC 17.46 14 27 123 MBM 01C 24.76 155 32 124 MBM 07H 22.30 155 17 125 MBM 05H 10.77 155 86 126 NQS 06H 13.14 155 33 127 MBM 01H 11.63 155 45 127 MBM 08C 6.12 153 47 127 MBM 03C 7.95 157 89 127 MBM 08C 25.66 159 66 128 MBM 07C 1.73 157 23 129 MBM 06H 14.76 157 41 129 NQS 08H 26.62 159 30 132 MBM 05H
-1.67 159 26 134 NQS 06C 19.13 159 74 134 MBM 06C 3.31 159 3
135 BLG 09H
-1.94 131 37 135 MBM 02C 3.04 161 63 135 MBM A12 2.21 161 73 137 NQS 07H 33.20 167 73 137 NQS 03H 27.92 167 2
138 MBM FBH 11.70 131 27 139 MBM 05H 33.64 167 57 139 MBM 08C 11.43 167 17 141 MBM 09H 2.64 167 20 142 NQS 08C 20.26 165 30 142 MBM 08H 4.01 165 7
143 NQS 08C 16.11 14 7
143 NQS 08C 23.32 14 9
143 MBM 06H 8.00 133 33 143 NQS 08H 11.94 167 9
147 NQS 08H 37.32 131 33 147 NQS 03C 3.19 169 47 147 MBM 05H 29.32 169 15 153 MBM 03H 21.78 167 2
154 MBM 07C 29.33 18 D-5
Tubes with Other Anomalous Signals SG-C ROW COLUMN INDICATION LOCATION CAL NUMBER 45 7
NQS A12 4.85 7
6 8
MBM 05H 34.25 107 8
8 MBM 05C 19.43 4
34 8
MBM TSC 14.92 11 44 8
MBM 02C 16.93 5
9 9
MBM 05C 3.72 4
9 9
MBM 04C 36.00 4
36 10 NQS 05H 9.89 11 49 11 NQS 07H 27.92 7
55 11 NQS 08H 13.05 7
65 13 MBM A15 7.09 9
18 14 MBM 02C 11.80 9
65 15 MBM 08C 29.37 9
65 15 MBM All 2.03 9
51 17 NQS 05H 9.23 15 18 20 MBM 02C 15.72 13 30 20 NQS 08C 27.10 15 31 21 MBM 05H 10.07 15 58 22 MBM TSC 14.04 15 9
23 MBM 04C 4.10 2
9 23 MBM 08C 36.15 2
27 23 MBM 08C 3.00 19 47 25 MBM 08C 9.30 25 88 26 MBM 08H 37.38 7
14 30 MBM 06C 26.29 31 21 31 MBM 03H 11.45 31 21 31 MBM 03H 13.98 31 71 31 MBM A10 6.26 31 62 32 NQS 09H 10.01 31 99 33 MBM 03C 25.76 33 20 34 MBM 02H 36.61 35 7
35 MBM 04H 9.95 105 77 35 MBM 08C 8.89 35 97 35 MBM A6 14.94 33 101 35 NQS 08H 17.05 35 6
36 MBM 06C 22.22 4
12 36 MBM 09H 2.10 35 50 36 NQS 03C 11.92 35 98 36 MBM 08H 30.69 35 20 38 MBM 05C 25.60 37 82 40 MBM 03H 13.98 35 75 41 MBM 02C 12.04 39 18 42 MBM 02C 31.21 41 34 42 MBM 03H 23.93 41 34 42 MBM 05C 10.98 41 36 42 MBM FBC 4.97 41 D-1 Appendix D
Tubes with Other Anomalous Signals SG-C 102 42 MBM 06C 21.73 43 95 43 MBM 01H 19.71 43 12 44 MBM 05H 7.07 41 106 44 MBM 08H 25.50 43 19 45 MBM 03C 5.46 49 6
46 MBM 06C 36.16 6
18 46 MBM 03C 3.80 51 18 46 MBM 01H 5.01 51 62 46 NQS 05C 17.80 49 15 47 NQS 04C 7.65 49 15 47 NQS 04C 7.84 51 65 47 MBM 08C 33.29 47 65 49 MBM 07C 26.94 49 22 50 MBM 06H 7.40 51 38 50 MBS 06H 16.09 51 56 50 MBM 04C 14.82 49 77 51 NQS 02C 21.60 53 77 51 MBM 02C 20.89 53 6
52 MBM FBC 2.25 8
56 52 MBM 07H 2.78 55 31 53 MBM 03H 37.75 55 31 53 MBM 04H 3.61 55 88 54 MBM 03H 2.84 55 92 54 NQS 07H 25.16 53 79 55 MBM 08C 10.63 53 44 56 MBM 07C
-1.59 53 39 57 MBM 01H 16.04 57 53 57 MBM 05C 31.45 57 51 61 MBM A2 7.12 65 71 61 MBM A16 9.40 65 117 61 NQS 07C 19.62 63 6
62 NQS 07C 32.30 6
74 62 MBM 04H
-1.70 63 118 62 NQS 05C 1.81 63 122 62 MBM 03C 2.47 63 23 63 NQS 04H 21.89 73 51 63 MBM 08H 23.74 63 69 63 MBM 05C 1.76 63 105 63 MBM 05H 35.43 65 4
64 MBM 02C 33.80 8
12 64 MBM 01H 3.80 71 54 64 MBM 04C 23.79 67 9
65 MBM 05H 2.30 105 33 65 MBM 04H 29.49 67 28 66 MBM 04H 25.79 69 124 66 MBM A16 5.81 63 37 67 MBM 01C 10.66 69 D-2 Appendix D
Tubes with Other Anomalous Signals SG-C 51 67 NQS All 3.25 69 117 67 MBM 08H 34.66 69 64 68 MBM 04C 5.14 67 2
70 MBM 01C
-1.72 6
102 70 MBM 07H 14.87 69 121 71 MBM 01H 8.65 69 100 72 MBM A8 11.51 77 102 72 MBM 07H 36.29 79 10 74 MBM 07H 26.59 71 106 74 MBM 05C 13.56 81 106 74 MBM 07H 32.55 81 15 75 MBM TSH 25.76 75 45 75 MBM 03H 9.63 75 51 75 MBM 05C 36.79 75 20 76 MBM 01C 29.23 77 106 76 NQS A16 7.20 95 25 77 MBM 01H 10.29 77 41 79 MBM 08H 35.42 75 20 80 NQS 06C 8.80 169 80 80 NQS 04H 23.08 77 80 80 NQS 04H 31.76 77 126 80 MBM 04C 33.82 83 37 81 MBM 01C 5.08 93 3
83 MBM 08H 12.21 157 123 83 NQS 06H 24.55 89 50 84 MBM 06C 16.67 93 50 84 MBM 06C 5.76 93 66 84 MBM 03C 7.76 93 76 84 MBM 04H 33.29 87 86 84 NQS 05H 24.78 87 113 87 MBM 02H 12.44 89 127 87 MBM 01C 29.94 89 127 87 MBM 06C 35.61 89 127 87 MBM 07C 25.55 89 22 88 NQS 03H 32.17 169 13 89 MBM 02C 12.12 169 15 89 MBM 07C 20.94 169 83 89 NQS 02H 36.81 87 20 90 MBM TSH 28.77 165 54 90 NQS 07C 3.78 91 58 90 MBM 05C 35.68 91 75 91 MBM 05H 29.89 89 109 91 MBM A12 15.26 93 117 91 MBM 07C 32.48 93 22 92 MBS TSC 16.87 165 26 92 MBM 05H 25.08 165 3
93 MBM 07H 24.18 157 D-3 Appendix D
Tubes with Other Anomalous Signals SG-C 37 93 MBM 05H 21.92 139 85 93 NQS 08H 4.23 91 99 93 MBM 02C 36.66 91 32 94 MBM 03H 14.30 139 50 94 MBM 08C 14.99 91 21 95 MBM 05C 36.32 165 25 95 MBM 01C 36.05 165 81 95 MBM 01C 35.15 93 85 95 NQS 06H 14.79 93 99 95 MBM 01H 9.65 93 99 95 MBM 02H 26.35 93 101 95 NQS 06C 37.07 93 107 95 MBM FBH 12.86 93 6
96 MBM 06C 3.18 12 14 96 MBM 02C 16.71 165 18 96 MBM 06H 20.77 165 51 97 MBM 08H 34.15 141 51 97 MBM A12 1.05 141 67 97 MBM 02C 21.76 141 50 98 NQS FBH 10.60 139 108 98 MBM A2 10.26 113 11 99 NQS 08H 13.41 135 79 99 NQS 08H 28.26 139 101 99 MBM 04C 13.12 113 107 99 MBM A2 2.00 113 2
100 MBM 08H 35.59 147 14 100 NQS 04C 33.77 135 63 101 NQS 01H 12.17 137 63 101 NQS 01H 14.74 137 65 101 NQS FBC 15.11 137 65 101 NQS FBC 15.96 137 91 101 MBM A6 9.98 111 107 101 MBM 03C 7.77 111 117 101 NQS 06H 21.85 111 121 101 NQS A10 4.98 111 9
103 MBM 07C 19.59 8
20 104 NQS 07C 32.90 135 93 105 MBM 04C 2.09 113 10 106 MBM 07C 9.56 135 58 106 NQS 04H 12.66 137 118 106 MBM A16 20.39 113 18 108 MBM 06C 6.49 135 64 108 MBM 05C 7.13 135 64 108 MBM 08C 9.32 135 49 109 MBM 03H 35.13 133 4
110 MBM 03C 11.21 8
19 111 MBM 08C 5.52 131 D-4 Appendix D
Tubes with Other Anomalous Signals SG-C 78 112 MBM 07C 25.89 115 25 113 MBM 06C 18.18 133 4
114 MBM 04C 18.68 8
38 114 NQS 04H 29.57 131 74 114 MBM A7 2.41 117 98 118 MBM 08C 16.06 117 86 120 MBM 09H 6.03 115 90 120 MBM 02H 36.24 115 65 121 MBM 05H 8.98 115 10 122 MBS 08C 32.58 127 88 122 MBM A4 5.54 117 92 122 MBM 09H 17.52 117 39 123 NOS 08C 9.38 127 33 125 NQS 08H 14.86 129 35 125 MBM 02C 32.12 129 6
126 NQS 04C 34.04 8
38 126 NQS 01C 18.45 127 33 127 NQS 05H 23.08 127 40 128 MBS 05C 28.16 129 42 128 MBS 06C 16.22 129 68 130 NQS 02C 32.02 121 41 131 MBM TSH 10.71 127 55 135 MBM 02C 2.25 125 71 137 MBM FBC 17.02 123 26 138 MBM 06H 1.84 123 47 141 MBM A5 4.81 123 35 145 NQS A13 1.39 123 2
150 MBM 02C 36.31 6
24 150 MBM TSH 12.51 123 6
152 MBM 08H 34.01 147 8
152 MBM 08H 18.42 147 6
154 MBM 08C
-1.73 6
D-5 Appendix D
Tubes with Other Anomalous Signals SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 10 4
MBM 06C 8.42 21 12 4
MBM 02C 26.14 21 30 6
MBM 01C 16.93 21 7
7 MBM 08C 15.89 4
27 7
MBM 03C 14.36 21 27 7
MBM 01C 28.85 21 24 8
MBM 03H 18.79 21 21 11 MBM FBH 6.28 3
43 11 MBM 07H 31.76 5
43 11 MBM 01H 27.29 5
4 12 MBM 06H 17.69 87 6
12 MBM 07H 34.49 89 44 12 NQS 07C 15.51 5
46 12 MBM 08C 30.94 7
37 13 MBM 01C 26.60 5
37 13 MBM 01C 29.76 5
2 14 NQS 09H 2.37 89 38 14 MBM 06C 9.11 5
42 14 MBM 02C 34.02 7
37 15 MBM 01C 22.21 5
22 16 MBM 07C 19.97 7
9 17 MBM 07C 18.21 2
13 17 NQS 07H 36.92 23 12 18 NQS TSC 14.03 23 46 18 MBM FBC 16.64 7
71 19 MBM 02H 33.96 7
74 20 MBM 06C 32.45 7
69 21 MBM 06H 21.68 5
26 22 MBM 08H 20.17 5
62 22 MBM 08H 10.94 7
64 22 MBM 05C 14.58 7
72 22 MBM 08C 36.54 7
22 24 MBM 05H 14.96 11 30 24 NQS 02H 11.26 9
5 25 MBM 04C
-1.50 2
55 25 NQS A14 3.95 11 45 27 MBM 02C 11.08 11 53 27 MBM 01H 30.22 11 59 27 MBM 01C 22.40 11 59 27 MBM FBC 8.05 11 59 27 MBM TSC 2.93 11 77 27 MBM 06H 35.74 11 12 28 NQS 04H 33.55 21 23 29 MBM 02H 26.89 11 93 29 MBM 02C 15.79 9
36 30 MBM 08C 2.68 85 D-1 Appendix D
Tubes with Other Anomalous Signals SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 88 30 MBM 03C 4.51 9
17 31 MBS 07C 32.02 21 17 31 MBS 07C 4.98 21 83 31 MBM 07H 37.54 13 53 33 MBM 08C 5.16 13 53 33 MBM 08C 8.94 13 75 33 MBM 06H 6.78 13 75 33 MBM 03C 19.13 13 76 34 MBM 08C 22.99 15 7
35 MBM 05C 28.08 4
87 35 MBM 08H 36.74 13 66 36 MBM 06H 9.89 13 78 36 MBM A12 5.35 15 27 37 MBM 05C 35.24 13 51 37 MBM 02H 13.96 13 54 38 NQS 03C 30.49 15 44 40 MBM 05C 22.67 13 58 40 MBM 05C 22.61 15 78 40 MBM 07C 10.48 13 19 41 MBM 01C 12.71 27 77 41 MBM 04C 20.59 17 24 42 MBM 07C 21.05 17 32 42 MBM 03C 16.53 17 66 42 MBM 01H 17.96 19 102 42 MBM 03H 21.98 17 69 43 MBM 08C 3.86 17 96 44 MBS 02C 21.90 17 27 45 MBM 02C 21.96 17 73 45 MBM 02C 19.04 19 113 45 MBM A16 3.64 17 64 46 MBM 05H 28.40 17 46 48 MBM 03C 36.78 27 15 49 MBM 02H 31.38 33 23 49 MBM 02C 13.02 85 81 49 NQS 08H 16.46 29 81 49 NQS 05C 15.65 29 46 50 MBM 08H 19.68 29 70 50 MBM 08C 32.32 31 98 50 MBS 09H 5.35 29 11 51 MBM 06H 30.87 35 114 54 MBM 02H 23.09 79 118 54 MBM 08C 14.74 37 13 55 MBM 04H 9.01 57 37 55 MBM 07H 26.74 41 45 55 MBM 05H 20.60 41 71 57 MBM 07H 26.67 41 D-2 Appendix D
Tubes with Other Anomalous Signals SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 2
58 MBM 07H 28.91 93 21 59 MBM 06C 12.00 41 79 59 MBM 01C 23.07 45 56 60 NQS TSC 13.98 45 1
61 MBM 02H 32.10 95 40 62 MBM 08H 25.99 49 83 63 MBM 03C 36.05 49 97 63 MBM 07H 35.28 51 113 63 MBM 04C 9.94 51 54 64 MBM 05C 17.73 49 55 65 NQS TSC 2.08 51 84 66 MBS 02H 3.57 49 84 66 MBM 02H 3.57 207 12 68 MBM 07C 14.40 63 106 68 MBM A3 1.50 57 21 69 MBM 07H 29.06 63 30 70 MBM TSH 2.09 59 80 70 MBS 05H 24.78 57 116 70 NQS 06C 34.66 57 79 71 MBM 05H 37.79 63 124 72 NQS 08C 26.86 61 69 75 MBM 07H 27.61 63 76 76 MBM 07H 5.56 65 109 77 NQS A4 2.78 61 109 77 MBM A4 4.42 61 117 77 MBM A5
-1.75 61 23 79 MBM 08H 21.08 67 23 79 MBM 04H 26.23 67 23 79 MBM 04H 24.49 67 28 80 NQS 07H 2.07 73 14 82 MBM TSH 21.19 191 50 82 NQS 04H 8.99 67 70 82 MBM 01H 10.54 69 70 82 MBM 07H 10.36 69 96 84 MBM 04H 35.62 69 114 84 MBM 06C 37.34 69 45 85 NQS 06C 19.07 75 87 85 MBM 08C 20.10 69 103 85 MBM 08H 16.49 69 51 87 MBM FBH 16.63 73 67 87 MBM 05H 9.35 73 117 87 MBM 03H 30.91 79 117 87 MBM 03H 34.54 79 89 89 MBM 06H 23.22 83 95 89 MBM 08C 14.10 83 4
90 MBM 03C 23.26 18 D-3 Appendix D
Tubes with Other Anomalous Signals SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 8
90 MBM 08C 1.40 18 42 90 NQS 04H 11.81 75 90 90 MBM FBH 16.07 85 21 91 MBM 03C 2.49 191 29 91 MBM 03H 37.77 155 97 91 NQS 01C 26.34 81 109 91 NQS 07H 33.66 81 4
92 MBM 07C 38.25 18 4
92 MBM TSH 18.96 193 4
92 MBM TSH 18.28 197 8
92 MBM 08H 22.71 193 8
92 MBM 08H 22.73 197 54 92 NQS 07H 37.67 107 54 92 NQS 04H 18.05 107 54 92 NQS 06H 7.18 107 64 92 MBM 07H 15.82 107 98 92 MBM 06H 25.35 107 6
94 MBM 01C 19.90 18 84 94 MBM 02C 28.67 105 112 94 MBM 02C 24.05 105 5
95 MBM TSC 5.11 18 19 95 MBM 01C 8.56 191 28 96 MBM 04C 18.39 153 52 96 MBM 07C 23.31 111 52 96 MBM 02H 12.06 111 99 97 MBM A12 5.26 111 14 98 MBM 08C
-1.99 153 18 98 MBM 07H 10.08 153 38 98 NQS TSC 17.44 155 38 98 NOS A16 3.86 155 38 98 NQS 01C 15.98 155 38 98 NQS TSC 11.09 155 38 98 NQS TSC 14.78 155 38 98 NQS TSC 9.42 155 38 98 NQS FBC 8.80 155 38 98 NQS 01C 6.67 155 38 98 NQS TSC 15.52 155 94 98 MBM A12 11.97 105 63 99 MBM 04H 27.95 109 67 101 MBM TSC 18.36 111 67 101 MBM 08H 12.07 111 93 101 MBM 01H 5.08 111 96 102 NQS 07H 22.36 109 114 102 MBM 05C 4.39 109 118 102 MBM 07H 8.83 109 4
104 MBM 04C 6.15 6
D-4 Appendix D
Tubes with Other Anomalous Signals SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 38 104 MBM 03C 4.59 111 39 105 NQS 01C 13.07 115 57 107 NQS 07C 9.03 113 57 107 NQS TSC 10.12 113 45 109 MBM 02H 5.32 115 4
110 MBM 03C 30.53 8
61 111 MBM 01H 11.94 113 28 112 MBM 04C 18.53 119 54 112 MBM 07H 22.43 115 54 112 MBM 04H 26.69 115 76 112 MBM TSH 5.28 115 9
113 MBM 06H 18.46 187 9
113 MBM 06H 18.39 163 25 113 MBM FBC 17.26 119 55 113 MBM 07H 27.50 119 32 114 MBM 09H 6.83 117 64 114 NQS 07H 12.95 113 106 114 NQS 08H 35.27 113 25 115 MBM FBH 15.34 117 41 115 MBM 03C 24.57 117 65 115 MBM 01C 24.13 117 34 116 MBM 05C 36.06 157 40 116 MBM A4 1.76 157 46 116 MBS 05H 32.78 123 62 116 MBM 02H 8.26 123 21 117 MBM 05C 22.80 145 32 118 NQS 08C 7.09 157 95 119 MBM 04C 20.05 123 30 120 MBM 03H 6.16 123 40 120 MBM A16 7.23 123 21 121 MBM FBH 3.79 145 89 121 MBS 06H 32.31 123 86 122 MBS 07H 11.52 127 75 123 MBM 04C 19.41 127 66 124 NQS 05C 29.49 129 29 125 MBM 01C 9.90 129 45 125 MBM 08H 6.23 129 2
126 MBM 08H 18.95 179 2
126 MBM 08H 18.96 173 22 126 NQS 06H 25.62 145 26 126 MBS 06H 11.75 127 26 126 MBM 06H 11.75 207 28 126 MBS 06H 3.06 127 29 127 MBM 05H 23.82 127 37 127 MBM 07C 32.14 127 95 127 MBM 03C 9.56 127 D-5 Appendix D
Tubes with Other Anomalous Signals SG-D ROW COLUMN INDICATION LOCATION CAL NUMBER 96 128 MBM 08C 24.65 129 87 129 MBM 08H 8.94 129 14 130 MBM FBH 9.39 145 36 130 MBM 01C 25.97 127 38 130 MBM 08C 17.17 127 46 130 MBM 08H 11.59 127 74 130 MBM 05C 34.97 127 76 130 MBM 02H 14.47 127 9
131 MBM 05H 6.73 165 22 132 MBM 07H 24.98 145 48 132 MBM A16 6.28 129 48 132 MBM 02C 38.09 129 35 133 MBM FBH 15.86 129 48 134 MBM 02C 38.11 127 61 135 MBM 08C 4.47 127 32 136 MBM 02C 27.73 129 48 136 MBM 02H 1.63 129 3
137 MBM FBH 7.53 165 30 138 NQS 06C 18.10 131 30 138 NQS 06H 14.27 131 30 138 NQS 05H 35.82 131 46 138 MBM 05C 25.32 131 46 138 MBM 06C 7.98 131 48 138 MBM 01H 29.54 131 11 139 NQS 06C 3.16 155 11 139 MBM 05C 38.04 155 13 139 MBM 01H 11.16 155 47 139 MBM 06H 7.06 133 72 140 MBM 01H 30.07 141 3
141 MBM 01H 19.67 165 20 142 MBM 03H 13.99 145 49 145 MBM 04C 36.01 145 49 145 MBM 08H 32.89 145 8
148 MBM 08C 21.71 10 50 148 MBM 03H 22.29 145 40 150 NQS 03C 23.08 143 7
151 MBM TSC 17.64 12 D-6 Appendix D
APPENDIX E TUBES REMOVED FROM SERVICE PRIOR TO AND DURING 1RE10
9Z:1,Z4Vb M~JSOM= 0DIS flSSN -oifl Auedwoo oMO913 tflO45u4lOM S
@t St OZ SZ SE SE St SV OS SS 09 59 SL 91 08 SO 06 96 GOT SOT SITt STT ST MZ GET SET Vtt SVTt OSt SSt 0000(00 0 0 "00 00"000010000T0 0100 00 00000 0D.00100
'D0'0I0 00100900'o
'0100
(
0I 90 01009.0 01".
0090TO1000 000000900040
- .0 0
o o
0..)0000 00 T,,
t Oo 0
.0 9
ST St OE SE St, 89 99 OL SL as S8 86 96 Sot Ott SZtt g*t gct S
,.o....
- .T...:*...T.:
.:.**...°..r..l.
o.....
o.....................
°.
' * *'t
" ~ o o."...'.'l.
.t.'."
I*..
o..
0" o..*._
,'-}.
.:.*.:.[!.:.T.:.:.:.I.:.[
l.:..:.:*.:..:.:
o.I.
0 S..
- o.
0.........
o o...I....l....
t...I..t..
I
+*.t.*
- .......:0.
.0
' T I.
I
.I
,T T " T i.:.
° 0
0 o
.t.
.l'"
l "l
l
- 'I:'"
l'
.:.1.
0
"'°"'""
?°°
}'°"....
I n
t
.t
- v.
o...
"....t.to......it....
o..
.'.'l.'.
a.'..t.'.'.'.).'.'.'.T..
e.t.
.ti*.l.*.Ts.'.'....
o....
o*
O O O '
.i
- l.
,.0 o...
- o.
.0:,:.o 0
o.
o o° 0o..
0
- 0.
- o.
0
- 0.
-o
- o.
0
- 0.
_o.
0 0
00
.~.
0 0
0 0 ~
.~
0 0o 0
0 o
.o o~ ~
~
0...0
-o~
o
-9 o-9 OT ST OZ SZ 8E SE St St 09 99 09 99 St 91 08 95 86 96 GOT SOT OTT S~t SZt S3T SCT SET Ott Stt S~t SST 3BN1 0399Nld CC a t76(] XDl0 OII.
sexej qlnoS S38nlCI30077d V-XOI
)
)
OT3MJT 9NIbrlI2 0399Nld S38N1 ON 9
OT ST Oz SE OC SC St, Sir a9 99 59 99 SL SL 59 98 56 96 GOt Sol O*T STr OZT SZT
Nl N-c4 5l to
-tS C
D S
C S
C D
C C11 LoD 0
0..
0.
..° 0.
0.
0 00700 0.'
- 0.
0
°00 I-
-J a
. o° 00 0.
'. *° L-.
CD
-J
- e.
MI U.'
0 CD 0
- 00.
- 0.
S-.
.0.
..° 0.
o.I T°.
o.?
..° I.
- o..
0 oI 1
+/- - -..
t 0.
0.
v2cý 0..
0'
- 0.
-0, 0 C
°oc La 0..
0o+'
0 0 0 t
0*
O0 0
L.
I. -
I -
.1 --
I. - 4-4 a.°+
..°
-.°,
In W
+..
.°.
° 1..
00.L.
0^...
- 0.
- 0.
0..
0.0.
0 °
=i!.
+..
CD S
61 0
WD W
U5 W
D S
C D
S C
C D
S C
D S
N~~~
~~~~ N) m4
.4C5 0
4 5
9 N
0 4
D C
11 4
-4
-4
-4
-4
-4 o
°-...~
.+
+..
0 00
.°°.'.
..i
...i.
iI
..l
.° 0n 0
0.
l
.n In aD CD 10 04 0
u.00 130 0
0 o° 0
00
- 0.
0...
0°.
0".
0*
0.
0.
0.
0, 0
- 0.
o 0 CD0 00 0
L0 CWD
- 0.
^..
0 0
0 Co m
D I
wx 0
I-i~
- 9) aD -4; 9n mD 9n CD
-4 CD)
- t..
.Oo.
. o
°°°
,°
,° 0
o, Oo o
+ _
000" 1
1 I
v v
.I
-i-i 0 " U : : :
° 0
..°
.il t*.
00*,°°
- ,...*.T 1
.°°
.°
°
°'
.+<'
.,+.,.,.
- °,-°"
"+*,'
+,
.°..
.°.'°
.°.."
.+.,.
.*°.
.*°
.°+
.°
.°°
.°-
X,,,
o 0,°oo oo
.°...
.i
° °
.+
..-. i.
' °
.0.0..
00 00
,.0o 0 () U
.*00
.. 0 0 0
- 0.
.0.
. 0
.. 0 0
.0
.00 Lo 0N
.0
.0
.- 0 o0
- 0
'0.0
.. 0
.00 0
CD
%00
.. 00
.. 0
..00o
.. 0
.- 0
.0
.0 0
0 Dn
.0
.0
.00 0 00
.0
.0 0 a
- '°o00
.0
-.°00 f
- 0.0 0..o
.0
- 0
.0
-4
. 0
.0
.0
° '00 0 m
- !e-, ý 0e
.0 0
m~
.0 0
.+.°000
- 0 00 "U,
.0
- ...:o;
.0 O-o
".o *°00 L "0
0 0 U
-.e-e-0 E
03
TGX-C PLUGGED TUBES South Texas 1REI0 TGX D94 a 26 PLUGGED TUBE NO TUBES PLUGGED DURING 1RE10 125 120 115 110 105 95 90 85 8s 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5
n a.,
a
O.
ft A
MS
1
19 5
155 150 145 140 135 130 125 120 115 110 105 100 95 90 85 80 75 70 655 60 b5 40 45 35 30 20 0
1W Westinghouse Eletuc Company LLC - NSBU ST2000 10115/2001 14:25:04 155 150 145 140 135 130 125 120 115 110 105O 1.0, 0 ;U ow 10 000 0 000 (0000 0 000 0 000 0 0 0
0 0
001 00 oo.
oo
- 0.
i
- 8 e.l
..o o S o?
,i o0 o-J
- : ; : : : o o0 0
.0
- 0.
.:0*
=
00
.0-
- 0.
.i
....°:..
00
.i
.i
.°':*.
0
.0
.°::
- =
?o..
- 0.
- 0.
o..
0 0'00 0
00 0
10 "0..
o;:..o.
.i ': :
.i
.i
". Oo o:~~ ~..
000.
.i
%0-i:ii 0:
- 00.
.i
.:°..° 0~0 o°°:: "
..i
.i
. : " :.: i:. :"
.,~
00 o...o'"~ ~.i
.i
.:i i..::
e0
.0 00 0
- 0.
0
.0 0
o.0 0.0 0:
0..
0
.0 0
0 0
00 00 000 0
0 000 00 0
0 0
0000 0
000 000 000 0000 000 00 0
0 0
00 00000*
00 0 0
0 0000 0000 0
000 0000 00 0
00000 0io' 0000 0
00000 00000*lo-000 0
00001 00o 125 120 115 110 195 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5
TGX-D PLUGGED TUBES South Texas 1RE10 TGX D94 a 9 PLUGGED TUBE NO TUBES PLUGGED DURING 1RE1I 155 150 145 126 120 115 110 105 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5
155 150 145 1W 135 130 125 120 115 110 105 100 95 90 85 80 76 70 65 60 56 50 45 49 35 30 25 28 15 is 5'
40 135 130 125 120 115 110 105 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5
I.
4
- ~ ~~
.[.
125 120 115 110 105 100 95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5
Westinghouse Electric Company LLC - NSBU ST2000 1/1G521 14:25:21
APPENDIX F OWNER'S REPORT FOR INSERVICE INSPECTIONS NIS-1 FORM
1 RE10 - Steam Generator Tubes FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules Page 1 of 2
- 1. Owner South Texas Project Nuclear Operating Company*; P.O. Box 289; Wadsworth, Texas 77483 (Name and Address of Owner)
- 2. Plant South Texas Project Electric Generating Station: P.O. Box 289; Wadsworth, Texas 77483 (Name and Address of Plant)
- 3. Plant Unit 1
- 4. Owner and Certificate of Authorization (if required)
N.A.
- 5. Commercial Service Date 08/25/88
- 6. National Board Number for Unit N.A.
- 7. Components Inspected ASME Code Class 1 (IWB) Items - Steam Generator Tubes
- South Texas Project Nuclear Operating Company (STPNOC) is the licensed operator of the S~dthexas Project Electric Generating Station STPNOC by &Date I 2.2/0?-Factory Mutual by Date Date_-22-0 M.E. Kanavos Insurance Co.
B.R.Russell,ANII Page 1 Component or Manufacturer or Manufacturer or State or National Appurtenance Installer Installer Serial Province No.
Board No.
No.
Steam Generator Westinghouse (M)
SG4L 12269 N. A.
66 IA Steam Generator lB Westinghouse (M)
SG4L 12270 N. A.
67 Steam Generator IC Westinghouse (M)
SG4L 12271 N. A.
68 Steam Generator Westinghouse (M)
SG4L 12272 N. A.
69 ID I
I
+/-
I I
4
-t I
I i
FORM NIS-1 (Back)
- 8.
Examination Dates 10-7-01 to 10-24-01
- 9. Inspection Interval from 9-25-00 to 9-25-10
- 10. Abstract of Examinations. Include a list of examinations and a statement concerning status of work required for current interval. (ASME Code Class 1 (IWB) Items - Steam Generator Tubes)
See Section 4.0 of the IRE1O Inservice Inspection Summary Report for Steam Generator Tubing.
- 11.
Abstract of Conditions Noted.
See Section 5.0 of the 1RE1O Inservice Inspection Summary Report for Steam Generator Tubing.
- 12. Abstract of Corrective Measures Recommended and Taken.
See Section 5.0 of the 1RE10 Inservice Inspection Summary Report for Steam Generator Tubing.
We certify that the statements made in this report are correct and the examinations and corrective mea sures taken conform to the rules of ASME Code,Section XI.
Certificate of Authorization No.(if applicable)
N.A.
Expiration Date N.A.
South Texas Project Nuclear Date I
21 7.
20 0 2.
Signed Operating Company Owner By 2A Ra L M. E. Kanavos 4m8 Page 2 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Texas and employed by Factory Mutual Insurance Co.
of Johnston, RI have inspected the components described in this Owner's Report during the period _
10-7-01 to 10-24-01 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising o
or connected with this inspection.
Commissions Tex 826 Inspec-tor's Signature National Board, State, Province, and Endorsements B. R. Russell Date 1
20 Page 2 of 2 1RE10 - Steam Generator Tubes