L-MT-08-043, Extended Power Uprate, Acceptance Review Supplemental Information Package 6
| ML081640435 | |
| Person / Time | |
|---|---|
| Site: | Monticello |
| Issue date: | 06/12/2008 |
| From: | O'Connor T Nuclear Management Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| L-MT-08-043, TAC MD8398 | |
| Download: ML081640435 (18) | |
Text
June 12,2008 L-MT-08-043 10 CFR 50.90 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Monticello Nuclear Generating Plant Docket 50-263 Renewed Facility Operating License License No. DPR-22 Monticello Extended Power Uprate (USNRC TAC MD8398):
Acceptance Review Supplemental lnformation Packaqe 6
References:
- 1) NMC Letter to USNRC, "License Amendment Request: Extended Power Uprate,"
dated March 31,2008
- 2) NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplement Regarding Radiological Analysis,"
dated May 20,2008
- 3) NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplemental Information," dated May 28, 2008
- 4) NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplemental lnformation Package 3," dated May 30,2008
- 5) NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplemental lnformation Package 4," dated June 3,2008
- 6) NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplemental lnformation Package 5," dated June 5,2008 Pursuant to 10 CFR 50.90, Nuclear Management Company, LLC (NMC), requested in Reference 1 approval of amendments to the Monticello Nuclear Generating Plant (MNGP) Renewed Operating License (OL) and Technical Specifications (TS) to increase the maximum power level authorized from 1775 megawatts thermal (MWt) to 1870 MWt, an approximate five percent increase in the current licensed thermal power (CLTP). The proposed request for Extended Power Uprate (EPU) represents an 2807 West County Road 75 Monticello, Minnesota 55362-9637 Telephone: 763.295.5151 Fax: 763.295.1454
Document Control Desk Page 2 increase of approximately 12 percent above the Original Licensed Thermal Power (OLTP). The Monticello EPU application was supplemented on May 20, 2008, May 28, 2008, May 30,2008, June 3,2008 and June 5,2008 by References 2, 3,4, 5 and 6.
On May 29, 2008, the NRC staff indicated that additional information was required by the Piping and Non-Destructive Examination Branch (CPNB) to complete the acceptance review. The responses to the questions are included in Enclosure 1.
In a teleconference held June 5, 2008, the NRC staff indicated that information in addition to that submitted in References 3 and 6 would be necessary for the Electrical Engineering Branch (EEEB) to complete the acceptance review of the Monticello EPU license amendment request (LAR). Responses to the questions are included as.
NMC has reviewed the No Significant Hazards Consideration and the Environmental Consideration submitted with Reference 1 relative to the enclosed supplemental information. NMC has determined that there are no changes required to either of these sections of Reference 1.
Commitment Summarv This letter makes no new commitments and does not change any existing commitments.
I declare under penalty of perjury that the foregoing is true and correct.
Nuclear Generating Plant cc: Administrator, Region Ill, USNRC Project Manager, Monticello, USNRC Resident Inspector, Monticello, USNRC Minnesota Department of Commerce Enclosures (2)
- 1., Piping and Non-Destructive Examination Branch Questions and Responses
- 2., Electrical Engineering Branch Questions and Responses to L-MT-08-043 Piping and Non-Destructive Examination Branch Questions and Responses In lieu of questions, the Nuclear Regulatory Commission (NRC) Piping and Non-Destructive Examination Branch (CPNB) staff provided references showing, by comparison, information that appears to be missing from the Monticello Extended Power Uprate (EPU) application. The references were:
Susquehanna, ML071000141, dated April 10,2007 Hope Creek, ML070460243, dated February 23,2007 Vermont Yankee, ML033640138, dated December 30,2003 Browns Ferry, ML043440045, dated December 30,2004 Based on review of the above precedent, Nuclear Management Company, LLC (NMC) has provided responses to the questions asked most recently in the Susquehanna reference. The questions from the remaining references are noted at the end of this enclosure and reference back to the responses provided below.
NRC Question:
1 Identify the materials of construction for the reactor coolant pressure boundary (RCPB) piping and safe-ends. Discuss and explain the effect of the requested power uprate on the RCPB piping and safe-end materials and its impact on the potential degradation mechanisms.
NMC Response:
Appendices A and B of the NRC staff's evaluation of Monticello Nuclear Generating Plant's (MNGP) response to Generic Letter (GL) 88-01 identify the materials of construction for the reactor coolant pressure boundary piping and safe end materials at Monticello. The NRC safety evaluation (SE) was received December 19, 1989 (Reference 1). The NRC SE noted that all welds in the reactor coolant pressure boundary within the scope established by GL 88-01 are category " A. Therefore, all reactor coolant pressure boundary welds at Monticello are resistant to sensitization and Intergranular Stress Corrosion Cracking (IGSCC).
MNGP was originally designed as an ANSI B31. I plant. Modifications to the RCPB have typically used ASME Section Ill materials as shown below. Some original materials still exist.
Location Material 1
Recirculation Outlet Nozzle (NI) Safe End Recirculafion Inlet Nozzle (N2) Safe End SA358 Type 31 6 SA182 F316L Steam Outlet Nozzle (N3) 'safe End A5 16 Grade 70 I End 1
Resistant Clad (CRC) 1 Feed Water Nozzle (N4) Safe End Core Spray Nozzle ( ~ 5 j Safe End Head Spray Cooling Nozzle (N6a) Safe Page 1 of 7 A508 Class 1 SA350 Gr. LF2QT SA182 Gr. F304 with Corrosion Implementation of EPU conditions at Monticello will result in an increase in:
Location Head Spray Cooling Spare Nozzle (N6b)
Safe End Vent Nozzle (N7) Safe End Jet Pump Instrumentation Nozzle (N8A &
B) Penetration Seal Core Differential Pressure & Liquid Control Nozzle Safe End (N 10)
Recirculation Piping Main Steam Piping Feed Water Piping Core Spray Piping RWCU Piping Jet Pump Instrumentation Piping (line sections >200°F)
CRD Nozzle N9 Weld Cap Core Differential Pressure & Liquid Control Piping (line sections >200°F)
CRD Scram Discharge Volume Piping LPCIIRHR Piping neutron fluence, main steam and feedwater flow rate operating temperature for the feedwater system Material SA182 Gr. F304 with Corrosion Resistant Clad (CRC)
SA182 Gr. F304 with Corrosion Resistant Clad (CRC) 316 nuclear grade with 0.02%
maximum carbon SA182 F316 or SA479 316 SA376 TP 3 16* or SA358 Type 316*
- 0.02% max. carbon, 0.06-0.1 3%
nitrogen A106 Gr. B A106 Gr B or SA106 Gr. B or SA-333 Gr 6 Seamless, SA 420-WPL6 SA333 Gr. 6 or SA 671 GR CC70 Class 32 or SA 106 GR B SA358 C1 or A-1 06B or A672, Gr B70 SA3 12 TP3 16L SA182 F316L SA312 TP304L or 316L A358 or A312 GR. 304L A-1 06B, SA-106 Gr. B, SA 358 TP316*, SA-333 Gr 6 (Seamless),
SA 671 Gr CC70 Class 32
- 0.02% max. carbon, 0.06-0.1 0%
nitrogen The primary material effects are increases in material fatigue usage, the potential for Irradiation Assisted Stress Corrosion Cracking (IASCC), the potential for Flow-Accelerated Corrosion (FAC), and the potential for flow induced vibration.
Page 2 of 7 These material effects are addressed as follows:
Impact on IGSCC (NRC Generic Letter 88-01 and NUREG-0313, Rev. 2) the Monticello EPU license amendment request (LAR), Reference 2, Enclosure 5 (NEDC-33322P), Section 2.2.2.
EPU effects on material fatigue usage for safe ends and piping are discussed in Reference 2, Enclosure 5, Sections 2.2.2 and 2.2.3.
The increase in fluence and the associated effect on IASCC are discussed in Reference 2, Enclosure 5, Section 2.1.4.
The increases in flow rate and temperature that result from EPU, and the associated effect on the FAC monitoring program are discussed in Reference 2,, Section 2.1.6 and Reference 3, Enclosure 3.
The increases in flow rate that result from EPU and the effects on flow-induced vibration are discussed in Reference 2, Enclosure 5, Section 2.2.2 and in Reference 2, Enclosure 10.
EPU will not reduce material resistance to sensitization for IGSCC.
NRC Question:
- 2.
ldentify the RCPB piping and safe-end components that are susceptible to intergranular stress-corrosion cracking (IGSCC). Discuss any augmented inspection programs that have been implemented and the adequacy of the augmented inspection programs in light of the EPU.
NMC Response:
As stated in Question 1 above, all subject welds at MNGP meet NUREG-0313, Rev. 2, Category "A" and are considered resistant to IGSCC. Therefore, there are no augmented inspection programs implemented at Monticello. The current Inservice Inspection (ISI) program examinations are adequate given the configuration and degradation mechanisms present.
NRC Question:
- 3.
ldentify all flawed components including overlay repaired welds that have been accepted for continued service by analytical evaluation based on the American Society for Mechanical Engineers,Section XI rules. Discuss the adequacy of such analyses considering the effect of the EPU on the flaws.
NMC Response:
No weld overlays have been installed to mitigate flaws within the reactor coolant pressure boundary. Furthermore, no ASME flaw evaluations have been performed on components within the reactor coolant pressure boundary as a result of indications discovered during IS1 examinations.
Page 3 of 7
Enclosure I NRC Question:
- 4.
Identify the mitigation processes being applied at Monticello to reduce the RCPB component's susceptibility to IGSCC, and discuss the effect@) of the requested EPU on the effectiveness of these mitigation processes. For example, if hydrogen water chemistry (HWC) was applied at the plant, it would be necessary to perform the electrochemical potential measurements at the most limiting locations to ensure that the applied hydrogen injection rate is adequate to maintain the effectiveness of HWC (since oxygen content in the coolant is expected to increase due to the increased radiolysis of water from extended power uprate).
NMC Response:
As discussed in the response to Question I, the NRC SE regarding MNGP's response to Generic Letter 88-01 (Reference I), noted that all welds in the reactor coolant pressure boundary are Category " A. Mitigation by use of resistant materials is not impacted since EPU does not impact pressure boundary material properties as defined by Section 2.1.1 of NUREG-031 3, Rev. 2.
Appendices A, B, and C of Reference 1 describe the RCPB welds that were solution heat treated or were stress improved using the induction heating stress improvement (IHSI) process. Corrosion resistant cladding (CRC) was applied to the internal surfaces of the welds in the Head Spray Nozzles and the Head Vent Nozzles. The flow, pressure, temperature and mechanical loading for most of the RCPB piping systems do not increase for EPU. Consequently, there are no changes in stress. Construction processes such as solution heat treatment, lHSl or CRC are not impacted by EPU.
Hydrogen Water Chemistry (HWC) is used at MNGP. The HWC system reduces the susceptibility of RCPB components to IGSCC in the primary system piping and improves the resistance to IGSCC in vessel internal components. The implementation of HWC further reduces the probability of degradation of pressure boundary welds to environmental effects. The HWC system was installed in accordance with the recommendations of the BWR Owners Group, "Guidelines for Permanent BWR Hydrogen Water Chemistry Installation - 1987 Revision." MNGP is a Category 2 plant using moderate HWC. Category 2 plants use the BWRVIP-112 (BWR Vessel and lnternals Project, BWR Vessel and lnternals Application (BWRVIA) Version 2.0 for Radiolysis and ECP Analysis) model to estimate the total oxidant and electrochemical potential (ECP) at various locations. Hydrogen injection rates will be increased to maintain hydrogen concentration in feedwater at a constant level and maintain ECP within acceptable limits. ECP is verified at Monticello to be <-330 mV SHE, which provides margin to the IGSCC mitigation value of -230 mV SHE. These actions will ensure that EPU will not affect the water chemistry controls used for IGSCC mitigation.
ECP probes have not been used in the recent past within MNGP's RCPB. However given the materials of construction, the use of solution heat treatment, IHSI, or CRC, and the presence of HWC with ECP verified by BWRVIA modeling, adequate mitigation Page 4 of 7 processes are in place to ensure continued acceptable performance of the RCPB welds.
Questions from the remaining references:
A.
Hope Creek, ML070460243, dated 2123107,lst page of attachment 5.1 ldentify the materials of construction for the reactor coolant pressure boundary (RCPB) pipinglsafe-ends. Discuss and explain the effect of the requested power uprate on the RCPB pipinglsafe-end materials.
See the response to Question 1 above.
5.2 ldentify the RCPB pipinglsafe-end components that are susceptible to intergranular stress corrosion cracking (IGSCC). Discuss any augmented inspection programs that have been implemented and the adequacy of the augmented inspection programs in light of the EPU.
See the response to Question 2 above.
5.3 ldentify all flawed components including overlay repaired welds that have been accepted for continued service by analytical evaluation based on American Society of Mechanical Engineers (ASME),Section XI rules.
Discuss the adequacy of such analysis considering the effect of the EPU on the flaws.
See the response to Question 3 above.
5.4 ldentify the mitigation processes being applied at Hope Creek to reduce the RCPB component's susceptibility to IGSCC, and discuss the effect of the requested EPU on the effectiveness of these mitigation processes. For example, if hydrogen water chemistry (HWC) was applied at the plant, it would be necessary to perform the electrochemical potential measurements at the most limiting locations to ensure that the applied hydrogen injection rate is adequate to maintain the effectiveness of HWC since oxygen content in the coolant is expected to increase due to increased radiolysis of water resulting from extended power uprate.
See the response to Question 4 above.
B.
Vermont Yankee, ML033640138, dated 12130103, page 5 of attachment
- 1.
Section 3.5.1 of Attachment 4 of your submittal dated September 10, 2003, provides the results of the structural evaluation of the reactor coolant pressure boundary (RCPB) piping. Provide the basis for the disposition of the first system listed in this section.
Page 5 of 7
- 2.
ldentify the materials of construction for the Reactor Recirculation System piping and discuss the effect of the requested EPU on the material.
If other than type "A" (per NUREG 0313) material exist, discuss augmented inspection programs and discuss the adequacy of augmented inspection programs in light of the EPU.
See the response to Questions 1 and 2 above.
- 3.
Section XI of the American Society of Mechanical Engineers (ASME)
Code allows flaws to be left in service after a proper evaluation of the flaws is performed in accordance with the ASME,Section XI rules. Indicate whether such flaws exist in the Reactor Recirculation System piping and evaluate the effect of the EPU on the flaws.
See the response to Question 3 above.
- 4.
Discuss flaw mitigation steps that have been taken for the RCPB piping and discuss changes, if any, that will be made to the mitigation process as a result of the EPU.
See the response to Question 4 above.
C.
Browns Ferry, ML043440045, dated 12/30/04, questions 1-4
- 1.
Explain why the reactor coolant pressure boundary (RCPB) piping materials are not affected by the power uprate.
See the response to Question 1 above.
- 2.
Identify the materials of construction for the Reactor Recirculation System piping and discuss the effect of the requested extended power uprate (EPU) on the material. If other than type "A" (per NUREG 0313) materials exist, discuss any augmented inspection programs and discuss the adequacy of augmented inspection programs in light of the EPU.
See the response to Questions 1 and 2 above.
- 3.
Section XI of the American Society of Mechanical Engineers (ASME)
Code allows flaws to be left in service after a proper evaluation of the flaws is performed in accordance with the ASME,Section XI rules. lndicate whether such flaws exist in the Reactor Recirculation System piping and evaluate the effect of the EPU on the flaws.
See the response to Question 3 above.
Page 6 of 7
Enclosure I
- 4.
Discuss flaw mitigation steps that have been taken for the RCPB piping and discuss changes, if any, that will be made to the mitigation process as a result of the EPU.
See the response to Question 4 above.
References:
- 1.
USNRC Letter to NSP, "Monticello Nuclear Generating Plant - Staff Evaluation of Response to Generic Letter 88-01 (TAC No. 69146)," dated December 7, 1989.
- 2.
NMC Letter to USNRC, "License Amendment Request: Extended Power Uprate," dated March 31, 2008.
- 3.
NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplemental Information," dated May 28,2008.
Page 7 of 7 to L-MT-08-043 Electrical Engineering Branch Questions and Responses NRC Question:
I. Provide the staff with the USAR section number that describes the AC load Study.
NMC Response:
The AC load study is described in Monticello USAR Section 8.1 0, "Adequacy of Station Electrical Distribution System Voltages."
NRC Question:
- 2.
The licensee will provide statements that the margins discussed in the acceptance review response for the batteries will be met during the development of the modifications.
NMC Response:
In Reference 2, Enclosure 4, NMC reported the following with respect to DC battery capacity margins at Current Licensed Thermal Power (CLTP) and Extended Power Uprate (EPU) conditions:
Table 1 - Battery Margin 1 250 VDC Division II Battery (
2.04 8.19 1
125 VDC Division I Battery 250 VDC Division I Battery 125 VDC Division II Battery Expected EPU electrical modifications that could impact DC loads are replacements in kind for instrument and control loads on the 125 VDC system. The additional 125 VDC loads due to these EPU modifications will not reduce the reported 125 VDC battery margin by more than five percent of the calculated capacity reported. For example, the EPU modifications will be controlled such that the remaining 125 VDC Division I battery margin is at least 10.83 percent.
Additionally, no changes to the margin for the 250V DC battery loads will result from EPU modifications.
CLTP (% Battery Margin) 10.50 23.63 20.24 Page 1 of 7 EPU (% Battery Margin) 15.83 20.64 26.58 NRC Question:
- 3.
For the EQ analyses, clearly state that it has been completed and that NMC has identified the equipment that is impacted by EPU conditions.
NMC Response:
The Reference 1 supplemental EPU submittal provided additional details regarding the EPU analyses relative to the qualification of electrical equipment outside containment.
The information provided in that submittal is the result of analyses that have been completed and documented in EPU task reports and supporting calculations.
Equipment impacted by EPU conditions was identified in the Reference 1 tables. A "Note" was added at the end of the tables to identify equipment impacted by EPU conditions. The note stated, "Additional supporting analysis to be performed and documented in EQ qualification file andlor equipment to be replacedlmodified prior to EPU implementation."
The Reference 1 table note was not intended to imply that the analyses necessary to identify the equipment impacted by EPU conditions have not been completed. As stated previously, and confirmed here, the necessary evaluations to identify the EQ equipment impacted by EPU conditions have been completed. The note explains that the process for final resolution of the identified EPU impact may include:
additional equipment-specific analysis to be documented in the equipment-specific qualification file, replacement or modification of a specific piece of equipment.
The process for final resolution of the identified EPU impacts (additional equipment-specific analysis, replacement or modification) is controlled in accordance with the Monticello EQ Program requirements.
A summary was included in the Reference 1 submittal. The summary concludes that analyses to determine the EPU impact are complete. It also states that the equipment-specific resolutions will be completed as controlled by the Monticello EQ Program requirements. Final resolution of identified impacts will be documented in the related equipment-specific qualification file prior to implementation of EPU in accordance with 10 CFR 50.49.
Page 2 of 7 NRC Question:
- 4.
The licensee states the SBO analysis has been revised for EPU conditions, but does not explain what the changes are. The licensee agreed to develop a table that outlines the changes in the SBO analysis from CLTP to the EPU. The table should include the standard acceptance criteria as well as changes in assumptions.
NMC Response:
The following two tables (Table 2 and 3) capture the SBO analysis changes in regard to acceptance criteria and analysis assumptions.
Table 2 - Station Blackout (SBO) 10 CFR 50.63 Acceptance Criteria met:
Criteria SBO 10 CFR 50.63 criteria "Sufficient capacity and capability to ensure that the core is cooled and appropriate containment integrity is maintained in the event of a SBO for the specified duration."
reactor water level cycles between low-low level
(-47") and the High Pressure Coolant Injection (HPCI) trip setpoint
(+48"), which is well above the Top of Active Fuel for the event duration.
CLTP Yes -
reactor water level cycles between low-low level
(-47") and the HPCI trip setpoint
(+48"), which is well above the Top of Active Fuel for the event duration.
maintained for the calculated coping duration (4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />)
EPU Yes -
Page 3 of 7 Result Adequate Core Cooling is Table 2 - Station Blackout (SBO) 10 CFR 50.63 Acceptance Criteria SBO 10 CFR 50.63 criteria I Drywell 1 Drywell I Peak containment met:
"Sufficient capacity and capability to ensure that the core is cooled and appropriate containment integrity is maintained in the event of a SBO for the specified duration."
Pressure 34.5 psia Suppression Chamber Pressure 34 psia Drywell shell temperature 271.5"F pressure 42.8 psia Suppression Chamber Pressure 41.3 psia Drywell airspace temperature 268.4"F (shell temperature bounded is by the gas temperature value) parameters are all within design values for the calculated coping duration (4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />)
Suppression Chamber airspace temperature 134°F Suppression Chamber airspace temperature 178.9"F Page 4 of 7 Peak Suppression Pool Temperature 151.2 Peak Suppression Pool Temperature 175.5 Tab Assumption Initial Reactor Power Analytical Method Isolation Valve (MSIV) closure signal Recirculation Pump Leakage
~ l e 3 - Changes to SBO Assumptions from CLTP to EPU MAAP 3.OB CLTP 1904 MWt with 100 day decay heat Occurs due to a Group 1 Primary Containment Isolation (Reactor Water Low-Low Level) as the simulation progresses (at approximately 28 seconds).
70 gpmlpump I
I HPCl only EPU 2004 MWt with GE 14 End of Cycle (EOC) (24 month) decay heat Preset to occur att=O Comment
~
The CLTP power of 1904 MWt was intended to bound the first EPU target power level for CLTP, which was ultimately reduced to 1775 MWt.
18 gpmlpump The EOC decay heat is conservative and bounds the NUMARC 87-00 guidance of 100 days for the decay heat parameter.
The suitability of SHEX-O6A for Station Blackout containment response applications is addressed in the Monticello EPU License Amendment Request (LAR) (Reference 3),.
This preset MSIV signal adds conservatism to the containment response because of the increased heat transfer to the torus.
This assumption change is consistent with NUMARC 87-00 Section 2.4.2 guidance for the plant-specific response to MSIV closure.
The CLTP value of 70 gpm per pump was a conservative generic leakage value that had been developed as part of the Monticello response to NU REG-0737 on recirculation 1 pump seal leakage. See MNGP USAR Section 4.3.2.2.5.
I The value of 18 gpm is recommended by Appendix J of Page 5 of 7 Table 3 - Changes to SBO Assumptions from CLTP to EPU inventory loss assumptions are artifacts of the SBO methodology, and the actual non-SRV reactor coolant inventory loss is likely to be less.
Assumption HPCl suction
, source modeling and operator actions Automatic HPCl initiation signal I The analysis now includes Page 6 of 7 CLTP The analytical model assumes a torus only HPCl suction source Low-low reactor level EPU The model has been changed to more accurately reflect automatic Condensate Storage Tank (CST) to torus HPCl suction transfers.
Low-low reactor level or high drywell pressure Comment The existing SBO model is a conservative simplification that does not account for HPCl via the CST as the preferred injection system. Plant emergency procedures direct the operator to use the CST HPCl suction sources if available.
Adequate CST inventory is available, and CST suction lowers overall SBO risk as the net positive suction head (NPSH) available to the HPCl pump is greater than with torus suction and improves HPCl reliability.
This approach is consistent with the NUMARC 87-00 guidance on CST usage during an SBO given in Sections 4.2.1 and 4.3.1 (5).
A reactor low-low level signal is assured in an SBO event regardless of the non-SRV (safety relief valve) reactor coolant inventory loss assumptions. The high drywell pressure automatic initiation HPCl signal is also possible and is sensitive to increased non-SRV reactor coolant inventory loss assumptions.
The non-SRV reactor coolant
References:
- 1.
NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplemental Information Package 5," dated June 5,2008 Table 3 - Changes to SBO Assumptions from CLTP to EPU
- 2.
NMC Letter to USNRC, "Monticello Extended Power Uprate (USNRC TAC MD8398): Acceptance Review Supplemental Information," dated May 28,2008 Assumption
- 3.
NMC Letter to USNRC, "License Amendment Request: Extended Power Uprate," dated March 31, 2008 Page 7 of 7 CLTP EPU Comment separate cases for each automatic HPCl initiation signal to conservatively account for both outcomes. The low-low reactor level HPCl start response case causes a more severe containment response, and this response is used in determining the torus temperature margin. The high drywell pressure HPCl start response case causes an extra HPCl loading cycle (greater DC loads) and is used in determining battery margin.