L-06-151, Emergency Response Data System
| ML062990219 | |
| Person / Time | |
|---|---|
| Site: | Beaver Valley |
| Issue date: | 10/23/2006 |
| From: | Lash J FirstEnergy Nuclear Operating Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| L-06-151 | |
| Download: ML062990219 (76) | |
Text
FENOC FirstEnergy Nuclear Operating Company James H. Lash 724-682-5234 Site Vice President Fax: 724-643-8069 October 23, 2006 L-06-151 Attention: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
Beaver Valley Power Station, Unit No. 2 BV-2 Docket No. 50-412, License No. NPF-73 Emergency Response Data System FirstEnergy Nuclear Operating Company (FENOC) has replaced the plant computer system at the Beaver Valley Power Station Unit No. 2. This has resulted in changes to the Data Point Library (DPL) for the Emergency Response Data System (ERDS), which are being submitted in accordance with the requirements of 10 CFR 50, Appendix E, Section VI. The changes are provided in Attachment 1 as DPL replacement pages for the affected data points. A description of the changes, which includes changes to several data point identification numbers, is provided in Attachment 2.
No new regulatory commitments are contained in this submittal.
If there are any questions or if additional information is required, please contact Mr. Gregory A. Dunn, Manager - FENOC Fleet Licensing, at (330) 315-7243.
Sincerely, ames H. Lash Attachments:
- 1. ERDS Data Point Library Replacement Pages
- 2. Summary Of Changes c:
Mr. T. G. Colburn, NRR Senior Project Manager Mr. P. C. Cataldo, NRC Senior Resident Inspector Mr. S. J. Collins, NRC Region I Administrator Mr. D. A. Allard, Director BRP/DEP Mr. L. E. Ryan (BRP/DEP)
L-06-151 Page 1 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit
[Point BV2 N0049A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Alarm / Trip Set Points: Changed to "HI ALM @ 101% / LO ALM @ 0.1%"
Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location N0050A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Alarm / Trip Set Points: Changed to "HI ALM @ 101% / LO ALM @ 0.1%"
Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location N0051A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Alarm / Trip Set Points: Changed to "HI ALM @ 101% / LO ALM @ 0.1%"
Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location N0052A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Alarm / Trip Set Points: Changed to "HI ALM @ 101% / LO ALM @ 0.1%"
Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location N0035A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "INT RNG DET 1 FLUX-LOG NM35B" Engr Units Conversion: Changed to "EU=eA[(3.684138E-03*mv)+(-2.532840E+01)]"'
Alarm / Trip Set Points: Changed from "N/A" to "HI = 8.5E-04" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location, corrected reference to sensor "2NMI-NE35" N0036A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "INT RNG DET 2 FLUX-LOG NM36B" Engr Units Conversion: Changed to"EU=e^[(3.684138E-03*mv)+(-2.532840E+01)]"
Alarm / Trip Set Points: Changed from "N/A" to "HI = 8.5E-04" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location N0031A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "SOURCE RNG DET 1 FLUX-LOG NM3 IF" Engr Units Conversion: Changed to "eA(2.763102E-03*mv)"
Alarm / Trip Set Points: Changed to "N/A in mode 1, mode 2 = 9.OE+03" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location N0032A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "SOURCE RNG DET 2 FLUX-LOG NM32F" Engr Units Conversion: Changed to "e^(2.763102E-03*mv)"
Alarm / Trip Set Points: Changed to "N/A in mode 1, mode 2 = 9.OE+03" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location
L-06-151 Page 2 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit Point BV2 L0072A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "UPSO 17" Plant Spec Point Desc.: Changed to "RVLIS DYNAMIC RANGE TRAIN A" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location L0075A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "UPSO 18" Plant Spec Point Desc.: Changed to "RVLIS DYNAMIC RANGE TRAIN B" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location UT1003 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "UPSOO 1" Plant Spec Point Desc.: Changed to "HIGHEST T/C TEMPERATURE" Minimum Instr Range: Changed to "100" Maximum Instr Range: Changed to "2200" How Processed: Changed to EXTR Alarm / Trip Set Points: Changed to "N/A" Unique System Desc.: Changed to reflect PCS input from PSMS computer UT1002 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "UPSO 12" Plant Spec Point Desc.: Changed to "TSAT MARGIN (SUBCOOLING)"
Minimum Instr Range: Changed to "-200" Maximum Instr Range: Changed to "35.0" How Processed: Changed to "INPUT FROM PSMS" Unique System Desc.: Changed to reflect PCS input from PSMS computer F0400C Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "F0400A" Plant Spec Point Desc.: Changed to RCL A FLW RCS-FT414" Engr Units Conversion: Changed to "FLOW" PROC or SENS: Changed from "P" to "S" Alarm / Trip Set Points: Changed to from "N/A" to "HI ALM @ 100, LO ALM @ 97" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location F0421C Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "F0421A" Plant Spec Point Desc.: Changed to RCL B FLW RCS-FT425" Engr Units Conversion: Changed to "FLOW" PROC or SENS: Changed from "P" to "S" Alarm / Trip Set Points: Changed to "HI ALM @ 100, LO ALM @ 97" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location
L-06-151 Page 3 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit Point BV2 F0442C Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "F0442A" Plant Spec Point Desc.: Changed to RCL C FLW RCS-FT436" Engr Units Conversion: Changed to "FLOW" PROC or SENS: Changed from "P" to "S" Alarm / Trip Set Points: Changed to "HI ALM @ 100, LO ALM @ 97" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location L0403A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to SG 21A WR LVL FWS-LT477 Engr Units Conversion: Changed to "LINEAR" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location L0423A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to SG 21B WR LVL FWS-LT487 Engr Units Conversion: Changed to "LINEAR" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location L0443A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to SG 21C WR LVL FWS-LT497 Engr Units Conversion: Changed to "LINEAR" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location UP 1003 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "U0414" Plant Spec Point Desc.: Changed to "STM GEN A STM OUT BELV 1 2+3" Engr Units Conversion: Changed to "N/A" How Processed: Changed to "CHAU" Alarm / Trip Set Points: Changed to "N/A" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UP 1004 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "U0434" Plant Spec Point Desc.: Changed to "STM GEN B STM OUT BELV 1 2+3" Engr Units Conversion: Changed to "N/A" How Processed: Changed to "CHAU" Alarm / Trip Set Points: Changed to "N/A" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location
L-06-151 Page 4 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit I
Point BV2 UP1005 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "U0454" Plant Spec Point Desc.: Changed to "STM GEN C STM OUT BELV 1 2+3" Engr Units Conversion: Changed to "N/A" How Processed: Changed to "CHAU" Alarm / Trip Set Points: Changed to "N/A" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UF1001 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "U0410" Plant Spec Point Desc.: Changed to "LOOP A CORR FW FLW AVG 1+2" Engr Units/Dig States: Changed from "KLB/HR" to "MLB/HR" Maximum Instr Range: Changed to from "5000" to "5.0000" How Processed: Changed to "REF" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UF1002 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "U0430" Plant Spec Point Desc.: Changed to "LOOP B CORR FW FLW AVG 1+2" Engr Units/Dig States: Changed from "KLB/HR" to "MLB/HR" Maximum Instr Range: Changed to from "5000" to "5.0000" How Processed: Changed to "REF" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UF1003 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "U0450" Plant Spec Point Desc.: Changed to "LOOP C CORR FW FLW AVG 1+2" Engr Units/Dig States: Changed from "KLB/HR" to "MLB/HR" Maximum Maximum Instr Range: Changed to from "5000" to "5.0000" How Processed: Changed to "REF" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UF3000 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "AFW FLOW TO SG A" How Processed: Changed to "DAVE" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UF3001 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "AFW FLOW TO SG B" How Processed: Changed to "DAVE" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location
L-06-151 Page 5 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit Point BV2 UF3002 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "AFW FLOW TO SG C" How Processed: Changed to "DAVE" Unique System Desc.: Replaced the "'" with a "-" in the referenced Functional Location T0419A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "RCL A WIDE RANGE THOT RCS-TE413" Engr Units Conversion: Changed from "N/A" to "LINEAR" Alarm / Trip Set Points: Changed from "N/A" to "HIGH ALM @ 650; LO ALM @ 541" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location T0439A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Dese.: Changed to "RCL B WIDE RANGE THOT RCS-TE423" Engr Units Conversion: Changed from "N/A" to "LINEAR" Alarm / Trip Set Points: Changed from "N/A" to "HIGH ALM @ 650; LO ALM @ 541" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location T0459A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "RCL C WIDE RANGE THOT RCS-TE433" Engr Units Conversion: Changed from "N/A" to "LINEAR" Alarm / Trip Set Points: Changed from "N/A" to "HIGH ALM @ 650; LO ALM @ 541" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location T0406A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "RCL A WIDE RANGE TCOLD RCS-TE410" Engr Units Conversion: Changed from "N/A" to "LINEAR" Alarm / Trip Set Points: Changed from "N/A" to "HIGH ALM @ 630; LO ALM @ 530" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location T0426A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "RCL B WIDE RANGE TCOLD RCS-TE420" Engr Units Conversion: Changed from "N/A" to "LINEAR" Alarm / Trip Set Points: Changed from "N/A" to "HIGH ALM @ 630; LO ALM @ 530" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location T0446A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "RCL C WIDE RANGE TCOLD RCS-TE430" Engr Units Conversion: Changed from "N/A" to "LINEAR" Alarm / Trip Set Points: Changed from "N/A" to "HIGH ALM @ 630; LO ALM @ 530" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location
L-06-151 Page 6 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit Point BV2 UP1001 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to UPS026 Plant Spec. Point Desc.: Changed to "RCS WIDE RANGE PRESSURE" How Processed: Changed to "INPUT FROM PSMS" Alarm/Trip Set Points: Changed to "N/A" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location, removed reference to UP10 11 and UP1012 UL1000 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to U0483 Plant Spec. Point Desc.: Changed to "AVERAGE PZR LEVEL (1/2/3)"
How Processed: Changed to "CHAU" Alarm/Trip Set Points: Changed to "N/A" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UF1013 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "TOTAL CHARGING FLOW" How Processed: Changed to "ADD" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location, description revised to clarify how total flow value is computed UF1011 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "HI SI FLOW TOTAL" How Processed: Changed to "ADD" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location UF1014 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "LO SI FLOW TOTAL" How Processed: Changed to "ADD" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location LOIOOA Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "CNMT SUMP LVL DAS-LT220" Engr Units/Dig States Changed from "IN" to "INCHES" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Desc.: Replaced the ""
with a "-" in the referenced Functional Location(s)
LO 1 02A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "CNMT SUMP LVL DAS-LT222" Engr Units/Dig States Changed from "IN" to "INCHES" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Dese.: Replaced the "*" with a "-" in the referenced Functional Location
L-06-151 Page 7 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL I
Description of Change(s)
Unit Point BV2 L0750A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "RX CNMT SUMP LVL RSS-LT 151 A" Engr Units/Dig States Changed from "IN" to "INCHES" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Desc.: Replaced the "'" with a "-" in the referenced Functional Location R0001A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Minimum Instr Range: Changed from "1.08E-7" to "0" Maximum Instr Range: Changed from "1.08E-1" to "1.0" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0010A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Minimum Instr Range: Changed from "2.33E-7" to "0" Maximum Instr Range: Changed from "2.33E-1" to "1.0" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0086A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "IN-CNMT HI RiNG AREA 2RMR-RQ206" Minimum Instr Range: Changed from "1" to "0.0" Maximum Instr Range: Changed from "1E8" to "1E9" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0087A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Minimum Instr Range: Changed from "1" to "0.0" Maximum Instr Range: Changed from "lE8" to "1E9" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0002A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Minimum Instr Range: Changed from "1.7E-4" to "0.0" Maximum Instr Range: Changed from "1.7E2" to "l.0E2" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS"
L-06-151 Page 8 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit Point BV2 R0088A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "MAIN STM ACTIVITY 2MSS-RQO10A" Minimum Instr Range: Changed from "2.5E-3" to "0.0" Maximum Instr Range: Changed from "2.5E3" to "l.0E4" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0089A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "MAIN STM ACTIVITY 2MSS-RQIO1B" Minimum Instr Range: Changed from "2.5E-3" to "0.0" Maximum Instr Range: Changed from "2.5E3" to "l.0E4" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0090A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec. Point Desc.: Changed to "MAIN STM ACTIVITY 2MSS-RQO10C" Minimum Instr Range: Changed from "2.5E-3" to "0.0" Maximum Instr Range: Changed from "2.5E3" to "l.0E4" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0079A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Minimum Instr Range: Changed from "7.7E-8" to "0.0" Maximum Instr Range: Changed from "7.7E-2" to "1.0" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the ""
with a "-" in the referenced Functional Location and "ERFCS" to "PCS" UP 1000 Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" How Processed: Changed to "DAVE" Alarm/Trip Set Points: Changed from "HI ALM @ 59.7 PSIA" to "N/A" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location T1002A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location TI008A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location
L-06-151 Page 9 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit Point BV2 T1013A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location T1014A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Desc.: Replaced the ""
with a "-" in the referenced Functional Location T1015A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location Y0752A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "CNMT H2 CONC TRN A HCS-HA100A" Engr Units Conversion: Changed from "LINEAR" to "N/A" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location L0751A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "RX CNMT SUMP LVL RSS-LT5 151B" Engr Units/Dig States Changed from "IN" to "INCHES" Engr Units Conversion: Changed from "N/A" to "LINEAR" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location Y0753A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "CNMT H2 CONC TRN B HCS-HA100B" Engr Units Conversion: Changed from "LINEAR" to "N/A" PROC or SENS: Changed from "S" to "P" Unique System Dese.: Replaced the "*" with a "-" in the referenced Functional Location L0074A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "UPS014" Plant Spec Point Desc.: Changed to "RVLIS FULL RANGE LEVEL TRAIN B" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "" with a "-" in the referenced Functional Location L0071A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Point ID: Changed to "UPS013" Plant Spec Point Desc.: Changed to "RVLIS FULL RANGE LEVEL TRAIN A" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location
L-06-151 Page 10 of 10
SUMMARY
OF CHANGES TO DATA POINT LIBRARY (DPL)
Reactor DPL Description of Change(s)
Unit Point BV2 R0094A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Minimum Instr Range: Changed from "5.1E-8" to "0.0" Maximum Instr Range: Changed from "5.15E-2" to "1.0E-1" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" R0003A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Minimum Instr Range: Changed from "7.2E-2" to "0.0" Maximum Instr Range: Changed from "7.2E4" to "l.0E5" PROC or SENS: Changed from "S" to "P" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location and "ERFCS" to "PCS" L0500A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Desc.: Changed to "RWST LVL QSS-LT100A" Engr Units/Dig States Changed from "IN" to "INCHES" Alarm/Trip Set Points: Changed to "LO ALM @ 718 IN / HI ALM @ 721 IN" Unique System Desc.: Replaced the "*" with a "-" in the referenced Functional Location L0501A Date: Changed to "9/16/2006" Data Feeder: Changed from "ERFCS" to "PCS" Plant Spec Point Dese.: Changed to "RWST LVL QSS-LTIOOB" Engr Units/Dig States Changed from "IN" to "INCHES" Alarm/Trip Set Points: Changed to "LO ALM @ 718 IN / HI ALM @ 721 IN" Unique System Desc.: Replaced the ""
with a "-" in the referenced Functional Location
L-06-151 Page 1 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS NI-POWER-RNG N0049A PWR RNG CHAN 1 FLUX NM41 F NUCLEAR INSTRUMENTS, POWER RANGE A
LINEAR 0
120 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 101%/LOALM @ 0.1%
N/A N/A LOW N
N/A Power Range level is calibrated from a secondary plant calorimetric calculation to provide full rated power level. Power Range level is an average of the upper and lower detector flux levels. 2NMP-NE41A and B (see attached NIS detector location dwg). Ref: Op Manual Chapter 2; 10080-TLD-02-005.
L-06-151 Page 2 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA1 NOO50A PWR RNG CHAN 2 FLUX NM42F NUCLEAR INSTRUMENTS, POWER RANGE A
LINEAR 0
120 N/A N/A S
I N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 101%/LO ALM @ 0.1%
N/A N/A LOW N
N/A Power Range level is calibrated from a secondary plant calorimetric calculation to provide full rated power level. Power Range level is an average of the upper and lower detector flux levels. 2NMP-NE42A and B (see attached NIS detector location dwg). Ref: Op Manual Chapter 2; 10080-TLD-02-006.
L-06-151 Attachment I Page 3 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC orSENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA2 N0051A PWR RNG CHAN 3 FLUX NM43F NUCLEAR INSTRUMENTS, POWER RANGE A
LINEAR 0
120 N/A N/A S
I N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 101%/LO ALM @ 0.1%
N/A N/A LOW N
N/A Power Range level is calibrated from a secondary plant calorimetric calculation to provide full rated power level. Power Range level is an average of the upper and lower detector flux levels. 2NMP-NE43A and B (see attached NIS detector location dwg). Ref: Op Manual Chapter 2; 10080-TLD-02-007.
L-06-151 Page 4 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA3 N0052A PWR RNG CHAN 4 FLUX NM44F NUCLEAR INSTRUMENTS, POWER RANGE A
LINEAR 0
120 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 101%/LO ALM @ 0.1%
N/A N/A LOW N
N/A Power Range level is calibrated from a secondary plant calorimetric calculation to provide full rated power level. Power Range level is an average of the upper and lower detector flux levels. 2NMP-NE44A and B (see attached NIS detector location dwg). Ref: Op Manual Chapter 2; 10080-TLD-02-008.
L-06-151 Attachment I Page 5 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum lnstr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS NI-INTER-RNG N0035A INT RNG DET 1 FLUX-LOG NM35B NUCLEAR INSTRUMENTS, INT RANGE A
AMP EU=eA[(3.684138E-03 *mv)+(-2.532840E+01) 1E-11 1E-3 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI = 8.5E-04 2/4 PWRRNG >10%
3/4 PWRRNG <10%
LOW N
N/A Intermediate Range level indication from 1.OE-1 1 to 1.OE-3 Amps corresponds to about 1OE-6% to 10E2% full rated power. Power Range level indication will not come on scale until the Reactor power rises to about 1 OE-5 Amps Intermediate Range level (- 1% full power). 2NMI-NE35 (see attached NIS detector location dwg). Ref: Op Manual Chapter 2; 10080-TLD-02-003.
L-06-151 Page 6 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA4 N0036A INT RNG DET 2 FLUX-LOG NM36B NUCLEAR INSTRUMENTS, INT RANGE A
AMP EU=eA[(3.684138E-03 *mv)+(-2.532840E+01)
IE-11 1 E-3 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI = 8.5E-04 2/4 PWRRNG >10%
3/4 PWRRNG <10%
LOW N
N/A Intermediate Range level indication from 1.OE-1 1 to 1.OE-3 Amps corresponds to about 10E-6% to 10E2% full rated power. Power Range level indication will not come on scale until the Reactor power rises to about 10E-5 Amps Intermediate Range level (- 1% full power). 2NMI-NE36 (see attached NIS detector location dwg). Ref: Op Manual Chapter 2; 10080-TLD-02-004.
L-06-151 Page 7 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS NI-SOURC-RNG NOO31A SOURCE RNG DET 1 FLUX-LOG NM31F NUCLEAR INSTRUMENTS,SOURCE RANGE A
CPS eA(2.763102E-03
- mv) 1 1E6 N/A N/A S
I N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A in mode 1, mode 2 = 9.OE+03 1/21NTRNG>I E-10 2/21NTRNGIE-10 2/21NTRNG<IE-10 LOW N
N/A The Source Range provides power level indication from about 1OE-10% to 10E-4%. Source Range power level is calibrated from 1 to 1.0E6 Counts per Second. 2NMS-NE32 (see attached NIS detector location dwg) Ref: Op Manual Chapter 2; 10080-TLD-02-002.
L-06-151 Attachment I Page 9 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS REAC-VES-LV1 UPS017 RVLIS DYNAMIC RANGE TRAIN A REACTOR VESSEL WATER LEVEL A
N/A 0
120 N/A N/A P
1 PSMS RVLIS ALGORITHM SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW Y
WET Connections to the Reactor Vessel Head at the Incore Instrumentation Tubes sense Reactor Vessel core and internal DP. Reference line tubing runs from the instrument tubes to High Volume Sensors which isolate the RCS from the remainder of the RVLIS tubing. Capillary tubing runs from the High Volume Sensors through the Containment Wall to hydraulic isolators. RTDs are installed on capillary lines for containment temperature compensation. PSMS receives transmitter output. Reading is invalid unless RCPs are running.
2RCS-LT1 312 senses DP across Reactor Vessel core and internals when any RCPs are running. Normal DP is 110-112%.
L-06-151 Page 10 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS REAC-VES-LV2 UPS018 RVLIS DYNAMIC RANGE TRAIN B REACTOR VESSEL WATER LEVEL A
N/A 0
120 N/A N/A P
1 PSMS RVLIS ALGORITHM SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW Y
WET Connections to the Reactor Vessel Head and Incore Instrumentation Tubes sense Reactor Vessel core and internal DP. Reference line tubing runs from the instrument tubes to High Volume Sensors which isolate the RCS from the remainder of the RVLIS tubing. Capillary tubing runs from the High Volume Sensors through the Containment Wall to hydraulic isolators. RTDs are installed on capillary lines for Containment temperature compensation.
PSMS receives transmitter output. Reading is invalid unless RCPs are running. 2RCS-LT1322 senses DP across Reactor Vessel core and internals when any RCPs are running. normal DP is 110-112%.
L-06-151 Attachment I Page 11 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS TMP-CORE-EX1 UPS001 HIGHEST T/C TEMPERATURE HIGHEST TEMPERATURE AT CORE EXIT A
DEGF N/A 100 2200 N/A N/A P
51 EXTR SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A PCS accepts the inputs of the compensated Core Exit Thermocouples (51 total) via data link from the Plant Safety Monitoring System (PSMS). This value is computed in PSMS and transmitted to the PCS via data link.
L-06-151 Page 12 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SUB-MARGIN1 UPS012 TSAT MARGIN (SUBCOOLING)
SATURATION TEMP - HIGHEST CET A
DEGF N/A
-200 35.0 N/A N/A P
0 INPUT FROM PSMS SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This point is received by the PCS from Plant Safety Monitoring System (PSMS) as PCS point UPS012.
L-06-151 Page 13 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CORE-FLOW1 F0400A RCL A FLW RCS-FT414 REACTOR COOLANT LOOP A FLOW A
FLOW 0
120 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HIALM@100, LOALM@97 N/A N/A LOW N
N/A 2RCS-FT414 senses RCS Loop A flow and provides a signal to the computer, SSPS, and the Main Control Board. The Reactor Coolant Pump design flow rate is 95,230 GPM at 542F and 2250 PSIG. 100% flow in Loop A is approximately 3.5E7 LBM/HR. 2RCS-FT414 senses flow at the Reactor Coolant Pipe Elbow at SG A Outlet. Ref: 10080-TLD-006-045; RM-406-1; RM-406-3; 2BVT 1.6.1.
L-06-151 Page 14 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CORE-FLOW2 F0421A RCL B FLW RCS-FT425 REACTOR COOLANT LOOP B FLOW A
FLOW 0
120 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 100, LOALM @ 97 N/A N/A LOW N
N/A 2RCS-FT425 senses RCS Loop B flow and provides a signal to the computer, SSPS, and the Main Control Board. The Reactor Coolant Pump design flow rate is 95,230 GPM at 542F and 2250 PSIG. 100% flow in Loop B is approximately 3.5E7 LBM/HR. 2RCS-FT425 senses flow at the Reactor Coolant Pipe Elbow at SG B Outlet. Ref: 10080-TLD-006-062; RM-406-1; RM-406-3; 2BVT 1.6.1.
L-06-151 Attachment I Page 15 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CORE-FLOW3 F0442A RCL C FLW RCS-FT436 REACTOR COOLANT LOOP C FLOW A
FLOW 0
120 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HIALM@100, LOALM@97 N/A N/A LOW N
N/A 2RCS-FT436 senses RCS Loop C flow and provides a signal to the computer, SSPS, and the Main Control Board. The Reactor Coolant Pump design flow rate is 95,230 GPM at 542F and 2250 PSIG. 100% flow in Loop C is approximately 3.5E7 LBM/HR. 2RCS-FT436 senses flow at the Reactor Coolant Pipe Elbow at SG C Outlet. Ref: 10080-TLD-006-079; RM-406-1; RM-406-3; 2BVT 1.6.1.
L-06-151 Page 16 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SG-LEVEL-1A L0403A SG 21A WR LVL FWS-LT477 STEAM GENERATOR A WATER LEVEL A
LINEAR 0
100 UTUBES SEE UNIQUE SYSTEM DESCRIPTION FIELD S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HIGH ALM @ 65 %/LO ALM @ 43 %
N/A N/A LOW N
N/A 2FWS-LT477 provides SG A Wide Range Level indication at the Main Control Board, Shutdown Panel, Alternate Shutdown Panel and at the Feedwater Control Valves. 2FWS-LT477 senses level in SG A from 789' 11 11/16" (upper tap) to 742' 1/16" (lower tap). Top of SG A U-Tubes is at 775' 9 1/16" with normal water level at 783' 2". Ref: Op. Manual Chapter 24A; RK-313R; TLD-24A-051.
Page 17 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SG-LEVEL-2B L0423A SG 218 WR LVL FWS-LT487 STEAM GENERATOR B WATER LEVEL A
LINEAR 0
100 UTUBES SEE UNIQUE SYSTEM DESCRIPTION FIELD S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HIGH ALM @ 65 %/LO ALM @ 43 %
N/A N/A LOW N
N/A 2FWS-LT487 provides SG B Wide Range Level indication at the Main Control Board, Shutdown Panel, Alternate Shutdown Panel and at the Feedwater Control Valves. 2FWS-LT487 senses level in SG B from 789' 11 1/16" (upper tap) to 741' 11 7/8" (lower tap). Zero
Reference:
Top of SG B U-Tubes is at 775' 8 7/8" with normal water level at 783' 1 3/4". Ref: Op. Manual Chapter 24A; RK-313V; TLD-24A-059.
L-06-151 Page 18 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SG-LEVEL-3C L0443A SG 21C WR LVL FWS-LT497 STEAM GENERATOR C WATER LEVEL A
LINEAR 0
100 UTUBES SEE UNIQUE SYSTEM DESCRIPTION FIELD S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HIGH ALM @ 65 %/LO ALM @ 43 %
N/A N/A LOW N
N/A 2FWS-LT497 provides SG C Wide Range Level indication at the Main Control Board, Shutdown Panel and at the Feedwater Control Valves. 2FWS-LT497 senses level in SG C from 790' 5 1/2" (upper tap) to 742' 1/8" (lower tap).
Zero
Reference:
Top of SG C U-Tubes is at 775' 9 1/8" with normal water level at 783' 2". Ref: Op. Manual Chapter 24A; RK-313Z; TLD-24A-066.
L-06-151 Page 19 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SG-PRESS-1A U0414 STM GEN A STM OUT P BELV 1 2+3 STEAM GENERATOR A PRESSURE A
PSIG N/A 0
1200 N/A N/A P
3 CHAU SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This signal is an average of the three Main Steam Line pressure sensors.
The Atmospheric Steam Dump Valves trip open at 1060 PSIG. The Main Steam Safety Valves begin lifting at 1075 PSIG. 2MSS-PT474, 2MSS-PT475 and 2MSS-PT476 sense pressure at SG A Main Steam Line between the Safety Relief Valves and the Main Steam Line Isolation Valves. 10080-TLD-21A-010; RM-421-1.
L-06-151 Attachment I Page 20 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SG-PRESS-2B U0434 STM GEN B STM OUT P BELV 1 2+3 STEAM GENERATOR B PRESSURE A
PSIG N/A 0
1200 N/A N/A P
3 CHAU SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This signal is an average of the three Main Steam Line pressure sensors.
The Atmospheric Steam Dump Valves trip open at 1060 PSIG. The Main Steam Safety Valves begin lifting at 1075 PSIG. 2MSS-PT484, 2MSS-PT485 and 2MSS-PT486 sense pressure at SG B Main Steam Line between the Safety Relief Valves and the Main Steam Line Isolation Valves. 10080-TLD-21A-011; RM-421-1.
L-06-151 Page 21 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SG-PRESS-3C U0454 STM GEN C STM OUT P BELV 1 2+3 STEAM GENERATOR C PRESSURE A
PSIG N/A 0
1200 N/A N/A P
3 CHAU SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This signal is an average of the three Main Steam Line pressure sensors.
The Atmospheric Steam Dump Valves trip open at 1060 PSIG. The Main Steam Safety Valves begin lifting at 1075 PSIG. 2MSS-PT494, 2MSS-PT495 and 2MSS-PT496 sense pressure at SG C Main Steam Line between the Safety Relief Valves and the Main Steam Line Isolation Valves. 10080-TLD-21A-020; RM-421-1.
L-06-151 Page 22 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum lnstr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS MN-FD-FL-1A U0410 LOOP A CORR FW FLW AVG 1+2 STM GEN A MAIN FEEDWATER FLOW A
MLB/HR N/A 0
5.0000 N/A N/A P
2 REF SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is the average of two flow signals sensed from the venturi flow element 2FWS-FE476. There are two, half capacity, Main Feed Pumps which have a design flow rate of 15,200 GPM at 1,694 ft. Total Design Head (TDH) each. 2FWS-FT476 and 2FWS-FT477 sense flow to SG A between the Main Feed Pump discharge and the Main Feed Regulating Valve. 10080-TLD-24A-052; 1 0080-TLD-24A-050; RM-45A.
L-06-151 Attachment I Page 23 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS MN-FD-FL-2B U0430 LOOP B CORR FW FLW AVG 1+2 STM GEN B MAIN FEEDWATER FLOW A
MLB/HR N/A 0
5.0000 N/A N/A P
2 REF SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is the average of two flow signals sensed from the venturi flow element 2FWS-FE486. There are two, half capacity, Main Feed Pumps which have a design flow rate of 15,200 GPM at 1,694 ft. Total Design Head (TDH) each. 2FWS-FT486 and 2FWS-FT487 sense flow to SG B between the Main Feed Pump discharge and the Main Feed Regulating Valve. 10080-TLD-24A-057; 10080-TLD-24A-058; RM-45A.
L-06-151 Page 24 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS MN-FD-FL-3C U0450 LOOP C CORR FW FLW AVG 1+2 STM GEN C MAIN FEEDWATER FLOW A
MLB/HR N/A 0
5.0000 N/A N/A P
2 REF SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is the average of two flow signals sensed from the venturi flow element 2FWS-FE496. There are two, half capacity, Main Feed Pumps which have a design flow rate of 15,200 GPM at 1,694 ft. Total Design Head (TDH) each. 2FWS-FT496 and 2FWS-FT497 sense flow to SG C between the Main Feed Pump discharge and the Main Feed Regulating Valve. 10080-TLD-24A-064; 1 0080-TLD-24A-065; RM-45A.
L-06-151 Attachment I Page 25 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS AX-FD-FL-1A UF3000 AFW FLOW TO SG A STM GEN A AUXILLIARY FW FLOW A
GPM N/A 0
400 N/A N/A P
2 DAVE SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is the average of two flow signals sensed from the same flow element located before the A Auxiliary Feed Line Containment Penetration.
The Auxiliary Feedwater system consists of two half size Motor Driven Feed Pumps (375 GPM at 2760 TDH) and one full size Turbine Driven Feed Pump (750 GPM at 2760 TDH) which take a suction on the 152,000 Gallon Primary Plant Demineralized Water Storage Tank. 2FWE-FT100A and 2FWE-FT100A1 sense flow between the Auxiliary Feedwater Throttle Valves and SG A. The Auxiliary Feedwater Line taps into the Main Feed Line between the Feedwater Isolation Valve and SG A.
L-06-151 Page 26 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS AX-FD-FL-2B UF3001 AFW FLOW TO SG B STM GEN B AUXILLIARY FW FLOW A
GPM N/A 0
400 N/A N/A P
2 DAVE SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is the average of two flow signals sensed from the same flow element located before the B Auxiliary Feed Line Containment Penetration.
The Auxiliary Feedwater system consists of two half size Motor Driven Feed Pumps (375 GPM at 2760 TDH) and one full size Turbine Driven Feed Pump (750 GPM at 2760 TDH) which take a suction on the 152,000 Gallon Primary Plant Demineralized Water Storage Tank. 2FWE-FT1 00B and 2FWE-FT1 00B1 sense flow between the Auxiliary Feedwater Throttle Valves and SG B. The Auxiliary Feedwater Line taps into the Main Feed Line between the Feedwater Isolation Valve and SG B.
L-06-151 Page 27 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS AX-FD-FL-3C UF3002 AFW FLOW TO SG C STM GEN C AUXILLIARY FW FLOW A
GPM N/A 0
400 N/A N/A P
2 DAVE SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is the average of two flow signals sensed from the same flow element located before the C Auxiliary Feed Line Containment Penetration.
The Auxiliary Feedwater system consists of two half size Motor Driven Feed Pumps (375 GPM at 2760 TDH) and one full size Turbine Driven Feed Pump (750 GPM at 2760 TDH) which take a suction on the 152,000 Gallon Primary Plant Demineralized Water Storage Tank. 2FWE-FT100C and 2FWE-FT100C1 sense flow between the Auxiliary Feedwater Throttle Valves and SG C. The Auxiliary Feedwater Line taps into the Main Feed Line between the Feedwater Isolation Valve and SG C.
L-06-151 Page 28 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS HL-TEMP-1A T0419A RCLA WIDE RANGE THOT RCS-TE413 STM GEN A INLET TEMPERATURE A
DEGF LINEAR 0
700 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 650; LO ALM @ 541 N/A N/A LOW N
N/A Reactor Coolant Loop A Hot Leg temperature signal is sent to the Main Control Board, Remote Shutdown Panel, and the plant and PSMS computers. 2RCS-TE413 is located between A Loop Stop Valve and Coolant Inlet to SG A. 10080-TLD-06-044; RM-75A.
L-06-151 Page 29 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS HL-TEMP-2B T0439A RCL B WIDE RANGE THOT RCS-TE423 STM GEN B INLET TEMPERATURE A
DEGF LINEAR 0
700 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 650; LO ALM @ 541 N/A N/A LOW N
N/A Reactor Coolant Loop B Hot Leg temperature signal is sent to the Main Control Board, Remote Shutdown Panel, and the plant and PSMS computers. 2RCS-TE423 is located between B Loop Stop Valve and Coolant Inlet to SG B. 10080-TLD-06-060; RM-75A.
L-06-151 Page 30 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS HL-TEMP-3C T0459A RCL C WIDE RANGE THOT RCS-TE433 STM GEN C INLET TEMPERATURE A
DEGF LINEAR 0
700 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 650; LO ALM @ 541 N/A N/A LOW N
N/A Reactor Coolant Loop C Hot Leg temperature signal is sent to the Main Control Board, Remote Shutdown Panel, and the plant and PSMS computers. 2RCS-TE433 is located between C Loop Stop Valve and Coolant Inlet to SG C. 10080-TLD-06-076; RM-75A.
L-06-151 Attachment I Page 31 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CL-TEMP-1A T0406A RCL A WIDE RANGE TCOLD RCS-TE410 STM GEN A OUTLET TEMPERATURE A
DEGF LINEAR 0
700 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION.FIELD HIGH ALM @ 630; LO ALM @ 530 N/A N/A LOW N
N/A Reactor Coolant Loop A Cold Leg temperature signal is sent to the Main Control Board, Remote Shutdown Panel, and the plant and PSMS computers. 2RCS-TE410 is located between 2RCS-P21A discharge and the A Loop Stop Valve. 10080-TLD-06-040; RM-75A.
L-06-151 Page 32 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CL-TEMP-2B T0426A RCL B WIDE RANGE TCOLD RCS-TE420 STM GEN B OUTLET TEMPERATURE A
DEGF LINEAR 0
700 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HIGH ALM @ 630; LO ALM @ 530 N/A N/A LOW N
N/A Reactor Coolant Loop B Cold Leg temperature signal is sent to the Main Control Board, Remote Shutdown Panel, and the plant and PSMS computers. 2RCS-TE420 is located between 2RCS-P21B discharge and the B Loop Stop Valve. 10080-TLD-06-056; RM-75A.
L-06-151 Attachment I Page 33 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CL-TEMP-3C T0446A RCL C WIDE RANGE TCOLD RCS-TE430 STM GEN C OUTLET TEMPERATURE A
DEGF LINEAR 0
700 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 630 DEGF; LO ALM @ 530 DEGF N/A N/A LOW N
N/A Reactor Coolant Loop C Cold Leg temperature signal is sent to the Main Control Board, Remote Shutdown Panel, and the plant and PSMS computers. 2RCS-TE430 is located between 2RCS-P21C discharge and the C Loop Stop Valve. 10080-TLD-06-072; RM-75A.
L-06-151 Page 34 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS RCS-PRESSURE UPS026 RCS WIDE RANGE PRESSURE REACTOR COOLANT SYSTEM PRESSURE A
PSIG N/A 0
3000 N/A N/A P
3 INPUT FROM PSMS SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This signal is an average of three Wide Range RCS pressure signals. 2RCS-PT440 and 442 senses pressure at Loop A Hot Leg RVLIS tap located between Loop A Hot Leg Isolation Valve and the Reactor Vessel. 2RCS-PT441 senses pressure at Loop B Hot Leg RVLIS tap located between the Loop B Hot Leg Isolation Valve and the Reactor Vessel. 10080-TLD-06-004; 10080-TLD-06-005; 10080-TLD-05D-008; RK-25G; RK-25E.
L-06-151 Page 35 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum lnstr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS PRZR-LEVEL U0483 AVERAGE PZR LEVEL (1/2/3)
PRIMARY SYSTEM PRESSURIZER LEVEL A
N/A 0
100 TOPHTR SEE UNIQUE SYSTEM DESCRIPTION FIELD P
3 CHAU SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A The indicated level can be the average of three, two or one level transmitter signal depending on the deviation between values. See attached curve of %
level vs Pressurizer volume in Gallons. 2RCS-LT459, 460 and 461 sense Pressurizer level from 748' 3 3/4" (lower transmitter tap) to 780' 10 9/16" (upper transmitter tap). Zero reference: minimum water level (top of Heaters) is at 752' 1 5/8" or approximately 12%. Ref: Op Manual Chapter 6; 2004.150-001-010; RK-326R; RK-326S; RK-326T.
L-06-151 Page 36 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
9/16/2006 BV2 PCS RCS-CHG-MU UF1013 TOTAL CHARGING FLOW PRIMARY SYSTEM CHG OR MU FLOW A
GPM N/A Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
0 195 N/A N/A P
4 ADD SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A Total Charging Flow is computed on the Plant Computer by adding the CHG LINE FLW CHS-FT122 (F0128A), and the three RCP SEAL INJECTION flows (FO131A, RCP 21A SEAL INJ FLOW CHS-FT1 30; F0129A, RCP 21B SEAL INJ FLOW CHS-FT1 27; and F0127A, RCP 21C SEAL INJ FLOW CHS-FT1 24).
L-06-151 Attachment I Page 37 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS HPSI-FLOW1 UF1011 HI SI FLOW TOTAL HIGH PRESS SAFETY INJECTION FLOW A
GPM N/A 0
2000 N/A N/A P
2 ADD SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is the total flow through the Train A and B High Pressure Safety Injection Lines. The Charging Pumps (2CHS-P21A, B and C) provide the HHSI flow. 2SIS-FT940 (Train A) and 2SIS-FT943 (Train B) sense flow at the discharge of 2CHS-P21A, B and C prior to the header connection to the Hot and Cold Legs of Reactor Coolant Loops A, B and C. 10080-TLD-1 1A-038; 10080-TLD-11A-039; RM-407-1; RM-41 1-1.
L-06-151 Attachment I Page 38 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS LPSI-FLOW1 UF1014 LO SI FLOW TOTAL LOW PRESS SAFETY INJECTION FLOW A
GPM N/A 0
10000 N/A N/A P
2 ADD SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This value is total flow through Train A and B Low Pressure Safety Injection Header or Safety Injection Flow from Recirculation Spray Pumps to Reactor Coolant Loops A, B and C. Pumps 2SIS-P21A and B have a design flow rate of 3000 GPM at 240 PSIG with a shutoff head of 350'. The Recirculation Pumps Pumps (2RSS-P21A, B, C and D) have a design flow rate of 3500 GPM at 280f and 266 FT. 2SIS-FT945 (Train A) and 2S(S-FT946 (Train B) sense flow at the discharge of the LHSI Pumps (2SIS-P21A and B) between the Recirculation Spray Pump connection to the injection header and the header connection to the Hot and Cold Legs for Reactor Coolant Loops A, B and C.
L-06-151 Attachment I Page 39 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-SP-NR1 L0100A CNMT SUMP LVL DAS-LT220 CTMNT SUMP NARROW RANGE LEVEL A
INCHES LINEAR 0
12 TNKBOT N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 3.0 IN N/A N/A LOW N
N/A Containment Sump Narrow Range level measures the 12 Inch floor recess (2DAS-TK204) located at the East side of Containment adjacent to the wall on elevation 692' 11". The sump has a volume of 258 Gallons or 21.5 Gallons/Inch. 2DAS-LE220 located in the East side of Containment adjacent to the wall at elevation 692' 11" (2DAS-LT222 located in the Service Building 730' elevation). Zero reference: tank bottom.
Ref: Op Manual Chapter 9, 10080-TLD-009-032.
L-06-151 Page 40 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum lnstr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-SP-NR2 L0102A CNMT SUMP LVL DAS-LT222 CTMNT SUMP NARROW RANGE LEVEL A
INCHES LINEAR 0
12 TNKBOT N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 3.0 IN N/A N/A LOW N
N/A Containment sump Narrow Range level measures the 12 Inch floor recess (2DAS-TK204) located at the East side of Containment adjacent to the wall on elevation 692' 11". The sump has a volume of 258 Gallons or 21.5 Gallons/Inch. 2DAS-LE222 located in the East side of Containment adjacent to the wall at elevation 692' 11" (2DAS-LT222 located in the Service Building 730' elevation). Zero reference tank bottom.
Ref: Op Manual Chapter 9, 10080-TLD-009-045.
L-06-151 Attachment I Page 41 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-SP-WR1 L0750A RX CNMT SUMP LVL RSS-LT151A CTMNT SUMP WIDE RANGE LEVEL A
INCHES LINEAR 0
225 CNTFLR SEE UNIQUE SYSTEM DESCRIPTION FIELD S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 35 IN N/A N/A LOW N
N/A 2RSS-LT151A measures Containment Sump level from the floor to a height of 709' 10 3/8". 2RSS-P21A thru D suction lines are at the 692' 11" level in containment. At 695' the Containment Air Recirculation A and C Fans trip.
2RSS-LT151A measures level from the Containment Floor at elevation 691' 1 3/8" to a height of 709' 10 3/8". Zero reference: Containment Floor (691' 1 3/8"). Ref: MSP-2-13.09, 10080-TLD-13A-003; RK-6M; Op. Manual Chapter 13.
L-06-151 Page 42 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS COND-AE-RAD1 R0001A AIR EJ DISCHARGE 2ARC-RQ100 COND AIR EJECTOR RADIOACTIVITY A
uCI/CC N/A 0
1.0 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2ARC-RQ100 monitors the gaseous effluent from the Condenser Air Ejector discharge for Xe-1 33 before the Charcoal Delay Beds. An alarm indicates a primary to secondary leak. Detector output is sent to digital radiation monitor system (DRMS) which transmits value and measurement condition once per minute to the PCS. A beta scintillation detector monitors the Condenser Air Ejector discharge upstream of the Charcoal Delay Beds. Ref: Op Manual Chapter 43, RM-419-2, TLD-43-056.
L-06-151 Page 43 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS COND-AE-RAD2 ROO1OA AIR EJ DELAY BED 2GWS-RQ102 COND AIR EJECTOR RADIOACTIVITY A
uCI/CC N/A 0
1.0 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2GWS-RQ102 monitors the gaseous effluent from the Air Ejector Charcoal Bed for Xe-133. An alarm indicates a primary to secondary leak and a possible malfunction of the Charcoal Delay Beds. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A beta scintillation detector monitors Air Ejector Charcoal Bed gaseous effluent.
Ref: Op Manual Chapter 43; RM-443-17; TLD-43-062.
L-06-151 Page 44 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-RAD1 R0086A IN-CNMT HI RNG AREA 2RMR-RQ206 RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 0.0 1E9 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2RMR-RQ206 monitors the radiation levels inside Containment and provides both local and Control Room alarms and indication. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. An ion chamber detects High Range area radiation levels inside Containment. Ref: Op Manual Chapter 43; TLD-43-017.
L-06-151 Page 45 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-RAD2 R0087A IN-CNMT HI RNG AREA 2RMR-RQ207 RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 0.0 1 E9 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2RMR-RQ207 monitors the radiation levels inside Containment and provides both local and Control Room alarms and indication. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. An ion chamber detects High Range area radiation levels inside Containment. Ref: Op Manual Chapter 43; TLD-43-018.
L-06-151 Page 46 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS RCS-LTD-RAD2 R0002A RX CLNT LTDN LO RNG 2CHS-RQ101A RAD LEVEL OF RCS LETDOWN LINE A
uCI/CC N/A 0
1.0E2 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A NIA LOW N
N/A 2CHS-RQ101A monitors the gross activity of the reactor coolant (Cs-137) by drawing samples from the Reactor Coolant Letdown Line and delaying them to permit sufficient decay of the N-16 isotope before they pass by the detectors. This is an indication of fission products present in the reactor coolant. This radiation monitor provides the Low Range indication. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A detector monitors gross activity of the reactor coolant at Reactor Coolant Letdown Line.
L-06-151 Page 47 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS MAIN-SL-1A R0088A MAIN STMACTIVITY 2MSS-RQ101A STM GEN A STEAM LINE RAD LEVEL A
uCI/CC N/A 0.0 1.0E4 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2MSS-RQ101A monitors the activity (Kr-88) following an accident in which the Power-Operated Dump Valves or Main Steam Safety Valves may be used as a discharge path to the environment. This monitor is activated by a Safety Injection Signal. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A gamma scintillator detects activity in the Main Steam Line between SG A and the Main Steam Trip Valves upstream of the Safety Valve tie-in. Ref: Op Manual Chapter 43; TLD-43-071; RM-421-2.
L-06-151 Attachment I Page 48 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS MAIN-SL-2B R0089A MAIN STM ACTIVITY 2MSS-RQ101B STM GEN B STEAM LINE RAD LEVEL A
uCI/CC N/A 0.0 1.0E4 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2MSS-RQ1 01 B monitors the activity (Kr-88) following an accident in which the Power-Operated Dump Valves or Main Steam Safety Valves may be used as a discharge path to the environment. This monitor is activated by a Safety Injection Signal. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A gamma scintillator detects activity in the Main Steam Line between SG B and the Main Steam Trip Valves upstream of the Safety Valve tie-in. Ref: Op Manual Chapter 43; TLD-43-075; RM-421-2.
L-06-151 Page 49 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS MAIN-SL-3C R0090A MAIN STM ACTIVITY 2MSS-RQ101C STM GEN C STEAM LINE RAD LEVEL A
uCI/CC N/A 0.0 1.0E4 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2MSS-RQ101C monitors the activity (Kr-88) following an accident in which the Power-Operated Dump Valves or Main Steam Safety Valves may be used as a discharge path to the environment. This monitor is activated by a Safety Injection Signal. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A gamma scintillator detects activity in the Main Steam Line between SG C and the Main Steam Trip Valves upstream of the Safety Valve tie-in. Ref: Op Manual Chapter 43; TLD-43-076; RM-421-2
L-06-151 Page 50 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS SG-BD-RAD-1A R0079A SG BLOWDOWN 2SSR-RQ100 STM GEN A/B/C BLOWDOWN RAD LEVEL A
uCI/CC N/A 0.0 1.0 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2SSR-RQI100 monitors the activity of the Steam Generator Blowdown for Cs-137. Samples are taken from a common header which acts as a manifold from the three Steam Generators. A High Alarm isolates the sample lines.
The sampling valve arrangement permits the operator to determine the source of the high activity. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A gamma scintillator monitors the activity of the Steam Generator Blowdown effluent in a common header from all three Steam Generators.
L-06-151 Page 51 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-PRESS UP1000 CNMT PRESS AVG CONTAINMENT PRESSURE A
PSIA N/A 0
180 N/A N/A P
2 DAVE SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A This signal is an average of two Containment pressure signals. The design pressure of the BV2 Reactor Containment is 8 PSIG to 45 PSIG. 2LMS-PT106A and 2LMS-PT106B sense Containment pressure from an open tap in Containment. Ref: 1 0080-TLD-1 2B-034; 10080-TLD-1 2B-035; RK-321 H; RK-321 K.
L-06-151 Page 52 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-TEMP T1002A RX CNMT TEMP LMS-TE100-2 CONTAINMENT TEMPERATURE A
DEGF LINEAR 0
300 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 121.3 DEGF; LO ALM @ 80.7 DEGF N/A N/A HIGH N
N/A 2LMS-TE1 00-2 measures Containment temperature inside the Crane Wall.
See attached drawing for detector locations in Containment. 2LMS-TE100-2 senses Containment temperature at 801' 6" elevation inside the Crane Wall.
Ref: 10080-TLD-12B-007; RK-14A.
L-06-151 Page 53 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA12 T1008A RX CNMT TEMP LMS-TE100-8 CONTAINMENT TEMPERATURE A
DEGF N/A 50 130 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 106.3 DEGF; LO ALM @ 79.5 DEGF N/A N/A HIGH N
N/A 2LMS-TE1 00-8 measures Containment temperature inside the Crane Wall.
See attached drawing for detector locations in Containment. 2LMS-TE100-8 senses temperature in Containment at 743' elevation inside the Crane Wall.
Ref:10080-TLD-12B-013; RK-14A.
L-06-151 Attachment I Page 54 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA 13 T1013A RX CNMT TEMP LMS-TE100-13 CONTAINMENT TEMPERATURE A
DEGF LINEAR 0
300 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 123.9 DEGF; LO ALM @ 83.4 DEGF N/A N/A HIGH N
N/A 2LMS-TE100-13 measures Containment temperature inside the Crane Wall.
See attached drawing for detector locations in Containment. 2LMS-TE100-13 senses temperature in Containment at 802' elevation inside the Crane Wall.
Ref:10080-TLD-12B-018; RK-14A.
L-06-151 Attachment I Page 55 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
.9/16/2006 BV2 PCS EXTRA14 T1014A RX CNMT TEMP LMS-TE100-14 CONTAINMENT TEMPERATURE A
DEGF LINEAR 0
300 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 90.4 DEGF; LO ALM @ 71.5 DEGF N/A N/A HIGH N
N/A 2LMS-TE100-4 measures Containment temperature outside the Crane Wall.
See attached drawing for detector locations in Containment. 2LMS-TE100-14 senses temperature in Containment at 701' 6" elevation outside the Crane Wall. Ref:10080-TLD-12B-019, RK-14A.
L-06-151 Page 56 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA 15 T1015A RX CNMT TEMP LMS-TE100-15 CONTAINMENT TEMPERATURE A
DEGF LINEAR 0
300 N/A N/A S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 132.4 DEGF; LO ALM @ 80.0 DEGF N/A N/A HIGH N
N/A 2LMS-TE1 00-5 measures Containment temperature outside the Crane Wall.
See attached drawing for detector locations in Containment. 2LMS-TE100-15 senses temperature in Containment at 777' 4" elevation outside the Crane Wall. Ref:10080-TLD-12B-020; RK-14A.
L-06-151 Attachment I Page 57 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS H2-CONC1 Y0752A CNMT H2 CONC TRN A HCS-HA100A CONTAINMENT HYDROGEN CONC A
N/A 0
10 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 0.5 %
N/A N/A LOW N
N/A Containment gas is sampled and analyzed at the Hydrogen Analyzer (2HCS-HA100A) with the results transmitted to 2HCS-PNL100A where % hydrogen is calculated. 2HCS-HA100A senses hydrogen at the 801' level in Containment. 10080-TLD-46-001; RK-3117C; RM-446-1.
L-06-151 Page 58 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS CTMNT-SP-WR2 L0751A RX CNMT SUMP LVL RSS-LT151B CTMNT SUMP WIDE RANGE LEVEL A
INCHES LINEAR 0
225 CNTFLR SEE UNIQUE SYSTEM DESCRIPTION FIELD S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 35 IN N/A N/A LOW N
N/A 2RSS-LT1 51B measures Containment Sump level from the floor to a height of 709' 10 3/8". 2RSS-P21A thru D suction lines are at the 692' 11" level in containment. At 695' the Containment Air Recirculation B and C Fans trip.
2RSS-LT151B measures level from the Containment Floor at elevation 691' 1 3/8" to a height of 709' 10 3/8". Zero reference: Containment Floor (691' 1 3/8"). Ref: MSP-2-13.09, 10080-TLD-13A-003; RK-6M; Op. Manual Chapter 13.
L-06-151 Page 59 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EXTRA 16 Y0753A CNMT H2 CONC TRN B HCS-HA100B CONTAINMENT HYDROGEN CONC A
N/A 0
10 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD HI ALM @ 0.5 %
N/A N/A LOW N
N/A Containment gas is sampled and analyzed at the Hydrogen Analyzer (2HCS-HA 001B) with the results transmitted to 2HCS-PNL100B where % hydrogen is calculated. 2HCS-HA100B senses hydrogen at the 802' level in Containment. 10080-TLD-46-002; RK-317C; RM-446-1.
L-06-151 Page 60 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS REAC-VES-LV4 UPS014 RVLIS FULL RANGE LEVEL TRAIN B REACTOR VESSEL WATER LEVEL A
PSMS RVLIS ALGORITHM 0
120 TAF TAF=729'3"(276" FROM BOT RX VESS)=62.5%
P 1
PSMS RVLIS ALGORITHM SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW Y
WET Connections to the Reactor Vessel Head and Incore Instrumentation Tube
- 20 at the Seal Table are the sensing points. Reference line tubing runs from these points to High Volume Sensors which isolate the RCS from the remainder of the RVLIS tubing. Capillary tubing runs from the High Volume Sensors through the Containment Wall to hydraulic isolators. RTDs are installed on capillary lines for Containment temperature compensation.
PSMS receives transmitter output. Reading is invalid if RCPs are running.
2RCS-LT1321 senses Reactor Vessel Head between the top of the Reactor Vessel Head elevation 746' 9" to Thimble Guide Tube #20 elevation 705' 9".
L-06-151 Attachment I Page 61 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS REAC-VES-LV3 UPS013 RVLIS FULL RANGE LEVEL TRAIN A REACTOR VESSEL WATER LEVEL A
PSMS RVLIS ALGORITHM 0
120 TAF TAF=729'3"(276" FROM BOT RX VESS)=62.5%
P 1
PSMS RVLIS ALGORITHM SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW Y
WET Connections to the Reactor Vessel Head and Incore Instrumentation Tube
- 20 at the Seal Table are the sensing points. Reference line tubing runs from these points to High Volume Sensors which isolate the RCS from the remainder of the RVLIS tubing. Capillary tubing runs from the High Volume Sensors through the Containment Wall to hydraulic isolators. RTDs are installed on capillary lines for Containment temperature compensation.
PSMS receives transmitter output. Reading is invalid if RCPs are running.
2RCS-LT1311 senses Reactor Vessel level between the top of the Reactor Vessel Head elevation 746' 6" to Thimble Guide Tube #20 elevation 705' 9".
L-06-151 Attachment I Page 62 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS EFF-LIQ-RAD1 R0094A LIQ WST EFFLUENT 2SGC-RQ100 RADIOACTIVITY OF RELEASED LIQ A
uCI/CC N/A 0.0 1.OE-1 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2SGC-RQ100 receives an auto-start signal and monitors the activity (Cs-137) in the Liquid Waste Process System when flow is detected. Upon detection of High radiation a valve is closed to prevent the release of this discharge.
Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A gamma scintillator detects activity in the discharge from the Liquid Waste Process System. Ref: Op Manual Chapter 43; TLD-43-048
L-06-151 Attachment I Page 63 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS RCS-LTD-RAD1 R0003A RX CLNT LTDN HI RNG 2CHS-RQ101B RAD LEVEL OF RCS LETDOWN LINE A
uCI/CC N/A 0.0 1.0E5 N/A N/A P
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD N/A N/A N/A LOW N
N/A 2CHS-RQ101B monitors the gross activity of the reactor coolant (Cs-137) by drawing samples from the Reactor Coolant Letdown Line and delaying them to permit sufficient decay of the N-16 isotope before they pass by the detectors. This is an indication of fission products present in the reactor coolant. This radiation monitor provides the High Range indication. Detector output is sent to Digital Radiation Monitor System (DRMS) which transmits value and measurement condition once per minute to the PCS. A detector monitors gross activity of the reactor coolant at Reactor Coolant Letdown Line.
L-06-151 Page 64 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS BWST-LEVEL1 LO500A RWST LVL QSS-LT100A BORATED WATER STORAGE TANK LEVEL A
INCHES LINEAR 0
730 COMPLX SEE UNIQUE SYSTEM DESCRIPTION FIELD S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD LOALM @ 718 IN / HI ALM @ 721 IN N/A N/A LOW N
N/A The BWST at BV2 is referred to as "Refueling Water Storage Tank" (RWST).
There is one RWST at BV2 with a capacity of 911,000 Gallons. There are 31,823 unusable Gallons below the Quench Spray Pump suction. There are approximately 1250 Gallons/Inch in the RWST. (see attached tank curve).
2QSS-LT100A senses level 12" from the bottom of the tank and 14" below the top of the Quench Spray Pump suction line. Zero reference 12" from bottom of BWST. Ref: MSP-2-13.11-1; 10080-TLD-13B-001; LSK-27-9D; LSK-29-6B; RK-325R.
L-06-151 Attachment I Page 65 of 65 BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-ON Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System Desc.:
9/16/2006 BV2 PCS BWST-LEVEL2 L0501A RWST LVL QSS-LT1 00B BORATED WATER STORAGE TANK LEVEL A
INCHES LINEAR 0
730 COMPLX SEE UNIQUE SYSTEM DESCRIPTION FIELD S
1 N/A SEE UNIQUE SYSTEM DESCRIPTION FIELD LO ALM @ 718 IN / HI ALM @ 721 IN N/A N/A LOW N
N/A The BWST at BV2 is referred to as "Refueling Water Storage Tank" (RWST).
There is one RWST at BV2 with a capacity of 911,000 Gallons. There are 31,823 unusable Gallons below the Quench Spray Pump suction. There are approximately 1250 Gallons/Inch in the RWST. (see attached tank curve).
2QSS-LT100B senses level 12" from the bottom of the tank and 14" below the top of the Quench Spray Pump suction line. Zero reference 12" from bottom of BWST. Ref: MSP-2-13.1 1-1; 10080-TLD-13B-002; LSK-27-9D; LSK-29-6B; RK-325Q.