Information Notice 2008-06, Instrument Air System Failure Resulting in Manual Reactor Trip

From kanterella
Jump to navigation Jump to search
Instrument Air System Failure Resulting in Manual Reactor Trip
ML073540243
Person / Time
Issue date: 04/10/2008
From: Michael Case
NRC/NRR/ADRA/DPR
To:
References
IN-08-006
Download: ML073540243 (4)


UNITED STATES

NUCLEAR REGULATORY COMMISSION

OFFICE OF NUCLEAR REACTOR REGULATION

WASHINGTON, DC 20555-0001 April 10, 2008 NRC INFORMATION NOTICE 2008-06: INSTRUMENT AIR SYSTEM FAILURE RESULTING

IN MANUAL REACTOR TRIP

ADDRESSEES

All holders of operating licenses or construction permits for nuclear power reactors, except

those who have permanently ceased operations and have certified that fuel has been

permanently removed from the reactor vessel.

PURPOSE

The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to alert

addressees of an event involving an instrument air system failure that resulted in a manual reactor trip. The NRC expects that recipients will review this information for applicability to their

facilities and consider actions, as appropriate, to avoid similar problems. Suggestions in this

information notice are not NRC requirements; therefore, no specific action or written response is

required.

DESCRIPTION OF CIRCUMSTANCES

On June 20, 2007, San Onofre Nuclear Generating Station Unit 2 (SONGS-2) was operating at

about 96 percent power when a line in the instrument air system separated at a soldered

connection. The resulting loss of instrument air pressure caused a loss of control of the steam

generator feedwater regulating valves. The water level in one of the steam generators rose in

an uncontrolled manner necessitating action by the control room operators to trip the reactor

manually. Subsequently, the operators tripped the main feedwater pumps to stop excess

feedwater to the steam generators and actuated the auxiliary feedwater system. The loss of air

also prevented the use of the steam dumps to the main condenser (i.e., the normal heat

removal method) and; therefore, operators controlled the steam generator pressure and decay

heat removal using the steam generator atmospheric dump valves. As designed, a loss of

instrument air system pressure will cause the isolation of cooling water to the normal

containment coolers; therefore, the operators manually started the containment emergency

cooling units as a conservative measure.

The licensee at SONGS-2 reported this occurrence in Licensee Event Report (LER)

50-361/2007-001-01, dated August 24, 2007 (Agencywide Documents Access Management

System (ADAMS) Accession No. ML072400033). The LER stated that the cause of this event

was the loss of instrument air system pressure when the instrument air system separated at a

soldered connection in a section of 3-inch diameter piping. The connection failed because of a

weak solder joint and corrosion of the solder joint. This section of pipe with the failed solder

joint was installed in about 1980 during original plant construction. The solder connection was

weak because the gap between the tube and the coupling was too large. The larger gap did not

allow for the capillary action necessary to provide an even distribution of the melted solder and

the solder pooled at the bottom of the coupling. The larger gap also allowed solder flux to

remain in the solder, which led to slow-acting corrosion of the solder joint. When corrosion had

sufficiently reduced the solder joint strength, the connection separated.

As corrective actions, the licensee inspected the instrument air piping and replaced the

instrument air line solder joint that had separated and the leaking joint adjoining it. The licensee

also inspected all soldered joints in the instrument air system on piping with a diameter greater

than 1 inch and installed pipe clamps to strengthen pipe joints, where needed, to supply

additional margin.

At SONGS-2, the instrument air system is a shared, nonsafety-related system. However, the

system is equipped with certain protective features (e.g., excess flow check valves) to ensure

that a failure in the piping system on one unit does not significantly affect instrument air

pressure on the other unit. In this incident, the SONGS-2 instrument air pressure dropped

significantly from 110 psig to about 43 psig while the back-up system and check valves

sustained service to Unit 3 until the break could be isolated. The loss of instrument air pressure

caused the feedwater control valves to stop functioning and the water level in the steam

generators increased in an uncontrolled manner necessitating a manual trip of the reactor by

the control room operators. The licensee has assessed the safety significance of the event and

performed a risk assessment based on the reported actual component unavailability, system

alignments, and operating conditions. The assessment of the conditional core damage

probability and conditional large early release probability found the safety significance of this

event to be very low.

Based on the conditions reported in the LER, as supported by the licensees risk analysis, the

NRC staff found that although this event challenged plant operations, it did not affect the health

and safety of either plant personnel or the public.

DISCUSSION

Although no specific requirements or standards were unmet, the failure of the instrument air

system at SONGS-2 illustrates the importance of understanding the potential failure

mechanisms associated with the fabrication/installation process, monitoring the

fabrication/installation of the systems, and performing inspections that check for potential failure

mechanisms.

CONTACT

This information notice does not require any specific action or written response. Please direct

any questions about this matter to the technical contact listed below.

/RA/

Michael J. Case, Director

Division of Policy and Rulemaking

Office of Nuclear Reactor Regulation

Technical Contact:

Edward Smith, NRR/DSS/SBPB

301-415-1548 Email: ets1@nrc.gov

Note: NRC generic communications may be found on the NRC public Web site, http://www.nrc.gov, under Electronic Reading Room/Document Collections.

ML073540243 OFFICE SBPB:DSS TECH EDITOR BC:SBPB:DSS D:DSS

NAME ESmith HChang DHarrison JWermiel for WRuland

DATE 04/03/2008 04/02/2008 04/03/2008 04/04/2008 OFFICE LA:PGCB:DPR PGCB:DPR BC:PGCB:DPR D:DPR

NAME CHawes DBeaulieu MMurphy MCase

DATE 04/10/2008 04/08/2008 04/10/2008 04/10/2008