IR 05000352/2005009

From kanterella
(Redirected from IR 05000353/2005009)
Jump to navigation Jump to search
IR 05000352-05-009, 05000353-05-009; 11/15/2005 - 11/18/2005; Limerick Generating Station; Emergency Preparedness Exercise
ML060030016
Person / Time
Site: Limerick  
Issue date: 12/30/2005
From: Ray Lorson
Plant Support Branch 1
To: Crane C
Exelon Generation Co, Exelon Nuclear
References
IR-05-009
Download: ML060030016 (10)


Text

December 30, 2005

SUBJECT:

LIMERICK GENERATING STATION - NRC EVALUATED EMERGENCY PREPAREDNESS EXERCISE INSPECTION REPORT 05000352/2005009, 05000353/2005009

Dear Mr. Crane:

On November 18, 2005, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection of your full-scale biennial Emergency Preparedness exercise that occurred at your Limerick Generating Station, Units 1 and 2 on November 15, 2005. The enclosed inspection report documents the inspection results, which were discussed with Mr. R. DiGregorio, Site Vice President, and other members of your staff during an exit meeting held on November 18, 2005.

The inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.

The inspectors reviewed procedures, observed activities associated with the exercise and interviewed personnel.

This report documents one NRC-identified finding of very low safety significance (Green). This finding was determined to involve a violation of NRC requirements. However, because of the very low safety significance and because it was entered into your corrective action program, the NRC is treating it as a non-cited violation (NCV) consistent with Section VI.A.1 of the NRC Enforcement Policy. If you contest the non-cited violation in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the Nuclear Regulatory Commission, ATTN.: Document Control Desk, Washington DC 20555-0001; with copies to the Regional Administrator, Region I, the Director, Office of Enforcement, United States Nuclear Regulatory Commission, Washington, DC 20555-0001; and the NRC Resident Inspector at the Limerick facility.

Mr. Christopher In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter, its enclosure, and your response if any will be made available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room). Should you have any questions, please contact Mr. Raymond K. Lorson at (610) 337-5282.

Sincerely,

/RA/

Raymond K. Lorson, Chief Plant Support Section 1 Division of Reactor Safety Docket Nos.: 50-352, 353 License Nos.: NPF-39, 85 Enclosure:

Inspection Report 05000352/2005005, 05000353/2005005 w/Attachment: Supplemental Information cc w/encl:

Chief Operating Officer, Exelon Generation Company, LLC Site Vice President - Limerick Generating Station Plant Manager, Limerick Generating Station Regulatory Assurance Manager - Limerick Senior Vice President - Nuclear Services Vice President - Mid-Atlantic Operations Vice President - Operations Support Vice President - Licensing and Regulatory Affairs Director - Licensing and Regulatory Affairs, Exelon Generation Company, LLC Manager, Licensing - Limerick Generating Station Vice President, General Counsel and Secretary Associate General Counsel, Exelon Generation Company Correspondence Control Desk Director, Bureau of Radiation Protection, PA Department of Environmental Protection J. Johnsrud, National Energy Committee Chairman, Board of Supervisors of Limerick Township J. Bradley Fewell, Assistant General Counsel, Exelon Nuclear D. Hammons, Chief, Tech Hazards Branch and RAC Chair FEMA Region III P. G. Arcuri, Acting Regional Director, FEMA, Region III

Mr. Christopher