Insp Rept 50-353/88-24 on 880912-15.No Violations Noted. Major Areas Inspected:Installation of safety-related Instrumentation Components & Status of Previously Identified Open Items
ML20204F258
Person / Time
Site: Limerick 
Issue date: 10/11/1988
From: Anderson C, Paolino R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20204F232 List:
References
50-353-88-24, NUDOCS 8810210542
Download: ML20204F258 (5)


Text

- _ _ _ _

_ - _ _ _ _ _ - _ _ _ _ _ _ _ _

.

.

.

.'

'

O.S. NUCLEAR REGULATORY COMMISSION

REGION I

Report No.

50-353/88-24 Docket No.

50-353 License No. CPPR-107 Priority Category B

-

Licensee:

Philadelphia Electric Company D 01 Market Street PhTladelphia, PA ilfD1 Facility Name:

Limerick Generating Station, Unit 2 Inspection At:

Limerick, Pennsylvania Inspection Conducted:

September 12 - 15, 1988 Inspectors:

668 d

/O-3"88

.JgPaoli r. Reactor [ngineer, P357$B da e

,

Approved by:

/o // df C. J. 'nderson, Chief, Plant Systems date Section, EB/DRS Inspection Summary:

Inspection on Septecer 12 - 15,1933 (Inspection Report RE $0735f785-~'47

~ 2 Areas !_nspected:

Routine, unannounced inspection of activities relating to the instailation of safety related instrumentation Components.

Review status

.

of previously identified open items.

Results: The inspector observed work activities in process and completed work relating to the installation of instru ents and instrument sensing lines for the RHR A and B loop, the RCIC turbine exhaust vent line and the standby liquid control system.

The inspector concluded that the installed system were in accordance with design requirements as reflected in the appitcable as-built drawings.

Documentation supporting the installed configuration was readily available.

No violations or deficiencies were identified.

8810210542 881018 PDR ADOCK 05000353 o

PDC

.

, - - - - - - - - - - - - - - - - - - _ _ _ _

.

'.

.,

Details 1.0 Persons Contacted 1.1 Philadelphia Electric Company

R. W. Chester, Quality Assurance Engineer J. M. Corcoran, Manager Quality Assurance

  • 0. A. DiPaolo, Superintendent, Unit 2 QA
  • W, D. Lamsom. Quality Assurance Engineer

"G. Lauderback, Jr., S/U Quality Control Supervisor i

K. W. Meck, Assistant Superintendent - Unit 2, QA

'

J. W. Mehaffey, Quality Assurance Engineer

  • R. L. Payne, Quality Assurance Engineer
  • G. D. Tepper, Electrical Construction Engineer
  • W. T. Ullrich, Startup Manager - Unit 2

"R. D. Weingard, Lead Engineer, I&C H. R. Wiegle, Superintendent - Startup Operations

,

t 1.2 Bechtel Power Corporation

  • B. T. Foote, Lead Construction Engineer
  • G. C. Kelly, Quality Assurance Engineer

.

H. Lilligh, Quality Assurance Manager W. L. McCullough, Project Startup Engineer

.

'

  • J. McVeigh, Lead Quality Contro'4 5.igineer K. G. Stout, Project Construction Quality Control Engineer i

1.3 U.S. Nuclear _ Regulatory Commission

  • R. L. Fuhrmeister, Resident Inspector D. T. Moy, Reactor Engineer J. Trapp, Reactor Engineer

"Denotes personnel present at exit meeting of September 15, 1938 2.0 Purpose The purpose of this inspection was to review the instructions and procedures for installing safety related instrumentation and to examine work in progress, completed work and related documentation records to ascertain whether these records reflect work accomplishments consistent with NRC requirements and licensee commitments.

3.0 Facility Tour The inspector observed work activities in progress, completed work and

.

plant status in several areas during a general inspection of the site.

The inspector examined work items for obvious defects or noncompliance

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _.

.

.

'.

.,

,

"

with NRC requirements or licensee commitments.

Particular note was taken regarding the presence of quality control inspectors and indications of

,

quality control activities through visual evidence such as inspection

records, material identifications, nonconformance and acceptance tags,

!

In addition, the inspector interviewed craf t and sup"visory personnel

[

encountered in the work area, j

No discrepancies were identified.

l

'

?

4.0 Status of Previously Identified Dgen Item

!

_(Closed) CDR 84-04-02 Misapplication of Westinghouse KF Underfrequency Relay in the interlock circuit associated with the Emergency Diesel Generator (EDG). The relays are supplied as part of the EDG control beard which had been modified to function in the diesel ready-to-load

'

circuit.

By design the relay should have closed its associated contact upon generator output frequency increasing above a set point. As l

'

shipped, the relay closed its contact on decreasing frequency.

The diesel generator manufacturer (Colt Industries) indicates the KF relay in the diesel breaker circuit is their "standard" design.

This item had been reported to the NRC as a 50.55e in a telecen of Februa ry 28, 1984 and a final report submitted on March 26, 1934.

This item, closed in NRC Report No. 50-352/84-14 for Limerick Unit 1 and 50-353/84-04 for Limerick Unit 2 was reopened for Limerick Unit 2 re-verification of the relay contact wiring modification to provide a contact which closes on increasing frequency. The circuit was successfully tested on August 31, 1983.

This item is closed.

5.0 Instrumentation (Corponents & Systems)---CA Procedures Review (52051)

The inspector reviewed pertinent installation and inspection procedures relative to instrument components and systems to ascertain whether quality assurance plans, instructions and procedures have been established and whether they conform to the QA program as described in chapter 17 of the FSAR.

Items reviewed for this determination include:

P&lD drawing nos. M-48 sh. 3, M-51sh 5, & M-51sh7.

  • Installation Details Specification M-830

Inspection Instructions 18240/1-1.10 revision 17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ - _ _ _ _

.

'.

.,

The inspector concluded that the licensee has established appropriate and adequate procedures for identification, storage, handling, installation, inspection and construction testing to assure that these specific activities are controlled and performed in accordance with NRC requireme ts and SAR commitments.

No discrepancies were identified.

6.0 Instrumentation (Components _& Systems)---Work Observations (52053)

The inspector observed work performance, partially completed work and completed work, as appropriate, for selections made below, with respect to instrument components utilized from sensor to trip logic, including sensing lines and other associated and interrelated devices to ascertian whether the requirements of applicable specifications, work procedures, inspection procedures have been accomplished.

Items selected for examination include:

R_HR A and B Loop - area 17, elevation 217'-0"

Flow fransmitters FT-51-2N001, 2N052A, 2N052B, 2N0158, 2N0150 and 2N0520.

RCIC Turbine Exhaust Vent Line - Area 18, elevation 177'-0"

~Pressure Transmitter PT!$d;iNQ55C & 2N055G

"

Standby _ Liquid Control System - Area 17, elevation 283'"0"

Level Transmitter LT-43-2N010A, 2N010E, 2N0108, 2N010K, 2NU10C and 2N010G.

.

The inspector conc'uded that the applicable requirements of'

'

specifications, procedures and instructions in the area of identification, louation, supports, routing, slope, inspection ann independence have been met.

No discrepancies were identified.

7.0 Instrumentation (Components & Systems)---Quality __ Record Review (52055)

The inspector reviewed pertinent work and quality records for instrument components associated with the systems referenced in section 6.0 above, from the sensor to the actuating or trip device, including instrument

.

components in the "loop", accessory components as well as sensing lines

'

for these components to ascert'.in uaether the records reflect work accomplishments consistent with NRC requirements and SAR commitments.

,

_ _

- - -.

-

_

-

-,

.-.

_

_

_ _ _.

.

.

,

. '.

,

ltems reviewed include:

Quality Control Inspection Reports - QCIR nos. FJ-51-06-37Q-53-1A

,

for item 51-06-37A; FJ-51-06-16Q-!,8-1 tor item 51-06-16A; FJ-51-06-140-58-1A for item 51-06-14A; FJ-50-04-092-58-1A for item FJ-50-04-09A.

l RCIC Turbine Exhaust Vent Line drawing FJ-50-04-09A revision 2.

"

Instrunent Location drawing M-1550.

Seismic Support drawing

'

M-830-G027 revision 12.

Rework Notice I-0131 Work Package JML-50-04-090A-A and JTL-50-04-09Q-A RHR A&B loop-drawing FJ-51-06-16-QA revision 0, drawing

FJ-51-06-14A revision 2 Instrument Location drawing M-1552; work package JTL-51-06-14Qa, seismic support drawing M-830-G026-2. Work Reavest 43398 and 25509, work package JTL-51-06-16QA

'

Standby liquid Control System - Location drawing M-1546 revision 14;

!

Work package JML-48-10-OSQ-A; installation detail drawing M-830-LO66 revision 3.

Instrument rack 20C011.

Field deviation disposition request (FDDR) HH2-3609 and FDI-TRDM revision 0 dated April 4. ',938.

Field change requests (FCR) ME-643 & MJ-601J.

The inspector concluded that the Quality Records confirm that the required materials records and certification meet applicabla requirements.

Records confirm procer instrument component and related devices vere inspected and properly installed.

No discrepancirts were identified.

8.0 Exit Meeting

.

At the conclusion of the inspection on September 15, 1988, the inspector ret with licensee representatives and construction personnel denoted in Details, paragraph 1.0.

The inspector sutmarized the scope of the inspection and tne inspection findings at that time.

No written naterial was given to the licensee during this inspection,