| Title | Part 21 - Defect Identified in Automatic Transfer Switch |
| Event Description | The following information was provided by Paragon Energy Solutions, LLC via email:
Pursuant to 10 CFR 21.21(d)(3)(i), Paragon Energy Solutions, LLC is providing initial notification of the identification of a defect potentially associated with a substantial safety hazard. The subject Automatic Transfer Switches contain Mar-Bal bus insulators. Based on Paragon testing performed, the insulators may have developed stress cracking due to over tightening of required mounting hardware during the assembly process which was not detected by inspection at Paragon. Stress cracks in the insulators could degrade the structural integrity of the automatic transfer switch to withstand seismic conditions which could potentially cause a substantial safety hazard. Only one customer, Talen Energy-Susquehanna, is affected by this issue. Serial numbers of the potentially effected units (QTY 4): 351029663-1 through 351029663-4. It is recommended the licensee inspect the insulators for the supplied automatic transfer switches for stress cracking and contact Paragon for any needed assistance to resolve any deficiencies identified. The date of discovery was 1/29/2023, and the date of the Part 21 Reportability determination was 3/2/2023. Formal notification will be submitted on or before 3/31/2023. Point of Contact: Richard Knott Vice President Quality Assurance 817-284-0077 rknott@paragones.com
Paragon Energy Solutions submitted their final report in accordance with 10CFR 21.21(d)(4). Paragon recommends inspection of the 4 automatic transfer switches supplied to Talen Susquehanna for insulator cracking at the next regularly scheduled maintenance period and replacement of any insulators found to exhibit stress cracking. Notified R1DO (Schroeder) and Part 21/50.55 Group via email. |
| Where | |
|---|---|
| Paragon Energy Solutions Forth Worth, Texas (NRC Region 4) | |
| Organization: | Paragon Energy Solutions |
| Reporting | |
| 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
| Time - Person (Reporting Time:+798.85 h33.285 days <br />4.755 weeks <br />1.094 months <br />) | |
| Opened: | Richard Knott 12:51 Mar 3, 2023 |
| NRC Officer: | Karen Cotton-Gross |
| Last Updated: | Mar 31, 2023 |
| 56387 - NRC Website
Loading map... | |
Paragon Energy Solutions with 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
WEEKMONTHYEARENS 581352026-01-26T05:00:00026 January 2026 05:00:00
[Table view]10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Defect with Electric Actuators ENS 579812025-10-09T05:00:0009 October 2025 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect ≪Br≫≪Br≫ ENS 571432024-05-09T04:00:0009 May 2024 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Defect with Emergency Diesel Generator Voltage Regulator ENS 568992023-12-18T06:00:00018 December 2023 06:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Initial Part 21 Report - Deficient Fuel Injectors ENS 566532023-08-03T00:00:0003 August 2023 00:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect, 10 CFR 21.21(a)(2), Interim Report for Comply or Defect in Component Initial Part 21 Report - Defect with Eaton/Cutler Hammer Size 4 and 5 Freedom Series Contactors ENS 563872023-01-29T06:00:00029 January 2023 06:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Defect Identified in Automatic Transfer Switch ENS 554972021-09-03T05:00:0003 September 2021 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report - Deviation in DC-DC Converter Rectifiers in Inverter Assemblies ENS 553002021-06-08T05:00:0008 June 2021 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Initial Report - Deviation Identified in Bolting Utilized to Maintain Seismic Qualification: ENS 552232021-03-29T05:00:00029 March 2021 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Failure of Size 1 and 2 Freedom Series Full Voltage Reversing Starters ENS 547342020-06-01T05:00:0001 June 2020 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report - Failure of Size 1 and 2 Freedom Series Auxiliary Contacts ENS 547602020-06-01T05:00:0001 June 2020 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect 2026-01-26T05:00:00 | |