ENS 53796
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
06:00 Dec 19, 2018 | |
| Title | |
| Event Description | On December 19, 2018, at 2322 CST, the shift operating crew declared the control room envelope inoperable in accordance with Technical Specification (TS) 3.7.6.1 due to valve HVC-102 exceeding its maximum allowed closed stroke time of 2.0 seconds during performing of surveillance procedure OP-903-119. Actual closed stroke time was 2.1 seconds. Valve HVC-102 is part of the control room envelope. TS 3.7.6.1 requires that two control room emergency air filtration trains shall be OPERABLE. Operations entered TS 3.7.6.1 action b, which requires that with one or more control room emergency air filtration trains inoperable due to inoperable control room envelope boundary in MODES 1, 2, 3, or 4, then: 1. immediately initiate action to implement mitigating actions; 2. within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, verify mitigating actions ensure control room envelope occupant exposures to radiological, chemical, and smoke hazards will not exceed limits; and 3. within 90 days, restore the control room envelope boundary to OPERABLE status. Actions b.1 and b.2 were completed by placing the control room ventilation system in isolate mode at 2355. This event is reportable pursuant to 10 CFR 50.72(b)(3)(v)(D), 'event or condition that could have prevented fulfillment of a safety function of structures or systems that are needed to (D) mitigate the consequences of an accident,' due to the control room envelope being inoperable.
The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Waterford Louisiana (NRC Region 4) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+23.53 h0.98 days <br />0.14 weeks <br />0.0322 months <br />) | |
| Opened: | Tracey Berry 05:32 Dec 20, 2018 |
| NRC Officer: | Brian P. Smith |
| Last Updated: | Dec 20, 2018 |
| 53796 - NRC Website
Loading map... | |
Unit 3 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |