The following was received by facsimile:
The ITT Conoflow models GT25CA1826 and GT25CD1826 current to pressure (l/P) transducers produce a calibrated 3.0 to 15.0 psi output pressure from a 4.0 to 20.0 mA DC (input) signal. Other dedicated l/P transducer part numbers are available with different output pressure ranges and input signal values.
On August 19, 2016 a defective model GT25CA1826 (s/n 628894) was received for evaluation. This transducer would only achieve 0-9 psi output pressure, falling short of the specified 3-15 psi output range. The failure was caused by misalignment of a key internal sub-assembly component as a result of shipping damage (mechanical shock). The product has been repaired, calibrated/tested, and is being returned to the customer (Arizona Public Service Co.).
The following is a list of customers, and the specific l/P transducer part numbers procured from ITT since 2006. These customers will be notified by November 1, 2016.
ACSYR SL GT25CA1826
ALABAMA POWER COMPANY GT25CA1826
AMERGEN ENERGY, LLC GT25CA1826
ARIZONA PUBLIC SERVICE CO GT25CA1826
ASIAM INT'L (TAIWAN) INC. GT25CA1826
CALVERT CLIFFS NUCLEAR POWER PLANT, INC GT25CD1826
CATAWBA NUCLEAR STATION GT25CA1826 GT25CD1826
CCNPP STOREROOM GT25CD1826
CENTRAL NUCLEAR DE ALMARAZ GT25CD1826
CONTROL COMPONENTS INC GT25CD1826
DETROIT EDISON GT25CD1826
DTE ENERGY GT25CD1826
ENERGY NORTHWEST GT25CA1826
ENERTECH CURTISS-WRIGHT GT25CA1826, GT25CD1826
ENRICO FERMI POWER PLANT 2 GT25CD1826
ENTERGY OPERATIONS GT25CA1826, GT25CD1826
ERGYTECHINC GT25CD1826
EXELON BUSINESS SERVICES GT25CA1826
FLOWSERVE GT25CA1826
GEFRAN BENELUX NV GT25CA1826 GT25CD1826
KOREA HYDRO & NUCLEAR PWR GT25CA1826
NEBRASKA PUBLIC POWER GT25CA1826
NUCLEAR POWER PLANT KRSKO GT25CA1826
OMAHA PUBLIC POWER DIST GT25CA1826 GT25CD1826
ONTARIO POWER GENERATION GT25CA1826 GT25CD1826
SPX MCKEAN GT25CA1826
TVA NUCLEAR ASSURANCE AND LICENSING GT25CA1826 GT65CD1826
WATTS BAR UNIT 2 CONSTRUCTION GT25CD1826
WEIR VALVES & CONTROLS UK GT25CA1826
ZVONIMIR
ZEC GT25CA1826