The following information was received via fax:
This letter is a Part 21 notification to the US Nuclear Regulatory Commission of a potential component defect.
The ITT Conoflow models GT25CA1826 and GT25CD1826 current to pressure (l/P) transducers produce a calibrated 3.0 to 15.0 psi output pressure from a 4.0 to 20.0 mA DC (input) signal.
On May 5, 2017 a non-safety related GT25CA1826 was received for evaluation. This transducer would not respond to the 4 to 20 mA operating signal. The failure was caused by a defective solder joint at a coil lead terminal on the printed circuit board. The circuit board was replaced and the unit worked correctly.
An immediate inspection of all stock revealed additional parts with defective solder joints. Based on our [Enidine] investigation, circuit boards with defective solder joints are limited to two lots, received on April 29, 2016 and May 27, 2016. Preventive measures have been implemented to prevent recurrence.
We [Enidine] have produced and shipped the following safety related products that have used parts from these two lots of circuit boards:
Enertech Purchase Order No.: 638764
Utility/Station P.O. No.: 15018770
Qty: 2
Part Number: GT25CD1826
Serial Numbers: 628974 and 628975
Customer/Station: Enertech\Gefran [Benelux NV]
Enertech Purchase Order No.: 638942-1
Utility/Station P.O. No. 500603219
Qty: 1
Part Number: GT25CA1826
Serial Numbers: 629276
Customer/Station: Enertech\Arizona Power [Palo Verde]
Enertech Purchase Order No.: 639238
Utility/Station P.O. No.: 343472
Qty: 2
Part Number: GT25CD1826
Serial Numbers: 629454 and 629455
Customer/Station: Enertech\CCI [Control Components Inc.]
Facilities which have procured suspect product will be notified and advised how to examine their stock for the potential defect. ITT will provide verified replacements for any defective or suspect circuit boards.
Enidine
105 Commerce Way
Westminster, SC 29691
Phone: (864)-647-9521
Fax: (864}-647-9574
Jeff Gotthelf
Engineering Manager