ENS 50108
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
14:20 May 12, 2014 | |
| Title | Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment |
| Event Description | During a review from industry operating experience it was identified that there are three additional unprotected DC control circuits for non safety related DC motors which are routed from the turbine building to other separate fire areas (this is in addition to the one circuit that was previously identified and submitted under event #50059). Fuses used to protect the motor power conductors appear to be inadequate to protect the control conductors. The concern is that under fire safe shutdown conditions, it is postulated that a fire in one area can cause short circuits potentially resulting in secondary fires or cable fires in other areas where the cables are routed. The secondary fires or cable failures are outside the assumptions of the 10 CFR 50 Appendix R Safe Shutdown Analysis.
This condition is reportable as an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> ENS report in accordance with 10 CFR 50.72(b)(3)(ii)(B) as an unanalyzed condition. Compensatory measures (fire watches) have been implemented for affected areas of the plant. The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Crane Pennsylvania (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| LER: | 05000289/LER-2014-001 Regarding Unfused DC Motor Control Circuits |
| Time - Person (Reporting Time:+0.47 h0.0196 days <br />0.0028 weeks <br />6.43806e-4 months <br />) | |
| Opened: | David Lewis 14:48 May 12, 2014 |
| NRC Officer: | Pete Snyder |
| Last Updated: | May 12, 2014 |
| 50108 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 531062017-12-06T14:58:0006 December 2017 14:58:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Diesel Fuel Oil Tank Supply Non-Conforming with Licensing Basis for Tornado Generated Missiles ENS 501082014-05-12T14:20:00012 May 2014 14:20:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 500592014-04-25T15:13:00025 April 2014 15:13:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 472942011-09-26T19:00:00026 September 2011 19:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition New River Hydraulic Analysis Raises Maximum Flood Level ENS 431392007-02-02T18:50:0002 February 2007 18:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Low Pressure Injection (Lpi) Net Positive Suction Head Flow Requirements Not Met for Certain Accident Sequences ENS 425272006-04-25T17:30:00025 April 2006 17:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Control Logic Error ENS 416632005-05-03T17:10:0003 May 2005 17:10:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Appendix R Fire Scenario Involving Multiple High Impedance Faults ENS 414442005-02-16T01:55:00016 February 2005 01:55:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Possible Failure to Meet Design Basis Requirements of Positive Pressure in the Control Tower Envelope Following a Design Basis Accident. 2017-12-06T14:58:00 | |