ENS Event | |
|---|---|
15:52 Dec 19, 2013 | |
| Title | Two of Three Emergencey Diesel Generators Inoperable at the Same Time |
| Event Description | On 12/19/13 Unit 1 Emergency Diesel Generator (EDG) 1-2 was inoperable for scheduled maintenance.
During an operational walk-down of the Unit 1 EDG 1-3, the associated fuel oil priming pump discharge fitting and pump housing were inadvertently damaged. Pacific Gas and Electric Company declared EDG 1-3 inoperable on 12/19/13 at 0752 PST. Since both Unit 1 EDGs were inoperable at the same time, this condition is reportable in accordance with 10 CFR 50.72(b)(3)(ii)(B) and 10 CFR 50.72(b)(3)(v)(D). The NRC Senior Resident Inspector has been notified. |
| Where | |
|---|---|
| Diablo Canyon California (NRC Region 4) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| LER: | 05000275/LER-2013-010 Regarding Two Emergency Diesel Generators Inoperable Due to Operator Error |
| Time - Person (Reporting Time:+0.48 h0.02 days <br />0.00286 weeks <br />6.57504e-4 months <br />) | |
| Opened: | Russell Cruzen 16:21 Dec 19, 2013 |
| NRC Officer: | Donald Norwood |
| Last Updated: | Dec 19, 2013 |
| 49663 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Diablo Canyon | |
WEEKMONTHYEARENS 544172019-11-30T19:00:00030 November 2019 19:00:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Both Trains of Containment Spray Removed from Service ENS 522602016-09-21T03:47:00021 September 2016 03:47:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Steam Line Pipe Whip Restraint Coupling Sleeve Found Not Engaged ENS 507112014-12-31T18:05:00031 December 2014 18:05:00 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Through Wall Seepage Affecting Rhr System ENS 503342014-08-01T00:29:0001 August 2014 00:29:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Unanalyzed Condition ENS 498792014-03-06T17:06:0006 March 2014 17:06:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Regarding Potential Tornado Missile Damage to Emergency Diesel Exhaust Plenum ENS 496632013-12-19T15:52:00019 December 2013 15:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Two of Three Emergencey Diesel Generators Inoperable at the Same Time ENS 496342013-12-14T23:03:00014 December 2013 23:03:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Affecting Unit 1 Emergency Diesel Generator ENS 491482013-06-26T04:58:00026 June 2013 04:58:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Plant Shutdown Required Due to Rhr System Socket Weld Leak ENS 491472013-06-24T23:15:00024 June 2013 23:15:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Emergency Diesel Generators Unavailable for Auto-Start ENS 487262013-02-06T23:24:0006 February 2013 23:24:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Control Room Ventilation ENS 485412012-11-28T04:38:00028 November 2012 04:38:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Ventilation System Will Not Automatically Start in Pressurization Mode ENS 483952012-10-04T01:15:0004 October 2012 01:15:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Fire Protection Deficiencies ENS 482462012-08-29T00:00:00029 August 2012 00:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Mitigating Actions Implemented for Inoperable Control Room Envelope ENS 480022012-06-07T08:29:0007 June 2012 08:29:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Both Trains of Low Temperature Overpressure System Inoperable ENS 475642011-12-31T10:00:00031 December 2011 10:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Fire Barrier Rating of Vital Swtichgear Walls May Not Meet Standards ENS 474142011-11-03T22:50:0003 November 2011 22:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Control Room Ventilation Single Point Vulnerability ENS 472582011-09-13T00:45:00013 September 2011 00:45:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Control Room Envelope Declared Inoperable ENS 472232011-08-30T00:24:00030 August 2011 00:24:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Maintenance Inadvertently Renders Control Room Ventilation System Inoperable ENS 465312011-01-10T21:21:00010 January 2011 21:21:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Both Trains of Auxiliary Building Ventilation Became Inoperable ENS 457542010-03-10T03:16:00010 March 2010 03:16:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Loss of 1E Pumps Due to Degraded Voltage During Postulated Accidents ENS 454612009-10-23T15:00:00023 October 2009 15:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Post Loca Recirculation Valve Position Interlocks ENS 449272009-03-22T20:34:00022 March 2009 20:34:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unit 1 Steam Generator Found in an Unanalyzed Condition Related to Gaps on Seismic Washer Plates ENS 442872008-06-11T21:05:00011 June 2008 21:05:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Identification of a Potential Issue with Accumulator Drain Valves 2019-11-30T19:00:00 | |