ENS 48452
ENS Event | |
|---|---|
22:55 Oct 29, 2012 | |
| Title | Notice of Unusual Event Declared Due to High Intake Structure Water Level |
| Event Description | At 1855 EDT on 10/29/2012, the licensee declared a Notice of Unusual Event (NOUE) per criteria HU4 for high water level in the station intake structure of greater than 4.5 feet. At the time of the notification, water level in the intake structure was approximate 4.8 feet and slowly rising. The cause of the increased water level was due to storm surge associated with Hurricane Sandy. No other station impacts were reported at the time. The licensee continues to monitor the intake levels and ocean tides.
The licensee has notified the NRC Resident Inspector and the State of New Jersey.
At 2044 EDT on 10/29/2012, the licensee escalated its emergency declaration to an Alert per criteria HA4 for high water level in the station intake structure of greater than 6.0 feet. At the time of the notification, water level in the intake structure was approximately 6.6 feet. The site also experienced a loss of offsite power event concurrent with the additional water level increase. Both emergency diesel generators started and are supplying power to the emergency electrical busses. Shutdown cooling and spent fuel pool cooling have been restored. Reactor pressure vessel level is steady at 584.7 inches. Intake levels continues to rise slowly and the licensee is monitoring. The licensee has notified the NRC Resident Inspector and the State of New Jersey. Notified DHS SWO, FEMA Ops Center, USDA Ops Center, HHS Ops Center, DOE Ops Center, DHS NICC Watch Officer, EPA EOC, and NuclearSSA via e-mail.
The licensee updated this report with an 8-hour non-emergency notification of emergency diesel generator auto-actuation due to the actual loss of off-site power event [which occurred at 2018 EDT on 10/29/2012]. This event caused a valid RPS actuation with automatic containment isolations that resulted in a temporary loss of shut-down cooling to the reactor. Shutdown cooling was subsequently restored with power provided by the emergency diesel generators. The licensee has notified the NRC Resident Inspector. Notified R1DO (Caruso).
Termination of Alert. The Oyster Creek Station has terminated the Alert that was declared at 2044 [EDT] on 10/29/12 due to Intake Structure high water level greater than 6.0 ft. MSL (EAL HA4). Intake water level has returned to normal and is now below the Unusual Event EAL threshold (4.5 ft. MSL) and continues to lower. The licensee informed state and local agencies and the NRC Resident Inspector. Notified Region I IRC (Clifford), NRR (Evans), and IRD (Marshall). Notified DHS SWO, FEMA Ops Center, USDA Ops Center, HHS Ops Center, DOE Ops Center, DHS NICC Watch Officer, EPA EOC, and NuclearSSA via e-mail. |
| Where | |
|---|---|
| Oyster Creek New Jersey (NRC Region 1) | |
| Reporting | |
| Emergency class: | Alert |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(3)(iv)(A), System Actuation 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat | |
| Time - Person (Reporting Time:+-3.62 h-0.151 days <br />-0.0215 weeks <br />-0.00496 months <br />) | |
| Opened: | Steve Serpe 19:18 Oct 29, 2012 |
| NRC Officer: | Ryan Alexander |
| Last Updated: | Oct 31, 2012 |
| 48452 - NRC Website
Loading map... | |
Oyster Creek with 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
WEEKMONTHYEARENS 531532018-01-06T10:24:0006 January 2018 10:24:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Declaration of Unusual Event Due to Abnormal Intake Structure Level ENS 528392017-07-03T14:15:0003 July 2017 14:15:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Scram on Low Condenser Vacuum ENS 501452014-05-28T14:37:00028 May 2014 14:37:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Release of Chlorinated Water ENS 496482013-12-18T00:57:00018 December 2013 00:57:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Protection System (Rps) Actuation with the Reactor in Hot Shutdown ENS 484522012-10-29T22:55:00029 October 2012 22:55:00 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Notice of Unusual Event Declared Due to High Intake Structure Water Level ENS 481252012-07-23T07:29:00023 July 2012 07:29:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Loss of Offsite Power ENS 471882011-08-23T18:05:00023 August 2011 18:05:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of an Unusual Event Due to a Seismic Event ENS 464432010-12-01T19:55:0001 December 2010 19:55:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Excessive Rcs Leakage from "B" Recirc Pump Seal ENS 463152010-10-07T14:41:0007 October 2010 14:41:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Loss of 4160 Volt Safety Bus ENS 451962009-07-12T05:48:00012 July 2009 05:48:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power ENS 448222009-02-02T02:56:0002 February 2009 02:56:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event and Reactor Scram Due to Main Transformer Fire ENS 446882008-11-29T02:01:00029 November 2008 02:01:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram Due to Main Transformer Fault ENS 434952007-07-17T09:22:00017 July 2007 09:22:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram on Low Reactor Vessel Water Level (Rvwl) ENS 425582006-05-06T10:07:0006 May 2006 10:07:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unplanned Manual Reactor Scram During Shutdown ENS 419452005-08-25T03:37:00025 August 2005 03:37:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Emergency Diesel Generator Automatic Start Due to Bus Supply Breaker Trip ENS 418992005-08-06T08:03:0006 August 2005 08:03:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared Due to Low Intake Water Level ENS 404562004-01-17T04:16:00017 January 2004 04:16:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Noue Declared at Oyster Creek Due to Intake Low Water Level 2018-01-06T10:24:00 | |