ENS 46315
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
14:41 Oct 7, 2010 | |
| Title | Loss of 4160 Volt Safety Bus |
| Event Description | Oyster Creek experienced a loss of 4160 volt 'D' safety bus. Emergency diesel generator number 2 fast started and re-powered the 'D' bus, as expected. All other safety systems responded as expected. Investigation into the loss of 'D' 4160 volt safety bus is in progress.
The licensee was performing grid undervoltage testing on the 'D' 4160 at the time of the event. The licensee has staffed the Outage Control Center. There is no affect on the other 4160 volt bus. Offsite power is normal. Plant risk was 'yellow' prior to and following the event as a result of Reactor Building Closed Cooling Water Pump 1-2 out of service for planned maintenance. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Oyster Creek New Jersey (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| Time - Person (Reporting Time:+-2.03 h-0.0846 days <br />-0.0121 weeks <br />-0.00278 months <br />) | |
| Opened: | Joshua Sistak 12:39 Oct 7, 2010 |
| NRC Officer: | Joe O'Hara |
| Last Updated: | Oct 7, 2010 |
| 46315 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_46315&oldid=425036"