ENS 41899
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
08:03 Aug 6, 2005 | |
| Title | Alert Declared Due to Low Intake Water Level |
| Event Description | The licensee declared an Alert (EAL HA3) at 0403 ET 08/06/05 due to low water level in the north half of the intake structure as a result of heavy grass accumulation due to a storm in the area. Intake level recovered to above the EAL value for an Alert, and the event was de-escalated to an Unusual Event (EAL HU3) at 0406 ET. One Circulating Water Pump associated with the north intake was immediately secured and reactor power was reduced to 43%. When the second Circulating Water Pump associated with the north intake was secured, intake water level returned to normal. As a result of the grassing, trash racks collapsed and traveling screen shear pins sheared at the north intake. The traveling screens were subsequently restored to service.
The licensee notified the NRC Resident Inspector.
|
| Where | |
|---|---|
| Oyster Creek New Jersey (NRC Region 1) | |
| Reporting | |
| Emergency class: | Alert |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
| Time - Person (Reporting Time:+-3.35 h-0.14 days <br />-0.0199 weeks <br />-0.00459 months <br />) | |
| Opened: | Mark Baratta 04:42 Aug 6, 2005 |
| NRC Officer: | Mike Ripley |
| Last Updated: | Aug 6, 2005 |
| 41899 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (43 %) |
Oyster Creek with 10 CFR 50.72(a)(1)(i), Emergency Class Declaration | |
WEEKMONTHYEARENS 531532018-01-06T10:24:0006 January 2018 10:24:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Declaration of Unusual Event Due to Abnormal Intake Structure Level ENS 501452014-05-28T14:37:00028 May 2014 14:37:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Release of Chlorinated Water ENS 484522012-10-29T22:55:00029 October 2012 22:55:00 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Notice of Unusual Event Declared Due to High Intake Structure Water Level ENS 481252012-07-23T07:29:00023 July 2012 07:29:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Loss of Offsite Power ENS 471882011-08-23T18:05:00023 August 2011 18:05:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of an Unusual Event Due to a Seismic Event ENS 464432010-12-01T19:55:0001 December 2010 19:55:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Excessive Rcs Leakage from "B" Recirc Pump Seal ENS 451962009-07-12T05:48:00012 July 2009 05:48:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power ENS 448222009-02-02T02:56:0002 February 2009 02:56:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event and Reactor Scram Due to Main Transformer Fire ENS 418992005-08-06T08:03:0006 August 2005 08:03:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared Due to Low Intake Water Level ENS 404562004-01-17T04:16:00017 January 2004 04:16:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Noue Declared at Oyster Creek Due to Intake Low Water Level 2018-01-06T10:24:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_41899&oldid=427793"