| Event Description | At 2209 EST on 12/28/11 following a planned station service water (SSW) pump swap, a motor operated valve (MOV) failed to close in a water treatment system for the SSW pump that was secured. This was discovered shortly after the pump was removed from service by the field operators. The control room was notified at 2230 EST of the issue and ongoing efforts to troubleshoot and correct the malfunction. The release was terminated by closing a manual isolation valve at 2240 EST. This malfunction resulted in the discharge of approximately 17 gallons of 15% sodium hypochlorite (product) to the idle SSW pump intake which communicates with the Delaware river, The idle SSW pump was restarted at 2240 EST thus withdrawing all residual product from the intake and directing it to plant treatment systems (dechlorination on the cooling tower outfall). A sample was obtained from the Delaware river just outside the intake structure and there was no detectable chlorine in the sample and there were no abnormal conditions noted on the river. Based on Environmental Licensing review, this is reportable to the state of NJDEP [New Jersey Department of Environmental Protection] within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. The report to the state was initiated at 0017 EST on 12/29/11.
The HC Senior NRC Resident has been informed. Affected systems are limited to the Station Service Water (SSW) system and the Sodium Hypochlorite water treatment system. There were no actuations or initiating signals. There was no impact on plant operations and these systems remain fully operable. The failure was limited to the MOV which has been isolated via a manual valve. There was nothing unusual or not understood. All safety related equipment continues to function as required. There were no injuries or reported wildlife impact. |
| Where | |
|---|---|
| Hope Creek New Jersey (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release | |
| Time - Person (Reporting Time:+-1.5 h-0.0625 days <br />-0.00893 weeks <br />-0.00205 months <br />) | |
| Opened: | Tom Fowler 02:00 Dec 29, 2011 |
| NRC Officer: | John Knoke |
| Last Updated: | Dec 29, 2011 |
| 47556 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 510022015-04-22T03:30:00022 April 2015 03:30:00
[Table view]10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Worker Fatality Not Related to Plant Operation ENS 508642015-03-04T19:08:0004 March 2015 19:08:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Elevated Tritium Detected Onsite ENS 491622013-07-01T12:46:0001 July 2013 12:46:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Fuel Oil Spill Into a Storm Drain Leading to the Delaware River ENS 475562011-12-29T03:30:00029 December 2011 03:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to State of New Jersey Due to a Discharge Into the Delaware River ENS 473232011-10-05T19:53:0005 October 2011 19:53:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Potential Chemical Spill in the Delaware River ENS 469262011-06-05T16:02:0005 June 2011 16:02:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification of a Sewage Spill Into a Storm Drain ENS 457612010-03-11T22:45:00011 March 2010 22:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Press Release Concerning a Former Plant Employee ENS 455602009-12-10T18:00:00010 December 2009 18:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Onsite Fatality ENS 448942009-03-06T19:40:0006 March 2009 19:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Gasoline Spill ENS 448502009-02-12T20:00:00012 February 2009 20:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Us Coast Guard and New Jersey Environmental Hotline Notified Due to Capsized Boat ENS 441632008-04-24T03:58:00024 April 2008 03:58:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Hydrazine Leak Into Storm Drain ENS 439222008-01-21T14:52:00021 January 2008 14:52:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release On-Site Fatality ENS 433682007-05-17T17:40:00017 May 2007 17:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Failed Emissions Test ENS 427642006-08-11T13:55:00011 August 2006 13:55:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Inadvertent Oca Siren Activaton 2015-04-22T03:30:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_47556&oldid=424154"