| Event Description | At 0930 on 10/5/11, a fuse failure in a 1E to non - 1E interface failed causing a false run signal to the water treatment system for a standby station service water pump. The water treatment system responded by opening the injection valve for the out of service pump. With the associated pump out of service, the sodium hypochlorite can communicate with the Delaware river. This was discovered at 1553 and immediately terminated. This resulted in the discharge of approximately 195 gallons of 15% sodium hypochlorite to SSW intake which communicates with the Delaware river. The associated service water pump was started thus withdrawing residual product from the intake. A portion of the discharged sodium hypochlorite may have entered the Delaware river. A sample was obtained from the Delaware river just outside the intake structure and there was no detectable chlorine in the sample and there were no abnormal conditions noted on the river. Based on Environmental Licensing review, this was reportable to the state of NJ within 15 minutes. The report to the state was initiated at 1608 on 10/5/11.
Subsequent calls were made to the Hope Creek Senior NRC Resident, the National Response Center and the US Coast Guard. Affected systems are limited to the Station Service Water (SSW) system and the sodium hypochlorite water treatment system. There was no impact on plant operations and these systems remain fully operable. Evaluation is underway to fully understand the impacts of the fuse failure to prevent reoccurrence. There was nothing unusual or not understood. All safety related equipment continues to function as required. There were no injuries or reported wildlife impact. |
| Where | |
|---|---|
| Hope Creek New Jersey (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release | |
| Time - Person (Reporting Time:+-0.6 h-0.025 days <br />-0.00357 weeks <br />-8.2188e-4 months <br />) | |
| Opened: | David Hall 19:17 Oct 5, 2011 |
| NRC Officer: | Joe O'Hara |
| Last Updated: | Oct 5, 2011 |
| 47323 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 510022015-04-22T03:30:00022 April 2015 03:30:00
[Table view]10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Worker Fatality Not Related to Plant Operation ENS 508642015-03-04T19:08:0004 March 2015 19:08:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Elevated Tritium Detected Onsite ENS 491622013-07-01T12:46:0001 July 2013 12:46:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Fuel Oil Spill Into a Storm Drain Leading to the Delaware River ENS 475562011-12-29T03:30:00029 December 2011 03:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to State of New Jersey Due to a Discharge Into the Delaware River ENS 473232011-10-05T19:53:0005 October 2011 19:53:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Potential Chemical Spill in the Delaware River ENS 469262011-06-05T16:02:0005 June 2011 16:02:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification of a Sewage Spill Into a Storm Drain ENS 457612010-03-11T22:45:00011 March 2010 22:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Press Release Concerning a Former Plant Employee ENS 455602009-12-10T18:00:00010 December 2009 18:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Onsite Fatality ENS 448942009-03-06T19:40:0006 March 2009 19:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Gasoline Spill ENS 448502009-02-12T20:00:00012 February 2009 20:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Us Coast Guard and New Jersey Environmental Hotline Notified Due to Capsized Boat ENS 441632008-04-24T03:58:00024 April 2008 03:58:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Hydrazine Leak Into Storm Drain ENS 439222008-01-21T14:52:00021 January 2008 14:52:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release On-Site Fatality ENS 433682007-05-17T17:40:00017 May 2007 17:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Failed Emissions Test ENS 427642006-08-11T13:55:00011 August 2006 13:55:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Inadvertent Oca Siren Activaton 2015-04-22T03:30:00 | |